Uptime Institute Annual Report: Data Center Density
|
|
|
- Edmund Jackson
- 10 years ago
- Views:
Transcription
1 U P T I M E I N S T I T U T E, L L C Uptime Institute Annual Report: Data Center Density By Vince Renaud, PE and Matthew Mescall, CFM Copyright 2011 by Uptime Institute, LLC 20 West 37th Street 6th Floor New York, NY All rights reserved. The Uptime Institute s (Institute) publications are protected by international copyright law. The Institute requires written requests at each and every occasion that the Institute s intellectual property or portions of the Institute s intellectual property are reproduced or used. The Institute copyright extends to all media paper, electronic, and video content and includes use in other publications, internal company distribution, company Web sites and marketing materials, and handouts for seminars and courses. For more information, please visit to download a Copyright Reprint Permission Request Form., LLC
2 INTRODUCTION Data center owners and operators have been sternly cautioned about the imminent and meteoric rise in the power density of their computing equipment. And, the drastic consequences on the cost and complexity of power and cooling infrastructure to accommodate racks as high as 30 kw each. In Uptime Institute field experience, pockets of highdensity equipment have been evident, but not pervasive in many data centers. Based upon this apparent divergence between the longstanding dire predictions and limited deployments, the Uptime Institute determined to confirm actual owner experience in operational, highavailability data centers. Accordingly, members of the Uptime Institute Network in North America and EMEA participated in a survey on power density in their data centers. SURVEY BASE Information was received on a total of 59 data centers: 46 in North America and 13 in Europe. Some data centers reported their information by distinct areas (rooms, pods, etc.), which provided more granular detail. The entire survey base was 1,911,000 ft 2 (177,536 m 2 ) and consumed 70.9 MW of electricity. The North American data centers totaled 1,522,000 ft 2 (141,397 m 2 ) of computer room and consumed 54.2 MW of electricity. The European data centers totaled 389,000 ft 2 (36,139 m 2 ) of computer room and consumed 16.7 MW of electricity. The data centers ranged in size from 2,400193,000 ft 2 (22317,930 m 2 ). The median size was 29,000 ft 2 (2,694 m 2 ), with the middle 50% of data centers (25 th 75 th percentile) between 13,60039,900 ft 2 (1,2643,707 m 2 ). By industry, 23 data centers were operated by Financial Services companies, 11 by IT, 5 by Healthcare and Retail, 4 Energy, 3 Colocation, and the remaining industries had 1 or 2 sites. SURVEY PARAMETERS For this survey, the area component of density is defined as the computer room floor (raised or slab) and includes the IT equipment, air handling equipment that resides in the space, and electrical distribution in that space. However, since the measurement of this space can vary from one company to another based on perceived definition or configuration differences (e.g., air handlers outside the computer room wall), Uptime Institute focused on the metric kilowatts per rack. To determine this, the survey asked respondents to clarify the makeup of the data center infrastructure. Acknowledging that many data centers contain a mix of server racks, mainframes, disk and tape storage, and network equipment, the survey provided an opportunity to breakout these types. Included in the rack quantity were populated server racks, and the equivalent measurement for mainframes and standalone disk storage. The survey excluded tape libraries and silos, and racks that were not populated or only contained network patch panels due to comparatively low power use. Additionally, some respondents answered the survey by dividing their data center into smaller sections (highdensity servers vs. tape vs. mainframes, etc.). This allows for a more granular analysis of the maximum average power use per rack. SURVEY FINDINGS The median designed power density was 68 W/ft 2 (730 W/m 2 ), with the middle 50% ranging from 5195 W/ft 2 (5521,021 W/m 2 ). The median of the current density (power currently used) was 41 W/ft 2 (437 W/m 2 ), with the middle 50% ranging from 2748 W/ft 2 ( W/m 2 ). A few smaller data centers were purpose built for highdensity racks and had design densities over 150 W/ft 2 (1,615 W/m 2 ). When taken as a whole, the responding data centers are using 54% of their available power, with the middle 50% using between 4573% of capacity. The following charts show the distribution of designed power density and data center size. Although the data shows a general trend that data centers designed for a higher density are smaller than lowdensity data centers, this only holds at the higher end of the design density data. That is, only the high end of the data center size and the high end of the design density are consistent with the general trend. Note that 49 of the 59 data centers are less than 50,000 ft 2 (4,645 m 2 ) and have densities below 150 W/ft 2 (1,615 W/m 2 ), with a wide range of size and density combinations. Figure 1A displays the data in International System of Units (SI) and U.S. units with axes aligned to show the conversion. Figures 1B and 1C show the data in SI and U.S. units separately. 2
3 Design Density vs. Data Center Size (U.S. & SI units) Data Center Size (m 2 ) ,000 10,000 15,000 20,000 Design Density (W/ft 2 ) ,500 4,000 3,500 3,000 2,500 2,000 1,500 Design Density (W/m 2 ) 100 1, , , , , ,000 Data Center Size (ft 2 ) Figure 1A 5,000 Design Density vs. Data Center Size (SI units) 4,500 4,000 3,500 Design Density (W/m 2 ) 3,000 2,500 2,000 1,500 1, ,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 Data Center Size (m 2) Figure 1B 3
4 450 Design Density vs. Data Center Size (U.S. units) Design Density (W/ft 2 ) , , , , ,000 Data Center Size (ft 2 ) Figure 1C The survey revealed that the highest average power use was a data center in the United States at 9.2 kw/rack. However, this was reported by a small (13,400 ft 2 ; 1,245 m 2 ), highdensity data center that appears to be built for that purpose. For all respondents, the middle 50% ranged from kw/rack with a median of 2.4 kw/rack. Maximum kw per rack Max: 9.2 kw/rack Middle 50%: 1.9 to Sites Figure 2A 4
5 When analyzing the data as a whole by combining separately reported pods or modules the averages declined. The maximum remained the same because that data center did not report by sections. The median declined to 2.1 kw/rack while the middle 50% range also declined to kw/rack. Average kw per rack Max: 9.2 kw/rack Middle 50%: 1.7 to 2.7 Sites Figure 2B The survey facilitated an analysis of power use per rack by industry. Breaking the sites down by industry, 23 were in Financial Services, 11 in IT, 5 in Healthcare and Retail, 4 Energy, 3 Colocation, and the remaining industries had 1 or 2 sites. The previously discussed 9.2kW/rack data center was the only entry for the Transportation industry, which leads all industries. The industries with the next highest maximum average power use per rack were Healthcare at 7.8 kw/rack, Aerospace at 7.5 kw/rack, and Financial Services at 4.8 kw/rack. The two industries with the highest average power use per rack were Retail and Energy with 4.1 kw/rack. All other industries were less than kw/rack. The complete results are shown in Figure 2C. 5
6 kw per rack by Industry Maximum Average kw per rack Figure 2C When average kw/rack was compared to the size of the data center, the distribution was similar to the design density vs. data center size. Avg kw/rack vs. Data Center Size (SI units) Avg kw/rack 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 Data Center Size (m 2 ) Figure 2D 6
7 Avg kw/rack vs. Data Center Size (U.S. units) Avg kw/rack 0 50, , , , ,000 Data Center Size (ft 2 ) Figure 2E To complement the energy use per rack, the survey gathered responses about the utilization of the racks, based on the number of rack units occupied. We found that 88% of respondents are utilizing more than half of their rack units. The middle 50% of respondents were utilizing between 5896% of their rack units. CONCLUSION One of the core objectives of this survey is to provide ground truth perspective and data to owners and operators as they plan for data center infrastructure to meet evolving IT power and cooling needs. Acknowledging that the data center industry evolves quickly, the 2011 findings are that 20kW racks are a reality for a typical data center, but not to the degree forewarned. Such high density is not pervasive enough to have a widespread impact on most of the surveyed data centers. Although respondents existing racks appear to be well utilized, there is still room to add equipment. As these rack units are filled, the power use per rack will increase. Assuming a trend that rack units are filled with higher powered servers that are well utilized, the Uptime Institute anticipates an increase in kw/rack in our next survey. Nevertheless, this survey demonstrates that the expectation for 20kW racks throughout is not manifested. In fact, at an average density of 2.1 kw per rack, this is far from being true. In an effort to provide trending data, the Institute will perform this survey annually. 7
8 , LLC 20 West 37th Street, 6th Floor, New York, NY Fax: uptimeinstitute.org professionalservices.uptimeinstitute.com Uptime Institute, LLC UI
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27. Tom Brey, IBM Operations Work Group
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27 Tom Brey, IBM perations Work Group 1 Virtualization Two Steps WP #19 USING VIRTUALIZATIN T IMPRVE DATA CENTER EFFICIENCY
How To Power And Cool A Data Center
Architecting the Green Data Center Viktor Hagen Field Business Development Data Center & High Performance Computing 1 Where we are Today Environmental sustainability is a major global trend for the 21st
Executive Summary. Metro Capacity
Executive Summary The worldwide colocation data center market continues to grow at a steady rate in 2015. While key Asian markets and some secondary markets have outpaced global average growth rates in
Calculating Space and Power Density Requirements for Data Centers
Calculating Space and Power Density Requirements for Data Centers White Paper 155 Revision 0 by Neil Rasmussen Executive summary The historic method of specifying data center power density using a single
NetApp Data Center Design
NetApp Data Center Design Presentation for SVLG Data Center Efficiency Summit November 5, 2014 Mark Skiff, PE, CEM, CFM Director, IT Data Center Solutions Data Center Design Evolution Capacity Build Cost
THE WORLD S MOST EFFICIENT DATA CENTER
THE WORLD S MOST EFFICIENT DATA CENTER HP POD 240a Ed Turkel Manager, WW HPC Marketing Hyperscale Business Unit 2011 Hewlett-Packard Development Company, L.P. The information contained herein is subject
Simplifying Data Center Design/Build
Simplifying Data Center Design/Build A new approach to deliver speed, cost, and performance (availability, efficiency, scalability) Eduard Bodor Data Center Business Development Manager for Central and
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
Data Center Site Infrastructure Tier Standard: Topology
U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2010 by Uptime Institute, LLC 20 West 37th
Data Center Equipment Power Trends
Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data
Cody Park One of Ark s high integrity data centre campus sites
UKC COMMERCIAL Cody Park One of Ark s high integrity data centre campus sites Ark is a privately held company that design, build, operate and finance third party data centre solutions tailored to meet
Colocation and Cloud Hosting Solutions. Build a strong and efficient physical infrastructure that delivers service reliability and profitability
Colocation and Cloud Hosting Solutions Build a strong and efficient physical infrastructure that delivers service reliability and profitability 2 Dependability and Deployment Speed that Improves Your Bottom
Fall 2014 Data Center Users Group Survey Results October 2014
Fall 04 Data Center Users Group Survey Results October 04 The Data Center Users Group (DCUG) is a collection of influential data center, IT and facility managers formed by Emerson Network Power. Founded
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
Advantages of Micro-container-based Data Center Infrastructure Simon Rohrich, Founding Member, Technology Evangelist
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Elliptical Mobile Solutions Advantages of Micro-container-based Data Center Infrastructure Simon Rohrich, Founding Member, Technology Evangelist This
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Stephen Worn Global CTO & Board Director DatacenterDynamics
Infrastructure, Technology & Investment Trends: Which Global Gateways are best placed to lead into the Digital World? HKEx Eco-System Conference March 20 2014 Stephen Worn Global CTO & Board Director DatacenterDynamics
FEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
ITNW 2305 Network Administration COURSE SYLLABUS
COURSE NUMBER AND TITLE: ITNW 2305 Network Administration ITNW 2305 Network Administration COURSE SYLLABUS COURSE (CATALOG) DESCRIPTION: Topics include network components, user accounts and groups, network
The Next-Generation Virtual Data Center
The Essentials Series: Managing Workloads in a Virtual Environment The Next-Generation Virtual Data Center sponsored by by Jaime Halscott Th e Next Generation Virtual Data Center... 1 Be nefits of Virtualization
Realizing the IT Management Value of Infrastructure Management
The Essentials Series: Infrastructure Management Realizing the IT Management Value of Infrastructure Management sponsored by by Chad Marshall Realizing the IT Management Value of Infrastructure Management...1
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
How To Test A Theory Of Power Supply
A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Avoid Rolling the Dice: Solving the CIO s Data Center Dilemma with Colocation
EXECUTIVE REPORT Avoid Rolling the Dice: Solving the CIO s Data Center Dilemma with Colocation Overview CIOs today face a litany of challenges and risks when it comes to meeting the goal of making the
How green is your data center?
Siemens Answers: Sustainable Future How green is your data center? Istanbul June 01, 2010 Agenda 1 Solution 2 Siemens Data Center Approach 2 Designing with multiple power density zones can reduce energy
Redundancy and Reliability for an HPC Data Centre
Available online at www.prace-ri.eu Partnership for Advanced Computing in Europe Redundancy and Reliability for an HPC Data Centre Erhan Yılmaz* 1 Ladina Gilly** 2 * National High Performance Computing
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
The 7 Principles of Data Center Cost Metrics
235 Montgomery, Suite 1017 San Francisco, CA 94104 (415) 373-0673 www.ramprate.com The 7 Principles of Data Center Cost Metrics The Cost Evaluation Methodology Vendors Wish You Didn t Know By Alex Veytsel
Common mistakes in datacentre planning
Common mistakes in datacentre planning White Paper Last edited: March 2013 Document Control Document Information Title Author Common mistakes in datacentre planning Nick Ewing This document is based upon
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs
WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level
Increasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
When Does Colocation Become Competitive With The Public Cloud? WHITE PAPER SEPTEMBER 2014
When Does Colocation Become Competitive With The Public Cloud? WHITE PAPER SEPTEMBER 2014 Table of Contents Executive Summary... 2 Case Study: Amazon Ec2 Vs In-House Private Cloud... 3 Aim... 3 Participants...
When Does Colocation Become Competitive With The Public Cloud?
When Does Colocation Become Competitive With The Public Cloud? PLEXXI WHITE PAPER Affinity Networking for Data Centers and Clouds Table of Contents EXECUTIVE SUMMARY... 2 CASE STUDY: AMAZON EC2 vs IN-HOUSE
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
UK regional peering Northern Ireland. Mike Higgins
UK regional peering Northern Ireland. Mike Higgins 5NINES Global LLP NORTHERN IRELANDS FIRST MAJOR CARRIER NEUTRAL DATA CENTRE Total 100M Investment Total Investment Investment level ~ 100M; Dual Data
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Data Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server
Data Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server Data Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server High availability for lower expertise
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
How Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that
Distributing Power to Blade Servers
Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily
How High Temperature Data Centers and Intel Technologies Decrease Operating Costs
Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features
Understanding How Cabinet Door Perforation Impacts Airflow by Travis North
& design deployment The first step in determining the proper perforation for an application is to understand the airflow requirements of the equipment that will be used in the cabinet. Understanding How
LEVEL 3 DATA CENTER SERVICES IN SAN FRANCISCO HOUSE POWER-INTENSIVE APPLICATIONS AND SUPPORT BUSINESS CONTINUITY
LEVEL 3 DATA CENTER SERVICES IN SAN FRANCISCO HOUSE POWER-INTENSIVE APPLICATIONS AND SUPPORT BUSINESS CONTINUITY THE SCALE TO SUPPORT GLOBAL ENTERPRISE IT THE SCALE TO SUPPORT FLEXIBLE ENTERPRISE IT It
Data Center Colocation Build vs. Buy
Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for
The ROI of Tape Consolidation
The ROI of Tape Consolidation NOTICE This white paper may contain proprietary information protected by copyright. Information in this white paper is subject to change without notice and does not represent
Building a data center. C R Srinivasan Tata Communications
Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
Cooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
Energy Efficiency and Availability Management in Consolidated Data Centers
Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal
Determining Total Cost of Ownership for Data Center and Network Room Infrastructure
Determining Total Cost of Ownership for Data Center and Network Room Infrastructure White Paper #6 Revision 3 Executive Summary An improved method for measuring Total Cost of Ownership of data center and
What is a Data Center? Racks and Servers. At The Click Level. Equinix - Key Facts
What is a Data Center? Internet Data Centers: End User & Developer Requirements Janice Fetzer KC Mares A highly specialized, reliable environment to support computers, network and data storage devices
What is a Datacenter?
What is a Datacenter? Telecom Room Primarily Cross Connect Equipment and switches. Computer room A room whose primary function is to house computer equipment. (Servers, Storage) 5 or less cabinets Small
Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
Increasing Data Center Efficiency through Metering and Monitoring Power Usage
White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency
Critical Infrastructure for the World s Leading Data Centers
Critical Infrastructure for the World s Leading Data Centers 2 YOU MAY KNOW US BY OUR BRAND NAMES THE EXPERTISE OF MANY. THE POWER OF ONE. Nortek Air Solutions provides critical infrastructure for the
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
Model Manage Monitor Maximize your Data Center
NetZoomDC is the most feature rich, fully-scalable, enterprise Data Center Infrastructure Management (DCIM) software application. It enables data center professionals to Model, Manage, Monitor and Maximize
Data Center Solutions - The Containerized Evolution
Data Center Solutions - The Containerized Evolution Power IT Cooling 7 th Green Connected World Tsikogias Thanassis Data Centers Solutions Architect, IT Business Athens 2015 1 We are the global specialist
DATA CENTRES POWERED BY EXCEL
DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,
Research Data Storage, Sharing, and Transfer Options
Research Data Storage, Sharing, and Transfer Options Principal investigators should establish a research data management system for their projects including procedures for storing working data collected
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment