1 Introduction to Sprinklers EFSN Training i Module 1 90 Minutes

2 Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler system design

3 How Sprinklers Work

4 How do Sprinklers Work? Glass bulb contains a liquid id with a vapour bubble bbl Liquid expands as the temperature rises, compressing the vapour bubble At a set temperature (usually 68 C) the bubble has p ( y ) gone and the bulb breaks, releasing the water seal

5 What happens then? In most sprinkler systems the pipe array to which the sprinkler is connected contains water under pressure, so water comes out of the sprinkler Pipe array water pressure drops and a switch sends a signal to start the pump if there is one Water flowing in the pipe array operates another switch which causes the fire alarm to ring Signals such as these can be used to send an automatic alarm to a monitoring station

6 Some More Details Hot gases rise from a fire and spread across the ceiling to meet the sprinkler bulb or fusible link It is important that the hot gases can freely reach the sprinkler and design rules make clear what obstructions are unacceptable Usually 1-2 sprinklers operate but if the fire is equally between 4 sprinklers they all may operate For most fire risks, the sprinkler system is designed for six sprinklers to operate four plus two reserve

7 Sprinklers do not: React to smoke from toast or a cigarette Open all at once (usually 1 or 2 sprinklers operate) Cause major water damage (system sprays less water than a single fire hose) Operate without reason (this is very rare) 1 in 1.6 million sprinklers for all reasons including end user or contractor damage (FM Global in 1977) 1 in 16 million sprinklers due to a manufacturing error (FM Global in 1977)

8 Performance of Sprinkler Systems

9 Reliability i i of fs Sprinklers Sprinklers release water when they get hot and control or extinguish fire Statistics show properly designed and maintained sprinkler systems control/extinguish ti i 98% of fires Swiss Cantonal Insurance Federation 100% in 2000 LPC 99% in 2000 Danish Institute of Fire Technology 98% in 2003 German Property Insurers 97.9% in APSAD of France 97% in 2000

10 Reliability i i of fs Sprinklers In >60% of cases only 1 or 2 sprinklers operate to release much hless water than a single fire hose Swiss Cantonal Insurance Federation: 87% of fires controlled by 1-2 sprinklers in 2000 APSAD: 61% of fires controlled by 1-2 sprinklers in 2000 VdS: 50% of fires controlled by 1-2 sprinklers in 2000 LPC: 44% of fires controlled by 1-2 sprinklers in 2000 E h h d l i l l f lif i Europe has never had a multiple loss of life in a building protected by a fire sprinkler system

11 Benefits of Sprinklers in Room of Origin Sprinklers sensitive to heat and respond quickly before conditions become life-threatening Prevent fire growth and so reduce evolution of toxic gases Keep temperature at survivable level Often extinguish fire 2004 report for UK Government showed sprinklers usually maintain tenable conditions in room of fire origin => Sprinklers offer the only hope to those who do not leave the room where the fire starts

12 Sprinklers Aid Escape Prevent growth of fire and evolution of smoke People can then more easily follow escape routes Sprinkler system can send an alarm to fire brigade

13 Sprinklers Prevent Flashover In a fire flammable vapours reach auto-ignition Ingress of oxygen => spontaneous combustion with fireball and shockwave Sprinklers cool vapours so they do not ignite when oxygen enters room Important contribution to safety of occupants and Important contribution to safety of occupants and fire-fighters specific aim of NFPA 13R and 13D

14 Sprinklers Reduce Fire Damage Respond before arrival of fire brigade Fire is still small and is not allowed to grow Less water is needed to deal with a small fire Average fire damage is reduced by over 85% Scottsdale (88% commercial buildings; 96% residential) Vancouver (92% residential) NFPA (42% residential; 67% manufacturing) NIST (32% in houses)

15 Warehouse Fires Extinguished by Sprinklers Birmingham 2004 ICI Paints 15 Feb sprinklers put out fire

16 A Warehouse without Sprinklers Matalan, Birmingham i 2 March 2006

17 Proof fth that ts Sprinklers Save Lives Scottsdale Zero deaths in sprinklered buildings (first death in 2007) Vancouver Zero deaths in sprinklered buildings from 1990 Fire death rate was worst, now best in Canada NFPA: 86% reduction overall; 78% residential ( ); 100% in houses ( ) NIST: 100% fire death reduction in houses

18 Scottsdale Sprinkler Legislation 1974 All buildings higher than 3 storeys or larger than 700m 2 must be sprinklered 1982 Ran residential sprinkler tests 1985 Approved ordnance requiring sprinklers in all new buildings from 1986

19 Scottsdale Sprinkler Ordinance Design Freedoms Increased hydrant spacing Reduced water main sizes No requirement for 360 access Reduced street widths Increased cul-de-sac lengths => Development density increased 4%

20 Costs to Install Sprinklers in Houses in Scottsdale February m 2 house 8.50/m 2 June 1989 Production home 5.87/m 2 Custom home 6.62/m 2 January 2001 Production home 4.38/m 2 Custom home 5.20/m 2

21 45 Fire Deaths in Vancouver Sprinklers retrofitted in 800 high h risk buildings Sprinklers in all new housing, hospitals and care facilities % of all housing has 37% of all housing has sprinklers

22 Sprinklers Make Economic Sense Allow architectural freedoms so buildings are more attractive and cost less to build Prevent loss of life and reduce injuries by 85% Reduce fire damage to property by over 85% Low maintenance costs through life of building NIST found an economic benefit

23 Types of Sprinkler

24 Deflector Compression Screw Frame Glass Bulb Btt Button Belleville Spring Sprinkler Parts

25 Sprinkler Variables Type Operating Opeat Temperature peatue K Factor Response Index Finish

26 Types of Sprinkler Pendant and Upright

27 Types of Sprinkler Vertical Sidewall, Horizontal Sidewall

28 Types of Sprinkler Recessed, Concealed, Flush

29 Types of Sprinkler Dry Pendant and Dry Upright

30

31 Types of Sprinkler Extended Coverage Sprinklers

32 Types of Sprinkler ESFR Pendant and Upright

33 Types of Storage Sprinkler Control Mode or Suppression Mode Control mode sprinklers allow the fire to burn out over a limited area Suppression mode sprinklers reduce the size of the fire Suppression mode sprinklers must be sensitive ii (fast response element and close spacing) and release a lot of water

34 Types of Storage Sprinkler In-Rack Sprinklers In general, above 7.6m control mode sprinklers must be supplemented by in-rack sprinklers These are protected from damage and from water from sprinklers above them

35 Control Mode Sprinklers

36 Ceiling control mode sprinklers In-rack sprinklers

37 ESFR suppression mode sprinklers In most cases ESFR sprinklers eliminate i the need for in rack sprinklers

38 Operating Temperatures Orange 57º C 135 o F Red 68 o C 155 o F Yellow 79 o C 175 o F Green 93 o C 200 o F Blue 141 o C 286 o F Mauve 182 o C 360 o F

39 The larger the bulb the higher the Operating Temperature Maximum Operating Temperature is 343 C

40 K Factor K Factor (Imperial) K Factor (Metric) % of 5.6/80 25% 33% 50% 75% % % % % % % % Reference Flowrate in l/min = K* Pressure (in bar) e.g. K80, 1 bar: flowrate = 80* 1 = 80 l/min

41 Response Time Index Plunge test in a heated wind tunnel

42 Response Time Index Standard Response RTI <200 Special ilresponse RTI <80 Quick Response RTI <50 Residential i Fire test

43 Introduction to Sprinkler Systems

44 Sprinkler System Pipe array Alarm valve station Water supply

45 Introduction ti to Sprinkler Systems

46 Introduction ti to Sprinkler Systems Riser

47 Introduction ti to Sprinkler Systems Main distribution pipe Riser

48 Introduction ti to Sprinkler Systems Distribution pipe Main distribution pipe Riser

49 Introduction ti to Sprinkler Systems Range pipes Distribution pipe Main distribution pipe Riser

50 Introduction ti to Sprinkler Systems Range pipes Distribution pipe Main distribution pipe Arm pipe Riser

51 Introduction ti to Sprinkler Systems Range pipes Upright Sprinkler Arm pipe Distribution pipe Riser Main distribution pipe

52 Introduction ti to Sprinkler Systems Range pipes Upright Sprinkler Distribution pipe Main distribution pipe Arm pipe Riser Pendant Sprinkler

53 Introduction ti to Sprinkler Systems Range pipes Upright Sprinkler Distribution pipe Main distribution pipe Arm pipe Pendant Sprinkler Riser Water motor alarm

54 Introduction ti to Sprinkler Systems Range pipes Inspector test valve Upright Sprinkler Distribution pipe Main distribution pipe Arm pipe Pendant Sprinkler Riser Water motor alarm

55 Wet Pipe Sprinkler Systems Most common type of sprinkler system All pipes filled with water under pressure When a sprinkler opens the alarm valve releases water to the gong Pressure gauges Pressure switch Retard chamber Drain valve

56 Dry Pipe Sprinkler Systems Pipe array filled with compressed air Used where there is a risk of water freezing When a sprinkler opens the air pressure falls and the valve opens to release water into the pipe pp array Valve held closed by differential clapper area

57 Deluge Sprinkler Systems Open sprinklers or nozzles Used in high hazard areas where all sprinklers must operate together Fire detection system sends signal to solenoid valve in deluge trim Pneumatic or hydraulic Pneumatic or hydraulic release also possible

58 Deluge Sprinkler Systems Open sprinklers or nozzles

59 Pre-Action Sprinkler Systems Pipe array filled with compressed air or N 2 Deluge valve opened by detection system No water flows until sprinkler also operates Used dif there is concern about false activation Configurable to require sprinkler and detection to operate to open valve

60 Pre-Action Sprinkler System

61 Pre-Action Sprinkler System

62 Pre-Action Sprinkler System

63 Pre-Action Sprinkler System

64 Pre-Action Sprinkler System

65 Introduction to Sprinkler System Design

66 Sprinkler System Design Based on the fire load, the type of occupancy and the type of system Design standards specify the: Design density in mm/min (like rainfall) Area of operation to be supplied with this density Duration of water supply Area coverage per sprinkler Sprinkler type, temperature and thermal sensitivity Hydraulic calculation methods

67 Sprinkler System Design Standards EN European standard written by representatives of national standards bodies within CEN (about 30 countries) CEA 4001 European insurance standard NFPA 13 US standard, widely used where other standards are silent Many similarities but some differences

68 Hazard Classes EN Nine classes Light Hazard Ordinary Hazard 1 Ordinary Hazard 2 Ordinary Hazard 3 Ordinary Hazard 4 High Hazard Production 1 High Hazard Production 2 High Hazard Production 3 High Hazard Production 4 Example - Annex A Prison Hospital Car park Woodworking factory Tobacco factory Paint manufacture Fire lighter manufacture Cellulose nitrate manufacture Firework manufacture High Hazard Storage

69 Design Criteria EN Table 3 Hazard Class Design Density mm/min Wet or pre-action Area of Operation m 2 Dry LH OH1 OH OH OH OH HHP1 HHP HHP HHP HHP4 Deluge not covered by EN 12845

70 Duration of fw Water Supply EN Light Hazard 30 minutes Odi Ordinary Hazard 60 minutes High Hazard Production 90 minutes High Hazard Storage 90 minutes

71 Max. Sprinkler Coverage/Spacing EN Table 19 Hazard Class Maximum area per sprinkler Maximum distances as shown in Figure 8 m Standard Staggered layout layout m 2 S and D S D LH OH HHP and HHS For sidewall sprinklers use Table NFPA13 includes extended coverage sprinklers

72 Example Shopping Centre 3,000m 2 OH 3 from Annex A 5mm/min on 216m 2 = 1,080 l/min Water supply 60 min = 65m 3 12m 2 per sprinkler = 250 sprinklers 60 l/min per sprinkler = K80 at 0.6 bar Numbers slightly higher after design

73 Thank you!

Sprinkler Systems in Hospitals. Lisbon 6 November 2008

Sprinkler Systems in Hospitals. Lisbon 6 November 2008 Sprinkler Systems in Hospitals Lisbon 6 November 2008 Some Statistics from NFPA USA 1994-1998 1998 2,600 fires/year in healthcare facilities Causes of fire: Other equipment 20% Cooking equipment 18% Appliances/tools/air-conditioning

More information

Extended Coverage Sprinklers

Extended Coverage Sprinklers Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible

More information

WHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS

WHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS WHAT YOU NEED TO KNOW ABOUT INSURING A HOME WITH FIRE SPRINKLERS A GUIDE FOR PROPERTY & CASUALTY INSURANCE PROFESSIONALS HomeFireSprinkler.org FIRE THE LARGEST SINGLE CAUSE OF PROPERTY LOSS Fire is the

More information

Fighting Fire in Sprinklered Buildings. Student Guide

Fighting Fire in Sprinklered Buildings. Student Guide Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction

More information

H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S

H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S HomeFireSprinkler.org F I R E T H E L A R G E ST S I N G L E C AU S E O F

More information

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

F.Y.I. Specifying Fire Protection Systems Using Division 13

F.Y.I. Specifying Fire Protection Systems Using Division 13 F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes

More information

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 DAEGU: 20 th August 2010 Karim KARZAZI 1 Development of sprinkler rules & standards in Europe. Overview of past, existing and future situation

More information

Fire detection, alarm, and suppression systems are installed to:

Fire detection, alarm, and suppression systems are installed to: Fire detection, alarm, and suppression systems are installed to: Notify occupants to escape a fire Summon emergency responders Initiate suppression systems Supervise suppression systems for operational

More information

Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE

Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE September 1, 2005 Fire Suppression Operations in Residential Occupancies equipped with Residential Fire Sprinkler Systems. Since human beings

More information

KODAK VERSAMARK, INC.

KODAK VERSAMARK, INC. KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF

More information

IDENTIFICATION BROCHURE FOR Central RESIDENTIAL WET SPRINKLERS

IDENTIFICATION BROCHURE FOR Central RESIDENTIAL WET SPRINKLERS IDENTIFICATION BROCHURE FOR Central RESIDENTIAL WET SPRINKLERS 1 INTRODUCTION TO THE VOLUNTARY REPLACEMENT PROGRAM This brochure provides information that will assist you in identifying whether the sprinklers

More information

MARKETING HOMES PROTECTED BY FIRE SPRINKLER SYSTEMS

MARKETING HOMES PROTECTED BY FIRE SPRINKLER SYSTEMS MARKETING HOMES PROTECTED BY FIRE SPRINKLER SYSTEMS A GUIDE FOR REAL ESTATE PROFESSIONALS HomeFireSprinkler.org HOME FIRE SPRINKLER SYSTEMS A GROWING TREND THAT S HERE TO STAY If you re marketing a home

More information

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications International Water Mist Conference, London, United Kingdom,23-24 September, 2009 High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications Fire Fighting In Civil Applications

More information

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following

More information

We look forward to working with you. Worldwide Headquarters 1400 Pennbrook Parkway Lansdale, PA 19446. www.tyco-rapidresponse.com

We look forward to working with you. Worldwide Headquarters 1400 Pennbrook Parkway Lansdale, PA 19446. www.tyco-rapidresponse.com TYCO IS HERE TO HELP Tyco will work closely with you to make the installation of Rapid Response Residential Fire Sprinkler Systems a quick and easy addition to your new home construction. We can develop

More information

Model F156 Sprinkler Types. Model F156 Recessed Sprinkler Types. Model F142, F1XLH & F128 Sprinkler Types

Model F156 Sprinkler Types. Model F156 Recessed Sprinkler Types. Model F142, F1XLH & F128 Sprinkler Types Bulletin 013 Rev. M Models F1 Series Standard Response s Bulletin 013 Rev. M Model F156 Types Standard Upright Standard Pendent Conventional Vertical Sidewall Model F156 Recessed Types Pendent/F1/F2/FP

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

Sprinkler and Fire Alarm Systems for the Building Official

Sprinkler and Fire Alarm Systems for the Building Official Sprinkler and for the Building Official Randall Kovacs, P.Eng., CP, FEC Gage-Babcock & Associates, Ltd. Topics Coordinated System Testing 1 Wet Dry Pre-action Deluge Wet System: Pipes filled with water

More information

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com Worldwide Contacts www.tyco-fire.com Model EC-HS 80 K-factor, Quick Response Extended Coverage Horizontal Sidewall Sprinklers Installations per VdS CEA 400, Annex E, LH/OH General Description The Model

More information

Use Of Residential Fire Sprinklers In New Housing Projects

Use Of Residential Fire Sprinklers In New Housing Projects STAFF REPORT ACTION REQUIRED Use Of Residential Fire Sprinklers In New Housing Projects Date: May 22, 2007 To: From: Wards: Reference Number: Community Development and Recreation Toronto Fire Services

More information

Risk Engineering Guideline

Risk Engineering Guideline www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.

More information

Model F1FR Series Quick Response Glass Bulb Sprinklers

Model F1FR Series Quick Response Glass Bulb Sprinklers Model F1FR56 Sprinkler Types Standard Spray Standard Spray Conventional / Vertical Sidewall Model F1FR56 Recessed Sprinkler Types Standard Spray Model F1FR56 Concealed Sprinkler Types Standard Spray Model

More information

AON SPRINKLER CERTIFICATION

AON SPRINKLER CERTIFICATION Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or

More information

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13? NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued

More information

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2)

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Formally part of NFPA 231 12.2.1 General 12.2.2 Protection of Class I - IV Commodities 12.2.3 Protection of Plastic & Rubber Commodities

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND

More information

Fire Safety Regulation, a comparative perspective, Ireland v Poland. Piotr Smardz

Fire Safety Regulation, a comparative perspective, Ireland v Poland. Piotr Smardz Fire Safety Regulation, a comparative perspective, Ireland v Poland Piotr Smardz Overview of the presentation Basic facts about Poland Fire statistics Fire and rescue service arrangement Building Law Regulation

More information

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting

More information

Home Fire Sprinkler Facts vs. Myths

Home Fire Sprinkler Facts vs. Myths Home Fire Sprinkler Facts vs. Myths MYTH: Home fire sprinklers can malfunction and cause severe water damage to my home. They re more of a liability than a help! FACT: It is extremely rare for home fire

More information

Sprinkler Identification Numbers

Sprinkler Identification Numbers Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 K-factor Horizontal Quick Response, Standard Coverage General Description described in this data sheet are quick response -standard coverage, decorative

More information

Quick response concealed horizontal sidewall sprinkler

Quick response concealed horizontal sidewall sprinkler January 1, 2011 Sprinkler 63a 1. DESCRIPTION Viking Quick Response Concealed Horizontal Sidewall Sprinkler VK408 is a small solder link and lever spray sprinkler designed for installation on concealed

More information

Mission-critical fire protection HI-FOG for data centres

Mission-critical fire protection HI-FOG for data centres Mission-critical fire protection HI-FOG for data centres Modern fire protection for a data-driven world We make a strong case that HI-FOG is the best available fire protection for mission-critical data

More information

FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE EXAMINATION FOR THE CERTIFICATE OF FITNESS FOR S-12 CITYWIDE SPRINKLER SYSTEM

FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE EXAMINATION FOR THE CERTIFICATE OF FITNESS FOR S-12 CITYWIDE SPRINKLER SYSTEM Rev: 3-27-13 FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE EXAMINATION FOR THE CERTIFICATE OF FITNESS FOR S-12 CITYWIDE SPRINKLER SYSTEM Issued 11/29/10 New York City Fire Department - All rights

More information

FIRE SPRINKLER DEMONSTRATION TRAILER

FIRE SPRINKLER DEMONSTRATION TRAILER IFIA FIRE SPRINKLER DEMONSTRATION TRAILER Recommendations for utilizing the fire sprinkler demonstration trailer in your fire department, business or association: INDEX: A) Picking up and towing the Trailer.

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description Worldwide Contacts www.tyco-fire.com Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description The TYCO Model WS Specific Application Window

More information

Upon completion of this unit of study, the student should be able to:

Upon completion of this unit of study, the student should be able to: UNIT OBJECTIVES Upon completion of this unit of study, the student should be able to: 1. Identify supervisory alarm equipment and demonstrate action to take upon receipt of an alarm according to local

More information

Maintaining Fire Protection Systems

Maintaining Fire Protection Systems Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars

More information

Roland Garcia Pearland Fire Department

Roland Garcia Pearland Fire Department Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and

More information

Second Revision No. 106-NFPA 72-2014 [ Global Comment ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 106-NFPA 72-2014 [ Global Comment ] Supplemental Information. Submitter Information Verification. Committee Statement of 1 9/22/2014 2:03 PM Second Revision No. 106-NFPA 72-2014 [ Global Comment ] Revise Figures A.17.6.3.1.1(c) and A.17.7.5.4.2.2(a) to replace the smoke detector symbol (a hexagon with a whisp of smoke)

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

Series MJC Multiple Jet Controls DN20, DN25, DN40, and DN50, 12 bar BSPT Inlet & Outlets Threads General Description.

Series MJC Multiple Jet Controls DN20, DN25, DN40, and DN50, 12 bar BSPT Inlet & Outlets Threads General Description. Worldwide Contacts www.tyco-fire.com Series Multiple Jet Controls DN20, DN25, DN40, and DN50, 2 bar BSPT Inlet & Outlets Threads General Description The TYCO Series Multiple Jet Controls are control valves

More information

Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1

Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1 Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1 Nuclear Power in Pakistan Nuclear Power Plants Capacity (MWe) Year of Commissioning In

More information

Improving fire safety through engineering (rational designs)

Improving fire safety through engineering (rational designs) Improving fire safety through engineering (rational designs) Johan van den Heever Fire Safety Indaba, Cape Town 2013 'Promoting responsible fire safety in Southern Africa' 1 Introduction What is fire safety

More information

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS 1.0 PURPOSE 1.1 To provide an overview of fire extinguisher use

More information

Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS

Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS Title 153 - NEBRASKA STATE FIRE MARSHAL Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS Scope. Chapter 19 of Title 153 of the Nebraska Administrative Code is concerned with the certification of contractors

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

PROTECT WHAT YOU VALUE MOST

PROTECT WHAT YOU VALUE MOST PROTECT WHAT YOU VALUE MOST HOME FIRE SPRINKLERS SAVE LIVES Fire kills more people in the United States annually than all natural disasters combined. In fact, more than 4,000 people perish in fires each

More information

Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems

Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Introduction Fire protection systems are provided in or at a building to safeguard the lives of building

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

Decree of the Ministry of the Environment. on fire safety of garages

Decree of the Ministry of the Environment. on fire safety of garages E4 THE NATIONAL BUILDING CODE OF FINLAND Fire safety of garages Guidelines 2005 Decree of the Ministry of the Environment on fire safety of garages Adopted in Helsinki, 22 March 2005 Pursuant to the Decision

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are

More information

Section 9 Major Urban Fire

Section 9 Major Urban Fire Section 9 Major Urban Fire Table of Contents WHY MAJOR URBAN FIRES ARE A THREAT...9-2 HAZARD PROFILE...9-3 HISTORY OF MAJOR URBAN FIRES...9-4 POTENTIAL DAMAGES AND LOSSES...9-5 MAJOR URBAN FIRE MITIGATION

More information

BUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE

BUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE BUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE AUTOMATIC FIRE SPRINKLER PROTECTION Residential fire sprinkler system installations are increasing every day thanks to growing buyer demand, lower costs,

More information

Sprinkler Guards Model C Model D

Sprinkler Guards Model C Model D Bulletin 208 Rev. M Sprinkler Guards Model C Model D Bulletin 208 Rev. M Model C Sprinkler Guards Model C Series sprinkler guards are designed to be assembled onto installed sprinklers. They are constructed

More information

FIRE SAFETY ONLINE TRAINING

FIRE SAFETY ONLINE TRAINING INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency

More information

Fire Detection, Protection, and Suppression Systems. Objectives (1 of 5) Objectives (2 of 5) Chapter 36

Fire Detection, Protection, and Suppression Systems. Objectives (1 of 5) Objectives (2 of 5) Chapter 36 Fire Detection, Protection, and Suppression Systems Chapter 36 Objectives (1 of 5) Explain why all firefighters should have a basic understanding of fire protection systems. Describe the basic components

More information

A Call for Fire Sprinklers in Chicago s Existing Residential High-Rises

A Call for Fire Sprinklers in Chicago s Existing Residential High-Rises FIREDYNE ENGINEERING, P.C. Fire Protection Engineering Code Consulting 18222 CORK ROAD, TINLEY PARK, IL 60477 PHONE: (708) 633-8140 From testimony presented to the Chicago Building Committee A Call for

More information

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern

More information

Wet alarm valves. Wet alarm valves. FM trim

Wet alarm valves. Wet alarm valves. FM trim Description Usually, a wet alarm valve station comprise: - a Rolland wet alarm valve linked to the water motor gong. - a set of valves and by pass used to test the system. - a drain valve. - a test valve

More information

Firefighter Review. Instructor Guide

Firefighter Review. Instructor Guide Firefighter Review Instructor Guide Session Reference: 3 Topic: Attack Line Handling Level of Instruction: Time Required: Three Hours Materials: Two Fully Equipped Pumpers Structure for Use in Advancing

More information

Diameter 3" 4" 6" 8" Flange type PN 16 PN 16 PN 16 PN 16. Orange-red ( RAL 2002) Height (cm) 27,70 26,30 28,70 29.70

Diameter 3 4 6 8 Flange type PN 16 PN 16 PN 16 PN 16. Orange-red ( RAL 2002) Height (cm) 27,70 26,30 28,70 29.70 Description Usually, a wet alarm valve station comprise: a Rolland wet alarm valve linked to the water motor gong. a set of valves and by pass used to test the system. a drain valve. a test valve gauges

More information

Fires in residences have taken a high toll of life and property. In 2002 there were:

Fires in residences have taken a high toll of life and property. In 2002 there were: Home Fire Safety RESIDENTIAL SPRINKLERS SPRINKLER SYSTEMS IN INDUSTRY Schools, office buildings, factories, and other commercial buildings have benefited from fire protection sprinkler systems for over

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

LAWS AND REGULATIONS for AUTOMATIC EXTINGUISHING SYSTEMS

LAWS AND REGULATIONS for AUTOMATIC EXTINGUISHING SYSTEMS DEPARTMENT OF FORESTRY AND FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING DIVISION LAWS AND REGULATIONS for AUTOMATIC EXTINGUISHING SYSTEMS AUTOMATIC EXTINGUISHING SYSTEM PROGRAM 1131

More information

How To Install A Fire Sprinkler

How To Install A Fire Sprinkler Fire Sprinklers: Coming to a Home Near You With a smoking record for saving lives and protecting houses, it s no surprise sprinklers were adopted into the International Residential Code BY CHRIS ERMIDES

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12 Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.

More information

FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE

FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE ACCEPTANCE INSPECTION AND TESTING PROCEDURE Wet Pipe Sprinkler Systems...2 Dry Pipe Sprinkler Systems...2 Clean Agent Fire Extinguishing System...4 Total Flooding Systems...4 Fire Dampers...5 Smoke Dampers...5

More information

Transformer Deluge Systems

Transformer Deluge Systems Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is

More information

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description The TYCO Type EA-1 PROTECTO- SPRAY Directional Spray Nozzles are automatic

More information

Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests. Project report number 204505. Dr Corinne Williams and R Harrison

Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests. Project report number 204505. Dr Corinne Williams and R Harrison Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests Project report number 2455 Dr Corinne Williams and R Harrison February 24 Section 4: Benchmark tests Contents 4 Benchmark

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

COMMON MYTHS ABOUT FIRE SPRINKLER PROTECTION

COMMON MYTHS ABOUT FIRE SPRINKLER PROTECTION "Water damage from a sprinkler system will be more extensive than fire damage." Water damage from a sprinkler system will be much less severe than the damage caused by water from firefighting hose-lines

More information

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity? A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered

More information

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use. Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections

More information

HOME FIRE PROTECTION SYSTEMS SPRINKLER SYSTEMS IN INDUSTRY

HOME FIRE PROTECTION SYSTEMS SPRINKLER SYSTEMS IN INDUSTRY HOME FIRE PROTECTION RESIDENTIAL FIRE SPRINKLER SYSTEMS SPRINKLER SYSTEMS IN INDUSTRY Sh Schools, office buildings, factories, and other commercial buildings have benefited from fire protection sprinkler

More information

CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance

CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance CIBSE Guide M: Maintenance engineering and management compliance legislation and guidance Types of System/Plant Action required Frequency by Type of Fire and Smoke Fire extinguishers Discharge (not CO

More information

Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description

Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and

More information

Fire Safety In High Rise Building

Fire Safety In High Rise Building Fire Safety In High Rise Building CLASSIFICATION OF BUILDINGS AS PER NATIONAL BUILDING CODE 1. GROUPING. Group A - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group B Group C - Educational

More information

Influence of fire source locations on the actuation of wet-type sprinklers in an office fire

Influence of fire source locations on the actuation of wet-type sprinklers in an office fire Influence of fire source locations on the actuation of wet-type sprinklers in an office fire Ko-Jen Chen 1 Chun-Ta Tzeng 2 Chi-ming Lai 3 Abstract An experiment is conducted on a full-scale model office

More information

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor,

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Appendix B Forms for Inspection, Testing, and Maintenance

Appendix B Forms for Inspection, Testing, and Maintenance Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete

More information