Section 14. Automatic Transfer Switches. BuyLog Catalog 14-1
|
|
|
- Philippa Nichols
- 9 years ago
- Views:
Transcription
1 Automatic Transfer Switches ATS (Residential) / ZTX Series ATS (Commercial) / ZTG Series ATS (Specification) / ZTS Series ATS (Specification) / ZTE Series ATS (Specification) / ZTED Series ATS (Specification) / ZTECT Series ATS (Specification) / ZBTE Series ATS (Specification) / ZBTED Series ATS (Specification) / ZBTECT Series Rev. 11/13 BuyLog Catalog 14-1
2 Introduction Automatic Transfer Switches It is imperative that emergency power systems allow for a smooth transition from a normal source to an emergency source and back again. Our automatic transfer switches are field-proven to be superior in design and reliability, regardless of the application. Model ZTX is built specifically for residential and light commercial applications. The switches are ideal for standby applications, and are available as NEMA 1 or NEMA 3R enclosed. Model ZTG is a product solution designed for standard open transition applications. Building on ZTS technology, the series uses the MX150 microprocessor control system and includes many of the most common features specified on a transfer switch. It also provides an intuitive user interface, communications capability and self-diagnostics. Model ZTGD has the features of the ZTG Series but is built for delayed transition applications that require the dependability and ease of operation of a power contactor switch. Model ZTGSE has the features of the ZTG Series but is built for a service entrance application that integrates the utility circuit breaker, optional surge protection device and power monitor into one simple coordinated package. Model ZTGDSE has the features of the ZTG Series but is built for delayed transition service entrance application that integrates the utility circuit breaker, optional surge protection device and power monitor into one simple coordinated package. Model ZTS is the building block of the transfer switch product line. Available in open type or NEMA enclosed to customer specifications, the ZTS withstand and closing ratings far exceed UL requirements and comes standard with our MX50 controller. Model ZTSD of delayed transition transfer switches allows for the full decay of rotating motors or transformer fields. They can also be used for load shedding of selected circuits or other applications. Model ZBTS Bypass-Isolation Transfer Switches are the solution when power interruption during service or testing is unacceptable. Incorporating a quick-make/quick-break manual load transfer handle and GE Zenith Controls control/interlock system, the bypass uses normal failure sensing and a time delay to start the engine automatically if a failure occurs when the automatic transfer switch (ATS) has been removed for service. Model ZBTSD Delayed Transition Transfer/Bypass-Isolation Switches incorporate the features of the ZBTS Bypass-Isolation Switch and the ZTSD unit for transfer of large motor loads, transformers, uninterruptible power supplies (UPS) systems or load shedding to a neutral off position. Model ZTSCT of closed transition switches combine ZTSD operation during a source failure with a highly engineered control system that allows momentary paralleling of two acceptable sources, limiting the impact of transfer on the load. Model ZBTSCT Closed Transition Transfer/Bypass-Isolation Switches combines all the functionality of our bypass and closed transition switches for the highest level in reliability. Model ZTSMV Medium Voltage Automatic Transfer Switches are designed for installations from 5 kv to 15 kv and loads up to 3000 amps. Model ZTE is specifically designed for large healthcare and mission-critical applications, with built-in metering, communications and advanced diagnostics. ZTE Automatic Transfer Switches go beyond simply source switching and are available from A and V. ZTE Series, Standard (Open) Transition. The GE Zenith ZTE standard (open) transition transfer switches go beyond just source switching. Integral metering and communications, high-level diagnostics and superlative flexibility make the ZTE a perfect solution for today s mission critical source switching. ZTED Series, Delayed Transition. The ZTED - Delayed Transition transfer switch offers the same features as the ZTE with the addition of an adjustable time delay in the centered "off" position. This delay allows motor loads to coast down and transformer field to decay; ensuring inductive loads are re-energized after transfer with only normal inrush starting currents. ZTECT Series, Closed Transition. The ZTECT -Closed Transition transfer switch offers the same features as the ZTE with the addition of a high-speed drive system, which ensures the overlap of the normal and alternate sources is less than 100 milliseconds. When one source is not within normal limits, such as during a power outage, the ZTECT automatically operates in delayed transition mode. 14- BuyLog Catalog Rev. 11/13
3 Introduction ZBTE Series Bypass-Isolation Transfer Switches are the solution when interruption of power during service or testing is not acceptable. Consisting of two major modules the Automatic Transfer (ATS) and the Bypass/Isolation Switch the ZBTE Series like the ZTE Series, incorporates the most advanced moicroprocessor controller in the industry as well as the same advanced rugged construction of all our ZTE Series automatic switches with a quick make/quick break bypass switch manual load transfer handle and our control/interlock system, which consists of both mechanical and electrical interlocks. ZBTE - Standard (Open) Transition Bypass/Isolation. The Zenith ZBTE Bypass/Isolation transfer switch is used in general and mixed load applications ZBTSE - Delayed Transition Bypass/Isolation. The ZBTED Bypass/Isolation transfer switch is used to transfer large motor loads, transformers, uninterruptible power supplies (UPS) systems or load shedding to a neutral "center" position. ZBTECT - Closed Transition Bypass/Isolation. The ZBTECT Bypass/Isolation transfer switch is used to transfer critical loads where a "no break" transfer is desired. Rev. 11/13 BuyLog Catalog 14-3
4 Model ZTX Features Model ZTX switches are built for residential and light commercial applications requiring the dependability and ease of operation found in a power contactor switch. Ratings 40 to 400 amps (, 3 and 4 pole) UL 1008, CSA and IEC listed to 480 VAC 50/60Hz Double throw, mechanically interlocked contactor mechanism Electrically operated, mechanically held Designed for standby applications Equipment (controls & power section) seismic test qualified to: IBC-009 IEEE Model ZTX switches are equipped with the MX60 control panel as standard. This microprocessor control includes: Undervoltage sensing (90% pickup/80% dropout) of the utility source Voltage and frequency sensing of the generator source (90% voltage/95% frequency pickup) Time Delay Engine Start 5 seconds (P) Time Delay Engine Warmup Transfer to Generator 0 seconds (W) Time Delay Utility Stabilization/Retransfer to Utility 5 minutes (T) Time Delay Engine Cool Down 5 minutes (U) All time delays are fixed. Indicating LEDs for source availability and switch position Pushbuttons for test, engine start (manual), generator exerciser and diagnostic reset Special status annunciation of in-phase transfer and timer operation Selectable 7, 14, 1 or 8 day (factory set 8 days) generator exerciser timer Diagnostic LED indications Additional options include: A3/A4 Auxiliary contacts (1 each) closed in utility and generator positions B9X 1.5 Amp/1 or 4 VDC Battery Charger ZTX Series Residential and Light Commercial Switch with MX60 Control Panel (front cover removed) MX60 Microprocessor Control Panel 14-4 BuyLog Catalog Rev. 11/13
5 Model ZTX Ordering Information Z T X Z E C Z V C M Model/Type Control Panel Application Ampere Size Switched Poles Enclosure Type Operational Voltage Accessories Z T X M B 0 1 A B A3/A4 Standard (Open Transition) MX60 Microprocessor Control Unit Utility- Generator 40 amps Poles Type 1 Enclosed Consult Table Below Auxiliary Contacts (1 each) Closed in Source 1 (normal) and Source (emergency) 0 0 No Microprocessor Control Unit amps amps Lug Configuration Amp Size Qty Per Phase and Neutral Size #8 to 3/ #6 to 50 MCM #4 to 600 MCM E 80 amps 3 Poles F 100 amps amps Product # Example ZTX000M60010E-ZEC01ZVC50M060 This number string shows the correct format for a ZTX Model Automatic Transfer Switch with MX60 micro - processor control unit, Utility-Generator, 100 amps, 3 pole, NEMA Type 1 enclosure, 480 V, 3φ, 3 wire, 60 Hz system with the standard group of accessories. Technical Specifications 8 to 85 mm 13 to 17 mm 1 to 304 mm 4 Poles 0 5 amps amps 3 R Type 3R Enclosure 0 0 Open Style Unit B9X Battery Charger 1.5 Amp/1 or 4 VDC For information on ZTX OEM plans, please consult your GE representative A B Voltage Phase Config. Hz wire / wire / wire wire wire wire / wire /0 3 4 wire / wire / wire / wire /0 3 4 wire /0 3 4 wire wire wire wire wire wire / wire / wire wire / wire wire wire / wire / wire / wire / wire wire 60 Note: Operating voltage must be specified at time of order. Only the most common voltages are shown above. Dimensions Ampere NEMA 1 NEMA 3R Poles Rating Height Width Depth Height Width Depth 40-5, 3, , 3, UL 1008 Withstand and Closing Ratings Please refer to GE Zenith Controls Bulletin TB-110. Rev. 11/13 BuyLog Catalog 14-5
6 Models ZTG and ZTGD Features Model ZTG switches are built for standard applications requiring the dependability and ease of operation found in a power contactor switch. Ratings 40 to 3000 amps (, 3 or 4 poles) UL 1008 listed at 480 VAC CSA certified at 600 VAC (00-60 amp-480v) IEC listed at 480V Equipment (controls and power section) seismic test qualified to: IBC 009 IEEE Double throw, mechanically interlocked contactor mechanism Electrically operated, mechanically held Designed for emergency and standby applications Available in standard (ZTG) or delayed transition (ZTGD) models ZTG switches are equipped with GE Zenith s next-generation MX150 microprocessor panel, which controls the operation and displays the status of the transfer switch s position, timers and available sources. As an embedded digital controller, the MX150 offers high reliability and ease of unattended operation across a range of applications. The MX150 features include: Timer and voltage/frequency settings adjustable without disconnection from the power section Built-in diagnostics with LCD displays for immediate troubleshooting LED/LCD indicators for ease of viewing and long life Nonvolatile memory clock battery backup not required for standard switch operation Processor and digital circuitry isolated from line voltage Inputs optoisolated for high electrical immunity to transients and noise Communications header for network interface Fully Approved UL, CSA and IEC listed IBC 009 IEEE Ringing wave immunity per IEEE 47 (ANSI C37.90A) Conducted and Radiated Emissions per EN550 Class B (CISPR ) (Exceeds EN55011 and MILSTD 461 Class 3) ESD immunity test per EN Class B (Level 4) Radiated RF, electromagnetic field immunity test per EN (ENV50140) 10v/m Electrical fast transient/burst immunity test per EN Surge immunity test per EN IEEE C6.41 (1. X 50µs, 0.5 and 4 kv) Conducted immunity test per EN (ENV50141) Voltage dips and interruption immunity EN Design and Construction Features Close differential 3 phase under-voltage sensing of the normal source factory standard setting 90% pickup, 80% dropout (adjustable); under-frequency sensing of the normal source factory setting 95% pickup (adjustable) Voltage and frequency sensing of the emergency source factory standard setting 90% pickup voltage, 95% pickup frequency (adjustable) Test switch (fast test/load/no load) to simulate normal source failure automatically bypassed should the emergency source fail Type 1 enclosure is standard also available in open style or Types 3R, 4, 4X or BuyLog Catalog Rev. 11/13
7 Models ZTG and ZTGD Options 6A 6AP A1 A1E A3 A4 A6 ATGEW-X CTAP DS HT LCM MCM Test Switch, Maintained Test Switch, Maintained Programmable Auxiliary Contact, operates on Source 1 line failure Auxiliary Contact, operates on Source line failure Auxiliary Contacts: Closed when the transfer switch is in Source position Auxiliary Contacts: Closed when the transfer switch is in Source 1 position Sequential Universal Motor Load Disconnect Circuit. Normally closed Auxiliary contacts for Motor Loads. Open 0-60 seconds pior to transfer, after transfer, or both in either direction then reclose in timed sequence after transfer. Extended annual parts and labor warranty (1-4 years for a total of 5 years max.) Alarm panel on transfer to emergency w/silence button & light Inhibits transfer in either direction when in inhibit. Allows automatic operation when in Auto (Standard on 800A and above) Heater and Thermostat LonWorks Communication Module Modbus RTU Communication Module UMD Universal Motor Load Disconnect Circuit: Auxiliary Contact opens 0-5 minutes prior to transfer in either direction, re-closes after transfer. Can be configured by end user for Pre-transfer, Post-transfer, or both. VI Voltage Imbalance Monitor (Three Phase) NOTE: For applications requiring additional options or other configurations, use GE Zenith Factory. M90 Series Power Measurement Meters (Not available in NEMA 4 enclosure) M90 EPM000 True RMS Digital Meter with display (Amps, Volts, Power, Energy, Power Factory and Frequency). 3 Line LED Display. 50/60 Hz Universal Operation. 1 or 3 phase. Standard Modbus RTU RS485 communications capability Amps. M90A Adds Pre-Wiring for Enervista Viewpoint Monitoring of M90 Accessory & ATS Status using Modbus RS485 Serial Communications M90B Adds Pre-Wiring for Enervista Viewpoint Monitoring of M90 Accessory & ATS Status using Ethernet TCP/IP Communications M91 EPM6000 True RMS Digital Meter with display (Amps, Volts, Power, Energy, Power Factory and Frequency, THD). Certified energy and demand metering. Meets ANSI C1.0 and IEC 687 Accuracy Classes. Front IrDA Port Laptop Connection. Standard Modbus RTU RS485 or DNP 3.0 communications capability. M91A Adds Pre-Wiring for Enervista Viewpoint Monitoring of M91 Accessory & ATS Status using Modbus RS485 Serial Communications M91B Adds Pre-Wiring for Enervista Viewpoint Monitoring of M91 Accessory & ATS Status using Ethernet TCP/IP Communications OCVR-1SG Lockable see-through microprocessor cover for NEMA OCVR-1SS 3R or 1 Lockable see-through microprocessor and meters cover for NEMA 3R or 1 T3/W3 Elevator Pre-Signal Auxiliary Contacts: Open 0-60 seconds prior to transfer to either direction, re-closes after transfer. Rev. 11/13 BuyLog Catalog 14-7
8 Model ZTG Reference Charts Testing Standards UL, CSA and IEC listed UL 1008, CSA. No. 178, IEC Ringing wave immunity IEEE 47 (ANSI C37.90A) Conducted and Radiated Emissions EN550 Class B (CISPR ) (Exceeds EN55011 & MILSTD 461 Class 3) ESD immunity test EN Class B (Level 4) Radiated RF, electromagnetic field immunity test EN (ENV50140) 10v/m Electrical fast, transient/burst immunity test EN Surge immunity test EN IEEE C X 50µs, 0.5 & 4 kv Conducted immunity test EN (ENV50141) Voltage dips and interruption immunity EN ZTG AL/CU UL Listed Solderless Screw-Type Terminals for External Power Connections 1 Normal, Emergency and Load Terminals Switch Size (Amps) Cables per Phase & Neutral Range of Wire Sizes #8 to 3/ mm #6 to 50 MCM mm 00, 5 60 #6 to 350 MCM mm #4 to 600 MCM mm , 1000, # to 600 MCM mm 1600, 000, 600, # to 600 MCM mm 1 For ZTGD Series data, contact the GE Zenith factory Standard MX150 Control Setting Ranges MSTDG MEXEG Options Control Function Range Factory Setting Source 1 Line Sensing Under-voltage Dropout/Pickup 75-98% 80% % 90% Source Line Sensing Under-voltage Dropout/Pickup 75-98% 80% % 90% Source Line Sensing Under-frequency Dropout/Pickup 88-98% 90% % 95% Time Delay Engine Start (Acc. P1) 0-10 seconds 3 seconds Time Delay Engine Cool Down (Acc. U) 0-60 minutes 5 minutes Time Delay Transfer to Source (Acc. W) 0-5 minutes 1 second Time Delay Retransfer to Source 1 (Acc. T) 0-60 minutes 30 minutes Time Delay Motor Disconnect or Transfer Presignal (Acc. UMD, or T3/W3) 0-60 seconds 0 seconds Delayed Transition Time Delays (DT, DW) 0-10 minutes 5 seconds Event Exerciser (CDT) 5-60 min.-1,7,14 or 8 days load or no load 0 min. - 7 days no load Programmable Event Exerciser (CDP) 365 day cycle, load or no load 0 min. - 7 days no load Voltage Imbalance (VI) 5-0% nominal; sec. 10% Fail, 8% Restore; 30 sec. Elevator Pre-Signal (T3/W3) 0-60 seconds 0 seconds Sequential Motor Load Disconnect (A6) 0-5 minutes 0 seconds Motor Load Disconnect (UMD) 0-60 seconds 5 seconds 14-8 BuyLog Catalog Rev. 11/13
9 ZTG Series Ordering Information Z A 0 Z E C Z V C Model/Type Control Panel Application Ampere Size Switched Poles Z T G A B Standard (Open Transition) Z T G D 0 0 Delayed Transition Entelli-Switch 150 Microprocessor Control Unit Utility- Generator 40 amps Poles U E Utility- Utility 80 amps 3 Poles M F Manual Transfer Switch Types Standard: Unless otherwise noted, the standard switch with quick transfer will be supplied. Delayed Transition: When ordered as the ZTGD, the delayed transition switch offers time delay during transfer from one position to the other. This is primarily for transfer of large motor or inductive loads. The operation of the delayed transition switch is totally independent of the synchronism of the power sources, eliminating the need for in-phase monitors or extensive motor-disconnect control wiring between the transfer switch and motor control centers. Product # Example ZTG000A00040F-ZEC01ZVC40MSTD This number string shows the correct format for a ZTG Series Automatic Transfer Switch with an MX150 microprocessor control unit, Utility - Generator, 400 amps, 4 pole, NEMA Type 1 enclosure, 10/08V 3φ, 4 wire, 60 Hz system with the standard group of accessories. UL 1008 Withstand and Closing Ratings Please refer to GE Zenith Controls Bulletin TB amps amps amps 0 5 amps amps amps amps amps amps amps amps amps amps amps 4 Poles Enclosure Type 0 1 Type 1 Enclosed 1 Type 1 Enclosure 3 R Type 3R Enclosure 4 0 Type 4 Enclosure 4 X Type 4X Enclosure 0 0 Open Style Unit Operational Voltage A B M S T D Consult Table Below A B Voltage Phase Config. Hz wire / wire / wire wire wire wire / wire /0 3 4 wire / wire / wire / wire /0 3 4 wire /0 3 4 wire wire wire wire wire wire / wire wire / wire / wire wire / wire wire /40 4/5 wire wire / wire / wire / wire / wire wire 60 Note: Operating voltage must be specified at time of order. Only the most common voltages are shown above. Accessories M E X E M A N O Then choose additional accessories 6A 6AP A1 A1E A3 A4 A6 ATGEW-X CTAP DS HT LCM M90 M90A M90B M91 M91A M91B MCM OCVR-15G OCVR-1SS T3/W3 UMD VI None Rev. 11/13 BuyLog Catalog 14-9
10 Models ZTG and ZTGD Dimensional and Weight Specifications NEMA 1 Weight Ampere Ref. Open NEMA Application Model Rating Poles Height (A) Width (B) Depth (C) Figure Type 1 Notes ZTG ZTGD 40, , , 60, , 1000, , , , , , 5 60, , 1000, , , 3000, 3 4 (61) 18 (46) 11 (8) A 1 (10) 57 (6) 4 4 (61) 18 (46) 11 (8) A 1 (10) 60 (7), 3 4 (61) 18 (46) 11 (8) A 1 (10) 57 (6) 4 4 (61) 18 (46) 11 (8) A 1 (10) 60 (7), 3 4 (61) 18 (46) 11 (8) A 1 (10) 57 (6) 4 4 (61) 18 (46) 11 (8) A 1 (10) 60 (7), 3 46 (117) 4 (61) 14 (36) A 70 (3) 175 (80) 4 46 (117) 4 (61) 14 (36) A 75 (34) 180 (8), 3 66 (168) 4 (61) 19.5 (50) B 165 (75) 400 (450) 4 66 (168) 4 (61) 19.5 (50) B 185 (84) 450 (04), 3 74 (188) 40 (10) 19.5 (50) B 190 (86) 455 (06) 4 74 (188) 40 (10) 19.5 (50) B 10 (95) 540 (45) 3 90 (9) 35.5 (90) 48 (1) C 345 (156) 1010 (458) 4 90 (9) 35.5 (90) 48 (1) C 450 (04) 1160 (56) 3 90 (9) 35.5 (90) 48 (1) C 465 (11) 1010 (458) 4 90 (9) 35.5 (90) 48 (1) C 670 (304) 1160 (56), 3 46 (117) 4 (61) 14 (36) A 1 (10) 57 (6) 4 46 (117) 4 (61) 14 (36) A 1 (10) 60 (7), 3 46 (117) 4 (61) 14 (36) A 1 (10) 57 (6) 4 46 (117) 4 (61) 14 (36) A 1 (10) 60 (7), 3 46 (117) 4 (61) 14 (36) A 1 (10) 57 (6) 4 46 (117) 4 (61) 14 (36) A 1 (10) 60 (7), 3 46 (117) 4 (61) 14 (36) A 80 (36) 0 (100) 4 46 (117) 4 (61) 14 (36) A 85 (39) 30 (10), 3 66 (168) 4 (61) 19.5 (50) B 185 (84) 400 (181) 4 66 (168) 4 (61) 19.5 (50) B 05 (93) 450 (04), 3 74 (188) 40 (10) 19.5 (50) B 10 (95) 475 (15) 4 74 (188) 40 (10) 19.5 (50) B 30 (104) 560 (54) 3 90 (9) 35.5 (90) 48 (1) C 365 (166) 1010 (458) 4 90 (9) 35.5 (90) 48 (1) C 470 (04) 1160 (56) 3 90 (9) 35.5 (90) 48 (1) C 485 (0) 1130 (513) 4 90 (9) 35.5 (90) 48 (1) C 690 (313) 1395 (633) , 7 1-5, 7 1-5, , , 7 1-5, 7 1-5, , 7-8 Application Notes: 1. Metric dimensions (cm) and weights (kg) shown in parentheses adjacent to English measurements.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, lights, switches, pushbuttons, etc. 3. All dimensions and weights are approximate and subject to change. 4. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 5. Special enclosure (NEMA 3R, 4, 4X, 1, etc.) dimensions and layouts may differ. Consult the GE Zenith factory for details. 6. A ZTG(D) 40-5A, when ordered with the following options, will require a larger enclosure: A6(T), Digital Meter, HT, OCVR-1SG, OCVR-1SS. Contact the GE Zenith factory for dimensions. 7. Add 3" in height for removable lifting eyes. 8. Ventilation louvers on side and rear of enclosure at amps. One set of louvers must be clear for airflow with standard cable connections. Reference Figures Figure A Figure B Figure C BuyLog Catalog Rev. 11/13
11 Models ZTGSE and ZTGDSE Features While providing the functionality of an automatic transfer switch the ZTGSE integrates the utility circuit breaker, optional surge protection device and power monitor into one simple coordinated package. Suitable for use as Service Entrance equipment Ratings 40 to 3000 amps (, 3 or 4 poles) UL 1008 listed at 480 Vac Double throw, mechanically interlocked contactor mechanism Electrically operated, mechanically held Designed for emergency and standby applications Optional Load center for multiple loadside connections available up to 40 volts Additional options include battery charger, GFP, shunt trip selector, power monitor and surge protection device Available with delayed transition feature ZTGSE switches are equipped with GE Zenith s next-generation MX150 microprocessor panel, which controls the operation and displays the status of the transfer switch s position, timers and available sources. As an embedded digital controller, the MX150 offers high reliability and ease of unattended operation across a range of applications. The MX150 features include: Timer and voltage/frequency settings adjustable without disconnection from the power section Built-in diagnostics with an LCD display for immediate troubleshooting LED/LCD indicators for ease of viewing and long life Nonvolatile memory clock battery backup not required for standard switch operation Processor and digital circuitry isolated from line voltage Inputs optoisolated for high electrical immunity to transients and noise Communications header for network interface Fully Approved UL891, UL1008, CSA. Ringing wave immunity per IEEE 47 (ANSI C37.90A). Conducted and Radiated Emissions per EN550 Class B (CISPR 11) (Exceeds EN55011 & MILSTD 461 Class 3) ESD immunity test per EN (Level 4) Radiated RF, electromagnetic field immunity test per EN (ENV50140) 10v/m Electrical fast transient/burst immunity test per EN Surge immunity test per EN IEEE C6.41 (1. X 50ms, 5 & 8 kv) Conducted immunity test per EN (ENV50141) Voltage dips and interruption immunity EN Design and Construction Features Includes Normal (Source 1) molded or insulated case style circuit breaker or 3 pole Includes mechanical lug connections for cables Close differential 3 phase under-voltage sensing of the normal source factory standard setting 90% pickup, 80% dropout (adjustable); under-frequency sensing of the normal source factory setting 95% pickup (adjustable) Voltage and frequency sensing of the emergency source factory standard setting 90% pickup voltage, 95% pickup frequency (adjustable) Test switch (fast test/load/no load) to simulate normal source failure automatically bypassed should the emergency source fail NEMA Type 1 enclosure is standard with optional NEMA 3R available Ground fault protection is standard 1000A and above Disconnect link on Neutral and Ground Rev. 11/13 BuyLog Catalog 14-11
12 Models ZTGSE and ZTGDSE Reference Charts Testing Standards UL, CSA UL 1008, UL891, CSA. Ringing wave immunity IEEE 47 (ANSI C37.90A) Conducted and Radiated Emissions EN550 Class B (CISPR 11) (Exceeds EN55011 & MILSTD 461 Class 3) ESD immunity test EN (Level 4) Radiated RF, electromagnetic field immunity test EN (ENV50140) 10v/m Electrical fast, transient/burst immunity test EN Surge immunity test EN IEEE C X 50µs, 5 & 8 kv Conducted immunity test EN (ENV50141) Voltage dips and interruption immunity EN AL/CU UL Listed Solderless Screw-Type Terminals for External Power Connections Normal, Emergency and Load Terminals Switch Size (Amps) Cables per Pole Range of Wire Sizes 40, 80, 100, 150 #8 to 3/0 AWG 8-85 mm 00, 5 #6 AWG to 50 MCM mm 1 60 #6 AWG to 350 MCM mm 400 #4 AWG to 600 MCM mm # AWG to 600 MCM mm 14-1 BuyLog Catalog Rev. 11/13
13 Models ZTGSE and ZTGDSE Ordering Information Z T G S E 0 A 0 0 Base Model Type Control Config. Ampere Size Switched Panel Poles N 0 1 M S T D G Enclosure Type Operational Voltage Accessories S Standard (Open Transition Transfer Switch) D E 0 Standard (Delayed Transition Transfer Switch) A 0 MX150 Utility - Microprocessor Generator Control Unit Product # Example ZTGSE0A0040E-N0140MSTDG This number string shows the correct format for a ZTGSE Series Automatic Transfer Switch with an MX150 microprocessor control unit, Utility - Generator application, 400 amps, 3 pole, NEMA Type 1 enclosure, 10/08V 3Ø, 4 wire, 60 Hz system with the standard group of accessories. Withstand Current Ratings per UL1008 S E B N 0 1 A B amps amps amps amps 0 00 amps 0 amps 6 60 amps amps amps amps Poles E 3 Poles F 4 Poles Type 1 Enclosure N 3 R Type 3R Enclosure Consult Table Below M S T If Required, choose additional accessories. A B Voltage Phase Config. Hz wire / wire / wire wire wire wire / wire /0 3 4 wire / wire / wire / wire /0 3 4 wire /0 3 4 wire wire wire wire wire wire / wire wire / wire / wire wire / wire wire /40 4/5 wire wire / wire / wire / wire / wire wire 60 Note: Will need to specify with order the operating voltage. Only the most common ones are shown here D G M E X E G Maximum Circuit Amps ZTGSE Maximum Circuit Amps When Used With ZTGDSE When Used With Switch Current Specific Switch Specific Ratings Limiting Fuse Coordinated Ratings Coordinated (Amps) ZTGSE/ZTGDSE Breaker Rating (Amps) Breaker Rating 40, 80, 100, 30, , 00, 5 40, 80, 100, , ,000 35,000 5, 60, 400, , , ,000 Rev. 11/13 BuyLog Catalog 14-13
14 Models ZTGSE and ZTGDSE Dimensional Specifications ZTGSE and ZTGDSE Model Transfer Switches NEMA 1 Enclosure NEMA 3R Enclosure Model Ampere Rating Poles H W D Ref. Fig. H W D Ref. Fig. App. Notes 40-80, 3, 4 51(130) 8(71) 16(41) A 51(130) 9(74) 0(51) A , 3, 4 51(130) 8(71) 16(41) A 51(130) 9(74) 0(51) A 1-5 5, 3, 4 51(130) 8(71) 16(41) A 51(130) 9(74) 0(51) A 1-5 ZTGSE/ 60, 3, 4 51(130) 8(71) 16(41) A 51(130) 9(74) 0(51) A 1-5 ZTGDSE 400, 3, 4 51(130) 8(71) 16(41) A 51(130) 9(74) 0(51) A , 3, 4 73(185) 34(86) 0(51) B 73(185) 34(86) 4(61) B , 3 73(185) 34(86) 0(51) B 73(185) 34(86) 4(61) B (185) 40(10) 0(51) B 73(185) 40(10) 4(61) B 1-6 Application Notes: 1. Metric dimensions (cm) and weights (kg) shown in parentheses adjacent to English measurements.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, lights, switches, pushbuttons, etc. 3. All dimensions and weights are approximate and subject to change. 4. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 5. Add 4 inches in depth for NEMA 3R enclosure. 6. Add 3 in height for lifting eyes. 7. Contact factory for dimensional and weight information for 1000 Amps and above. Weights Model Amp Rtg Poles NEMA 1 Weight NEMA 3R Weight 157(71) 1(96) (7) 14(97) 4 163(74) 18(99) 16(74) 17(99) (75) 19(99) 4 168(76) 3(101) 169(77) 4(10) (78) 6(103) 4 175(79) 30(104) 178(81) 33(106) ZTGSE (83) 38(108) 4 187(85) 4(110) 54(115) 309(140) (10) 30(145) 4 89(131) 344(156) 467(1) 55(50) (19) 568(57) 4 51(3) 597(71) 567(57) 65(96) (6) 66(300) 4 66(300) 767(348) 6(119) 317(144) (14) 38(149) 4 96(134) 351(159) 475(15) 560(54) ZTGDSE () 576(61) 4 50(36) 605(74) 570(59) 655(97) (63) 665(30) 4 665(30) 770(349) Reference Figures D W D W H H Figure A ZTGSE Series Transfer Switch ( Amp) Figure B ZTGSE Series Transfer Switch ( Amp) BuyLog Catalog Rev. 11/13
15 ZTS Series ZTS Series Automatic Transfer Switches An Introduction to the ZTS Series of Automatic Transfer Switches Since its introduction, the GE Zenith ZTS Series of transfer switches has become a hallmark of quality and performance. Reliability resulting from superior design and heavy duty construction has made the ZTS the industry standard for critical installations. Our emphasis on research and development, design improvements, materials, manufacturing methods, quality assurance, and service yields products that have been proven in hundreds of thousands of applications. Our engineering staff has been dedicated to the improvement and expansion of our line. Today, GE Zenith offers the widest selection of transfer switch products worldwide. ZTS Automatic Transfer Switches Amps ZTSD Delayed Transition Transfer Switches Amps ZTSCT Closed Transition Transfer Switches Amps ZBTS Automatic Transfer/Bypass Switches Amps ZBTSD Delayed Transition Bypass Switches Amps ZBTSCT Closed Transition Bypass Switches Amps ZTSMV Medium Voltage Switches Amps All ZTS products meet or exceed industry requirements allowing specification and installation confidence. UL 1008 listed through 480 VAC CSA C. No. 178 listed through 600 VAC IEC listed through 480 VAC Codes and Standards NFPA 70, 99, 101, 110 IEEE 446, 41 NEC 517, 700, 701, 70 NEMA ICS-447 Controls tested in accordance with: IEEE 47 (ANSI C37.90A) EN550 Class B (CISPR ) (Exceeds EN55011 & MILSTD 461 Class 3) EN (Level 4) EN (ENV50140) 10 v/m EN EN , IEEE C6.41 (1. X 50µs, 0.5 & 4 kv) EN (ENV50141) EN Enclosures meet the requirements of: UL 508, 50 ANSI C33.76 ICS 6 NEMA 50 Quality System: ISO 9001 Registered Equipment (controls and power section) seismic tested to: IBC 009 IEEE Rev. 11/13 BuyLog Catalog 14-15
16 Model ZTS Model ZTS Automatic Transfer Switches The ZTS Model is the foundation of the transfer switch product line. This ruggedly built power contactor family of switches has been specifically designed for transfer switch duty with dependability, versatility and user friendliness of prime concern. ZTS switches are available in open type construction for switchboard installation or NEMA enclosed to the customer s specifications. The power panel components, consisting of power switching contacts, drive mechanism and terminal lugs, are mounted on a specially formed panel. Logic devices including microprocessor control auxiliary time delays and special accessory equipment are assembled on the door for ease of maintenance and separation from the power section. They are connected with a numbered wiring harness equipped with a disconnect plug that allows isolation of the control panel for maintenance. ZTS Model Operation When the normal source fails or the voltage drops to a predetermined point (usually 80% of nominal), if required, a circuit is closed to start the engine generator set. When the emergency source reaches 90% of rated voltage and 95% of rated frequency, the drive solenoid is energized through the emergency coil control relay, causing the main contacts to disconnect the load from the normal source and connect it to the emergency source. After the drive solenoid has completed its electrical stroke and is seated, the emergency coil control relay opens to disconnect it. The transfer switch is now mechanically locked in the emergency position. When normal voltage is restored to a predetermined point (usually 90% of nominal), the control voltage sensing energizes. The normal side coil relay closes, and after the drive solenoid has completed its electrical stroke and is seated, the coil control relay opens to disconnect it. The transfer switch is now mechanically locked in the normal position. Drive Mechanism All GE Zenith ZTS switches employ the simple over-center principle to achieve a mechanically locked position in either normal or emergency. GE Zenith s high speed drive assures contact transfer in 100 ms or less. High contact pressure and positive mechanical lock allow for high withstand and closing ratings, far exceeding UL requirements. All ATS units are listed with UL umbrella breaker and current limiting fuse ratings. Ratings Ratings 40 to 4000 amperes, 3 or 4 Poles Open type, NEMA 1, 3R, 4, 4X and 1 Available to 600 VAC, 50 or 60 Hz Suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 amps UL 1008 listed at 480 VAC CSA C. No. 178 certified at 600 VAC IEC listed at 480 VAC Equipment (controls and power section) seismic test qualified to: IBC 009 IEEE Performance Features Contact transfer speed less than 100 milliseconds High close-in and withstand capability Temperature rise test per UL 1008 conducted after overload and endurance tests - exceeds UL requirements Available in: ZTS (utility-generator) ZTSU (utility-utility) ZTSG (generator-generator) ZTSM (manual) configurations Design and Construction Features Double throw, interlocked operation Electrically operated, mechanically held by a simple, overcenter mechanism Segmented silver tungsten alloy contacts with separate arcing contacts on 600 amp and above Arc quenching grids, enclosed arc chambers, and wide contact air gap for superior source-to-source isolation on all units Control disconnect switch for safe maintenance Components accessible for inspection and maintenance without removal of the switch or the power conductors Mechanical indicator and contact chamber cover designed for inspection, safety and position designation BuyLog Catalog Rev. 11/13
17 Model ZTSD Model ZTSD Automatic Transfer Switches The ZTSD Model provides an adjustable time delay after the opening of the closed contacts and before the closing of the open contacts for transferring large motor and/or transformer loads. This delayed transition time allows for motors to coast down and transformer fields to decay, thus allowing inductive loads to be reenergized after transfer with only normal inrush starting currents. The delayed transition design is an effective method of handling these applications and can be utilized as an alternative to a standard transfer switch equipped with an in-phase monitor. The delayed transition transfer switch is ideally suited for pumping stations, sewage treatment plants, hospital X-ray equipment, or wherever the bulk of the load being controlled consists of large motors and/or transformers. Major UPS manufacturers strongly recommend the use of delayed transition type transfer switches to ensure proper operation of their rectifier circuit and battery system. The ZTSD Model allows a UPS system sufficient delay to recognize a power failure and transfer to batteries, acknowledge the return of power and allow the rectifier to walk onto the new source, reducing any transfer anomalies. Except for the delayed transition period, the performance, operating capabilities, ratings, UL listings, with-stand current values and available options are identical to those of the GE Zenith ZTS Series Automatic Transfer Switches. The ZTSD incorporates all of the important features of the standard ZTS Series switches as well as features oriented toward its specific operation. ZTSD Delayed Transition Transfer Switch 400 amp, 3 pole (shown) N 1 Open L Ratings Ratings 40 to 4000 amperes, 3 or 4 Poles Open type, NEMA1, 3R, 4, 4X and 1 Available to 600 VAC, 50 or 60 Hz Suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 amps UL 1008 listed at 480 VAC CSA C. No. 178 certified at 600 VAC IEC listed at 480 VAC Equipment (controls and power section) seismic test qualified to: IBC 009 IEEE Performance Features Adjustable center-off time to meet specific installation requirements High close-in and withstand capability Temperature rise test per UL 1008 conducted after overload and endurance tests - exceeds UL requirements Available in: ZTSD (utility-generator) ZTSDU (utility-utility) ZTSDG (generator-generator) ZTSDM (manual) configurations Design and Construction Features Mechanically interlocked center-off position for load decay Electrically operated, mechanically held by a simple, over-center mechanism Segmented silver tungsten alloy contacts with separate arcing contacts on 600 amp and above Arc quenching grids, enclosed arc chambers, and wide contact air gap for superior source-to-source isolation on all units Control circuit disconnect plug and drive inhibit switch for safe maintenance Components accessible for inspection and maintenance without removal of the switch or the power conductors Mechanical indicator and contact chamber cover designed for inspection, safety and position designation E Rev. 11/13 BuyLog Catalog 14-17
18 Model ZTSCT Model ZTSCT Closed Transition Transfer Switches An automatic transfer switch is the single vital link between utility and alternate power supplies. Yet it is the very operation and retransfer back to normal that may be the cause of concern for many users. Loads such as electronic equipment, HID lighting, motor starters, etc., are sensitive to even the millisecond outage experienced during a typical transfer switch operation. Therefore, testing and use of the standby system is not optimized and necessary system checks are not performed because of concerns about the effects of transfer. In addition to these applications, opportunities for peak shaving and utility incentive rates may be passed over because of the inability to accept the short power interruptions inflicted during operation. In response to the needs of these installations, GE Zenith offers the ZTSCT Closed Transition Transfer Switch and ZBTSCT Closed Transition Transfer/Bypass Switch. These products utilize the proven switching technology of the ZTS/ZTSD Models of transfer switches combined with controls developed during GE Zenith s years of experience in the manufacture of synchronizing switchgear. They provide the capability to transfer in a closed transition mode when both sources are within preset parameters. Utilizing GE Zenith s high speed drive system, the overlap of the normal and alternate sources is less than 100 milliseconds. When one source is not within specified limits, such as during a power failure, the ZTSCT operates in an open transition mode. Description and Operation Closed transition switches have two basic modes of operation. During a failure of one source or an out of specification condition, the ZTSCT Model operates as a delayed transition switch (ZTSD Model). This sequence allows clear separation of an unreliable source from an available one. ZTSCT Closed Transition Transfer Switch 800 amp, 3 pole Closed transition operation takes place when both sources are within preset voltage and frequency parameters and the phase angle differential is less than five degrees. The closed transition sequence may be initiated by the test switch, a load exerciser clock, peak shaving controls or special utility incentive rate signals. Ratings Ratings 100 to 4000 amperes, 3 or 4 Poles Open type, NEMA 1, 3R, 4, 4X and 1 Available in Transfer Switch (ZTSCT) or Transfer/Bypass Switch (ZBTSCT) styles Suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 amps UL 1008 listed at 480 VAC CSA certified at 600 VAC IEC listed at 480 VAC Equipment (controls and power section) seismic test qualified to: IBC 009 IEEE Performance Features Incorporates the applicable features of the ZTS and ZBTS Series Source parallel time of less than 100 milliseconds Closed transition operation (no power interruption) during transfer and retransfer when sources are within specified parameters Open transition transfer operation is initiated upon a source failure Available in: ZTSCT (utility-generator) ZTSCTU (utility-utility) ZTSCTM (manual) configurations Design and Construction Features Electrically operated, mechanically held Segmented silver tungsten alloy contacts with separate arcing contacts on 600 amps and above Arc quenching grids, enclosed arc chambers, and wide contact air gap Components accessible for inspection and maintenance without removal of the switch or the power conductors Standard annunciation and operational selection package for user interface Active control of the generator governor not required, but is available as an option BuyLog Catalog Rev. 11/13
19 Models ZBTS, ZBTSD and ZBTSCT Models ZBTS, ZBTSD and ZBTSCT Bypass-Isolation Transfer Switches The ZBTS Model Bypass-Isolation Transfer Switch consists of two major modules the automatic transfer and the bypass-isolation switch. The automatic transfer switch module is the proven GE Zenith ZTS Series, built in ZTS, ZTSD or ZTSCT configuration and constructed for reliable operation. The same components, heavyduty silver alloy contacts, rugged drive mechanism and silver plated bus bar inter-connections are used throughout the ZBTS Model. The bypass section is a basic ZTS switch provided with a quick make/quick break manual load transfer handle and GE Zenith s control/interlock system consisting of both mechanical and electrical interlocks. The bypass is equipped with normal failure sensing and a time delay to start the engine automatically if the ATS has been removed for service and a failure occurs. The modules are mounted in a compact enclosure and completely interconnected requiring only the normal source, emergency source and load cable connections. Once installed, no cables need to be removed to isolate the transfer switch module for maintenance or inspection. The automatic transfer switch may be withdrawn for testing or maintenance without disturbing the load. The transfer switch module has three positions: ZBTS Transfer/Bypass-Isolation Transfer Switch 100 amp, 3 pole (shown) 1. Automatic: The transfer switch is carrying the load, and the bypass switch is in the open position. This is the normal operating mode.. Test: The bypass switch is closed and feeding the load. The transfer switch has control power and may be operated for test purposes via the test switch on the enclosure door. 3. Isolate: The transfer switch is withdrawn from all power and ready for maintenance. The load is served by the bypass switch. The ZTS Transfer Switch is installed on a draw-out mechanism, with electrical and mechanical interlocks for secure removal after the load has been bypassed. The ZTS control/logic panel is mounted on the enclosure door and connected by a wire harness and multi-pin disconnect plugs. The transfer switch and/or the control panel may be tested, isolated and removed for maintenance without load interruption. The bypass-isolation switch module is the same basic design as the transfer switch module and has the same electrical ratings. Manually operated, it features high speed, quick make/quick break contact action. The bypass-isolation switch has three basic positions: 1. Automatic: Normal bypass contacts open, emergency bypass contacts open.. Bypass Normal: Normal bypass contacts closed, emergency bypass contacts open. 3. Bypass Emergency: Normal bypass contacts open, emergency bypass contacts closed. GE Zenith s design requires no additional load break contacts which cause load interruption during bypass-isolation functions. The bypass-isolation switch contacts are out of the system current path except during actual bypass operation. Therefore, they are not constantly exposed to the destructive effects of potential fault currents. The normal, emergency and load are connected between the automatic transfer switch and the bypass-isolation switch through solidly braced isolating contacts that are open when the transfer switch is isolated. All current carrying components provide high withstand current ratings in excess of those specified in UL 1008 standards. Rev. 11/13 BuyLog Catalog 14-19
20 Models ZBTS, ZBTSD and ZBTSCT Models ZBTS, ZBTSD and ZBTSCT Bypass-Isolation Transfer Switches (Continued) Interlocks and Indicators Every ZBTS Model Bypass-Isolation Transfer Switch is supplied with all necessary electrical and mechanical interlocks to prevent improper sequence of operation as well as the necessary interlocking circuit for engine starting integrity. Each ZBTS is furnished with a detailed step by step operating instruction plate as well as the following functional diagnostic lights: Normal Source Available Emergency Source Available Bypass Switch in Normal Position Bypass Switch in Emergency Position Automatic Transfer Switch in Test Position Automatic Transfer Switch Isolated Automatic Transfer Switch Inhibit Automatic Transfer Switch Operator Disconnect Switch Off Automatic Transfer Switch in Normal Position Automatic Transfer Switch in Emergency Position ZBTSCT Model Closed Transition Transfer/Bypass-Isolation Switches The ZTSCT Closed Transition Transfer Switch may be applied with a bypass-isolation switch for the utmost in reliability and versatility. The ZBTSCT Series provides the ability to withdraw the transfer switch unit for maintenance or inspection. Reference the ZTSCT unit features and operational description for more details. ZBTSD Model Delayed Transition Transfer/Bypass-Isolation Switches The ZTSD Delayed Transition Transfer Switch with a timed centeroff position is available in a bypass configuration. The ZBTSD Series Bypass incorporates the features of both the ZBTS Bypass-Isolation Switch and the ZTSD unit for transfer of large motor loads, transformers, UPS systems or load shedding to a neutral Off position. Reference the ZTSD unit features and operational description for more details. Ratings Ratings 100 to 4000 amperes, 3 or 4 Poles Open type, NEMA 1, 3R, 4, 4X and 1 Available with ZTS, ZTSD and ZTSCT Series Transfer Switch Bypass and transfer switch have identical ratings Suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 amps UL 1008 listed at 480 VAC CSA C. No. 178 certified at 600 VAC IEC listed at 480 VAC Equipment (controls and power section) seismic test qualified to: IBC 009 IEEE Performance Features Load is not interrupted during bypass operation High close-in and withstand capability Temperature rise test per UL 1008 conducted after overload and endurance tests - exceeds UL requirements Available in: ZBTS (utility-generator) ZBTSU (utility-utility) ZBTSG (generator-generator) ZBTSM (manual) configurations; models include standard, delayed and closed transition Design and Construction Features Transfer switch is located on a draw out mechanism to facilitate maintenance Emergency power systems can be electrically tested without disturbing the load Power cables do not have to be disconnected to remove the transfer switch Bypass to any available source with transfer switch removed Engine start circuit maintained during bypass operation; normal power failure causes engine start contact closure even with the ATS removed Diagnostic lights and detailed instructions for simple step-bystep operation Mechanical and electrical interlocks ensure proper sequence of operation Bypass switch contacts are closed only during the bypassisolation operation Silver plated copper bus interconnection of the transfer and bypass switches on all sizes 14-0 BuyLog Catalog Rev. 11/13
21 MX50 Microprocessor Controller Automatic Transfer Switch Controller With more powerful integrated features, the new MX50 Microprocessor, standard with the entire ZTS product family, offers expanded programmability and field adaptability. This premium product is designed for use in specification-grade applications. As an embedded digital controller, the MX50 offers high reliability and ease of unattended operation across a range of applications. Available in ALL transfer modes: Open, Delayed and Bypass Closed User-friendly programmable engine exerciser, used for the engine generator with or without load, at ANY interval in a one-year period Operating voltages available in a single controller for most domestic and international applications Real-time display of ATS status, including active timer(s) Multiple levels of user-defined password protection Serial communications allowing connectivity with other ATS's, paralleling switchgear, and SCADA systems Time-tested synchronous logic automatically measures phase angle and frequency allowing disturbance-free transfer Unsurpassed statistical ATS/System monitoring available in real-time T3/W3 elevator pre-signal. Automatically bypassed if the selected source fails, minimizing time an elevator is without power Universal Motor Disconnect (UMD) sends a pre-signal, post-signal or both to any motor control center. Not bypassed in an outage, the UMD ensures safety in the event of a single phase loss Voltage unbalance detection standard Imbedded synchoscope with display to ensure smooth transfer Performance Features UL, CSA and IEC listed Ringing wave immunity per IEEE 47 (ANSI C37.90A) Condusted and Radiated Emissions per EN550 Class B (CISPR ) (Exceeds EN55011 and MILSTD 461 Class 3) ESD Immunity test per EN (Level 4) Radiated RF, electromagnetic field immunity test per EN (ENV50140) 10v/m Electrical fast transient/burst immunity test for EN Surge immunity test per EN IEEE C6.41 (1. x 50µs, 0.5 and 4 kv) Conducted immunity test per EN (ENV50141) Voltage dips and interruption immunity EN L O A D D I S C O N N E C T T D P R E X F R T I M E R E M A I N I N G 0 4 : 0 M ORE Entelli-Switch 50 The control operates off a close differential 3 phase under-voltage sensing of source 1, factory standard setting 90% pickup, 80% dropout; under-frequency sensing of source 1 factory setting 95% pickup; voltage and frequency sensing of source, factory standard setting 90% pickup voltage, 95% pickup frequency. All factory settings are operator adjustable see table on reverse side). A test is standard (fast test/load/no load) to simulate source 1 failure - automatically bypassed should source fail. User-Friendly Operation LEDs are used in a recognizable line configuration for continuous monitoring of switch position. A new LCD display shows source availability, exercise time delay operation and system source condition. A new simplified adjustment is featured for voltage, frequency and time delay settings. Rev. 11/13 BuyLog Catalog 14-1
22 ZTS Series ZTS Series Accessory Definitions 6P 6A 6AP 6B 6C A1 A1E A3 A4 A6 Microprocessor activated test switch (Momentary) Hardwired test switch (Maintained) Microprocessor activated test switch (Maintained) Hardwired test switch (Maintained Auto - Momentary Test) Key operated Hardwired test switch (Maintained Auto - Maintained Test) Key operated Auxiliary Contact S.P.D.T. - Normal (Source 1) Failure Auxiliary Contact S.P.D.T. - Emergency (Source ) Failure Auxiliary Contact - closed in emergency (Source ) Additional available (10 max.) on ZTS Series and need to be specified Auxiliary Contact - closed in normal (Source 1) Additional available (10 max.) on ZTS Series and need to be specified Motor disconnect and staged restart (1 contact) AB3 Auxiliary Contact - closed in bypass emergency (Source ) (S.P.T.D.) (Standard up to 400A) Additional available (10 max.) on ZBTS Series and need to be specified AB4 Auxiliary Contact - closed in bypass normal (Source 1) (S.P.T.D.) (Standard up to 400A) Additional available (10 max.) on ZBTS Series and need to be specified Calibrate CDP CDT CTAP DS DT DW E ECM EL/P F Microprocessor activated calibration feature Programmable exerciser daily, 7/14/8/365 days userselectable, with or without load Exerciser no load timer Chicago transfer alarm panel mounted in door of enclosure. Includes 3 aux. contacts and fuse. Disconnect Switch. Disconnects source voltage to transfer power panel. (Delayed Transition Only) Time Delay from Neutral Switch position to Source 1 on retransfer (Delayed Transition Only) Time Delay from Neutral Switch position to Source on retransfer Engine Start Relay Ethernet Communication Adapter. Requires MCM (Modbus) Accessory. Event log of last 16 events Fan contact, closed when engine runs. HT(1)() Heater and Thermostat 08/40V (1) 380/600V () mounted and interwired in enclosure. (requires larger enclosure for 40-00A) K K/P LNP L1 L L3 L4 LCM M1 M Frequency Meter (Analog) - Door mounted Frequency Indication on the controller Center-off position LCD-Indicator LED light indicates Switch in Source position LED light indicates Switch in Source 1 position LED light indicates Source 1 available LED light indicates Source available LonWorks Communication Module Single Phase Amp Meter (Analog) Three Phase Amp Meter (Analog) M90 M90A M90B M91 M91A M91B MCM N1 N P1 P Q Q3 Q7 R1-1/R1-3 R15/R15D R16 R6/R6D R50 S5P S1P EPM000 True RMS Digital Meter with display (Amps, Volts, Power, Energy, Power Factory and Frequency). 3 Line LED Display. 50/60 Hz Universal Operation. 1 or 3 phase. Standard Modbus RTU RS485 communications capability Amps. Adds Pre-Wiring for Enervista Viewpoint Monitoring of M90 Accessory & ATS Status using Modbus RS485 Serial Communications Adds Pre-Wiring for Enervista Viewpoint Monitoring of M90 Accessory & ATS Status using Ethernet TCP/IP Communications EPM6000 True RMS Digital Meter with display (Amps, Volts, Power, Energy, Power Factory and Frequency, THD). Certified energy and demand metering. Meets ANSI C1.0 and IEC 687 Accuracy Classes. Front LRDA Port Laptop Connection. Standard Modbus RTU RS485 or DNP 3.0 communications capability. Adds Pre-Wiring for Enervista Viewpoint Monitoring of M91 Accessory & ATS Status using Modbus RS485 Serial Communications Adds Pre-Wiring for Enervista Viewpoint Monitoring of M91 Accessory & ATS Status using Ethernet TCP/IP Communications Modbus RTU Communication Module Running Time Indicator - Door mounted Operation Counter - Door Mounted Engine Start Timer (adjustable to 6 sec.) Engine Start Timer (adjustable to 300 sec.) Peak shave/remote load test/area protection - Relay (S.P.D.T.) (Need to specify voltage - 10 VAC, 4 VAC, 4 VDC - 10V default standard) Inhibit transfer to emergency (Source ) (load add relay) - Relay (S.P.D.T.) (Need to specify voltage - 10 VAC, 4 VAC, 4 VDC - 10V default standard) Inhibit transfer to normal (Source 1) - Relay (S.P.D.T.) (Need to specify voltage - 10 VAC, 4 VAC, 4 VDC - 10V default standard) Over Voltage sensing for normal (Source 1) single (R1-1) or three (R1-3) phase Load Shed. Should Source become overloaded, a signal can be given to switch to the Neutral position. Phase rotation sensing of Normal (Source 1) and Emergency (Source ) Interruptable Power Rate Provisions. Allow transfer out of Source 1 position to Mid position or dead Source. Alarm and Pre-Signal circuit included. (Need to specify voltage - 10 VAC, 4 VAC, 4 VDC - 10V default standard) In Phase monitor between Normal (Source 1) and Emergency (Source ) to allow transfer Microprocessor activated auto/manual retransfer selector switch for trnsferring to Normal (Source 1) (includes microprocessor activated YN accessory) Microprocessor activated auto/manual retransfer selector switch for trnsferring to Normal (Source 1) (includes microprocessor activated YN & YE accessory) 14- BuyLog Catalog Rev. 11/13
23 ZTS Series ZTS Series Accessory Definitions (continued) S13P Microprocessor activated commit/no commit on transferring to Emergency (Source ) (with enable/disable settings) S14 SW1 SW SW3 Keyed selector switch for retransfer to normal-test-auto Auto/Off/Start Engine control selector - Door mounted (keyed or non-keyed operation available) Auto/Off Engine control selector - Door mounted (keyed or non-keyed operation available) Source Priority Selector Switch - Door mounted Allows selection of Source 1 or Source to be the Prime Source. Transfer Switch will transfer to selected Prime Source if that Source is available. (keyed or non-keyed operation available) T T3/W3 U UMD VI W YEN Retransfer to Normal (Source 1) adjustable time delay Pre-signal contact on transfer to Normal (Source 1) or Emergency (Source ) during test Engine stop /cool adjustable cool down timer Pre and ppost transfer output adjustable time range. Functions in both directions. Includes circuits. (Additional circuits available). Voltage imbalance between phases (3 Phase only) Adjustabvle time delay on transfer to Emergency (Source ) Bypass transfer timers function (soft key switch in microprocessor) ZTS Series Accessory Group Matrix Accessories 6P A1 A1E A3 A4 Calibrate CDT CDP **DS *DT *DW E EL/P K/P L1 L L3 L4 *LNP P1 Q Q3 Q7 R1-1 R1-3 R15 *R15D R16 R50 S5P S1P S13P T T3/W3 U UMD VI W YEN Group Packages MSTD MEXE MCON MSEN MSPE MPSG Standard Accessory included in the group package. Optional Accessory not included but can be added to group package. Optional Accessory. Can not be used with accessory having the same symbol. N/A Denotes an Accessory with circuits as a standard. Denotes an Accessory with 3 circuits as a standard. * Delayed Transition Units Only. ** Optional for Amp Rev. 11/13 BuyLog Catalog 14-3
24 ZTS Series ZTS Series Ordering Information Z B 0 Z E C Z V C Model/Type Control Application Ampere Size Switched Enclosure Type Operational Voltage Accessories Panel Poles Z T S Standard (Open Transition) Z T S D 0 0 Delayed Transition Z T S C T 0 Closed Transition Z B T S 0 0 Standard (Open Transition) w/bypass Z B T S D 0 Delayed Transition w/bypass Z B T S C T Closed Transition w/bypass B 0 Entelli-Switch 50 Microprocessor Control Unit B Poles E 3 Poles F 4 Poles Switch Types 400 amps Standard: Unless otherwise noted, the standard switch with quick transfer will amps be supplied. Delayed Transition: When ordered as the ZTSD, the delayed transition switch offers 800 amps time delay during transfer from one position to the other. This is primarily for transfer of 1000 amps large motor or inductive loads. Closed Transition: When ordered as the amps ZTSCT, the closed transition switch offers two basic modes of operation. During a failure of one source or an out of specification condition, the ZTSCT Model operates 1600 amps 0 0 as a standard delayed transition switch 000 amps (ZTSD Model). This sequence allows clear separation of an unreliable source from an available one amps Bypass: When ordered as the ZBTS, the bypass transition switch offers a draw-out 4000 amps mechanism, with electrical and mechanical interlocks for secure removal after load bypass. In this way the transfer switch and/or the control panel may be tested, isolated and removed for maintenance without load interruption. Product # Example ZTSCT0B00040F-ZEC01ZVC40MSTD This number string shows the correct format for a ZTS Model Automatic Transfer Switch with closed transition, an Entelli-Switch 50 microprocessor control unit, Utility - Generator, 400 amps, 4 pole, NEMA Type 1 enclosure, 10/08V 3F, 4 wire, 60 Hz system with the standard group of accessories. UL 1008 Withstand and Closing Ratings Please refer to GE Zenith Controls Bulletin TB Utility - Generator U Utility - Utility M Manual G Gen to Gen amps amps amps amps 0 5 amps amps 0 1 Type 1 Enclosed 1 Type 1 Enclosure 3 R Type 3R Enclosure 4 0 Type 4 Enclosure 4 X Type 4X Enclosure 0 0 Open Style Unit A B Consult Table Below M S T D Then choose additional accessories A B Voltage Phase ConWg. Hz wire / wire / wire wire wire wire / wire /0 3 4 wire / wire / wire / wire /0 3 4 wire /0 3 4 wire wire wire wire wire wire / wire wire / wire / wire wire / wire wire /40 4/5 wire wire / wire / wire / wire / wire wire 60 Note: Operating voltage must be specified at time of order. Only the most common voltages are shown above. M M M M M M E C S S P A X O E P S E N N E G N BuyLog Catalog Rev. 11/13
25 ZTS Series ZTS Model, Dimensions and Weights Application Notes: 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are approximate and subject to change. 4. Special enclosures (NEMA 3R, 4, 1, etc.) dimensions and layout may differ. Consult the GE Zenith factory for details. 5. Normal and emergency may be ordered inverted on any switch. The load may be inverted amps. Consult the GE Zenith factory for details. 6. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact the GE Zenith factory. 7. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 8. Add 4" in height for removable lifting lugs. 9. Lug adapters for amp limits may be staggered length for ease of entrance. Consult the ge Zenith factory for details. 10. Ventilation louvers on both sides and rear of enclosure. Louvers must be clear for airflow with standard cable connections. 11. A ZTS A, when ordered with the following options, will require a larger enclosure of 46" x 4" x 14" (HxWxD): A6(T), Digital Meter, HT, HH, K, LDS, L11, N1, N, OCVR-1SG, OCVR-1SS, P, QM, Q3M, Q7M, R6(D). 1. For Delayed and Closed Transition dimensions and weights, refer to GE Zenith Publication PB-5067 and PB For Bypass/Isolation dimensions and weights, refer to GE Zenith Publication pb A ZTS, when ordered with compression lugs suitable for use with copper cables, will require a larger enclosure. For 40-5A, the enclosure is 46" x 4" x 14" (HxWxD). For A, the enclosure is 66" x 4" x 19.75". For 600A, the enclosure is 74" x 40" x 19.75". For certified drawings, please contact the GE Zenith factory. NEMA 1 Weight Reference Open Application Ampere Rating Poles Height (A) Width (B) Depth (C) Figure Type NEMA 1 Notes 40, 80, 3 4 (61) 18 (46) 11 (8) A 1 (10) 57 (6) 4 4 (61) 18 (46) 11 (8) A 1 (10) 60 (7) 1-7, , 150, 3 4 (61) 18 (46) 11 (8) A 1 (10) 57 (6) 4 4 (61) 18 (46) 11 (8) A 1 (10) 60 (7) 1-7, , 3 46 (117) 4 (61) 14 (36) A 70 (3) 165 (75) 4 46 (117) 4 (61) 14 (36) A 75 (34) 170 (68) 1-7, , 400, 3 46 (117) 4 (61) 14 (36) A 70 (3) 165 (75) 4 46 (117) 4 (61) 14 (36) A 75 (34) 170 (68) 1-7, , 3 74 (188) 40 (10) 19.5 (50) B 165 (75) 380 (17) 4 74 (188) 40 (10) 19.5 (50) B 185 (84) 430 (195) 1-8, , 1000, 100, 3 74 (188) 40 (10) 19.5 (50) B 190 (86) 455 (06) 4 74 (188) 40 (10) 19.5 (50) B 10 (95) 540 (45) 1-8, , (9) 35.5 (90) 48 (1) C 345 (156) 1010 (458) 4 90 (9) 35.5 (90) 48 (1) C 450 (04) 1160 (56) (9) 35.5 (90) 48 (1) C 465 (11) 1130 (513) 4 90 (9) 35.5 (90) 48 (1) C 670 (304) 1395 (633) (9) 46.5 (118) 60 (15) C 770 (349) 1595 (73) 4 90 (9) 46.5 (118) 60 (15) C 105 (465) 1850 (839) 1-13 Notes * Line and load terminals are located in rear and arranged for bus bar connection. Terminal lugs are available as an accessory. Contact GE Zenith factory for more details. 1. Special terminal lugs and neutral bars are available at additional cost. Contact factory and advise cable sizes and number of conductors per pole.. Fully rated neutral provided on 3 phase, 4 wire system. 3. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact the GE Zenith factory. C A Figure A B C A C Figure C A Figure B AL-CU UL Listed Solderless Screw-Type Terminals for External Power Connections Normal, & Load Terminals Switch Size Amps Cables/Pole Wire Ranges #8 to 3/0 100, #6 to 50 MCM 5 1 #4 to 600 MCM 60 1 #4 to 600 MCM #4 to 600 MCM 600 # to 600 MCM 800, 1000, # to 600 MCM 1600, 000,3000, 4000 * B B Rev. 11/13 BuyLog Catalog 14-5
26 ZTS Series ZTS Series Dimensional Specifications Model ZTS Transfer Switches NEMA 1 Enclosure Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Fig. Open Type NEMA 1 App. Notes 40, 80, 100, 150, 5, 60, , 1000, , , 3 4 (61) 18 (46) 11 (8) A 1 (10) 57 (6) 1 7, (61) 18 (46) 11 (8) A 1 (10) 60 (7) 1 7, 11-14, 3 46 (117) 4 (61) 14 (36) A 70 (3) 165 (75) 1 7, (117) 4 (61) 14 (36) A 75 (34) 170 (68) 1 7, 1-14, 3 74 (188) 40 (10) 19.5 (50) B 165 (75) 380 (17) 1 8, (188) 40 (10) 19.5 (50) B 185 (84) 430 (195) 1 8, 1-14, 3 74 (188) 40 (10) 19.5 (50) B 190 (86) 455 (06) 1 8, (188) 40 (10) 19.5 (50) B 10 (95) 540 (45) 1 8, (9) 35.5 (90) 48 (1) C 345 (156) 1010 (458) (9) 35.5 (90) 48 (1) C 450 (04) 1160 (56) (9) 35.5 (90) 48 (1) C 465 (11) 1130 (513) (9) 35.5 (90) 48 (1) C 670 (304) 1395 (633) (9) 46.5 (118) 60 (15) C 770 (349) 1595 (73) (9) 46.5 (118) 60 (15) C 105 (465) 1850 (839) 1 13 Application Notes: 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are approximate and subject to change. 4. Special enclosures (NEMA 3R, 4, 4X, 1, etc.) dimensions and layout may differ. Consult the GE Zenith factory for details. 5. Normal and emergency may be ordered inverted on any switch. The load may be inverted amps. Consult the factory for details. 6. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact the GE Zenith factory. 7. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 8. Add 4" in height for removable lifting lugs. 9. Lug adapters for amp limits may be staggered length for ease of entrance. Consult the GE Zenith factory for details. 10. Ventilation louvers on both sides and rear of enclosure. Louvers must be clear for airflow with standard cable connections. 11. A ZTS A, when ordered with the following options, will require a larger enclosure of 46 x 4 x 14 (HxWxD): A6(T), Digital Meter HT, HH, K, LDS, L11, N1, N, OCVR- 1SG, OCVR-1SS, P, QM, Q3M, Q7M, R6(D). 1. For Delayed and Closed Transition dimensions and weights, refer to GE Zenith publication PB-5067 and PB For Bypass/Isolation dimensions and weights, refer to GE Zenith publication PB A ZTS, when ordered with compression lugs suitable for use with copper cables will require a larger enclosure. For 40-5A, the enclosure is 46 x 4 x 14 (H x W x D). For A, the enclosure is 66 x 4 x For 600A, the enclosure is 74 x 40 x For certified drawings, please contact the GE Zenith factory. Model ZTSD Transfer Switches NEMA 1 Enclosure Weight Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Fig. Open Type NEMA 1 App. Notes 40, 80, 100, 150, 5, 60, 400, 3 46 (117) 4 (61) 14 (36) A 80 (36) 00 (91) 1-7, (117) 4 (61) 14 (36) A 85 (39) 05 (93) 1 7, , 3 74 (188) 40 (10) 19.5 (50) B 185 (84) 400 (181) 1 8, (188) 40 (10) 19.5 (50) B 05 (93) 450 (04) 1 8, , 1000, 100, 3 74 (188) 40 (10) 19.5 (50) B 10 (95) 475 (15) 1 8, (188) 40 (10) 19.5 (50) B 30 (104) 560 (54) 1 8, , (9) 35.5 (90) 48 (1) C 365 (166) 1030 (467) 1 8, 10, (9) 35.5 (90) 48 (1) C 470 (13) 1190 (540) 1 8, 10, (9) 35.5 (90) 48 (1) C 485 (0) 1150 (5) 1 10, (9) 35.5 (90) 48 (1) C 690 (313) 1415 (64) 1 10, (9) 46.5 (118) 60 (15) C 80 (37) 1635 (74) 1 10, (9) 46.5 (118) 60 (15) C 1045 (474) 1870 (848) 1 10, 1-13 Application Notes: 1-9, 11, 13. Same as above 10. Ventilation louvers on both sides and rear of enclosure. One set of louvers must be clear for airflow with standard cable connectors. Reference Figures Weight Figure A Figure B Figure C 14-6 BuyLog Catalog Rev. 11/13
27 ZTS Series ZTS Series Dimensional Specifications Model ZBTS and ZBTSD Transfer/Bypass-Isolation Switches NEMA 1 Enclosure Weight Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Fig. Open Type NEMA 1 App. Notes 100, 150, 5, 60, , 1000, , , 3 83 (11) 30 (76) 8.5 (73) D 310 (141) 770 (350) (11) 30 (76) 8.5 (73) D 380 (173) 840 (381) (9) 36 (91) 8.5 (7) E 660 (99) 10 (553) (9) 40 (10) 8.5 (7) E 770 (349) 1365 (619) (9) 40 (10) 8.5 (7) E 765 (347) 1355 (615) (9) 46 (117) 8.5 (7) E 910 (413) 1570 (71) (9) 40 (10) 61.5 (156) F 900 (1315) 3100 (1406) (9) 50 (17) 61.5 (156) F 3800 (174) 4000 (1814) 1 7, (9) 40 (10) 73.5 (186) F 3700 (1678) 3900 (1769) 1 7, (9) 50 (17) 73.5 (186) F 4800 (177) 5000 (68) (9) 47.5 (11) 81 (06) F 4310 (1955) 4660 (113) 1 7, (9) 54 (137) 81 (06) F 5510 (499) 5860 (658) 1 7, Model ZBTSCT Closed Transition Transfer/Bypass-Isolation Switches NEMA 1 Enclosure Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Fig. Open Type NEMA 1 App. Notes 3 90 (9) 36 (91) 8.5 (7) E 730 (331) 180 (581) , 150, 5, 60, 400, (9) 40 (10) 8.5 (7) E 840 (381) 1385 (68) (9) 40 (10) 8.5 (7) E 835 (379) 1435 (651) , 1000, (9) 46 (117) 8.5 (7) E 980 (444) 1640 (744) (9) 40 (10) 61.5 (156) F 970 (1347) 3170 (1438) 1 7, , (9) 50 (17) 61.5 (156) F 3870 (1755) 4070 (1846) 1 7, (9) 40 (10) 73.5 (186) F 3770 (1710) 3970 (1801) 1 7, (9) 50 (17) 73.5 (186) F 4870 (09) 5070 (300) 1-7, (9) 47.5 (11) 81 (06) F 4380 (1986) 4730 (145) 1 7, (9) 54 (137) 81 (06) F 5580 (531) 5930 (689) 1 7, 10 1 Application Notes: 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are approximate and subject to change. 4. Special enclosures (NEMA 3R, 4, 4X, 1, etc.) dimensions and layout may differ. Consult the GE Zenith factory for details. 5. Bypass Model product can not be ordered with inverted style. 6. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact the GE Zenith factory. 7. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 8. Add 4" in height for removable lifting lugs. 9. ZBTS(D) A and ZBTSCT A standard configuration is top entry. 14 rear adapter bay required for bottom entry. Consult GE Zenith factory for details. 10. Bypass switch weights for amp units vary up to 10% based on connections variations. Weights shown are for estimation only amp depth dimension shown is standard. Depending on your cable/conduit requirements you may desire a deeper enclosure. Consult the GE Zenith factory for further details. 1. Lug adapters for amp limits may be staggered length for ease of entrance. Consult the GE Zenith factory for details. Weight Reference Figures C B 14" C B C B Vent A See Note 9 A A Vent Figure D Figure E Figure F Rev. 11/13 BuyLog Catalog 14-7
28 ZTS Series ZTS Series Dimensional Specifications Model ZTSCT Transfer Switches NEMA 1 Enclosure Weight Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Fig. Open Type NEMA 1 App. Notes, 3 74 (188) 40 (10) 19.5 (50) A 185 (84) 400 (181) , 150, 5, 60, 400, (188) 40 ( (50) A 05 (93) 450 (04) 1 8, 3 74 (188) 40 (10) 19.5 (50) A 10 (95) 475 (15) , 1000, (188) 40 (10) 19.5 (50) A 30 (104) 560 (54) (9) 35.5 (90) 48 (1) B 365 (166) 1030 (467) , (9) 35.5 (90) 48 (1) B 470 (04) 1190 (540) (9) 35.5 (90) 48 (1) B 485 (0) 1150 (5) (9) 35.5 (90) 48 (1) B 690 (313) 1415 (64) (9) 46.5 (118) 60 (15) B 80 (37) 1635 (74) (9) 46.5 (118) 60 (15) B 1045 (474) 1870 (848) 1 10 Application Notes: 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are approximate and subject to change. 4. Special enclosures (NEMA 3R, 4, 4X, 1, etc.) dimensions and layout may differ. Consult the GE Zenith factory for details. 5. Normal and emergency may be ordered inverted on any switch. The load may be inverted amps. Consult the factory for details. 6. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact the GE Zenith factory. 7. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 8. Add 4" in height for removable lifting lugs amp depth dimension shown is standard. Depending on your cable/conduit requirements you may desire a deeper enclosure. Consult the GE Zenith factory for further details. 10. Lug adapters for amp limits may be staggered length for ease of entrance. Consult the GE Zenith factory for details. Reference Figures Figure A Figure B 14-8 BuyLog Catalog Rev. 11/13
29 Model ZTSMV Model ZTSMV Medium Voltage Transfer Switches The Standard of Quality in Design and Manufacturing Introduction ZTS Series Automatic Transfer Switches have been the preferred standard for quality and reliability in the electrical industry. The ZTSMV Model medium voltage automatic transfer switches provides that same quality for installations from 5kV to 15kV. The ZTSMV Model is designed for use in the most critical applications: hospitals, military sites, airports, communications facilities, and computer installations. ZTSMV Model switches fit the need for dependable continuity of power where emergency or standby applications exist. Backed by over 75 years of experience in manufacturing automatic transfer switches, as well as extensive experience in the design and development of paralleling switchgear systems, the GE ZTSMV Model provides the reliable answer to critical medium voltage switching applications. Like all GE switches, the ZTSMV Model is supported by a nationwide network of field service facilities. Construction The switching elements consist of two vacuum circuit breakers interlocked to ensure that only one set of contacts can be closed at any one time. The control module for transferring operations of the power unit is the same reliable microprocessor control system that GE has designed, built and used on our low voltage automatic transfer switches. The control module is physically isolated from the power portion by an insulating barrier. The completed unit is enclosed in a NEMA1 cabinet (NEMA 3R optional) and is both front and rear accessible. ZTSMV Model ZTSMV Medium Voltage Transfer Switches Standard Features The ZTSMV Features: State-of-the-art vacuum breaker design Electrically interlocked for secure operation Over-current protection for the load A drawout P.T. trunnion design on utility to facilitate removal of control fuses from rear of cabinet The control module completely isolated from power section Standard indication of source availability MX50 control with MSPES Options provided for use with generator as an alternate source A control circuit disconnect switch Capable of supporting modules to allow remote communication to annunciators, modems and SCADA systems Drawout vacuum breaker design Dual electrical interlocks Compliance with ANSI/IEEE spec C37 and NEMA spec SG5 A drawout P.T. trunnion design on utility and generator side to facilitate removal of control fuses while the system is operating The control module completely isolated from power section Standard indication of source availability One year warranty Rev. 11/13 BuyLog Catalog 14-9
30 Model ZTSMV ZTSMV Series Medium Voltage Transfer Switches Electrical Ratings The ZTS-MV Series is available in a wide range of voltage, current and MVA classes. It is critical to evaluate the project requirements prior to specifying the equipment. Verify: Normal and emergency system voltages Current rating requirements MVA class Short circuit rating Protective relay requirements (if any) ZTSMV Rated Voltage 5kV 15kV 15kV MVA Class ,000 System Voltage kv kv kv Rated Current 1,00 A 1,00-3,000 A 1,00-3,000 A Short Circuit Rating kv kv kv kv NOTE: Additional ratings are available. Consult the factory for details. Ordering Information Z T S M V Block A Block B Block C Block D Block E Block F Block G Block H Block I Block A Model Designation ZTSMV05-5kV Class ZTSMV15-15 kv Class Block B Transition Type S - Standard Transition D - Delayed Transition T - Closed Transition Block C NEMA C - NEMA 1 S - NEMA 3R Block D Number of Poles 3 Block E System Voltage V0 = 400V, 3 phase, 3 wire V1 = 400V, 3 phase, 4 wire V = 4160V, 3 phase, 3 wire V3 = 4160V, 3 phase, 4 wire V4 = 6600V, 3 phase, 3 wire V5 = 6600V, 3 phase, 4 wire V6 = 700V, 3 phase, 3 wire V7 = 700V, 3 phase, 4 wire W0 = 1.47kV, 3 phase, 3 wire W1 = 1.47kV, 3 phase, 4 wire V8 = 13.8kV, 3 phase, 3 wire V9 = 13.8kV, 3 phase, 4 wire VX = Special Voltage Block F Rated Current 03 1,00A 04,000A 05 3,000A Block H Current Transformer Ratio on Utility / / / / / / / / / / / / / / / /5 Block G MVA Rating Block I Current Transformer Ratio on Emergency Use same chart as Block H 1 115kV Class (7.-15 kv only) *Other ratings are available. Contact the factory for details BuyLog Catalog Rev. 11/13
31 Model ZTSMV Standard Accessories MSPES Option Group A1 A1E A3 A4 A6 C/D E JE JN L1 L L3 L4 P1 Q Q3 R1 R8 R16 R17 R50 T U W YEN Auxiliary Contact Energized on Normal (SPDT) Auxiliary Contact Energized on Emergency (SPDT) Auxiliary Contact Closed in Emergency Position Auxiliary Contact Closed in Normal Position Timed Load Disconnect Prior to Transfer (Adjustable) Load/No-load exerciser clock (specify 7, 14 or 365 day) Engine Start Contact Over/Under Frequency Normal Source Over/Under Frequency Emergency Source Pilot Light Transfer Switch in Normal Position Pilot Light Transfer Switch in Emergency Position Pilot Light Emergency Power Available Pilot Light Normal Power Available Time Delay Engine Start (Adjustable) Peak Shave/Remote Load Test: Input for peak shave or remote load test; includes automatic return to normal if emergency source fails and normal is present; 10 VAC or 4 VDC Inhibit Transfer: Input circuit to inhibit transfer to emergency; 10 VAC or 4 VDC Over Voltage Normal Source Over Voltage Emergency Source Phase Sequence Sensing Under-voltage Sensing: Emergency (3 phase) In-phase monitor (if delayed transition units are not specified) Time Delay Retransfer to Normal (Adjustable) Time Delay Engine Cooldown (Adjustable) Time Delay Transfer to Emergency (Adjustable) Time Delay Bypass Switch (T & W Timers) Optional Accessories Protective Relays UPR1-A Utility Source 1 Protective Relay (GE SR750) UPR1-B Utility Source 1 Protective Relay (GE F60) UPR-A Utility Source Protective Relays (GE SR750) UPR-B Utility Source Protective Relays (GE F60) GRP-A Generator Source 3 IPR1-C IPR-C Protective Relays (GE SR489) Source 1 Industrial Grade Protective Relay (MX3500) Source Industrial Grade Protective Relay (MX3500) Other Accessories Available Include: Multi-function power measurement metering including amps, volts, frequency, KW, KVA, KVAR, etc. Soft load switches are available. Consult the factory. Rev. 11/13 BuyLog Catalog 14-31
32 Model ZTE ZTE Series Low-Voltage, Open Transition, Automatic and Manual Transfer Switches Ideal for mixed (inductive and resistive) mission critical loads Contact transfer speed less than 100 milliseconds Double throw, interlocked operation Ratings 40 to 4000 amperes Ratings & Construction Ratings Voltage, Ampere and Pole configuration per Order Code Certifications UL 1008, CSA C. Certifications Third-party Seismic Certification to IBC 009, Ip = 1.5 (operation during event) Electrical Operator Momentarily energized, high-speed solenoid mechanism Mechanism Mechanically-held with mechanical interlock to inhibit connection of both sources to the load Contacts GE design and manufactured, silver tungsten alloy with separate arcing contacts on 600A and above ratings for high withstand and close-on capability Neutral Pole (4 pole only) Identical construction to phase poles with fully rated main and arcing contacts. Operation via same mechanism as phase poles to prevent sustained connection of source neutrals in separately derived systems, as lastbreak/first-make transfer. Controller Construction Dual-processor based, with dedicated processor for high-speed Serial or Ethernet communications Source Sensing Direct V sensing and software configuration of rated voltage and frequency without the need for potential transformers, step-down transformers or DIP switches Control Wiring All customer connections at one location. All signals in/out relay-isolated via DIN-mounted relay/terminal blocks. All control wiring via factory-installed wiring harnesses Enclosure Type per Order Code Display, Sensing & Time Delays Display ¼ VGA color graphical with embedded HELP menus Annunciation High intensity LED for Source Availability (), Source Connected (), Transfer Inhibit (not in Auto) Source Fail/Restore Independently adjustable pickup & dropout of 3-phase U/O voltage, U/O Freq, Volts Balance plus Phase Rotation Time Delays Gen start, Source stabilize, Source fail override, Retransfer to Source 1, Gen cool down, Independent settings for Fast Test, Time Delay for Generator Voltage Sag Remote Access All parameters locally (front USB port) or remotely (serial or Ethernet) Adjustable Control Group Options (see order code) Group A: All standard features, Field re-programmable I/O (4 inputs, 4 outputs), Control Switches (Test with Load, Test no load, Fast Test, Alarm Reset, Auto/Man Re-transfer Source 1, Auto/Man Transfer both sources, Preferred Source select, Commit/No Commit Transfer to Gen, Time Delay Bypass Group B: All features from A plus: 10 User-configurable Analog & 10 Digital Alarms, 0-channel data logger, 10-channel waveform capture, Auto Load Shed (with voltage, frequency, and kw triggers) Group C: All features from B plus: 4 additional field programmable inputs (total 8 inputs, 8 outputs) Group D: All features from C plus: 4 additional field programmable inputs (total 1 inputs, 1 outputs) & GE Flexlogic userconfigurable control logic Group M: Manual ATS configuration Additional Standard Features Engine Exerciser Configurable Periodic Exerciser (7 Event Daily, Weekly, 14 or 8 day) or Clock Exerciser Type (1 Event, 365 day Programmable) System Status Screen Active state of switch, display of all time delays and alarm conditions Event Recorder 56 Event, 1ms accuracy, clock sync via Network Time Protocol (NTP) Outage & Test Report Screen Date/time stamping of: outage or test event, start signal sent, Gen start time, connection to Gen, Max Gen Volts & Freq dip, return of utility, re-transfer to normal External Power Supply Standard 10VAC input for controller power and communication and 4 VDC input for remote control and annunciation when both sources de-energized Flexible Feature Assignment Field reassignable I/O for any/all control features In-Phase Monitor For phase matching prior to Live-Live transfers of load Optional Features (see order code) Serial Communications High speed, up to 115k Baud Modbus RTU Ethernet Communications Fast Ethernet, (10/100 Mbit), Modbus TCP/IP Power Quality Metering True RMS metering, including THD% (up to 8th order) Load Shed Ability to transfer to de-energized normal source or center position in event of generator overload Integral Surge Protective Device (SPD) Load-connected medium or high exposure type Integral Battery Charger 3 or 10A, 1 or 4VDC type Lugs Compression lugs in lieu of standard mechanical lugs on 100A-100A switches Lugs Mechanical or Compression lugs in lieu of standard rearbus connection on A switches 14-3 BuyLog Catalog Rev. 11/13
33 Model ZTE Order Code Abbreviated Product Configuration (see full Product Brochure, Publication DEA-405, for full configuration) Z10 X Amperage A = 40 B = 80 C = 100 D = 150 F = 5 G = 60 I = 400 J = 600 K = 800 L = 1000 M = 100 N = 1600 O = 000 Q = 3000 R = 4000 # of Poles = Pole 3 = 3 Pole 4 = 4 Pole Application S = Util-Gen U = Util-Util G = Gen-Gen Controller Language 1 = English NEMA Enclosure (Open) A = NEMA 1 B = NEMA 1A C = NEMA 3R D = NEMA 3R w/htr E = NEMA 4 F = NEMA 1 G = NEMA 4X Control Group Options A = Group A B = Group B C = Group C D = Group D M = Group M Voltage Code 70 = 77/480V, 3PH, 4W, 60Hz 0 = 10/40V, 1PH, 3W, 60Hz 40 = 10/08V, 3PH, 4W, 60Hz 9 = 0/380V, 3PH, 4W, 50Hz 50 = 480V, 3PH, 3W, 60Hz 38 = 10/08/40V, 3PH, 4W, High-Leg Delta, 60Hz 30 = 40V, 3PH, 3W, 60Hz 31 = 08V, 3PH, 3W, 60Hz 61 = 347/600V, 3PH, 4W, 60Hz brochure for other options Lug Options X = Std lugs or Rear bus (per chart below) brochure for lug option details) Metering & Accessories A = Load Shed D = PQ Metering Ground Bus 1 = Ground bus- Mech Lugs (Qty. 3) #14-1/0-GB1 = Ground bus- Mech Lugs (Qty. 6) #8-1/0 -GB SPD (Load-Side Connected) 100A - 100A Rating A = 65kA B = 80kA C = 100kA 1600A A Rating D = 100kA E = 150kA F = 00kA G = 300kA Communications S = CCM S-Modbus RTU (Serial) communication module E = CCM E Modbus TCP/IP (Ethernet) communication module E = plus Modbus RTU (Serial) communication module Battery Charger 1 = Battery Charger-1 Volt-3 Amp = Battery Charger-1 Volt-10 Amp ZTE Model, Dimensions and Weights NEMA 1 Weight Application Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Figure Open Type NEMA 1 Notes *100, 150, (57) 0 (100) 66 (168) 4 (61) 0 (50) B 60, (66) 41 (109) , 80, 100, 3 14 (7) 10 (55) 46 (117) 4 (61) 14 (36) A 150, (9) 16 (57) , 400, 3 59 (7) 168 (76) 46 (117) 4 (61) 14 (36) A 4 70 (3) 180 (8) , (68) 410 (186) 74 (188) 40 (10) 19.5 (50) B (8) 440 (00) , 1000, 100, (86) 460 (09) 74 (188) 40 (10) 19.5 (50) B 4 30 (104) 490 () , (156) 1010 (458) 90 (9) 35.5 (90) 48 (1) C (04) 1160 (56) (11) 1130 (513) 90 (9) 35.5 (90) 48 (1) C (304) 1396 (633) (349) 1595 (73) 90 (9) 46.5 (118) 60 (15) C (465) 1850 (839) 1-9 * For ZTECT models only AL-CU UL Listed Mechanical Lugs Normal, Emergency & Load Terminals Switch Size Amps Cables/Pole Wire Ranges ZTE 40, 80 1 #8 to 3/0 100, #6 to 50 MCM 5 1 #4 to 600 MCM 60 1 #4 to 600 MCM #4 to 600 MCM 600 # to 600 MCM 800, 1000, # to 600 MCM 1600, 000, 3000, 4000 * * Notes: * Line and load terminals are located in rear and arranged for bus bar connection. Terminal lugs are available as an accessory. See full product brochure (DEA-405) for option details. 1. Fully rated neutral provided on 3 phase, 4 wire system Application Notes 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are subject to change. 4. NEMA 3R, 4, 4X and 1 enclosure dimensions may differ than NEMA 1 shown above. Consult the factory for details. 5. Special lug arrangements may require different enclosure dimensions. See full product brochure (DEA-405) for details. 6. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 7. Add 4" in height for removable lifting lugs. 8. Lug adapters for A limits may be staggered length for ease of entrance. Consult the factory for details A switches have ventilation louvers on both sides and rear of enclosure. Louvers must be clear for airflow with standard cable connections. Rev. 11/13 BuyLog Catalog 14-33
34 Model ZTED ZTED Series Low-Voltage, Delayed Transition, Automatic and Manual Transfer Switches Ideal for inductive (motors/transformers, UPS) mission critical loads Adjustable, time delay in centered off position Mechanically interlocked center-off position for load decay Ratings 40 to 4000 amperes Ratings & Construction Ratings Voltage, Ampere and Pole configuration per Order Code Certifications UL 1008, CSA C. Certifications Third-party Seismic Certification to IBC 009, Ip = 1.5 (operation during event) Electrical Operator Momentarily energized, high-speed solenoid mechanism Mechanism Mechanically-held with mechanical interlock to inhibit connection of both sources to the load Contacts GE design and manufactured, silver tungsten alloy with separate arcing contacts on 600A and above ratings for high withstand and close-on capability Neutral Pole (4 pole only) Identical construction to phase poles with fully rated main and arcing contacts. Operation via same mechanism as phase poles to prevent sustained connection of source neutrals in separately derived systems, as lastbreak/ first-make transfer. Controller Construction Dual-processor based, with dedicated processor for high-speed Serial or Ethernet communications Source Sensing Direct V sensing and software configuration of rated voltage and frequency without the need for potential transformers, step-down transformers or DIP switches Control Wiring All customer connections at one location. All signals in/out relay-isolated via DIN-mounted relay/terminal blocks. All control wiring via factory-installed wiring harnesses. Enclosure Type per Order Code Display, Sensing & Time Delays Display ¼ VGA color graphical with embedded HELP menus Annunciation High intensity LED for Source Availability (), Source Connected (), Transfer Inhibit (not in Auto) Source Fail/Restore Independently adjustable pickup & dropout of 3-phase U/O voltage, U/O Freq, Volts Balance plus Phase Rotation Time Delays Gen start, Source stabilize, S1 g S transfer center-off delay, Source fail override, Retransfer to Source 1, S g S1 transfer center-off delay, Gen cool down, Independent settings for Fast Test, Time Delay for Generator Voltage Sag Remote Access All parameters locally (front USB port) or remotely (serial or Ethernet) Adjustable Control Group Options (see order code) Group A: All standard features, Field re-programmable I/O (4 inputs, 4 outputs), Control Switches (Test with Load, Test no load, Fast Test, Alarm Reset, Auto/Man Re-transfer Source 1, Auto/Man Transfer both sources, Preferred Source select, Commit/No Commit Transfer to Gen, Time Delay Bypass Group B: All features from A plus: 10 User-configurable Analog & 10 Digital Alarms, 0-channel data logger, 10-channel waveform capture, Auto Load Shed (with voltage, frequency, and kw triggers) Group C: All features from B plus: 4 additional programmable inputs (total 8 inputs, 8 outputs) Group D: All features from C plus: 4 additional field programmable inputs (total 1 inputs, 1 outputs) & GE Flexlogic user-configurable control logic Group M: Manual ATS configuration Additional Standard Features Engine Exerciser Configurable Periodic Exerciser (7 Event Daily, Weekly, 14 or 8 day) or Clock Exerciser Type (1 Event, 365 day Programmable) System Status Screen Active state of switch, display of all time delays and alarm conditions Event Recorder 56 Event, 1ms accuracy, clock sync via Network Time Protocol (NTP) Outage & Test Report Screen Date/time stamping of: outage or test event, start signal sent, Gen start time, connection to Gen, Max Gen Volts & Freq dip, return of utility, re-transfer to normal External Power Supply Standard 10VAC input for controller power and communication and 4 VDC input for remote control and annunciation when both sources de-energized Flexible Feature Assignment Field reassignable I/O for any/all control features Programmable Center-Off Position For transition of motor and regenerative loads Optional Features (see order code) Serial Communications High speed, up to 115k Baud Modbus RTU Ethernet Communications Fast Ethernet, (10/100 Mbit), Modbus TCP/IP Power Quality Metering True RMS metering, including THD% (up to 8th order) Load Shed Ability to transfer to de-energized normal source or center position in event of generator overload Integral Surge Protective Device (SPD) Load-connected medium or high exposure type Integral Battery Charger 3 or 10A, 1 or 4VDC type Lugs Compression lugs in lieu of standard mechanical lugs on 100A-100A switches Lugs Mechanical or Compression lugs in lieu of standard rear-bus BuyLog Catalog Rev. 11/13
35 Model ZTED Order Code Abbreviated Product Configuration (see full Product Brochure, Publication DEA-405, for full configuration) Z1D X Amperage A = 40 B = 80 C = 100 D = 150 F = 5 G = 60 I = 400 J = 600 K = 800 L = 1000 M = 100 N = 1600 O = 000 Q = 3000 R = 4000 # of Poles = Pole 3 = 3 Pole 4 = 4 Pole Application S = Util-Gen U = Util-Util G = Gen-Gen Controller Language 1 = English NEMA Enclosure (Open) A = NEMA 1 B = NEMA 1A C = NEMA 3R D = NEMA 3R w/htr E = NEMA 4 F = NEMA 1 G = NEMA 4X Control Group Options A = Group A B = Group B C = Group C D = Group D M = Group M Voltage Code 70 = 77/480V, 3PH, 4W, 60Hz 0 = 10/40V, 1PH, 3W, 60Hz 40 = 10/08V, 3PH, 4W, 60Hz 9 = 0/380V, 3PH, 4W, 50Hz 50 = 480V, 3PH, 3W, 60Hz 38 = 10/08/40V, 3PH, 4W, High-Leg Delta, 60Hz 30 = 40V, 3PH, 3W, 60Hz 31 = 08V, 3PH, 3W, 60Hz 61 = 347/600V, 3PH, 4W, 60Hz brochure for other options Lug Options X = Std lugs or Rear bus (per chart below) brochure for lug option details) Metering & Accessories A = Load Shed D = PQ Metering Ground Bus 1 = Ground bus- Mech Lugs (Qty. 3) #14-1/0-GB1 = Ground bus- Mech Lugs (Qty. 6) #8-1/0 -GB SPD (Load-Side Connected) 100A - 100A Rating A = 65kA B = 80kA C = 100kA 1600A A Rating D = 100kA E = 150kA F = 00kA G = 300kA Communications S = CCM S-Modbus RTU (Serial) communication module E = CCM E Modbus TCP/IP (Ethernet) communication module E = plus Modbus RTU (Serial) communication module Battery Charger 1 = Battery Charger-1 Volt-3 Amp = Battery Charger-1 Volt-10 Amp ZTED Model, Dimensions and Weights NEMA 1 Weight Application Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Figure Open Type NEMA 1 Notes 40, 80, 100, 3 80 (36) 10 (59) 150, (39) 16 (57) A 1-6, 3 (1168) (610) (356) 80 (36) 168 (76) 60, (39) 180 (8) 600, (84) 410 (186) (93) 440 (00) 800, 3 (1880) (1016) (50) 10 (95) 460 (09) B 4 30 (104) 490 (3) , 100, (95) 460 (09) 4 (1880) (1016) (495) 30 (104) 490 (3) 1600, (166) 1010 (458) (04) 1160 (56) 1-7, (86) (90) (116) 485 (0) 1130 (513) C (313) 1396 (633) (37) 1595 (73) 4 (86) (1180) (154) 1045 (474) 1850 (839) 1-9 AL-CU UL Listed Mechanical Lugs Normal, Emergency & Load Terminals Switch Size Amps Cables/Pole Wire Ranges ZTED 40, 80 1 #8 to 3/0 100, 150, 5 1 #4 to 600 MCM 60 1 #4 to 600 MCM #4 to 600 MCM 600 # to 600 MCM 800, 1000, # to 600 MCM 1600, 000, 3000, 4000 * * Notes: * Line and load terminals are located in rear and arranged for bus bar connection. Terminal lugs are available as an accessory. See full product brochure (DEA-405) for option details. 1. Fully rated neutral provided on 3 phase, 4 wire system Application Notes 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are subject to change. 4. NEMA 3R, 4, 4X and 1 enclosure dimensions may differ than NEMA 1 shown above. Consult the factory for details. 5. Special lug arrangements may require different enclosure dimensions. See full product brochure (DEA-405) for details. 6. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 7. Add 4" in height for removable lifting lugs. 8. Lug adapters for A limits may be staggered length for ease of entrance. Consult the factory for details A switches have ventilation louvers on both sides and rear of enclosure. Louvers must be clear for airflow with standard cable connections. UL 1008 Withstand and Closing Ratings Please refer to GE Publication TB-110 Rev. 11/13 BuyLog Catalog 14-35
36 Model ZTECT ZTECT Series Low-Voltage, Closed Transition, Automatic and Manual Transfer Switches Ideal for mission critical loads (computer servers, HID emergency lighting, data acquisition equipment) Two source parallel time ( bumpless transfer ) of less than 100 milliseconds Integrated backup protection to prevent extended parallel conditions Ratings 100 to 4000 amperes Ratings & Construction Ratings Voltage, Ampere and Pole configuration per Order Code Certifications UL 1008, CSA C. Certifications Third-party Seismic Certification to IBC 009, Ip = 1.5 (operation during event) Electrical Operator Momentarily energized, high-speed solenoid mechanism Mechanism Mechanically-held with highspeed transfer mechanism for make-beforebreak closed transition transfers Contacts GE design and manufactured, silver tungsten alloy with separate arcing contacts on 600A and above ratings for high withstand and close-on capability Neutral Pole (4 pole only) Identical construction to phase poles with fully rated main and arcing contacts. Operation via same mechanism as phase poles to prevent sustained connection of source neutrals in separately derived systems, as last-break/ first-make transfer. Controller Construction Dual-processor based, with dedicated processor for high-speed Serial or Ethernet communications Source Sensing Direct V sensing and software configuration of rated voltage and frequency without the need for potential transformers, step-down transformers or DIP switches Control Wiring All customer connections at one location. All signals in/out relay-isolated via DIN-mounted relay/terminal blocks. All control wiring via factory-installed wiring harnesses. Enclosure Type per Order Code Display, Sensing & Time Delays Display ¼ VGA color graphical with embedded HELP menus Annunciation High intensity LED for Source Availability (), Source Connected (), Transfer Inhibit (not in Auto) Source Fail/Restore Independently adjustable pickup & dropout of 3-phase U/O voltage, U/O Freq, Volts Balance plus Phase Rotation Time Delays Gen start, Source stabilize, Source fail override, Retransfer to Source 1, Gen cool down, Independent settings for Fast Test, Time Delay for Generator Voltage Sag Remote Access All parameters locally (front USB port) or remotely (serial or Ethernet) Adjustable Control Group Options (see order code) Group A: All standard features, Field re-programmable I/O (4 inputs, 4 outputs), Control Switches (Test with Load, Test no load, Fast Test, Alarm Reset, Auto/Man Re-transfer Source 1, Auto/Man Transfer both sources, Preferred Source select, Commit/No Commit Transfer to Gen, Time Delay Bypass Group B: All features from A plus: 10 User-configurable Analog & 10 Digital Alarms, 0-channel data logger, 10-channel waveform capture, Auto Load Shed (with voltage, frequency, and kw triggers) Group C: All features from B plus: 4 additional field programmable inputs (total 8 inputs, 8 outputs) Group D: All features from C plus: 4 additional field programmable inputs (total 1 inputs, 1 outputs) & GE Flexlogic user-configurable control logic Group M: Manual ATS configuration Additional Standard Features Engine Exerciser Configurable Periodic Exerciser (7 Event Daily, Weekly, 14 or 8 day) or Clock Exerciser Type (1 Event, 365 day Programmable) System Status Screen Active state of switch, display of all time delays and alarm conditions Event Recorder 56 Event, 1ms accuracy, clock sync via Network Time Protocol (NTP) Outage & Test Report Screen Date/time stamping of: outage or test event, start signal sent, Gen start time, connection to Gen, Max Gen Volts & Freq dip, return of utility, re-transfer to normal External Power Supply Standard 10VAC input for controller power and communication and 4 VDC input for remote control and annunciation when both sources de-energized Flexible Feature Assignment Field reassignable I/O for any/all control features Fail to Sync and Extended Parallel Protection Hardwired, independent controller Optional Features (see order code) Serial Communications High speed, up to 115k Baud Modbus RTU Ethernet Communications Fast Ethernet, (10/100 Mbit), Modbus TCP/IP Power Quality Metering True RMS metering, including THD% (up to 8th order) Load Shed Ability to transfer to de-energized normal source or center position in event of generator overload Integral Surge Protective Device (SPD) Load-connected medium or high exposure type Integral Battery Charger 3 or 10A, 1 or 4VDC type Lugs Compression lugs in lieu of standard mechanical lugs on 100A-100A switches Lugs Mechanical or Compression lugs in lieu of standard rearbus connection on A switches BuyLog Catalog Rev. 11/13
37 Model ZTECT Order Code Abbreviated Product Configuration (see full Product Brochure, Publication DEA-405, for full configuration) Z1C X Amperage C = 100 D = 150 F = 5 G = 60 I = 400 J = 600 K = 800 L = 1000 M = 100 N = 1600 O = 000 Q = 3000 R = 4000 # of Poles = Pole 3 = 3 Pole 4 = 4 Pole Application S = Util-Gen U = Util-Util G = Gen-Gen Controller Language 1 = English ZTECT Model, Dimensions and Weights NEMA Enclosure (Open) A = NEMA 1 B = NEMA 1A C = NEMA 3R D = NEMA 3R w/htr E = NEMA 4 F = NEMA 1 G = NEMA 4X Control Group Options A = Group A B = Group B C = Group C D = Group D M = Group M Voltage Code 70 = 77/480V, 3PH, 4W, 60Hz 0 = 10/40V, 1PH, 3W, 60Hz 40 = 10/08V, 3PH, 4W, 60Hz 9 = 0/380V, 3PH, 4W, 50Hz 50 = 480V, 3PH, 3W, 60Hz 38 = 10/08/40V, 3PH, 4W, High-Leg Delta, 60Hz 30 = 40V, 3PH, 3W, 60Hz 31 = 08V, 3PH, 3W, 60Hz brochure for other options Lug Options X = Std lugs or Rear bus (per chart below) brochure for lug option details) Metering & Accessories A = Load Shed D = PQ Metering NEMA 1 Weight Application Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Figure Open Type NEMA 1 Notes 100, 150, (57) 0 (100) 66 (168) 4 (61) 0 (50) A 60, (66) 41 (109) 10 (59), (84) 16 (57) (76) A (1880) (1016) (50) 05 (93) 180 (8) 800, 1000, 3 10 (95) 460 (09) (104) 490 (3) 1600, (166) 1010 (458) (04) 1160 (56) (86) (90) (116) 485 (0) 1130 (513) B (313) 1396 (633) (37) 1595 (73) 4 (86) (1180) (154) 1045 (474) 1850 (839) Ground Bus 1 = Ground bus- Mech Lugs (Qty. 3) #14-1/0-GB1 = Ground bus- Mech Lugs (Qty. 6) #8-1/0 -GB SPD (Load-Side Connected) 100A - 100A Rating A = 65kA B = 80kA C = 100kA 1600A A Rating D = 100kA E = 150kA F = 00kA G = 300kA Communications S = CCM S-Modbus RTU (Serial) communication module E = CCM E Modbus TCP/IP (Ethernet) communication module E = plus Modbus RTU (Serial) communication module AL-CU UL Listed Mechanical Lugs Battery Charger 1 = Battery Charger-1 Volt-3 Amp = Battery Charger-1 Volt-10 Amp Normal, Emergency & Load Terminals Switch Size Amps Cables/Pole Wire Ranges ZTECT 100, #4 to 600 MCM 5 1 #4 to 600 MCM 60 1 #4 to 600 MCM #4 to 600 MCM 600 # to 600 MCM 800, 1000, # to 600 MCM 1600, 000, 3000, 4000 * * Notes: * Line and load terminals are located in rear and arranged for bus bar connection. Terminal lugs are available as an accessory. See full product brochure (DEA-405) for option details. 1. Fully rated neutral provided on 3 phase, 4 wire system Application Notes 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are subject to change. 4. NEMA 3R, 4, 4X and 1 enclosure dimensions may differ than NEMA 1 shown above. Consult the factory for details. 5. Special lug arrangements may require different enclosure dimensions. See full product brochure (DEA-405) for details. 6. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 7. Add 4" in height for removable lifting lugs A depth dimension shown is standard. Depending on your cable/conduit requirements, you may desire a deeper enclosure. Consult the factory for further details A switches have ventilation louvers on both sides and rear of enclosure. Louvers must be clear for airflow with standard cable connections. UL 1008 Withstand and Closing Ratings Please refer to GE Publication TB-110 Rev. 11/13 BuyLog Catalog 14-37
38 Model ZBTE ZBTE Series Low-Voltage, Bypass/Isolation Open Transition, Automatic and Manual Transfer Switches Ideal for mixed (inductive and resistive) mission critical loads Contact transfer speed less than 100 milliseconds Bypass/Isolation for ease of ATS maintenance/testing without load loss of power Ratings 100 to 4000 amperes Ratings & Construction Ratings Voltage, Ampere and Pole configuration per Order Code Certifications UL 1008, CSA C. Certifications Third-party Seismic Certification to IBC 009, Ip = 1.5 (operation during event) Electrical Operator Momentarily energized, high-speed solenoid mechanism Mechanism Mechanically-held with mechanical interlock to inhibit connection of both sources to the load Contacts GE design and manufactured, silver tungsten alloy with separate arcing contacts on 600A and above ratings for high withstand and close-on capability Neutral Pole (4 pole only) Identical construction to phase poles with fully rated main and arcing contacts. Operation via same mechanism as phase poles to prevent sustained connection of source neutrals in separately derived systems, as last-break/first-make transfer. Controller Construction Dual-processor based, with dedicated processor for high-speed Serial or Ethernet communications Source Sensing Direct V sensing and software configuration of rated voltage and frequency without the need for potential transformers, step-down transformers or DIP switches Control Wiring All customer connections at one location. All signals in/out relay-isolated via DIN-mounted relay/terminal blocks. All control wiring via factory-installed wiring harnesses. Enclosure Type per Order Code Display, Sensing & Time Delays Display ¼ VGA color graphical with embedded HELP menus Annunciation High intensity LED for Source Availability (), Source Connected (), Transfer Inhibit (not in Auto) Source Fail/Restore Independently adjustable pickup & dropout of 3-phase U/O voltage, U/O Freq, Volts Balance plus Phase Rotation Time Delays Gen start, Source stabilize, Source fail override, Retransfer to Source 1, Gen cool down, Independent settings for Fast Test, Time Delay for Generator Voltage Sag Remote Access All parameters locally (front USB port) or remotely (serial or Ethernet) Adjustable Control Group Options (see order code) Group A: All standard features, Field re-programmable I/O (4 inputs, 4 outputs), Control Switches (Test with Load, Test no load, Fast Test, Alarm Reset, Auto/Man Re-transfer Source 1, Auto/Man Transfer both sources, Preferred Source select, Commit/No Commit Transfer to Gen, Time Delay Bypass Group B: All features from A plus: 10 User-configurable Analog & 10 Digital Alarms, 0-channel data logger, 10-channel waveform capture, Auto Load Shed (with voltage, frequency, and kw triggers) Group C: All features from B plus: 4 additional field programmable inputs (total 8 inputs, 8 outputs) Group D: All features from C plus: 4 additional field programmable inputs (total 1 inputs, 1 outputs) & GE Flexlogic user-configurable control logic Group M: Manual ATS configuration Additional Standard Features Engine Exerciser Configurable Periodic Exerciser (7 Event Daily, Weekly, 14 or 8 day) or Clock Exerciser Type (1 Event, 365 day Programmable) System Status Screen Active state of switch, display of all time delays and alarm conditions Event Recorder 56 Event, 1ms accuracy, clock sync via Network Time Protocol (NTP) Outage & Test Report Screen Date/time stamping of: outage or test event, start signal sent, Gen start time, connection to Gen, Max Gen Volts & Freq dip, return of utility, re-transfer to normal External Power Supply Standard 10VAC input for controller power and communication and 4 VDC input for remote control and annunciation when both sources de-energized Flexible Feature Assignment Field reassignable I/O for any/all control features In-Phase Monitor For phase matching prior to Live-Live transfers of load Optional Features (see order code) Serial Communications High speed, up to 115k Baud Modbus RTU Ethernet Communications Fast Ethernet, (10/100 Mbit), Modbus TCP/IP Power Quality Metering True RMS metering, including THD% (up to 8th order) Load Shed Ability to transfer to de-energized normal source or center position in event of generator overload Integral Surge Protective Device (SPD) Load-connected medium or high exposure type Integral Battery Charger 3 or 10A, 1 or 4VDC type Lugs Compression lugs in lieu of standard mechanical lugs on 100A-100A switches Lugs Mechanical or Compression lugs in lieu of standard rearbus connection on A switches BuyLog Catalog Rev. 11/13
39 Model ZBTE Order Code Abbreviated Product Configuration (see full Product Brochure, Publication DEA-405, for full configuration) Z O X Product Type Operation Z** = Bypass/ O = Open Isolation Vertical Transition Construction Z3** = Bypass/Isolation Horizontal Construction * Amperage Excluded ** Applicable to Amperage Amperage C = 100 D = 150 F = 5 G = 60 I = 400 J = 600 K = 800 L = 1000 M = 100 N = 1600 O = 000 P = 600 Q = 3000 R = 4000 # of Poles = Pole 3 = 3 Pole 4 = 4 Pole Application S = Util-Gen U = Util-Util G = Gen-Gen Controller Language 1 = English ZBTE Model, Dimensions and Weights NEMA Enclosure (Open) H = NEMA 1 w/adapter Bay I = NEMA 3R w/adapter Bay J = NEMA 3R/Heater & Thermostat/ Adapter Bay K = NEMA 4 w/adapter Bay L = NEMA 1 w/adapter Bay M = NEMA 4X Controller w/adapter Bay Control Group Options A = Group A B = Group B C = Group C D = Group D M = Group M Voltage Code 70 = 77/480V, 3PH, 4W, 60Hz 0 = 10/40V, 1PH, 3W, 60Hz 40 = 10/08V, 3PH, 4W, 60Hz 9 = 0/380V, 3PH, 4W, 50Hz 50 = 480V, 3PH, 3W, 60Hz 38 = 10/08/40V, 3PH, 4W, High-Leg Delta, 60Hz 30 = 40V, 3PH, 3W, 60Hz 31 = 08V, 3PH, 3W, 60Hz 61 = 347/600V, 3PH, 4W, 60Hz brochure for other options Lug Options X = Std lugs or Rear bus (per chart below) brochure for lug option details) NEMA 1 Enclosed Weight Application Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Figure Open Type NEMA 1 Notes 100, 150, 3 83 (109) 30 (76) 8.5 (74) 310 (141) 180 (580) 5, 60 A (109) 30 (76) 8.5 (74) 380 (173) 1385 (68) 400, 3 90 (86) 36 (914) 8.5 (737) 660 (99) 1435 (651) (86) 40 (1016) 8.5 (737) 770 (349) 1540 (699) B , 1000, 3 90 (86) 40 (1016) 8.5 (737) 765 (347) 1485 (674) (86) 46 (1168) 8.5 (737) 910 (413) 1590 (71) 1600, 000, 3 80 (03) 40.6 (1031) 64.6 (1640) 1978 (897) 4044 (1835) 1-6, (03) 46.1 (1171) 64.6 (1640) 75 (103) 4431 (010) C 3 80 (03) 40.6 (1031) 64.6 (1640) 57 (1166) 4456 (01) (03) 46.1 (1171) 64.6 (1640) 3049 (1383) 4977 (58) 1-6, (86) 47.5 (106) 80.8 (051) 4310 (1955) 4730 (145) 4000 D 4 90 (86) 54 (137) 80.8 (051) 5510 (499) 5930 (690) Application Notes 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are subject to change. 4. NEMA 3R, 4, 4X and 1 enclosure dimensions may differ than NEMA 1 shown above. Consult the factory for details. 5. Special lug arrangements may require different enclosure dimensions. See full product brochure (DEA- 405) for details. 6. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 7. Add 4" in height for removable lifting lugs. 8. ZBTE A standard configuration is top entry. 14" rear adapter bay required for bottom entry. Consult the factory for details. 9. Bypass switch weights for A units vary up to 10% based on connections variations. Weights shown are for estimation only. Consult the factory for details A switches have ventilation louvers on both sides and rear of enclosure. Louvers must be clear for airflow with standard cable connections. 11. Lug adapters for A limits may be staggered length for ease of cable entrance. Consult the factory for details. AL-CU UL Listed Mechanical Lugs Normal, Emergency & Load Terminals Switch Size Amps Cables/Pole Wire Ranges ZBTE 100, 150, 5 1 #3/0 to 50 MCM 60 1 #4 to 600 MCM #4 to 600 MCM 600 # to 600 MCM 800, 1000, # to 600 MCM 1600, 000, 600, 3000, 4000 * * Notes: * Line and load terminals are located in rear and arranged for bus bar connection. Terminal lugs are available as an accessory. See full product brochure (DEA-405) for option details. 1. Fully rated neutral provided on 3 phase, 4 wire system UL 1008 Withstand and Closing Ratings Please refer to GE Publication TB-110 Metering & Accessories A = Load Shed D = PQ Metering Communications Ground Bus 1 = Ground bus- Mech Lugs (Qty. 3) #14-1/0-GB1 = Ground bus- Mech Lugs (Qty. 6) #8-1/0 -GB SPD (Load-Side Connected) 100A - 100A Rating A = 65kA B = 80kA C = 100kA 1600A A Rating D = 100kA E = 150kA F = 00kA G = 300kA S = CCM S-Modbus RTU (Serial) communication module E = CCM E Modbus TCP/IP (Ethernet) communication module E = plus Modbus RTU (Serial) communication module Battery Charger 1 = Battery Charger-1 Volt-3 Amp = Battery Charger-1 Volt-10 Amp Rev. 11/13 BuyLog Catalog 14-39
40 Model ZBTED ZBTED Series Low-Voltage, Bypass/Isolation Delayed Transition, Automatic and Manual Transfer Switches Ideal for inductive (motors/transformers, UPS) mission critical loads Adjustable ATS time delay in center off position Bypass/Isolation for ease of ATS maintenance/testing without load loss of power Ratings 100 to 4000 amperes Ratings & Construction Ratings Voltage, Ampere and Pole configuration per Order Code Certifications UL 1008, CSA C. Certifications Third-party Seismic Certification to IBC 009, Ip = 1.5 (operation during event) Electrical Operator Momentarily energized, high-speed solenoid mechanism Mechanism Mechanically-held with mechanical interlock to inhibit connection of both sources to the load Contacts GE design and manufactured, silver tungsten alloy with separate arcing contacts on 600A and above ratings for high withstand and close-on capability Neutral Pole (4 pole only) Identical construction to phase poles with fully rated main and arcing contacts. Operation via same mechanism as phase poles to prevent sustained connection of source neutrals in separately derived systems, as lastbreak/ first-make transfer. Controller Construction Dual-processor based, with dedicated processor for high-speed Serial or Ethernet communications Source Sensing Direct V sensing and software configuration of rated voltage and frequency without the need for potential transformers, step-down transformers or DIP switches Control Wiring All customer connections at one location. All signals in/out relay-isolated via DIN-mounted relay/terminal blocks. All control wiring via factory-installed wiring harnesses. Enclosure Type per Order Code Display, Sensing & Time Delays Display ¼ VGA color graphical with embedded HELP menus Annunciation High intensity LED for Source Availability (), Source Connected (), Transfer Inhibit (not in Auto) Source Fail/Restore Independently adjustable pickup & dropout of 3-phase U/O voltage, U/O Freq, Volts Balance plus Phase Rotation Time Delays Gen start, Source stabilize, S1 g S transfer center-off delay, Source fail override, Retransfer to Source 1, S g S1 transfer center-off delay, Gen cool down, Independent settings for Fast Test, Time Delay for Generator Voltage Sag Remote Access All parameters locally (front USB port) or remotely (serial or Ethernet) Adjustable Control Group Options (see order code) Group A: All standard features, Field re-programmable I/O (4 inputs, 4 outputs), Control Switches (Test with Load, Test no load, Fast Test, Alarm Reset, Auto/Man Re-transfer Source 1, Auto/Man Transfer both sources, Preferred Source select, Commit/No Commit Transfer to Gen, Time Delay Bypass Group B: All features from A plus: 10 User-configurable Analog & 10 Digital Alarms, 0-channel data logger, 10-channel waveform capture, Auto Load Shed (with voltage, frequency, and kw triggers) Group C: All features from B plus: 4 additional field programmable inputs (total 8 inputs, 8 outputs) Group D: All features from C plus: 4 additional field programmable inputs (total 1 inputs, 1 outputs) & GE Flexlogic user - configurable control logic Group M: Manual ATS configuration Additional Standard Features Engine Exerciser Configurable Periodic Exerciser (7 Event Daily, Weekly, 14 or 8 day) or Clock Exerciser Type (1 Event, 365 day Programmable) System Status Screen Active state of switch, display of all time delays and alarm conditions Event Recorder 56 Event, 1ms accuracy, clock sync via Network Time Protocol (NTP) Outage & Test Report Screen Date/time stamping of: outage or test event, start signal sent, Gen start time, connection to Gen, Max Gen Volts & Freq dip, return of utility, re-transfer to normal External Power Supply Standard 10VAC input for controller power and communication and 4 VDC input for remote control and annunciation when both sources de-energized Flexible Feature Assignment Field reassignable I/O for any/all control features Programmable Center-Off Position For transition of motor and regenerative loads Optional Features (see order code) Serial Communications High speed, up to 115k Baud Modbus RTU Ethernet Communications Fast Ethernet, (10/100 Mbit), Modbus TCP/IP Power Quality Metering True RMS metering, including THD% (up to 8th order) Load Shed Ability to transfer to de-energized normal source or center position in event of generator overload Integral Surge Protective Device (SPD) Load-connected medium or high exposure type Integral Battery Charger 3 or 10A, 1 or 4VDC type Lugs Compression lugs in lieu of standard mechanical lugs on 100A-100A switches Lugs Mechanical or Compression lugs in lieu of standard rearbus connection on A switches BuyLog Catalog Rev. 11/13
41 Model ZBTED Order Code Abbreviated Product Configuration (see full Product Brochure, Publication DEA-405, for full configuration) Z D X Product Type Z** = Bypass/ Isolation Vertical Construction Z3** = Bypass/Isolation Horizontal Construction * Amperage Excluded ** Applicable to Amperage Operation D = Delayed Transition Amperage C = 100 D = 150 F = 5 G = 60 I = 400 J = 600 K = 800 L = 1000 M = 100 N = 1600 O = 000 Q = 3000 R = 4000 # of Poles = Pole 3 = 3 Pole 4 = 4 Pole Application S = Util-Gen U = Util-Util G = Gen-Gen Controller Language 1 = English ZBTED Model, Dimensions and Weights NEMA Enclosure (Open) H = NEMA 1 w/adapter Bay I = NEMA 3R w/adapter Bay J = NEMA 3R/Heater & Thermostat/ Adapter Bay K = NEMA 4 w/adapter Bay L = NEMA 1 w/adapter Bay M = NEMA 4X Controller w/adapter Bay Control Group Options A = Group A B = Group B C = Group C D = Group D M = Group M Voltage Code 70 = 77/480V, 3PH, 4W, 60Hz 0 = 10/40V, 1PH, 3W, 60Hz 40 = 10/08V, 3PH, 4W, 60Hz 9 = 0/380V, 3PH, 4W, 50Hz 50 = 480V, 3PH, 3W, 60Hz 38 = 10/08/40V, 3PH, 4W, High-Leg Delta, 60Hz 30 = 40V, 3PH, 3W, 60Hz 31 = 08V, 3PH, 3W, 60Hz 61 = 347/600V, 3PH, 4W, 60Hz brochure for other options Lug Options X = Std lugs or Rear bus (per chart below) brochure for lug option details) NEMA 1 Enclosed Weight Application Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Figure Open Type NEMA 1 Notes 100, 150, (141) 180 (580) 5, (109) 30 (76) 8.5 (74) A (173) 1385 (68) (86) 36 (914) 8.3 (737) 660 (99) 1435 (651) 1-7, (86) 40 (1016) 8.3 (737) 770 (349) 1540 (699) B 800, (86) 40 (1016) 8.3 (737) 765 (347) 1485 (674) (86) 46 (1168) 8.3 (737) 910 (413) 1590 (71) 1600, (03) 40.6 (1031) 64.6 (1640) 1978 (897) 4044 (1835) 1-6, (03) 46.1 (1171) 64.6 (1640) 75 (103) 4431 (010) C 3 80 (03) 40.6 (1031) 64.6 (1640) 57 (1166) 4456 (01) (03) 46.1 (1171) 64.6 (1640) 3049 (1383) 4977 (58) 1-6, 3 90 (86) 47.5 (106) 80.8 (051) 4310 (1955) 4730 (145) 8, D 4 90 (86) 54 (137) 80.8 (051) 5510 (499) 5930 (690) Metering & Accessories A = Load Shed D = PQ Metering Communications Ground Bus 1 = Ground bus- Mech Lugs (Qty. 3) #14-1/0-GB1 = Ground bus- Mech Lugs (Qty. 6) #8-1/0 -GB SPD (Load-Side Connected) 100A - 100A Rating A = 65kA B = 80kA C = 100kA 1600A A Rating D = 100kA E = 150kA F = 00kA G = 300kA S = CCM S-Modbus RTU (Serial) communication module E = CCM E Modbus TCP/IP (Ethernet) communication module E = plus Modbus RTU (Serial) communication module Battery Charger 1 = Battery Charger-1 Volt-3 Amp = Battery Charger-1 Volt-10 Amp Application Notes 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are subject to change. 4. NEMA 3R, 4, 4X and 1 enclosure dimensions may differ than NEMA 1 shown above. Consult the factory for details. 5. Special lug arrangements may require different enclosure dimensions. See full product brochure (DEA- 405) for details. 6. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 7. Add 4" in height for removable lifting lugs. 8. Lug adapters for A limits may be staggered length for ease of entrance. Consult the factory for details A standard configuration is top cable entry. 14" adapter bay is required for bottom cable entry. Consult the factory for details A switches have ventilation louvers on both sides and rear of enclosure. Louvers must be clear for airflow with standard cable connections. ZBTED Model Delayed Transition Transfer/Bypass-Isolation Switches The ZTED Delayed Transition Transfer Switch with a timed center-off position is available in a bypass configuration. The ZBTED Model Bypass incorporates the features of both the ZBTE Bypass-Isolation Switch and the ZTED unit for transfer of large motor loads, transformers, UPS systems or load shedding to a neutral Off position. Reference the ZTED unit features and operation discussion for more details. UL 1008 Withstand and Closing Ratings Please refer to GE Publication TB-110 AL-CU UL Listed Mechanical Lugs Normal, Emergency & Load Terminals Switch Size Amps Cables/Pole Wire Ranges ZBTED 100, 150, 5 1 #3/0 to 50 MCM 60 1 #4 to 600 MCM #4 to 600 MCM 600 # to 600 MCM 800, 1000, # to 600 MCM 1600, 000, 600, 3000, 4000 * * Notes: * Line and load terminals are located in rear and arranged for bus bar connection. Terminal lugs are available as an accessory. See full product brochure (DEA-405) for option details. 1. Fully rated neutral provided on 3 phase, 4 wire system Rev. 11/13 BuyLog Catalog 14-41
42 Model ZBTECT ZBTECT Series Low-Voltage, Bypass/Isolation Closed Transition, Automatic and Manual Transfer Switches Ideal for mission critical loads (computer servers, HID emergency lighting, data acquisition equipment) Two source parallel time ( bumpless transfer ) of less than 100 milliseconds Bypass/Isolation for ease of ATS maintenance/testing without load loss of power Ratings 100 to 4000 amperes Ratings & Construction Ratings Voltage, Ampere and Pole configuration per Order Code Certifications UL 1008, CSA C. Certifications Third-party Seismic Certification to IBC 009, Ip = 1.5 (operation during event) Electrical Operator Momentarily energized, high-speed solenoid mechanism Mechanism Mechanically-held with highspeed transfer mechanism for make-before break closed transition transfers Contacts GE design and manufactured, silver tungsten alloy with separate arcing contacts on 600A and above ratings for high withstand and close-on capability Neutral Pole (4 pole only) Identical construction to phase poles with fully rated main and arcing contacts. Operation via same mechanism as phase poles to prevent sustained connection of source neutrals in separately derived systems, as lastbreak/first-make transfer. Controller Construction Dual-processor based, with dedicated processor for high-speed Serial or Ethernet communications Source Sensing Direct V sensing and software configuration of rated voltage and frequency without the need for potential transformers, step-down transformers or DIP switches Control Wiring All customer connections at one location. All signals in/out relay-isolated via DIN-mounted relay/terminal blocks. All control wiring via factory-installed wiring harnesses. Enclosure Type per Order Code Display, Sensing & Time Delays Display ¼ VGA color graphical with embedded HELP menus Annunciation High intensity LED for Source Availability (), Source Connected (), Transfer Inhibit (not in Auto) Source Fail/Restore Independently adjustable pickup & dropout of 3-phase U/O voltage, U/O Freq, Volts Balance plus Phase Rotation Time Delays Gen start, Source stabilize, Source fail override, Retransfer to Source 1, Gen cool down, Independent settings for Fast Test, Time Delay for Generator Voltage Sag Remote Access All parameters locally (front USB port) or remotely (serial or Ethernet) Adjustable Control Group Options (see order code) Group A: All standard features, Field re-programmable I/O (4 inputs, 4 outputs), Control Switches (Test with Load, Test no load, Fast Test, Alarm Reset, Auto/Man Re-transfer Source 1, Auto/Man Transfer both sources, Preferred Source select, Commit/No Commit Transfer to Gen, Time Delay Bypass Group B: All features from A plus: 10 User-configurable Analog & 10 Digital Alarms, 0-channel data logger, 10-channel waveform capture, Auto Load Shed (with voltage, frequency, and kw triggers) Group C: All features from B plus: 4 additional field programmable inputs (total 8 inputs, 8 outputs) Group D: All features from C plus: 4 additional field programmable inputs (total 1 inputs, 1 outputs) & GE Flexlogic user-configurable control logic Group M: Manual ATS configuration Additional Standard Features Engine Exerciser Configurable Periodic Exerciser (7 Event Daily, Weekly, 14 or 8 day) or Clock Exerciser Type (1 Event, 365 day Programmable) System Status Screen Active state of switch, display of all time delays and alarm conditions Event Recorder 56 Event, 1ms accuracy, clock sync via Network Time Protocol (NTP) Outage & Test Report Screen Date/time stamping of: outage or test event, start signal sent, Gen start time, connection to Gen, Max Gen Volts & Freq dip, return of utility, re-transfer to normal External Power Supply Standard 10VAC input for controller power and communication and 4 VDC input for remote control and annunciation when both sources de-energized Flexible Feature Assignment Field reassignable I/O for any/all control features Fail to Sync and Extended Parallel Protection Hardwired, independent controller Optional Features (see order code) Serial Communications High speed, up to 115k Baud Modbus RTU Ethernet Communications Fast Ethernet, (10/100 Mbit), Modbus TCP/IP Power Quality Metering True RMS metering, including THD% (up to 8th order) Load Shed Ability to transfer to de-energized normal source or center position in event of generator overload Integral Surge Protective Device (SPD) Load-connected medium or high exposure type Integral Battery Charger 3 or 10A, 1 or 4VDC type Lugs Compression lugs in lieu of standard mechanical lugs on 100A-100A switches Lugs Mechanical or Compression lugs in lieu of standard rearbus connection on A switches 14-4 BuyLog Catalog Rev. 11/13
43 Model ZBTECT Order Code Abbreviated Product Configuration (see full Product Brochure, Publication DEA-405, for full configuration) Z C X Product Type Z** = Bypass/ Isolation Vertical Construction Z3** = Bypass/Isolation Horizontal Construction * Amperage Excluded ** Applicable to Amperage Operation C = Closed Transition Amperage C = 100 D = 150 F = 5 G = 60 I = 400 J = 600 K = 800 L = 1000 M = 100 N = 1600 O = 000 P = 600 Q = 3000 R = 4000 # of Poles = Pole 3 = 3 Pole 4 = 4 Pole Application S = Util-Gen U = Util-Util G = Gen-Gen Controller Language 1 = English ZBTECT Model, Dimensions and Weights NEMA Enclosure (Open) H = NEMA 1 w/adapter Bay I = NEMA 3R w/adapter Bay J = NEMA 3R/Heater & Thermostat/ Adapter Bay K = NEMA 4 w/adapter Bay L = NEMA 1 w/adapter Bay M = NEMA 4X Controller w/adapter Bay Control Group Options A = Group A B = Group B C = Group C D = Group D M = Group M Voltage Code 70 = 77/480V, 3PH, 4W, 60Hz 0 = 10/40V, 1PH, 3W, 60Hz 40 = 10/08V, 3PH, 4W, 60Hz 9 = 0/380V, 3PH, 4W, 50Hz 50 = 480V, 3PH, 3W, 60Hz 38 = 10/08/40V, 3PH, 4W, High-Leg Delta, 60Hz 30 = 40V, 3PH, 3W, 60Hz 31 = 08V, 3PH, 3W, 60Hz 61 = 347/600V, 3PH, 4W, 60Hz brochure for other options Lug Options X = Std lugs or Rear bus (per chart below) brochure for lug option details) NEMA 1 Enclosed Weight Application Ampere Rating Poles Height (A) Width (B) Depth (C) Ref. Figure Open Type NEMA 1 Notes 100, 150, 5, (331) 180 (580) 90 (86) 36 (914) 8.5 (74) 60, (381) 1385 (68) (86) 36 (914) 8.3 (737) 730 (331) 1435 (651) A 4 90 (86) 40 (1016) 8.3 (737) 840 (381) 1540 (699) 1-7, 9 800, (86) 40 (1016) 8.3 (737) 835 (379) 1485 (674) (86) 46 (1168) 8.3 (737) 980 (444) 1590 (71) 1600, (03) 40.6 (1031) 64.6 (1640) 1978 (897) 4044 (1835) 1-6, (03) 46.1 (1171) 64.6 (1640) 75 (103) 4431 (010) B 3 80 (03) 40.6 (1031) 64.6 (1640) 57 (1166) 4456 (01) (03) 46.1 (1171) 64.6 (1640) 3049 (1383) 4977 (58) 1-6, (86) 47.5 (106) 80.8 (051) 4380 (1986) 4730 (145) 8, 10 C 4 90 (86) 54 (137) 80.8 (051) 5580 (531) 5930 (690) Metering & Accessories A = Load Shed D = PQ Metering Communications Ground Bus 1 = Ground bus- Mech Lugs (Qty. 3) #14-1/0-GB1 = Ground bus- Mech Lugs (Qty. 6) #8-1/0 -GB SPD (Load-Side Connected) 100A - 100A Rating A = 65kA B = 80kA C = 100kA 1600A A Rating D = 100kA E = 150kA F = 00kA G = 300kA S = CCM S-Modbus RTU (Serial) communication module E = CCM E Modbus TCP/IP (Ethernet) communication module E = plus Modbus RTU (Serial) communication module Battery Charger 1 = Battery Charger-1 Volt-3 Amp = Battery Charger-1 Volt-10 Amp Application Notes 1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.. Includes 1.5" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are subject to change. 4. NEMA 3R, 4, 4X and 1 enclosure dimensions may differ than NEMA 1 shown above. Consult the factory for details. 5. Special lug arrangements may require different enclosure dimensions. See full product brochure (DEA- 405) for details. 6. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 7. Add 4" in height for removable lifting lugs. 8. Lug adapters for A limits may be staggered length for ease of entrance. Consult the factory for details A standard configuration is top cable entry. 14 adapter bay is required for bottom cable entry. Consult the factory for details A switches have ventilation louvers on both sides and rear of enclosure. Louvers must be clear for airflow with standard cable connections. ZBTECT Model Closed Transition Transfer/Bypass-Isolation Switches The ZTECT Closed Transition Transfer Switch may be applied with a bypass-isolation switch for the utmost in reliability and versatility. The ZBTECT Model provides the ability to withdraw the transfer switch unit for maintenance or inspection. Reference the ZTECT unit features and operation discussion for more details. UL 1008 Withstand and Closing Ratings Please refer to GE Publication TB-110 AL-CU UL Listed Mechanical Lugs Normal, Emergency & Load Terminals Switch Size Amps Cables/Pole Wire Ranges ZBTECT 100, 150, 5, 60, #4 to 600 MCM 600 # to 600 MCM 800, 1000, # to 600 MCM 1600, 000, 600, 3000, 4000 * * Notes: * Line and load terminals are located in rear and arranged for bus bar connection. Terminal lugs are available as an accessory. See full product brochure (DEA-405) for option details. 1. Fully rated neutral provided on 3 phase, 4 wire system Rev. 11/13 BuyLog Catalog 14-43
44 NOTES: BuyLog Catalog Rev. 11/13
CTS SERIES AUTOMATIC TRANSFER SWITCH
CTS SERIES AUTOMATIC TRANSFER SWITCH The Cat CTS Series Automatic Transfer Switch (ATS) is configurable for applications requiring the dependability and ease of operation found in a full featured power
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
GTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply
GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator
Transfer switch BTPC open, closed or delayed transition
Transfer switch BTPC open, closed or delayed transition 150-4000 Amp Description The Cummins Power Generation BTPC series bypass isolation transfer switch combines an automatic transfer switch with a drawout
ASCO SERIES 185 Power Transfer Switches
ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches
PART 1 GENERAL 1.01 Scope SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches Division 16 - Electrical Standby Power Generator Systems A. Furnish and install service entrance automatic
How To Test A Power Switch On A Power Supply
transfer switches Soft load Innovative, reliable, integrated solution Built with years of experience Powered with innovation Delivered with reliability A history of experience, innovation and reliability
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
Zenith Controls ISO 9001 50R-1000C 5/99
OPERATION AND MAINTENANCE MANUAL TRANSFER SWITCH CONTROL PANEL MX100 MICROPROCESSOR CONTROLLER g GE Zenith Controls ISO 9001 50R-1000C 5/99 Table of Contents Page Safety... 1 Final Equipment Inspection...
Continuous Power... Continuous Protection
Series 165 We Keep Your Power On Continuous Power... Continuous Protection An Automatic Transfer Switch helps prevent... Your business or home from losing power during bad weather or utility power equipment
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
Automatic Transfer Switch Controller
Automatic Transfer Switch Controller Decision-Makerr MPAC 1500 Model KBS with Decision-Makerr MPAC 1500 Controller Applicable Models Model Description KCS Standard-Transition Any Breaker ATS ] KCP Programmed-Transition
Transfer Switches GE Zenith Controls
ZTS Series Transfer Switches GE Zenith ontrols ZTS Series Power ontrol Equipment Quality-Assurance from Start to Shipment Since 92, GE Zenith has designed products with customer satisfaction in mind commencing
Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
Series TS 870 100-1200 Amp. Automatic Transfer Switches
Series TS 870 100-1200 Amp Automatic Transfer Switches A Regal Brand TS 870 AUTOMATIC TRANSFER SWITCHES THOMSON POWER SYSTEMS TS 870 AUTOMATIC TRANSFER SWITCHES OFFER THE FOLLOWING OUTSTANDING FEATURES:
Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
ATC-300 Automatic Transfer Switch Controller
ATC-300 Technical Data New Information Technical Data Page 2 Effective: May 2004 ATC-300 Introduction The Cutler-Hammer ATC-300 from Eaton s Electrical business is a comprehensive, multi-function, microprocessor-based
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)
9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE
WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1930-61 FTA1930 Digital Solid State Starting Electric Fire Pump Controllers Product Description Fire Pump Controllers for Business-Critical Continuity
Limited Service Fire Pump Controllers Features
Must Be Installed Per Applicable Code and Manufacturers Recommendations Limited Service Fire Pump Controllers Features 1-1 FD20 Full Voltage - Limited Service with Plus Microprocessor Power I/O Board Transformers
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
POWER GENERATION. www.mtu-online.com
POWER GENERATION A TOGNUM GROUP BRAND Valid for north america Europe / Middle East / Africa / Latin America MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 / Fax + 49 7541
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
ATC-900 Automatic Transfer Switch Controller
ATC-900 Automatic Transfer Switch Controller center industries. An intelligent control architecture allows the ATC-900 to address virtually any system requirements. Typical applications include utility-to-utility,
Medium Voltage Motor Control Assemblies
Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................
Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance
Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
Specification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
SWITCHGEAR. EGP Switchgear
SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all
Generator Differential Relay Electrical Apparatus
Generator Differential Relay Electrical Apparatus MD3G Rotating Machine Differential Relay 150-3 The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor
PowerCommand Paralleling System Digital MasterControl
PowerCommand Paralleling System Digital MasterControl Description The PowerCommand Digital MasterControl is a systemlevel controller designed to interface directly with Cummins Power Generation PowerCommand
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies. www.stacoenergy.com
Popular Variable Transformers and AC Power Supplies Product Guide AC Voltage Control Devices Guide Guide Your Tailored Power Solutions Provider TM Staco Energy Products Co. has been a leading manufacturer
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
TSC 800 TRANSFER SWITCH CONTROLLER INSTALLATION, OPERATING & SERVICE MANUAL
TSC 800 TRANSFER SWITCH CONTROLLER INSTALLATION, OPERATING & SERVICE MANUAL Software Version 2.2 PM049 REV 11 14/01/23 9087A 198 th Street, Langley, BC Canada V1M 3B1 Telephone (604) 888-0110 Telefax (604)
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps
Integrated Power Systems for Data Centers
Integrated Power Systems for Data Centers A Commitment to Data Centers Caterpillar is committed to providing optimum value to the Data Center industry by leveraging our engineering, manufacturing, distribution,
TOSHIBA G9000 80/100/160/225 kva
CORPORATE OFFICE 13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041 PHONE: (713) 466-0277 (800) 231-1412 FACSIMILE: (713) 896-5226 TOSHIBA G9000 80/100/160/225 kva GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
ELECTRICAL: AUTOMATIC TRANSFER SWITCHES
AUTOMATIC TRANSFER SWITCHES BASIS OF DESIGN This section applies to the design of design and installation of automatic transfer switches. Design Criteria Clearly indicate in the drawings and specifications
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
32VFD Variable Frequency Drives for Centrifugal Chillers
32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
Tmax MCCBs. Molded case circuit breakers. Tmax
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
Sentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
Centro-Matic Automatic Lubrication Systems System Controls
Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the
Everything you need for protection scheme testing
Power System Simulator for Testing Protection Relays and Schemes Everything you need for protection scheme testing The is the only instrument with the high power, flexibility and software to perform full
HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
Low Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY
The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY PowerGate - Cost effective solutions for F 1 Horsepower Rating 001 1-40 HP (208V) 075 1-75 HP (480V) Input Voltage 2V 208-240V 4V 380-480V Disconnect
SENTRON Switching and Protection Devices Air Circuit Breakers
Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
Eaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
Power Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: [email protected] Cleaveland/Price Type TP-C2 Motor Operator
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules
CHIEF EN TERPRISES INC. M a s t e r I n t e r n a t i o n a l D i s t r i b u t o r Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules M AS TER IN
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation
EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility
EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility Catalog 2800CT1001 2014 Class 2800 CONTENTS Description............................................ Page 2 Outdoor
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
Series 427. 1/16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS
Series 427 1/16 DIN Multi-Mode Bar Graph Display Timer PRODUCT HIGHLIGHTS Digital Setting with 0.1% Accuracy Unique LED Bargraph Indicates Time Cycle in 20% Increments 8 Field Selectable Modes of Operation
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
Uninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
AUTOMATIC TRANSFER SWITCHES
AUTOMATIC TRANSFER SITCES RMT ual Operator ith Model Control RMT Russelectric Automatic Transfer Switches - Model RMT 2-, -, and -pole configuration Front accessible wiring Safe manual operator provides
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
