THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS
|
|
|
- Beryl Gardner
- 10 years ago
- Views:
Transcription
1 Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS Michaël Kummert 1, William Dempster 1, and Ken McLean 2 1 Mechanical Engineering University of Strathclyde, Glasgow, Scotland 2 WSP UK Ltd, Glasgow ABSTRACT This paper describes the modelling and analysis of a 5 MW chilled water plant used for the cooling of a recently constructed data centre in the UK. The model was developed using the TRNSYS software with the aim of studying the impact of perturbations such as chiller failure on the water and air temperatures in the system. The model includes the chillers, hydraulic network (piping, valves and pumps) and individual water-to-air heat exchange units. The coupling between the data centre air temperature levels and the cooling plant has enabled a full assessment of the cooling system design in response to system perturbations to be carried out. The paper examines a number of scenarios involving the failure of the chillers and shows how the inherent thermal inertia of the system plus additional inertia achieved through buffer vessels allowed a suitable design to be achieved. The effective sizing of these vessels could not have been achieved with confidence without the use of transient analysis of the complex system dynamics. INTRODUCTION The growth of data centre demand in the last years has led to an increase in their size and reliability requirements with a significant effort given to ensure operational effectiveness. For example, the largest data centre recently commissioned being the Microsoft Chicago data centre requiring nearly 200 MW of power, 500,000 ft² and costing $500 million (Reuters). Data centres housing the IT infrastructure of large organisations constitute a considerable technical challenge to ensure even the minimum requirements of 96.67% reliability for the lowest Tier 1 operational availability. For mission critical IT systems, the Tier 4 criteria require significant redundancy and therefore cost to ensure the % reliability (Turner et.al). One of the major requirements of continuous operation is the cooling of the IT systems. The IT infrastructure accounts for some 50% of the data centre power needs; the remaining being dominated by the electrical power system and the cooling equipment. Mission-critical data centres such as the one considered in this study require tight environmental control that meet the "class 1" requirements defined by ASHRAE (ASHRAE, 2004). Specifying cooling systems to maintain suitable temperature levels and dissipate the heat generated can be carried out using industry standard design methods. However, accounting for perturbations in cooling due to failure of plant and restart of backup systems requires for faster thermal transients to be addressed than would normally be encountered in building system analysis. The most common approach to the design of large data centres is to cool the IT systems with fan driven air cooling, the heat from which is transferred via air-water heat exchanger units to chilled water circulating in a central ring main. Water chillers are then used to extract the heat and transfer this to the atmosphere. To ensure reliable operation and address failure in the major cooling components redundancy is built into the system (see e.g. Hasan, 2009). The issue considered in this paper are the consequences of a failure in the chiller systems and the inherent time delays that result when starting a chiller or when changing load. The consequences are that the cooling system may not meet the cooling requirements temporarily and thus rely on the thermal inertia of the chilled water existing in the pipework to keep the IT system within their operation limits. The transient response of the system is partly determined by the hydraulic circuit transit times and since this is of the order of minutes it imposes a level of analysis that is not normally required in building system simulation. Furthermore, to address the impact on the IT cooling, the thermal coupling between the server data rooms, the chilled water circuit and the chillers all need to be accounted for. This results in a model that encompasses the whole cooling system with the smallest scale being that of the individual heat exchanger unit. This paper examines these issues by presenting a study carried out during the design phase of a tier 3 data centre designed by WSP UK Ltd on behalf of Norwich Union (now Aviva). Of particular interest was the effect of the loss of
2 cooling caused by chiller failure and the resulting temperature transient that propagated to the IT halls. This paper describes the model used to analyse the cooling system and the failure scenarios that were considered. The transient response of system temperatures (chilled water and data room air temperature) are presented for two of the chiller failure scenarios. The effect of including added thermal inertia into the system by including buffer vessels is also examined DATA CENTRE AND MODELLING Data Centre Cooling System The cooling system for the data centre is shown in Figure 1. The heat load comes primarily from the IT requirements with a small percentage from office air conditioning. The IT load is distributed between 46 Room Air Conditioning Units (RACUs), and 24 water-based cooling units referred to as Heat Exchanger Pumping Units (HEPUs), which are supplied by cooling water from a chilled water pipework system. The pipework consists of a 300 mm diameter supply ring main and a return ring main adding to a total length of over 1500 m of pipework. Each ring main has two inlet and two exit connections which delivers and removes water from each half of the rings providing a flow split which allows both clockwise and anti-clockwise circulation of the cooling flow. The flow in the supply ring is continuously extracted for RACU use from the supply pipework, which results in a natural depletion of the flow by, see Figure 1. The IT room cooling is achieved with an air circulation system as shown in Figure 2. Cold air is supplied via floor vents and hot air extracted via ceiling vents with the RACU s extracting the heat to the chilled water using air-water heat exchangers. Two optional buffer tanks each consisting of approximately 30% of the system mass and used to increase the thermal inertia of the system are also shown in Figure 1. Their effect on the system response will be discussed later. The circuit flow is provided by up to 6 parallel primary pumps and the heat load is removed using up to 6 parallel chillers.. Pipework: 288 pipes, 70 diverters, 70 tee-pieces (All RACU and HEPU units are modelled, just a few are identified) Buffer vessels Office load Chillers Pumps Figure 1 Data Centre Cooling System
3 RACU Figure 2 IT Hall cooling system The total design heat load for the system is 4.6 MW with a control system that requires to maintain the IT room air conditions below 24 C for chilled water supplied at 9 C. The redundancy that is required of this Tier 3 data centre consists primarily of additional chiller capacity and over specification of the heat transfer capacity of the RACU and HEPU units. During normal operation only 4 chillers are required with 2 being redundant. The RACU s are operated at approximately 85% of their capacity with 4 of the 6 pumps in normal operation. These features provide a total cooling capacity of 7.8 MW, which is 40% above the normal operating design loads. However, these requirements are not in themselves sufficient to ensure that the IT equipment will remain cooled under transient conditions resulting from plant failure. In this work the effect of failure in up to two chillers was examined; i.e. the required use of all of the redundant plant. Since the chillers considered for the Data Centre take up to 8 minutes to reach full capacity and the effect of a loss of cooling would have propagated to the RACU s within this time a number of scenarios were conceived to minimise the air temperature upsets in the IT halls of the data centre. This involved minimising the chiller start up time by running at part load more than the four chillers normally required for cooling. The time for a chiller to increase from a part load of 60% to a full load could be as short as 15% of the time to start up from cold. A number of different scenarios were examined but only two extremes discussed here to show the main effects, as follows (i) (ii) Chilled water return line Chilled water supply line 4 chillers running at 90% load, 2 awaiting start up ("N" configuration) 6 chillers running at 60% load ("N+2") Different buffer vessel sizes are also compared in the results presented below. Plant Modelling Approach The model has been developed and implemented in TRNSYS (Klein et al., 2006), a component-based integrated energy performance modelling tool, using a combination of existing component models and bespoke components. The model includes a simplified but complete description of the hydraulics in the chilled water system and the interaction with the air-side cooling systems in the IT hall. This enables assessing the impact of chilled water temperature disturbances on the overall IT environment. The hydraulic network shown in Figure 1 is modelled faithfully using standard TRNSYS components for pumps, diverters and teepieces. Each RACU is modelled separately with an individual TRNSYS component. HEPU s only handle 17% of the load and since their specification was unknown these have been modelled as RACU s. However, it has been assumed that the thermal inertia in the heat exchangers is low compared to the thermal mass of the rest of the system which allows standard heat exchanger theory to be applied. The standard pipe component in TRNSYS accounts for travel time and for the thermal mass of the fluid in the pipe but not for the thermal mass of the pipe wall and insulation. A more detailed pipe model was obtained (TESS, 2007) in order to take full account of the thermal inertia provided by the mass of steel pipework. This thermal mass has a notable impact on the dynamic system response. Room-side heat transfer is modelled by splitting the IT hall into different "zones". Each zone represents the notional part of the hall served by each RACU unit. The Zone air volume and floor area are proportional to the share of the total roomside cooling load provided by the corresponding RACU. A schematic of a zone and its associated RACU is represented in Figure 3. No interaction is assumed between the different zones. T out, ChW Q coil T in, ChW Q fan T supply T Return Air = T Room Heat gains (IT + others) T Room (lumped capacitance) T plenum (lumped capacitance) Concrete floor (Finite Element) Figure 3 IT hall air heat transfer model
4 Two "air nodes" (air volumes assumed to be at a uniform temperature) are modelled for each zone: the IT hall and the ventilation plenum under the raised floor. Thermal mass is added to the nodes to account for IT equipment and other structures, while the heavy concrete floor is modelled by a finite element approach. This simple model was implemented in a bespoke TRNSYS component. The calculated return air temperature only provides an approximate indication of the air temperature surrounding the IT equipment (a full CFD model would otherwise be required) but the model is accurate enough to represent the room response to changes in chilled water supply temperature and its impact on the chilled water flowrate and exhaust temperature. The distribution of the heat gains are presented in Table 1 and it can be seen that the majority of the heating is from the IT Hall, i.e. 70% of the total load with the remainder from the cooling equipment, office loads or gains from the surrounding atmosphere via pipe walls. Description Cooling load IT cooling load 3375 kw Other room loads 215 kw RACUs fan gains 390 kw HEPUs fan and pump gains 375 kw Office air conditioning 200 kw Piping, pumps 45 kw Total cooling load 4600 kw Table 1 Data Centre heat gains The IT room cooling loads are distributed evenly between the RACU s. The design operating conditions for these heat loads are to maintain the IT data room below a maximum temperature of 24 C. As mentioned above the RACUs are operating well below their rated capacity, which results in a flowrate equal to 50 % of the rated value and a chilled water return temperature of 19.4 C (supply temperature = 9 C). Control dynamics The plant cooling systems have a number of dynamic constraints that can have an impact on the response of the system. The most significant is the start up of the standby chillers or if running the change in load response. This is shown in Figure 4, which indicates that the chiller produces no cooling for the initial two minutes after starting and then ramps to full load over a period of 5 minutes. It is the impact of this period of reduced cooling that is studied in this paper. Chiller capacity [% of full load] Figure 4 Chiller load-time response The flowrate to the chillers is controlled by butterfly valves that have a 20-second response time for a fully open to a fully shut condition or vice versa. This relative short time period can have a significant effect on the initial transient due to the nonlinear flow-valve area characteristic, which is shown on Figure 5. This characteristic indicates a fast opening but a slow closure, which means that during the initial part of a transient all 6 chillers will be supplied with a water flow. However, only 2 chillers may be operating in a cooling mode immediately after a failure thus only cooling one third of the flow. The consequences on the cooling water temperature will be seen shortly. % of full flow at cst pressure drop 0% 90% 80% 70% 60% 50% 40% 30% 20% % 0% 0% % 20% 30% 40% 50% 60% 70% 80% 90% 0% % of full valve stem travel Figure 5 Chiller Control Valve Flow- Area Curve There are further control issues that have been modelled but have a lesser effect. When a failure is detected, the BMS (Building Management System) resets the chilled water setpoint to 6 C in order to utilise all the available chiller capacity. The flowrate in each RACU is controlled by a 2-way valve while secondary pumps are controlled to maintain a constant pressure difference across selected RACUs. The 2-way valves are controlled by local controllers (PID, Proportional Integral Derivative) in order to maintain a constant return air temperature at 24 C. The response of these PID controllers has an impact on the overall transient system response and different assumptions were compared. The "average" assumption was kept for the results presented in this paper
5 The behaviour of system components (e.g. curves presented in Fig. 4 and 5) was derived from information available from the manufacturer. In the context of this project, it was not possible to compare them to actual performance data measured by the Building Energy Management System. CALCULATION RESULTS System Response to Scenario (i) The worst-case scenario is when 4 chillers are operating, two fail and the redundant chillers start up from cold. The system response to this cooling failure is taken as the reference case and used to show the main issues that arise when a chiller failure occurs. Figure 7 shows the chiller response with the total cooling being substantially reduced at time zero due to the failure of chillers 3 and 4. Chillers 1 and 2 see a reduced flowrate for about 20 seconds because all the butterfly valves open at the same time. After that, they start to ramp-up to their full capacity, responding to the "failure mode" chilled water setpoint of 6 C instead of 9 C. Chillers 1 and 2 reach their full capacity after less than one minute. During this time chillers 5 and 6 are still not producing cold. They only start to ramp-up after 3 minutes and they reach their full capacity after 8 minutes. Cooling power [kw] Chiller 1 Chiller 2 Chiller 5 Chiller 6 Chiller 3 Chiller 4 Figure 7 Chiller response during failure of Chillers 3/4 and start of chiller 5/6 The reduction in cooling along with delayed opening and closing of the chiller control valves (Figure 5) produces an increase of 7 C in the overall chilled water temperature as can be seen in Figure 8. The temperature remains warmer until the cooling capacity of the chillers recovers. This surge of hotter water propagates through the cooling system as can be seen in Figure 9 where the cooling water is identified at different locations through the circuit, (refer to figure 1 for locations). Chiller outlet Temp [ C] All chillers Chillers 1-2 Chillers 3-4 Chiller 5-6 Figure 8 Chiller water Outlet temperature This temperature change in the cooling water leads to a reduction of over 40% in the water-air temperature difference across the HEPU and RACU s and if left unchecked would lead to substantial increases in the air temperatures of the data room. There are two features of the system which prevent this. Firstly, the rise in water temperature is partially reduced by heat transfer to the circuit pipework and can be seen in the reduction of the peak temperature as the hot water surge travels around the circuit, Figure 9. T Ch W [ C] Chillers outlet After buffer Inlet Inlet Inlet Inlet Figure 9 Chilled water supply temperature at different locations throughout circuit. Secondly, the RACU and HEPU inlet valves are opened in response to an increase in air temperature resulting in an increase in flowrate, which is shown in Figure. In that figure, flowrate is expressed in % of the rated value, and as explained above the flowrate in normal operating conditions is around 50% of that value because of RACUs oversizing. Ch W Flow[% rated] Chillers buffer outlet Figure Chilled water flow at different locations Thus, the effect of system thermal inertia combined with a control feature limits the temperature excursion and improves the heat transfer limiting the rise in IT hall air temperature to less than 1 C at the first RACU, as shown in Figure
6 IT room temperature [ C] Figure 11 Room air (return) temperature System Response to Scenario (ii) The system response to chiller failure with 6 chillers running at part load was examined in Scenario (ii). Again two chillers are assumed to fail but since the remaining chillers are already running the time to increase from part load to full load is shorter than starting from cold and results in a much lesser transient. Figure 12 and 13 shows the overall cooling and the resulting air temperature increase. Figure 12 shows the impact on cooling is much less with only a 35% drop in capacity (see Figure 7) and the recovery time is shorter. Cooling power [kw] Chiller 1 Chiller 2 Chiller 5 Chiller 6 Chiller 3 Chiller 4 Figure 12 Chiller capacity during Scenario (ii) The effect on air temperature is also significantly reduced, as shown on Figure 13, which uses the same scale as Figure 11. IT room temperature [ C] Figure 13 Room air temperatures, scenario (ii) Effect of Buffer vessels To improve the operating safety margin the thermal inertia of the system can be increased by the addition of buffer vessels. Due to the mixing of the inlet flow and the contents, the buffer vessel can only provide a reduction in the temperature excursion rather than negate it completely. Also since the vessel is of finite size the reduction can only be provided for a limited period. Thus the effect of adding a vessel and the sizing of the vessel was investigated. Vessels were added in both main inlet pipes downstream of the chillers, see Figure 1. Two buffer vessel sizes were investigated: 2 x 6 m 3 and 2 x 12 m 3 and both conditions were run with the scenario (i) case, ie the worst-case chiller failure condition. Figure 14 shows the effect of the buffer vessels on the chilled water temperature. Even without buffer vessels, the thermal mass in the (long) piping between the chiller plant room and the IT rooms introduces some damping, bringing the peak from 14.9 C to 14.1 C. The 2 x 6 m 3 vessel case shows a further reduction of the peak by 1.5 C and the 2 x 12 m 3 vessel case a reduction of 0.9 C. The initial temperature rise (9 to 14.1) is almost reduced by 50% in the case of the large vessel.. T Ch W [ C] Chillers outlet Inlet, no buffer Inlet, 2x6m³ Inlet, 2x12m³ Figure 14 Chilled water temperature for scenario (i), different buffer cases Figure 15 shows the effect of the buffers on the air temperature and shows a small reduction in the temperature increase by a about 0.5 C, the air temperature largely being maintained by an increase in the liquid flowrate for each RACU or HEPU IT room temoerature [ C] IT room T, no buffer IT room T, 2x6m³ IT room T, 2x12m³ Figure 15 IT room temperature for scenario (i), different buffer cases DISCUSSION The results presented in this paper were obtained using a detailed transient model of a data centre chilled water cooling plant. The most significant simplifying assumption was made in modelling the IT rooms, which was split into "slices" served by each individual RACU. The lack of interaction between RACUs was retained to provide a worstcase estimate of the air temperature disturbances, given that individual RACUs will "see" chilled water supply temperature disturbances at different points in time. On the other hand, the simple model
7 described in Figure 3 only gives a rough estimate of the conditions within the IT racks. A full CFD simulation would be required to investigate this. The disturbances in chilled water supply temperature and in room air temperature may seem very small but they should be related to the strict environmental conditions imposed in this class 1 data centre. Recent work by ASHRAE has resulted in relaxed environmental criteria for data centres (ASHRAE, 2008), and servers performing well in extreme environments have been reported in the news (Miller 2008). But tier 3 and tier 4 data centres built today in the UK still have to meet very stringent criteria for environmental conditions and for the reliability and redundancy of cooling systems. This is mainly because the cost of service interruption is orders of magnitude higher than the cost of a few MW chilling capacity or the increase in energy cost that might result from very strict operating set points. The role of the detailed model described in this paper was to quantify the disturbances in the chilled water system temperatures and to design a system that would ensure that these disturbances would remain within the margins defined by the client. The model demonstrated that the system can be maintained within very tight operating air temperature margins through running redundant chillers (i.e. operating N+2 chillers) or adding relatively modest buffer vessels, as was verified for a failure scenario involving the simultaneous loss of two chillers. In addition, the model provided valuable insight on the system behaviour in different operating conditions, e.g. by highlighting the very low chilled water velocities in the system resulting from a fully redundant distribution loop and highly part-loaded RACUs. The model is also useful to assess different scenarios such as running the RACUs at reduced fan speed or assessing the impact of controlling the supply air temperature rather than the return air temperature. CONCLUSION The response of a large data centre cooling system to failure in the chiller units is primarily dictated by thermal inertia of the system, the response time of the valve components and control strategies for the RACUs and HEPUs. The complex interaction that results requires a system modelling approach to identify the viability of the system to address operational upsets and to quantify the extent on the most important parameters. A detailed numerical model was developed in TRNSYS, using components taking into account the dynamic behaviour of all system components at the scale of one minute or less. The calculations carried out proved that when the system encountered sizable fluctuations in cooling water temperature that the designed system could maintain air temperatures in the IT hall to almost near normal operating levels. It is also beneficial that this could be achieved by several of the operating scenarios studied, whether by variations in chiller operation or by the increase in thermal inertia by the addition of buffer vessels. REFERENCES ASHRAE Thermal Guidelines for Data Processing Environments. American Society of Heating, Refrigerating, and Air-Conditioning Engineers. Atlanta, GA, USA ASHRAE, ASHRAE Environmental Guidelines for Datacom Equipment - Expanding the Recommended Environmental Envelope. American Society of Heating, Refrigerating, and Air-Conditioning Engineers. Atlanta, GA, USA Hasan, Z., Redundancy for Data Centers ASHRAE Journal, 51(2), pp Klein, S. A. et al., TRNSYS 16.1 A TRaNsient SYstem Simulation program, User manual. University of Wisconsin-Madison, SolarEnergyLaboratory Miller, R., New from Microsoft: Data Centers In Tents. Data Center Knowledge website, consulted in February Reuters,2007. Microsoft invests $500 mln in Illinois data center. Reuters website, AndPR/idUSN Consulted in February TESS, TRNSYS Type 604, multi-node pipe model. Personal communication. Thermal Energy Systems Specialists, Madison, WI. Turner, W.P., Seader, J.H. Brill, K.G. Industry Standard Tier Classifications Define Site Infrastructure Performance, white Paper, The Uptime Institute,
Thermal Mass Availability for Cooling Data Centers during Power Shutdown
2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,
Data Center Temperature Rise During a Cooling System Outage
Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 0 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly
Data Center Temperature Rise During a Cooling System Outage
Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 1 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly
IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling
White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
The Benefits of Supply Air Temperature Control in the Data Centre
Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have
Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
Rate of Heating Analysis of Data Centers during Power Shutdown
2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction,
Reducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
Thermocline Management of Stratified Tanks for Heat Storage
Thermocline Management of Stratified Tanks for Heat Storage M.R.W. Walmsley, M. J. Atkins, J. Riley Energy Research Group, Department of Engineering, University of Waikato Hamilton, NZ Stratified tanks
Application of CFD modelling to the Design of Modern Data Centres
Application of CFD modelling to the Design of Modern Data Centres White Paper March 2012 By Sam Wicks BEng CFD Applications Engineer Sudlows March 14, 2012 Application of CFD modelling to the Design of
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Investigations of a Long-Distance 1000 MW Heat Transport System with APROS Simulation Software
th International Conference on Structural Mechanics in Reactor Technology (SMiRT ) Espoo, Finland, August 9-4, 9 SMiRT -Division 3, Paper 56 Investigations of a Long-Distance MW Heat Transport System with
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
Application of Building Energy Simulation to Air-conditioning Design
Hui, S. C. M. and K. P. Cheung, 1998. Application of building energy simulation to air-conditioning design, In Proc. of the Mainland-Hong Kong HVAC Seminar '98, 23-25 March 1998, Beijing, pp. 12-20. (in
Condensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
Water cooled chiller plant (cp/vs)
Data Center Water cooled chiller plant (cp/vs) Design Envelope File No: 9.573 Date: december 16, 2014 Supersedes: 9.573 Date: november 14, 2014 design envelope s performance improvements are among the
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
GREEN DATA CENTER DESIGN
Jeffrey Menig Global Facilities Facility Engineering The application of multiple available technologies resulting in improved energy optimization without significantly increasing capital investment. A
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory
Rules for Classification and Construction Ship Technology
I Rules for Classification and Construction Ship Technology 1 Seagoing Ships 19 Guidelines for the Carriage of Refrigerated Containers on Board Ships Edition 2003 The following Guidelines come into force
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
COOKING THE ROOF CFD BEYOND THE WHITE SPACE
COOKING THE ROOF CFD BEYOND THE WHITE SPACE Alex Nock 20 November 2013 CONTENTS 1. Introduction» Introduction to RED» Modeling in Data Centres 1. What is CFD» How it works» CFD in Data Centres 3. Cooking
Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates
Chilled Water System Commissioning: Variable Primary Flow John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. History of chilled water system configurations
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
C. starting positive displacement pumps with the discharge valve closed.
KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers
HEAT RECOVERY FROM CHILLED WATER SYSTEMS Applications for Heat Reclaim Chillers April 2008 TABLE OF CONTENTS INTRODUCTION... 3 WASTE HEAT SOURCES... 3,4 Capturing Sufficient Heat for Useful Purposes...
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Continuous flow direct water heating for potable hot water
Continuous flow direct water heating for potable hot water An independently produced White Paper for Rinnai UK 2013 www.rinnaiuk.com In the 35 years since direct hot water systems entered the UK commercial
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
presents Hydraulic Separation Beyond Primary / Secondary Piping
presents Hydraulic Separation Beyond Primary / Secondary Piping This Webinar is exclusively sponsored and the property of Caleffi Hydronic Solutions. All rights reserved. October 2007 Modern compact boilers
Analysis of the UNH Data Center Using CFD Modeling
Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,
MODELLING COUPLED HEAT AND AIR FLOW: PING-PONG VS ONIONS
MODELLING COUPLED HEAT AND AIR FLOW: PING-PONG VS ONIONS Jan Hensen University of Strathclyde Energy Systems Research Unit 75 Montrose Street, GLASGOW G1 1XJ, Scotland Email: [email protected] SYNOPSIS
Dynamic Process Modeling. Process Dynamics and Control
Dynamic Process Modeling Process Dynamics and Control 1 Description of process dynamics Classes of models What do we need for control? Modeling for control Mechanical Systems Modeling Electrical circuits
SPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
EnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
Effect of Rack Server Population on Temperatures in Data Centers
Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,
Closed-Loop Ground-Coupled Heat Pump Systems
The following article was published in ASHRAE Journal, September 2006. Copyright 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
RVH/BCH Data Centres Proposals for Surge Protection and Ventilation
REPORT Proposals for Surge Protection and Ventilation BELFAST HEALTH AND SOCIAL CARE TRUST ROYAL GROUP OF HOSPITALS GROSVENOR ROAD BELFAST BT12 6BA Rev. 01 6th September 2013 Table of Contents 1.0 Ventilation
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
Energy Impact of Increased Server Inlet Temperature
Energy Impact of Increased Server Inlet Temperature By: David Moss, Dell, Inc. John H. Bean, Jr., APC White Paper #138 Executive Summary The quest for efficiency improvement raises questions regarding
OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa
OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a
Energy savings in commercial refrigeration. Low pressure control
Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary
Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.
Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial
CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER
International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services
Technical Support Bulletin Nr. 20 Special AC Functions
Technical Support Bulletin Nr. 20 Special AC Functions Summary! Introduction! Hot Start Control! Adaptive Control! Defrost Start Temperature Compensation Control! Anti-Sticking Control! Water Free Cooling
The CEETHERM Data Center Laboratory
The CEETHERM Data Center Laboratory A Platform for Transformative Research on Green Data Centers Yogendra Joshi and Pramod Kumar G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology
Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances
Heating, ventilation and air conditioning equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Introduction 03 Background 03 Setting the scene 03 Benefits of purchasing ETL
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers
Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems ASHRAE TRP-1384 Scott P. Hackel Under the supervision of Professors Greg Nellis and Sanford Klein and the University of Wisconsin
Guidelines for Precast Concrete Grease Interceptors
Guidelines for Precast Concrete Grease Interceptors Purpose Provide an overview of the basic design principals that govern why gravity grease interceptors work Provide a forum for discussion of common
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
CFD Beyond the Whitespace. Datacentres Central & Eastern Europe
CFD Beyond the Whitespace Datacentres Central & Eastern Europe September 2013 CONTENTS 1.0 Introduction 2.0 What is CFD? How it Works CFD in Data Centres 3.0 CFD Outside the White Space Case Study 4.0
Energy Efficient Cooling Solutions for Data Centres
Kara Mackay Department of Mechanical Engineering MSc Energy Systems and the Environment Energy Efficient Cooling Solutions for Data Centres Submitted in partial fulfilment with the requirements of the
Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle
INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
Thermal Coupling Of Cooling and Heating Systems
This article was published in ASHRAE Journal, February 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
Increasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
HVAC: Cool Thermal Storage
HVAC: Cool Thermal Storage Thermal storage systems offer building owners the potential for substantial operating cost savings by using offpeak electricity to produce chilled water or ice for use in cooling
Data Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. [email protected] Abstract Data centre energy consumption
Cooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
Water Volume Calculation in Hydronic Heating & Cooling Systems
Water Volume Calculation in Hydronic Heating & Cooling Systems Preface There are several methods which can be used to calculate the volume of water in a hydronic heating or cooling systems. However, these
Building HVAC Load Profiling Using EnergyPlus
Building HVAC Load Profiling Using EnergyPlus Dong Wang School of EEE Nanyang Technological University Singapore Email: [email protected] Abhisek Ukil, Senior Member, IEEE School of EEE Nanyang Technological
