1 Safety instructions. 2 Device components. 3 Function. Leader in Led solutions. Compact presence detector. Operating instructions
|
|
|
- Neil Riley
- 9 years ago
- Views:
Transcription
1 Compact presence detector Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe the instructions may cause damage to the device and result in fire and other hazards. Danger of electric shock. Device is not suitable for disconnection from supply voltage. Danger of electric shock. Always disconnect before carrying out work on the devise or load. At the same time, take into account all circuit breakers that supply dangerous voltage to the device or load. Do not press on the lens. Device can be damaged. The device is not suitable for use as a burglar alarm or other alarm. These instructions are an integral part of the product, and must remain with the end customer. 2 Device components (1) Brightness sensor (2) Sensor window (3) Decor ring (4) Connection box (5) LED (6) Set time, run-on time (7) Set lux, brightness 3 Function Intended use Automatic switching of lighting depending on the heat motion and ambient brightness. Ceiling installation, surface-mounted
2 Product characteristics 2-point light control Run-on time and brightness value settable Test operation for checking the detection area Push-on cover for limiting the detection area Parallel connection of multiple presence detectors possible Manual switch-on and switch-off possible with installation button Automatic operation The presence detector detects heat motions of people, animals and objects. The light is switched on if someone or something enters the monitored detection area and the brightness is below the set level. The light remains switched on as long as there are motions present in the detection area and the brightness is not below the set level. The light is switched off if no more movement is detected in the detection area and the runon time has elapsed. The light is switched off if the brightness exceeds twice the set value for longer than 10 minutes. i The minimum switch-off brightness is 400 lux, even if a lower value is set. Function of presence detectors that are connected in parallel Presence detectors that are connected in parallel operate largely independently of each other. Run-on time and brightness are set separately on each presence detector. A soon as a presence detector switches on, this is detected by the other presence detectors. They switch on when there is motion in their detection area, unless the brightness in their detection area is double the set value. As a general rule, the following applies: the light is switched on when the first presence detector switches on, and is switched off when the last presence detector switches off. Behaviour in case of a mains failure Less than 0.2 seconds: the old switching position is restored after mains return. Longer than 0.2 seconds: a self-test is performed after mains return. This takes approx. 30 seconds. The light is switched on during the self-test; operation via extensions is not possible. 4 Operation Switching on the light An installation button is connected. o Press the installation button. The light is switched on for at least 2 minutes. i If motions are detected, the light remains on after the 2 minutes have elapsed. The run-on time is set to the time specified on the adjuster. i If the time adjuster is set to test,, then the light remains switched on as long as the installation button is pressed. The light remains switched off for approx. 1 second after release. Switching the light off It is possible to switch the automatic function off in a targeted fashion, e.g. in order to darken a room. An installation button is connected. Light is switched on o Press the installation button. The light is switched off for 3 minutes. Each detected motion extends the time by 3 minutes. After the 3 minutes have elapsed the presence detector is in automatic mode again. During these 3 minutes the light can only be switched on using the installation button.
3 i In the case of presence detectors connected in parallel the time in each device elapses independently of each other. The result may be unwanted switching-on of the light, if the time has already elapsed in a presence detector and if it detects motions. Switching of the brightness evaluation The brightness evaluation can be switched off if the brightness is perceived as too dark after the light is switched off. An installation button is connected. The presence detector has switched the light off due to adequate extraneous light, e.g. daylight. o Press the installation button within 3 minutes after switch-off. The light is switched on. The light remains switched on as long as the presence detector detects motions. The brightness is not evaluated. i After the run-on time has elapsed, the presence detector switches off and is in automatic mode once again. 5 Information for electrically skilled persons 5.1 Fitting and electrical connection DANGER! Electrical shock when live parts are touched. Electrical shocks can be fatal. Before carrying out work on the device or load, disengage all the corresponding circuit breakers. Cover up live parts in the working environment. Selecting the installation location The presence detector is installed on the ceiling, and monitors the surface under it (Figure 2). The presence detector has a detection area of 360. Die PIR sensor system operates with 6 detection levels and 80 lenses.
4 The range is approx. 5 m in diameter at table height, e.g. approx. 80 cm. At floor level the range diameter is approx. 8 m(figure 3). These data are applicable for installation on the ceiling at an installation height of 2.5 m. At installation heights greater than 2.5 m the detection area becomes larger, while at the same time the detection density and sensitivity are reduced. i If necessary, the detection area can be limited using the push-on cover (see Limiting the detection area). o Select a vibration-free installation location; vibrations can lead to unwanted switching. o Avoid interference sources in the detection area. Interference sources, e.g. heaters, ventilation, air conditioners, and cooling light bulbs can lead to unwanted switching. Preparations for installation (3) Decor ring (11) Fastening pins (12) Screws o Pull off decor ring (3) (Figure 4). o Loosen screws (12).
5 Installing the connection box (8) Fastening holes (9) Cable entry, surface-mounted (10) Thin points for optional cable entries o For an additional flush-mounted cable entry or surface-mounted cable entry, break out the appropriate thin point (10) (Figure 5). o Align the presence detector so that the brightness sensor is on the side away from the windows. This reduces the effects of scattered light. o Fasten connection both (4) with enclosed anchor/screw set through holes (8) (Figure 5). i Alternatively, the presence detector can also be mounted on a 60 mm appliance box. The screws are not included in the scope of delivery. Connecting the presence detector Max. power cable length 100 m. This takes into account all connecting cables between the presence detector and lamps.
6 o Connect presence detector according to connection diagram (Figure 6). o If multiple miniature circuit breakers supply dangerous voltages to the device or load, couple the miniature circuit breakers or label them with a warning, to ensure release is guaranteed. Connection assignment black, BK, L brown, BR, blue, BU, N grey, GY, 1 PE External conductor Switched external conductor Neutral conductor Installation button connection Earth conductor o Connect optional installation button (13) (Figure 6). This is only necessary if manual operation is also desired. i Lit installation buttons may only be connected if they have an N terminal. o Screw presence detector to connection box (4) with screws (12) and mounting pins (11) (Figure 4). Connecting presence detectors in parallel Several presence detectors can be connected in parallel to expand the detection area. Connect all presence detectors to the same external conductor. Do not connect more than five presence detectors in parallel. Max. power cable length 100 m. This takes into account all connecting cables between the presence detectors and lamps. i The connection in parallel does not increase maximum connected load. o Connect presence detector according to connection diagram (Figure 7). Connection assignment black, BK, L brown, BR, blue, BU, N grey, GY, 1 External conductor Switched external conductor Neutral conductor Installation button connection
7 PE Earth conductor o Connect optional installation button (13) to all presence detectors (Figure 7). This is only necessary if manual operation is also desired. i Lit installation buttons may only be connected if they have an N terminal. o Screw presence detector to connection box (4) with screws (12) and mounting pins (11) (Figure 4). 5.2 Commissioning Testing the detection area The presence detector is mounted and connected properly. o Pull off decor ring (3). o Set lux adjuster to 3 (Figure 1). The presence detector operates independently of the brightness. o Turn time adjuster to test(figure 1). The presence detector switches on for approx. 1 second when there is motion. o Pace off the detection area, paying attention to reliable detection and interference sources. Limit detection area if necessary using the push-on cover. i In the case of presence detectors connected in parallel, check the detection areas one after the other. Turn lux adjuster to 0 on the presence detectors whose detection areas are not being tested (Figure 1). o Attach decor ring (3). Limiting the detection area The push-on cover can be used to limit the detection area, e.g. in order to mask out interference sources.
8 Cover size Complete cover Area I cut out Areas I + II cut out Without cover Detection area on the floor Ø approx 2.2 m Ø approx 4 m Ø approx 6 m Ø approx 8 m All data are applicable for an installation height of 2.5 m o Pull off push-on cover o Using scissors, cut out push-on cover along the marked lines as required. o Push on push-on cover Calibrating the brightness value Brightness calibration is necessary to prevent light oscillations from occurring. A light oscillation occurs when the presence detector switches off again due to the lighting that has been switched on (brightness value exceeded). The brightness calibration is performed in the lighting situation that is required as workplace brightness. The lighting controlled by the presence detector is switched on. Avoid extraneous light, e.g. from daylight and other lighting. Various lamps, e.g. fluorescent lamps, require some time to reach full brightness. Therefore note the run-in phase of the lamp. The LED (5) can be used as an adjustment aid. Meaning of the LED with the load switched off LED off LED on or LED flashes Monitored surface is too dark, load switches on when motion detected. Monitored surface is bright enough, load remains off when motion detected. Meaning of the LED with the load switched on LED off LED on LED flashes Monitored surface is too dark, load remains switched on when motion detected. When no motion is detected, it is switched off after the run-on time elapses. Monitored surface is bright enough due to lighting that is switched on, load remains switched on when motion detected. When no motion is detected, it is switched off after the run-on time elapses. Monitored surface is very bright due to lighting that is switched on or extraneous light, load switches off after approx. 10 minutes, even if the run-on time is set longer or if motion is detected. o Pull off decor ring (3). o Turn time adjuster (7) to 30 min. o Turn lux adjuster to 3. LED (5) is off. i Do not place brightness sensor (1) in shadow, because otherwise correct brightness measurement will not be possible. The measured brightness value consists of the reflected artificial light and daylight, and depends on the reflective characteristics of the surface under the presence detector. o Switch on presence detector via motion in the detection area. o Turn lux adjuster (7) in 2 direction until LED (5) lights up. Presence detector is set to the current brightness.
9 i If lux adjuster is on 0, the presence detector only switches on through operation of an extension. In this case the switch-off brightness is 400 lux. o Attach decor ring (3). Setting the switch-off delay The fewer the motions expected in the monitored area, the longer the run-on time setting should be. This reduces the probability that the presence detector will switch off even though people are present. Use 10 minutes as the default setting value. o Pull off decor ring (3). o Turn time adjuster (6) in the appropriate direction. The presence detector is ready for operation o Attach decor ring (3). 6 Appendix 6.1 Technical data Rated voltage AC 230 / 240 V ~ Mains frequency 50 / 60 Hz Ambient temperature C Protection rating IP 20 Circuit breaker max. 10 A Detection angle 360 Detection area Desk height Ø approx. 5 m Floor Ø approx. 8 m Switch-off delay approx. 10 s min Run-on time, test approx. 1 s Brightness setting approx lx Connected load at 25 C Incandescent lamps 1000 W HV halogen lamps 1000 W Tronic transformers 750 W Inductive transformers 750 VA Fluorescent lamps, uncompensated 500 VA Fluorescent lamps, parallel compensated 400 VA Electronic ballast Type-dependent Switching current at 25 C Ohmic 10 A Switch-on current max. 4 s at 10% switch-on 35 A time Minimum switching current AC 100 ma Contact type μ Connection Single stranded mm² finely stranded with tin-plated conductor ends mm² Number of extension units Non-illuminated installation buttons unlimited Total length of extension unit cable max. 100 m Total length power cable max. 100 m 6.2 Troubleshooting Presence detector switches does not switch on when there is motion, even though the brightness is too low Brightness value setting too low. Turn lux adjuster in 3 direction.
10 lux adjuster is set to 0. Initial detection is switched off. Switch on via extension. Turn lux adjuster in 3 direction (see Calibrating the brightness). Switched off via extension. Switch on via extension. Presence detector switches on without any detectable motion Interference sources in the detection area. Pay attention to interference sources, e.g. heating, ventilation, air conditioners, cooling light bulbs in the detection area. Possibly limit detection area with the push-on cover (see Limiting the detection area). Presence detector does not switch off even when there is a great deal of extraneous light. The brightness value setting is too high. Turn lux adjuster in 2 direction (see Calibrating the brightness value). Presence detector switches off, even though people are present and the brightness is too low Detection problem, the surface to be monitored is not in the detection area, or furniture or pillars are in the way. Use an additional presence detector (see Connecting presence detectors in parallel). Run-on time too short. Motion of persons is not detected. Extend run-on time using time adjuster (see Setting the run-on time). Presence detector switches on and of constantly time adjuster is set to test. Set run-on time using time adjuster (see Setting the run-on time). Presence detector switches off briefly and then on again immediately Brightness drops below the brightness value setting after switch-off. Turn lux adjuster in 3 direction (see Commissioning section) 6.3 Accessories Not combinable with devices from System Warranty The warranty is provided in accordance with statutory requirements via the specialist trade. Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company/electrical specialist trade). They will forward the devices to the Gira Service Center.
11 LED & LED Lerklockan Riddarhyttan Sweden Tel: [email protected] Webb:
Operating instructions IV / 2007
General Operating instructions IV / 2007 Contents General Installation Application and function Application and function... 2 Safety information... 2 Design and dimensions... 3 Wiring diagram... 3 Installation
Operating instructions II / 2004
Operating instructions II / 2004 Light and presence sensor TOUCH DIM LS/PD LI OSRAM GmbH Costumer-Service-Center (CSC) Steinerne Furt 62 86167 Augsburg, Germany www.osram.com www.osram.de Tel. : (+49)
basicdim DGC Compact control module
luxctrol lighting control sstem DGC Compact control module Product description Compact dimensions for luminaire installation For up to 0 DSI or LI ballasts ( per output channel) LI IN input LI/DSI output
Product and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
DALI RC BASIC SO. Control unit Operating instructions
DALI RC BASIC SO Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Function 5 Light control 5 Brightness
EBDSPIR-PRM, EBDSPIR-PRM-IP
Product Guide EBDSPIR-PRM, EBDSPIR-PRM-IP Ceiling PIR presence/absence detector Overview The EBDSPIR-PRM PIR (passive infrared) presence detector provides automatic control of lighting loads with optional
60W PIR BULKHEAD LIGHT SLB88-Black/SLW89-White INSTALLATION & OPERATING INSTRUCTIONS
60W PIR BULKHEAD LIGHT SLB88-Black/SLW89-White INSTALLATION & OPERATING INSTRUCTIONS SLB88 PIR BULKHEAD LIGHT - BLACK WEATHERPROOF LAMP TYPE IP44 60w ES MAXIMUM PIR SWITCHING 500w MAXIMUM TIME ON DETECTION
5W LED Energy Saver PIR Bulkhead
5W LED Energy Saver PIR Bulkhead Model: LED88PIR Black I n s t a l l a t i o n & Ope r a t i n g I n s t r u c t i o n s 1. General information: The unit utilises passive infrared technology to detect
ACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
Operating instructions Diffuse reflection sensor. OJ50xx 701396 / 01 07 / 2004
Operating instructions Diffuse reflection sensor OJ50xx 7096 / 0 07 / 004 Contents Preliminary note. Symbols used Function and features Installation. Installation of the supplied mounting fixture 4 4 Electrical
Installation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Energy savings
Features SMART SWITCH OCCUPANCY SENSOR Installation Manual Maximum Energy savings Sensitive 180º view passive infrared motion detector keeps lights on only when rooms are in use. No ON switch so lights
PRESENCE DETECTOR PD-C360i/24 KNX ECO (EP10425844)
In the Master function, the remote control entries will be acknowledged as follows: acknowledged 3 x with the red LED In the Slave function, each detection is acknowledged 2 x with the green LED. 6 TEST
Busch-Watchdog Presence EIB Type: 6131-74-102-500
Type: 6131-74-102-500 Contents Technical data 2-2 Application programs (List) 2-3 Circuit diagrams 2-3 in combination with Bus coupler FM (6120-102): Switch Value Cyclic Monitoring /3 2-4 Switch Value
MOTION SENSOR PIR LIGHT SWITCH INSTALLATION & OPERATING. Cat No. ZV810 INSTRUCTIONS
MOTION SENSOR PIR LIGHT SWITCH Cat No. ZV810 INSTALLATION & OPERATING INSTRUCTIONS ZV810 Motion Sensor PIR Light Switch Please read the instructions before using the product and retain for future use.
Infrarot-Bewegungsmelder IP44
Infrarot-Bewegungsmelder IP44 infrared motion sensors IP44 ODA (weiß) slim ODA (schwarz) slim 95174 96000 ODA (weiß) ODA (schwarz) 95175 96001 Betriebsanleitung User s Manual User s Manual infrared motion
LOS 2500 SUPER CEILING SENSOR. Installation Manual
LOS 2500 SUPER CEILING SENSOR Installation Manual How Do RAB Occupancy Sensors Work? Selecting A Location: The L0S2500 sensor sees infrared heat changes caused by the motion of people within its detection
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION Caution! UV-radiation of this device is in the range of UV-A (320-400 nm). Direct exposure to eyes shall therefore be avoided. UV protection glasses shall
Operating instructions Optical distance sensor O1D100 O1D103 704991 / 00 08 / 2012
Operating instructions Optical distance sensor UK O1D100 O1D103 704991 / 00 08 / 2012 Contents 1 Preliminary note4 1.1 Symbols used 4 1.2 Warning signs used 4 2 Safety instructions 4 3 Functions and features
Mounting and operating instructions. Surface-mounted hands-free feature home station 1250..
Mounting and operating instructions Surface-mounted hands-free feature home station 1250.. Device description The surface-mounted hands-free feature home station is a prefabricated unit and is part of
How To Use A Power Supply On A Powerline 2.2 (Ai)
KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang
EBDSPIR-DD, EBDSPIR-DD-IP
Product Guide EBDSPIR-DD, EBDSPIR-DD-IP Ceiling PIR presence detector DALI / DSI dimming Overview The EBDSPIR-DD PIR (passive infrared) presence detector provides automatic control of lighting loads with
Installation Instructions
Specifications PW-100-24 v3 Passive Infrared Low Voltage Wall Switch Occupancy Sensor Voltage...18-24VDC, 24VAC or Half-wave rectified AC Current Consumption...20mA Power Supply... WattStopper Power Packs
Emergency lighting units EM powerled
M BASIC 1 W Combined emergency lighting Driver 1 4 W Product description Emergency lighting Driver for manual testing SEV for output voltage < 60 V DC ow-profile casing (21 x 30 mm cross-section) 5-year
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5
T5 TC-L PCA T5 BASIC lp Y II, 1 80 W BASIC T5 Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal,
PIR Motion Detector INSTALLER GUIDE E-806. SF-SA-360-CS-W.qxd 12/04/2005 11:34 Page 1
SF-SA-360-CS-W.qxd 12/04/2005 11:34 Page 1 PIR Motion Detector E-806 INSTALLER GUIDE V2.0-02/05 IQ-SA-360-CS-W IQ Europe Limited Sandbeck Lane, Wetherby LS22 7TW. Visit us at www.iq-europe.co.uk Installation
Electronic Pressure Switch EDS 300
Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5
Operating Instructions Bedienungsanleitung Mode d emploi
Operating Instructions Bedienungsanleitung Mode d emploi DW 400 www.bron-kobold.com Operating instructions DW 400 Before use Please read all the information contained in these operating instructions carefully.
Contactless Encoder RI360P0-QR24M0-INCRX2-H1181
Compact, rugged housing Many mounting possibilities Status displayed via LED Immune to electromagnetic interference 1024 pulses per revolution (default) 360, 512, 1000, 1024, 2048, 2500, 3600, 4096, parametr.
LiteAide OWNER'S MANUAL PREASSEMBLED AUTOMATIC SECURITY FLOODLIGHTS MOTION SENSOR SECURITY LIGHTING SYSTEMS
OWNER'S MANUAL PREASSEMBLED AUTOMATIC SECURITY FLOODLIGHTS MOTION SENSOR SECURITY LIGHTING SYSTEMS LiteAide HE-100B HE-100BW HE-112 HE-112W HE-117 HE-117W HE-117-2B OWNER'S MANUAL FLOOD LAMPS (BULBS) Your
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
Installation and operating instructions: Radio dimmer Type: DALI DM ADVANCED LI
Installation and operating instructions: Radio dimmer Type: DALI DM ADVANCED LI OSRAM GmbH Hellabrunner Str. 1 D-81536 Munich Tel.: +49 (0) 89 6213 0 Fax: +49 (0) 89 6213 2020 Customer Service Center (KSC)
Cross-beam scanning system to detect slim objects. 100 mm 3.937 in
891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC
Application software. Fan coil actuator 2gang RMD. Electrical / Mechanical characteristics : see product information
Application software Fan coil actuator 2gang RMD Electrical / Mechanical characteristics : see product information Order number Product designation Application software ref. TP device RF devices TYF642F
Die-Cast Metal, Motion- Activated Post Light
TM Die-Cast Metal, Motion- Activated Post Light Model: SH-9392AU Installation and Operating Instructions FEATURES Automatically comes on when motion is detected. Automatically turns light off. Photocell
ABB i-bus KNX SA/S Switch Actuators Product Manual
ABB i-bus KNX SA/S Switch Actuators Product Manual Contents Contents Page 1 General... 5 1.1 Using the product manual...5 1.1.1 Structure of the product manual...6 1.1.2 Notes...6 1.2 Product and functional
PIR Motion Detector INSTALLER GUIDE E-700. SF-SA-140 -B.qxd 16/05/2005 11:19 Page 1
SF-SA-140 -B.qxd 16/05/2005 11:19 Page 1 PIR Motion Detector E-700 INSTALLER GUIDE V2.0-02/05 IQ-140-B IQ Europe Limited Sandbeck Lane, Wetherby LS22 7TW. Visit us at www.iq-europe.co.uk Installation helpline
FL ballasts Electronic dimming. PCA T5 ECO lp Y II, 14 80 W ECO T5
EL PCA ECO lp Y II, 1 80 W ECO Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DALI or DSI signal, switchdim
instabus KNX / EIB System System E F G H
Product name: Uninterruptible power supply (USV) 640 ma Design: REG (rail-mounted device) Article-no.: 1079 00 ETS search path: Gira Giersiepen / system components / power supply / power supply 640mA DRA
PIR Motion Detector E-808
SF-SA-180-D PIR HiLo 10A.qxd 16/05/2005 11:17 Page 1 PIR Motion Detector E-808 INSTALLER GUIDE Version 2 : 02/05 IQ-SA-180-D-GR IQ Europe Limited Sandbeck Lane, Wetherby LS22 7TW. Visit us at www.iq-europe.co.uk
ISL-540 TBTS SERIES D EMERGENCY LIGHTING EQUIPMENT
P.O. BOX 11846 TUCSON, AZ 85734 (520) 294-3292 FAX (520) 741-2837 www.iotaengineering.com INSTRUCTION MANUAL IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always
INFRARED QUARTZ WALL HEATER
INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this
15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE
Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050
Extract from the online catalog DEK-REL- 24/1/SEN Order No.: 2964050 Relay terminal block for sensor, with soldered-in miniature relays, contact (AgNi+Au): small to medium loads, 1 N/O contact, input voltage
Operating instructions Diffuse reflection sensor with background suppression O1D101 O1D104 706114 / 00 01 / 2012
Operating instructions Diffuse reflection sensor with background suppression O1D101 O1D104 706114 / 00 01 / 2012 Contents 1 Preliminary note 3 1.1 Symbols used 3 1.2 Warning signs used 3 2 Safety instructions
7 Lighting Technology
7 Lighting Technology Series HS6145 For use in Zone 1 and Zone 2 Comply with requirements of Fire Department standard DIN 14 462 Battery state display Deep discharge protection Open circuit monitor Light
2400W PIR LIGHT C O N T R O L L E R Cat No. SLW2400
2400W PIR LIGHT C O N T R O L L E R Cat No. SLW2400 1 Introduction The SLW2400 utilises passive infrared technology to detect heat radiation of moving human bodies. Upon detection, the attached lighting
2 Wire Electronic Time Delay Switch. 2 Wire Slave Switch. 3 Wire Electronic Time Delay Switch
2 Wire Electronic Time Delay Switch Cat No. DS1 2 Wire Slave Switch Cat No. DSS 3 Wire Electronic Time Delay Switch Cat No. DS2 Installation & Operating Instructions DS1/DSS Instructions for Installation
www.osram.com Guide to Starters Guide to Starters Page 1 of 17
www.osram.com Guide to Starters Guide to Starters Page 1 of 17 Guide to starters 1 Contents 1 Contents... 2 2 Introduction... 4 3 Definitions (important technical parameters of a starter)... 4 3.1 Partial
TYXIA. *2702178_Rev.1* Installation and User Guide. Wireless receiver. TYXIA RF 642-1 channel
Installation and User Guide TYXIA Wireless receiver TYXIA RF 642-1 channel DELTA DORE Bonnemain - 35270 COMBOURG - France E-mail : [email protected] Unit compliant with the requirements of directives:
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.
ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011
Technical Data 2CDC505051D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are
Unit 4: Electricity (Part 2)
Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State
FIRERAY 2000 Installation Guide
FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description
2013 Wireless Video Intercom INSTALLATION GUIDE
2013 Wireless Video Intercom INSTALLATION GUIDE INDEX System configuration and wiring VL-SWD501 System Component.. 4 VL-SWD501EX wiring schematic diagram VL-SWD501EX wiring type and length... 5.... 6 Door
How To Read A Pipe From A Sensor
Liquid Level Sensor Installation on pipes. Sensing by means electrostatic capacity and is not influenced by the color of the pipe or liquid. Available in 8 to mm dia. and to mm dia. models to enable sensing
DALI DIM/CONVERTER CONTROL (DC NV) 1 10V (0-10 V) analog DALI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions
DAI DIM/COVERTER COTRO (DC V) 1 10V (0-10 V) analog DAI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions Dim-and Switch Functions: The DAI Dim/Converter Control DC V is suitable
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
IVIOS LED III. LUM Technical Information
LUM Technical Information Extremely flat high power LED downlights with splashing water protection (IP44). Ideal for substituting traditional CFL and halogen downlights with wide beam angle. Tender text
Operating Instructions. Room temperature controller
Operating Instructions 1. Area of application The room temperature controller is used to regulate the temperature in closed rooms such as flats, schools, function suites, workshops, etc. Safety instructions
ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011
, 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.
Technology. Presence Detectors. Presence Detection. Light Measurement. Configurations
Technology Presence Detectors Presence Detection Light Measurement Configurations Theben AG Hohenbergstrasse 32 72401 Haigerloch Phone +49 (0) 74 74 692-0 Fax +49 (0) 74 74 692-150 [email protected] 1104008602/03.10
IH 17025 E Sigma Island 90
INSTRUCTIONS FOR USE Kitchen extractor hood Type: IH 17025 E Sigma Island 90 Dear Customer!! You are now a user of the newest generation kitchen extractor hood type IH 17025 E Sigma Island 90. This hood
Product Catalogue August 2015. Energy management Switches and controls
Product Catalogue August 2015 Energy management Switches and controls Energy management Switches and controls Introduction Range overview Timers & Outdoor timers & Technical section Cable glands & terminal
Transmitter Actuator 230V wave UP 560. Operation
Transmitter ctuator 230V wave UP 560 5WG3 560-201 Product- and pplication Description Diagram The transmitter actuator 230V wave UP 560 (Diagram ) is a flush-mounted device with radio communication for
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
HID H4 BI-XENON FITTING GUIDE. Carefully read the following notes before starting work.
HID H4 BI-XENON FITTING GUIDE Carefully read the following notes before starting work. WARNING! This HID kit should only be installed by someone competent in vehicle wiring and electrics. Incorrect fitment
PHASED OUT. Digital dimmable ballasts for fluorescent lamps ECO series. PCA TCL ECO, 18 80 W Compact and T5c fluorescent lamps
Product description Noise-free precise control via DSI signal or switchdim CELMA energy class A1 1) Interfaces DSI switchdim Integrated SMART-Interface Functions Optimum filament heating in any dimmer
Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB
, GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well
Installation Guide. DEVIreg 530. Electronic Thermostat. www.devi.com
Installation Guide DEVIreg 530 Electronic Thermostat www.devi.com The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive
Application and Instruction Manual Motion Activated Solar Powered LED Security Light with Camera MODEL: XP-2H38WC
Application and Instruction Manual Motion Activated Solar Powered LED Security Light with Camera MODEL: XP-2H38WC Please do not return this item to the store. If you have any questions, please contact
Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk
1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
60W Security Twinspot. 754HB2/180/60 180 Outdoor Motion Sensor. Installation Instructions. Please leave these instructions at the installation site.
60W Security Twinspot 754HB2/180/60 180 Outdoor Motion Sensor Installation Instructions Please leave these instructions at the installation site. Contents 1.0 Introduction... 3 1.1 Features... 3 1.2 Wireless
PHOENIX CONTACT - 2012-12-14. Features
Electronic monitoring relay for phase sequence, phase failure, and asymmetry monitoring Data sheet 101748_en_03 1 Description PHOEIX COTACT - 2012-12-14 Features Increasingly higher demands are being placed
Operating instructions. RCD flat 4-fold, 6-fold
Operating instructions 1. Safety instructions Electrical equipment must be installed and fitted by qualified electricians only. Observe the current accident prevention regulations. Failure to observe the
Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)
Operating Manual for the Electronic Built-in Interval Timer Micro II (Countdown Timer) Note: This document has been designed for our OEM customers. They can use it as supporting material when creating
Residual current socket 30mA Order No.: 0477..
30mA Order o.: 0477.. 1. Operating description The operating principle of the residual current socket is identical to that of the residual current device. In a fault-free installation, in which no current
PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, 18 80 W Compact and T5c fluorescent lamps
EXCEL oneall series Product description Noise-free precise control via DSI signal, switchdim, corridorfunction or DALI DALI-MEMORY Extended DALI commands CELMA energy class A1 1) Interfaces DALI DSI switchdim
Wespot. SecNurse A NEW GENERATION TECHNICAL AIDS USER S GUIDE
Wespot SecNurse A NEW GENERATION TECHNICAL AIDS USER S GUIDE EN This manual is published by OPTEX, without any warranty. Improvements and changes to this manual necessitated by typographical errors, inaccuracies
ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011
, 2CDG 110 1xx R0011 SA/S 8.16.6.1 2CDC 071 006 S0010 The 16/20 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are especially
Rapide Inline Ceiling Extractor Fan, White Fascia 41800040590. Rapide Inline Ceiling Extractor Fan, Chrome Fascia 41800040580
Any Queries Call : 08000 23 23 23 Rapide Inline Ceiling Extractor Fan, White Fascia 41800040590 Rapide Inline Ceiling Extractor Fan, White Fascia Illuminated 41800040670 Rapide Inline Ceiling Extractor
Fire suppression system for engine compartments USER MANUAL
Fire suppression system for engine compartments USER MANUAL Contractor s machinery/vehicles, tooling machines and special machines Edition 2011-3 Hydro pneumatic activation Mechanical activation Electrical
Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
PRELIMINARY MANUAL STAGE COLOR 48. Preliminary User Guide. Official version will follow soon on: WWW.BRITEQ-LIGHTING.COM TABLE OF CONTENTS
STGE COO 48 Preliminary User Guide Official version will follow soon on: WWW.BITEQ-IGHTIG.COM TBE OF COTETS 1. Safety Instruction 2. Technical Specification 3. How To Set The Unit 4. How To Control The
GB/DAS User Instruction
GB/DAS User Instruction devireg 540/550 Table of contents Introduction 3 Introducing devireg 540/550 4 How to use your deviheat heating system 6 Daily operation 7 Setting the clock & day 10 Timer programming
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
ABB i-bus KNX Fan Coil Controller FC/S 1.1
Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation
6x 54w SuperZoo T5 HIGH FREQUENCY ELECTRONIC CONTROLLER LUMINAIRE
1 SAFETY, INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR: ASZ01, ASZ02, ASZ03, ASZ04 6x 54w SuperZoo T5 HIGH FREQUENCY ELECTRONIC CONTROLLER LUMINAIRE Unit Weight: 8.5 Kg Dimensions: L1440*W400*H80mm Power
13 SERIES. Electronic step relays 10-16 A 13.81 13.91
13 Electronic step relays 10-16 A 13 13.81 - Electronic step relay - Rail mount - 1 Pole 13.91 - Electronic step relay and timing step relay Switch box mount - 1 Pole Fixed time (10 minutes) timing function
WIRELESS ALARM KIT INSTRUCTION MANUAL COMPLETE ALARM SYSTEM FOR HOME OR BUSINESS. Model Number: IT214054
WIRELESS ALARM KIT COMPLETE ALARM SYSTEM FOR HOME OR BUSINESS Model Number: IT214054 INSTRUCTION MANUAL Warranty Details/Support This product is warranted against defects for a period of One year if the
Air Sensor. SAC Ex. Manual ATEX. AQ Elteknik AB
Air Sensor SAC Ex Manual AQ Elteknik AB ATEX Air Sensor SAC Ex ATEX Certified model Manual version 2.0 Oct 2010 AQ Elteknik AB 2 Table of contents 1. Manufacturer information... 4 Manufacture Declaration
Tilt switches N3 / N4... MEMS technology, one or two axis. Use. Options. + long lifetime and highly reliability due to mechanism-free MEMS technology
Tilt switches MEMS technology, one or two axis N3 / N4... + long lifetime and highly reliability due to mechanism-free MEMS technology + combinable output signals + one or two axis measurement + tilt range
Installation Instructions. ThermoCall TC4. Entry/Advanced
Installation Instructions ThermoCall TC4 Entry/Advanced Thermo Call TC4 1 2 # 24990A 965 082 AMP 3 4 # 98393A # 67769A Thermo Call TC4 5 ThermoCall TC4 Entry 1 2 3 4 5 6 7 8 9 10 11 12 sw Please refer
TS1200 Intelligent Lead Free Soldering Station. Operation Manual
TS1200 Intelligent Lead Free Soldering Station Operation Manual Thank you for purchasing an Intelligent Lead Free Soldering Station. It is designed for lead free soldering. Please read this manual before
Mounting and Operating Instructions. TV gateway 2610..
Mounting and Operating Instructions TV gateway 2610.. Table of contents Device description... 3 Connection to a television... 4 Connection to a BK system (cable connection)... 5 Connection to the world
Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an