1 Application program for pco Graphic Standard Air-Conditioning units with humidifier Graphic display Manual version: 1.0-2/4/97 Program code: EPSTDECG0A Rif.: 98EM
2 MICROPROCESSOR REGULATION AND CONTROL SYSTEM FOR AIR CONDITIONING UNITS: Introduction to the regulation system: This system can be installed directly on the air handling and conditioning units. SYSTEM FEATURES - Temperature and relative humidity regulation. - Control and signal of the condition of all components in the system - Possibility of selecting and modifying regulation parameters. - Signal of any anomaly of controlled devices through acoustic (BUZZER) and visual (ALARM MASK) warning. - Communication interface USER - MACHINE (KEYPAD- DISPLAY) - Possibility of connecting to a remote supervisor through serial communication RS422. pag.1
3 DOCUMENTATION INDEX: 1 - INSTALLATION GUIDE DESCRIPTION OF THE CONTROLLER AND ITS COMPONENTS CONTROL BOARD List of components: USER INTERFACE...6 TERMINAL ON STANDARD PCO (COD.PCOT00PGH0)...6 MOUNTING OF THE TERMINAL...8 PANEL MOUNTING...8 WALL MOUNTING...8 ELECTRICAL CONNECTION...8 PROGRAM EPROM INSTALLATION pco KEYPAD WHAT TO DO IF HARDWARE: USER INTERFACE POWER SUPPLY INPUTS/OUTPUTS pco OPTIONAL BOARDS INSTALLATION FIRST INSTALLATION CONFIGURATION GUIDE SET-POINT - DIFFERENTIAL - DEAD ZONE STEP DEFAULT VALUES TEMPERATURE CONTROL DIAGRAMS...25 TWO-COMPRESSOR UNIT WITHOUT ENERGY SAVING OPTION...26 TWO-COMPRESSOR UNIT WITH ENERGY SAVING OPTION MANAGEMENT OF COMPRESSORS ENERGY SAVING COMPRESSOR UNIT WITHOUT ENERGY SAVING OPTION COMPRESSOR UNIT WITH ENERGY SAVING OPTION...29 TWO-HEATER UNIT...29 ONE-HEATER UNIT HUMIDITY CONTROL DIAGRAMS HUMIDIFIER CONTROL...33 GENERALITIES: CONNECTION DIAGRAM OF THE PCO INTERFACE TO THE HUMIDITY OPTIONAL CARD Description of humidifier parameters C0-C1 PARAMETER SELECTION TABLES...36 C0 and C1 for single-phase cylinders F200MA with a nominal production ranging from 1 to 3Kg/h :...36 C0 and C1 for three-phase cylinders F400TA with a nominal production ranging from 3 to 5 Kg/h:...36 C0 and C1 for three-phase cylinders E400TA with a nominal production ranging from 8 to 13Kg/h:...36 C0 and C1 for three-phase cylinders I400TW with a nominal production ranging from 23 to 42 Kg/h: PROGRAMMING OF THE HUMIDIFIER...38 Selection of the type of humidifier...38 Regulation of humidity and production...38 Activation of the humidifier...38 Monitoring of the steam production and of the values that typical of the humidifier MANAGEMENT OF THE HUMIDIFIER ALARMS USER GUIDE...41 pag.2
4 3.1 MASK ALARM MASKS COMPONENTS AND CODES...62 pag.3
5 1 - INSTALLATION GUIDE 1.1-DESCRIPTION OF THE CONTROLLER AND ITS COMPONENTS - CONTROL BOARD The main board is the core of the controller. It is made of # a section which includes the microprocessor and the memory for the machine control algorithm; # an I/O section which allows interfacing with controlled devices by means of a plug-in terminal. # a section devised for interfacing with supervisory network and terminal which can be installed in a remote position. The control board represents the core of the system as it contains the microprocessor which performs the control algorithm and the user interface management. This board is connected to a pco terminal and to any options. 1 6 G G0 J17 IC3 RS422 4 J28 J29 7 B8 J J19 B7 3 J15 J14 B6 AVSS B5 B4 5 VG0 VG1 Y1 Y0 ID11 (220V) ID11 (24V) ID11R ID12R ID12 (24V) ID12 (220V) NO11 C11 NC11 J20 J21 R11 8 J2 J3 J4 AVSS B3 B2 AVSS B1 IDCM2 ID10 ID9 ID8 ID7 ID6 IDCM1 ID5 ID4 ID3 NO10 C10 NC10 J22 R10 R1 ID2 ID1 C1 NO1 NO9 C9 NC9 R9 R2 J5 C2 NO2 NO8 C8 R8 R3 C3 NO3 NO7 C7 R7 R4 C4 NO4 NO6 C6 J24 R6 R5 J6 C5 NO5 NO13 C13 R13 R12 C12 NO12 - List of components: (1)24 Vac supply cable (2)Telephone cable connector for terminal connection (RS485) or for local network connection (3)Optional Clock board (4)Optoisolated RS422 board for serial line connection for supervision and telemaintenance (5)Pin strip to select B5 and B6 voltage or current inputs (6)Eprom with the programme (7)Pin strip to select B28 and B29 voltage or current inputs (8)Relay outputs Rxx: No: Nc: C : Connectors for digital relay outputs Normally open contact Normally close contact Common reference for contacts pag.4
6 ID : IDCM: Bx : AVSS: Yx: VG1/0: Digital inputs Common reference for digital inputs Analogue input Reference for analogue outputs Analogue outputs 24V A.C. Analogue outputs power supply pag.5
7 - USER INTERFACE GENERAL REMARKS The pco terminals with graphic display devices are available in three different models and all of them operate with a main board of the PCOB000A21 and PCOB000B21 type, each one provided with the PCOADR**** addressing card. The backlighting of every display allows to read them even with a faint lighting. The programmability of the device through the EasyTools package permits the realization of customized programs both for the air conditioning and the commercial refrigeration. Terminal on standard pco (cod.pcot00pgh0) Room 1 Tem p on-off alarm enter Display: Buttons: of translucid LEDs: Case: LED backlighting display Dot number : 128 x 64 Wide range of temperature no. 10 mechanical buttons protected by polycarbonate + no. 5 buttons made silicone rubber no. 13 signaling LEDs The same plastic case as for the standard pco terminal Panel/wall mounting (See pcouser Guide for details) The terminal allows exchange of information by means of a LCD which displays the values of all controlled parameters, selected set-points, alarm thresholds and in general all data concerning the controlled variables in the specified formats. Moreover, the display will show particular messages any time an alarm condition occurs. A keypad allows the setting of configuration parameters such as set-points, alarm thresholds, alarm activation delays, etc.... The visible rubber keys, which can be seen and pressed even when the front door is closed, are the most important and the most used ones, above all when the machine is ON.The above quoted keys are the following: -1- ON/OFF key; -2- Buzzer silencing and alarm deactivating key; -3- UP key; -4- DOWN key; -5- ENTER key pag.6
8 Main terminal board The board supports the microprocessor, memories and the eprom containing the management application program of the display and keyboard. It also includes the optional serial-card connector for printer control (Carel code PCOSERPRN0) and the one for the card containing the clock and the 32K of EEPROM. Figure 1 1: Connector to the inverter and signal-control card for the display 2: Connector for optional printer-card 3: Telephone-connector for terminal connection to the pco main board (PCOB*21) or to the T- connector TCONN6J000 if the connection is in the plan local area network (see plan UserGuie0 4: Alarm acoustic-signaling buzzer 5: Metalized fastening holes 6: Connector for connection to the additional printer card 7: Eprom program and mounting direction/sense 8: Connector for EEprom card,dip-switch, clock 9: Power supply connector pag.7
9 MOUNTING OF THE TERMINAL The model equipped with plastic container (cod. PCOT00PGH0) has been designed for the panel and wall mounting. The drilling template, in the case of panel mounting, must have the following dimensions: 167x108mm. For the installation, comply the following instructions: Panel mounting Figure references on the side 1. Back cover 2. Panel 3. Front cover 4. Drilling templates (window tolerance: mm relating to the dimensions shown in the figure) 5. Gasket for the front cover 6. Gasket for the back cover Panel maximum thicknessis 6mm. unscrew the two screws placed on the terminal back cover and remove the cover lean the front on the panel frontal part Fit in the cover from behind carefully matching the two holes in the back cover with the two holes of the frontal cover Screw again the screws Finally carry out the necessary electrical connections Wall mounting Wall mouting involves the use of an appropriate fastening stirrup and of a 3-module standard switch wall-box in order to allow the cable passage. Fasten the stirrup (1) to the wall (3) by means of the screw (2); fit in the back of the instrument into the stirrup. Finallly carry out the required electrical connections. Electrical connection pag.8
10 Connect the telephone cable (cod. S90CONN00*) coming from the power card (cod..pcob000*21) to the appropriate socket; DO NOT connect any power supply to the screw terminal block indicated at the point 9 of the Figure 1. Directly from the keypad it is possible to gain access to the main parameters or to some parameters loops. The " AL " message, on the upper right corner of the display, indicates an alarm condition and allows the access to the masks where the exact type of alarm is identified (for further information see below - ALARM key) All reading and setting values are displayed according to a tree structure the user can enter by means of the controller keypad. PROGRAM EPROM INSTALLATION All information on the graphic display (character fonts, graphs, diagrams and various symbols to be displayed ) are produced by an application program contained in the eprom, to be positioned as shown at point 7 of the Figure 1. To install the eprom, turn the power supply OFF remove the screen card (see previous page) or the serial printer optional card (if present), by unscrewing the respective screws; mount the eprom, being careful to place the reference notch in the same direction as that one indicated by the serigraph (see point 2 Errore. L'origine riferimento non è stata trovata.) infact wrong connections destroy the eprom. Maximum care is required when handling the eprom: do not bent the pins and insert them carefully into the appropriate socket located on the main board, handling the component on the areas where they are not present before touching the eprom, touch a grounding in order to discharge the possibly accumulated electostatic energy (do not touch other devices supplied with power) to remove the component from the socket, use a small screwdriver, avoiding to damage the printed circuit tracks or some other adjacent components. once the eprom has been inserted, mount the card that serves as a screen or the possible printer optional card before placing the cover and operate again the terminal. Socket connection and disconnection of the eprom must always be carried out with the terminal not being power supplied.. With reference to the picture : - pco KEYPAD GENERAL FUNCTIONING: The first 10 keys, the ones which disappear when closing the front door, are meant to allow the user to perform any kind of procedures from programming to parameters simple display. The blue and red keys have not been used. Their function is to select the required loop (or chain of masks). The 5 rubber keys are used for programming and for parameters display. Once completed the procedures in a loop, which has been selected by pressing a key, the user only has to press another key to go at once to another loop. The keys share the following peculiar features : pag.9
11 -1- A green led next to each key indicates which key has been selected. The led remains ON as long as that loop of masks is being used. The led is important in case the user does not remember which loop has been selected. It is important to point out that only one out of the 8 grey keys can be ON, therefore activation of one automatically deactivates the others. Moreover, the user must remember that the leds will never be all OFF, because the mask menu is always on display; therefore, the led next to the menu key is ON even if no procedure is being performed or after a RESET due to a blackout: menu' -2- In the programme itself there is an automatic function which brings back on display the menu mask and, as a consequence, the led next to the menu key will be turned ON again. If, for example, the last procedure has been the setting of the printer parameters, for some seconds the last selected mask will remain on display and the led next to the printer key will remain ON: Once the selected time has elapsed, the led next to the printer key will be turned OFF, the one next to the menu key will be turned ON and the temperature and humidity values will be displayed. menu' -3- Each loop of masks follows an order. This means that by pressing a key the first mask of the corresponding loop will be displayed. If the user then moves to other masks of the loop and by chance presses again the same key, the first mask will be displayed again. MENU KEY menu' Gives information on the temperature and humidity values measured by the selected probes (the temperature probe is the only one to be always present and not selectable). The procedure to be followed is: - press the MENU key once Result of procedure: - the display will show the mask which indicates ambient temperature, ambient humidity, time, date and condition of the machine. Procedure to be followed: - press the Up and Down keys Result of procedure: - cyclic visualisation of the loop of probe reading masks. MAINTENANCE KEY Allows visualisation and clearing of the total functioning hours of the main devices. Procedure to be followed: - press the Maintenance key once Result of procedure: - the display will show the working hours of the first three selected devices. Procedure to be followed: - press the Up and Down keys Result of procedure: pag.10
12 - cyclic visualisation of the masks which indicate for each device (heaters excluded) the activity hours and the setting of threshold hours and hour clearing. N.B. Reset of functioning hours: it is necessary to press ENTER to move the cursor to the "NO" sign. To reset the machine it is necessary to keep the Up or the Down key pressed for a couple of seconds until the YES sign appears. At this point wait for the "NO" sign to be displayed again. PRINTER KEY Allows the user to manage the printer and to select its required parameters. Procedure to be followed: - press the Printer key once. Result of procedure: - the display will show a mask for the immediate setting of printing by simply pressing Enter. Procedure to be followed: - press the Up and Down keys. Result of procedure: - activates the cyclic repetition of masks for immediate printing setting, for cyclic printing and, if the latter has been activated, of masks for the setting of cyclic printing interval. I/O INPUT/OUTPUT KEY Allows visualisation of the status of interface board inputs/outputs. Procedure to be followed: - press the Input/Output key once. Result of procedure: - the display will show the status of all digital inputs. Procedure to be followed: - press the Up and Down keys. Result of procedure: - activates the repetition of masks which indicate the status of digital outputs, analogue outputs and of digital inputs. Analogue inputs are already read in the Menu branch, therefore they are not visualised here. N.B. Since digital inputs can manage different devices according to the settings effected in the manufacturer branch, I/O masks will indicate the selected device next to the output number in question. CLOCK/TIME ZONES KEY Allows the setting of time and date as well as the management of time zones. Procedure to be followed: - press the Clock key once. Result of procedure: - the display will show a mask for the setting of the date (day, month, year). Procedure to be followed: - press the Up and Down keys. Result of procedure: - repetition of the masks for the management of time, for the setting of the password to gain access to the time zones branch, and again for the setting of the date. pag.11
13 Procedure to be followed: - press the Enter key when the display shows the Password selecting mask. Result of procedure: - access to the field where the correct password (which is the same as the user password, that is 1234) is to be selected. If the password has been correctly selected, by pressing Enter you will move to the time zones branch, otherwise you will return to the clock loop. Only for Time Zones setting Once the above quoted procedures have been followed, you reach a mask asking if you want to select the time zones: if so, the following masks will be used to select times and set-points for temperature and humidity, otherwise you will go back to the first mask of the clock branch. SET KEY set Allows the setting of set-points for ambient temperature and humidity regulation. Procedure to be followed: - press the Set key once. Result of procedure: - the display will show the mask for temperature set-point setting. Procedure to be followed: - press the Up and Down keys. Result of procedure: - visualisation of the mask for humidity set-point setting. PROGRAMMING KEY prog Allows access to system parameters programming masks in all those functions the user need to personalise regulation. Procedure to be followed: - press the Prog key once. Result of procedure: - the display will show the user password (1234) selecting mask. If the password has been correctly selected, by pressing Enter you will reach the user branch; otherwise, you will remain in this mask. Procedure to be followed: - press the Up and Down key more than once. Result of procedure: - visualisation of a series of masks for the setting of all values necessary to humidity and temperature control and for the setting of set-points and differentials of connected devices.? INFO KEY? info Allows visualisation of the software version. Procedure to be followed: - press the Info key once. Result of procedure: - the display will show the software version. prog pag.12
14 MANUFACTURER KEYS menu' Allow access to the manufacturer password selecting mask which, if correctly selected (0123), enables entering the branch for activation of probes, connected devices and their main functions, and for default configuration set-up (standard values). Procedure to be followed : - press at the same time the Programming and the Menu keys for a couple of seconds. Result of procedure: - the display will show a mask for password setting. If the password has been correctly selected, by pressing the Enter key you will gain access to said branch, otherwise you will remain in the password selecting mask. ON/OFF KEY Allows machine turning ON and OFF. Procedure to be followed: - press the On/Off key once. Result of procedure: -the led indicator under the On/Off key turns on : Unit ON. -the led indicator under the On/Off key turns off : Unit OFF. ALARM KEY Allows silencing of the buzzer which has been activated in case of alarm and resetting of alarms as soon as the reasons that caused them disappeared. Procedure to be followed: - press the Alarm key once. Result of procedure: - if before following this procedure there are no active alarms (led under Alarm key OFF, buzzer OFF, no alarm messages on display), the display will show a mask informing of the absence of any alarms. The mask will disappear if another key is pressed. - if before following this procedure there is at least one active alarm (led under the Alarm key ON, buzzer ON, alarm message on display), the pressing of the Alarm key silences the buzzer and on display appears the exact message of the alarm which can be the only one or the first of a series. At this point, it is possible to check if there are more than one active alarms and in that case which kind of alarms have been activated. It is sufficient to press the Up or the Down keys. In this case if there are more than one active alarms a list of alarm messages will be displayed. - if before following this procedure the buzzer has been silenced and the display shows an alarm mask, two are the possibilities: if the reasons which caused the alarms have disappeared, the led indicator under the Alarm key will turn OFF and the programme will automatically return to the menu mask (this function is called Clear); if the reasons which caused the alarms have not disappeared the buzzer will be reactivated. - if before following this procedure the buzzer has been silenced and the display shows any masks except an alarm one, the programme will automatically enter the alarm branch where it is possible to select the Clear function. UP/DOWN KEYS Allow to move upwards or downwards in the masks of the loop. If used after pressing the Enter key, they allow selection of the parameter values. pag.13
15 (1) If a loop is composed of masks 1, 2, 3, 4, and 5 and mask 1 is on display, by pressing the Up key more than once the masks will scroll following the order: 1, 2, 3, 4, 5, 1 etc... By pressing the Down key more than once the masks will scroll following the order: 1, 5, 4, 3, 2, 1 etc... (2) If, with reference to the same example, mask 3 is on display and the Enter key is pressed, the cursor will jump from position 0,0 to the numeric field. By pressing the Up key the number will increase; by pressing the Down key the number will decrease. ENTER KEY Allows parameter setting (through the Up and Down keys) and is used to confirm data after setting. (1) If, for example, the display shows a mask with the message: Temperature Setpoint Setting, by pressing Enter the cursor will go from 0,0 position to the numeric field where a digit like (20 ºC) is displayed. By means of the Up and Down key it is possible to modify this value. (2) By pressing Enter again the cursor will go back to 0,0 and at the same time the modified value will be memorised.\ pag.14
16 - WHAT TO DO IF THE UNIT DOES NOT START Led of the ON/OFF key is turned OFF, the display is OFF, other leds turned OFF. Check : a. that power supply is present b. that there are 24 VAC of power supply voltage at the secondary coil transformer ( VAC) c. the correct insertion of 24 VAC power supply connector in the proper socket. WHEN TURNING ON THE INSTRUMENT YOU FIND: alarm led indicator ON, display with no or random messages buzzer ON. Check : a. that the Eprom has been inserted with the correct polarity b. that the Eprom pins have not been bent on inserting the Eprom itself c. that the microprocessor chip has not been damaged: in that case contact the assistance. WRONG INPUT SIGNALS READING Check: a. that the connection of probes cables is in accordance with instructions b. that probe signals pass on cables installed at a sufficient distance from possible excessively disturbing sources (power cables, contactors, high-voltage cables and cables with high inrush ampere consumption connected devices) c. connections between interfaces and controller (flat cables) d. correct power supply of interfaces and probes DAMAGED EPROM ALARM a. Contact the assistance THE CONTROLLER ACTIVATES THE WATCH-DOG FUNCTION, THAT IS IT TURNS ON AND OFF AS FOR A POWER SUPPLY FAILURE OR ACTIVATES SOME OUTPUTS AT RANDOM (DIGITAL AND/OR ANALOGUE) Check : a. the connections between controller and interfaces b. that power cables do not pass near interfaces and control board microprocessors. pag.15
17 - DIGITAL VOLTAGE INPUTS CONNECTION (220 Volt ac; 24 Volt ac) The pco controller allows voltage digital inputs to be connected with terminals ID11 - ID11R and ID12 - ID12R as shown in the picture below. When the general alarm input is open, the high pressure alarm on pco input will be detected. Connections must be done as follows: Digital Input 11: connection between ID11R (common) and ID11 (24V) if 24V are applied, or between ID11R (common) and ID11 (220V) if 220V are applied. Digital Input 12: connection between ID12R (common) and ID12 (24V) if 24V are applied, or between ID12R (common) and ID12 (220V) if 220V are applied. N.B. Do not apply 220V to the terminals ID11 (24V) and ID12 (24V. 220/24 Volt = normal situation 0 Volt = alarm situation 220 Volt 24 Volt general alarm compressor ID11R ID11 (24/220V) inputs pco voltage - DIGITAL OUTPUTS CONNECTION Macroplus / pco terminal connector 1c / C 1o / NO 24/220 Volt device (ex. motor pump) pag.16
18 1.2- HARDWARE: USER INTERFACE The user interface comprises all those components, such as keypad, display and led indicators, which are necessary for the exchange of information between the user who needs air conditioning and the microprocessor devised by CAREL for the managing of this operation. - POWER SUPPLY Connect the 24 V secondary of the network transformer to inputs G0-G placed on the controller. pag.17
19 - INPUTS/OUTPUTS The Reference column indicates the contacts on the board shown on page 3. DIGITAL INPUTS REFERENCE ID1 - IDCM1 ID2 - IDCM1 ID3 - IDCM1 ID4 - IDCM1 ID5 - IDCM1 ID6 - IDCM2 ID7 - IDCM2 ID8 - IDCM2 ID9 - IDCM2 ID10 - IDCM2 ID11 - ID11R ID12 - ID12R DIGITAL INPUT LEVEL HUMIDIFIER SENSOR ALARM FIRE COMPRESSOR 1 LOW PRESSURE COMPRESSOR 2 LOW PRESSURE CLOGGED FILTER FAN OVERLOAD AIR FLOW DETECTOR REMOTE ON / OFF COMPRESSOR 1 GENERAL ALARM (HIGH PRESSURE OR OVERLOAD) COMPRESSOR 2 GENERAL ALARM (HIGH PRESSURE OR OVERLOAD) HEATER 1 OVERLOAD HEATER 2 OVERLOAD ANALOGUE INPUTS REFERENCE ANALOGUE INPUT B1 - AVSS AMBIENT TEMPERATURE PROBE B2 - AVSS OUTLET AIR TEMPERATURE PROBE B3 - AVSS OUTLET WATER TEMPERATURE PROBE B4 - AVSS OUTSIDE AIR/ INLET WATER TEMPERATURE PROBE B5 - AVSS AMBIENT HUMIDITY PROBE B6- AVSS not utilized B7- AVSS TAM input (0..1V) B8- AVSS CONDUCTIVITYinput (0..1 V) DIGITAL OUTPUTS REFERENCE DIGITAL OUTPUT R1 PARTIALISATION /REDUCTION FAN SPEED VALVE R2 MAIN FAN - (SYSTEM ON) R3 ENERGY SAVING VALVE R4 HUMIDIFICATION POWER R5 FILL WATER VALVE R6 DRAIN WATER VALVE R7 OPENING COLD WATER THREE-POINT VALVE/COMPRESSOR 1 R8 OPENING COLD WATER THREE-POINT VALVE/COMPRESSOR 2 R9 OPENING HOT WATER THREE-POINT VALVE/HEATER 1 R10 OPENING HOT WATER THREE-POINT VALVE/HEATER 2 R11 GENERAL ALARM SITUATION ANALOGUE OUTPUTS REFERENCE ANALOGUE OUTPUT pag.18
20 VG0 - Y0 VG0 - Y1 COLD WATER VALVE HOT WATER VALVE - pco OPTIONAL BOARDS INSTALLATION Clock board This board allows to display date and time as well as the management of time-zones. To use this board connect it to the connector (3) shown in the picture on page 3. Cod. PCOCLKMEM0 Serial optoisolated board RS422 This serial board RS422 allows pco network connection. This enhances remote and local telemaintenance and supervisory systems. To use this board connect it to the connector (4) shown in the picture on page 3. Cod. PCOSER0000. pag.19
21 - JUMPER SETTING FOR 4-20 ma PROBES N.B. Remember to place the jumper of J14 (analogue input n.5), J15 (analogue input n.6), J28 (analogue input n.7) and J29 (analogue input n.8) in the position shown in the picture in order to configure the pressure transducer reading into the 4-20 ma mode. - FIRST INSTALLATION There are two phases: a) Hardware connection AFTER HAVING CHECKED THAT THE MATERIAL RECEIVED IS EXACTLY THE ONE YOU REQUESTED, UNPACK IT AND CONNECT THE SINGLE PARTS TO ASSEMBLE THE CONTROLLER AS DESCRIBED BELOW: - connect the telephone cable between the Interface and the pco controller. - insert the Eprom with the programme in the proper socket *** WARNING: INSERT THE EPROM IN THE RIGHT WAY *** - connect all probes and devices to the controller, following the indications of the inputs/outputs table - connect power supply with interface b) Software initialisation Software initialization means to correctely set-up all the parameters in order to allow the unit to work. The machine will thouroughly meet the costumer's requirements, only if all the selected parameters (contained in the following branches: Programming, Manufacturer, and Maintenance) take into account the type of plant, present devices, and control parameters (setpoints, threshold alarms, etc). All the selected parameters are contained in the buffer storage (a memory that maintain the selected values also in the absence of voltage). When the machine is first installed, the stored parameters are the parameters established by Carel (Default values) which ensure a standard working of the machine but not really meet the costumer's requirements. To modify the parameters the operator must enter the branches of interest and change the incorrect parameters. All the modified parameters are stored again. On page 20 a complete list of the default values is shown. On certain circumstances the machine could present some parameters no more answering the needs of the user (following a test or change of the equipment to be controlled, etc), and their recovery would involve an excessive expenditure of time. In this case it is advisable to recover the default values established by Carel and afterwards to change the ones tha are not in a accordance with the equipment. To do this the following operations are needed: Keep pressed for more than 2 seconds the Menu + Prog keys; pag.20
22 - due to the previous action you are now in the Manufacturer Password. Now it is necessary to correctly select the Manufacturer Password. Two different passwords are available: - hardaware " 0123 " password that must be known only by the assistance technician or qualified personnel. It is used during the preliminary operations, and whenever it is impossible to have access to the branch MASTER password (because the memory has been "spoiled"). - MASTER password: the value of this password is selected in the password set mask. It must be used during the normal working of the machine; - having correctly selected the password, press Enter; you reach the mask indicating the branch "Special Procedures"; - you are now in the INSCONFIG mask which permit the erasure and the installation of the default values in the buffer storage; pressing once UP or DOWN allows to change the answer to the question from NOT to YES. Do not do any operation and wait until the text becomes again No. Now the installation of the default values is completed. pag.21
23 2. - CONFIGURATION GUIDE 2.1 SET-POINT - DIFFERENTIAL - DEAD ZONE Temperature control may be based on a proportional or proportional + integral regulation that can be selected by entering the GTEMP2 mask, the branch is named "Temperature Management" under password service. The proportional control works in a proportional way in function of the difference between the required temperature or humidity value (SET-POINT) and the actual value. The P+I regulation is based on the error between the required temperature and the measured temperature in relation to the moment in which the difference between the two values persists (the integration constant can be selected in the GTEMP5 mask). The humidity control is a proportional control; the humidifier is activated when the relative humidity value is lower than the "set-point-differential". The PROPORTIONAL BAND defines the temperature/humidity control area. The more the value differs from the selected Set-point the greater is the control effect. -The selected differential is half of the total differential: for temperature control, the 3 Centigrade Degrees selected as default values are to be intended above and below the set-point; in case there are 3 heaters and 2 compressors, the latter will turn ON when the set-point is 23 degrees (default) + differential (3 degrees), whereas all heaters will be active at 20 degrees. - The selected DEAD ZONE corresponds to a half of the total dead zone; the dead zone prevents the control action when the temperature values are near the set-point. pag.22
24 2.2 STEP For each step it is possible to select the following: - the set-point of the step itself (% value of the regulation differential) - the hysteresis, that is half of the step dimension and a % value of the differential Each step is connected to a device: Cold step > Compressor Hot step > Heater pag.23
25 2.3 DEFAULT VALUES The factory-set configuration provides for the following devices: - ambient temperature probe - ambient relative humidity probe - outside air temperature probe - water temperature probe - cold water valve - hot water valve - all heaters enabled (n.2) - both compressors enabled - external humidifier Here is the list of the default values the controller accepts as machine parameters whenever the user answers affirmatively to the mask successive to that of back-up memory deletion in the special procedures branch. SELECTABLE PARAMETERS RANGE PRE-SET Temperature set-point º Temperature differential º High temperature threshold º Low temperature threshold º Integration constant sec Only 1 compressor enabled; Set-point compressor 1 in CW 0 100% 50% Hysteresis compressor 1 in CW 0 100% 50% or; Set-point compressor 1 in ES 0 100% 66% Hysteresis compressor 1 in ES 0 100% 33% Both compressors enabled; Set-point compressor 1 in CW 0 100% 25% Hysteresis compressor 1 in CW 0 100% 25% Set-point compressor 2 in CW 0 100% 75% Hysteresis compressor 2 in CW 0 100% 25% or; Set-point compressor 1 in ES 0 100% 49% Hysteresis compressor 1 in ES 0 100% 16% Set-point compressor 2 in ES 0 100% 82% Hysteresis compressor 2 in ES 0 100% 16% 1 heater enabled; Set-point 0 100% 25% Hysteresis 0 100% 25% 2 heaters enabled; Set-point heater % 25% Hysteresis heater % 25% Set-point heater % 75% Hysteresis heater % 25% pag.24
26 Beginning cold water valve 0 100% 0% End cold water valve 0 100% 100% Beginning hot water valve 0 100% 0% End hot water valve 0 100% 100% Set-point relative humidity 0 100UR% 50% Humidity differential 5 20%UR 10% High humidity threshold 0 100% 80% Low humidity threshold 0 100% 30% Set-point dehumidification step 0 100% 50% Hysteresis dehumidification step 0 100% 10% Logic dehumidification N.O/N.C. N.O Start-up delay **** 15 sec Threshold working hours h 4000h compressor 1 Threshold working hours h 4000h compressor 2 Threshold working hours humidifier h 4000h Threshold working hours fan h 4000h Water high temperature threshold **** 20º Water low temperature threshold **** 2º Delay between compressors startups **** 360 sec Min. time compressors ON **** 60 sec Min. delay for compressors re-start **** 180 sec Low pressure alarm delay **** 180 sec Digital inputs detection delay **** 60 sec High/low temperature alarm delay **** 30 min Heaters insertion delay **** 3 sec Time-zone 1 (hs) for temperature 00:00/23:59 6:00 Time-zone 2 (hs) for temperature 00:00/23:59 12:00 Time-zone 3 (hs) for temperature 00:00/23:59 18:00 Time-zone 1 (hours) for humidity 00:00/23:59 6:00 Time-zone 2 (hours) for humidity 00:00/23:59 12:00 Time-zone 3 (hours) for humidity 00:00/23:59 18:00 Temperature set-point 1st zone **** 21º Temperature set-point 2nd zone **** 21º Temperature set-point 3rd zone **** 21º Temperature set-point 4th zone **** 21º Humidity set-point 1st time-zone **** 50% Humidity set-point 2nd time-zone **** 50% Humidity set-point 3rd time-zone **** 50% Humidity set-point 4th time-zone **** 50% 2.5 TEMPERATURE CONTROL DIAGRAMS pag.25
27 TWO-COMPRESSOR UNIT WITHOUT ENERGY SAVING OPTION COLD WATER VALVE DIFFERENTIAL (HALF OF THE TOTAL) Default values: - Set-point compressor 1: 25% Hysteresis compressor 1: 25% - Set-point compressor 2: 75% Hysteresis compressor 2: 25% In case of use of default partialised compressors, the compressor steps coincide with the relative partialisations. TWO-COMPRESSOR UNIT WITH ENERGY SAVING OPTION &2/':$7(59$/9( Default values: DIFFERENTIAL (HALF OF THE TOTAL) - Set-point compressor 1: 49% Hysteresis compressor 1: 16% - Set-point compressor 2: 82% Hysteresis compressor 2: 16% In case of use of default partialised compressors, the compressor steps coincide with the relative partialisations. pag.26
28 -MANAGEMENT OF COMPRESSORS After the compressor has been turned ON, it must go on working for at least 1 min (default) (VALUE SELECTABLE THROUGH DEDICATED MASK). After the compressor has been turned OFF, it is necessary to wait for at least 6 min (default) before restarting it (VALUE SELECTABLE THROUGH DEDICATED MASK). The second compressor can not be turned ON before 3 min. have elapsed from the starting up of the first one (default) (VALUE SELECTABLE THROUGH DEDICATED MASK). In the 2-compressor configuration it is possible to select the compressor ROTATION option. The HIGH-LIMIT step activates during dehumidification as follows: - if within one minute from the indication of higher limit of the cooling differential (85%) the temperature value is not comprised within the regulation differential (85% -15%), the HIGH- LIMIT step is activated and dehumidification stopped. - the step remains active until 15% of the heating differential is reached, then dehumidification will restart only if required. -ENERGY SAVING In order to adopt the Energy Saving option check that: Ambient Temperature - Water Temperature > (SET energy saving + HYST energy saving) The value of SET ENERGY SAVING can be selected through a dedicated mask (mask GTEMPES in the "Temperature Management" branch). If this condition occurs: - by answering affirmatively to the COM-ES mask ("Compressors compatible with the valve in the Energy Saving option"), the compressors steps within the differential will be postponed with respect to the cold water valve, but only when the conditions necessary to the energy saving activation occur. Otherwise, with activated energy saving option but functioning conditions, the compressors will be normally functioning. - by answering negatively to the COM-ES mask, the compressors steps will be eliminated and only the valve will remain active in case the conditions necessary to the energy saving activation occur. Otherwise, the compressors will be normally functioning. 1 COMPRESSOR UNIT WITHOUT ENERGY SAVING OPTION pag.27
29 COLD WATER VALVE DIFFERENTIAL (HALF OF THE TOTAL) Default values: - Set-point compressor: 50% Hysteresis compressor: 50% In case of use of default partialised compressors, the compressor step coincides with the relative partialisation. pag.28
30 1 COMPRESSOR UNIT WITH ENERGY SAVING OPTION COLD WATER VALVE DIFFERENTIAL (HALF OF THE TOTAL) Default values: - Set-point compressor 1: 66% Hysteresis compressor 1: 33% In case of use of default partialised compressors, the compressor step coincides with the relative partialisation. TWO-HEATER UNIT HOT WATER VALVE DIFFERENTIAL (HALF OF THE TOTAL) Default values: - Set-point heater 1: 25% Hysteresis heater 1: 25% - Set-point heater 2: 75% Hysteresis heater 2: 25% pag.29
31 ONE-HEATER UNIT HOT WATER VALVE DIFFERENTIAL (HALF OF THE TOTAL) Default values: - Set-point heater: 50% Hysteresis heater: 50% NOTES The 2-step heating configuration allows setting of the following two alternatives: - STANDARD during insertion: HEATER 1 HEATER 1 + HEATER 2 during disinsertion: HEATER 1 + HEATER 2 HEATER 1 - BINARY during insertion: HEATER 1 HEATER 2 HEATER 2 + HEATER 1 during disinsertion: HEATER 2 + HEATER 1 HEATER 2 HEATER 1 The LOW-LIMIT step intervenes during dehumidification as follows: pag.30
32 - if within one minute from the indication of lower limit of the heating differential (-85%) the temperature values are not comprised within the regulation differential (-85% _-15%) the LOW- LIMIT step is activated and dehumidification stopped. - the step remains active up to -15% of the heating differential, then dehumidification will restart only if required. pag.31
33 2.6 HUMIDITY CONTROL DIAGRAMS FEATURES: The type of control can be selected through the dedicated mask (mask SR1U within the "PROBE MANAGEMENT" branch) DEHUMIDIFICATION can be achieved: - by starting one compressor (chosen in the DEU mask within the "Compressors Management" branch); - through partialisation of cold water valve (chosen in the GUMI1DEU mask within the "Compressors Management" branch); - through fan reduction speed (chosen in the GUMI2DEU mask within the "Compressors Management branch); - Dehumidification is enabled only if ambient temperature is within the alarm limits. IN CASE OF OUT-OF-RANGE TEMPERATURE VALUES DEHUMIDIFICATION IS PREVENTED (see diagrams of temperature control). HUMIDITY REGOLATION humidification dehumidification set point differential (half of the total) pag.32
34 3.Humidifier control Generalities: The humidifier control for pco air-conditioner standard manages the immersed-electrode humidifiers (to be coupled with the OEM kits), is able to control all the 1 to 42 Kg/h humidifiers, both three-phase and single-phase, with supply voltages from 200 to 660 V( V or V voltages are suggested). Regulation is ensured by a pco interface with eight analog inputs and an optional card so as the pco interface can read the signal coming from the TAM current transducer, the conductivityreading signal and the full load sensor. In accordance with the current and relative humidity signals, the pco controls steam production and the humidifier working condition; furthermore, it controls and signals all the states and alarms of the humidifier. pag.33
35 3.1 Connection diagram of the Pco interface to the humidity optional card 220 Vac 24Vac G G0 RS422 J1 1 B8 +24 B7 CONDUCTIVITY CURRENT B6 clock J15 J14 AVSS B5 B4 VG0 VG1 Y2 Y1 ID11R 1 J20 1 J2 1 AVSS B3 B2 AVSS B1 IDCM2 B8 G0 B7 J6 G G0 J5 O1 O2 J4 ID11 ID12R J21 J3 ID10 ID9 ID8 ID7 24 Vac ID12 NO11 C11 NC11 NO10 C10 NC10 NO9 C9 NC9 NO8 1 J22 1 R11 R10 R9 R8 R1 R2 R3 1 J4 1 J5 1 ID6 IDCM1 ID5 ID4 ID3 ID2 LEVEL ID1 C1 NO1 C2 NO2 C3 J3 T1 T2 J2 C1 C2 J1 L1 L2 DRAIN C8 NO7 C7 NO6 C6 NO13 C13 J24 R7 R6 R13 R4 R5 R12 J6 1 NO3 C4 NO4 C5 NO5 C12 NO12 FILL POWER TAM L1 N pag.34
36 3.2 Description of humidifier parameters To select and control the humidifier it is necessary to set out properly the following parameter: No. NAME DESCRIPTION U.M. RANGE DEF.. 1 Nominal p. Nominal or maximum kg/h production that can be supplied by the cylinder 2 Voltage Supply voltage Volt Phase no. Phase no. of the power... 1/3 1 supply 4 TAM model Utilized TAM model Set p. Production set out as kg/h 30%Pn. 3 maximum. 100%P n 6 Humidity Setpoint of the humidity Ur% setpoint regulation Ur% 7 Humidity Band of the humidity Ur% differential regulation Ur% 8 High humidity High humidity alarm Ur% threshold threshold Ur% 9 Low humidity Low humidity alarm threshold Ur% threshold Ur% 10 C0 Algorithm constant(see the following paragraph) 11 C1 Algorithm constant (see the following paragraph) 12 C2 Algorithm constant (value for the assistance) 13 C3 Algorithm constant (value for the assistance) 14 C4 Algorithm constant (value for the assistance) 15 C5 Algorithm constant (value for the assistance) 16 C6 Algorithm constant (value for the assistance) 17 C7 Algorithm constant (value for the assistance) 18 C8 Algorithm constant (value for the assistance) pag.35
37 3.3 C0-C1 parameter selection tables The C0 and C1 constants differ according to the type of humidifier being connected. In the following tables, the C0 and C1 values as a function of the nominal production (columns) and voltage (rows) are shown: The C0 and C1constants change according to the type of humidifier being connected. In the following tables the C0 and C1 values are shown as a function of the nominal production (columns) and of the voltage (rows) : C0 and C1 for single-phase cylinders F200MA with a nominal production ranging from 1 to 3Kg/h : Nominal Production in Kg/h 1 Kg/h 2 Kg/h 3 Kg/h C0 C1 C0 C1 C0 C C0 and C1 for three-phase cylinders F400TA with a nominal production ranging from 3 to 5 Kg/h: Nominal Production in Kg/h 3 Kg/h 5 Kg/h C0 C1 C0 C C0 and C1 for three-phase cylinders E400TA with a nominal production ranging from 8 to 13Kg/h: Nominal Production in Kg/h 8 Kg/h 13 Kg/h C0 C1 C0 C pag.36
38 C0 and C1 for three-phase cylinders I400TW with a nominal production ranging from 23 to 42 Kg/h: Nominal Production in Kg/h 23 Kg/h 33 Kg/h C0 C1 C0 C Nominal Production 42 Kg/h C0 C pag.37
39 3.4 Programming of the humidifier Selection of the type of humidifier To select the type of humidifier to be controlled, it is necessary to properly select 4 parameters in the humidifier masks through the manufacturer s password: NOMINAL P. is the nominal steam production or maximum deliverable steam from the cylinder that is available. It is possible to select values ranging from 1 kg/h to 42 Kg/h. VOLTAGE is the voltage value of the power supply. It possible to select values ranging from 0 to 660 V. PHASE No. is the number of phases of the power supply. It is possible to select 1 or 3 phases (single-phase or three-phase) TAM MODEL the model of amperometric transformer being utilized is selected, by selecting 0= TAM 50, 1=TAM 100, 2=TAM 150, 3= TAM 300,4=TAM 500, 5=TAM 700 DRAINAGE ENABL. WITHOUT VOLTAGE the drainage type is selected whether with the power contactor being connected or disconneced. Regulation of humidity and production The regulation of the humidifier steam production depends on: -Humidity regulation -Set production SELECTED P. ( HUMI_PCO_SET1mask SET button) The humidity regulation is carried out by the control in accordance with the reading of the humidity probe at a setpoint and a humidity differential. The control calculates a proportional humidity error ERP : ERP 100 0% DIFFERENZ. UMIDITÁ %Ur The selected production is the maximum wanted production and is a value that can range between the 30% of nominal P. and the 100% of nominal P. Based on the nominal production, the selected production and the proportional humidity error ERP, the graph of the humidifier regulation is obtained: A B C Produzione di vapore 30%P_NOM desiderata : A-100%Pn B-50%Pn The humidifier has a minimum production of the 30% of the nominal P. when the ERP = 0 and it C-30%Pn increases proportionally to the increase of the ERP until it reaches the selected production when 100%ERP the ERP=100% 10%ERP 0%ERP Activation of the humidifier SETPOINT 100%P_NOM ERP = errore proporzionale di umidita rispetto set e differenziale pag.38
40 The humidifier is ativated when the following conditons occur: TheERP > 10 %. The air-conditioner standard unit has been activated by an On/Off button or by a remote start/stop digital input. The humidifier is enabled to operate in the HUMI_PCO_SET3 mask at the item ENABLING, group of masks associated to the SET button. Monitoring of the steam production and of the values that typical of the humidifier The user will be able to verify the instantaneous production of steam by examining the value occurring in the of masks connected to the MENU button The user will also be able to monitor some characterisic values such as the water supply conductivity, the absorbed current per phase and the various operation modes in the group of masks associated to the I/O button. pag.39
41 3.5 Management of the humidifier Alarms Yes Yes The different detectable alarms, with the detection criterion and the possible corrections, are shown below. DISPLAY CRITERIA ACTION REL SIRENS AY Power failure When the water level reaches Cut power alarm the full sensor and Im < 5%In 1 is measured Empty the cylinder 2 Lack of water Load valve open for more None Yes Yes alarm than 20 minutes High or low Humidity over or below the None Yes Yes humidity alarm established thresholds. Signalled only 20 minutes after the On button has been pressed Foam presence The situation is NO NO indication managed until its Full cylinder indication High alarm current Foam has been detected within the cylinder. The presence of foam is signalled in the i/o mask HUMI_PCO_IO1. The cylinder is full of limestone. Current exceding the established limits (see the relevant chapter) extinction through a special procedure by the control (temporarily maximum production is not ensured) (cylinder replacement is suggested) Forced drainage for 5 seconds. Cut power. HIGH CURRENT ALARM Limits have been established in order to prevent the current from exceding the maximum acceptable values. However, they depend on time, as they must allow momentary peaks when the instrument is started. Imax 300%In 250%In 200%In 170%In 130%In Alta corrente Scarico forzato NO NO t The forced drainage lasts for 5 seconds and is not signalled. The high current alarm caauses water drainage for 30 seconds and stops the humidifier. 1 In case of power failure, the control too would not be operating, but in the absence of only one phase, no current could be measured, whereas the last one is exeding the safety threshold. 2 To prevent a rapid current increase beyond the established limits, once the alarm has been reset and the power contactor has been enrgized again. pag.40
42 3. USER GUIDE The Liquid Crystal Display is the main communicative channel between pco and user. All information that can be read on display is stored in a series of masks. All masks will be listed below. 3.1 MASK The typical mask structure is the following (the display has 4 rows x 20 columns): In case of numeric setting fields, press ENTER to move the cursor from the current position (for example 0,0) to the first figure of the first numeric field available; if the current position corresponds to the last possible setting field, by pressing ENTER the cursor will return on "home" position - 0,0. pag.41
43 3.2 ALARM MASKS Each alarm condition is signalled ; - by the incorporated buzzer; - by the red led indicator on the front panel of user interface and by the AL message which appears on the higher right corner of display. It is possible to display an alarm message indicating the type of problem occurred by pressing the ALARM key. All alarms are subjected to 1 minute delay at the unit start-up, with the exception of high/low temperature & humidity alarms and of damaged probe alarm which are subjected to a delay selectable in the Manufacturer branch. The keys that can be used within the alarm branch are: - UP KEY - DOWN KEY - MENU KEY pag.42
44 MENU MASK First mask of synoptic tree.this is the menu mask. Access is gained by pressing the menu key Temp C Humi. 00.0% MAINTENANCE MASKS First mask of the maintenance branch you reachby pressing the Maintenance key. This is the mask for the visualisation of fan/2 compressors working hours. By pressing the Up and the Down keys you can move upwards and downwards the loop. Operating hours Main fan compr compr Maint. Password Mask for Fan Hours Threshold programming and for already calculated hours clearing. For the clearing function it is necessary to keep pressed for a couple of seconds the Up or the Down key on theno word. (warning the threshold is multiply by 1000) Fan hours meter Hours : Threshold (x1000) :000 Reset :N pag.43
45 Mask for Compressor 1 Hours Threshold programming and for already calculated hours clearing. C.1 hours meter Hours : Threshold (x1000) :000 Reset :N Mask for Compressor 2 Hours Threshold programming and for already calculated hours clearing. C.2 hours meter Hours : Threshold (x1000) :000 Reset :N The following probe adjust mask allow you to adjust the value read from the the probe. Probe adjust Room temp. Supply air Outl.water 0.0 C 0.0 C 0.0 C Probe adjust Inl. water. Room hum. 0.0 C 0.0 C pag.44
46 the following manual masks allow you switch on and switch off the devices without the temperature or humidity regulation Manual procedure Main Fan :N Energy saving :N Manual procedure Dehumidifier :N Manual procedure Compressor 1 :N Compressor 2 :N Manual procedure Unloader 1 :N Unloader 2 :N Manual procedure Heater 1 :N Heater 2 :N pag.45
47 Manual procedure Cooling valve N 00.0 Heating valve N 00.0 Manual procedure Disable humidification N Manual drain (120 sec) N I/O MASK Analog inputs Room tmp Supply air temperat. Room Hum C 00.0 C 00.0 C Analog inputs Ext.Air out Water C 00.0 C pag.46
48 Digital outputs C=Close O=Open Dout 01-03: CCC Dout 04-06: CCC Dout 07-09: CCC Dout 10-11: CCC Analog outputs Cooling Valve Heating Valve Humidifier Main switch Fill valve Drain valve 00.0 V 00.0 V :OFF :OFF :OFF Humidif.(Amps.)" Measured Target Nominal : A : A : A Humidifier W. Level: OPEN Conductivity 00000Us/Cm pag.47
49 Humidifier Cyl. worn out : N Mode : Status: TIME ZONES MASKS This is the first mask of the Time /Time-zones branch you can reach by pressing the "Clock key. By pressing the "Up" and the "Down keys you canmove within the loop.this mask allows date and hour setting. CLOCK Hour 00:00 Date 00/00/00 Clock Password First mask of temperature Time Zones which is meant to selectactivation/deactivation of Time Zones. Daily time zone with automatic temperature set. variation :N Mask for the setting of time and set-point of the first temperature Time Zone. Temperature Daily time zone1 Start time 00:00 Setpoint 00.0 C pag.48
50 Mask for the setting of time and set-point of the second temperature Time Zone. Temperature Daily time zone2 Start time 00:00 Setpoint 00.0 C Mask for the setting of time and set-point of the third temperature Time Zone. Temperature Daily time zone3 Start time 00:00 Setpoint 00.0 C Mask for the setting of time and set-point of the fourth temperature Time Zone. Temperature Daily time zone4 Start time 00:00 Setpoint 00.0 C First mask of humidity Time Zones which is meant to selectactivation/deactivation of Time Zones. Daily time zone with automatic humidity setp. variation :N Mask for the setting of time and set-point of the first humidity Time Zone. Humidity Daily time zone1 Start time 00:00 Setpoint 00.0% Mask for the setting of time and set-point of the second humidity Time Zone. Humidity Daily time zone2 Start time 00:00 Setpoint 00.0% pag.49
51 Mask for the setting of time and set-point of the third humidity Time Zone. Humidity Daily time zone3 Start time 00:00 Setpoint 00.0% Mask for the setting of time and set-point of the fourth humidity Time Zone. Humidity Daily time zone4 Start time 00:00 Setpoint 00.0% SET MASK This is the first mask of the set-point branch you can reach by pressing the "Setpoint" key. By pressing the "Up" and the "Down" keys you can move within the loop which is composed of only another mask. This mask allows temperature set-point setting. SET T C SET H. 00.0% USER MASKS This is the first mask of the user branch you can reach by pressing the "Prog." key. In this mask it is necessary to set the user password correctly to be able to move to the other masks of the branch. Service Password This mask allow the setting of temperature and humidity setpoint limits Tmp.setp.limits Minimum 00.0 C Maximum 00.0 C Hum setp.limits Minimum 00.0% Maximum 00.0% pag.50
52 This mask allow the setting of temperature proportional band and neutral zone Temperature Band 00.0 C Neut.zone 00.0 C Humidity Band 00.0% Prod.kg/h 00.0 this mask allow the setting of : automatic unit switch on after power failure Unit switch on and switch off by digital input Chinese character in the main mask differential of energy saving Autom.restart N Remote On/Off Chinese N N Differential of En.saving 00.0 This mask allow the setting compensation parameter Compensation procedure N Setpoint Band Offset 00.0 C 00.0 C 00.0 C pag.51
53 This mask allow setting of high/low offset for low/high air temperature/humidity alarms Room tmp.alarms Offs.low 00.0 C Offs.high 00.0 C Room hum alarms Offs.low 00.0 C Offs.high 00.0 C This mask allow setting of high/low outlet water temperature alarms Outl.water temp. threshold alarms high 00.0 C low 20.0 C New service password pag.52
54 MANUFCTURER MASKS Manuf Password Unit config -> General par -> Timing -> Unit.init. -> Configuration parameter branch The following mask allow the configuration of the unit;it is possible select probes devices and regulator Clock board N Superv. board N Ext.air probe N Suppl. air p. N Outl.water p. N Inl. water p. N Room humid.p. N Energy saving Compress. nr. Heaters numb. Cooling valv. Heating valve N N N N N pag.53
55 General parameter branch This mask allow setting the following parameter: Kind of temperature regulation proportional or proportional + integral Enable or disable rotation of compressors Number of compressors call in dehumidification Enable or disable compressors in energy saving Tmp.regolat.:P Rotat.compr.:N Cmp.for deh.:0 Compr.with valve in ES :N this mask allow setting of the following parameter: Logic of dehumidification relay :normaly oen or normaly closed dehumidification step temperature step to allow the dehumidification Logic dehumi. N.O. Dehum.Pos 00.0% Dehum.Hys 00.0% Low T Pos 00.0% Low T Hys 00.0% HighT Pos 00.0% HighT Hys 00.0% pag.54
56 This mask allow setting the following parameter: temperature steps of compressors in normal function temperature steps of compressors in energy saving C1 Pos 00.0% C1 His 00.0% C1 Pos Es 00.0% C1 Pos Es 00.0% C2 Pos 00.0% C2 His 00.0% C2 Pos Es 00.0% C2 Pos Es 00.0% This mask allow setting the following parameter: temperature steps of heaters in normal function H1 Pos 00.0% H1 His 00.0% H2 Pos 00.0% H2 Pos 00.0% This mask allow setting the following parameter: temperature steps of modulating and floating valve in normal function V c In 000.0% V c End 000.0% V h In 000.0% V h End 000.0% pag.55
57 This mask allow setting humidifier parameter: Voltage production kg/h drain without power in the electrode y/n C0 C1 they dipends from the boiler number of phases they dipends from the boiler TAM Voltage V Product 00 kg/h Drain without Voltage N C0 000 phase 1 C1 000 TAM 100 Timing parameter Branch This mask allow setting the following parameter Delay fan on Delay after switch on or power failure delay fan off delay after switch off integr.time integration time of proprtional+integral temperature regulation runn time total running time of floating valve Delay FAN on 000 Del. FAN off 000 Integr.time 000 Runn. time 000 This mask allow setting the following parameter low press... low pressostat delay after compressor start up probe alarm... high and low alarm delay air flow... integration time of proprtional+integral temperature regulation Low press.alarm delay time: 0000 Probe alarm delay time: 0000 Air flow alarm delay time: 0000 pag.56
58 This mask allow setting the anti-courtcycle timing of compressors Min. COMP. time OFF : 0000 ON : 0000 Delay between two starts of same comp.: 0000 diff.comp.: 0000 Delay between stars two unl. 0000sec Delay between starts diff.hea. 0000sec Unit initialization branch Press key ENTER to insert" DEFAULT paramet Enter new manufacturer password pag.57
59 Alarm masks AL01 Compressor 1 General Alarm AL02 Compressor 2 General Alarm AL03 Circuit 1 Low Pressure Pressostat AL04 Circuit 2 Low Pressure Pressostat AL05 Air Flow Alarm (serius alarm UNIT OFF AL06 Main Fan overload (serious alarm)" UNIT OFF AL07 Heater 1 overload pag.58
60 AL08 Heater 2 overload AL09 Fire/Smoke or Floading alarm (serious alarm) UNIT OFF AL10 Air Filter Alarm AL11 High Room Temperat. Alarm AL12 Low Room Temperat. Alarm AL13 High Room Humidity Alarm AL14 Low Room Humidity Alarm AL15 High Outl. Water Temperat. Alarm pag.59
61 AL16 Low Outlet Water Temperat. Alarm AL17 Compressor 1 Operation Hours Alarm AL18 Compressor 2 Operation Hours Alarm AL19 Operation Hours Main Fan Alarm AL20 Room temperature Probe Faulty or not Connected AL21 Outl.Water temp. Probe Faulty or not Connected AL22 Extern.Air temp. Probe Faulty or Not Connected pag.60
62 AL23 Supply Air Temp. Probe Faulty or Not Connected AL24 Room Humidity Probe Faulty or not Connected AL25 Alarm E06 High Current in the Humidifier AL26 Alarm E09 Lack of Water in the Humidifier AL27 Alarm E10 Lack of Current in the Humidif. AL28 Clock Board Faulty or not Connected AL29 EEPROM Faulty Call Assistance pag.61
63 4. COMPONENTS AND CODES In the STANDARD A/C UNITS the following devices are available: - user interface: cod. PCOT000PGH0 LCD "8X16 graphic - eprom; cod. EPSTDECG0A - pco control board: cod. PCOB000A21 plug-in connectors cod. PCOB000B21 fixed screw connectors -pco address board cod.pcoadr0000 cod.pcoclkmem0 with clock function Derivation box cod.tconn6j000 - connetting cable interface/main board: cod. S90CONN002 cod. S90CONN000 cod. S90CONN001 0,8 mt. 1,5 mt. 3 mt. pag.62
Standard air-conditioning units Manual version: 1.0-14/09/97
Application program for pco Standard air-conditioning units Manual version: 1.0-14/09/97 Program code: EPSTDECZUA Rif.: 36 EM REGULATION AND MICROPROCESSOR-CONTROL MANUAL FOR AIR-CONDITIONING UNITS: 1.
Standard 1/3 compressor pack control Manual version: 1.0-21/10/94
Application program for pco Standard 1/3 compressor pack control Manual version: 1.0-21/10/94 Program code: EPSTDEFC2A Rif.: 83EM pco controller for refrigeration EPSTDIFC2A ver. 1.002 (normally closed
Standard 1/2 compressor chiller/heat pump
Application program for pco Standard 1/2 compressor chiller/heat pump Manual version: 1.3-25/06/99 Program code: EPSTDEHP0A Rif.: 86EM Index Hardware architecture---------------------------------------------------------------------------------------------
Standard air conditioning unit pco in plan Manual version: 1.1-09/07/1998
Application program for pco Standard air conditioning unit pco in plan Manual version: 1.1-09/07/1998 Program code: EPSTDECZUB Rif.: 102EM CONTENTS 1. INTRODUCTION TO THE REGULATION:...3 1.1. FUNCTIONS
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS
pco 2 Standard Application Pack Control Code: FLSTDMFC0A Version 1.2 s manual
pco 2 Standard Application Pack Control Code: FLSTDMFC0A Version 1.2 s manual We wish to save you time and money! We can assure you that the thorough reading of this manual will guarantee correct installation
Standard air-conditioning units Manual version 1.2 April 11, 2003
Application program for pco¹ and pco 2 Standard air-conditioning units Manual version 1.2 April 11, 2003 Program code: FLSTDMCZ0E To save time and money! The thorough reading of this manual will ensure
REGTRONIC OPERATING INSTRUCTIONS
REGTRONIC OPERATING INSTRUCTIONS 1.FEATURES Electrical connection: M12 8-pin connector Preset pressure range 0.05-10 bar with possible full scale regulation. 10 100 mbar adjustable deadband Supply pressure:
COMPTROL 5000 INDEX 52. Issue 5.99 AIR CONDITIONING MICROPROCESSOR OPERATING INSTRUCTIONS. STULZ GmbH, Hamburg
COMPTROL 5000 INDEX 52 Issue 5.99 AIR CONDITIONING MICROPROCESSOR STULZ GmbH, Hamburg OPERATING INSTRUCTIONS Contents Page INTRODUCTION... 4 NOTES ON SAFETY... 4 PAGE CODE... 4 DESCRIPTION OF THE CONTROLLER...
2.1 Instrument and accessory codes...8 2.2 Meaning of the inputs/outputs...10
à à 1.1 pco 2 : SMALL, MEDIUM, LARGE...4 1.1.1 Features common to all the versions...4 1.1.2 Features of the individual versions...4 1.2 Programmability...5 2.1 Instrument and accessory codes...8 2.2
HEAT HEAT COOL HEAT PUMP COOL
OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control
Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions
Alpha Climatic Programmable Modulating Boiler Energy Manager Part No 3.022144 (Hard Wired) Part No 3.022143 (Radio Frequency) Installation and User Instructions 1. Description The Alpha Climatic energy
PD 100A. Printing data system
PD 100A Printing data system Operating instructions ENGLISH IMPORTANT: Read these instructions carefully before installing and using the device; do not forget following all additional information. Keep
TABLE OF CONTENTS. 1.1 Features... 1. 2.1 System Screen... 4 2.2 Main Unit Screen... 6 2.3 Navigating Through the Liebert icom Menus...
Liebert icom User Manual -Intelligent Communications & Monitoring for Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert DS Liebert PeX with Software Version PA2.01.029.03R TABLE OF
Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A
COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850
www.sebury.com.cn Digital Keypad Use s Manual
K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4
BA Touch. Operating Instructions. Operation and Display Unit for systemp Temperature Controllers and Hot Runner Control Cabinets
Operating Instructions Operation and Display Unit for systemp Temperature Controllers and Hot Runner Control Cabinets BA Touch PSG Plastic Service GmbH Postbox 42 01 62 68280 Mannheim Germany Tel. +49
Inwall Room Temperature Unit
Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall
INSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE
NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module
NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module 1. General Description 1 2. General Warnings 1 3. Interface 2 4. Temp Alarms Setting 3 5. Programming 3 6. Light Management 4 7. Installation and
Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC
HOJA TÉCNICA 1400H101 Edición 01 (02 de 08) www.ako.es GENERAL TECHNICAL SPECIFICATIONS Temperature range: -50ºC to +99ºC type: NTC Total accuracy ( + controller): ±1ºC lead extension with cable AKO-15586:
Liebert icom - PEX Product Application
Precision Cooling For Business-Critical Continuity Liebert icom - PEX Product Application User Manual - Intelligent Communications & Monitoring 1.0 INTRODUCTION TABLE OF CONTENTS 1.1 Features...................................................................
PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator
3.635.5275.251 IM-P486-19 CH Issue 2 PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator Installation, Start-up and Operation Manual 1. Safety information 2. General product information 3.
UM-X Field display for continous level sensors
Technical Documentation Field display for continous level sensors 10/2007 Edition: 1 Item No.: 207120 FAFNIR GmbH Bahrenfelder Str. 19 D-22765 Hamburg Telephone: +49 (0)40-39 82 07-0 Fax: +49 (0)40-3 90
How to read this guide
How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information
Standard compressor packs Application software for pco 1, pco 2, pco 3, pco xs
Standard compressor packs Application software for pco 1, pco 2, pco 3, pco xs User manual Manual version: 2.6 del 01/04/09 Programm code: FLSTDMFC0A LEGGI E CONSERVA QUESTE ISTRUZIONI READ AND SAVE THESE
COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions
COMPUTHERM Q7 Programmable, digital room thermostat Operating Instructions GENERAL DESCRIPTION OF THE THERMOSTAT The COMPUTHERM Q7 type switched-mode room thermostat is suitable to regulate the overwhelming
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
STERILIZERS, LABORATORY DRYING OVENS
TS9026 TS9053 TS9135 TS9430 TS 9000 SERIES: STERILIZERS, LABORATORY DRYING OVENS Series TS9000 consists of four different cabinets available in sizes from 26 litres to 430 litres. Interior housing and
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2
COMMERCIAL INSTALL GUIDE 2 Contents How to Use This Guide: The first section of this guide is designed to assist you with the installation of your DECK Monitoring hardware. The revenue grade meter and
Liebert Deluxe System/3
Precision Cooling For Business-Critical Continuity Liebert Deluxe System/3 Operation and Maintenance Manual 50 and 60 Hz, 6-30 Ton DX Systems (DH/DE/VH/VE); 12-60 Ton CW Systems (FH/UH) TABLE OF CONTENTS
AC-115 Compact Networked Single Door Controller. Installation and User Manual
AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.
User manual. Application program for pco 1, pco 2, pco 3. Standard Chiller Modular HP 1/4 Generic /Bitzer screw compressor and CAREL valve
Standard Chiller Modular HP 1/4 Generic /Bitzer screw compressor and CAREL valve Application program for pco 1, pco 2, pco 3 User manual Manual Version: 1.4 dated 11/09/08 Program code: FLSTDmMSBE LEGGI
FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1
BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -
Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify
Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Standard Air-conditioners
Application software for pco¹ pco 2 pco XS Standard Air-conditioners Program code: FLSTDMCZ0E We wish to save you time and money! We can assure you that the thorough reading of this manual will guarantee
USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat
Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage
Dyeing Programmer DP - 01
Dyeing Programmer DP - 01 Display and Controls. 1) Display: 16/2 alphanumeric display 2) Temperature range: 0 to 150 degree. 3) Resolution: 1 degree. 4) Accuracy: +/- 1 degree. 5) Temperature control setting:
Technical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
Monitoring Network DMN
Monitoring Network DMN User Manual Table of contents Table of contents... 2 1. Product features and capabilities... 3 2. System requirements... 5 3. Getting started with the software... 5 3-1 Installation...
NX Series Inverters. HVAC Pocket Programming Guide
NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product
GSM HOME SECURITY SYSTEM
Cell /Mobile phone home security system GSM HOME SECURITY SYSTEM Model : GSM-120 TABLE OF CONTENTS 1. FEATURES... 1 2. APPLICATION... 2 3. SPECIFICATIONS... 3 4. FRONT PANEL & LAYOUT DESCRIPTION...6 5.
ABB i-bus KNX Fan Coil Controller FC/S 1.1
Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation
How To Use A Power Supply On A Powerline 2.2 (Ai)
KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
RZAHUC program version 1.1 Regulation for Reznor Air Handling Units
INSTALLATION INSTRUCTIONS OPTION 1xxx 1104_1000_EN Comfort Regulation (Carel pco) Detailed instructions RZAHUC program version 1.1 Regulation for Reznor Air Handling Units INDEX 1. Introduction... 4 1.1.
A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.:
Documento: M-010.1-MGAS-ENG Edizione: 01/1997 Rev.: A.1 a Division of Pittway Corporation FRONT PANEL & VISUAL INDICATIONS GENERAL TROUBLE GENERAL PROGRAMMING IN PROGRESS ENABLE/ALARM/TROUBLE (ZONE 1 ALARM
TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.
TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection
T-100-R Installation Guide
T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard
INSTALLATION MANUAL. Address card EKAC10B
INSTALLATION MANUAL 88 44 µchiller compact 70 64 4a 4b G G0 power supply G G0 power supply 50 5 50 5 4a 4b 5a 5b 4 5a 5b Installation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT. DO
LEN s.r.l. Via S. Andrea di Rovereto 33 c.s. 16043 CHIAVARI (GE) Tel. +39 0185 318444 - Fax +39 0185 472835 mailto: [email protected] url: http//www.len.
MA511 General Index 1 INTRODUCTION... 3 1.1 HARDWARE FEATURES:... 4 2 INTERFACE... 5 2.1 KEYBOARD... 6 2.2 POWER ON... 7 2.3 POWER OFF... 7 2.4 DETECTOR CONNECTION... 7 2.5 DETECTOR SUBSTITUTION...7 3
TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C
Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
Technical Support Bulletin Nr. 20 Special AC Functions
Technical Support Bulletin Nr. 20 Special AC Functions Summary! Introduction! Hot Start Control! Adaptive Control! Defrost Start Temperature Compensation Control! Anti-Sticking Control! Water Free Cooling
TABLE OF CONTENTS. 1.1 Features... 1. 2.1 Control Interface Large Display... 4. 2.1.1 Navigating to Various Views in the Liebert icom...
Liebert icom User Manual -Intelligent Communications & Monitoring for Liebert Challenger 3000, Liebert CW and Liebert DS with Software Version PA2.01.48R TABLE OF CONTENTS 1.0 INTRODUCTION..........................................................1
Workshop 7 PC Software - Tracker
Workshop 7 PC Software - Tracker Goal: You will startup and perform advanced setup functions using Tracker PC software. You will also setup equations to control MP503 binary outputs. The Binary Output
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR
Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions
Aerona Air Source Heat Pumps
ADDENDUM to INSTALLATION INSTRUCTIONS for Aerona Air Source Heat Pumps DOC.87-05/05 Rev.04 March 2013 ATTENTION INSTALLERS - UPDATED INFORMATION! Your Grant Aerona Air Source Heat Pump has a number of
UM0272 User manual. Central Unit for Alarm System (CUAS) Evaluation Board. Introduction
User manual Central Unit for Alarm System (CUAS) Evaluation Board Introduction The Central Unit for Alarm System (CUAS) Evaluation Board provides a complete reference system addressing the low- to middle-end
SMM. Installation Operation Maintenance
SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation Foreword These installation,
INSTALLATION OPERATING & MAINTENANCE MANUAL
INSTALLATION OPERATING & MAINTENANCE MANUAL Basic Climatic TM Controller Ecologic English November 2002 CONTENTS PAGE GENERAL DESCRIPTION 3 USER INTERFACE 4 The keypad incorporated on the unit 4 The keypad
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER
MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER Starting Serial No. "LA" This manual provides General Information, Installation, Operation, Maintenance and System Set-Up Information
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
MP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types
Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,
Chilled Water Precision Air Conditioner For Critical Application
AIRSYS-P-SC-OPTIMA-HD-E1304V01.2 HD Chilled Water Precision Air Conditioner For Critical Application Cooling capacity: 42.1kW~161.5kW OPTIMA product family is designed for medium to large data center.
NetworkAIR FM Precision Air Conditioner. Operation and Maintenance
NetworkAIR FM Precision Air Conditioner Operation and Maintenance Contents Operation...1 Display Interface.................................... 1 Using the Display................................... 2
PPM Users Manual Signature Software 01-12-00
PPM Users Manual Signature Software 0-2-00 PPM User Manual /8/02 Software Versions: 0.0.27 Contents. Introduction 2 2. Parameters 3 2. Overload Limit...4 2.2 Relative Upper Limit...4 2.3 Relative Lower
Automatic Phone-Out Home Monitoring Systems
Automatic Phone-Out Home Monitoring Systems Power Outage and Freeze Alarm Model Number: THP202 Power Outage, Freeze and Flood Alarm Product Description Model Number: THP201 These monitoring systems are
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
CRE Monitor Instructions Manual
CRE Monitor Instructions Manual CRE TECHNOLOGY believes that all information provided herein is correct and reliable and reserves the right to update at anytime. CRE TECHNOLOGY does not assume any responsibility
SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030)
PART 1 - GENERAL SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) 1.01 SUMMARY This section describes the operation and control of a drip irrigation system. The major components
AGRI-ALERT 800T / AGRI-ALERT 800 ALARM SYSTEM USER MANUAL
AGRI-ALERT 800T / AGRI-ALERT 800 ALARM SYSTEM USER MANUAL Manufacturer: Viatron Electronics 3514 1st Street, St-Hubert (Quebec) Canada J3Y 8Y5 WARNING: the warranty can be void if the Agri-Alert 800T or
Business/Home GSM Alarm System. Installation and User Manual
Business/Home GSM Alarm System Installation and User Manual Brief Introduction: GSM 900/1800/1900 bands, can be used in most parts of the world Full duplex communication with the host Monitor the scene
Limited Service Fire Pump Controllers Features
Must Be Installed Per Applicable Code and Manufacturers Recommendations Limited Service Fire Pump Controllers Features 1-1 FD20 Full Voltage - Limited Service with Plus Microprocessor Power I/O Board Transformers
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance
Automation System TROVIS 5100 Ventilation Controller TROVIS 5177
Automation System TROVIS 5100 Ventilation Controller TROVIS 5177 ounting and Operating Instructions EB 5177 EN Electronics from SASON Firmware version 1.05 Edition September 2000 Contents 1 Scope of the
DATA AIRE, Inc. MINI DATA ALARM PROCESSOR II
DATA AIRE, Inc. MINI DATA ALARM PROCESSOR II Operation and Maintenance Manual Precise Temperature and Humidity Control Air and Water/Glycol Cooled and Chilled Water TABLE OF CONTENTS INTRODUCTION... 1-5
Model: DC-A2IO Advanced HVAC Controller
Model: DC-A2IO Advanced HVAC Controller Job Name: Schedule Reference: Date: DC-A2IO Advanced HVAC Controller Package PAC-IF01 M-Net Adapter AL2-14MR-D α2 Simple Application Controller Accessories AL2-2DA
Wash Select II to WashPay Integration Field Retrofit Installation Guide
Wash Select II to WashPay Integration Field Retrofit Installation Guide Wash Select II Software Version 6.00 and above POS4000 Software Version 8.25 Unitec www.startwithunitec.com WASH SELECT II TO WASHPAY
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
IPThermo206G. Offline/online data collector, SMS alarm sender, watchdog terminal for IPThermo Pro network
IPThermo206G Offline/online data collector, SMS alarm sender, watchdog terminal for IPThermo Pro network IPThermo 206G is the central data handling terminal of the IPThermo Pro measurement network. This
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x
B.IQ push button 3-5gang with room Product name: Design: ETS search path: B.IQ push button 3-, 4-, 5gang with room thermostat and display V2 Flush-mounted Push button / B.IQ / B.IQ push button xgang with
HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS
ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete
RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions
RVR Hybrid System Controller Installation Instructions 1 Introduction to Hybrid Systems The RVR Hybrid system uses a combination of the Immergas Audax range of heat pumps with gas or oil boilers to create
ELECTRIC POSITION for electric heat, then confirm with Fan Test below.
Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
PORTABLE AIR CONDITIONER
VERY IMPORTANT! MODEL: GDC-AC9RW / GDC-AC9RCS GDC-AC9RCW / GDC-AC12RW GDC-AC12RB / GDC-AC12RCB GDC-AC12RCW INSTRUCTIONS FOR USE PORTABLE AIR CONDITIONER Do not install and use your portable air conditioner
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
CONTENTS General features Front panel and buttons Installation List of the working parameters to be checked before starting the unit
CONTENTS General features..... 1 Models available..... 1 Main features of the Infrared Series.... 2 Front panel and buttons..... 4 LED display Indicators..... 4 Keypad..... 5 Installation..... 6 Standard
Computer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC
Technical Teaching Equipment Computer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC Teaching Technique used EDIBON SCADA System 2 Control Interface Box 5 Cables and Accessories 6 Manuals 3