TEST REPORT for ASTM D7147 Direct Vertical Load Capacity (Downward and Uplift) and Modified Lateral Capacity. Rendered to: HDG, INC.

Size: px
Start display at page:

Download "TEST REPORT for ASTM D7147 Direct Vertical Load Capacity (Downward and Uplift) and Modified Lateral Capacity. Rendered to: HDG, INC."

Transcription

1 TEST REPORT for ASTM D7147 Direct Vertical Load Capacity (Downward and Uplift) and Modified Lateral Capacity Rendered to: HDG, INC. PRODUCT: Deck Ledger Support Brackets Report No.: Test Date(s): 11/07/ /11/2020 Report Date: 09/03/ pages 257 E Randolph St Nappanee, IN Phone:

2 Test Report 09/03/2020 TABLE OF CONTENTS 1.0 General Information Referenced Standards ASTM D7147 Direct Load Capacity Test: Vertical Modified ASTM D7147 for Lateral Load Capacity Closing Statement Appendix A Photographs Appendix B - Drawings Appendix C - Data Appendix D - Revision Log FORM QA 4.3 Test Report Page 2 of 40

3 TEST REPORT Rendered to: HDG, INC. 209 Tidwell Drive Alpharetta, Ga Report No.: Test Date: 11/07/ /11/2020 Report Date: 09/03/ General Information 1.1 Product Deck Ledger Support Brackets 1.2 Project Summary ICC NTA, LLC was contracted by HDG, INC. to evaluate their Deck Ledger Support Brackets in accordance with ASTM D7147 to establish maximum ultimate loads. Results obtained herein are tested values and were secured by using the designated test method(s). Testing was conducted at ICC NTA's facility in Nappanee, IN. 1.3 Product Description HDG, Inc Deck Ledger Brackets Deck Ledger Support Brackets: 4-in. Queen (H1-GQ) 4-in. Queen Splice (H1-GQS) Deck Corner Bracket (H2-GCL and H2-GCR) Produced in a Manufacturing facility using the following Materials: 12 Gauge cold-formed steel 1.4 Qualifications ICC NTA in Nappanee, IN has demonstrated compliance with ISO/IEC and is consequently accredited as a Testing Laboratory. ICC NTA is accredited to perform all testing reported herein. FORM QA 4.3 Test Report Page 3 of 40

4 1.5 Product Sampling A representative of ICC NTA visited HDG, INC.'s facility located in Alpharetta, GA on November 15, 2019 and again on July 25-26, 2020 and selected the materials for the testing reported herein. All test specimens were supplied by HDG, INC. See photograph in Appendix A for typical sampling mark. 1.6 Witnessing A representative of HDG, INC. witnessed remotely, the testing of ASTM D7147 Modified Lateral Test of HDG s bracket assembly containing the Queen Bracket, Deck Corner Bracket and H7-GJR Corner Bracket on June 8 th through June 11 th of Conditions of Testing Unless otherwise indicated, all testing reported herein was conducted in a laboratory set to maintain temperature in the range of 73.4 ± 3.6 F and humidity in the range of 50 ± 5% RH. All test specimen materials were stored in the laboratory environment for no less than 40 hours prior to testing. 2.0 Referenced Standards ASTM D , Standard Specification for Testing and Establishing Allowable Loads of Joist Hangers ASTM D , Standard Test Methods of Direct Moisture Content Measurement of Wood, and wood-based Materials (Method B) ASTM D e1, Standard Test Methods for Density and Specific Gravity (Relative Density) of Wood and Wood based materials (Method A) FORM QA 4.3 Test Report Page 4 of 40

5 3.0 ASTM D7147 Direct Load Capacity Test: Vertical 3.1 General The results from this testing provided load data for metal devices used for wood to wood, wood to concrete, or wood to steel connections. These devices are commonly referred to as Joist hangers, and connect joist, beams, and girders together. 3.2 Test Specimens In the testing conducted herein, 3 identical bracket assemblies comprised of two brackets connected to a joist and a header were subjected to vertical loading. Testing consisted of a 4 Queen Bracket, a 4 Queen Splice bracket and a Deck Corner bracket. Each Support was made of 12 Gauge Cold-Formed Steel and installed in the wood members using lag screw or lag bolts per manufactures installation instructions. Each wood member was verified to have a moisture content not less than 11 percent before construction of the test setups. In addition, each member had its specific gravity taken, results can be seen in Appendix C. 3.3 Test Setup and Procedure Each Deck Ledger support bracket was tested in both vertical directions, Upward (uplift) and downward (gravity). Supports were tested in pairs in accordance with figure 1 from ASTM D7145 which can be seen in Appendix B. The test setup consisted of a joist supported between two headers by the support bracket that was being tested. The minimum header length was 18-in. The joist length was of adequate size to prevent contact between the joist hangers and any other material other than that of the header and joist. For downward load capacity, an initial preload was used to seat the brackets. The initial preload did not to exceed 20% of the ultimate load. For Uplift capacity test a preload was not applied. The Joist was loaded through a load transfer block at a uniform rate between 0.03 and.20 in./min. For all tests, the ultimate load shall not be reached in less than 5 minutes. The basic test setup can be seen in Photo 2. Supports were added to the setup as seen in Photo No. 9 to eliminate the specimens wood members from pulling apart during testing. Deviations from the standard include: None. 3.4 Test Results Test Results can be seen in the tables below for each bracket. Additional data can be found in appendix C for each test. Queen Splice Downward Specimen Ultimate Number Load (lbf) Ult. Per Bracket (lbf) Time to Ultimate (sec) Failure ,595 6, Crushing at center of inside board, no damage to brackets ,350 6, Crushing at center of inside board, no damage to brackets ,340 6, Crushing at center of inside board, no damage to brackets Average: 12,428 6, Minimum: 12,340 6, FORM QA 4.3 Test Report Page 5 of 40

6 Queen Splice Upward Specimen Ultimate Number Load (lbf) Ult. Per Bracket (lbf) Time to Ultimate (sec) Failure , Failure in wood substrates, no damage to brackets ,528 7, Failure in wood substrates, no damage to brackets ,350 7, Failure in wood substrates, no damage to brackets Average: 14,523 7, Minimum: 12,692 6, Queen Downward Specimen Number Ultimate Load (lbf) Ult. Per Bracket (lbf) Time to Ultimate (sec) Failure ,697 4, Failure in wood substrates, no damage to brackets ,535 4, Failure in wood substrates, no damage to brackets ,247 4, Failure in wood substrates, no damage to brackets Average: 9,160 4, Minimum: 8,535 4, Queen Upward Specimen Number Ultimate Load (lbf) Ult. Per Bracket (lbf) Time to Ultimate (sec) Failure ,213 4, Failure in wood substrates, no damage to brackets ,860 4, Failure in wood substrates, no damage to brackets ,453 4, Failure in wood substrates, no damage to brackets Average: Minimum: Deck Corner Bracket Downward Specimen Ultimate Number Load (lbf) Ult. Per Bracket (lbf) Time to Ultimate (sec) ,834 3, Failure Failure in wood substrates, damage to holes on left and right bracket on header piece ,025 3, Failure in wood substrates ,439 2, Failure in wood substrates Average: 6,099 3, Minimum: 5,439 2, FORM QA 4.3 Test Report Page 6 of 40

7 Deck Corner Bracket Upward Specimen Number Ultimate Load (lbf) Ult. Per Bracket (lbf) Time to Ultimate (sec) Failure ,178 3, Failure in wood substrates, bracing to corner bracket on right side is loose ,682 2, Failure in wood substrates, Bracket pulled through top of headers ,396 3, Failure in wood substrates, Bracket pulled through top of headers Average: 6,086 3, Minimum: 5,682 2, Summary and Conclusions ICC NTA, LLC was contracted by HDG, INC. to evaluate their Deck Ledger Support Brackets in accordance with ASTM D7147 to establish maximum ultimate loads in both the upward and downward direction. The load rating for each bracket can be seen below. Conclusion Bracket 4-in. Queen Splice (H1-GQS) 4-in. Queen (H1-GQ) Deck Corner Bracket (H2-GCL and H2-GCR) Direction Ultimate Load Rating per Bracket a (lbf) Downward 2,056 Upward 2,115 Downward 1,422 Upward 1,368 Downward 906 Upward 947 a Load Rating was determined by dividing the minimum ultimate per bracket load (from each set of 3 specimens) by a safety factor of 3 FORM QA 4.3 Test Report Page 7 of 40

8 4.0 Modified ASTM D7147 for Lateral Load Capacity 4.1 General The results from this testing provided load data for metal devices used for wood to wood, wood to concrete, or wood to steel connections. These devices are commonly referred to as Joist hangers, and connect joist, beams, and girders together. 4.2 Test Specimens The specimens tested and reported herein are HDG Deck Corner Brackets and an assembly containing the Queen Bracket (H1-GQ) and Deck Corner Bracket (H2-GCL,H2-GCR). Photos of the assembly can be seen in Appendix A. Each Support was made of 12 Gauge Cold-formed Steel and installed in the wood members using lag screw or lag bolts per manufactures installation instructions. Each wood member was verified to have a moisture content not less than 11 percent before construction of the test setups. In addition, each member had its specific gravity taken before testing, results can be seen in Appendix C. 4.3 Test Setup and Procedure The Deck Ledger support bracket was tested in combination with the queen support bracket and bolted to a header and joist to simulate a deck. The test setup was done per section 5.1 of ASTM D7147 but modified to align the tested assemblies so that the test load being applied was lateral or in-line with the bracket. The initial preload did not exceed 20% of the ultimate load. The header was loaded through a solid bar at a uniform rate between of.20 in./min. For all tests, the ultimate load was not be reached in less than 5 minutes. The basic test setup can be seen in Photo 10. Deviations from the standard include: Test specimens were rotated and tested in the lateral direction pulling apart from the header. 4.4 Test Results Test Results can be seen in the tables below for each bracket assembly. Additional data can be found in appendix C for each test. FORM QA 4.3 Test Report Page 8 of 40

9 Queen Brackets with Deck Corner Brackets Specimen Number Ultimate Load (lbf) Ult. Per Side of Assembly (lbf) Time to Ultimate (sec) Failure ,835 3, Corner brackets bending and pulling queen bracket through lumber ,975 5, Corner brackets bending and pulling queen bracket through lumber ,855 4, Corner brackets bending and pulling queen bracket through lumber Average: 9,222 4, Minimum: 7,835 3, Summary and Conclusions ICC NTA, LLC was contracted by HDG, INC. to evaluate their Deck Ledger Support Brackets as assemblies in accordance with ASTM D7147 to establish maximum ultimate loads in the lateral direction. The load rating for each bracket assembly can be seen below. Conclusion Bracket Assembly Ultimate Load Rating per Bracket Assembly Side a (lbf) 4-in. Queen and Deck Corner Bracket 1306 a Load Rating was determined by dividing the minimum ultimate per side load (from each set of 3 specimens) by a safety factor of 3 FORM QA 4.3 Test Report Page 9 of 40

10 5.0 Closing Statement This report contains only findings and results arrived at after employing the specific test procedures listed herein. It does not constitute a recommendation for, endorsement of, or certification of the product or material tested. ICC NTA, LLC makes no warranty, expressed or implied, except that the test has been performed, and a report prepared, based upon the specimen specified by the client. Extrapolation of data, from the test data provided herein, to the batch or lot from which the specimens were obtained may not correlate and should be interpreted with extreme caution. ICC NTA assumes no responsibility for variations in quality, composition, appearance, performance, or other features of similar materials produced by the client, other persons, or under conditions over which ICC NTA has no control. ICC NTA has issued this report for the exclusive use of the client to whom it is addressed. Any use or duplication of this report shall not be made without their consent. This report shall only be reproduced in its entirety. For ICC NTA, LLC: Cody Meyer 09/03/2020 Brad Wear 09/03/2020 Test Engineer Senior Test Engineer FORM QA 4.3 Test Report Page 10 of 40

11 Appendix A Photographs Photo No. 1 Common Sampling Mark Photo No. 2 ASTM D7147 Vertical Load Test Setup FORM QA 4.3 Test Report Page 11 of 40

12 Photo No. 3 ASTM D7147 Vertical Load Test: Failure in Wood Member Photo No. 4 ASTM D7147 Vertical Load Test Setup: Common Failure for Deck Corner Bracket FORM QA 4.3 Test Report Page 12 of 40

13 Photo No. 5 ASTM D7147 Vertical Load Test Setup: Deck Corner Bracket Being Tested Photo No. 6 ASTM D7147 Vertical Load Test Setup: Common Failure for Queen Bracket FORM QA 4.3 Test Report Page 13 of 40

14 Photo No. 7 ASTM D7147 Vertical Load Test Setup with Supports to Limit Rotation FORM QA 4.3 Test Report Page 14 of 40

15 Photo No. 8 Queen Bracket being tested Vertically Photo No. 9 Bracket Assembly Before Testing FORM QA 4.3 Test Report Page 15 of 40

16 Photo No. 10 Lateral Load Test Setup with Deck Corner Bracket and Queen Bracket Photo No. 11 Failure in Deck Corner Bracket, Deck Corner Bracket pulling Queen through Lumber FORM QA 4.3 Test Report Page 16 of 40

17 Photo No. 12 Common Failure: Failure of Wood Members FORM QA 4.3 Test Report Page 17 of 40

18 Appendix B - Drawings Diagram 1: General Test Setup for Vertical Loading FORM QA 4.3 Test Report Page 18 of 40

19 Appendix C - Data FORM QA 4.3 Test Report Page 19 of 40

20 FORM QA 4.3 Test Report Page 20 of 40

21 FORM QA 4.3 Test Report Page 21 of 40

22 FORM QA 4.3 Test Report Page 22 of 40

23 FORM QA 4.3 Test Report Page 23 of 40

24 FORM QA 4.3 Test Report Page 24 of 40

25 FORM QA 4.3 Test Report Page 25 of 40

26 FORM QA 4.3 Test Report Page 26 of 40

27 FORM QA 4.3 Test Report Page 27 of 40

28 FORM QA 4.3 Test Report Page 28 of 40

29 FORM QA 4.3 Test Report Page 29 of 40

30 FORM QA 4.3 Test Report Page 30 of 40

31 FORM QA 4.3 Test Report Page 31 of 40

32 FORM QA 4.3 Test Report Page 32 of 40

33 FORM QA 4.3 Test Report Page 33 of 40

34 FORM QA 4.3 Test Report Page 34 of 40

35 FORM QA 4.3 Test Report Page 35 of 40

36 FORM QA 4.3 Test Report Page 36 of 40

37 FORM QA 4.3 Test Report Page 37 of 40

38 FORM QA 4.3 Test Report Page 38 of 40

39 FORM QA 4.3 Test Report Page 39 of 40

40 Appendix D - Revision Log Rev. # Date Page(s) Revision(s) 0 09/03/2020 N/A Original report issue 1 09/03/ Split testing from section 4 into two reports FORM QA 4.3 Test Report Page 40 of 40

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40 TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax:

More information

TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing

TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4 x 4 and 5 x 5 PVC Porch Posts with Aluminum Reinforcing TEST REPORT Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing Report No.: Report Date: 01/28/14 Test Record Retention Date: 12/20/17 130 Derry

More information

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: LandMarke Railing System. PVC Guardrail System "Patent Number 7,487,941"

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: LandMarke Railing System. PVC Guardrail System Patent Number 7,487,941 TEST REPORT Rendered to: FAIRWAY BUILDING PRODUCTS, LP For: LandMarke Railing System PVC Guardrail System "Patent Number 7,487,941" Report No: Report Date: 05/25/10 130 Derry Court York, PA 17406-8405

More information

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19

More information

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10

More information

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized

More information

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration

More information

PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims

PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32, 1/16, 1/8 and 1/4 PRODUCT: Plastic Shims PERFORMANCE EVALUATION TEST REPORT Rendered to: HANDI-SHIM, LLC SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims Report No: Report Date: 11/04/08 Expiration Date: 10/26/12 130

More information

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method

More information

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration

More information

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court

More information

SECTION 05 42 16 COLD-FORMED METAL DECK FRAMING Elevations Steel Deck Framing by Trex

SECTION 05 42 16 COLD-FORMED METAL DECK FRAMING Elevations Steel Deck Framing by Trex (Specifier Note: The purpose of this guide specification is to assist the specifier in correctly specifying cold-formed metal deck framing products and execution. The specifier needs to edit the guide

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC. Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its

More information

FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight

FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight FM 4473 TEST REPORT Rendered to: VTECH INDUSTRIES, LLP SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight Report No.: 92240.01-801-75 Test Date: 08/27/09 Report Date: 08/31/09 Expiration Date: 08/27/13

More information

Assembly Instructions ShadeTree Canopy Systems. A wood support constructed with a ShadeTree Bracket System. Garden Getaway

Assembly Instructions ShadeTree Canopy Systems. A wood support constructed with a ShadeTree Bracket System. Garden Getaway Assembly Instructions ShadeTree Canopy Systems A wood support constructed with a ShadeTree System. Garden Getaway Dear Customer: Thank you for purchasing our ShadeTree Canopy System. We trust these assembly

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13

More information

SIMPLE SAVER SYSTEM DESIGN MANUAL

SIMPLE SAVER SYSTEM DESIGN MANUAL SECTION 5: BAR JOIST CONSTRUCTION DETAILS SIMPLE SAVER SYSTEM DESIGN MANUAL Call Toll-free: 1-800-255-0776 Fax: 1-402-454-2708 E-mail us at: custserv@thermaldesign.com SIMPLE SAVER SYSTEM DESIGN MANUAL

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

TEST PROCEDURE FOR FIELD WITHDRAWAL RESISTANCE TESTING

TEST PROCEDURE FOR FIELD WITHDRAWAL RESISTANCE TESTING TESTING APPLICATION STANDARD (TAS) No. 105-98 TEST PROCEDURE FOR FIELD WITHDRAWAL RESISTANCE TESTING 1. Scope 1.1 This Testing Application Standard (TAS) covers procedures for withdrawal resistance testing

More information

By SP Partners, LLC. www.rainbowatticstair.com INSTALLATION GUIDE. Prestige

By SP Partners, LLC. www.rainbowatticstair.com INSTALLATION GUIDE. Prestige By SP Partners, LLC www.rainbowatticstair.com INSTALLATION GUIDE Prestige IMPORTANT READ THIS FIRST Inspect stair for any damage prior to installation. Stair is NOT to be installed while home is under

More information

Wisconsin Building Products Evaluation

Wisconsin Building Products Evaluation Safety & Buildings Division 201 West Washington Avenue P.O. Box 2658 Madison, WI 53701-2658 Evaluation # 200813-O Wisconsin Building Products Evaluation Material Best Management Standards for Foundation

More information

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test

More information

PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM

PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM PERFORMANCE TEST REPORT Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM Report No: Report Date: 01/31/11 Expiration Date: 01/19/15 130 Derry Court York, PA 17406-8405 phone: 717-764-7700

More information

REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013

REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND

More information

Ceiling Mounted Folding Attic Ladders Installation Instructions

Ceiling Mounted Folding Attic Ladders Installation Instructions Ceiling Mounted Folding Attic Ladders Installation Instructions WARNING Before you start installing your new Louisville Ceiling Mounted Folding Attic Ladder, you must read and understand the following:

More information

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael

More information

OPERATOR S MANUAL SUPPORTED TORQUE CALIBRATION BEAM. Part Number 34320 Issue 4 Original Instructions (English)

OPERATOR S MANUAL SUPPORTED TORQUE CALIBRATION BEAM. Part Number 34320 Issue 4 Original Instructions (English) OPERATOR S MANUAL SUPPORTED TORQUE CALIBRATION BEAM Part Number 34320 Issue 4 Original Instructions (English) CONTENTS Part Numbers Covered by This Manual 2 Safety 2 Introduction 2 Parts Included 2 Accessories

More information

WARNING! DO NOT ATTEMPT TO INSTALL THIS KIT IN A POWERED CONVEYOR.

WARNING! DO NOT ATTEMPT TO INSTALL THIS KIT IN A POWERED CONVEYOR. Model: Document Number: 64058111 Kit Number: 64058112 Revision: 02 Description: Release Date: 04/08 Introduction This kit allows a PS90 scale to be integrated into a standard gravity conveyor. The kit

More information

Assembly Instructions

Assembly Instructions Assembly Instructions Overhead Storage Rack 4 x 8 3 x 8 2 x 8 4 x 6 3 x 6 2 x 6 4 x 4 Two 4x8 Racks Pictured Eagle Industrial Group, Inc. 25471 Arctic Ocean Drive Lake Forest, CA 92630 877.655.3443 888.313.9228

More information

TSL Professional Services

TSL Professional Services Report For: Laboratory #: 402876-05 5375 Edgeway Drive, ALLENDALE, MI, USA Report Date: December 21, 2005 49401 Received Date: November 3, 2005 Phone: 616 875 7725 Fax: 616 875 6009 Customer P.O. #: COD

More information

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test

More information

Screw Penetration Testing with the ProSTUD

Screw Penetration Testing with the ProSTUD Screw Penetration Testing with the ProSTUD 24 June 2010 Structural Testing and Research Inc. 498 Eagle St. N., Unit 6 Cambridge, ON, Canada, N3H 1C2 Tel: (519) 653-5255 www.starlabs.ca STaR Technical Report

More information

SUPER SHED. Indoor shelter for your outdoor tools.

SUPER SHED. Indoor shelter for your outdoor tools. SUPER SHED Indoor shelter for your outdoor tools. Not everyone needs a garden shed. But, if you've no more space on your garage wall for that new leaf rake, if you can't find your potting trowel because

More information

DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION: 06 05 23 WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION: 06 05 23 WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 ICC ES Report ICC ES (800) 4 6587 (56) 699 054 www.icc es.org 000 Most Widely Accepted and Trusted ESR 0 Reissued 07/06 This report is subject to renewal 07/07. DIVISION: 06 00 00 WOOD, PLASTICS AND

More information

Seismic Technical Guide

Seismic Technical Guide Technical Document Seismic Technical Guide Hanger Wire Attachment Code Requirements 1 The International Building Code (IBC) defines the requirement for hanger wire and their supports and attachment methods.

More information

SAN25 (6904-002001 <00>)

SAN25 (6904-002001 <00>) SAN25 () Wood 002752.eps Concrete 13mm (1/2 in.) 5mm (3/16 in.) Sanus Systems 2221 Hwy 36 West Saint Paul, MN 55113 USA Customer Service Americas: 800-359-5520 651-484-7988 info@sanus.com Europe, Middle

More information

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This

More information

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration

More information

ABOUT CWB CERTIFICATION/ QUALIFICATION The work CWB does on behalf of our clients can be divided into five main categories:

ABOUT CWB CERTIFICATION/ QUALIFICATION The work CWB does on behalf of our clients can be divided into five main categories: CWB CERTIFICATION/ CWB CERTIFICATION/ QUALIFICATION QUALIFICATION SERVICES SERVICES CANADIAN WELDING CERTIFICATION AN OVERVIEW Canada, like many countries around the world, has specific rules and regulations

More information

Code of Standard Practice for Timber Frame Structures

Code of Standard Practice for Timber Frame Structures TFEC 2-2013 Code of Standard Practice for Timber Frame Structures August 2013 Preface This Code is intended to represent a reasonable consensus of what constitutes ordinary and acceptable practice within

More information

Patio Covers / Carports

Patio Covers / Carports Patio Covers / Carports Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed

More information

AMF112 (6904-002010 <00>) 13mm (1/2 in.)

AMF112 (6904-002010 <00>) 13mm (1/2 in.) AMF112 () Concrete Wood 13mm (1/2 in.) 5.5mm (7/32 in.) 10mm (3/8 in.) Sanus Systems 2221 Hwy 36 West Saint Paul, MN 55113 USA Customer Service Americas: 800-359-5520 651-484-7988 info@sanus.com Europe,

More information

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022 M G C O N S T R U C T O R S & E N G I N E E R S, I N C. I N S P E C T O R S E N G I N E E R S B U I L D E R S C A L I F O R N I A E N G I N E E R I N G A N D B U I L D I N G L I C E N S E A / B 6 4 2 0

More information

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions Printing 3 March 2008 CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions This instruction is intended for CP2 cable pedestal installations and replacements. The following tools will be

More information

Owner's Manual & Assembly Instructions

Owner's Manual & Assembly Instructions Owner's Manual & Assembly Instructions PM01 BASE KIT Model No. FDN1014 717090311 CAUTION: SOME PARTS HAVE SHARP EDGES. CARE MUST BE TAKEN WHEN HANDLING THE VARIOUS PIECES TO AVOID A MISHAP. FOR SAFETY

More information

How To Test For An Architectural Test

How To Test For An Architectural Test Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

AMF112 Instruction Manual

AMF112 Instruction Manual AMF112 Instruction Manual Scan here to view product demo and install videos or visit san.us/103 Milestone AV Technologies 6436 City West Parkway Eden Prairie, MN 55344 USA Customer Service Americas: 800-359-5520

More information

Guidelines for Earthquake Bracing Residential Water Heaters

Guidelines for Earthquake Bracing Residential Water Heaters Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the

More information

ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 8 TEST : Whisper Industries, L.L.C. Report Date: August 14, 2008 Date: July 9, 2008 Number: RESULT

More information

PC-Concrete Injectable Concrete Anchoring and Repair System

PC-Concrete Injectable Concrete Anchoring and Repair System PC-Concrete Injectable Concrete Anchoring and Repair System DESCRIPTION: PC-Concrete is a two component (1:1 ratio), 100% solids, high modulus, structural epoxy paste. PC-Concrete is a solvent free, no

More information

Featuring TJ Rim Board and TimberStrand LSL

Featuring TJ Rim Board and TimberStrand LSL #TJ-8000 SPECIFIER S GUIDE TRUS JOIST RIM BOARD Featuring TJ Rim Board and TimberStrand LSL Multiple thicknesses, grades, and products to cover all your rim board needs 1¼" Thickness matches lateral load

More information

E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion

E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex

More information

Uncovered Decks & Porches

Uncovered Decks & Porches Uncovered Decks & Porches Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed

More information

Proper use of the Rebound Hammer Updated to reflect the changes to ASTM C805

Proper use of the Rebound Hammer Updated to reflect the changes to ASTM C805 CEMEX USA - Technical Bulletin 2.1 Proper use of the Rebound Hammer Updated to reflect the changes to ASTM C805 The Rebound Hammer has been around since the late 1940 s and today is a commonly used method

More information

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona Project Report Structural Investigations Yuma, Arizona Prepared by: 2619 Spruce Street Boulder, CO 80302 303-444-3620 Prepared for: Principle Engineering Group, Inc. 833 East Plaza Circle, Suite 100 Yuma,

More information

INSTALLATION INSTRUCTIONS for Bifold Doors (JII103)

INSTALLATION INSTRUCTIONS for Bifold Doors (JII103) Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for premium composite, hollow and solid core molded Bifold Doors. Bifolds are designed for fast

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering

More information

REPORT HOLDER: JENWEST ENTERPRISES LLC, DBA ADVANCED CONNECTOR SYSTEMS 321 SOUTH 1240 WEST #15 LINDON, UTAH 84042 EVALUATION SUBJECT:

REPORT HOLDER: JENWEST ENTERPRISES LLC, DBA ADVANCED CONNECTOR SYSTEMS 321 SOUTH 1240 WEST #15 LINDON, UTAH 84042 EVALUATION SUBJECT: 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3635 Reissued 04/2016 This report is subject to renewal 04/2018. DIVISION: 03 00 00 CONCRETE

More information

ESR-1190 Reissued December 1, 2009 This report is subject to re-examination in two years.

ESR-1190 Reissued December 1, 2009 This report is subject to re-examination in two years. ICC-ES Evaluation Report ESR-90 Reissued December, 2009 This report is subject to re-examination in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs. Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12

More information

TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION

TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006

More information

Pole Lathe and Shave Horse Design

Pole Lathe and Shave Horse Design Pole Lathe and Shave Horse Design These pictures and accompanying words are Copyright Michael Hughes February 2002. They are not to be re-produced, in part or whole, without permission from the author.

More information

OAK WORKBENCH WITH 2 DRAWERS

OAK WORKBENCH WITH 2 DRAWERS OAK WORKBENCH WITH 2 DRAWERS Model 93991 ASSEMBLY Instructions Visit our website at: http://www.harborfreight.com Read this material before using this product. Failure to do so can result in serious injury.

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

Post and Beam Construction

Post and Beam Construction Post and Beam Construction A Presentation By the Canadian Wood Council Canadian Conseil Wood canadien Council du bois Early settlers introduced the concept of post and beam construction in North America

More information

TYPICAL PATIO COVERS 111

TYPICAL PATIO COVERS 111 City of Laguna Niguel Building Division 30111 Crown Valley Pkwy Laguna Niguel, CA 92677 (949) 362-4360 FAX 362-4369 www.cityoflagunaniguel.org TYPICAL PATIO COVERS 111 PLEASE NOTE: This information Bulletin

More information

Contact person Date Reference Page Bengt-Åke Andersson 2013-11-27 3F020623A Rev1 1 (4) Wood Technology +46 10 516 54 34 bengt-ake.andersson@sp.

Contact person Date Reference Page Bengt-Åke Andersson 2013-11-27 3F020623A Rev1 1 (4) Wood Technology +46 10 516 54 34 bengt-ake.andersson@sp. issued by an Accredited Testing Laboratory Contact person Bengt-Åke Andersson 2013-11-27 3F020623A Rev1 1 (4) Wood Technology +46 10 516 54 34 bengt-ake.andersson@sp.se 1002 ISO/IEC 17025 Nordic Comfort

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER:

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER: 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1900 Reissued 03/2016 This report is subject to renewal 03/2017. DIVISION: 07 00 00 THERMAL

More information

HP 16/18-Port Cable Management Kit Installation Guide

HP 16/18-Port Cable Management Kit Installation Guide HP 16/18-Port Cable Management Kit Installation Guide Abstract This document describes how to attach the HP 16 Port or 18 Port Cable Management Kit to an HP rack. The cable management bracket is designed

More information

CEILING SYSTEMS. Between us, ideas become reality. Installing. Suspended Ceilings. North America Version

CEILING SYSTEMS. Between us, ideas become reality. Installing. Suspended Ceilings. North America Version CEILING SYSTEMS Between us, ideas become reality Installing Suspended Ceilings North America Version 1 Installing Armstrong Suspended Ceilings An Armstrong suspended mineral fiber ceiling is functional,

More information

DIVISION: 10 00 00 SPECIALTIES SECTION: 10 73 00 PROTECTIVE COVERS REPORT HOLDER: METALS BUILDING PRODUCTS/LATIUM USA TRADING, INC.

DIVISION: 10 00 00 SPECIALTIES SECTION: 10 73 00 PROTECTIVE COVERS REPORT HOLDER: METALS BUILDING PRODUCTS/LATIUM USA TRADING, INC. 0 ICC ES Report ICC ES (800) 23 6587 (562) 699 053 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1953 Reissued 06/2016 This report is subject to renewal 06/2017. DIVISION: 10 00 00 SPECIALTIES

More information

ACCREDITATION CRITERIA FOR INSPECTION PROGRAMS FOR MANUFACTURERS OF METAL BUILDING SYSTEMS AC472

ACCREDITATION CRITERIA FOR INSPECTION PROGRAMS FOR MANUFACTURERS OF METAL BUILDING SYSTEMS AC472 ACCREDITATION CRITERIA FOR INSPECTION PROGRAMS FOR MANUFACTURERS OF METAL BUILDING SYSTEMS AC472 August 2012 (Effective September 1, 2012) (Editorially revised September 4, 2013) (Editorially revised February

More information

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within

More information

LEGACY REPORT ER-5110. www.icc-es.org. ICC Evaluation Service, Inc. Reissued November 1, 2003. Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER-5110. www.icc-es.org. ICC Evaluation Service, Inc. Reissued November 1, 2003. Legacy report on the 1997 Uniform Building Code LEGACY REPORT Reissued November 1, 2003 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900

More information

NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)

NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) Summary of Results Standardized Thermal Transmittance (U-Factor)

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination Structural Effective Beginning with the April 2011 The structural engineering exam is a breadth and exam examination offered in two components on successive days. The 8-hour Vertical Forces (Gravity/Other)

More information

Residential Decks. Planning and Development Services Department

Residential Decks. Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks

More information

CHAPTER 6 CONSTRUCTION TYPES

CHAPTER 6 CONSTRUCTION TYPES CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use

More information

Dock Hardware & Accessory Products Catalog

Dock Hardware & Accessory Products Catalog Dock Hardware & Accessory Products Catalog Product Page # Product Page # Angle Brackets/Clips 8 Back Up Plate 5 Backing Plate/Hurricane Stop 10 Carriage Bolt Sets 4 Chain Retainer 10 Connector Pin Set

More information

609 West Rock Road, Radford,VA 24141 540-633-5000 / (fax) 540-731-3712 RECOMMENDED ATTACHMENTS & CONNECTION DETAILS

609 West Rock Road, Radford,VA 24141 540-633-5000 / (fax) 540-731-3712 RECOMMENDED ATTACHMENTS & CONNECTION DETAILS 609 West Rock Road, Radford,VA 24141 540-633-5000 / (fax) 540-731-3712 RECOMMENDED ATTACHMENTS & CONNECTION DETAILS INDEX OF DRAWINGS SECTION A: A-1 = METAL TRACK TO PANEL ATTACHMENT A-2 = WOOD PLATE TO

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

HP 36-Port InfiniBand Switch Cable Management Kit Installation Guide

HP 36-Port InfiniBand Switch Cable Management Kit Installation Guide HP 36-Port InfiniBand Switch Cable Management Kit Installation Guide HP Part Number: 574412-doc Published: May 2009 Copyright 2009 Hewlett-Packard Development Company, L.P. The information contained herein

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Monday, May 07, 2012 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website:

More information

Technical Assignment 2 TABLE OF CONTENTS

Technical Assignment 2 TABLE OF CONTENTS 2 TABLE OF CONTENTS Executive Summary...3 Introduction..5 Gravity Loads......6 Design Codes......7 Materials..8 Existing Structural System.. 10 Existing Floor System 15 Alternate Floor Framing Systems...17

More information

www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council *Revised April 2014

www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council *Revised April 2014 ICC-ES Evaluation Report ESR-1647* Issued July 2013 This report is subject to renewal August 1, 2015. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

Convertible Crib and Changer (M668)

Convertible Crib and Changer (M668) Model No.: M668 PO #: Serial #: Convertible Crib and Changer (M668) THIS PRODUCT IS NOT INTENDED FOR INSTITUTIONAL OR COMMERCIAL USE. If you have any questions or missing parts, please contact us. DO NOT

More information

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors Installation Manual Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors SW602206 Rev B Table of Contents Chapter 1: Safety Warning... 3 Chapter 2: Kit Contents... 4 Included in Kit...

More information

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015 0 ICC ES Report ICC ES (800) 42 6587 (562) 699 054 www.icc es.orgg 000 Most Widely Accepted and Trusted ESR 2269 Reissued 02/205 This report is subject to renewal 02/207. DIVISION: 0 00 00 CONCRETE SECTION:

More information

A701 (6904-002018 <01>)

A701 (6904-002018 <01>) A70 () Wood Stud mm (7/6 in.).4 mm (3/3 in.) 6 mm (5/64 in.) 3 mm (/8 in.) Sanus Hwy 36 West Saint Paul, MN 553 USA Customer Service Americas: 800-359-550 65-484-7988 info@sanus.com Europe, Middle East,

More information