INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL
|
|
|
- Willis Franklin Anderson
- 9 years ago
- Views:
Transcription
1 INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard Manufacturing Company Bryan, Ohio 4350 Since 94...Moving ahead, just as planned. Manual : 0-35G Supersedes: 0-35F File: Volume III Tab Date: --05 Copyright 000 Manual 0-35G Page of
2 Contents Electrical Data... 3 General... 4 System Capacity Control... 4 Bypass to Evapat Inlet with Distribut... 5 Externally Equalized Bypass Valves... 5 Head Pressure Control... ORI Valve Operation... ORD Valve Operation... 7 Adjustable ORI / ORD System Operation... 7 Refrigerant Charge... Refrigerant Piping and Flow Diagram... Troubleshooting Guide... Wiring (Typical Control Circuit Wiring)... Wiring Main Power... Figures Figure Hot Gas Bypass Valve... 4 Figure Capacity Control Piping... 5 Figure 3 Head Pressure Control Valve... Figure 4 ORD Valve... 7 Figure 5 ORI / ORD System... 7 Figure Troubleshooting Guide... 9 Figure 7 Low Voltage Wiring... Figure Hot Gas Bypass Typical Piping... Figure 9 Hot Gas Bypass Compress Burnout Procedure... Tables Table Electrical Specifications... 3 Manual 0-35G Page of
3 Manual 0-35G Page 3 of TABLE ELECTRICAL SPECIFICATIONS odels M d Rate of No. Power Circuits Circuit ingle S t Circui Dual Minimum Circuit Ampacity Maximum Fuse External Circuit Breaker Field Wire Size Ground Wire Size Minimum Circuit Ampacity Maximum External Circuit Fuse Breaker Size Wire Field Size Wire Ground A C B C C C A C B C C C A C B C C C A C B C C C WA44HA WA44HA0 WA44HB09 WA44HB /0- /0- /0-3 / / WA44HC0Z WA44HC5 WA44HF WL44HF07 WL44HF WAHA WAHA0 WAHB09 WAHB /0- /0- /0-3 / / WAHC0Z WAHC09 WAHC5 WAHF WLHF07 WLHF WA70HA WA70HA5 WA70HB09 WA70HB /0- /0- /0-3 / / WA70HC0Z WA70HC09 WA70HB Maximum size of the time delay fuse HACR type circuit breaker f protection of field wiring conducts Based on 75 copper wire
4 GENERAL The Hot Gas Bypass System design consists of two imptant modifications to the standard air conditioning unit:. system capacity control; and. head pressure control. Each of these sets of controls perfm a specific function, but both are necessary and dependent upon one another in the overall operation of the system. The system is designed f outdo operating temperature range of -0 F to 5 F. Both the head pressure control and the system capacity control are accomplished in the refrigerant cycle design and are independent of the electrical circuit. Therefe, it can be applied to all voltage, phase, KW and other variations of basic system design package air conditioners. Cycling the outdo fan to control the head pressure is not recommended f use in conjunction with this system. SYSTEM CAPACITY CONTROL The hot gas bypass valve monits the outlet pressure of the evapat and will begin to modulate open as the load on the unit decreases to the point where the evapat temperature is at the setpoint of the bypass valve. The bypass valves are facty adjusted to a setting of psig (35 F evapat temperature). This means that the compress can be operated continuously and the minimum evapat temperature will be maintained at 35 F regardless of indo outdo load conditions. Should a high evapat temperature be desired, it can be increased by turning the adjusting screw in a CW direction. The hot gas bypass valve (also called Discharge Bypass Valve, DBV) responds to changes in downstream pressure (suction pressure ) from the evapat. When the evapating pressure is above the valve setting the valve remains closed. As the suction pressure drops below the valve setting, the valve responds and begins to open. As with all modulating type valves, the amount of opening is proptional to the change in the variable being controlled - in this case the suction pressure. As the suction pressure continues to drop, the valve continues to open farther until the limit of the valve stroke is reached. See Figure. FIGURE HOT GAS BYPASS VALVE ADJUSTING SPRING DIAPHRAGM EXTERNAL EQUALIZER SET PISTON ASSEMBLY Manual 0-35G Page 4 of
5 FIGURE CAPACITY CONTROL PIPING BYPASS TO EVAPORATOR INLET WITH DISTRIBUTOR This method of application, illustrated in Figure, provides distinct advantages. The primary advantage of this method is that the system thermostatic expansion valve will respond to the increased superheat of the vap leaving the evapat and will provide the liquid required f desuperheating. Also the evapat serves as an excellent mixing chamber f the bypassed hot gas and the liquid-vap mixture from the expansion valve. This insures a dry vap reaching the compress suction. Oil return from the evapat is also improved since the velocity in the evapat is kept high by the hot gas. EXTERNALLY EQUALIZED BYPASS VALVES Since the primary function of the DBV is to maintain suction pressure, the compress suction pressure is the control pressure and must be exerted on the underside of the valve diaphragm. When the DBV is applied, as shown in Figure, where there is an appreciable pressure drop between the valve outlet and the compress suction, the externally equalized valve must be used. This is true because when the valve opens a sudden rise in pressure occurs at the valve outlet. A thermal expansion valve with external equalizer and a special refrigerant distribut to allow hot gas injection at the inlet of the evapat by feeding the side connection distribut is utilized. The expansion valve also has a rapid pressure balancing feature to allow system pressure equalization during any periods the compress may be turned off. Manual 0-35G Page 5 of
6 HEAD PRESSURE CONTROL Design of air conditioning system utilizing air cooled condensing units involves two main problems which must be solved if the system is to operate reliably and economically - High ambient and low ambient operation. If the condensing unit is properly sized, it will operate satisfactily during extremely high ambient temperatures. However, since most units will be required to operate at ambient temperatures below their design dry bulb temperature during most of the year, the solution to low ambient operation is me complex. Without good head pressure control during low ambient operation, the system can experience both running cycle and off-cycle problems. Two running cycle problems are of prime concern:. Since the pressure differential across the thermostatic expansion valve pt affects the rate of refrigerant flow, low head pressure generally caused insufficient refrigerant to be fed to the evapat.. Any system using hot gas f compress capacity control must have a nmal head pressure to operate properly. In either case, failure to have sufficient head pressure will result in low suction pressure and/ iced evapat coils. The primary off-cycle problem is the possible inability to get the system on-the-line if the refrigerant has migrated to the condenser. Insufficient flow through the TEV will cause a low suction pressure, which results in compress cycling. When low ambient conditions are encountered during operation on air cooled systems with the resultant drop in condensing pressure, head pressure control s purpose is to hold back enough of the condensed liquid refrigerant so that some of the condenser surface is rendered inactive. This reduction of active condensing surface results in a rise in condensing pressure and sufficient liquid line pressure f nmal system operation. The head pressure control valve is used in conjunction with a receiver to allow f proper head pressure control. Any system using hot gas f capacity control must have a nmal head pressure to operate properly. fce. These two fces are the operating fces of the ORI. When the outdo ambient temperature changes the ORI opens closes in response to the change in condensing pressure. An increase in inlet pressure above the valve setting tends to open the valve. If the ambient temperature drops the condenser capacity is increased and the condensing pressure drops off. This causes the ORI to start to close assume a throttling position. The head pressure control valve will begin to throttle when the condensing pressure falls below the setting of the valve. This restricts the flow of liquid from the condenser causing the refrigerant to back up into the condenser and raising the head pressure. The valve is facty set to maintain a nominal 5 psig minimum head pressure. Head pressures of higher than 5 psig will occur during any conditions of indo outdo loading that would dictate so. FIGURE 3 HEAD PRESSURE CONTROL VALVE ADJUSTING SPRING BELLOWS ORI VALVE OPERATION The ORI head pressure control valve is an inlet pressure regulating valve and responds to changes in condensing pressure only. The valve designation stands f Opens on Rise of Inlet pressure. As shown in Figure 3, the outlet pressure is exerted on the underside of the bellows and on top of the seat disc. Since the effective area of the bellows is equal to the area of the pt, the outlet pressure cancels out the inlet pressure acting on the bottom of the seat disc opposes the adjusting spring SEAT SEAT DISC Manual 0-35G Page of
7 FIGURE 4 ORD PRESSURE DIFFERENTIAL VALVE SEAT DISC SEAT ORD VALVE OPERATION The ORD valve is a pressure differential valve that responds to changes in the pressure difference across the valve. Refer to Figure 4. The valve designation stands f Open on Rise of Differential pressure. Therefe, the ORD is dependent on some other control valve action f its operation; and in this respect, it is used with the ORI head pressure control. As the ORI valve starts to throttle the flow of liquid refrigerant from the condenser, a pressure differential is created across the ORD. When the differential reaches 5 psi, the ORD starts to open and bypasses hot gas to the liquid line. As the differential increases, the ORD opens further until its full stroke is reached at a differential of psi. The hot gas flowing through the pressure differential valve heats up the cold liquid being passed by the head pressure control valve, and the liquid refrigerant reaching the receiver is warm and with sufficient pressure to assure proper expansion valve operation. ADJUSTABLE ORI / ORD SYSTEM OPERATION The adjustable ORI head pressure control valve and the nonadjustable ORD pressure differential valve comprise an improved system of head pressure control. The operation of the ORI / ORD system is such that a constant receiver pressure is maintained f nmal system operation. As shown in Figure 5, the ORI is located in the liquid line between the condenser and the receiver. The ORD is located in a hot gas line bypassing the condenser. During periods of low ambient temperature the condensing pressure falls until it approaches the setting of the ORI valve. The ORI then throttles, restricting the flow of liquid from the condenser. This causes refrigerant to back up in the condenser thus reducing the active condenser surface. This raises the condensing pressure. Since it is really receiver pressure that needs to be maintained, the bypass line with the ORD is required. FIGURE 5 ORI / ORD SYSTEM Manual 0-35G Page 7 of
8 REFRIGERANT CHARGE When refrigerant side head pressure control is utilized on a system, two additional considerations must be completely analyzed. First of all, there must be the crect amount of refrigerant to flood the condenser at the lowest expected ambient and still have enough charge in the system f proper operation. A shtage of refrigerant will cause hot gas to enter the liquid line and the expansion valve and refrigeration will cease. Too much charge doesn t cause any operating difficulties during the low ambient season; however, this will cause high head pressures during the summer season when head pressure control is not required. Secondly, the receiver must have sufficient capacity to hold all of the liquid refrigerant in the system since it will be returned to the receiver when high ambient conditions prevail. If the receiver is too small, liquid refrigerant will be held back in the condenser during the high ambient conditions and excessively high discharge pressure will be experienced. The receiver has been sized to hold the necessary amount of refrigerant required during light load conditions so the head pressure system can function properly, and also to accommodate the surplus charge that occurs under periods of nmal loading at the warmer outdo temperatures. Any erratic operating during light load conditions either inside outside could be attributed to an undercharge of refrigerant even though the unit may operate nmally at higher temperatures. Because of the complexity of the system design and operation, the only way to assure crect system charge and operating characteristics over the entire design operating range of the unit is to completely recharge the system with the total amount of R- shown on the unit serial plate after proper leak test and evacuation procedures have been followed. REFRIGERANT PIPING AND FLOW DIAGRAM Earlier in this manual, Figure reviewed the components used in System Capacity Control. Please refer to Figure 5 f complete piping diagram including System Capacity and Head Pressure Control. TROUBLESHOOTING GUIDE Troubleshooting the refrigerant system can be quite complicated because of the number of refrigerant valves in the system. There are two devices installed in the system to aid in this process:. A liquid line sight glass is located directly above the filter drier. If a solid column of refrigerant is not present during nmal operation, an undercharge defective pressure differential valve should be suspected.. A manual shutoff valve is installed in the feed line from the discharge line to the hot gas bypass valve. This valve is nmally open but can be closed down by service personnel to help in evaluating system operation should it be necessary. Please refer to Figure, Refrigerant System Troubleshooting Guide, f complete details. Manual 0-35G Page of
9 FIGURE TROUBLESHOOTING GUIDE Manual 0-35G Page 9 of
10 WIRING TYPICAL CONTROL CIRCUIT WIRING The air conditioning ption of the system is designed f continuous run type of operation f those types of installations that require cooling operation without cycling of the compress during critical periods (see earlier discussion titled System Capacity Control ). Many systems may also employ electric heaters f certain conditions that may necessitate heating rather than cooling operation. The control of the space temperature is dependent upon several variables such as basic size of the air conditioner; structure design; internal heat generation from people, lights and equipment; and external weather conditions. A generally recommended control circuit would consist of conventional heat/cool wall thermostat with an additional SPST toggle switch used to provide a manual cooling switch (continuous run type of operation). This would allow the flexibility of having the wall thermostat cycle the compress during noncritical periods, and when the manual cooling switch is thrown (closed) the compress would run all of the time. A secondary feature of this type of setup is that the manual cooling switch can be activated, and at the same time the wall thermostat can be set f heating and the thermostat adjusted to the desired temperature. This would allow the electric heater to cycle on demand to help regulate the space temperature. This type of operation may prove helpful if the basic air conditioner is way oversized there are tempary conditions when a maj ption of the heat producing equipment within the building is shut down f some reason. Shown in Figure 7 is a typical 4V connection. FIGURE 7 LOW VOLTAGE WIRING WIRING MAIN POWER Refer to the rating plate f wire sizing infmation and maximum fuse HACR type circuit breaker size. Each outdo unit is marked with a Minimum Circuit Ampacity. The Minimum Circuit Ampacity f Hot Gas Bypass models is calculated f the concurrent operation of the air conditioner and electric heaters. Many Hot Gas Bypass installations require continuous operation of the compress with a room air temperature being maintained by cycling the electric heat strips on and off. This leads to the higher than nmal Minimum Circuit Ampacity of the Hot Gas Bypass units. Since the field wiring must be sized to carry the concurrent current of both compress and electric heaters, the field wiring must be sized to carry the Minimum Circuit Ampacity current. See instruction sheet f further details. Manual 0-35G Page of
11 FIGURE HOT GAS BYPASS SYSTEM TYPICAL PIPING DIAGRAM Manual 0-35G Page of
12 FIGURE 9 HOT GAS BYPASS SYSTEM COMPRESSOR BURNOUT CLEANUP PROCEDURE Manual 0-35G Page of
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls
Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
Models: WA182, WA242. Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List... 4. Control Panel.
REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE AIR CONDITIONER Models: WA182, WA242 General Notes! Revised and/or additional pages may be issued from time to time.! A complete and current manual consists
POLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
PACKAGE AIR CONDITIONERS REPLACEMENT PARTS MANUAL
REPLACEMENT PARTS MANUAL PACKAGE AIR CONDITIONERS Models: P1142A3 P1148A1 P1148A1-B P1148A1-C P1060A1 P1060A1-B P1060A1-C P1148A1-A/H P1148A1-B/H P1148A1-C/H P1060A1-A/H P1060A1-B/H P106A1-C/H General
Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 -
Skills Canada National Competition Instructions and Competition Details / Post - Secondary May 27-30, 2015 - Saskatoon 1. Test Project Details This project is designed to test the range of skills used
HVAC-02, Air Conditioning Troubleshooting and Repair
HVAC-02, Air Conditioning Troubleshooting and Introduction Since I'm constantly receiving questions on 944 air conditioning systems, I figured it's time to come up with come helpful troubleshooting tips.
Table Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
COMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
WALL MOUNTED PACKAGE AIR CONDITIONER REPLACEMENT PARTS MANUAL W70A1 W70L1. Models: Contents. General Notes. Important. Description
REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE AIR CONDITIONER Models: W0A W0L General Notes Contents Revised and/or additional pages may be issued from time to time. A complete and current manual consists
LOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.
I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
Solenoid Valves and Their Importance in Refrigeration Systems. October 2007
Solenoid Valves and Their Importance in Refrigeration Systems October 2007 Overview Introduction Solenoid valves play an important role within refrigeration and air conditioning systems, controlling the
Automobile Air Conditioning Primer
Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
Customized Assessment Blueprint
Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC
How To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
A/C refrigerant system, overview
Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -
WALL MOUNTED PACKAGE HEAT PUMPS REPLACEMENT PARTS MANUAL WH483 WH602. Contents. General Notes. Important. Description
REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE HEAT PUMPS Models: WH421 WH483 WH602 General Notes Contents Ø Ø Revised and/or additional pages may be issued from time to time. A complete and current manual
Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
Test Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
NSN 4120-01-21 4-3692
*TM 9-4120-388-14 TECHNICAL MANUAL Operator s, Unit, Direct Support, And General Support Maintenance Manual AIR CONDITIONER, VERTICAL, COMPACT, 18,000 BTU/HR 208 VOLT, 3 PHASE, 50/60 HERTZ NSN 4120-01-21
Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400
Owners Manual Refrigerated Air Dryer HX75 thru HX2400 IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS INFORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILIAR WITH THE PROPER INSTALLATION
Holdover Plates Transport Refrigeration Systems
Holdover Plates Transport Refrigeration Systems Hercules Manufacturing Company 800 Bob Posey Street PO Box 497 Henderson, KY 42419-0497 1-800-633-3031 270-826-9501 www.herculesvanbodies.com FAX: 270-826-0439
HOW HVAC WORKS. How HVAC. Works PAGE 1
How HVAC Works PAGE 1 Heat - What is it? Heat is more than a physical concept - it is a feeling. Heat is taught to us at a very young age as a danger to be avoided. Yet, have you ever stopped and thought
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)
www.inspection-for-industry.com
Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.
NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS
INFORMATION INFORMATION ON THE TECHNOLOGY The -Frost refrigerators are different from the other static refrigerators in terms of their operational system. In normal refrigerators, in the freezing section,the
Models: Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List... 4. Control Panel. Blower Housing
REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE HEAT PUMPS Models: WH301 WH361 General Notes! Revised and/or additional pages may be issued from time to time.! A complete and current manual consists of pages
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS BULLETIN 240-10-3 June 2004 Supersedes June 1983 Many centrifugal systems get little maintenance. As a result they operate with the refrigerant highly contaminated
T-Series Air Conditioner T62 Model
INSTRUCTION MANUAL T-Series Air Conditioner T62 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
Research on the Air Conditioning Water Heater System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Automation of Commercial Refrigeration Plant
Automation of Commercial Refrigeration Plant REFRIGERATION AND AIR CONDITIONING Automation of commercial Refrigeration Plant The purpose of this manual is to show some examples of the use of Danfoss automatic
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
How To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
How Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
AIR CONDITIONING TECHNOLOGY
AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air
COMPRESSOR REPLACEMENT PROCEDURE
R-22 and R-410A COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003F Supersedes 2100-003E File: Volume I,
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction
ALCO s series of Thermo -Expansion Valves are designed for air conditioning, chillers, rooftops, close control, A/C transportation, heat pumps, industrial cooling process and refrigeration applications.
CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!
CPX/HT Series REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM High-performance products. Designed for you! COMPRESSED AIR WATER CONTAMINATION Atmospheric air contains water in vapor form in different
Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet
Thermostatic expansion valves type REFRIGERATION AND AIR CONDITIONING Technical leaflet Thermostatic expansion valves, type Contents Page Introduction........................................................................................3
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29
Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 A refrigerant retrofit project, involving the conversion of a large Data Room cooling system from R22 to R422D (DuPont
T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200
INSTRUCTION MANUAL FOR: T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleanthermal.com INSTRUCTION MANUAL TABLE OF CONTENTS
Air Conditioning 101. STN Presentation AC101
Air Conditioning 101 What is Refrigeration? Refrigeration is Cooling by the Removal of Heat Heat is Measured In BTU s A BTU is a British Thermal Unit It is the Amount of Heat to Raise One Pound of Water,
STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE
Page 1 of 9 PURPOSE Steam is the most commonly used heating medium for maintaining process temperatures. Compared to other heating media, steam contains a significant amount of heat energy, and this heat
ENERGY RETROFIT PROGRAM
ENERGY RETROFIT PROGRAM An innovative but simple retrofit for existing hot water and chilled water piping systems that will help you save money. REDUCE FLOW BY 50% REDUCE PUMP HEAD BY 75% REDUCE PUMP POWER
Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
Refrigeration System Installation & Operation Manual
Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
Thermostatic valve Type AVTA
MAKING MODERN LIVING POSSIBLE Data sheet Thermostatic valve Type AVTA Thermostatic valves are used for proportional regulation of flow quantity, depending on the setting and the sensor temperature. The
Compressors, Chillers & Condensers
Chillers & Condensers SUCTION CUTOFF UNLOADING VS HOT GAS BYPASS UNLOADING Suction Cutoff Unloading Head Hot Bypass Unloading Head Suction cutoff unloading is a more efficient unloading method for the
High kw Electric Tankless Water Heater Troubleshooting Guide
Technical Service Bulletin High kw Electric Tankless Water Heater Troubleshooting Guide Models: WH17, WH27, WH36 AE115, AE125, (FD108 and higher) DANGER: ELECTRIC SHOCK ELECTRICITY IS EXTREMELY DANGEROUS.
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
REGULATORS 175/153 Series
175/153 Series 175 HEATING 153 COOLING Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2002 Watson McDaniel Company Revised 7/2002 175 / 153 Screwed
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS 1. Define an accumulator and explain its function A hydraulic accumulator is a device that stores the potential energy of an incompressible fluid
PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS
NOR-LAKE, INCORPORATED 727 Second Street P.O. Box 248 Hudson, Wisconsin 54016 800-955-5253 715-386-2323 866-961-5253 Parts 800-388-5253 Service 715-386-4291 FAX www.norlake.com Split-Pak Pre-Assembled
High School Graduation years 2013, 2014, 2015. Unit/Standard Number
1 Secondary Task List 100 INTRODUCTION TO HVAC 101 Identify HVAC systems. 102 Describe career opportunities in the HVAC profession. 103 Demonstrate awareness of the occupational requirements. 104 Explain
Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange
Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange ING. TOMMASO FERRARESE Thermodynamics Laboratory Engineer
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
Central Air Conditioning Plants
Central Air Conditioning Plants In our department, these plants (Air cooled or water cooled) are commonly available above 10 TR up to 100 TR. These types of plants are more suitable for large installations
T-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177
T-SERIES Air Conditioners T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177 88043249 TABLE OF CONTENTS RECEIVING THE AIR CONDITIONER...3 HANDLING AND
Condensing unit type EPSILON-ECHOS LE Technical information manual
Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps
ON-VEHICLE INSPECTION
Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI
Fully Pumped Systems
Fully Pumped Systems (also see the picture gallery and System Basics) The term for any boiler that uses a pump to move all the heat from the boiler to every part of the system is fully pumped. As a rule
System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes
System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Faults on refrigeration systems, general...3 Fault location without the use of instruments...3 Categorisation...3
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams
Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose
AFE424 SERVICE PARTS
This is the parts list for the AFE. When looking up part numbers, always check the complete model and serial numbers to be certain of ordering the correct parts. The Air Cooled model has also been manufactured
Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify
Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2
Heating Water by Direct Steam Injection
Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space
Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet
Perkins Statewide Articulation Agreement Documentation item: Secondary Task List Coversheet The Secondary School agrees to: A. Implement the approved PDE Program(s) of Study. B. Provide assessment of student
REGULATING VALVE APPLICATIONS
REGULATING APPLICATIONS GENERAL REGULAR APPLICATION & INSTALLATION NOTES Regulator Application & Installation Notes The following are considerations for all steam regulator installations, as system operation
MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump
MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................
MP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER
INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-360B Supersedes: 2100-360A File: Volume
Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL Service Information If service or parts are required, contact the nearest Norcold Service Center. To find an authorized Norcold Service Center
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from
