LOSS CONTROL ALERT. Water Damage Prevention Sprinkler Contractors
|
|
|
- Stephany Byrd
- 10 years ago
- Views:
Transcription
1 LOSS CONTROL ALERT Water Damage Prevention Sprinkler Contractors The Problem Claims for water damage arising from sprinkler system leakage are the largest source of general liability losses for Sprinkler Contractors. Almost eight out of ten claims (79%) and over seven dollars out of every ten (72%) in paid claims for sprinkler contractors come from sprinkler leakage. The cost per claim is high averaging about $20,000. Sprinkler leakage claims are of two primary types, claims which occur while the sprinkler contractor is on the premises and at work, and claims which occur later, after the work is complete. The largest claims occur after the work is finished and the building has been occupied. Common causes for these claims include: Leaving sprinkler heads exposed to physical damage, installing defective heads and improper installation. Failure of or leakage from couplings and fittings. Pipes or components bursting due to freezing, primarily because systems that were supposed to be dry pipe systems were left with water in them or from extending wet pipe systems into or through areas subject to freezing. Improper gluing of plastic pipe or failure to allow sufficient cure time before pressurizing the system leading to joint separation. Special Precautions for CPVC Sprinkler Piping More and more jobs are specifying CPVC piping rather than the traditional metal piping as a cost saving measure. Using CPVC piping in sprinkler jobs involves special hazards that can cause water damage and special precautions and work procedures are required to prevent water damage claims. See the special section on Preventing Water Damage Claims on CPVC Piping Jobs at the end of this document. Preventing Sprinkler Leakage Claims Contractual responsibilities, hold harmless agreements and insurance verification Work contracts should clearly identify the responsibilities of each party involved in the installation, including any sub-contracted operations. Contracts for sub-contractors should include hold harmless provisions and require evidence of general liability insurance with limits equal to the contractor. Refer to Everest Loss Control Alert, Risk Transfer Techniques at If any valuable or highly sensitive equipment exists, the contract should specify the owner s responsibility to move or protect these items before work begins. If a wet sprinkler system is to be installed in a normally unheated area, the contract should clearly state that it is the responsibility of the building owner to provide and maintain heat. Define the impaired sprinkler system notification requirements of the owner s business insurance policies and local jurisdictions, and designate who has the responsibility of the building owner to provide and maintain heat. When making the notifications., some jurisdictions require notification to the local fire department. Identify the need for a fire watch during the work or overnight if the sprinkler system cannot be returned to full operating condition the same day, designate who will provide the fire watch and what their duties will be. If there is a Central Station alarm system, determine who has the responsibility of making the alarm company notifications. Responsibility to communicate proposed changes or modifications to the specifications and approval of these changes prior to implementing them. Pre-Job Inspection before beginning any work on an existing building, the entire building should be inspected for existing and potential problems. Take photographs or make video recordings to document pre-existing conditions and problem areas. Address these problems in the work contract. Require the building owner to make repair s before the work commences or include these repairs in the scope of work specifications or list these as specific exclusions. Inspection Items: Evidence of past or current sprinkler system leakage; Evidence of improper work by other contractors; Examine building modifications such as the addition or removal of internal walls, build- out of un-sprinklered office, changes to the sprinkler piping (including heat tape for freeze protection), changes to or removal of insulation around finished areas, turning off heat in suspected freeze areas; Identify changes in the building occupancy, storage of high value materials, rack storage or hazardous materials requiring a higher water density and in-rack protection; Look for damage to the existing sprinkler system from powered industrial trucks, high lifts or construction work and maintenance activities; Locate sprinkler control valves for the work area and for adjacent areas.
2 Page 2 Preventing Claims During the Work Once work begins, the job supervisor is the contractor s first line of defense against claim incidents. It is the supervisor s responsibility to: Make initial notifications Assure that the initial required notifications that the sprinkler system is being taken out of service have been made. Turn off the water Turn off the water, and conduct tests to ensure that the correct valve has been turned off and that the valve is fully closed. In larger building with multiple sprinkler control valves, verify that the work area is not supplied by multiple valves. Once this has been done, the supervisor should insure that the valve is not turned on again (accidentally or intentionally) until the work is complete and tested. The valve should be tagged out of service and locked out (if locking the valve is acceptable to the local jurisdiction). Provide spill control supplies Despite your best efforts, an unexpected leak or discharge can occur. When this happens, it is important to minimize the effect of the leak. A spill kit should be immediately available in the event of a leak. This spill kit should include large plastic containers (preferably on wheels/dollies), temporary protection such as tarps, floor squeegees, mops, pails, shop vacuums that can be used in wet environments, extra rags, absorbent granules, etc. The spill kit should be immediately available whenever a wet system is charged with water. Supervise the work Regularly inspect the work and ensure that the plan and specifications are followed. Remember the old saying: Plan the work, work the plan. Dry pipe system drain For dry pipe systems, ensure that all water has been drained from the system at the end of the work, using the low point drains, and that the drains are then fully closed. Testing the work When the work is complete, and if plastic pipe has been installed, following the manufacture s glue cure time, all parts of the sprinkler system (including piping and attached equipment) should be hydrostatically tested in accodance with the manufacturer s specifications and the contractor s standard operating procedures. A typical test for metal pipe systems is a hydrostatic test at 200 PSI for 2 hours. The system should maintain pressure for the entire 2 hours without pressure loss. Loss will be indicated by a drop in gauge pressure or visual leakage. Read the pressure from the gauge located at the lowest elevation point of the system. Document the results of the text. Warning: Some plastic pipe manufacturers do not recommend air pressure testing of plastic pipe due to the potential for injury: the pipe may shatter and explode. Plastic pipe may be tested with city water pressure. If the pressure holds for 24 hours then it may be gradually raised to the 200 PSI test point. Establish a Leak Watch When the testing is complete and ready to be charged with water, one person should always be positioned at the valve/gauges to monitor pressure. If a pressure drop occurs, indicating a major leak, that person must immediately close the control valve and operate the main drain. At the same time, the supervisor should walk the entire work area, examine the work for any evidence of leaks. Restore water to the system When the work is complete and tested (and dry pipe systems have been drained and charged with air), the sprinkler control valves that were closed should be fully reopened and out of service tags or signage removed. In a building served by multiple sprinkler control valves, it is important to verify that all valves that were closed have been reopened. Make final notifications When the system has been restored to full operation, the responsible party should make the required notifications to the city, the insurance company, local jurisdiction and the alarm company Central Station. Post-job re-inspection Initiate an inspection of completed installations about 1 week following completion of the work. The purpose is to identify any evidence of leaks or other problems. Responsibilities of the Owner When the work is complete, the responsibility for the system is handed over from the contractor to the owner. This hand-over process must be properly documented, and should include the following items: Job Progress & In-Service Notifications - The owner should be regularly briefed on the status of the installation and all approved changes or modifications to the job specifications. The owner should be notified when the system is charged and returned to service. NFPA 25 and system documentation - The owner must be given a copy of the current version of NFPA 25 and the sprinkler system s operation and maintenance instructions. Restore water to the system When the work is complete and tested (and dry pipe systems have been drained and charged with air), the sprinkler control valves that were closed should be fully reopened and out of service tags or signage removed. In a building served by multiple sprinkler control valves, it is important to verify that all valves that were closed have been reopened. Location of valves - The owner must know where all control valves are located, and which control valves control which areas of
3 Page 3 the building. Handover of keys - If the contractor installs control valve closets or provides locks for interior or exterior control valves, the contractor should clearly identify which keys open which locks and the owner must be given these keys. Test Certificates - The proper Contractors Material and Test Certificates (CM & TC) must be completed for above and below ground piping as required by NFPA 13 and given to the owner. Completion checklist - A complete inspection of the jobsite with the owner must be documented on an inspection checklist. The contractor and the owner must sign the document where the owner acknowledges that: The work was completed; The owner has received training on and understands his operation & maintenance responsibilities; All keys have been provided and; The owner received a current copy of NFPA 25. If Water Leak Incident Occurs When notified of a water leak, the contractor should respond to the site as quickly as possible. The purpose is to assist the owner in minimizing the damages, assist in the cleanup and very important gather information and document via photographs, video and witness statements exactly what happened before any evidence is modified or removed. If you cannot go to the site immediately, give the owner instructions over the phone to minimize the damage and go as soon as you can. While on site, the contractor should: Attempt to minimize the loss by making sure that the water flow is stopped, draining or collecting spilled water, protecting equipment and contents for further damage. Determine the cause(s) or the incident. Document the incident and the damage with written notes, photos and videos. Complete and send a report of loss as soon as possible to your insurance carrier. IMPORTANT: It is important at this stage not to engage in any argument(s), discussions, debates etc., or make any statements, regarding fault for the incident. Your focus should be solely upon minimizing the damages, assisting in the clean-up and documenting the incident. Preventing Water Damage Claims on CPVC Piping Jobs More and more jobs are specifying CPVC piping rather than the traditional metal piping as a cost saving measure. Using CPVC piping in sprinkler jobs involves special hazards that can cause water damage and special precautions and work procedures are required to prevent water damage claims. This section will recap some of these special precautions. Install in Strict Accordance with Manufacturer s Instructions In cases of water damage claims for sprinkler leakage, there is always a question of whether the damage is the responsibility of the pipe manufacturer or the installing sprinkler contractor. The sprinkler contractor s first line of defense in these cases is to be able to document that: The sprinkler contractor is certified to install the CPVC sprinkler piping, All of the contractor s workers have been trained to install in strict accordance with the manufacturer s instructions, and Selection of Materials All CPVC piping and materials used on the job should be approved for the specific installation and working pressures and included in the job specifications. All CPVC piping and materials used on the job should be approved for the specific installation and working pressures and included in the job specification. Use only CPVC pipe that has been stored and maintained properly. CPVC pipe and fittings deteriorate when exposed to sunlight or other sources of UV radiation. This deterioration typically makes the pipe more brittle and more likely to fail during testing and use. Do not use CPVC pipe that has been stored outdoors unless it has been covered properly, and do not use pipe that has faded in color. Keep CPVC pipe and fittings in original packaging until needed. This is to prevent both physical damage and deterioration from sunlight. Installation Methods and Procedures Each length of pipe should be visually inspected for defects and physical damage before installing. When installing CPVC piping, be sure to allow for movement caused by normal expansion in hot weather and contraction in cold weather. CPVC piping expands and contracts differently from metal piping. Use only pipe hangers designed for CPVC plastic pipe. One common problem is workers using metal pipe hangars they have available if they happen to run out of plastic pipe hangers while on the job. CPVC pipe is lighter than metal pipe. Because of this, sprinkler heads must be properly supported to prevent the water jet effect Water Damage Prevention-Sprinkler contractors November 2010
4 Page 4 from lifting the head through the ceiling when the sprinklers are activated. Use Teflon tape on sprinkler head threads and on all other threaded connections. Some pipe dope compounds are petroleum-based and can cause deterioration of the CPVC. Cut the pipe ends square using a miter box. The pipe ends must be deburred and beveled with a chamfering tool after cutting. Failure to do this can cause the pipe end to partially wipe off the cement when the pipe in inserted into the fitting, thus making the joint more likely to fail. To properly spread the cement, insert the pipe fully into the fitting and then rotate the pipe one-quarter turn. Do not connect rigid metal couplers to CPVC grooved adapters. Do not thread, groove, or drill CPVC pipe. Use Solvents, Lubricants, and Anti-Freeze Solutions Properly Use only thread sealants, gasket lubricants, and fire stop materials that are compatible with CPVC. Do not use petroleum or solvent-based sealant, edible oils (such as Crisco ) as a gasket lubricant. or non-compatible fire stop materials as these can cause deterioration of the CPVC. Use proper solvent cement approved for use with the pipe and fittings, and follow application instructions carefully. Do not use solvent cement that has exceeded its shelf life or that has become discolored or jellied. Apply solvent cement carefully. Do not allow solvent cement to run into or puddle in fittings and pipe, since accumulations can plug sprinkler head orifices. Avoid using solvent cement near ignition sources, sources of heat; and do not smoke near solvent cements or when applying them. Use only glycerin and water solutions for freeze protection. Do not use any glycol-based solutions as an anti-freeze. Mix glycerin and water solution in clean containers. Before Pressure Testing Follow the manufacturers recommended cure times prior to pressure testing. Do not pressure test the system until minimum recommended cure times are met from the last connection made in the installation. Conduct blowback testing to verify that the sprinkler system piping has no significant openings. Bleed the air from the system prior to pressure testing, and fill the lines slowly with water. During Pressure Testing Pressure test the CPVC installation in strict accordance with the manufacturer s recommendations. WARNNG: Some plastic pipe manufacturers do not recommend air pressure testing of plastic pipe due to the potential for injury: the pipe may shatter and explode. Plastic pipe may be tested with city water pressure. If the pressure holds for 24 hours then it may be gradually raised to the 200 PSI test-point. Document the results of the pressure test. Follow the procedures outlined above when pressurizing the system. Special Provisions for CPVC Piping Below the Slab When the job requires placing CPVC pipe below a concrete slab, additional special precautions must be taken. This is because leaks below the slab are difficult to detect, can take a long time to manifest, and are very expensive to repair once the slab has been poured. Use CPVC pipe and fittings that are approved by the manufacture for direct burial. Each length of pipe should be visually inspected for defects and physical damage before installing. The buried pipe should be evenly supported in smooth bottom trenches. After the below-slab piping is installed, but before pouring the slab, the pipe system MUST be pressure-tested in accordance with the manufacturer s instructions. 1" foam insulation pipe sleeve should be applied to the CPVC pipe at changes in direction, where the pipe exits the slab, and at expansion joints in the slab. Don t skimp on the sleeving where the pipe comes through the slab; allow 12 above and below the slab. Tape the sleeving to the exposed pipe to prevent slippage. Test the buried pipe twice: once before backfilling, so that any problems can be easily located, and then again after backfilling but before the slab is poured, to make sure that the pipe was not damaged during backfilling.
5 Page 5 EVEREST LOSS CONTROL ALERT Backfill over buried CPVC pipes should be free of rocks and debris that could damage the pipe. If a termiticide is to be applied, this should be done after the CPVC pipe has been backfilled. Do not allow heavy concentrations of termiticides to come into direct and sustained contact with CPVC pipe. To reemphasize: THOROUGHLY PRESSURE TEST THE BURIED PIPING IN ACCORDANCE WITH THE MANUFACTURER S IN- STRUCTIONS BEFORE THE SLAB IS POURED. Remember, Everest Loss Control offers services to help you in your loss prevention efforts. If you would like more information about these services, visit our web site at Loss Control is a daily responsibility of your individual management. This publication is not a substitute for your own loss control program. The information that is provided in this Alert should not be considered as all encompassing, or suitable for all situations, conditions, or environments. Each organization is responsible for implementing their safety/injury/illness prevention program and should consult with legal, medical, technical, or other advisors as to the suitability of using the information contained in this Alert. The information contained in this publication is intended for general informational purposes only and is not intended to constitute legal advice or opinions. You should contact an attorney if you need legal advice and/or you have any questions concerning your obligations under any law, statute and/or code identified in this publication. CONTACT US Westgate Corporate Center 477 Martinsville Road P.O. Box 830 Liberty Corner, NJ Everest focuses on specialty property and casualty insurance business and is licensed to conduct business in all 50 states, including the District of Columbia. Everest is rated A+ XV (Superior) by A.M. Best. To learn more about Everest, visit our website at : Loss Control Department Phone: Fax: [email protected]
Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
A cure for water damage in real estate
A cure for water damage in real estate Presented for BC Non-Profit Housing Association by Jeff Shearman, Zurich Services Corporation 2010 Zurich Canada Focused on our customer Reduce overall risk by reducing:
Water Damage During Construction
Allianz Global Corporate & Specialty Americas Water Damage During Construction May 2012 A Contractor s Loss Prevention Guide Water damage losses are a major cause of loss during construction and represent
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
Inspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
FIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
Finding and Fixing Leaks
Finding and Fixing Leaks Where did all that water go? Could we have splashed all that water out of the tub? These are all common thoughts that can run through your mind when you open up the hot tub cover
How to Prevent Liquid Damage Property Losses
1. The leading cause of property losses is from liquid damage. A review of Zurich North America claims data highlights the problem. 2. Water damage originates from a number of sources: Domestic water lines
Maintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
STANDARD SPECIFICATIONS SECTION 02512 CLEANING AND LINING WATER MAINS
STANDARD SPECIFICATIONS SECTION 02512 CLEANING AND LINING WATER MAINS PART 1 GENERAL 1.1 DESCRIPTION A. Section includes requirements for cleaning and lining existing cast iron and ductile iron water mains
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
CONTROL METHODS. There are five ways to control the release of asbestos fibers:
Control Methods CONTROL METHODS When asbestos containing materials are found in a building, the owner must decide which method or methods will be used to deal with the asbestos. The decision will be based
STORED PRESSURE STAINLESS STEEL
STORED PRESSURE STAINLESS STEEL WATER FIRE EXTINGUISHERS Model 240-2-1/2 Gallon OWNER'S SERVICE MANUAL NO. 05601 INSPECTION, MAINTENANCE AND RECHARGE All fire extinguishers should be installed, inspected
Transformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
What is water main cleaning & lining
What is water main cleaning & lining The Borough s water distribution system includes cast iron pipe. The program involves cleaning older section of cast iron pipe and lining it with cement mortar. Over
INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303
WATER MIST HAND PORTABLE FIRE EXTINGUISHERS Model B270 ¾ Gallon Model B272 2 ½ Gallon INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 6303 All fire extinguishers should be installed, inspected
Section 02702 SEWER PIPE INSTALLATION AND TESTING
PART 1 - GENERAL Section 02702 SEWER PIPE INSTALLATION AND TESTING 1-1. SCOPE. This section covers the installation and testing of all sewer pipe furnished under the following specification sections: Concrete
Fighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
Core & Shell Construction. Rules and Regulations
Core & Shell Construction Rules and Regulations 1. Protection: During the construction Contractor shall endeavor to protect all areas of work from damage caused by workers, weather or equipment. 2. Permits
Powered Industrial Truck Safety Program
Powered Industrial Truck Safety Program TABLE OF CONTENTS Forklift Safety Program 1.0 Overview... 3 2.0 Policy.....3 3.0 Requirements 3 4.0 Purpose. 3 5.0 Scope......4 6.0 Forklift Procedures 4 6.0 Responsibilities.....6
Fire Alarm and Protection Impairment Policy and Procedures
1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced
MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND
EFFECTIVE FEBRUARY 2014. note: drainage permit required to call for a dampproof inspection
EFFECTIVE FEBRUARY 2014 note: drainage permit required to call for a dampproof inspection 1. ROOF DRAINS/DECK DRAINS (INTERIOR ) All roof and deck drains within the perimeter of the building shall be APPROVED
STCC Contractor/Vendor Rules and Regulations
STCC Contractor/Vendor Rules and Regulations STCC maintains specific rules and regulations that apply to all contractors and vendors who perform work or provide services. It is the responsibility of the
Select Radiators Installation Guide
Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall
Commercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
Installation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of
Engineering Specifications
PUREFLOW PEX PRODUCTS PART 1 GENERAL 1.1 SUMMARY 1.1.1 This specification covers Branch & Main, Parallel Water Distribution Systems (MANABLOC), Cross-linked Polyethylene tubing and fittings using PEX Press
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
How To Install An Overhead Sewer
Village of Broadview Flood Control Assistance Program Village of Broadview 2350 S. 25 th Avenue, Broadview, IL 60155 INTRODUCTION The Village of Broadview is served by combined sewers which carry sewage
SECTION 1 GENERAL REQUIREMENTS
Page 1 of 6 SECTION 1 GENERAL REQUIREMENTS 1. SCOPE OF WORK: The work to be performed under the provisions of these documents and the contract based thereon includes furnishing all labor, equipment, materials,
Civil Engineering Sector Labour-Management Health and Safety Committee
PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION SITES Civil Engineering Sector Labour-Management Health and Safety Committee July 2008 PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
SECTION 807 PUMP STATION REHABILITATION
SECTION 807 PUMP STATION REHABILITATION 807-1 DESCRIPTION: Rehabilitation of pump stations shall be defined as the cleaning, removal, repair and/or replacement of any and/or all components including but
SEVERE WINTER WEATHER PROPERTY RISK CONTROL
WEATHER HAZARDS AND PRECAUTIONS STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN SEVERE WINTER WEATHER PROPERTY RISK CONTROL Winter weather not only brings freezing temperatures with it, but all
Inspections Standard Operating Procedure 5 Aboveground Storage Tanks
Aboveground Storage Tanks Aboveground Storage Tank Inspection This Standard Operating Procedure describes the steps that campus units that manage aboveground oil storage tanks (ASTs) or containers must
MOISTURE MANAGEMENT DURING THE CONSTRUCTION PROCESS
MOISTURE MANAGEMENT DURING THE CONSTRUCTION PROCESS Ed Light 1,*, James Bailey 1, and Roger Gay 1 1 Building Dynamics, LLC, Ashton, MD (USA) *Corresponding email: [email protected] Published
FIBERGLASS UNDERGROUND STORAGE TANKS Special Installation Instructions for New York City Gasoline and Diesel Motor Fuels
INTRODUCTION The purpose of this manual is to provide speci c, detailed supplemental instruction regarding the installation of special Fiberglass Double-Wall Underground Storage Tanks (including compartment
Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue. Photo Essay
Original HVAC Units: Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue Photo Essay One fan motor draws air from the lower section of the unit,
later damage - Loss ControL
later damage - Loss ControL axisinsurance.ca Table of Contents EXECUTIVE SUMMARY... 1 FACILITY SYSTEMS WATER DAMAGE... 2 Frozen Pipes.....................................................................................
Terms of Reference Air Handling Unit (HVAC System) Cleaning
Terms of Reference Air Handling Unit (HVAC System) Cleaning Introduction General cleaning of the air handling units is currently undertaken by the Mechanical Division staff composing of 3 personnel. Cleaning
FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE
Page 1 of 10 FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE SYSTEM TESTING 1. Testing of the Fire Alarm and Fire Protection Systems 1.1. The Building Engineer, Electrician, Plumber (or
NCCER 13614 Progress Blvd., Alachua, FL 32615 Tel: (888) 622-3720 E-mail: [email protected]. Task Number Item Date(s) Recorded By
NCCER 13614 Progress Blvd., Alachua, FL 32615 Tel: (888) 622-3720 E-mail: [email protected] PIPELINE MAINTENANCE On-the-Job Training Level One MODULE 66101-02 INTRODUCTION TO THE PIPELINE INDUSTRY This is
SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes)
SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes) Maintenance Office Administrative Office Billing Office 530-426-7802 530-426-7800 916-332-4872
Safe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
Refrigeration Installation 101
Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Universal Installation and Maintenance Instructions 71CD-1212 Spill Containment Bucket
Universal Installation and Maintenance Instructions 71CD-1212 Spill Containment Bucket IMPORTANT: Please read these instructions completely and carefully before installing Universal s 71CD-1212 Spill Containment
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
OVERVIEW SCOPE DEFINITIONS
Procedure No 400.10 Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: March 2008 Distribution All Employees Review Date: April 2008 Purpose: To establish
UNIVERSITY OF TOLEDO
UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect
A cure for water damage in offices and habitational facilities. Risk Services: Understanding risk across your business
A cure for water damage in offices and habitational facilities Risk Services: Understanding risk across your business Focused on helping our customers At Zurich, we are focused on helping customers reduce
WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.
WET/DAMP BASEMENTS PROBLEM. IS THIS BASEMENT LEAKING OR COULD WE HAVE ANOTHER PROBLEM? Water line arching up on wall in corners of basement. Water collecting on concrete floor starting in corners. ANSWER:
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
Freeze Damage May 21, 2014
Freeze Damage May 21, 2014 Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case basis
History of the SPCC Rule
2010 SPCC Training SPCC Rule History of the SPCC Rule The SPCC plan is a document required under the clean water act (CWA) It became effective in 1972 and has changed little in 32 years. The rule was formally
TECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
SECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN XXXX FARM (CITY OR COUNTY), MICHIGAN CONTACT (NAME), OWNER CERTIFICATION: I hereby certify that I have examined the facility, and being familiar with the
Inspection and Testing Program Fire Protection Equipment
I. Introduction Inspection and Testing Program Fire Protection Equipment State of Minnesota Emergencies seldom give warning before they strike. Thus, it is essential that fire protection equipment be inspected,
have been provided with information on whether they do or do not contain asbestos before starting work;
Health Effects of Asbestos If your work involves possible exposure to asbestos, you should: be aware of the risks from asbestos exposure; understand the importance of keeping exposure as low as possible;
A cure for water damage in Public Sector facilities. Risk Services: Understanding risk across your community
A cure for water damage in Public Sector facilities Risk Services: Understanding risk across your community Focused on helping our customers At Zurich, we are focused on helping customers reduce and mitigate
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
Fire Watch. Fire safety systems may not be deactivated in whole or in part for any reason other than for repairs or hot work.
Emergency Guideline GU.FAC.039 For Team Leaders, Caretakers, Trades, and Project Supervisors Approved by FS Leadership Team, August 28, 2013 Fire Watch A Fire Watch is a temporary surveillance system for
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING
ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING 1.0 General 1.1 The work covered by this section consists of providing all labor, equipment, material and supplies, insurance, accessories, tools, transportation,
Metropolitan Washington Airports Authority Office of Public Safety Fire & Rescue Department. Fire Code Enforcement Division
Metropolitan Washington Airports Authority Office of Public Safety Fire & Rescue Department Fire Code Enforcement Division Fire Protection System Impairment Requirements For Contractors and Service Personnel
Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
Roland Garcia Pearland Fire Department
Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and
Fire Alarm Log Book. Any activity regarding this system must be documented in writing.
CASTLE ROCK FIRE AND RESCUE DEPARTMENT 300 Perry Street Castle Rock, Colo. 80104 303-660-1066 Do not remove from the premises: Fire Alarm Log Book Any activity regarding this system must be documented
Asbestos WHAT TO DO? Studies of people who were exposed to high levels of asbestos in factories and shipyards, are at increased risk of:
Asbestos WHAT TO DO? What Is Asbestos? Asbestos is mineral fiber. It can be positively identified only with a special type of microscope. There are several types of asbestos fibers. In the past, asbestos
APPENDIX 7-B. Hazardous Materials Management Plan
S TAR-ORION S OUTH D IAMOND P ROJECT E NVIRONMENTAL I MPACT A SSESSMENT APPENDIX 7-B Hazardous Materials Management Plan SX03733 Section 6.0 1.1.1 Hazardous Materials Management Plan 1.1.1.1 Introduction
SECTION 01 50 00 CONSTRUCTION FACILITIES AND TEMPORARY CONTROLS
SECTION 01 50 00 CONSTRUCTION FACILITIES AND TEMPORARY CONTROLS PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. Regulations: Comply with industry standards and applicable laws and regulations of authorities
Water Damage on Construction Sites. A guide to loss prevention
Water Damage on Construction Sites A guide to loss prevention Water damage is the second most frequent cause of loss during building projects and represents a large percentage of Construction All Risk
Asbestos Abatement Work Plan for the Carter Carburetor Superfund Site
for the Prepared for: ACF Industries LLC 101 Clark Street St. Charles, Missouri 63301 Prepared by: AMEC Environment & Infrastructure, Inc. 15933 Clayton Road, Suite 215 Ballwin, Missouri 63011 Project
Outdoor Storage of Raw Materials SC-33
Objectives Cover Contain Educate Reduce/Minimize Description Raw materials, by-products, finished products, containers, and material storage areas exposed to rain and/or runoff can pollute stormwater.
Proposed Minimum Subterranean Termite Treatment Standards
Proposed Minimum Subterranean Termite Treatment Standards Introduction This document is intended to serve as a model for states considering the adoption of standards for soil application of termiticides.
Antifreeze Solutions in Residential Fire Sprinkler Systems
Antifreeze Solutions in Residential Fire Sprinkler Systems The 2013 edition of NFPA 13D, as amended by TIA 13 1, discourages the use of antifreeze solutions within residential fire sprinkler systems unless
A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.
PART 1 GENERAL 1.1 SCOPE A. This item shall include the work necessary for the installation of storm sewer line construction. B. Reference Section 3800 Trenching and Backfill and the General Conditions,
Commercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
Contingency Plan. Community College of Denver - Auraria Campus Facility Name
Contingency Plan Community College of Denver - Auraria Campus Facility Name This plan is reviewed annually and amended whenever changes occur that will significantly affect the ability of this facility
Boiler & Pressure Vessel Inspection discrepancies and failures
Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:
ACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas
ACTIVITY NAME Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas CY 2014 BOTTOM LINE UP FRONT To prevent oil discharges
Clean Water: Supply side potable water, not wastewater. Gray Water/Sewage: Wastewater originating from a drain (sink, toilet, urinal).
Procedures for Emergency Responses to Flooding and Building Water Intrusion PURPOSE: To establish uniform, sanitary, and systematic procedures for responding to flooding and water intrusion emergencies.
CSC-DIVISION 1-MASTER SECTIONS Description
CSC-DIVISION 1-MASTER SECTIONS Description 01 11 00 Summary of Work by Consultant 01 12 00 Multiple Contract Summary by Consultant 01 14 00 Work Restrictions see below 01 21 00 Allowances by Consultant
SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.
SECTION LS 2530 SANITARY SEWERS PART 1 GENERAL 1.1 SUBMITTALS A. General: Submit the following in accordance with The General Conditions. 1. Product data for drainage piping specialties. 2. Shop drawings
Beacon Hill Sewer District Standard Specifications
Beacon Hill Sewer District Standard Specifications Residential Gravity Side Sewer Including Design Criteria and Standard Construction Drawings Residential Gravity Side Sewer Design Criteria 1. Provisions
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
