ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
|
|
|
- Constance Hill
- 10 years ago
- Views:
Transcription
1 ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay, Hong Kong ABSTRACT Energy conservation is one of the key issues for environmental protection and sustainable development. Currently, about 17% of the total energy is being consumed for heating, ventilation, air conditioning (HVAC) and refrigeration in Hong Kong. Therefore, energy saving in the HVAC systems of buildings is an important topic. In this paper, a study on the energy saving in a hotel HVAC system was carried out. The cooling load features of the hotel were analyzed. Retrofitting strategy of the HVAC system in the hotel was then designed. It included replacement of the chillers and pumps followed by adopting a newly designed control scheme based on the pattern of the cooling load. The control scheme consisted of controls of the chillers, pumps and cooling towers. An intelligent algorithm was developed to ensure the chillers work at the highest COP under different conditions. It was found that with the new system, about 63% to 74% of the chiller/pump system energy could be saved in that hotel. The result shows that for buildings such as hotels, a good control on the operation of the chillers and pumps is crucial. KEYWORDS Energy Saving, Hotel, HVAC, Control Scheme INTRODUCTION Since the International Oil Crisis in 1973, energy has become such an important issue that strongly affects people s lives and the policy of every country. Enormous efforts have been devoted in the past decades on energy resources and energy efficiencies. Currently, a large amount of energy is being consumed by heating, ventilation and air conditioning (HVAC) systems in buildings. According to the statistics from the Hong Kong SAR government, about 17% of the total energy, which is about 30% of the electric energy (Chow 2006) is being consumed by HVAC systems in buildings. Therefore, energy conservation of HVAC systems in buildings will clearly have a sizeable impact on total energy consumption. Up to date, a lot of efforts have been made in various buildings to minimize the energy consumption in HVAC systems. For example, Marriott (2006) proposed three approaches that can be easily applied in buildings to improve the energy efficiencies of HVAC systems. The approaches are optimizing the supply air temperature, recovering energy from condenser water and making use of the geothermal heat pump system. Chan (2006) proposed an optimum control logic for the HVAC system of a building in Hong Kong, which minimized the mismatch of cooling load demand and chilled water flow demand. Around 435,000 kwh was saved by the developed control logic from June 2003 to May Montgomery and Baker (2006) conducted a practical study on the effect of cleaning coils of air handling unit on building HVAC systems in New York City. The building has a total area of 111,500 m 2 and was served by four air handling units with the total capacity of 2,023 kw. It was found that the cleaned coils of the air handling units saved about $40,000 in Pressure drop of air through the air handling units was decreased by 14% and the thermal efficiency of the cooling coils was increased by 25%. Montgomery and Baker s work provided a valuable understanding on the effect of cleaning coils on energy saving in HVAC systems. Mathews et al. (2002) developed a simulation tool, QUICKcontrol. It estimates the effect of different control strategies on the energy saving performance in various buildings. Effects of control strategies such as fan scheduling, set point setback, economizer cycle, new set point, fan control, heat plant control, etc. can be investigated in detail via Corresponding Author: Tel: , Fax: address: [email protected]
2 this simulation tool. Mathews et al. used this simulation tool to study the energy saving potential in a conference center in South African. A new control strategy was developed with the aid of this simulation tool. It was predicted that about 58% of the HVAC system energy could be saved. Chan (2006) and Mathews et al. (2002) showed that besides the energy efficiency of the machines (chillers, pumps, fans, etc.), control strategy also plays a very important role on HVAC energy consumption. Kim et al. (2001) conducted a computational fluid dynamic simulation for analyzing the indoor cooling/heating load. It was coupled with a radiative heat transfer simulation program and a simulated HVAC control system. The output of the simulated HVAC control system can be fed back to the boundary condition of the CFD simulation program and the indoor environment was simulated. New control signal can then be determined based on the indoor environment. Energy saving performance of the control strategy can be investigated accurately. With the same simulation program, thermal comfort can also be estimated by the calculated indoor status using PMV based approach. In review of the previous studies on energy saving of HVAC systems, most were conducted in office buildings. Only a few studies were carried out in hotels. Hotels may consume a large amount of energy in some tourist cities and hence it is also an important issue. In this paper, a practical study on energy saving in a hotel was carried out. Chillers, pumps and the control system were retrofitted based on the analysis of the characteristics of hotel cooling load. Energy conservation performance of the retrofit was investigated. HOTEL, CHILLERS AND PUMPS DESCRIPTION The hotel is located in the East Kowloon area, Hong Kong, where it is located in the subtropical region. The monthly average temperature is ranging from about 15.9 to 28.8 o C throughout a year. The monthly relative humidity is about 68% to 83%. The hotel consists of 16 stories and has a total airconditioned area of 24,326 m 2. It has about 400 guestrooms together with some restaurants, meeting rooms, function rooms, kitchens, offices and shops. Most of the area is opened for 24 hours a day. The chillers of the hotel are located in a plant room on a lower level. Originally, there were 4 chillers having the refrigeration capacity of 1,235 kw, respectively. All the four chillers were air cooled chillers. The COP of two chillers was 3.7 and the COP of the other two was about 4.0. These chillers and the chilled water pumps have been operated for 17 years since The operation of the chillers was controlled manually by the operators according to the return temperature of the chilled water. When the return temperature of the chilled water was higher than 12 o C, one more chiller was put into operation. When the return temperature was lower than 11 o C, one chiller was turned off. Four centrifugal pumps with 37 kw each were used to drive the chilled water. The pumps were operated manually by the operators according to the number of the operated chillers. RETROFIT OF THE CHILLERS, PUMPS AND CONTROL SYSTEM The efficiencies of the devices were estimated to be low as the chillers and the pumps of the hotel were aged. The owner was eager to improve energy efficiency of the HVAC system to save the electric bill. Before the retrofit of the HVAC system, an analysis was carried out. It was revealed that: The HVAC system has to be operated for 24 hours a day. Compared to the HVAC systems in office buildings, which are generally operated in office hours, there was a large room to save the energy in hotels. Although the chillers with higher COPs are more expensive, they are suitable for hotel applications and the payback period is reasonable. Based on such consideration, water cooled chillers were proposed to replace the original air cooled chillers. Cooling load of the hotel varies dramatically from season to season, day to night, and with the varying occupancy level. In most of the time, especially at night, the original chillers might operate with part load. Therefore, chillers with less cooling capacity were proposed to cater for the low cooling load period. This could ensure that the chillers can operate with almost the full cooling load in most of the time.
3 Cooling load of the hotel may vary fast due to the possible sudden change in the occupancy level. For example, a group of tourists may check in or check out simultaneously. Manual control may not respond fast enough and may result in waste of energy. Therefore, an automatic control system was proposed. Based on the statistics from the Hong Kong Observatory, free cooling can be adopted for around 4 months in Hong Kong. Therefore, the control system should take into account the outdoor temperature to fully utilize free cooling for energy saving. Due to the large variation in the cooling load, flow rate of the chilled water should be carefully controlled. The pumps consumed a considerable amount of energy, which was about 20% of the chiller/pump system energy. In the past, chilled water flow rate was adjusted by valves. Energy was wasted via friction while water flowed through the valves. Frequency inverter based flow control system was proposed in order to reduce the pump energy together with the precise control of the chilled water flow rate. Based on this analysis, retrofits of the chillers, pumps and control system were carried out as follows. Chillers Sixteen water cooled chillers were adopted to replace the original four air cooled chillers. Among the sixteen chillers, two have the cooling capacity of 1265 kw and COP of 5.88 each. The cooling capacities of the rest are 90 kw and the COP of around 4.55 each. It is seen that the energy efficiency of the new chillers are evidently higher than the original chillers. COP of the smaller chillers is somewhat lower than that of the larger chillers. However, their smaller cooling capacity can ensure the chillers operate with the full cooling load most of the time and thus the highest energy efficiency can be obtained. Pumps The original pumps have been operated for 17 years and their efficiency was estimated to be low. The pumps were replaced by four new pumps with similar capacities. A frequency inverter was installed in one of the pumps to cater for the large variation in cooling load. With this configuration, flow rate of the chilled water can be adjusted continuously. Control System To obtain a maximum energy saving performance, a programmable logic controller (PLC) and PC based control system was developed. PLC was used to collect signals from temperature sensors, pressure sensors, flow rate sensors, etc. and to control the operation of the chillers and pumps. PC with a developed supervisory control and data acquisition (SCADA) system was used to monitor the whole system and to adjust the parameters. The control system carries out the following functions. a) Operation of the Chillers Free cooling can be used in Hong Kong for about 4 months as mentioned above. In fact, more accurately, free cooling can be used on most of the evenings and mornings according to the weather conditions. Therefore, the controller will judge if the chillers need to be operated to save energy. A temperature sensor was installed outside the hotel. Ambient temperature is measured in real time manner. Chillers are operated according to the two prescribed setpoints, T 1 and T 2, where, T 1 < T 2. T 1 and T 2 are selected according to the thermal comfort of the clients based on the experience of the operator. If the temperature is lower than T 1, which means that temperature is low enough for thermal comfort, no chiller is turned on. If the temperature is higher than T 2, which means that the clients may feel hot, the chiller is turned on. If the temperature is between T 1 and T 2, cooling will be supplied at some specified time, e.g., lunch time, etc. T 1, T 2 and the time can be set through the SCADA system. b) Operate the Chillers with the Highest Efficiency
4 Two larger chillers and fourteen smaller chillers were installed and the efficiencies of the chillers at different cooling load are different. Operating chillers with the highest efficiency can be a key issue for energy saving. For this purpose, a database of the efficiency of the chillers at different part loads was established. Real time cooling load is determined by the control system through the measurement of the supply and return temperature of the chilled water and the flow rate of the chilled water by an ultrasound flowmeter. The chiller (or the combination of the chillers) with the highest energy efficiency will be selected to operate according to the measured cooling load. c) Chilled Water Temperature Setpoint The temperature of the chilled water is important to the efficiency of the chillers. The higher the chilled water temperature is, the higher the efficiency of the chiller is. However, if the chilled water temperature is too high, the desired cooling capacity may not be offered. With the measured cooling load, the highest feasible chilled water temperature is calculated by the control system and it is then used as the setpoint of the chilled water. The PLC controller sets the setpoint of the chillers and the chillers change the chilled water temperature to the setpoint by the internal controllers. d) Cooling Water Temperature Control The cooling water temperature is important to the efficiency of the chillers. The cooling water is cooled in the cooling towers by fans. The supply temperature of the cooling water is limited by the ambient temperature. Improper setpoint of the supply cooling water temperature will cause the waste of the fan power. Therefore, setpoint of the supply temperature of the cooling water is adjusted in real time mode according to the ambient temperature. The number of cooling tower used and the fan speed are controlled in order to change the outlet cooling water temperature of the cooling tower to the setpoint. Temperature difference of the cooling water through the condenser is controlled by adjusting the flow rate of the cooling water via frequency inverters. The optimum temperature difference is selected for the highest possible energy efficiency for chillers and pumps. e) Chilled Water Pump Frequency inverter is installed to adjust the chilled water pumps to minimize the pump energy. While the load varies, a constant pressure at the furthest point will be maintained by modifying the speed and the number of the motors. So the energy consumed on the valves will be minimized while maintaining the desired water flow rate. The detailed flow chart of the control scheme is shown in figure 1. Figure 2 shows the schematic diagram of the new chiller/pump system.
5 Start Measure the outdoor temperature To To<T1 Y Turn off all chillers and pumps. To>T2 N N Y Turn on a chiller and a pump if no chiller and pump are being operated Measure the cooling load Turn on the chillers with the highest efficiency under current cooling load Y Is it the prescribed time to turn on chiller N Calculate the possible highest supply chilled water temperature and send commend to chillers Adjust the frequency inverter and the number of chilled water pump in operation to maintain the pressure at the furthest point from the setpoint Adjust the frequency inverter of cooling tower fan and the number of cooling tower in operation to control the cooling water temperature to the setpoint. Adjust the frequency inverter and the number of cooling water pump in operation to control the condenser water temperature difference to the setpoint. Figure 1: Flowchart of the Control Scheme ENERGY SAVING PERFORMANCE The new chillers, pumps and control system have started to operate since October It was found that the new system had much higher energy efficiency than the original system. Figure 3 shows the energy consumption of the new chiller/pump system of the hotel from October 2005 to August Energy consumption of the original system from October 2003 to August 2004 is also presented for comparison. During the two periods, the indoor temperature setting was the same. The monthly average ambient temperatures of the two periods were similar as shown in Figure 4. The average
6 . p chilled water AHU/fan coil unit flow meter chilled water pump frequency inverter T chiller. input PLC T T output SCADA T cooling water cooling water pump frequency inverter cooling tower frequency inverter Figure 2: Schematic Diagram of the New Chiller/pump System
7 temperature from October 2003 to August 2004 was about 22.9 o C while that in the period from October 2005 to August 2006 was 23.1 o C. Although the ambient temperature was slightly higher when the new system was used, the energy consumption was much less than that when the original system was used as can be seen in figure 3. The monthly electric energy consumption by the chiller/pump system was about 433,255 to 841,969 kwh with the old system. While the monthly electric energy consumption decreased to 128,960 to 269,232 kwh with the new system. About 63% to 74% of the chiller/pump energy was saved. 900, Energy Consumption (kwh) 800, , , , , , , , Month Figure 3. Energy Consumption in the Hotel by the Chillers and Pumps 35 Temperature ( o C) Month Figure 4. Monthly Average Temperature
8 In review the retrofit of the hotel HVAC system, the improved energy efficiency resulted from three aspects, i.e., improved energy efficiency of the chillers, improved energy efficiency of the pumps and the intelligent control system. Comparing the COPs of the original and the new chillers, it is seen that the new chillers has an energy efficiency about 18% to 36% higher than the original chillers which may contribute to about 14.4% to 28.8% of the total energy saving. The efficiency of the new pumps is estimated to be 30% higher than the original pumps. As the pumps generally consume about 20% of the total chiller/pump system energy, the replacement of the pumps contributes to about 6% of the total energy saving. Then, the remaining 27% to 45% of the energy saving should result from the intelligent control system. It is seen that a good control system is important to energy saving as well as the enhancement of the machines. The payback period of the system is predicted to be less than three years, which is quite acceptable. CONCLUSION Energy conservation of the HVAC systems in hotels is important to energy saving in tourist cities. In this paper, cooling load features of a hotel were analyzed. Retrofit of the HVAC system of the hotel was conducted including replacement of the chillers, replacement of pumps and installing a new control system with an intelligent control algorithm. This intelligent control algorithm ensures the energy is used with the highest efficiency. With the new system, 63% to 74% of the chiller/pump energy was saved. The result shows that a considerable amount of energy can be saved in hotels with a good control system and high efficiencies of the chillers and pumps. ACKNOWLEDGMENT This project was supported by the HKUST Research Grant ICL001.04/05. REFERENCES 1. Chow, T.T. (2006) HVAC System Optimization for Energy Management by Evolutionary Programming, Energy and Buildings, Vol. 38 (3) Marriott, C. (2006) Optimal Air, Energy Recovery, Geothermal: 3 Simple Approaches to Energy Efficiency, ASHRAE Journal, Vol. 48(7) Chan, C.W.H. (2006) Optimizing Chiller Plant Control Logic, ASHRAE Journal, Vol. 48(7) Montgomery, R.D., Baker, R. (2006) Study Verifies Coil Cleaning Saves Energy, ASHRAE Journal, Vol. 48(11) Mathews, E.H., Arndt, D., Geyser, M.F., (2002) Reducing the Energy Consumption of a Conference Centre - A Case Study Using Software, Building and Environment, Vol. 37 (4) Kim, T., Kato, S., Murakami, S., (2001) Indoor Cooling/Heating Load Analysis Based on Coupled Simulation of Convection, Radiation And HVAC Control, Building and Environment, Vol. 36 (7)
HEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
ENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM
Proceedings of Building Simulation 211: ENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM Yoshitaka Uno 1, Shinya Nagae 1, Yoshiyuki Shimoda 1 1
Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Absolute and relative humidity Precise and comfort air-conditioning
Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances
Heating, ventilation and air conditioning equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Introduction 03 Background 03 Setting the scene 03 Benefits of purchasing ETL
A heat pump system with a latent heat storage utilizing seawater installed in an aquarium
Energy and Buildings xxx (2005) xxx xxx www.elsevier.com/locate/enbuild A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Satoru Okamoto * Department of Mathematics
The Business Case Annual fuel cost savings of 26% worth more than 28,000 Annual fuel savings of 1.3million kwh Annual CO2 savings of over 245 tonnes
North Lanarkshire Council The Business Case Annual fuel cost savings of 26% worth more than 28,000 The Sir Matt Busby Sports Complex is an important local facility for the people of Bellshill, North Lanarkshire.
Heating, ventilation and air conditioning (HVAC) equipment. A guide to equipment eligible for Enhanced Capital Allowances
Heating, ventilation and air conditioning (HVAC) equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Boost Introduction your cash flow 03 1. Background Check it s on the
Using Time-of-Day Scheduling To Save Energy
The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Building HVAC Load Profiling Using EnergyPlus
Building HVAC Load Profiling Using EnergyPlus Dong Wang School of EEE Nanyang Technological University Singapore Email: [email protected] Abhisek Ukil, Senior Member, IEEE School of EEE Nanyang Technological
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *
Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting
Impact of Control System Technologies on Industrial Energy Savings
Impact of Control System Technologies on Industrial Energy Savings Priyam Parikh Industrial Assessment Center Texas A&M University Bryan P. Rasmussen Industrial Assessment Center Texas A&M University http://farolconsulting.com/?page_id=110
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany
Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment
CONTROL STRATEGIES FOR HVAC SYSTEMS
CONROL SRAEGIES FOR HVAC SYSEMS ZBIGNIEW POPIOLEK Department of Heating, Ventilation and Dust Removal echnology Silesian University of echnology, Poland 1 Definition of control: to apply a regulating influence
Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX
Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX Content Heating / Ventilation / Air Conditioning 3 The Right Room Climate 4 Optimised Energy Efficiency and well-being Room
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling
HOT & COLD Basic Thermodynamics and Large Building Heating and Cooling What is Thermodynamics? It s the study of energy conversion using heat and other forms of energy based on temperature, volume, and
Code of Practice for Building Energy Audit
Code of Practice for Building Energy Audit 2012 Code of Practice for Building Energy Audit Table of Contents Page No. 1. Introduction 1 2. Interpretations 1 3. Application 4 4. Technical Compliance with
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
Secondary Loop Chilled Water In Super High-Rise
The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
Fundamentals of HVAC Control Systems
ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong
Condensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747
POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
ALONE. small scale solar cooling device Project No TREN FP7EN 218952. Project No TREN/FP7EN/218952 ALONE. small scale solar cooling device
Project No TREN/FP7EN/218952 ALONE small scale solar cooling device Collaborative Project Small or Medium-scale Focused Research Project DELIVERABLE D5.2 Start date of the project: October 2008, Duration:
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
ROTEX gas hybrid heat pump. A strong team.
ROTEX gas hybrid heat pump A strong team. The new ROTEX HPU hybrid gas hybrid heat pump always selects the most favourable heating mode automatically. For a long time the general opinion was that a heat
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
Scope of Work. See www.sei.ie for resources available
HVAC SWG Summary Background Pool energy-efficiency knowledge Increase cost-competitiveness Develop resources aimed at assisting in reducing HVAC energy consumption Address barriers to energy-saving HVAC
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Application of Building Energy Simulation to Air-conditioning Design
Hui, S. C. M. and K. P. Cheung, 1998. Application of building energy simulation to air-conditioning design, In Proc. of the Mainland-Hong Kong HVAC Seminar '98, 23-25 March 1998, Beijing, pp. 12-20. (in
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)
Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to
Heating, ventilation and air conditioning zone controls
Technology information leaflet ECA762 Heating, ventilation and air conditioning zone controls A guide to equipment eligible for Enhanced Capital Allowances Contents Introduction 01 Background 01 Setting
Energy Efficiency Experience with a Successful Performance Contract Island Place Shopping Centre
Energy Efficiency Experience with a Successful Performance Contract Island Place Shopping Centre Dr Leonard Chow 1, Ir Cary Chan 2, Ir K L Chan 3 1 ISPL Consulting Ltd 2 Swire Properties Management Ltd
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS by Dr. Bing Chen and Prof. John Bonsell Passive Solar Research Group University of Nebraska-Lincoln Omaha campus and Richard
Wet Bulb Temperature and Its Impact on Building Performance
Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?
EUROPEAN COMMISSION. Energy Audits - Cyprus
EUROPEAN COMMISSION DIRECTORATE-GENERAL FOR ENERGY SAVE II Programme Energy Savings by CHCP plants in the Hotel Sector Energy Audits - Cyprus May 2001 CONTENTS 1. Selection of hotels in Cyprus...2 2 Energy
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
Year project completed or estimated year of completion: October 2014
Name (Mr/Ms/Dr): Mr Rainer Tenius Job title: General Manager Company s name: Swissôtel Merchant Court, Singapore Award won: BCA Green Mark Award (Platinum) Name of Project that won the award, if applicable:
The natural ombination
The natural ombination DAikin Altherma Hybrid heat pump system The future is now The new hybrid system Heat pump solution for gas boiler replacement market Daikin Altherma hybrid combines heat pump technology
How To Save Money On Energy
Business Programs and Services At our Delray location, we had an immediate 23 percent drop in lighting kilowatt-hour usage. That has a significant impact on our energy bills. Ken Infante, AutoNation, Inc.
HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers
HEAT RECOVERY FROM CHILLED WATER SYSTEMS Applications for Heat Reclaim Chillers April 2008 TABLE OF CONTENTS INTRODUCTION... 3 WASTE HEAT SOURCES... 3,4 Capturing Sufficient Heat for Useful Purposes...
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction What is DNSS EcoSave? The Daikin Network Service System (DNSS EcoSave) is a Daikin developed internet based remote
ULTRA-EFFICIENT HVAC DESIGN AND CONTROL
CASE STUDY ULTRA-EFFICIENT HVAC DESIGN AND CONTROL MAJOR HEATING, VENTILATING AND AIR- CONDITIONING REPLACEMENT AT THE COUNTY OF SAN DIEGO CRIME LAB December 30, 2005 8520 Tech Way, Suite 110 San Diego,
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
HVAC System Optimization
UNITED TECHNOLOGIES CARRIER CORPORATION HVAC System Optimization MAXIMIZING PERFORMANCE, ENERGY SAVINGS & COMFORT Revitalize Your Building s System Sometime between the initial purchase and the need to
AQUACIAT2 HYBRID THE COMPACT DUAL-ENERGY SOLUTION HEAT PUMP & GAS BOILER. Cooling and heating capacities of 45 to 80 kw AVAILABLE 2 ND QUARTER OF 2014
AVAILABLE 2 ND QUARTER OF 2014 HEAT PUMP & GAS BOILER C O M F O R T A I R Q U A L I T Y E N E R G Y O P T I M I S A T I O N AQUACIAT2 HYBRID Cooling and heating capacities of 45 to 80 kw THE COMPACT DUAL-ENERGY
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
*At the AHRI Standard flow rate of 3 gpm/ton, using today s efficient chillers, the ΔT is 9.3 F rather than the 10 F often assumed.
providing insights for today s hvac system designer Engineers Newsletter volume 41 3 Condenser Water System Savings Optimizing flow rates and control Optimized flow rates in the condenser water system
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
Example of audit of an air conditioning system
Example of audit of an air conditioning system Authors and affiliations: André Philippe Hannay Cleide, Hannay Jules, Lebrun Jean University of Liège, Belgium Main author: Jean Lebrun Email : [email protected]
Energy Saving Tips. Adjust set point temperature up a few degrees... Window contact. Occupancy sensor. A Programmable Thermostat
Energy Saving Tips Nowadays when Energy costs are skyrocketing and the awareness to environmental issues is increasing, we all want to reduce energy consumption and have a greener lifestyle. Heating &
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)
2015 C&I HVAC RETROFIT APPLICATION FOR PRESCRIPTIVE REBATES
2015 C&I HVAC RETROFIT APPLICATION FOR PRESCRIPTIVE REBATES WELCOME TO THE POWER MOVES C&I HVAC RETROFIT PROGRAM. We look forward to working with you. If you have questions after reading this application,
Rev. No. 0 January 5, 2009
ENERGY & ENVIRONMENTAL ENERGY ISSUES COMMITTEE 415 Main Building Telephone (574) 631-6666 Notre Dame, Indiana Facsimile (574) 631-5883 46556 USA Energy Conservation Plan For HVAC Systems Rev. No. 0 January
HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium
HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING Cleide Aparecida Silva 1, [email protected] Stéphane Bertagnolio 1, [email protected]
Energy Conservation of Heat, Ventilation & Air- Conditioning System with the help of Fuzzy Controller
Energy Conservation of Heat, Ventilation & Air- Conditioning System with the help of Fuzzy Controller i Harkamaljeet Singh Bhullar, Vikram Kumar Kamboj Abstract: The Management and Automation of a Commercial
Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
Small-Scale Solar Heating and Cooling Systems
Contact Austria: AEE INTEC (www.aee-intec.at) France: Tecsol (www.tecsol.fr) Germany: Fraunhofer ISE (www.ise.fraunhofer.de) Greece: CRES (www.cres.gr) Italy: EURAC (www.eurac.edu) University of Bergamo
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
www.hft-global.com/education Refrigeration & HVAC
www.hft-global.com/education The HFT Refrigeration and HVAC range has been designed and developed to allow study of the theoretical and practical operation of many types of refrigeration and air conditioning
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants
HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: [email protected] 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
Crowne Plaza Copenhagen Towers The world s greenest hotel
Crowne Plaza Copenhagen Towers The world s greenest hotel The new Crowne Plaza Copenhagen Towers in Copenhagen, has been designed with sustainability in top of mind. The hotel is one of the first hotels
Rules of Thumb Energy Efficiency in Buildings
Energy Efficiency in Buildings Energy Savings Cost Savings Increased Productivity Economic Development Other Standard lighting retrofits: $0.90-$1.20 per square foot. High-efficiency packaged and split
Hot Water. Heat pump water heaters. Residential and Commercial R410a
Hot Water Heat pump water heaters Residential and Commercial R410a Heat pump technology Heat Pump Water Heating is a new idea using existing technology and is viewed as the latest generation of water heating
5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment
5.6 Technical Specification: Premium Efficiency Electric Conditioning Equipment Small Premium Project Type: For Premium Conditioning Retrofit Projects: Projects that voluntarily replace existing unitary
Thermal Coupling Of Cooling and Heating Systems
This article was published in ASHRAE Journal, February 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation
Information Guide Domestic Air Source Heat Pumps
Information Guide Domestic Air Source Heat Pumps Issue 41 Domestic Air Source Heat Pumps This is an independent guide produced by Mitsubishi Electric to enhance the knowledge of its customers and provide
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...