COMPRESSOR REPLACEMENT PROCEDURE
|
|
|
- Louisa Day
- 9 years ago
- Views:
Transcription
1 COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio Since Moving ahead just as planned Manual No.: E Supersedes D File: Volume I, Tab 1 Date: Copyright 2002
2 CONTENTS General Information Three Phase Scroll Compressor Start Information... 1 Steps to Replace Compressor... 1 Suction and Discharge Tube Brazing... 2 Conclusion... 4 Tables Table 1 Table 2 Air Contitioner Liquid Line Filter Driers (Directional)...3 Heat Pump Liquid Line Filter Driers (Bidirectional)...3 Table 3 Sunction Line Filter Driers...3 Table 4 Additional Refrigeration Requirements..4 Figures Figure 1 Brazing Diagram...3 Figure 2 Typical A/C Filter Drier Locations...5 Figure 3 Typical Self-Contained H/P Filter Drier Locations...5 Figure 4 Typical Split System H/P Filter Drier Locations...5 i
3 GENERAL Before replacing any compressor, make absolutely sure that it is the compressor that is at fault. Problems with the external electrical components are many times diagnosed as a faulty compressor. Please note the information below on three phase scroll compressors. THREE PHASE SCROLL COMPRESSOR START UP INFORMATION Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction. However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as substantially reduced current draw compared to tabulated values. Verification of proper rotation must be made at the time the equipment is put into service. There is no negative impact on durability caused by operating three phase Compliant Scroll compressors in the reversed direction. However, after several minuted of operation the compressor s internal protector will trip. Reverse operation for over one hour may have a negative impact on the bearings. NOTE: Some units are equipped with a Phase Monitor that will automatically govern whether the compressor contactor can be activated. Check the unit wiring diagram and installation instructions. All three phase ZR*3 compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminals should maintain proper rotation direction. The direction of rotation of the motor may be changed by reversing any two line connections to the unit. Step 1. If the compressor tries to start and cycles overload: A. Measure line voltage at the unit terminals at the moment of start. It must be within the operation voltage range as sown on the unit serial plate. If it is less than the minimum voltage shown, check all electrical connection and branch wire size. B. Check to determine whether the run capacitor is good and of the correct rating. Replace the capacitor if in doubt. C. If a start capacitor and start relay are employed, check out these components. D. If there are no starting components used on the system, connect a start kit of the correct size temporarily to the compressor circuit. If the compressor motor now starts and runs okay, install start kit permanently. If the compressor does not try to start and blows fuses: A. Remove the wiring from the compressor terminals and check for ground between each terminal and the compressor housing. B. Check for continuity between the common terminal C and run terminal R, and between the common terminal C and start terminal S. If either one of these checks show continuity and the other does not, one of the motor windings is open. If neither show continuity and a check between terminal R and terminal S show continuity, both motor windings are intact and the internal overload is open. (Normally, any time the compressor housing is cool enough to hold your hand tight against, the overload should be closed.) Step 2. It is essential to establish the type of compressor failure that has occurred before any further work can take place. A. If there was a mechanical failure that would cause a no pump condition (any situation where the motor starts and runs okay but little or no refrigerant is pumped), the system cleanup procedure can be bypassed. Replace the compressor and proceed to Step 6. Page 1
4 If the compressor failure resulted from some form of an electrical failure, the compressor has undergone a burnout condition of some degree of magnitude. It is essential to determine the type and extent of the burnout before the new compressor is installed. A. Through the service ports, sample the refrigerant for the characteristic acrid odor of a burnout. WARNING Smell cautiously, the gas could be toxic and highly acrid. B. Recover the system refrigerant charge using correct recovery procedures and send the refrigerant to any authorized reclaim facility. CAUTION Avoid getting the refrigerant in the eyes or on the skin. C. Remove the burned compressor. Use rubber gloves when handling contaminated parts if there is any likelihood of contacting the oil or sludge. D. If the discharge line shows no evidence of sludge and the suction stub is likewise clean, or perhaps has some light carbon deposits, the burnout occurred while the compressor was not rotating. Contaminants are, therefore, largely confined to the compressor housing and a single installation of liquid and suction line filter-driers will probably suffice to clean up the system. E. If the sludge is evident in the discharge line (and very likely also found in the suction line) the compressor motor burned while running. Sludge and acid has been pumped throughout the system and several changes of the liquid and suction filter-driers will probably be necessary to cleanse the system. Step 3. System suffering running burnouts will also require additional cleansing of various piping and components, and even this may not rule out the possibility of having to replace these components. A. An extensive burnout condition may clog the screen and/or the capillary tubing, orifice or TXV requiring replacement. B. The reversing valve may become inoperative or sluggish due to sludge and acid action attacking the moving parts and their bearing surfaces. C. It is highly probable that the accumulator bleed orifice would be plugged on a severe burnout, and is recommended that the accumulator be replaced as it is practically impossible to assure the reliability and performance of the accumulator even though it has been flushed out. Step 4. An evaluation should be made to determine what the system fault that caused the burnout was and take the necessary steps to correct that situation. A. Check all electrical components (capacitors, relays, overload, etc. where applicable). Check the contacts of the compressor contactor. B. Install the new compressor. Make sure that the replacement compressor is exactly the same as the defective one, or a substitute authorized by the factory. The following information is to be noted for installation of the replacement compressor. SUCTION AND DISCHARGE TUBE BRAZING Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors. Due to different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used. To disconnect: Heat joint areas 2 and 3 slowly and uniformly until braze material softens and the tube can be pulled out of suction fitting. (See Figure 1.) To connect: Recommended brazing materials: silfos with minimum 5% silver or silver braze material with flux. Reinsert tube into fitting. Page 2
5 Heat tube uniformly in area 1 moving slowly to area 2. When joint reaches brazing temperature, apply brazing material. (See Figure 1.) Heat joint uniformly around the circumference to flow braze material completely around the joint. Slowly move torch into area 3 to draw braze material into joint. (See Figure 1.) Do not overheat joint. FIGURE 1 BRAZING DIAGRAM TABLE 2 HEAT PUMP LIQUID LINE FILTER-DRIER (BIDIRECTIONAL) Unit Size Unit Size L ine Size P art No. Model No. 0-36,000 BTU 3/8" BFK-083S 37-60,000 BTU 3/8" BFK-163S TABLE 3 SUCTION LINE FILTER-DRIER L ine Size P art No. Model No. 0-24,000 BTU 1/2" C-164-ST-HH 25-31,000 BTU 5/8" C-165-ST-HH 32-37,000 BTU 3/4" C-166-ST-HH 38-60,000 BTU 3/4" C-306-ST-HH 38-60,000 BTU 7/8" C-307-ST-HH C. Install liquid line and suction line filterdriers as selected from Table 1 based upon line size and unit BTU size. Unit Size TABLE 1 AIR CONDITIONER LIQUID LINE FILTER-DRIER (DIRECTIONAL) MIS-1179 IMPORTANT Heat pump units require a different liquid line filter -drier than air conditioners. The or bidirectional liquid line filter-drier must be used on heat pumps, and if desired, could also be used on air conditioners. Under no circumstances should the or directional filter-driers be used on heat pumps as shown by Figures 3 or 4. L ine Size P art No. Model No. 0-36,000 BTU 3/8" C-083S 37-60,000 BTU 3/8" C-163S CAUTION Suction line filters are not acceptable substitutes for filter-driers. D. Figures 2, 3 and 4 on Page 5 illustrate the recommended locations for both the liquid line and suction line filter driers on both air conditioning and heat pump systems. It is imperative that the filter-driers be installed as shown for the heat pumps to assure adequate protection and so that there is no reverse flow of refrigerant through the filter-drier. Step 6. Evacuate the system to less than 1,000 microns using a good vacuum pump and an accurate high vacuum gauge. Operate the pump at 1,000 microns, or less, for one hour and then allow the system to stand for 30 minutes to be sure the vacuum is maintained. A. Charge System with the specified quantity of refrigerant. See Step 7. NOTE: At no time use the compressor to evacuate the system or any part of it. Page 3
6 Step 7. Charge the system and place in operation. A. Self-contained units. The unit serial plate lists the total amount of refrigerant required for recharge. Also see Step 7, C. B. Split-system units. The unit serial plate refers you to a system charge table located elsewhere in the unit. Using specific model number for indoor and outdoor units, and the length of the interconnection tubing, determine the total system charge. There is a blank on the serial plate for this to be marked and is supposed to be done by the original installer. Also see Step 7, C. C. The addition of liquid line filter-driers to any system requires additional refrigerant. This is shown in the Table 4 and applies to each liquid line filter-drier used. TABLE 4 ADDITIONAL REFRIGERANT REQUIREMENTS P art No. Model No. Oz. of R C-063S C-163S BFK-083S BFK-163S 13 Step 8. After the system is charged and placed in operation, immediately check the pressure drop across the suction line filter-drier. This will serve two purposes: A. Verify that the drier selection was correct; that is, large enough. B. Serve as a base point to which subsequent pressure checks can be compared. Because the permissible pressure drop across the drier is relatively small, it is suggested that a differential pressure gauge be use for the measurement. After the system has been operating for an hour or so, measure the pressure drop across the suction line filterdrier. The maximum pressure drop for a permanent installation is 3 PSIG. In the case of a cleanup of a standing burnout, little change should be noted and, in most cases, the pressure drop will be less that the maximum allowable 3 PSIG. On the other hand, where a severe running burnout has occurred, and increased pressure drop will be measured. Change the suction filter-drier and the liquid line filterdrier whenever the pressure drop approaches or exceeds that allowed for temporary operation during cleanup, 15 PSIG. Keep changing both the suction and liquid line filter-driers until the pressure drop stabilizes at a figure equal to or below that permitted for permanent operation in a system, 3 PSIG. At this point, it is the serviceman s option as to whether to leave the suction drier in the system or remove it from operation. CONCLUSION If the system is to be opened to permit permanent removal of the suction filter-drier, then the liquid line filter-drier should be changed once more. The above procedure for the cleanup of hermetic systems after burnout through the use of suction line filter-drier will prove satisfactory in most instances provided the system is monitored and kept clean by repeated drier changes, if such are needed. The failure to follow these minimum cleanup recommendations will result in an excessive risk of a repeat burnout. Page 4
7 FIGURE 2 TYPICAL AIR CONDITIONER FILTER-DRIER LOCATIONS FIGURE 3 TYPICAL SELF-CONTAINED HEAT PUMP FILTER-DRIER LOCATIONS FIGURE 4 TYPICAL SPLIT SYSTEM HEAT PUMP FILTER-DRIER LOCATIONS Page 5
COMPRESSOR REPLACEMENT PROCEDURE
R-22 and R-410A COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003F Supersedes 2100-003E File: Volume I,
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
Test Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
This chapter is devided into two sections:
This chapter is devided into two sections: Page Installation requirements........................................................................ 127 The installation process..........................................................................
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS BULLETIN 240-10-3 June 2004 Supersedes June 1983 Many centrifugal systems get little maintenance. As a result they operate with the refrigerant highly contaminated
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as
Flushing and Cleaning the A/C System
Flushing and Cleaning the A/C System Once an AC system has been contaminated or has suffered a failure, the most important part of the AC service to restore the cooling performance to the system = FLUSHING
Table Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List
10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS
Service Literature ACC SERIES UNITS ACC Corp. 0201 L1 Revised 08 2004 The ACC is a residential split-system condensing unit available in sizes ranging from 1 1/2 to 5 tons. Condensing coil size, circuiting
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Owner s Manual Phoenix 300
PO Box 8680 Madison, WI 53708 Phoenix 300 High Capacity Dehumidifier Part number TS-218 Owner s Manual Phoenix 300 Installation, Operation and Service Instructions Read and Save These Instructions The
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
ice 3 FLUID TO FLUID HEAT PUMP
ice 3 FLUID TO FLUID HEAT PUMP SUBMITTAL DATA (888) 530-7713 P O Box 5, Wentworth, H 03282 Rev.3 (5-30-14) ice 3, IC-2040 Fluid-to-Fluid R-410a Heat Pump Engineering Guide Specifications General otes:
Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
A brief explanation on how air conditioning works and what terms mean
A brief explanation on how air conditioning works and what terms mean -presented by- Before we begin, let s explain the air conditioning process. In the most basic of terms, air conditioning simply takes
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard
14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C
GUIDELINES FOR UTILIZATION OF R407C 2009 Tecumseh Products Company. All rights reserved. Page 1 of 6 After many years of testing and investigation, R407C is recognized as a suitable alternative refrigerant
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
T-Series Air Conditioner T62 Model
INSTRUCTION MANUAL T-Series Air Conditioner T62 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
Owner s Manual Phoenix 200 MAX
420 Lien Rd. Madison, WI 53704 Owner s Manual Phoenix 200 MAX Installation, Operation & Service Instructions Read and Save These Instructions The Phoenix 200 MAX is one of the most effective and versatile
Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 -
Skills Canada National Competition Instructions and Competition Details / Post - Secondary May 27-30, 2015 - Saskatoon 1. Test Project Details This project is designed to test the range of skills used
HVAC-02, Air Conditioning Troubleshooting and Repair
HVAC-02, Air Conditioning Troubleshooting and Introduction Since I'm constantly receiving questions on 944 air conditioning systems, I figured it's time to come up with come helpful troubleshooting tips.
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Refrigeration System Installation & Operation Manual
Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3
LOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
High School Graduation years 2013, 2014, 2015. Unit/Standard Number
1 Secondary Task List 100 INTRODUCTION TO HVAC 101 Identify HVAC systems. 102 Describe career opportunities in the HVAC profession. 103 Demonstrate awareness of the occupational requirements. 104 Explain
SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)
Form #SB4-304AS AirSourceR SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION) Second only to refrigerant hose leaks, compressors have the highest rate
PACKAGE AIR CONDITIONERS REPLACEMENT PARTS MANUAL
REPLACEMENT PARTS MANUAL PACKAGE AIR CONDITIONERS Models: P1142A3 P1148A1 P1148A1-B P1148A1-C P1060A1 P1060A1-B P1060A1-C P1148A1-A/H P1148A1-B/H P1148A1-C/H P1060A1-A/H P1060A1-B/H P106A1-C/H General
DEALER SERVICE BULLETIN
DEALER SERVICE BULLETIN Number: DSB 14-0025 Date: 4/1/14 Supersedes: DSB 11-0025A Revised 9/17/12 Title: Bristol Two Stage Compressor or Unit Replacement Program PRODUCT CATEGORY: Heat Pumps and Split
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
Training Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. www.cliplight.com/hvacr/ Page 2 3 4 4 5 6 8 9
SUPER SEAL PROFESSIONAL FORMULA Training Manual a. b. c. d. e. f. g. h. i. j. k. l. m. Inside Your Guide Frequently Asked Questions... How does Super Seal work?... Can you use Super Seal on 410a systems
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507 Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale changeover of HCFCs
Customized Assessment Blueprint
Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC
10 tips for getting more reliability from your air-conditioning system [reliability]
10 tips for getting more reliability from your air-conditioning system [reliability] A guide for installers, specifiers, contractors and architects February 2010 10 tips for getting more reliability from
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
GENERAL INFORMATION FOR REPAIR AND MAINTENANCE OF CENTRAL AIR CONDITIONING PLANT ( Direct & Chiller ).
GENERAL INFMATION F REPAIR AND MAINTENANCE OF CENTRAL AIR CONDITIONING PLANT ( Direct & Chiller ). Name of sector Refrigeration & Air Conditioning Name of Module REPAIR AND MAINTENANCE OF CENTRAL AIR CONDITIONING
Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K*
Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K* 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety statements... 1 1.3 General instructions... 2 2 Product description...
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
01-3 6820-11 6820-11 AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON 2010.01
682011 013 GENERAL 1. SPECIFICATIONS 682011 014 682011 2. REPAIR INSTRUCTIONS 1) Precautions for Working with R134a R12 refrigerant and R134a refrigerant are not compatible. These refrigerants must never
Split System Heat Pump Product Data
Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]
INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES Split System Air Conditioner Save these instructions for future reference WARNING The equipment covered in this manual is to be installed by trained
PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS
NOR-LAKE, INCORPORATED 727 Second Street P.O. Box 248 Hudson, Wisconsin 54016 800-955-5253 715-386-2323 866-961-5253 Parts 800-388-5253 Service 715-386-4291 FAX www.norlake.com Split-Pak Pre-Assembled
Air Conditioning Sign-Off Sheet
Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet
Perkins Statewide Articulation Agreement Documentation item: Secondary Task List Coversheet The Secondary School agrees to: A. Implement the approved PDE Program(s) of Study. B. Provide assessment of student
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you
SERVICE MANUAL FOR 6700, 7000, 8000 & 9000 SERIES AIR CONDITIONERS (MECHANICAL CONTROLS ONLY)
SERVICE MANUAL FOR 6700, 7000, 8000 & 9000 SERIES AIR CONDITIONERS (MECHANICAL CONTROLS ONLY) FOR WALL MOUNT THERMOSTATS AND LOW VOLTAGE CONTROL CIRCUITS, REFER TO THEIR APPROPRIATE MANUALS FOR ELECTRICAL
Packaged Glycol Chiller Systems Operation Manual
Packaged Glycol Chiller Systems Operation Manual ii Pro Refrigeration, Inc Contents 1 Preface iii CUSTOMER SERVICE MANUFACTURE S INFORMATION RECEIVING & UNLOADING WARNINGS & CAUTIONS iii iii iii iii PRO
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
DIABLO VALLEY COLLEGE CATALOG 2015-2016
HEATING, VENTILATION, AIR CONDITIONING, REFRIGERATION - HVACR Tish Young, Dean Physical Sciences and Engineering Division Physical Sciences Building, Room 263 Possible career opportunities Upon successful
APPLICATION GUIDELINE & SERVICE MANUAL R 410A & R 22 Split System AC & HP
APPLICATION GUIDELINE & SERVICE MANUAL TABLE OF CONTENTS PAGE PAGE UNIT IDENTIFICATION... 2 REFRIGERATION SYSTEM REPAIR... 24 26 SAFETY CONSIDERATIONS... 4 INTRODUCTION... 4 INSTALLATION GUIDELINE... 4
POLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
http://www.smartpdfcreator.com
Technical Service Bulletin Transaction No.: 2018162/2 87 Cleaning of the air conditioning refrigerant circuit Release date: Dec 5, 2008 Condition REVISION HISTORY Revision Date Purpose 2 - Revised Title
User s Information/Installation Instructions
Outdoor Heat Pump User s Information/Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity and effi ciency in accordance with A.R.I.
How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.
Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)
SSB*H4. Service Literature. SSB*H4 Commercial Air Conditioner
Service Literature Corp. 0628 L5 Revised 07 2010 SSB*H4 Commercial Air Conditioner SSB*H4 The SSB*H4 is a high efficiency commercial split system condensing unit, which features a two stage scroll compressor
Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system
AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and
System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes
System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Faults on refrigeration systems, general...3 Fault location without the use of instruments...3 Categorisation...3
SYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING. Effective From :- UNDER DEVELOPMENT.
SYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING Effective From :- UNDER DEVELOPMENT Prepared by: Curriculum development cell Institute of Research Development
123 street Salt Lake City, Utah 84092
Salt Lake City, Utah 84092 Prepared for: Sample AC inspection Prepared by: Page 1 of 8 Table of Contents Definitions 2 General Information 2 Air Conditioning 3 Heating System 6 Summary 8 Page 2 of 8 Definitions
INSTALLATION INSTRUCTION
INSTALLATION INSTRUCTION OUTDOOR SPLIT-SYSTEM AIR CONDITIONER MODELS: 10, 12, 13 AND 14 SEER 1 PHASE - 1.5 TO 5 TONS TABLE OF CONTENTS GENERAL INFORMATION.................... 2 INSPECTION..............................
Models: WA182, WA242. Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List... 4. Control Panel.
REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE AIR CONDITIONER Models: WA182, WA242 General Notes! Revised and/or additional pages may be issued from time to time.! A complete and current manual consists
Danfoss compressors - Repair of hermetic refrigeration systems
Contents Page 1.0 General... 97 1.1 Fault location... 97 1.2 Replacement of thermostat... 98 1.3 Replacement of electrical equipment... 99 1.4 Replacement of compressor... 99 1.5 Replacement of refrigerant...
TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR
3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,
T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200
INSTRUCTION MANUAL FOR: T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleanthermal.com INSTRUCTION MANUAL TABLE OF CONTENTS
Name: Air Conditioning, Heating and Refrigeration (47.0201)
Name: Air Conditioning, Heating and Refrigeration (47.0201) Directions: Evaluate the student by entering the appropriate number to indicate the degree of competency. Rating Scale (0-6): 0 No Exposure no
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
PC1131 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
Refrigerants and the Refrigeration System
M25_STAN0893_00_SE_C25.QXD 9/4/08 9:54 PM Page 1 SECTION FOUR Refrigerants and the Refrigeration System UNIT 25 Accessing Sealed Refrigeration Systems OBJECTIVES After completing this unit you will be
AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6
AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2
REPAIR OF HERMETIC REFRIGERATION SYSTEMS
With more than 50 years of experience in compressor technology and highly committed employees, our focus is to develop and apply the advanced compressor technologies to achieve standard setting performance
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. This Troubleshooting Guide covers the electric coolant valve and control
Split System Cooling Product Data
Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
Water valves REFRIGERATION AND AIR CONDITIONING. Fitters notes
REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Application...3 Identification...3 Installation...5 Setting...6 Maintenance...6 Spare parts...8 Fault location...9 2 RZ4DA202 DKRCC.PF.D00.A1.02
Models: Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List... 4. Control Panel. Blower Housing
REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE HEAT PUMPS Models: WH301 WH361 General Notes! Revised and/or additional pages may be issued from time to time.! A complete and current manual consists of pages
Solenoid Valves and Their Importance in Refrigeration Systems. October 2007
Solenoid Valves and Their Importance in Refrigeration Systems October 2007 Overview Introduction Solenoid valves play an important role within refrigeration and air conditioning systems, controlling the
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
Subject: 2005 Air Conditioning Service Guidelines
Date: June 27, 2005 Bulletin Number: 05D-J-114 To: DDG Headquarters and Branches and Jobbers Category: Service From: Steve Sigg, Product Service and Training Line(s): 10 and 15 Subject: 2005 Air Conditioning
T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL. Rev. F 2016 Pentair Equipment Protection P/N 89104464
T-SERIES Air Conditioner T29 Model INSTRUCTION MANUAL Rev. F 2016 Pentair Equipment Protection P/N 89104464 89104464 TABLE OF CONTENTS RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3
UA-NJ Air Conditioning & Refrigeration Division Training Curriculum
UA-NJ Air Conditioning & Refrigeration Division Training Curriculum 1st Year Basic Mathematics for HVAC Using formulas as an expression of logical sequence in solving problems. Measuring using a ruler
Panel Mounted Air Conditioners by Dantherm, Inc.
Panel Mounted Air Conditioners by Dantherm, Inc. CS020020A/B with USACG-6 Control PRODUCT INFORMATION MANUAL AC-2 CS020020 USACG-6 Manual Rev H Page 1 of 17 Dantherm, Inc. 110 Corporate Drive, Suite K
Pump Maintenance - Repair
Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A
COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A (All unshaded skill sets must be demonstrated/completed) PROTECT SELF AND OTHERS Identify, interpret, and