SIMULATION OF A DATA CENTER COOLING SYSTEM IN AN EMERGENCY SITUATION
|
|
|
- Estella Townsend
- 5 years ago
- Views:
From this document you will learn the answers to the following questions:
What is the main concern of the server room?
What did the computer room air conditioning units do to estimate the time period during which the internal air temperatures will not exceed the limit?
What assumption was used to determine the thermal capacity of already chilled water?
Transcription
1 Simulace budov a techniky prostředí konference IBPSA-CZ Praha, 6. a SIMULATION OF A DATA CENTER COOLING SYSTEM IN AN EMERGENCY SITUATION Vojtěch Zavřel 1, Martin Barták 2, Jan L.M. Hensen 1 1 Eindhoven University of Technology, Building Physics and Services dept., the Netherlands 2 Czech Technical University in Prague, Dept. of Environmental Engineering, Czech Republic [email protected] ABSTRACT The paper deals with keeping server rooms at reasonable air temperature in the case of an electrical power failure in a data center and with building performance simulations used to support emergency power planning. An existing data center was analyzed in detail with respect to the possibilities of emergency cooling. Based on the assumption that the thermal capacity of already chilled water can be used to prolong functionality of the cooling system when the roof chillers are out of operation, a backup power supply was designed for Computer Room Air-Conditioning and even for the cooling liquid circuit pumps (i.e. not for the roof chillers). Special models representing the data center indoor environment and cooling system, including a detailed model of the Computer Room Air Conditioning (CRAC) units, were developed in order to estimate the time period during which the internal air temperatures in the server room will not exceed the limit. The numerical model of the server room and the cooling system was built in the TRNSYS software and calibrated by measured data acquired from a real power outage situation. The results and conclusions obtained from the performed analyses and simulations helped to improve the emergency power plan of the data center. The study also forms the basis for the development of an emergency decision algorithm that will included in the novel supervisory control platform: GENiC 1 Keywords: Data Centre, Cooling System, Emergency situation, Building Energy Simulation, GENIC control platform SIMULACE CHLADICÍHO SYSTÉMU DATACENTRA V HAVARIJNÍM STAVU Článek pojednává o udržení vnitřní teploty vzduchu v prostorách data centra v případě havarijní situace a o použití nástrojů pro simulaci energetického chování budov pro vyhodnocení efektivního využití nouzového zdroje elektrické energie. Byla provedena analýza skutečného data centra zejména v souvislosti s chlazením při havarijním stavu. Na základě předpokladu, že tepelná kapacita vodního chladícího okruhu může být použita k prodloužení funkce chladicího systému v době, kdy je venkovní kompresorová chladicí jednotka mimo provoz, byla záloha elektrické energie navrhnuta jak pro vnitřní chladicí jednotku data centra, tak i pro čerpadla okruhu chladicí kapaliny (ne pro venkovní kompresorovou jednotku). Byl vyvinut speciálně navržený model pro vnitřní prostředí data centra a chladicího systému, včetně detailního modelu výměníku vnitřní chladicí jednotky za účelem odhadu doby, při které vnitřní teplota prostředí data centra nepřekročí kritickou hodnotu. Numerický model data centra a chladicího systému byl vytvořen v programu TRNSYS a kalibrován na základě dat naměřených při skutečné havárii. Výsledky získané v provedených analýzách a simulacích pomohly k lepšímu rozvržení dodávky elektrické energie ze záložního zdroje data centra. Tato studie také slouží jako podklad pro vývoj algoritmu pro automatický zásah v nouzové situaci, která bude součástí nově vyvíjené dohlížecí řídící platformy GENiC 1 Klíčová slova: data centra, Havarijní situace, Simulace energetického chování budov, GENiC řídící platforma INTRODUCTION Usage of Internet became an integral part of our lives. The following numbers illustrate the huge utilization of this service. The number of Internet users exceeded 2 billion people in 2010 and the amount of transferred data was estimated at 667 billion gigabyte for year the 2013, while these numbers are expected to increase rapidly in the near future [1],[2]. Since users expect non-stop access to their applications, there is a high requirement for uninterrupted processing of data in data centers. IT management standards require operators of data centers to have a minimum of % expected availability of their IT infrastructure per year [3]. Any interruption of processing, even in case of maintenance, is very complicated and causes significant financial losses, so backup systems for electricity supply for data centers and its systems are absolutely necessary. However, the capacity of uninterrupted power systems (UPS) is usually limited for technical or economic reasons, and most of the time, energy demand cannot be fully covered in emergency situations. The operator or an advanced fault detection and diagnostics (FDD) control system 1 more information available
2 has to decide very carefully which component should be backed up. This paper investigates the performance of back up plans for the breakdown of data center s cooling system using building energy simulation tools. Individual components of the cooling system during the breakdown were studied in detail with respect to their influence to data center indoor environment. In particular, the influence of the chilled-water circuit thermal capacity was assessed. A complex numerical model was developed in the simulation environment TRNSYS 16 to predict energy flows and air temperatures in the data center environment. The simulation model describes in detail the cooling system including control elements and it also takes the heat accumulation in room constructions into account. Model geometry and parameters of the cooling system were set up based on descriptions from a real data center. Furthermore the model was calibrated by using measured data from a real emergency situation. CASE STUDY DESCRIPTION The case study deals with a server room placed in the ground floor of an administration building. The server room, with floor area 231 m 2 and layout dimension 16x14m, belongs to a category of small data centers. Wall constructions are built from standardized bricks with a thin layer of plaster, while the ceiling and floor consist of concrete. Interior concrete columns and cabling in a raised floor were considered for calculating the efficient thermal capacity of the room. The sever room is equipped with eight rows of racks with hot and cold aisle arrangement without any separation of the data center environment (white space). The maximum internal heat gain from IT devices was estimated at 80 kw. The backup system contains only batteries for short-period electricity outage. Diesel generators are not available. Since the server room is included in a wider complex of utility rooms and an underground garage, the ambient air temperature around the case study server room is very stable at about 18 to 20 C during the whole year. This assumption was confirmed by measurements. The indoor climate of the server room during regular operation is kept in range of 18 to 27 C, with a relative humidity range of 30 to 60% (recommended by ASHRAE TC 9.9 Committee [4]). The limit for the inlet air temperature for IT equipment, as defined by the ASHRAE guideline, is 35 C. When this limit is exceeded, automatic disconnection may occur or in the worst case IT equipment may be damaged. The required indoor climate is ensured by 4 internal CRAC units, which are placed on one side of the room. The supply air is distributed via an under floor air distribution (UFAD) system, so supply air goes through perforated floor tiles to front side of IT devices, where is air inlet. Used hot air is taken under the ceiling from the top of CRAC units. Circulating air is adjusted in a heat exchanger, where heat is removed by cooling water. Then cooling water is transported to an air-cooled chiller on the roof. The design water temperature difference is 7/12 C. Fig. 1 - Scheme of cooling system, inner circuit The cooling system is divided into an inner (fig.1) and outer circuit (fig.2) by an hydraulic balance tank in order to fulfill different pressure requirements of internal CRAC units and external roof chillers. Redundant backup is applied for each component of the cooling system. Fig. 2 - Scheme of Cooling System, Outer Circuit Estimation of the total water volume inside the cooling system was based on technical documentation [5](see below in tab. 1). The potential thermal energy of the filling and a rough estimate of prolonging of operation can be calculated with the following assumptions: Potential energy is calculated for maximum water temperature difference during breakdown, where the low value is the mean water temperature during regular operation at 10 C and the high value is the temperature limit of 35 C considering ideal heat exchange.
3 Water properties are: density 998 kg m -3 and specific heat capacity 4.18 kj kg -1 K -1. Heat dissipation of IT equipment is constant. Internal heat gain 80 kw is used for calculation of potential prolonging of operation. The calometry formula is used to estimate potential energy of cooling system filling. Tab. 1- Initial Estimation of Potential Energy of Cooling System Filling and Prolonging of Operation V (m 3 ) C (kj K -1 ) E pot (kwh) τ pot (hour) Inner C Outer C Total CALIBRATION DATA A real emergency situation in the case study server room happened in August Both pumps of the inner circuit were broken down due to a water leakage to its electronics. IT devices were still processing and the FDD system increased the CRAC airflow to its maximum value in order to ensure intensive air change in the server room. The whole situation was recorded by a monitoring system. Fig.3 shows measured data from 4 sensors placed in the white space of the data center. mentioned below. Name of type is referred to be able to find detailed mathematical description in TRNSYS manuals [6] [7] Fig. 4 Numerical Model in TRNSYS software Fig. 4 illustrates the complexity of the model, where a detail model of CRAC heat exchangers and an individual model for each unit, PI control of water flow of a CRAC unit, humidification, transport delay and physical properties of coolant, and also simplified building model using the multi-zone component (type56) are taken into account. Among other things, all variables can be monitored and exported for post-processing. Fig. 3 Calibration Data Due to inhomogeneous heat dissipation distribution across the server room, the measured temperature field varies with the position in the room. Since the spatial resolution of building energy simulation techniques is limited, the temperature field of the white space is represented only by one temperature node. In further work, the mean value is used for calibration of the numerical model. NUMERICAL MODEL A complex numerical model was developed in software TRNSYS 16 in order to assess transient behavior of the data center during an emergency situation. The user interface of TRNSYS allows connection of individual components (called type) such as model of fan, pump, heat exchanger or controller which are available in a program library. By combining these types, TRNSYS allows the creation of a complex model of the whole system. A brief description of the main part of the model is Fig. 5 - Scheme of Server Room Model Simplified Building Model A simplified 3-zone model of the server room was created in subprogram TRNbuild which is interfaced with TRNSYS via type56. Fig. 5 shows a schematic model of the server room, where the underfloor zone, rack zone and white-space zone are defined. Zones interact with each other as well as with the cooling system and the ambient environment. The mode of heat transfer interaction is indicated by the symbols
4 in the scheme. A rectangular symbol means mainly conductive heat transfer; the fan symbol indicates convective heat transfer. An effective thermal capacity was specified for each zone (grounding symbol). It is worth mentioning that the setting of this parameter has a major influence on the transient behavior of temperature in the zone. Internal heat gain is applied for the rack zone. Detailed Heat Exchanger Model Detailed parameters of a CRAC unit placed in server rooms are investigated in a previous study [7] and there is possibility to use Braun s Effectiveness NTU calculation method (type52) [8]. Tab.2 shows all parameters which are necessary for calculation of the detailed cooling coil model. Tab. 2 Cooling coil parameters Parameter Value Unit Outside tube diameter m Inside tube diameter 0.01 m Tube thermal conductivity 380 W m -1 K -1 Fin thickness 0.1 mm Fin spacing 1.5 mm Number of fins Fin thermal conductivity 200 W m -1 K -1 Center to center distance 11.2 mm Tube spacing 36 mm The Model was calibrated using a report with technical data from the manufacturer. PI controller settings Control of CRAC units is based on constant airflow and variable water flow. This means that a change of water flow rate keeps supply air temperature at the required set points value. A PI controller (type23) is applied in the numerical model. In order to be able to set appropriate gains and integral time constants, initialization of a surrogate model needed to be done. The surrogate model was initialized as a Laplace domain time-invariant model expressed by the following transfer function. 11,8 G ( s) (1) 2550s 1 The transfer function was validated and evaluated based on a step response of supply air temperature with respect to a water flow change from 0 to 100% (valve control signal). A comparison between the step response predicted by TRNSYS and the surrogate model is presented in fig. 6. After initialization of the surrogate model, the surrogate system sensitivity (-) and time constant 2550 (sec) was read, and the method by Fruehauf et al. [9] was used to estimate PI controller parameters such as proportional gain (-) and integral time constant 1250 (sec). Fig. 6- Step Response of Supply Air Temperature Transport Delay and Coolant Properties A numerical model is primarily created for prediction of thermal utilization of energy potential of the coolant. Transport delay has to be taken into account because it is crucial to assess states during the emergency situation. Therefore, a model of the distribution system has to contain many pipe components (type 31) which calculate not only transport delay but also heat transfer losses during transport. Parameters of the distribution model were estimated based on technical documentation [10]. In the initial estimate of potential energy of the filling (tab.1), we assumed that the coolant is pure water. Technical documentation shows that actual coolant is a mixture of water with antifreeze in ratio 3 to 1, so physical properties of coolant are slightly changed. This change is expressed by equation 2 [11] P x A 1 273,15 A2 A3 T 2 273,15 A4 T 273,15 A5 (2) T Where A i are coefficients which define calculated parameter P x. The formula is validated for density, specific heat capacity, and thermal conductivity. ξ is the concentration of the mixture and T is thermodynamic temperature. The changes of physical properties are demonstrated in tab. 3 Tab. 3 Physical properties differences for temperature 10 C Type of Coolant ρ (kg m -3 ) c (kj kg -1 K -1 ) λ (kw m -1 K -1 ) Water Mixture The main parts of the numerical model were briefly described. In addition to these components there are models of fans, pumps, humidifiers or ON/OFF controllers. Its meaning is not so significant. Also, the model of the roof chiller was simplified (type92) because operation of this unit during emergency situation is not considered.
5 RESULTS Fig. 7- Prediction of Course of the Air Temperature during an Emergency Situation The main result of this study is shown in fig. 7. Four scenarios for four different levels of cooling system failure were investigated. For each scenario, two lines for zone air temperatures are shown: a dashed line for the rack zone and a solid line for the white-space zone. Calculation is with consideration of constant heat dissipation from IT devices. Scenario 1 (orange) is the scenario that describes total cooling system failure. In this scenario a significant difference between courses of zone air temperature can be observed. Whereas the white space zone temperature rises slowly, as influenced by the thermal capacity of indoor constructions, the rack zone temperature shows a sharp increase. This step change may be very dangerous and can cause large damage to IT equipment. Scenario 2 (red) is the scenario that describes failure of the roof chiller unit and its distribution system. In this case, the CRAC unit can provide only intensive air change of the white-space without any cooling. This scenario may also be understood as the situation of only backing up CRAC unit fans during an electricity outage. Conditions of scenario 2 were set in such a way that they meet the conditions of a real emergency situation. The results of this scenario are considered comparable with the referenced data. Scenario 3 (light blue) is the scenario that describes failure of the roof chiller unit and outer circuit of a distribution system, or backing up of CRAC units and pumps of the inner circuit during an electricity outage. Finally, scenario 4 (dark blue) is the scenario that describes failure of the roof chiller or backing up of CRAC units and all distribution systems during the electricity outage. Tab. 4- numerical comparison Scenario 2 Scenario 3 Scenario 4 τ p (min) P el (kw) E el (kwh) E coolant (kwh) Numerical results are presented in tab. 5. In order to compare the results in an easy way, the prolonging period of operation τ p was defined as the period from the start of failure, until the time when the whitespace temperature reaches the limit of 35 C. Other indicators are mentioned such as required peak power and electric energy consumption during prolonging period as input information for back up devices and also heat removed from the space to the circulating coolant, which is output from the detailed heat exchanger model. Fig. 8 shows the transient behavior of energy flows through the heat exchanger for scenarios 3 and 4 (blue lines). The assumption of constant internal heat gain (red line) is not very realistic. However, it may be interpreted as the worst case scenario, when the server room utilization is 100% during the whole outage period. On the other hand, a constant energy consumption (green lines) of backed up cooling system is very likely with respect to common practice, in which backed up components of cooling systems tend to be set to full power during emergency situations (e.g. fans of CRAC units due to intensive air change.). The influence of the step control action is most visible in initial course of energy flows through the heat exchanger (blue lines) Fig. 8 Prediction of energy flows.
6 DISCUSSION A numerical model based on a case study and calibrated by using measured data of a real emergency situation proved the significant influence of usage of coolant thermal capacity during emergency situation in data centers. This influence is even greater than our initial expectation. The reason for this difference is probably the additional thermal capacity of constructions which helps to keep temperatures in the recommended range. For a target group of small or medium sized data centers with water based cooling, which are mostly integrated in office buildings with long distance distribution systems, we recommended a back-up distribution system to be used during electricity outage. In addition, we recommend that additional water thermal storage tanks are included in the distribution systems in case the thermal capacity of the distribution system is not enough. For the case study, the prolonging period of operation is around 2 hours, considering backing up of inner circuit with volume of filling of 1.6 m 3. For backing up of the whole distribution system with volume of filling of 5.5 m 3, the emergency operation period can be prolonged by more than 3 hours. This solution provides more time for operators to manage troubleshooting of failure of roof chiller units or launching of emergency electricity generators (if available) in case of long-term electricity outage. In case of short-term electricity outage, the thermal capacity of coolant contained in the distribution system is enough to cool the data center with minor additional requirements of batteries included in the UPS because fans of CRAC unit, which are already taken into account, are major consumers in comparison with consumption of circulation pumps. Unfortunately, detailed data about utilization of IT devices or workload distribution were not available, so heat dissipation had to be estimated by only catalogue values of IT devices and internal heat gain was considered as constant. However, the value of internal heat gain represents the worst case, when the data center is fully utilized during the period of emergency situation and thus the influence of thermal capacity of distribution system might be even more significant. Another limitation of this study is the level of resolution of temperature field calculation in the white-space, which could be higher. Using a methodology with a three-zone model offers only limited information and this issue should be investigated in future work. In general, using building energy simulation is feasible for data center case and provides detailed information about the transient behavior and prediction of operation states of data center and its systems especially. With building energy simulations, many types of analyses can done which are not possible with conventional methods. Of course, the development of numerical models using advanced simulation methods is time consuming, however, this model does not have to be used only for design purposes but also may be included in an advanced model-based control platform. CONCLUSION The modeling of transient behavior of data center and its systems is a multidisciplinary task, where most of a conventional tools are failing. The use of dynamic building energy simulation methods such as TRNSYS seems feasible for this purpose. There already exist many models of HVAC, electrical and control components and by combining these components, the program allows the creation of a complex model. However some limitations were found in modeling of the data center environment. The methodology with a three-zone model offers only limited information. The simulation results prove that backing up of the pumps of distribution systems has a positive influence during emergency situations in data centers. For the target group of small and medium size data centers with long distance water distribution systems, backing up of the distribution system offers alternative short-term energy back up for cooling of the data center with minimal efforts and additional investments. Usage of an additional storage tank added to the distribution system as alternative energy back up is also recommended with assumption that backing up of distribution system is applied The results provide valuable information to data center operators and may also be used as theoretical basis for FDD decision algorithms, such as the supervisory control platform GENiC, which is currently being developed. ACKNOWLEDGEMENT This project was partially funded by the European Commission under the 7 th Framework Programme - Grant Agreement no REFERENCES [1] Internet Systems Consortium, Internet host count history, Retrieved 2012, available online: [2] Cisco System, V roce 2016 proteče internetem 4x více dat než dnes, Retrieved 2012, available online: s/2012/ html [3] Uptime Institute, Uptime Institute Tier Certification, Retrieved 2014, available online: [4] ASHRAE, Thermal guidelines for data processing environments expanded data center classes and usage guidance, American Society for Heating, Refrigeration and Air Conditioning, Atlanta, 2011 [5] The Solar Energy Laboratory, TRNSYS 16 vol.4, manual 2007
7 [6] The Solar Energy Laboratory, TRNSYS 16 vol.5, manual 2007 [7] Šesták P., Chlazení technologického centra v havarijní situaci, Diploma thesis, CTU in Prague 2012 [8] Braun J. E., Methodologies for the Design and Control Chilled Water Systems, University of Wisconsin- Madison, 1988 [9] Klán. P., Moderní metody nastavení PID regulátoru, AUTOMA, vol.9, pp.1-4, 2000 [10] Sofim spol s.r.o, Rekonstrukce dopravy chladu technical documentation, 2008 [11] Conde M., Thermo Physical Properties of Brines, Zurich, 2011 [12] Zavřel V. Model pro simulaci havárie chlazení, Diploma thesis, CTU in Prague 2013 [13] Joshi, Y. and Kumar, P. et al. Energy Efficient Thermal Management of Data Centers. Springer, 2012, p ISBN: [14] Barták M., Šourek B., Building and HVAC system simulation, semester course, CTU in Prague, 2013.
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Thermal Mass Availability for Cooling Data Centers during Power Shutdown
2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS
Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS Michaël Kummert 1, William Dempster 1, and Ken McLean
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
News in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Rate of Heating Analysis of Data Centers during Power Shutdown
2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction,
Energy savings in commercial refrigeration. Low pressure control
Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers
Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data
AIR-SITE GROUP. White Paper. Green Equipment Room Practices
AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Reducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Field test of a novel combined solar thermal and heat pump system with an ice store
Field test of a novel combined solar thermal and system with an ice store Anja Loose Institute for Thermodynamics and Thermal Engineering (ITW), Research and Testing Centre for Thermal Solar Systems (TZS),
Analysis of the UNH Data Center Using CFD Modeling
Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *
Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting
DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple
CHAPTER SEVEN L. Glicksman and J. Lin (eds), Sustainable Urban Housing in China, 116-123 2006 Springer. Printed in the Netherlands. DESIGN OF NATURAL VENTILATION WITH CFD Qingyan Chen INTRODUCTION As the
OPTIMIZATION OF DATA CENTER CHILLED WATER COOLING SYSTEM ACCORDING TO ANNUAL POWER CONSUMPTION CRITERION
OPTIMIZATION OF DATA CENTER CHILLED WATER COOLING SYSTEM ACCORDING TO ANNUAL POWER CONSUMPTION CRITERION Piotr Kowalski 1, Mieczysław Porowski 2 1 Poznan University of Technology Piotrowo 5 60-695 Poznan,
The Benefits of Supply Air Temperature Control in the Data Centre
Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
Absolute and relative humidity Precise and comfort air-conditioning
Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No
CoolTeg Plus Chilled Water (CW) version: AC-TCW
version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Effect of Rack Server Population on Temperatures in Data Centers
Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,
Data Center Temperature Rise During a Cooling System Outage
Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 1 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly
CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
Center Thermal Management Can Live Together
Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
White Paper Rack climate control in data centres
White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014)
EPJ Web of Conferences 67, 02070 (2014) DOI: 10.1051/ epjconf/20146702070 C Owned by the authors, published by EDP Sciences, 2014 Flow in data racks Lukáš Manoch 1,a, Jan Matěcha 1,b, Jan Novotný 1,c,JiříNožička
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Guide to Minimizing Compressor-based Cooling in Data Centers
Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
imagine SOLAR AIR CONDITIONING MADE EASY
imagine SOLAR AIR CONDITIONING MADE EASY WHY SOLAR COOLING? Imagine...being able to fit a solar air conditioning system to your building that would result in dramatic reductions in electricity consumption
Data Center Temperature Rise During a Cooling System Outage
Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 0 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
HVAC: Cool Thermal Storage
HVAC: Cool Thermal Storage Thermal storage systems offer building owners the potential for substantial operating cost savings by using offpeak electricity to produce chilled water or ice for use in cooling
Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
Article Mechanical Engineering July 2011 Vol.56 No.20: 2185 2190 doi: 10.1007/s11434-011-4500-5 SPECIAL TOPICS: Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
Software Development for Cooling Load Estimation by CLTD Method
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
The CEETHERM Data Center Laboratory
The CEETHERM Data Center Laboratory A Platform for Transformative Research on Green Data Centers Yogendra Joshi and Pramod Kumar G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Application of Building Energy Simulation to Air-conditioning Design
Hui, S. C. M. and K. P. Cheung, 1998. Application of building energy simulation to air-conditioning design, In Proc. of the Mainland-Hong Kong HVAC Seminar '98, 23-25 March 1998, Beijing, pp. 12-20. (in
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
Building HVAC Load Profiling Using EnergyPlus
Building HVAC Load Profiling Using EnergyPlus Dong Wang School of EEE Nanyang Technological University Singapore Email: [email protected] Abhisek Ukil, Senior Member, IEEE School of EEE Nanyang Technological
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling
White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that
Performance Estimation of Water Thermal Energy Storage Tank by Using Simplified Simulation
Performance Estimation of Water Thermal Energy Storage Tank by Using Simplified Simulation M. Kubota, K. Sagara, T. Yamanaka, H. Kotani Division of Global Architecture, Graduate School of Engineering,
CRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
EHDC. Cooling system for Data Center and server cabinets.
EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY
EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY Rajat Ghosh, Pramod Kumar Vikneshan Sundaralingam Yogendra Joshi [email protected] G.W. Woodruff School
Using thermal mapping at the data centre
Technical Using thermal mapping at the data centre by Gregory Stockton, CompuScanIR.com Cooling the servers in data centres efficiently is critical to increasing IT reliability, maintaining high performance,
Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
Natural geothermal energy.
ROTEX ground source heat pump Natural geothermal energy. ROTEX HPU ground the ground source heat pump that heats with free geothermal energy. Compact, environmentally responsible and uniquely efficient.
Office of the Government Chief Information Officer. Green Data Centre Practices
Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain
Application of CFD modelling to the Design of Modern Data Centres
Application of CFD modelling to the Design of Modern Data Centres White Paper March 2012 By Sam Wicks BEng CFD Applications Engineer Sudlows March 14, 2012 Application of CFD modelling to the Design of
Energy Performance Optimization of Server Room HVAC System
International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department
COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION
COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION 1/16 Contents: 1. Introduction: the increasing importance of energy efficiency 1.1 Power consumers in the data
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
Data Center Environments
Data Center Environments ASHRAE s Evolving Thermal Guidelines By Robin A. Steinbrecher, Member ASHRAE; and Roger Schmidt, Ph.D., Member ASHRAE Over the last decade, data centers housing large numbers of
Rittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
