Lower Energy Costs with Rooftop Air-Conditioning Package Units
|
|
|
- Amber Mosley
- 10 years ago
- Views:
Transcription
1 Lower Energy Costs with Rooftop Air-Conditioning Package Units Sponsored by Mike West, PhD, PE Advantek Consulting, Inc
2 Package Unit Efficiency Factors Sensible and latent performance ratings Unit efficiency ratings (IPLV, SEER, or EER) Fan motor drive and efficiency rating Fan is 10 to 20% of unit power draw [kw] Fan is 20% to 50% of unit energy usage [kwh] Number of stages / capacity control Geographical location / climate Likelihood of maintenance Total life-cycle installed and operating costs including options
3 EER Rating Specification
4 Efficiency Ratings EER Energy Efficiency Ratio MBH per kw SEER Seasonal EER MBTU per kwh IPLV Integrated Part-load Value MBH per kw Energy Star light commercial HVAC equipment uses 7 10% less energy than standard equipment. Energy Star package units can save $3 to $4 per square foot over the life of the equipment. For example, a 12,000 square foot building using an ENERGY STAR qualified HVAC product, could save $36,000 to $48,000 over 15 years, more than enough to justify the upgrade cost.
5 Energy Star efficiency rating Units rated at 65,000 to 135,000 Btuh 11.0 EER or higher -and IPLV or higher Units rated at 135,000 to 250,000 Btuh 10.8 EER or higher -and IPLV or higher Three-phase equipment rated below 65,000 Btuh SEER 13.0 or higher Air conditioner EER ratings are measured at outdoor temperature of 95 F, indoor 80ºF db 67ºF WB or 50% Relative Humidity. IPLV takes into account the higher efficiency of air conditioning units at part load. IPLV is measured using ARI Standard weightings and provides more of an apples to apples comparison than EER alone. SEER was intended to rate efficiency over an entire cooling season, not a single outdoor temperature. In theory, SEER is calculated by total amount of cooling (Btu) over the entire season divided by the total Watt-hours it will consume. SEER is used only for units 5-tons and less.
6 SEER ratings In some cases manufacturer s simply rate SEER as x EER at 82 F outdoor (instead of ARI 95 F) The SEER of a system is determined by multiplying the steady state energy efficiency ratio (EER) measured at conditions of 82 F outdoor temperature, 80 F db and 67 F wb indoor entering air temperature by the Part Load Factor (PLF) of the system. (The PLF is supplied by the government.) The PLF is a measure of the cyclic performance (CD) of a system and is calculated as follows, where CD is Cyclical Data: PLF = (CD x 0.5) "The cyclic performance (CD) value in the above equation has been determined by the government to be 0.25." The government contends that the PLF should equal: (.25 x.5) = 0.875, which yields: PLF of 0.875
7 Rating Specifications
8 Savings Estimates / Quick Need estimated annual operating hours, cost of electricity. MBH unit size = Tons x 12 EER 1 = rating of standard efficiency unit EER 2 = rating of high efficiency Energy Star unit Hours = annual operating hours ~ 1.3 x CDD Rate = $ cost of electricity, demand and tax per kwh MBH EER 1 MBH EER 2 Savings = ( - ) x Hours x Rate
9 Capacity selection Avoid Oversizing Performance Ratings are at steady-state Larger units costs more & use more power Example: compare power of 2 units at full load 15 ton: 15.7 kw 17½ ton: 18.9 kw added cost of $1500 Added electric demand of 3.2 kw ~ $400 per year Documented sizing calculations should be performed using accepted ACCA or ASHRAE procedures. ACCA methods have sufficient built-in safety factors. Use ASHRAE design conditions. Don t exaggerate outdoor design temperatures by using the AHR 95 F test point, or an unrealistically low indoor space condition such as 70 or 72 F.
10 Load-calc Lessons Learned Perform an accurate hourly load calculation Use the correct project location weather data 1. Peak Sensible Load 2. Maximum Latent Load 3. Lowest SHR Reasonably estimate infiltration airflow ACH Or, if an hourly load calc is not feasible, calculate the cooling load at three design conditions: ASHRAE Fundamentals 2003 Chapter 27, Miami 0.4% F.2005 Chapter 28 data available on CD-ROM 1. Cooling: 91db / 78wb / 125 grains 2. Dehumidification: 83db / 79 wb / 145 grains 3. Latent-Part-Load: 75db / 72 wb / 116 grains
11 Equipment Specification Tips Use manufacturer s performance software or tables to determine actual unit capacity (don t use nominal) Select the model closest in capacity to the load Specify that TAB shall include supply air CFM, fan RPM, External SP, and EAT LAT OA CFM must meet ASHRAE 62, provide exhaust makeup, and pressurize the building 0.02 to 0.04 in.wg [5 to 10 Pa] Request prices - be able to support and defend your equipment specification with hard economics.
12 The importance of carefully selecting the design airflow The SHR of a DX package unit will try to follow it s capacity curve to match the SHR of the space load. Load SHR drops as the space humidity drops, yet equipment SHR increases as entering wet bulb drops. If airflow is too low, temperature may rise and energy is wasted. If airflow is too high, humidity may be excessive at times. Higher airflow increases fan kw, but cooling capacity also increases, so EER usually goes up at the higher fan speeds. However, too high a fan speed means the latent load will not be met at times and fan energy use will be excessive.
13 Air Delivery Considerations Air leakage and heat gain from ducts significantly reduce air-conditioning system efficiency. The insulation level of traditional ducting is typically only R-4 to R-6 (1.5 to 2.2 inches). Specify R-8 (2¾ to 3 inches) Larger ducts typically mean lower static pressure, less leakage and higher system efficiency, if well insulated. With no attention, duct leakage rates can be 10% to 15% of total system airflow, sometimes higher. Specify ASHRAE Leakage Class-3 on the design drawings Test and Balance the Unit and Duct System
14 Test and Balance Package Units are not Plug-and-Play Engineering observation of startup is a must. Set fan speed and airflow according to design engineers specifications. Verify rotation direction of fan. Check and adjust refrigerant charge according to manufacturer s procedure. Adjust and calibrate fresh air damper and linkage to obtain design amounts of fresh air. Properly install high-efficiency filters.
15 Commissioning Example: Motorized Fresh-air damper with Economizer
16 Commissioning Some problems can be identified in the design phase: sizing, supply and outside airflows, controls Most problems can be identified at the project site: 1. Leak-test curb and ducts under pressure 2. Calibrate thermostats and sensors 3. Check ceiling diffusers for short-circuits 4. Functional performance test in all modes 5. Operations and maintenance training 6. Checkup visits at 30 and 90 days
17 Equipment Selection Factory Equipment Options Select evaporative condenser option wherever available Motorized fresh-air damper with Economizer Dehumidification enhancements needed below SHR ~ 0.65 Face and bypass damper, heat pipes, liquid reheat, hot gas reheat Filter pressure drop sensor so filter losses remain low BACNET Communications interface Avoid High Static Drive Use static regain duct design, and VFD or staged air-volume with SP or LAT control DCV - Demand Controlled Ventilation based on return air CO 2 Field Installed LPA liquid pressure amplification for low ambient conditions EER-Plus desuperheater / subcooler for the adventurous Auxiliary Condenser - increased heat rejection is a plus
18 Stages and Capacity Control This unit has 1- compressor, thus 1 refrigerant circuit Single scroll compressor Digital Scroll TM provides variable capacity control
19 Stages and Capacity Control This unit has 2 compressors, but only 1 refrigerant circuit 1 2
20 Stages and Capacity Control This unit has 4 compressors and 4 refrigerant circuits, but only 2 control stages. Modification to 4 stages is simple
21 Model Selection This unit has a Thermostatic Expansion Valve (TXV) Evaporator coil TXV
22 Evaporative Condenser Wet condenser coil uses evaporative cooling like a cooling tower, except refrigerant flows inside copper tubes. Less condenser fan HP Energy savings are typically 20% - 30%, up to 40% in dry climates Highly climate dependent Near-peak versus off-peak operating hours and MC wet-bulb temperatures wb 10 to 30 degrees cooler than db Integrated water treatment system, chemical and/or ozone Stainless steel, copper, PVC, FRP Desuperheater coils not wetted
23 Evaporative Condenser - AAON
24 Savings Estimates / Calculator
25 Savings Estimates / Calculator Range is still 8.9 to 13.5 Estimate based on location and type Billed rate including kw demand and tax
26 Savings Estimates / Calculator Annual Hours of Operation to 900 hours to 1400 hours to 2000 hours to 2800 hours to 4000 hours
27 Savings Estimates / Calculator Hours of Operation = 1.3 x CDD
28 Savings Estimates / Calculator $ $3200 = $994 savings per year Cost of 10-ton high efficiency (EER 13.5) unit: $7,000 Cost of a standard (EER 10.3) typical unit: $5,000 Upgrade cost for a high-efficiency unit: $7,000 - $5,000 = $2,000 Payback period = $2,000 / $994 = 2 years to recover higher price Return on investment = $994 / $2000 = 49% every year for life of equipment
29 Savings Estimates / Calculator Lifetime savings for 5 units: $82,370 in today s dollars (15 years) assuming a 4.1% annual increase in electricity Cost of 5 units: 5 x $7,000 = $35,000 Benefit / Cost Ratio = 83,370 / 35,000 = 2.4
30 Market Availability ENERGY STAR Partner List Results Look for Product Manufacturers in a different Country and State: New Search Refine Search Results 1-7 of 7 All Countries All States All # A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Name Product Type Location Award Category (Year) Carrier Central ACs and Air-Source Heat Connecticut Corporation Pumps, Furnaces, Geothermal Heat Pumps, Light Commercial HVAC, Programmable Thermostats, Room Air Conditioners Daikin U.S. Light Commercial HVAC New York Corporation Goodman Manufacturing Company, L.P. Lennox Industries Incorporated Rheem-Ruud Manufacturing Central ACs and Air-Source Heat Pumps, Furnaces, Light Commercial HVAC, Room Air Conditioners Central ACs and Air-Source Heat Pumps, Furnaces, Light Commercial HVAC, Programmable Thermostats Central ACs and Air-Source Heat Pumps, Furnaces, Light Commercial HVAC, Programmable Thermostats Texas Texas Arkansas Trane Company Light Commercial HVAC Tennessee York International Central ACs and Air-Source Heat Oklahoma Corp. UPG Pumps, Furnaces, Light Commercial HVAC Go Excellence in Efficient Products(2003,2004,2005,2007) 1. Carrier 2. Daikin 3. Goodman 4. Lennox 5. Rheem-Ruud 6. Trane 7. York
31 Market Availability Carrier Centurion EER , SEER , to 5-tons Centurion EER , IPLV , 6 to 25-tons WeatherMaster EER 11.8 to 25-tons Goodman SEER 13 to 5-tons EER 11.5 to 7.5-tons Lennox Strategos EER , IPLV , to 20-tons L-Series EER 12.2 to 30-tons T-Class EER 11.0 to 25-tons S-Class EER 10.8 to 50-tons Trane Precedent SEER 15 to 5-tons, EER 11.5 to 10-tons Voyager Hi-E EER to 25-tons York Affinity SEER to 5-tons Predator EER 11.5 to 12½-tons
32 Savings Example / Quick MBH unit size = 20-Tons x 12 = 240 MBH EER 1 = rating of Lennox T-Class = 10.8 EER 2 = rating of Lennox Strategos = 12.6 Hours = annual operating hours ~ 1.3 x CDD = 3000 Rate = cost of electricity = $0.12 per kwh billed MBH EER 1 MBH EER 2 Savings = ( - ) x Hours x Rate Savings = ( - ) x 3000 x 0.12 $1,143 per year savings
33 Design-in Maintainability Numerous energy surveys clearly show that lack of preventative maintenance is by far the major cause of air conditioning performance degradation. Common and costly problems include: clogged, corroded cooling and condenser coils sizeable duct leaks and cabinet air leaks low refrigerant, even in brand-new units maladjusted or stuck air dampers un-calibrated or nonfunctioning controls or sensors Design for Easy Access Provide Manuals and Training
34 Model Selection Likelihood of maintenance is important. VS.
35 Model Selection filter compartment access door Ease of Maintenance Fiberglass pre-filters MERV-11 final filters Filter rack was specified to fit 2-inch pre-filters and 2-inch final filters. Angled position of top filters improves flow.
36 Refrigerant Charge Both Over- and Under-charging are common Even a 5% adjustment is worthwhile the air conditioning system can be performing below its capacity because of poor maintenance and maintain comfort while energy use increases. I don t see anyone really checking charge right, most technicians only do a touch method. I have even found 8 ounces overcharge on brand new units. [total charge is 5 to 8 pounds]
37 Preventative maintenance program critical to realizing rated performance for the life of the unit.
38 Lower Energy Costs with Rooftop Air-Conditioning Package Units Thank you! Mike West, PhD, PE Advantek Consulting Engineering, Inc.
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
HVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
Get the FACTS about SEER and Deliver Better Customer Value
What is SEER? SEER stands for Seasonal Energy Efficiency Ratio. It s a number that describes how well air-conditioning equipment works. A higher SEER means better efficiency and lower energy bills. SEER
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
How To Buy A Lennox Power System
HVAC for Schools A Comprehensive Look at Products for a Clean, Comfortable Learning Environment Why Schools Choose Lennox Even as resources for schools continue to be constrained, education leaders and
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons
Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Air-Conditioning Buying Guide
Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Air Conditioning Contractors of America
Air Conditioning Contractors of America WHO IS ACCA???? Industry Manuals Residential D, J, S, H, RS, T, P A manual J load calculation is a measurement of how much heating and cooling capacity a home will
air conditioners how to choose a cooling system
air conditioners how to choose a cooling system taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home and a reduced
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
Massachusetts COOL SMART. RESIDENTIAL CENTRAL AC/DUCTED AIR SOURCE HEAT PUMP Rebate Application
Massachusetts COOL SMART 2015 RESIDENTIAL CENTRAL AC/DUCTED AIR SOURCE HEAT PUMP Rebate Application COOL SMART CENTRAL AC/HP PROGRAM COOL SMART is a residential central air conditioning rebate program
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE <[email protected]
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE
Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water
2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
Energy Efficient Homes: Air Conditioning 1
FCS3262 Energy Efficient Homes: Air Conditioning 1 Wendell A. Porter, Hyun-Jeong Lee, and Kathleen C. Ruppert 2 Quick Facts Heating, ventilation and air conditioning accounts for more than 40% of your
Preventive Maintenance Strategies and Technologies Can Pave the Path for Next Generation Rooftop HVAC systems
Preventive Maintenance Strategies and Technologies Can Pave the Path for Next Generation Rooftop HVAC systems Ramin Faramarzi, P.E. Technology Test Centers October 14, 2014 Overview 1. Why is HVAC maintenance
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models. Up to 17.0 SEER, Up to 12.8 EER
Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models Up to 17.0 SEER, Up to 12.8 EER SAVING ENERGY WITH INTELLIGENCE Designed to intelligently achieve the lowest total cost of ownership Energence
Mechanical Rooftop Custom Capabilities
Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition
Certified HVAC Audit Report Key Takeaways and Implications. Created for: Pets On the Go 445 Logging Road, Building 3 Yardley, PA-19034
Certified HVAC Audit Report Key Takeaways and Implications Created for: Pets On the Go 44 Logging Road, Building 3 Yardley, PA-9034 May, 0 Executive Summary Proposal Generator Demo aims to reduce your
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
Strategy Guideline: HVAC Equipment Sizing
Strategy Guideline: HVAC Equipment Sizing Arlan Burdick IBACOS, Inc. February 2012 This report received minimal editorial review at NREL NOTICE This report was prepared as an account of work sponsored
A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
TWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
Packaged Gas/Electric Rooftop Units
Packaged Gas/Electric Rooftop Units Precedent 3-10 Tons 60 Hz October 2004 Introduction Packaged Rooftop Air Conditioners Through the years, Trane has designed and developed the most complete line of Packaged
HSX19 Air Conditioner Up to 19.20 SEER. Home Comfort Systems HSX19. The most quiet and efficient central air conditioner you can buy.
HSX19 Air Conditioner Up to 19.20 SEER Home Comfort Systems HSX19 The most quiet and efficient central air conditioner you can buy.* Dave Lennox Signature Collection HSX19 Air Conditioner Lennox makes
DOAS UNITS. www.reznorhvac.com MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR. Kitchens Hotel Corridors Laboratories. Paint Booths. Capacities Tons MBH
MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR Kitchens Hotel Corridors Laboratories Conference CENTERS Schools Paint Booths Malls/Shopping Centers DOAS UNITS Capacities 5-35 Tons 50-800 MBH 30-120 kw 650-9,000
Introduction. Motor Types
QwikSEER+ Theory of Operation and Retrofit Potential Mainstream Engineering Corporation Rockledge, FL 32955 http://www.qwik.com/products/qwikseer/index.jsp Prepared by Robert P. Scaringe and R. Paul Roth
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment. Partner Commitments.
ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment Partner Commitments Commitment The following are the terms of the ENERGY STAR Partnership
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Dehumidification Design
Dehumidification Design Using Data-Center Heat Utilizing free heat from a server room was the concept behind an air-handling system in a college-campus building Considerable energy savings are possible
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)
Energy Efficient Homes: Air Conditioning
Energy Efficient Homes: Air Conditioning Quick Facts The average energy bill for a typical single family home in the U.S. is $2,200. Roughly 46 percent of the bill, or $1,012, is spent on heating, ventilation,
Laboratory Performance Testing of Residential Window Mounted Air Conditioners
Laboratory Performance Testing of Residential Window Mounted Air Conditioners Jon Winkler Chuck Booten Dane Christensen Jeff Tomerlin April 29, 2012 NREL is a national laboratory of the U.S. Department
Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers
COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
AND SIMPLE HVAC SYSTEMS
The City of New York Mayor Michael R. Bloomberg NYC Buildings Robert D. LiMandri, Commissioner BUILDING HVAC (1) REQUIREMENTS MANDATORY REQUIREMENTS AND SIMPLE HVAC SYSTEMS CHAPTER 5 COMMERCIAL ENERGY
Packaged Cooling with Electric Heat Rooftop Units
Packaged Cooling with Electric Heat Rooftop Units Voyager 12½ - 25 Tons - 60 Hz December 2003 RT-PRC002-EN Introduction Voyager TM... a proven performer built to provide ultimate indoor comfort. Voyager
ARMSTRONG AIR HEAT PUMPS www.armstrongair.com
INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7
newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer
engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
Todd M. Rossi, Ph.D. President
Residential Air Conditioning Fault Detection and Diagnostics (FDD) and Protocols to Support Efficient Operation DOE - Building America Program Residential Buildings Integration Meeting - July 20-22, 2010
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start
Ground Source Heat Pumps The Fundamentals. Southington, Connecticut 860 628 4622 John F. Sima III P.E.
Ground Source Heat Pumps The Fundamentals Southington, Connecticut 860 628 4622 John F. Sima III P.E. Winter/Spring 2010 Ground Source Heat Pumps The Fundamentals TOPICS: Heat Pump Terminology Basic Physics
48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT
48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED
Commercial Packaged Rooftop Units. Designed to achieve the lowest lifecycle cost. *
L Series Packaged Rooftop Unit Up To 13.25 SEER, 12.2 EER and 14.7 IPLV L Series Commercial Packaged Rooftop Units LG/LC/LH Models Designed to achieve the lowest lifecycle cost. * Maximum performance to
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Pool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
1/15/2013. HVAC Maintenance Repair or Replace & Planned Replace Initiative. Reduce Operating Costs. Improve Comfort / Process Conditions
HVAC Maintenance Repair or Replace & Planned Replace Initiative Greg DuChane, Retail Vertical Market, Director, TRANE Jack Rehder, Western Territory Manager, TRANE Why Maintain Rooftop Units? Reduce Operating
Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects
Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony
The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity
Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. AFFORDABLE SOLUTIONS FROM AMERISTAR. We know that heating and cooling systems can be a major investment for homeowners. Our goal is