1 DIOCESE OF LINCOLN GUIDELINES FOR ELECTRICAL INSTALLATIONS INSIDE CHURCHES Diocesan Advisory Committee for the Care of Churches Revised March 2006
2
3 Electrical Installations inside Churches As with all works in Churches, PCCs are advised to obtain 3 quotations for works to be undertaken. A faculty may be required and PCCs should seek advice from the Archdeacon or DAC Secretary. The Insurance Company which provides cover for the church building should also be informed of any electrical work to be undertaken. The following is a list of notes of guidelines for specifiers and electrical contractors installing electrical installations inside churches in the Diocese of Lincoln. Introduction 1. Any design of electrical installation should include an introduction describing the type of church and any particular features which are important to the re-wire. The design should mention any special areas which will require avoidance or protection. Schedule 2. The design should include a schedule of outlets and lighting points to be provided, together with a list of specific suppliers of equipment. Calculation Sheets 3, The design must always include calculation sheets, confirming that the cables and protection devices comply with the current edition of the IEE Regulations. Drawings 4. A drawing with plan and elevations should also be provided showing location of the various points and fittings. Visit to Site 5. Any quotations for electrical work should be checked to ensure that the provider of the quotation has visited the site before providing the tender. MICC Cables 6. It is recommended that either MICC (mineral insulated copper conductor) cable with a white LSF over sheath or FP200 Gold cable be used in all cases. The cables are to be installed in the church so as to be as unobtrusive as possible without damaging the existing fabric.
4 Painting 7. Cables should be painted to match the background material. Glands 8. All glands should be complete with necessary shrouds, brass lock nuts and steel lock washers. Seals 9. All seals should be earth tail seals which will provide a separate CPC at terminations. Switchgear 10. All switchgear should contain miniature circuit breakers, selected for the correct current rating, fault level and magnetic tripping characteristics. 11. A check should be made of the meter position to ensure that where multiple switch fuses and distribution boards are fitted and connected to a multi-way connection box and if at all possible be replaced at the same time as any wiring work. PME 12. All circuits should be adequately earthed using a PME system (protective multiple earthing) provided by the local electricity supply company and the installation should be completed bonded to any tape in accordance with PME regulations and the IEE regulations. RCDs 13. a. In addition to solid earthing it is recommended that 30mA RCDs be fitted to each individual outgoing final circuit using combined MCB/RCDs (or at least one RCD protecting each fuse board). Alternatively, a 100mA split load board with 30mA for sockets should be used. However, this does have a disadvantage that in the event of a fault the whole distribution board will be disconnected. Care needs to be taken in selecting the type of RCDs to be installed, bearing in mind the capital costs.
5 b. For heating, cooking and water heating systems 100mA RCD, should be fitted. Quartzray Installations 14. a. Where proposed it is recommended that Linear type Quartzray heaters be fitted at wall plate level and these be fitted with Phillips gold lamps. It should be noted that Quartzray type heating is not normally permitted in Grade I buildings. b. A controller should be fitted to reduce heat in Spring and Autumn. c. A timer must be fitted to provide a pre-heat period of at least one-hour before a service. Conduits 15. Conduits should generally not be used. However, where it is necessary to re-use existing conduits to light switch drops, these should be bonded and earthed to the system and in addition a separate CPC should be run down the conduit to the accessory/outlet point. Test Certificate 16. In addition to the provision of calculation sheets before the start of work, a test certificate should be provided at the end of the work and this should be fully completed and signed by the contractor then passed onto the parish, who should arrange for this to be kept in the parish files and readily available for inspection by the insurance officer, and the architect/surveyor carrying out the quinquennial inspection. Bell Towers 17. Bell towers should be fitted internally with floodlights and a socket outlet (RCD protected) for maintenance work. Lighting fittings should also be installed in tower turrets. Lighting 18. a. Pendant fittings should be avoided wherever possible. b. Wall mounted uplighter fittings (metal halide) together with electronic controller should be installed wherever possible.
6 c. Lighting fittings containing S.O.N. lamps or mercury vapour (MVFU) would not normally be recommended for churches. d. Floodlights should be fitted as low as possible (see para 20. below). e. Dimmers should be installed wherever possible. f. Where a particular lamp source cannot be dimmed care should be given to switching on groups of luminaires to allow reduction of lighting levels. g. Emergency lighting should be provided, particularly towards the areas of emergency doors. h. Localised emergency lighting fittings should be used and not the emergency exit type signs. i. Where costs are important, tungsten halogen floodlighting may be considered, but this has a disadvantage of high lamp failure and safety implications (see para 20 below). Load Approval 19. Should additional substantial electrical load be installed, the existing mains electricity service should be checked to ensure that it is adequate. This particularly applies in the case of heating appliances. Maintenance 20. Lighting design should always allow for ease of access for changing of lamps and switchgear. Delivery 21. Delivery to site should be carefully arranged and discussed with all parties concerned. General Specifications 22. The installation should be generally wired as per the general specification for The wiring of Churches - available from the Council for the Care of Churches.
7 Insurance 23. Details of his insurance policy should be obtained from the electrical contractor, for any work carried out on the church, to ensure that the contractor is fully covered to a minimum of 5,000, and checks should be made to ensure that the insurance certificate is valid and current. Designer s liability insurance should also be included in the prices proposed by the contractors. CDM Regulations 24. If it is envisaged that:- a) the work will continue for more than 30 days (5 weeks), assuming a six day week, or b) involves 5 or more men on site (more than 3 men and a supervisor of mixed trades), or c) will last for more than 500 days, or d) involves any demolition then the CDM Regulations will apply and you will need to obtain the help of an architect, and/or a planning supervisor before carrying out this work. The Health and Safety Executive need to be notified officially before any work commences on site. Hazard Analysis and Method Statement 25. a. Any tenders or quotations should also include copies of hazard analysis and proposed method statement for carrying out the necessary work. b. The Hazard analysis and Method statement must be checked thoroughly before any contract is awarded and before the commencement of work on site. Checks should also be made to ensure that the work will not come under the CDM regulations. Manuals and Manufacturer s Catalogues 26. Manuals, manufacturer s catalogue and copies of delivery notes should be obtained. This is to enable the parish to obtain names of suppliers, spare parts and codes.
8 Qualifications 27. All electricians working on churches should be JIB graded and have had experience in working in similar buildings. Contractors carrying out electrical work must be members of the NICEIC and preferably the ECA and carry out the work in line with the current edition of the IEE regulations. Periodic Inspection and Testing (Existing Installations) 28. a. It is recommended that churches and associated buildings are tested every 2 years, with a maximum of 5 years between tests. b. Test and inspection certificates should be kept in the parish file, available for inspection by the architect and church insurance officer. PAT Testing 29. All electrical appliances should be tested at least once per year or a maximum of every 5 years. This advice and information is given in good faith and is based on the DAC s understanding of the current law. The DAC cannot accept any liability whatsoever for any errors or omissions, which may result in injury or loss or damage including consequential or financial loss.
9 Also available in the DAC guideline series:- 1. DAC Members and Consultants 2. Churchyard Regulations Cremated Remains Areas 4. De minimis matters 5. Electrical Installations 6. Floodlighting of Churches 7. How to look after your Pipe Organ 8. Installation of Sound Enhancement Systems 9. Looking after your Church Clock 10. Maintenance of Church Bell Installations 11. Trees in Churchyards 12. Care of church textiles
Circuit Electrical Testing
Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au
ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks
Electrical Practices for Construction Work
1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in
Fire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
NATIONAL COIR RESEARCH AND MANAGEMENT INSTITUTE (NCRMI) KUDAPPANAKUNNU.P.O, THIRUVANANTHAPURAM NOTICE INVITING LIMITED QUOTATION
NATIONAL COIR RESEARCH AND MANAGEMENT INSTITUTE (NCRMI) KUDAPPANAKUNNU.P.O, THIRUVANANTHAPURAM NOTICE INVITING LIMITED QUOTATION NCRMI/LIB/ELE001/15 4.09.2015 Competitive sealed quotations are invited
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
GUIDE TO THE AM2 EXAM
AM2 GUIDE TO THE AM2 EXAM What is AM2? AM2 or the Achievement Measurement 2 is a practical performance skill test administered by the National Electrotechnical Training (NET). You must take the AM2 test
Article 10 - ADMINISTRATIVE SECTION
Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
Residual Current Devices. Switching on to Safety
Residual Current Devices Switching on to Safety Contents What is a Residual Current Device? 2 Types of RCDs 3 Switchboard RCDs 3 1 Residual Current Devices Socket outlet RCDs 4 Portable RCDs 4 Changes
6.0 Electrical Installations
6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is
SPECIFICATIONS FOR TENDER NO: PSNR/SCP/VKS/E 1635 ANNEXURE I TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST
TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST ANNEXURE I Sl.No. Description for BHEL Requirement Offered Deviation Scope of supply, erection and commissioning: 1 The scope of this specification covers
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
St Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
St Peter s College ELECTRICAL SAFETY References: A. Peninsula Business Services Guidance Note 4-1, Electrical Safety. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
Building Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24
1 Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are safe. The introduction of the 17 th Edition
METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT
TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
ELECTRICAL PRACTICES FOR CONSTRUCTION WORK
CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
Inspection and testing of portable electrical equipment
February 2008 Inspection and testing of portable electrical equipment This is a guidance document for Schools and Support Services. Units should use the guidance to help them develop their own local health
chapter8 Testing and commissioning Unit 2 outcome 2
Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.
Commercial/Industrial Electricity
1 ELC 210 Commercial/Industrial Electricity Course Package Presented and Approved July 31, 2008 2 Contact person(s) DAVE WHITE Date of proposal to JULY 31, 2008 Curriculum Committee NEW COURSE PACKAGE
City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines
Western Riverside County Code Uniformity Program City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines PHONE (951) 826-5697 3900 Main Street, Riverside, CA 92522
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES
1 By kind permission of MK INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES By Mark Coles The IEE receives many enquiries relating to the inspection and testing of electrical
Electrical Resistance Resistance (R)
Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed
House Wiring and EMFs
House Wiring and EMFs Introduction (please also read the legal and safety Notes on page 12) Electric and magnetic fields (EMFs) are produced as a result of the flow of electric current. The wiring in our
Trouble-shoot and repair faults in low voltage electrical apparatus and circuits
UEENEEG108A Trouble-shoot and repair faults in low voltage electrical apparatus and circuits AS3000:2007 & AS3017:2007 Summary MANUFACTURING AND ENGINEERING DIVISI M & E UEENEEG108A TESTING Before any
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
Homeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
DESCRIPTION UNIT QTY RATE TOTAL (KSHS) Supply and install the following: -
PROPOSED KISUMU HOUSING 3 BEDROOM-TYPE 1 ELECTRICAL INSTALLATION -SITE 01 DESCRIPTION UNIT QTY RATE TOTAL (KSHS) Supply and install the following: - 1.0 Final sub-circuit from Consumer Unit to lighting
GUIDANCE ON ELECTRICAL INSPECTIONS
GUIDANCE ON ELECTRICAL INSPECTIONS Electricity Electricity is a versatile and convenient source of energy. However, it can be potentially dangerous if the system has not been properly designed, installed,
CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2
IT Power Solutions CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2 Thomas B. Jones 1 Introduction Operators and managers consider outages, operational
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation
Questions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
Linear Luminaire with LED Series EXLUX 6402/2
> Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the
ONLINE VERSION ONLINE VERSION ONLINE VERSION. 2006 edition. Electrical safety dwellings APPROVED DOCUMENT. The Building Regulations 2000
The Building Regulations 2000 P1 P Design and installation of electrical installations APPROVED DOCUMENT Coming into effect 6 April 2006 2006 edition Amendments to Approved Documents and Compliance Guides
MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing
MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing Release: 1 MEM10019 Select circuit protection devices by type and rating, fit to switchboards and
Safety & Environmental Protection Services Guidance Note
Safety & Environmental Protection Services Guidance Note A STEP-BY-STEP GUIDE TO VISUAL INSPECTION OF ELECTRICAL EQUIPMENT Why Inspect? The Health and Safety at Work etc Act 1974 and the Electricity at
Electrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS
Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS
SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS 2 This water heater must be installed (water and electrical installation), commissioned and serviced
RCD Inspection Log Book
RCD Inspection Log Book This book is the property of: Commenced: / /. Completed: / /. 2 Clipsal Australia Pty Ltd Clipsal Australia Pty Ltd 3 4 Clipsal Australia Pty Ltd Clipsal Australia Pty Ltd 5 6 Clipsal
PART P: DOMESTIC ELECTRICAL SAFETY April 2006 Revisions (modified April 2007)
THE BUILDING REGULATIONS Guide for Householders, Designers and Builders PART P: DOMESTIC ELECTRICAL SAFETY April 2006 Revisions (modified April 2007) THE BUILDING REGULATIONS PART P : Domestic Electrical
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
INFRARED QUARTZ WALL HEATER
INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this
Work in Substations - General
Work in Substations - General Summary: This document supports the Power System Safety Rules and its requirements assembled under Work in Substations General Category 3 and apply to all persons working
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
Linear Luminaire for Fluorescent Lamps Series EXLUX 6001
> As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
A B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB1 60898
NAPIT Electrical Test Continuation Sheet Requirements for Electrical Installations BS 767 [IEE Wiring Regulations] and for Please complete all the unshaded areas. This sheet forms part of *Inspection Report
AS/NZS 3000:2007 Amendment 2
AS/NZS 3000:2007 Amendment 2 Published 14 December 2012 Under Victorian legislation the day a revised standard is published it becomes the requirement. The aim of this document is to highlight the important
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
Addendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:
When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory
Electrical safety and you
Electrical safety and you A brief guide Introduction Electricity can kill or severely injure people and cause damage to property. Every year many accidents at work involving electric shock or burns are
PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.
MANAGING ELECTRICAL RISKS IN THE WORKPLACE
MANAGING ELECTRICAL RISKS IN THE WORKPLACE Code of Practice MARCH 2015 Safe Work Australia is an Australian Government statutory agency established in 2009. Safe Work Australia consists of representatives
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions
The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs:
RFQ number PR4877728 The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs: A- Supplying and installing 30 high wall A/C split unit 3HP- 24,000
How To Keep An Eye On Electric Safety
Table of Contents Keep an Eye on Electric Safety................ 1 Safety in an Emergency...................... 1 Downed Power Lines...................... 1 Keep an Eye on Electric Safety Electricity is
THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE
THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE December 2013 Electrical Hazard Warning Sign Disclaimer Whilst this guide endeavours to provide general information on work health and safety issues relating
A Guide to 17th Edition Testing
Seaward, Bracken Hill, South West Industrial Estate, Peterlee, County Durham, SR8 2SW United Kingdom Tel: +44 (0) 191 586 3511 Fax: +44 (0) 191 586 0227 Email: [email protected] Web: www.seaward.co.uk
Electrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
Guidance for Electricity and Gas Meter Installation Consumer Facing Issues
Guidance for Electricity and Gas Meter Installation Consumer Facing Issues A guide for meter operatives on how to act and actions to take when identifying consumer facing issues May 2015 Energy UK Version:
1 Introduction. 2 Hazards From Electricity
Risk Assessment Application to Electrical Rigs A guide to assist the Competent Named person who will verify the safety of rigs consisting mainly of electrical equipment. 1 Introduction Every employer shall
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
Preventative Maintenance & Statutory Testing
Preventative Maintenance & Statutory Testing Emergency Evacuation Lighting - Inspection and Maintenance It is an Occupational Health and Safety Act requirement that employers have a legal duty of care
Understanding HUD s UPCS Protocol for Inspecting Electrical Devices Revised Oct. 2010
PIH REAC is providing the following information to assist in properly identifying and mitigating electrical hazards that may exist on the property. This information presents common electrical hazards but
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
CalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
Acumen Enterprises, Inc.
Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter
This Guideline does not address electrical equipment in the following categories:
Policy Hierarchy link Responsible Officer Contact Officer Superseded Documents HS418 Portable Electrical Equipment Inspection, Testing and Tagging Guideline Work Health and Safety Act 2011 Work Health
Welcome to Home Wiring Repair Essential. No-cost, no hassle home wiring repairs.
Welcome to Home Wiring Repair Essential. No-cost, no hassle home wiring repairs. Important program terms and conditions are inside. Please file for future reference. 2015 Duke Energy Corporation 151299-hw
CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
How To Wire Wireline Cable To A Cell Phone (New Zealand)
Installation Guide EnerNOC Site Server - S2 Installation Guide - AUS, NZ v 1.7 EnerNOC New Zealand Limited 2 Collina Terrace PO Box 12-202 Thorndon Wellington NZ 6144 +64 4 909 7546 1 Table of Contents
SMD Rework Station TABLE OF CONTENTS
SMD Rework Station Thank you for purchasing the Hakko 50B SMD Rework Station. The Hakko 50B is designed to solder and desolder surface mounted devices with hot air. Please read this manual before operating
SELECTION OF FINAL CIRCUIT PROTECTION
SELECTION OF FINAL CIRCUIT PROTECTION By Phil Williams, Product Marketing Manager, Power Distribution Components, Eaton Executive summary The selection of devices for final circuit protection in electrical
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
3 IN 1 BATHROOM HEATER
3 IN 1 BATHROOM HEATER MODEL NO.: A515 - SH MINI FUNCTION: HEATER, EXHAUST FAN AND LIGHT Dear customers, Thank you for selecting the AUPU 3 in 1 Bathroom Heater. Please read all instructions before commencing
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
PROTECTION AGAINST ELECTRIC SHOCK by John Ware
16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created