Firefighter Review. Instructor Guide
|
|
|
- Domenic Robbins
- 10 years ago
- Views:
Transcription
1 Firefighter Review Instructor Guide Session Reference: 3 Topic: Attack Line Handling Level of Instruction: Time Required: Three Hours Materials: Two Fully Equipped Pumpers Structure for Use in Advancing Hose References: Engine Company Fireground Operations, Second Edition, NFPA, Pages 2-6, and Chapters 4 and 6-11 Essentials of Fire Fighting, Fourth Edition, IFSTA, Chapters 12 and 13 ================================================================= PREPARATION: Motivation: Objective (SPO): The firefighter will demonstrate a general understanding of the construction, operation, and utilization of fog and solid stream nozzles and, by participation and observation, a knowledge of the various nozzles, hose layouts, appliances, and procedures involved in applying water at a structural fire. Overview: Attack Line Handling Handlines and master streams Built-in fire protection system components Hose and nozzle selection Hose stream placement Supporting built-in fire protection systems Page 1
2 Session 3 Attack Line Handling SPO EO 3-1 EO 3-2 EO 3-3 EO 3-4 EO 3-5 The firefighter will demonstrate a general understanding of the construction, operation, and utilization of fog and solid stream nozzles and, by participation and observation, a knowledge of the various nozzles, hose layouts, appliances, and procedures involved in applying water at a structural fire. Describe the appropriate number, size, and placement of fire streams needed to deliver the required fire flow at structural fires. Describe the engine company responsibility for supporting built-in fire protection systems. Demonstrate various sizes of hose and different nozzles used to produce streams for fire attack. Demonstrate the placement of fire streams at structural fires. Demonstrate the utilization of the engine company to support built-in fire protection systems. Page 2
3 I. Handlines And Master Streams (3-1) NOTE: Some material may be a review since handline operation and setting up master stream devices are included in Firefighter I. Focus should be more on handline and master stream selection and application in fire situations. A. Hose Line Selection 1. Engine company must be considerate of limitations of various sizes of hose 2. In addition to flow limitation, there is factor known as friction loss which affects fire flows a. Loss of pressure within hose line due to internal resistance of water against hose lining b. Friction loss affected by three factors 1) Flow 2) Hose length 3) Size of hose c. Should be consideration to engine company crew when selecting attack lines which must be stretched over long distances 3. Maximum flow capabilities for attack lines 1-1/2-inch 1-3/4-inch 2-inch 2-1/2-inch 3-inch 125 gpm 150 gpm 200 gpm 250 gpm 400 gpm 4. Range of nozzle flows for combination nozzles with recommended nozzle pressure of 100 psi 1-1/2-inch 30 gpm to 125 gpm 1-3/4-inch/2-inch 95 gpm to 200 gpm 2-1/2-inch 125 gpm to 250 gpm 5. Flows for a 2-1/2-inch straight tip nozzle with recommended nozzle pressure of 50 psi 1-inch tip 1-1/8-inch tip 1-1/4-inch tip 210 gpm 266 gpm 328 gpm Page 3
4 6. Flows from master stream devices a. Fog nozzle minimum is 500 gpm at 100 psi nozzle pressure b. Flows for straight tips with recommended nozzle pressure of 80 psi (rounded) 1-1/2-inch 1-5/8-inch 1-3/4-inch 1-7/8-inch 2-inch 600 gpm 700 gpm 800 gpm 900 gpm 1000 gpm 7. Friction loss for attack lines a. For 1-1/2-inch, 1-3/4-inch, and 2-inch attack lines, 30 psi per hundred feet b. For 2-1/2-inch attack lines, 15 psi per hundred feet c. 1-1/2-inch, 1-3/4-inch, and 2-inch attack lines should not exceed 300 feet in length d. 2-1/2-inch attack lines should not exceed 500 feet e. When lengths of attack line beyond those recommended are required, consideration should be given to using 3-inch, 4-inch, or 5- inch hose to get water closer to the fire scene and dividing the flow into more manageable size attack lines using wyes or manifolds B. Initial Attack 1. Indirect attack - fog stream used to attack fire from outside building a. Should not be used to fight fire in occupied building b. Quick interior attack should not be made in building undergoing demolition, abandoned, had previous fires or under construction c. If large intense fire encountered, may be necessary to knock down or control fire from outside using solid stream before making interior attack Page 4
5 2. Solid streams versus fog streams a. For safest and most effective operation where people in area, solid stream or fog nozzle on solid stream position should be used 1) Aid rescue 2) Reduce steam production b. Use of fog should be restricted to unoccupied confined spaces c. When building adequately ventilated opposite direction from fog nozzle, fog stream can be used 1) No more than 30-degree angle 2) Produces reach and fog pattern 3. Effective stream operation a. Use solid stream nozzles or set fog nozzles on solid stream setting b. Stay low upon entering fire area to let heat and gases vent before moving in c. Before door to fire area opened, all firefighters should be positioned on same side of entrance and remain low d. Crack nozzle and bleed air out of line ahead of water e. If fire shows at top of door as opened, ceiling should be hit with solid stream to cool and control fire gases f. Sweep floor with stream to cool burning debris and hot surfaces g. Do not open stream until fire can be hit unless firefighter safety involved h. Direct stream at base of fire if localized i. As advance made, angle of stream should be lowered and attempt made to hit main body of fire j. When main body of fire knocked down, shut down stream and let area to vent Page 5
6 k. When fire knocked down, shut down l. Upon entering area which is very hot and finding no fire, withdraw immediately and check area below m. When attacking basement fire down interior stairs, solid stream should be used because fog will generate steam 4. Number of lines a. Attack main body of fire b. Get over fire c. On each side of fire d. Consideration must be given to mobility of hose and flow requirements C. Back-Up Lines 1. Purpose of back-up lines a. Used when initial attack lines cannot quickly control fire b. Not used to protect exposures or attack fire c. Held in readiness for use in place of attack lines d. May also be used for back-up or safety team 2. Stretched whenever not completely obvious that fire quickly extinguished with initial attack lines a. Taken into building immediately after initial attack lines b. Positioned close to initial attack lines c. Charged and ready for use 3. Size of back-up lines a. For 1-1/2-inch lines, minimum 1-3/4-inch b. For 1-3/4-inch lines, minimum 2-1/2-inch c. For 2-1/2-inch lines, minimum 2-1/2-inch with larger tip Page 6
7 d. For fire where initial attack is 2-1/2-inch line, master stream devices may be required 4. If back-up lines placed in service, initial attack lines should be shut down 5. Once fire controlled, back-up lines shut down and smaller line used for mop up 6. On any working fire, a back-up or safety team should be standing by with charged line and ready to make entry should the initial attack crew require assistance D. Master Stream Devices 1. Water supply for master streams a. Pumper at water source sending water to pumper at fire b. Adequate number of supply lines laid between pumpers and from pumper at fire to master stream device c. No more than 100 feet of hose between pumper at fire and master stream device 2. Use of master stream devices a. Fire attack b. Back-up c. Exposure protection 3. Solid stream versus fog stream a. Solid stream most effective 1) Wind conditions 2) Strong draft created by large fire 3) Distance from nozzle to building b. Fog streams superior 1) Exposure protection 2) Covers wider area Page 7
8 4. Positioning device a. Fog nozzle must be positioned close to structure b. Solid stream functions better if positioned some distance from building 5. Directing heavy streams a. Move horizontally back and forth across fire area b. Move up and down to reach full depth c. Look to see if water is entering building or hitting building II. Built-In Fire Protection Systems (3-2) A. Standpipe Systems 1. Piping arrangement that carries water vertically and horizontally through building for firefighting operations 2. Two types of systems a. Dry system - not connected to water supply 1) Interior system has at least one outlet on each floor 2) Exterior system usually runs along fire escape 3) May include multiple interconnected systems b. Wet system - connected to one or more sources of water 1) Minimum flow of 250 gpm at residual pressure of 65 psi on roof or 2) Minimum pressure of 40 psi on 1-1/8-inch tip connected to 100 feet of 2-1/2-inch hose attached to highest outlet with nozzle on roof 3) May include multiple separate or interconnected risers Page 8
9 3. Fire department siamese a. Water should be pumped into any standpipe system being used for firefighting b. At least two lines should be connected 1) First line to left intake and charged 2) Second line to right intake c. If supply line cannot be connected to siamese, water can be supplied to system through outlet on first floor d. Pumper should be positioned within 50 feet 4. Fire attack from standpipe systems a. Equipment 1) 150 feet of 1-1/2-inch or 1-3/4-inch hose 2) Nozzle 3) Gated wye 4) Pipe wrench in the event the hand wheel on outlet missing 5) Secondary standpipe pack consisting of 2-inch or 2-1/2-inch hose 6) Short section (5 feet) of 2-1/2-inch or 3-inch hose to go between outlet and gated wye 7) Gated wye may be equipped with 1-1/2-inch to 2-1/2-inch increaser to permit connection of larger attack hose b. Beginning attack operations 1) Connect to outlet in stairwell on fire floor (Firefighter I teaches to connect on floor below fire floor) 2) Pull excess hose up stairway toward next floor before charging 3) If outlet in corridor, connect on floor below fire floor Page 9
10 4) Be careful not to impede evacuation or allow great volumes of smoke in stairway B. Automatic Sprinkler Systems 1. Types of systems a. Wet system - piping completely filled with water from source to heads b. Dry system - system contains water only from source to control valve c. Pre-action system - dry system with air exhausters controlled by heat detectors d. Deluge system - designed to deliver large volume of water; water only from source to control valve 2. Water supply a. Can be supplied by gravity tank, pressure tank, fire pump, or water main b. Engine company should attach two lines to siamese and prepare to pump system III. Hose and Nozzle Selection (3-3) A. During the evolutions below, the students will demonstrate their proficiency in the handling and use of various hoses and nozzles used to control and extinguish a fire. B. The nozzles will first be reviewed by the instructor. All water will be discharged outside the structure. C. The student should already be familiar with the appliances required and the techniques involved in the evolutions. What is being emphasized here is teamwork and operating efficiency. IV. Hose Stream Placement (3-4) A. The student will perform the following evolutions: 1. Advance an uncharged 1-1/2-inch, 1-3/4-inch, or 2-inch line up an interior stairs to a location above the ground floor. 2. Advance a charged 1-1/2-inch, 1-3/4-inch, or 2-inch line up an interior stairs to a location above the ground floor. Page 10
11 3. Advance a charged 1-1/2-inch, 1-3/4-inch, or 2-inch line down an interior stairs to a location below the entry floor. 4. Advance an uncharged 1-1/2-inch, 1-3/4-inch, or 2-inch line up a ladder to a floor above the ground floor. 5. Advance a charged 1-1/2-inch, 1-3/4-inch, or 2-inch line up a ladder to a floor above the ground floor. 6. Advance a charged 1-1/2-inch, 1-3/4-inch, or 2-inch line to the fire floor and a second charged line of the same size to the floor above the fire floor. 7. Advance a charged 2-1/2-inch line up an interior stairs to a location above the ground floor. 8. Advance a charged 2-1/2-inch line up a ladder to a floor above the ground floor. 9. Advance a charged 1-1/2-inch, 1-3/4-inch, or 2-inch line to the fire floor and a 2-1/2-inch charged line to the floor above the fire floor. 10. Advance an uncharged 1-1/2-inch, 1-3/4-inch, or 2-inch line to the floor below the fire floor, connect it to the standpipe connection, charge it, and advance it to the fire floor. After charged, extend the line to a higher floor. 11. Advanced an uncharged 3-inch, 4-inch, or 5-inch line to the base of a structure, attach a wye, connect two 1-1/2-inch, 1-3/4-inch, or 2-inch lines, charge the system, and advance the attack lines into the structure. 12. Set up, advance lines, and charge a portable master stream device. B. The evolutions will first be reviewed by the instructor before being run with moving apparatus. All water will be discharged so a not to damage any structures or surroundings. C. These evolutions are designed to expose the student to various methods of applying water at the fire scene. The student should already be familiar with the appliances required and the techniques involved in the evolutions. What is being emphasized here is teamwork and operating efficiency. Page 11
12 V. Supporting Built-In Fire Protection Systems (3-5) A. Set up and establish a water supply from the attack pumper to a fire protective system using multiple lines of 2-1/2-inch or 3-inch hose. B. The evolution will first be reviewed by the instructor before being run with moving apparatus. This evolution can be conducted in conjunction with Evolution No. 7 above. C. The evolution is designed to expose the student to the method of supporting built-in fire protection systems at the fire scene. The student should already be familiar with the appliances required and the techniques involved in the evolution. What is being emphasized here is teamwork and operating efficiency. Page 12
13 SUMMARY: Review: Attack Line Handling Handlines and master streams Built-in fire protection system components Hose and nozzle selection Hose stream placement Supporting built-in fire protection systems Remotivation: Assignment: ================================================================= EVALUATION: Page 13
Truck Company Operations
Truck Company Operations Instructor Guide Session Reference: 1-1 Topic: Salvage Level of Instruction: Time Required: 2 Hours Materials: Various Items of Salvage Equipment Salvage Covers References: Ladder
The In-Line Gauge in Standpipe Operations
The In-Line Gauge in Standpipe Operations BY RUSS CHAPMAN Your engine company receives a report of fire in a mid-rise elderly housing complex during morning coffee at the beginning of a shift. You know
St. John s University
St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
1402 Hybrid Firefighter I. Course Orientation Guide (Rev 1)
1402 Hybrid Firefighter I Course Orientation Guide (Rev 1) Department of Labor, Licensing and Regulation Division of Fire and Life Safety South Carolina Fire Academy 2014 1402 Hybrid Firefighter I Course
Natural Gas Emergencies
Natural Gas Emergencies Purpose To protect the personnel within the department, and citizens from the hazards involved in a natural gas emergency. The Incident Commander is to use his/her best judgment
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
A. Fire Protection Plan. B. Access and Parking
Standards for Construction Site Fire Safety For Use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire Code (CFC) These standards are intended to prescribe
LOS ANGELES COUNTY FIRE DEPARTMENT CONTEXT TRAINING PROGRAM ENGINE COMPANY SKILLS 1 ¾ RESIDENTIAL ATTACK LINES
3 ENGINE COMPANY SKILLS 1 ¾ RESIDENTIAL ATTACK LINES 1. General Information The attack line of choice for a residential fire is the pre-connected 1 ¾ attack line with an Automatic Nozzle 1 ¾ attack lines
I. Introduction. 10 minutes
I. Introduction 10 minutes Introduction (1 of 2) An uninterrupted water supply is: The primary weapon for extinguishment Essential for fire fighter safety Ensuring a dependable water supply is a critical
Fire is the rapid oxidation of a combustible material, releasing heat, light, smoke, and various toxic gases
VENTILATION Fire is the rapid oxidation of a combustible material, releasing heat, light, smoke, and various toxic gases If a fire is contained in a building, the heat, smoke, and toxic gases will spread.
FIRE FIGHTER I CHARACTERISTICS AND FUNCTIONS OF WILDLAND HOSE LAYS TOPIC: TIME FRAME: 1:00. Level II LEVEL OF INSTRUCTION:
TOPIC: CHARACTERISTICS AND FUNCTIONS OF WILDLAND HOSE LAYS TIME FRAME: 1:00 LEVEL OF INSTRUCTION: Level II AUTHORITY: 1997 NFPA 1001 3.3-18 BEHAVIORAL OBJECTIVE: Condition: Behavior: Standard: A written
FIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
Current as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
Workplace Fire Safety
Teaching Guide Workplace Fire Safety for staff Seattle Fire Department Fire Prevention Division Workplace Fire Safety Instructor Outline Introduction Goals: To ensure that employees are knowledgeable in
Springdale Fire Department Backup Driver Certification Program. Behavioral Objectives
Springdale Fire Department Backup Driver Certification Program Backup Driver Task Book I. Obtain required prerequisites 1. Performance a. Complete Probationary Program b. Complete CEVO Fire Course c. Complete
Toms River Fire Academy
Pump School Manual Toms River Fire Academy Table of contents Chapter 1 Characteristics of Water Page 3 Pressures, Atmospheric, Static, Residual, Head.Page 7 Chapter 2 Pump Construction and Gauges Page
Define Fire Stream. A stream of water, or other extinguishing agent, after it leaves the fire hose and nozzle until it reaches the desired point
Nozzles and Streams Define Fire Stream A stream of water, or other extinguishing agent, after it leaves the fire hose and nozzle until it reaches the desired point Identify the Purposes of a Fire Stream
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
United States Fire Administration
United States Fire Administration Technical Report Series High-rise Office Building Fire One Meridian Plaza Philadelphia, Pennsylvania Federal Emergency Management Agency United States Fire Administration
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
How To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
FIRE PROTECTION BUREAU ACCREDITATION AND CERTIFICATION PO Box 42600 Olympia WA 98504-2600 (360) 596-3945 FAX: (360) 596-3936 FIREFIGHTER I
5.1 GENERAL REQUIREMENTS Evaluation Sheet: 5.1.2 5.1.2 GENERAL SKILL REQUIREMENTS DON PPE Skill Sheet: A Standard Area: General Skill Requirements STANDARD: 5.1.2 TASK: Don personal protective clothing
FIRE DEPARTMENT HYDRAULICS
FIRE DEPARTMENT HYDRAULICS BASIC CONCEPTS & FORMULAS WATER MEASUREMENTS 1 Cubic foot of water weighs 62.5 pounds 1 Cubic foot of water contains 1,728 cubic inches 1 Cubic foot of water contains 7.5 gallons
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
CHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST
SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
NFPA Fire Fighter II
State of Oregon Department of Public Safety Standards and Training NFPA Fire Fighter II Task Book Task Book Assigned To: Name DPSST Fire Service # Department Name Date Initiated Signature of Department
2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
HS-901(A) BASIC STEAM HEATING SYSTEMS
HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,
FIRE SAFETY PLAN FOR KITCHENER, ONTARIO
FIRE SAFETY PLAN FOR KITCHENER, ONTARIO Additional information of fire safety plans may be found at our website at www.kitchener.ca/fire.htm. Before submission, please read and change all sections to address
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
Fighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT
[Sub-Art. or Sec.]* SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT TABLE OF CONTENTS Art. or Sec.** [1700.0] Art. 1 General [1700.1] 923 Scope [1700.2] 924 Standards [1700.3] 925 Definitions
Appendix B Forms for Inspection, Testing, and Maintenance
Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete
WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS
GAP.14.1.2.2 A Publication of Global Asset Protection Services LLC WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS INTRODUCTION A hydrant or other large-volume flow test is necessary for proper water
Division 21. Fire Suppression
21 00 00. Fire Suppression For campus projects that require a fire suppression system shut down in a campus facility, a Shut Down Procedure of Fire Safety System Sheet must be completed and filed seven
Introduction to and Operation of Compressed Air Foam Systems (CAFS)
Compressed Air Foam Systems (CAFS) Mesa Fire Department currently has nine (9) compressed air foam pumpers. Each unit has 20 to 30 gallons of Class A foam on board. Typical compressed air foam is available
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.
Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable
RESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
Law No. (9) of 2012 Amending some provisions of Law No. (13) of 1997 Concerning the Civil Defense
Law No. (9) of 2012 Amending some provisions of Law No. (13) of 1997 Concerning the Civil Defense We, Hamad Bin Khalifa Al-Thani, Emir of the State of Qatar Having pursued the Constitution, And the Law
MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND
Tank Farm and Bulk Storage Fire Incidents
Instructor Manual Module 7 Tank Farm and Bulk Storage Fire Incidents Module Objective Upon the successful completion of this module, participants will be able to develop plans to fight or contain fires
SOUTH LYON FIRE DEPARTMENT Manual of Procedures 404
GENERAL STRUCTURAL FIRE FIGHTING Issued: February 6, 2011 Revised: March 6, 2015 Approved: Chief Mike Kennedy I. SCOPE The general structural firefighting procedure will provide guidelines to incident
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
Class A Foam Mixing and Application Equipment
Class A Foam Mixing and Application Equipment Adding Phos-Chek Class A foam concentrate to water: There are many methods of adding Phos-Chek Class A foam concentrate to water. The different methods have
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
Element D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
SUPERYACHT SPARES. Nozzles and portable monitors. www.superyachtspares.com / [email protected] / +31 183 639193
Nozzles and portable monitors Rosenbauer - Nozzles and portable monitors EN Maximum extinguishing effect. Minimal water consumption. The Rosenbauer nozzle enables the manual adjustment of the water flow
St. John s University Fire Safety Plan
St. John s University Fire Safety Plan Flynn Hall St. John s University Fire Safety Plan Part 1-Building Information Section Flynn Hall 300 Howard Ave. Staten Island, N.Y. 10301 Fire Safety Director: Address:
(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;
(1979) (Rev.1 1990) (Rev.2 1996) (Rev.3 Jan 2012) Safety features.1 Fire protection and extinction.1.1 General Fire protection arrangements and fire extinguishing systems are to be in accordance with the
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
Greater Manchester Fire and Rescue Service
Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY
Based on the initial size-up and any information available, Command will formulate an action plan to deal with the situation.
Hazardous Materials Response Clear Creek Fire Authority This plan provides a basic philosophy and strategic plan for hazardous materials situations. All Clear Creek Fire policies and procedures, unless
Al-Balqa Applied University
In The Curriculum of Associate Degree in Fire & Rescue Techniques Consists of (72 Credit Hours) as follows: SERIAL NO. First Second Third REQUIREMENTS University Requirements Engineering Program Requirements
Flammable Liquids 29 CFR 1910.106
Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,
RESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009
Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
FIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program
Sable Altura Fire Department
Position: Immediate Supervisor: FLSA Status: Service Hours: Firefighter Lieutenant Volunteer As necessary to perform volunteer responsibilities, and meet training and response requirements This position
SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
build safe live safe
NYC Buildings Department 280 Broadway, New York, NY 10007 Robert D. LiMandri, Commissioner BUILDINGS BULLETIN 2012-009 Technical Supersedes: Issuer: None Thomas Fariello, R.A. First Deputy Commissioner
Top 10+ Mistakes of DWV plumbing design
Top 10+ Mistakes of DWV plumbing design Listed below are the some of the most frequently missed items, noticed by our inspectors, at plumbing rough-in when non-plumbers attempt plumbing design. Most of
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
NEW SCIENCE FIRE SAFETY ARTICLE INNOVATING FIRE ATTACK TACTICS SUMMER 2013 UL.COM/NEWSCIENCE
NEW SCIENCE FIRE SAFETY ARTICLE INNOVATING FIRE ATTACK TACTICS SUMMER 2013 UL.COM/NEWSCIENCE NEW SCIENCE FIRE SAFETY OVERVIEW UL s dedicated team of scientists, engineers and researchers is creating New
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
RESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK PERRONET HOUSE PRINCESS STREET LONDON SE1 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
CAREER OPPORTUNITY Brunswick Fire Department
CAREER OPPORTUNITY Brunswick Fire Department Job Title: Firefighter (24/48 hour schedule) Hiring Rate: $8.85 non certified (annual base approximately $27,030) $9.29 certified (annual base approximately
Warehouse Checklist. Warehouse Construction
PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage
EMERGENCY RESPONSE TEAMS AND INCIDENT MANAGEMENT SYSTEMS
GAP.1.7.0.2 A Publication of Global Asset Protection Services LLC EMERGENCY RESPONSE TEAMS AND INCIDENT MANAGEMENT SYSTEMS INTRODUCTION A key part of an emergency response system is to create the necessary
Transformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
FLA S FIRE SAFETY INITIATIVE
Improving Workers Lives Worldwide FLA S FIRE SAFETY INITIATIVE Preventing fires and saving lives by empowering workers and factory managers SCENARIO 1 OCCURS AT FACTORY ABC, WHICH HAS NOT IMPLEMENTED NECESSARY
Operating, Installation, and Maintenance Instructions
ELKHART BRASS MFG. CO., INC. 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 Operating, Installation, and Maintenance Instructions RAM Personal Portable Monitor
U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live!
U.S. Department of Housing and Urban Development Office of Public and Indian Housing A Good Place to Live! Introduction Having a good place to live is important. Through your Public Housing Agency (or
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
Fire detection, alarm, and suppression systems are installed to:
Fire detection, alarm, and suppression systems are installed to: Notify occupants to escape a fire Summon emergency responders Initiate suppression systems Supervise suppression systems for operational
MOTOR FUEL DISPENSING SAFETY
STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.
Housing Quality Standards Inspection Checklist
Housing Quality Standards Inspection Checklist To prevent delays, the R.T.A. must be complete and upon submission the unit must be in move in condition or an inspection will not be conducted. A Fair Housing
FIRE SAFETY PLAN 123 TOWER STREET CAMBRIDGE, ONTARIO
S A M P L E FIRE SAFETY PLAN 123 TOWER STREET CAMBRIDGE, ONTARIO This sample Fire Safety Plan can be used to assist in developing a Fire Safety Plan for your building. TABLE OF CONTENTS 1. HUMAN RESOURCES
Applications for building permits will not be reviewed until all of the required information has been submitted.
NOTICE: Applications for building permits will not be reviewed until all of the required information has been submitted. Once all items are submitted a minimum of ten (10) working days are required to