Guide to Commercial Installations. Part 1: Type B Distribution Boards and the Regulations
|
|
|
- Reynold May
- 9 years ago
- Views:
Transcription
1 Guide to Commercial Installations Part 1: Type B Distribution Boards and the Regulations
2 Introduction The whole nature of electrical sub and final distribution for commercial installations has changed in the last few years. There is a demand for more RCD protection of final circuits, more metering and often more control to meet energy saving targets. This guide expands upon some of the requirements found in the 17 th Edition of the IEE Wiring Regulations and Building Regulations and how they affect Type B MCB distribution boards and their protective devices. You should be aware that this guide does not ensure compliance with BS 7671 or the Building Regulations. You should always consult the relevant regulations to ensure compliance.
3 Type A & B distribution boards Manufacturers refer to Type A or Type B distribution boards. This terminology refers to the busbar arrangement and the type of overcurrent protective device (OCPD) that it accepts. Type A distribution boards have a busbar arrangement designed to accept single and/or double pole OCPDs. They typically have a horizontal busbar arrangement that accepts multi-pole and/or single pole OCPDs. Type B distribution boards have a busbar arrangement designed to accept multi-pole and/or single pole OCPDs. They generally have a vertical busbar with the OCPDs connected to the sides. Contents Selection and erection Cable entry Isolation and switching Protection against fault current Protection against electric shock Protection against overvoltage Building regulations Invicta Type B distribution boards Invicta Type B board range Page 4 Page 6 Page 8 Page 10 Page 13 Page 16 Page 18 Page 20 Page 22
4 Selection & erection All equipment must be correctly selected and erected. BS 7671 states that the following, along with manufacturer s instructions should be considered: Compliance with standards Operational conditions External influences Accessibility Compliance with standards A fundamental principle of BS 7671 is that all equipment must comply with the appropriate British Standard. For distribution boards BS EN is applicable. If equipment has a foreign standard based on an IEC standard then the designer or specifier must confirm that any differences will not result in reduced safety. Operational conditions The electrical designer will need to select distribution boards for operational conditions such as voltage, current and frequency. In the UK the nominal voltage and frequency is typically 400/230V and 50Hz. Installations and the distribution boards within them will, however, have different current requirements in the 17 th Edition requires that the equipment is suitable for the design current and the current likely to flow in abnormal conditions. The latter would include short circuit and earth faults. The specifier will therefore need to assess the current demand taking into account diversity. They will also need to assess the prospective fault current at the distribution board location before selecting the board and the protective devices (see page 10).
5 External influences All equipment including the distribution board must be suitable for the external influences that they are likely to encounter. There will be conditions where a suitably IP rated distribution board will be needed. These installations may include: Caravan parks Marinas Agricultural or horticultural installations Temporary electrical installations for structures at fairgrounds, amusement parks and circuses Locations where there is a risk of fire due to the nature of processed or stored materials Accessibility Equipment should be located to facilitate its operation, inspection and maintenance. All equipment including the distribution board must be suitable for the external influences that they are likely to encounter. 5
6 Cable entry Designers and installers must select a wiring system that avoids damage to the sheath and insulation of cable during installation, use and maintenance. Where cables enter a distribution board from trunking, the cables must be protected from any sharp edges in order to comply with Common methods of complying include deburring edges and using grommet strips or manufactured spacers. Regulation requires that the cores of unsheathed cables from which the sheath has been removed and non-sheathed cables at the termination of the trunking etc are enclosed. Complying with these regulations can be difficult when passing the cables from the trunking into a distribution board. The on-site construction of a spacer using material such as paxolin is a common solution. This is, however, time consuming and produces dust, so appropriate health and safety protection may need providing. Also the installer must take care that the solution fully complies with the regulations by making a proper seal.
7 Not only does this cable entry system meet the requirements of the regulations, but it also cuts the time taken to fit the board to trunking by up to four times. A better alternative Another answer is to use a distribution board that has an end plate adapted for coupling to trunking. In Hager s new boards, for example, the end plate has a removable section that leaves a smooth edge return that is free from screw heads and nuts. This allows flush coupling to trunking and a smooth entry for cables to meet the requirements of and of the Wiring Regulations. Not only does this cable entry system meet the requirements of the regulations, but it also cuts the time taken to fit the board to trunking by up to four times. In an independent trial, the time taken to fit a typical distribution board to trunking when the installer needs to cut out the gland plate and cut paxolin to shape was 50 minutes. When there is no need to prepare gland plates, use paxolin or adjust the trunking, the same installer took just 13 minutes to fit the comparable Hager board. 7
8 Isolation and switching Isolation aims to make dead, for safety reasons, all or a discrete section of the electrical installation by separating it from every source of electric energy. This is commonly achieved by switching off an isolation device within the distribution board. Regulation requires that the device shall isolate all live conductors, subject to the provisions of regulation Regulation , however, says that there should be some provision for disconnecting the neutral, for example by using a bolted link. Three-phase TT supplies will require disconnection of the neutral, so a four-pole isolation device is needed. For a single-phase supply where the main switch will be used by ordinary persons, the isolating switch must interrupt both live conductors. The neutral conductor is also a live conductor. In a TN-S or TN-C-S installation, however, regulation allows the neutral conductor to not be isolated where it is reliably connected to earth. If the supply complies with the Electrical Safety, Quality and Continuity Regulations 2002, a three-pole isolating device is sufficient for a three-phase supply. Symbol indicating suitability for isolation
9 Table 53.2 identifies that circuit breakers to BS EN are suitable for isolation. These are commonly used as outgoing devices in distribution boards and can be used as isolation devices for individual circuits. The table below gives guidance as to whether the neutral conductor needs to be switched or not. Table 53.2 Isolation requirements of Neutral Conductor Origin Downstream Use by ordinary persons Use by skilled or instructed persons Use by ordinary persons Use by skilled or instructed persons SP TP SP TP SP TP SP TP TN YES NO* NO* NO* NO NO NO NO TT YES YES YES YES YES YES YES YES Note* There should be some means of disconnecting the neutral by means of a bolted link BS 7671 also requires that the device used for isolation is designed and/or installed so as to prevent unintentional or inadvertent closure. Usually this means that you need to fit some kind of locking mechanism to the device. IEE Guidance Note 2 gives more detailed guidance on isolation and switching. 9
10 Protection against fault current The value of prospective fault current will need to be assessed when selecting a distribution board and devices. For an installation with several distribution boards there will be different values, so you will need to assess this at different points. Section 434 of BS 7671 details the requirements of fault current protection. Only faults belonging to the same circuit need to be considered. On a three-phase distribution board, where there is a mixture of three-phase and single-phase circuits we need to look at these individually.
11 A single-phase (line to neutral) fault will be approximately half that of the three-phase fault (across all lines). This affects the fault current ratings of individual devices for the distribution board. For example, if a distribution board has a three-phase 10kA prospective fault current, then the single-phase devices need to be selected to have a minimum fault current rating of 5kA, assuming that the line to neutral prospective fault current is equal to or higher than the prospective earth fault current states that the short circuit capacity of devices in the distribution board shall not be less than the prospective fault current where the device is installed. A lower breaking capacity is permitted if another device on the supply side has the necessary breaking capacity. In this case the supply side device provides back up protection for the load side device. Manufacturer s data should be sought to obtain the level of back up protection provided. Using back up protection can produce a more cost effective installation with perhaps the incomer to a TP&N board being a 250A MCCB. 10kA outgoing devices could then be installed where there is a 20kA fault level at that distribution board, subject to manufacturer s data. 11
12 Use by skilled or instructed persons? Where there are larger fault currents you should also consider the type of person who will operate the devices. If you can restrict access to the board to skilled or instructed persons only, perhaps by having the board in a locked riser or ensuring that the door to the board is locked, then BS EN can apply if the device has ratings assigned by the manufacturer. Distribution board fault current rating The manufacturer is responsible for ensuring the capability of the equipment between the incoming and the outgoing terminals of the distribution board, which includes busbars and connections as well as incoming and outgoing devices. The manufacturer will have determined the distribution board fault current rating(s), in accordance with the product standard. In such a case the 10kA BS EN devices may be rated to 15kA; again manufacturer s information must be obtained.
13 Protection against electric shock Protection against electric shock needs to be provided by offering both basic protection and fault protection. Basic protection includes the insulation of live parts and barriers or enclosures such as distribution boards. Appropriate devices or blanks must be fitted to maintain IP2X or IPXXB. If the top of the horizontal surface is readily accessible then the level of protection there should be IP4X or IPXXD. Automatic disconnection of supply will usually provide fault protection. This involves protective earthing, protective equipotential bonding and the automatic disconnection of a device if there is an earth fault. The designer will normally need to ensure co-ordination of protective devices and earth fault loop impedances so that disconnection will occur within the maximum times given in , or An additional requirement for the protection against electric shock is to specify RCDs where they are needed recognises that RCDs with a rated residual operating current (IΔn) up to 30mA and an operating time not exceeding 40ms at a residual current of 5 IΔn provides additional protection for ac systems if the basic or fault protection fails, or against carelessness by the end user. 13
14 Socket outlets Regulation requires that an RCD not exceeding 30mA be provided for: i. Socket outlets up to 20A that are for general use by ordinary persons. ii. Mobile equipment up to 32A that is for use outdoors. One exception is permitted where the use of the socket outlet is under the supervision of someone skilled or instructed. So, for commercial or industrial applications the designer will need to consult with the client about whether someone who is skilled or instructed will normally supervise the installation before deciding which socket outlets need RCD protection. Another exception is for a specific labelled/identified socket-outlet for a particular item of equipment. Clearly ordinary persons will use some commercial installations i.e. persons who do not have the necessary knowledge to avoid the dangers from electricity. If this is the case then the designer/installer may decide to provide RCD protection to all socket outlets. For socket outlets used by cleaners, those in common or circulation areas, in self-catering areas or which might supply outdoor equipment, it is generally considered that RCD protection is required.
15 Nuisance tripping In a commercial installation it is likely that socket outlets will supply computers, printers, copiers and other electronic equipment. This type of equipment produces small amounts of protective current. Nuisance tripping could be a problem if several of these are on one circuit protected by a 30mA RCD. The designer will need to consider this problem and may decide to reduce the number of sockets on each circuit by, for example, increasing the number of final circuits. Alternatively you can label sockets used for such equipment. This, plus the occupant/employer operational systems and health and safety policy, should ensure compliance where RCD protection is not provided. Cables in walls It is likely that metal partitions will separate rooms in a commercial installation. If this wall has a cable inside it then the requirements of will need to be met. These requirements are similar to those for socket outlets in that if there is adequate supervision by skilled or instructed persons then you do not need to provide additional RCD protection. If there is some doubt about this, then the designer could make the decision to apply part (v) of this regulation and provide 30mA RCD protection. This applies to all circuits, not just socket outlet circuits. Electric shock protection - conclusion More circuits need RCD protection since the introduction of the 17 th Edition. In commercial distribution boards, it would be appropriate to use RCBOs for individual outgoing circuits. In commercial distribution boards it would be appropriate to use RCBOs for individual outgoing circuits. 15
16 Protection against overvoltage Table 44.4 in BS 7671 provides examples of various impulse categories for equipment and table 44.3 gives the corresponding minimum impulse withstand voltage. For distribution boards where the nominal voltage of the installation is 230/240V or 277/480V category III, 4kV would be appropriate. The designer or installer may choose to apply the requirements of regulation This uses a risk assessment method to determine whether SPDs are required. Section 443 of BS 7671 deals with the protection of electrical installations against transient overvoltages. These can be from the supply distribution system or generated by equipment. Overvoltage protection by surge protection devices (SPDs) is not generally needed for a distribution board where a suitable rated impulse withstand voltage is declared by the manufacturer.
17 Fire detection and alarm circuits Chapter 56 of BS 7671 covers fire detection and alarm circuits. Regulation states that these safety services must be independent of other circuits. This is also a requirement of BS 5859 Fire Detection and Fire Alarm Systems for Buildings. Clause 25.2 states that the mains supply to the fire alarm system should be from the load side of the main isolating device for the building and have its own isolating protective device (such as a circuit-breaker). The circuit should also be from a point in the electrical distribution system that is close to the main isolating device for the building. In addition, every protective device that can isolate the supply to the fire alarm system, other than the main isolator for the building, should be clearly labelled: FIRE ALARM. DO NOT SWITCH OFF in a durable and fade resistant material. 17
18 Building regulations The Approved Documents L2A and L2B provide guidance to the technical requirements of the Building Regulations in respect to the conservation of fuel and power. While they only affect England and Wales, the principle is still useful for the rest of the UK. Part of these approved documents is to provide the owner with relevant energy meters so that at least 90% of the annual energy consumption can be traced to end use categories such as heating, lighting or power. To help achieve this, you should install an incoming meter for every building that has a floor area greater than 500m 2. In addition, CIBSE TM 39 recommends sub meters should be provided for a final electrical distribution board that has an input power greater than 50kW.
19 In order to segregate the energy used by different services, such as lighting and power, you can either use two boards which each have separate meters or you might consider using a lighting and power metered board. Saving energy Conservation of power cannot just be about measurement. It is also about using efficient systems and controls. Timers and photocells help ensure that energy is used efficiently. More sophisticated control such as knx/tebis bus based systems also offer solutions. Such controls are often DIN rail mounted so provision of extension boxes provides a neat and functional purpose. 19
20 Invicta Type B distribution boards Hager has developed its new Invicta Type B boards as a solution for modern commercial installations. Electrical distribution is at the heart of a building s services. Modern distribution systems must enable designs that meet the demands of the 17 th Edition, the need for more metering and the demands for energy efficient solutions through control devices or building management systems. The new Invicta range of Type B boards makes it easier for you to design and install electrical distribution systems that meet the needs of today and the future. Why specify Invicta Type B boards? Multiple incomer choices for 125A and 250A boards Unique trunking entry system no need for paxolin Earth and neutral bars positioned for easier cabling Transparent IP2X shrouds for earth and neutral bars Optimal cabling space Metering fitted next to incomer within board Wide range of extension boxes for side, top and bottom No spacers needed to mount boards, cableways or extension boxes Removable door and front cover for ease of fitting 125A tap off for board extensions or MCB
21 Transparent IP2X shrouds for earth and neutral bars Unique trunking entry system Metering fitted next to incomer within board 21
22 Invicta 3 125A / 250A Type B TP&N distribution board Characteristics JK1** JK2** Standards Designed, manufactured and tested to BS EN Designed, manufactured and tested to BS EN Busbar Current Rating 125A 250A Busbar Type Fully Shrouded Copper Fully Shrouded Copper Busbar Rating 25kA Conditional 25kA Conditional Incoming 100A Switch 100A Switch 125A Switch 125A Switch 63A Contactor AC3 250A MCS 100A Contactor AC3 250A MCCB Direct Connection 160A Contactor AC3 Direct Connection More incomer options available Outgoing Ways 4, 6, 8, 12, 16 Triple pole outgoing ways 8, 12, 16, 18, 24 Triple pole outgoing ways Outgoing Protection Type B MCB (0.5A to 63A, 1P and 3P) Type C, D MCB, (0.5A to 63A, 1P & 3P) 1Mod and 2Mod RCBO (6A to 50A Type B & C, 30mA & 10mA) Voltage Rating in AC 230 / 400V 230 / 400V Type B MCB (0.5A to 63A, 1P & 3P) Type C, D MCB, (0.5A to 63A, 1P & 3P) 1Mod and 2Mod RCBO (6A to 50A Type B & C, 30mA & 10mA) IP Protection IP3X to BS EN IP3X to BS Enclosure Body Type and Paint Type Steel, Powder Coat Grey White RAL 9002 Steel, Powder Coat Grey White RAL 9002 Cable Entry Obround protected cable entry points Obround protected cable entry points
23 For further information The new range of Invicta 3 Type B TP&N distribution boards is available with a huge range of extension boxes, metering kits and other accessories. There are also several different incomer options and outgoing ways. Hager also manufactures Panelboards and Type A distribution boards to help you with your commercial electrical distribution needs and consumer units for residential applications. This is all supported by our CPD accredited training courses and technical and after sales service. For further information about our complete electrical distribution range of products telephone , or [email protected] to receive a free copy of our new catalogue. You can also visit our website 23
24 Hager Ltd. Hortonwood 50, Telford Shropshire. TF1 7FT Customer Services Hotline: Customer Services Faxline: Technical Helpline: Technical Faxline: Hager Ltd. Ireland Unit M2, Furry Park Industrial Estate Swords Road, Santry Dublin 9. Ireland Northern Ireland Tel: Northern Ireland Fax: Republic of Ireland Tel: Republic of Ireland Fax:
Building Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24
1 Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are safe. The introduction of the 17 th Edition
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation
PROTECTION AGAINST ELECTRIC SHOCK by John Ware
16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created
ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
Distribution Boards & Consumer Units
Distribution Boards & Consumer Units Enclosures for system pro M compact Distribution Boards & Consumer Units Contents General 2/ Distribution Boards Mini Center compact Mounting kits for compact accessories
SELECTION OF FINAL CIRCUIT PROTECTION
SELECTION OF FINAL CIRCUIT PROTECTION By Phil Williams, Product Marketing Manager, Power Distribution Components, Eaton Executive summary The selection of devices for final circuit protection in electrical
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
SURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES
1 By kind permission of MK INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES By Mark Coles The IEE receives many enquiries relating to the inspection and testing of electrical
Distribution Boards. A perfect blend of aesthetics, functionality and safety
Distribution Boards A perfect blend of aesthetics, functionality and safety ABB a global leader Distribution Boards ABB (www.abb.com) is a global leader in power and automation technologies that enable
The complete range of consumer switchboards and switchgear
Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
GE Power Controls. MiniFORM Switchboards
GE Power Controls MiniFORM Switchboards MiniFORM MiniFORM MiniFORM switchboards Arrangement Modules Arrangement modules 1-6 6 Arrangement modules 7-12 7 Arrangement modules 12-14 8 Arrangement modules
A B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB1 60898
NAPIT Electrical Test Continuation Sheet Requirements for Electrical Installations BS 767 [IEE Wiring Regulations] and for Please complete all the unshaded areas. This sheet forms part of *Inspection Report
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation
IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 01 (January. 2014), V6 PP 01-12 www.iosrjen.org Paper on Basbar Trunking System for Electrical Supply to Industrial
Circuit Electrical Testing
Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved
BS 7671:2008+A3:2015 MODEL FORMS
BS 7671:2008+A3:2015 MODEL FORMS Usage and Reproduction of IET Forms Subject to your agreement to the following conditions, you are permitted to, free of charge, photocopy and/or electronically manipulate
NEW RANGE OF CABINETS DRIVIATM. Innovation at your service. THE GLOBAL SPECIALIST in electrical and digital building infrastructures
NEW RANGE OF CABINETS DRIVIATM Innovation at your service THE GLOBAL SPECIALIST in electrical and digital building infrastructures Drivia true innovation The new electrical panel for the residential and
Electrical Contractors Association
Electrical Contractors Association Presents BS 7671 2008: Amendment No 1 BS 7671: 2008 Amendment No 1, 2011 IEE Wiring Regulations Now called IET Wiring Regulations History 1882 first edition of the Wiring
GUIDE TO THE AM2 EXAM
AM2 GUIDE TO THE AM2 EXAM What is AM2? AM2 or the Achievement Measurement 2 is a practical performance skill test administered by the National Electrotechnical Training (NET). You must take the AM2 test
Screened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
KAM 25-32 A Lighting Busbar System KAP 40-63 A Plug-in Busbar Distribution System
2-32 A Lighting Busbar System 4-63 A Plug-in Busbar Distribution System / E-LINE KX Compact Busbar Distribution System 63...63 A E-LINE KB Compact Busbar Distribution System 8...63 A E-LINE KO Plug-in
IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.
ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications. Ensuring operational continuity To ensure the operational continuity of an electrical
Residual Current Circuit Breaker
Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
Transformers from 25va to 500kva. Standard despatch in days not weeks
Transformers from 25va to 500kva Standard despatch in days not weeks JMS Transformers Ltd 20 Ivatt Way Westwood Business Park Peterborough PE3 7PG UK Tel: +44 (0)1733 760000 Fax +44 (0)1733 760004 e-mail:
DIOCESE OF LINCOLN GUIDELINES
DIOCESE OF LINCOLN GUIDELINES FOR ELECTRICAL INSTALLATIONS INSIDE CHURCHES Diocesan Advisory Committee for the Care of Churches Revised March 2006 Electrical Installations inside Churches As with all
Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125
Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated
Electrical Practices for Construction Work
1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in
chapter8 Testing and commissioning Unit 2 outcome 2
Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.
ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
Grounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
NZECP 14: 1995 ISSN 0114-0663 COVER PAGE
NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14:1995 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR CONTROL PROTECTION AND SWITCHBOARDS Issued by the Office of The Chief Electrical Engineer, Energy and
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS
GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS 2008 EDITION www.st.gov.my CONTENTS Chapter Title Page 1. 1.1 1.2 1.3 Introduction Purpose References 4 4 5 2. Supply System 6 2.1 Electricity
Masterseal Plus TM. ingress protected wiring devices. technical hotline +44 (0) 1268 563720. www.mkelectric.com IP66. Improved catch.
Masterseal Plus TM technical hotline +44 (0) 268 63720 Improved catch Rear drill holes Available in grey, white and black Fixed gasket speds installation gasket Now has all the features and logic plus
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
ADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
Guidance notes for the installation of electrical supply in mobile trailers for breast screening
NHS Breast Cancer Screening Programme Cancer Screening Programmes Guidance notes for the installation of electrical supply in mobile trailers for breast screening B Mansfield, CP Lawinski NHSBSP PUBLICATION
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
HIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
1 Introduction. 2 Hazards From Electricity
Risk Assessment Application to Electrical Rigs A guide to assist the Competent Named person who will verify the safety of rigs consisting mainly of electrical equipment. 1 Introduction Every employer shall
Modis 25/32. Modular Switchboard Solution
Modis 25/32 Modular Switchboard Solution Dorman Smith Switchgear Limited With over 130 years of experience in switchgear design and production Dorman Smith Switchgear Limited continues to provide high
ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW
ADS8 IP54 Direct-On-Line Starter Technical Focus Replaces ADS7 Rated up to 9kW New ADS8 Motor Starter The new ADS8 range of motor starters replaces the successful ADS7 range which was introduced 20 years
ASSEMBLED SOCKET-COMBINATIONS
ASSEMBLED SOCKETCOMBINATIONS Enclosure extra strong, schockresistant easily open, it provides a comfortable mount it can be connected across a cable gland it consists of a 35 mm mounting rail Window 6
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Smart solutions for electrical distribution in commercial and industrial applications
Power distribution components MCB Distribution boards and enclosures MCCB Panelboards Switch and protection devices Industrial switch and fusegear Enclosed motor, heating and lighting control HRC cartridge
6.0 Electrical Installations
6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is
How can a charging station for electric vehicles be set up simply and safely?
SB18 Building > Electromobility > Charging Station Design How can a charging station for electric vehicles be set up simply and safely? Requirement In order to supply electric vehicles with electric power,
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
MNS is Switchgear System Technical Overview
Switchgear System Technical Overview Innovative Design ABB s innovative MNS is concept combines the long term experience, energy efficiency, grid reliability and industrial productivity of the well-known
Electrical safety and protection devices
Electrical safety and protection devices RCD PROTECTION The easy, economical way to safeguard yourself when working with electricity. RCDs are specifically designed to minimise the risk of a fatal electric
ELECTRICAL PRACTICES FOR CONSTRUCTION WORK
CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational
The complete guide to Low Voltage switchgear
The complete guide to Low Voltage switchgear The complete guide to low voltage switchgear Contents 4-7 Merlin Gerin LV Switchgear An introduction to the Merlin Gerin low voltage range of switchgear, and
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
Protection catalogue 15
15 Protection catalogue Protection devices MCBs, RCBOs, RCCBs, fuse carriers and surge protection Hager offers a wide range of Modular Protection Devices, such as miniature circuit breakers, auxiliaries
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
Guide to the Selection & Use of Residual Current Devices
Guide to the Selection & Use of Residual Current Devices ET214:2005 Edition 1 Electro-Technical Council of Ireland Limited Published by the Electro-Technical Council of Ireland Limited Date of Publication:
SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.
The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
Installation instructions for mains wire-in protectors ESP D1, D1R, D1/LCD and D1R/LCD variants
Installation instructions for mains wire-in protectors ESP D1, D1R, D1/LCD and D1R/LCD variants Introduction This document explains how to install Furse Electronic Systems s for mains power supplies: Single
MK Electric Sentry Circuit Protection Solutions
MK Electric Sentry Circuit Protection Solutions The Sentry range of Consumer Units from MK Electric has been stylishly designed to blend in with its environment. The curved lines and slim-line appearance
Securing your electrical installations Prisma,
Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards
INFRARED QUARTZ WALL HEATER
INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this
IEC specifications for LV assembly switchboards
Technical set IEC specifications for LV assembly switchboards In conformity with IEC 61439-1&2 standard Specifier Guide Introduction Within the IEC 61439 series of standards for low-voltage switchgear
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
ABB. Installation Enclosures Meter Boxes. SMB s. DMB s. Enclosures
Meter Boxes SMB s To house a single phase kilowatt hour meter Standard kwh meter mounting Square or triangular securing screw Stand off for circuit breaker Optional circuit breaker reset rod DMB s To house
Technical data. RCBO s DS 261 / DS 271 Residual current operated circuit breakers with integral overcurrent protection
Technical data RCBO s DS 261 / DS 271 Residual current operated circuit breakers with integral overcurrent protection When connecting aluminium conductors ensure that the contact surfaces of the conductors
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
AS/NZS 3000:2007 Amendment 2
AS/NZS 3000:2007 Amendment 2 Published 14 December 2012 Under Victorian legislation the day a revised standard is published it becomes the requirement. The aim of this document is to highlight the important
Smart solutions for electrical distribution in commercial and industrial applications
Power distribution components MCB Distribution boards and enclosures MCCB Panelboards Switch and protection devices Industrial switch and fusegear Enclosed motor, heating and lighting control HRC cartridge
FORMS for the 17th Edition
FORMS for the 17th Edition Usage and Reproduction of IEE Forms Subject to your agreement to the following conditions, you are permitted to, free of charge, photocopy and/or electronically manipulate the
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection
Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
Grounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
QUICK REFERENCE PRICE GUIDE JULY 2015
QUICK REFERENCE PRICE GUIDE JULY 2015 ISO 9001: 2008 OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed All products supplied from this Quick Price Guide carry a guarantee against defects in materials
Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility