TAC I/NET. Installation Guide. Seven. Process Control Unit TCON /10. for TAC I/NET Building Automation Systems

Size: px
Start display at page:

Download "TAC I/NET. Installation Guide. Seven. Process Control Unit TCON127. 09/10. for TAC I/NET Building Automation Systems"

Transcription

1 vi TAC I/NET Seven Installation Guide Process Control Unit 5 for TAC I/NET Building Automation Systems TCON. 0/0

2 We at Schneider Electric have tried to make the information contained in this manual as accurate and reliable as possible. Nevertheless, Schneider Electric disclaims any warranty of any kind, whether express or implied, as to any matter whatsoever relating to this manual, including without limitation the merchantability or fitness for any particular purpose. Information in this document is based on specifications determined at the time of publication. As we introduce design enhancements, we reserve the right to make changes in specifications and models without obligation to notify the purchaser. In no event shall Schneider Electric be liable for any indirect, special, incidental, or consequential damages arising out of purchase or use of this manual or the information contained herein. The software described in this document is furnished under a license agreement or nondisclosure agreement. The software may be used or copied only in accordance with the terms of the agreement. It is against the law to copy Schneider Electric s TAC I/NET System software onto magnetic tape, disk, or any other medium for any purpose other than the purchaser's personal use. Printed in the United States of America. Document Number: Copyright 00 Schneider Electric. All rights reserved. On October st, 00, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric; however, there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes.

3 Contents FCC Warning vi Overview Input/Output Communication Reset Physical Description PCBs and Baseplates Power Supply Input/Output Terminals Input Terminations Output Terminations Communication Ports Serial Communication Port LAN Communication Port Memory Static RAM Memory Exhaustion Warning Battery Backup Universal Enclosure RS Serial Expansion Module Installation Procedures Initial Installation Procedures Grounding Requirements Earth Ground Baseplate Ground LAN Ground Setting the 5 PCU Address Setting the Tap Emulation Setting the Tap Baud Rate Setting the Controller LAN Baud Rate Setting the Power Line Frequency Schneider Electric. All rights reserved. iii

4 Contents 5 Installation Guide Setting the Maximum Pulse Input Rate Installing the Input Field Connections V Sensor Connection V Sensor Connection Milliampere Sensor Connection Connecting Discrete Input Points Installing Supervised Field Inputs Connecting Thermistor Inputs Connecting Lini-Temp Inputs Variable Voltage Selection Resistor Installation Installing the Output Field Connections Form-C Relay (Universal) Output Connection Analog Output Connection Voltage-Sourcing Triac Output Connection Connecting the HHC Connecting the LAN Connecting an External PC Connecting the Modem Installing the Optional RS Serial Interface Board Connecting the Power Supply Field Hardware Checkout and Addressing Connecting the HHC Cold Starting the 5 PCU Check Signal Voltages Check Analog Inputs Checkout Discrete Inputs Checkout Discrete Outputs Set Up and Operation Hardware Inputs Lookup Tables Selecting Input Type Control Outputs Upper Motherboard Outputs Lower I/O Board Outputs Analog Output Points Triac Output Points iv 00 Schneider Electric. All rights reserved.

5 5 Installation Guide Contents Manual Override Communication Ports LEDs RS Port HHC Port RS85 LAN Port Protocol LAN Node Address Data Rate Serial Expansion Module RS Serial Expansion Module Function Tap Emulation and Modem Setup Emulation and Beeper Calls Tap Emulation and Pager Operation Modem Switch Settings Auto Dial/Auto Answer Integrated Dial Point Address Summary Outputs Inputs HOA Switch Status Resistor Configurations Troubleshooting Pinout Chart Upper Motherboard Lower I/O Board RS Expansion Module Internal RS Specifications Index Schneider Electric. All rights reserved. v

6 FCC Warning 5 Installation Guide FCC Warning FCC Warning The Federal Communications Commission (FCC) requirements prescribe certification of personal computers and any interconnected peripherals in the FCC rules and regulations. This device complies with Part 5 of the FCC rules. Operation is subject to the following two conditions: this device may not cause harmful interference, and this device must accept any interference received, including interference that may cause undesired operation. This equipment generates and uses radio frequency (rf) energy for its operation and, if not installed and used in accordance with the installation and operation manual, may cause interference to radio and television reception. It has been found to comply with the limits for a Class A computing device pursuant to the aforementioned regulations. These are designed to provide reasonable protection against such interference when operated in a residential area. Only peripherals (computer input/output devices) certified to comply with the Class A limits may be connected to this device. Operation with noncertified computer peripherals is likely to result in interference with radio and television reception. If this equipment does cause interference to radio or television reception, the user is encouraged to correct the situation by one or more of the following measures. Relocate the receiver with respect to the computer. Move the computer away from the receiver. Plug the equipment into a different outlet, so that the computing device and receiver are on different branch circuits. Disconnect and remove any unused cables that may be acting as a transmission source. Make certain that the computing device is plugged into a grounded outlet receptacle. If necessary, contact Schneider Electric for additional suggestions. vi 00 Schneider Electric. All rights reserved.

7 5 5 Installation Guide Overview Overview Input/Output The Model 5 Process Control Unit (PCU) from TAC is a combination of a highspeed, fully distributed microprocessor-based motherboard and a high-resolution I/O board which together provide full adaptive Direct Digital Control (DDC), energy management, and process control of up to 5 addressable I/O points. The 5 PCU is designed to connect directly to a controller LAN and works in conjunction with all other controllers and workstations on the TAC I/NET system. Processing, memory management, communication, and field input/output functions are provided on two printed circuit boards mounted in a double-layer stack. The upper motherboard provides the processing, memory, and communication support for the unit as well as a collection of I/O points. The lower I/O board provides an additional 0 I/O connections, conditioning, and analog signal processing with microprocessor management provided from the upper motherboard. The controller features all quick-disconnect terminals, downloadable firmware, onboard modem drivers, and a direct-connect RS port. The controller is further enhanced with extensive transient protection and automatic self-test features. The 5 PCU comes with the capability of supervising and controlling up to 5 addressable external points and internal points. The I/O configuration flexibility provided by the controller allows it to be interfaced with a variety of industry standard I/O devices. The 5 PCU supports the hardware I/Os listed in Table. Table. 5 PCU Hardware I/Os Upper Motherboard Lower I/O Board 8 universal inputs 8 universal relay outputs universal inputs 8 universal triac outputs 8 analog outputs Universal inputs can be defined as: analog inputs discrete inputs pulse inputs 00 Schneider Electric. All rights reserved.

8 Overview 5 Installation Guide Communication The 5 PCU provides up to four communication ports on the upper motherboard. A standard synchronous RS85 controller LAN port. Two asynchronous serial ports. These ports provide access to external PCs, external modems, and the Model HC0 hand-held console (HHC). The first asynchronous port provides an RS port for direct connection to a PC, or external Direct Distance Dial (Hayes compatible) modem. The RS port s baud rate is set using a TAC HC0. When connected directly to a PC, the 5 performs the functions of a TAC 80 Tap without consuming a second LAN address. When connected to a Hayes-compatible modem, the Integrated Dial function (i.e. one-way dial from the host PC to the controller LAN) is provided. The second asynchronous port provides a modular TTL-level interface to an HC0 and operates at 00 BPS. An optional plug-on board providing an RS serial port that can be used to connect an external synchronous or asynchronous modem or one of several communication multiplexing devices. (Refer to RS Serial Expansion Module on page 8.) Reset Upon power loss/restoration, the 5 PCU executes an automatic reset memory test of RAM and EPROM. The test uses a Checksum check, and, if the check is successful, control and execution is passed to programmed memory. A manual reset that is started by pressing the reset button executes the same tests. 00 Schneider Electric. All rights reserved.

9 5 Installation Guide Physical Description Physical Description PCBs and Baseplates The 5 PCU is comprised of two printed circuit boards mounted on a double-layer metal baseplate. The I/O board is mounted on the lower layer, while the motherboard is mounted on the top layer. The top layer is hinged such that easy access is provided to the lower interface. The baseplate provides keyhole mounting for easy installation within a TAC universal enclosure. All I/O connections to the 5 PCU are accomplished via plug-on terminal blocks. Power Supply The upper motherboard (see Figure ) measures approximately 8.5" W " H (.. cm); the baseplate measures approximately 8." W " H (.8. cm). A hinge allows the upper baseplate to swing downward, thus providing access to the lower I/O board. The lower I/O board (see Figure ) measures approximately 8.5" W 0" H (. 5. cm); the baseplate measures approximately." W " H (.. cm). The lower baseplate provides keyholes required for mounting the 5 unit within a TAC universal enclosure. Sensor input wiring to the upper interface board can be bundled and routed along the edge of the hinged upper baseplate to allow access to the lower I/O board without disconnecting the upper motherboard terminations. A cutout in the hinged upper baseplate provides user access to the HOA override switches on the lower I/O board. The lower I/O board connects to the upper motherboard through a 0-conductor ribbon cable. Electrical input power connections for the 5 PCU are provided along the lower left side of the lower I/O board. The 5 PCU is powered from a dual VAC source (external transformer). The AC input provides power to five on-board supplies. A switching power supply circuit is used to generate the +5 VDC logic power. Four linear power supplies are used to generate +5 VDC internal, +5 VDC External, 5 VDC and + VDC. The supply voltages are used for analog signal processing and RS communication. The separate +5 VDC (external) regulator is provided for supplying current loop excitation power to avoid loss of communication due to a field sensor wiring problem. Power line frequency selection (50/0 Hz) is available through an HHC connected directly to the Schneider Electric. All rights reserved.

10 Physical Description 5 Installation Guide lower baseplate width." (. cm) 8.5" (. cm) TB TB " (. cm) " (.8cm) RS85 port signal inputs TB signal inputs TB resistors resistors U U P U U LEDs reset button manual override switches TB signal outputs P RJ hand held console port TB power input serial option port I/O expansion port RS port modem or external PC P P 8." (.8 cm) Input/Output Terminals Figure. Upper Motherboard and Baseplate The 5 PCU s input and output terminals are located in different areas of both the upper motherboard and the lower I/O board. The inputs and outputs do not use the same number of terminals to make up a terminal set. See Figure for the upper motherboard terminal locations. See Figure for the lower I/O board terminal locations. Input Terminations Both the upper motherboard and lower I/O board provide universal inputs for the 5 PCU. The upper motherboard provides 8 universal inputs. The lower I/O board provides additional universal inputs. All universal inputs are user-configurable for 0 5 VDC, 0 0 VDC, 0 0 ma, or discrete/pulse contact input. Additionally, the lower I/O board universal inputs can be configured for fast scan of pulse input (0 Hz) points. 00 Schneider Electric. All rights reserved.

11 5 Installation Guide Physical Description.0" (.0 cm).00" (.8 cm) TBB TBA TB U U U5 U TBB TBA.00" (. cm).00" (.8 cm) TBB TBA Analog Type Selection Resistors TB 0" (5. cm) 0-Pin Ribbon Cable Connector TB P TB5A TB5B HOA Switches 8.50" (.0 cm) Figure. Lower I/O Board and Baseplate Signal inputs to the upper motherboard are provided along the upper left side of the board in two groups of four inputs (TB and TB). Three screw terminations are provided for each input (Signal, Ground and +5/ V). The inputs (analog, discrete, or pulse) use point addresses Jumper settings on the upper motherboard allow selection of variable voltages for contact excitation and input pull-up levels. Signal inputs to the lower I/O board are provided along the left side of the board in three groups of eight inputs. Each group provides two tiers of terminal blocks: TBA through TBA on the lower tiers, TBB through TBB on the upper tiers. The inputs (analog, discrete, or pulse) use point address (TBA/B), (TBA/B), and (TBA/B). Output Terminations Output terminations for the 5 PCU are provided along the right side of both the upper motherboard and the lower I/O board. Discrete (Form-C relay) outputs are provided on the upper motherboard. The lower I/O board provides two output types: analog and discrete voltage-sourcing triac. Universal output terminations along the upper right side of the upper motherboard are arranged in two groups of four outputs, with a single -pin plug-on terminal block for each group (TB and TB). Each output consists of a Form-C relay contact capable of 00 Schneider Electric. All rights reserved. 5

12 Physical Description 5 Installation Guide Communication Ports Serial Communication Port handling 0.5 amp (derated from amps) at volts AC/DC. Each output provides discrete control of a field contact or a proportional control via pulse-width-modulation of the output contact. The outputs use point addresses Output terminations for the lower I/O board are arranged in two groups: analog outputs along the upper right side (TB) and triac outputs below the analog outputs (TB). A single -pin plug-on terminal block is provided for each group. The analog output terminal block (TB) provides 8 high-resolution, -bit analog output points. Each output provides a 0 0 volt span and is capable of handling up to 5 ma. The eight analog outputs use point addresses The triac output terminal block (TB) provides 8 voltage-sourcing triac outputs which are user-configured as discrete latching, momentary contacts, or pulse-width-modulated (PWM) proportional outputs. Each output is capable of switching up to 0.5 amps at VAC. A manual override switch (HOA switch) is provided for each triac output as well as discrete input feedback of the switch status. Each HOA switch allows the individual output to be placed in Manual-On, Manual-Off, or Automatic mode. An LED indicator is provided adjacent to each HOA switch and will illuminate when the individual triac output is energized. The eight voltage-sourcing triac outputs use point addresses There are three communication ports on the upper motherboard and an optional communication board that can be added as a plug-on daughterboard. All connections to the LAN, modems, external PCs and the HHC are made using these ports. See Figure for port locations. The two asynchronous serial ports (on the upper motherboard) provide access to external PCs, external modems, and the HC0. Modem and PC Connection HHC Connection LAN Communication Port The first asynchronous port (P) provides an RS port for direct connection to a PC or external direct dial (Hayes) modem. The RS port s baud rate is set using the HHC. The second asynchronous port (P) provides a modular interface to the standard HC0 HHC and operates at 00 BPS. An RJ modular jack is provided along the lower left side of the upper motherboard for connection of the HHC. The LAN communication port (TB) is located along the lower left side of the upper motherboard. A terminal block provides connection of the RS85 shielded, twisted pair on the standard controller LAN. The normal speed of communication on the controller LAN is,00 baud. The controller LAN speed can be lowered to 00 baud using the HHC in order to accommodate lower grade cable installations. 00 Schneider Electric. All rights reserved.

13 5 Installation Guide Physical Description Memory The 5 PCU upper motherboard provides support for several types of memory with variable amounts of each. The memory is currently organized as follows: Table. 5 Memory Socket Amount Memory Type U KB EPROM (Stores boot firmware) U, U and U KB Static RAM The upper motherboard also provides 5 bytes of serial nonvolatile RAM (NOVRAM) memory storage. This memory is used to hold all parameters necessary to establish basic communication with the controller after a long-term power outage (i.e., loss of RAM memory). The software can be downloaded while the 5 is on-line with TAC I/NET. The software design and memory organization supports the complete download of all software, including revised LAN drivers that are invoked after completion of the download. The downloaded software is held in RAM. When the 5 is emulating a 80 Tap, it can store telephone numbers as a standard 80 Tap would. At least eight 5-digit telephone numbers can be stored in memory. Static RAM The 5 PCU provides a minimum of KB of battery-backed static RAM for software data storage and embedded 80, 805 and 80 Tap functions such as message queue, dial telephone numbers, and async/sync communication buffers. Memory Exhaustion Warning Battery Backup The PCU editors provide a warning message when the user adds a point or function that could exceed the available PCU memory. The 5 provides battery-backup of static RAM contents and of the clock/calendar. The onboard NiCad rechargeable battery provides backup for up to 0 days during a power failure. Note: The backup battery must be fully charged in order to provide the full span of backup power. Due to normal discharge during product storage and shipment, the battery may not be fully charged immediately following installation and power-up. You must allow the controller to operate continuously for a minimum of seven days (8 hours) before depending on battery backup. 00 Schneider Electric. All rights reserved.

14 Physical Description 5 Installation Guide Universal Enclosure TAC s universal enclosures provide a protected environment in locations in which dirt, dust, or other contaminants may exist. TAC universal enclosures are available in several sizes and capacities designed to house various combinations of TAC control units and interfaces. The model used for the 5 PCU is the ENCL8, measuring.5" W 8.5" H." D (.. 0. cm). The universal enclosure allows back panel mounting, providing additional space for optional equipment such as transformers and electrical junction boxes. The enclosure includes a door key lock. The 5 PCU boards are shipped already mounted on a double-layer baseplate. That baseplate/pcb assembly is then mounted into the universal enclosure. If the perforated backplane is used to mount the baseplate, then the size of the baseplate and the enclosure are the limiting factors for enclosure mounting. Baseplates vary in dimension depending upon the type of controller. All controllers or interface units are attached to a baseplate for mounting in a universal enclosure. Table. Universal Enclosure Dimensions Model Panel Dimensions Standard Door Mounting Baseplate Qty Perforated Panel Backplane Dimension W H D W H Panel Backplane w/studs Door Key Lock ENCL8 with Knockouts and Gasketed Door.5" (. cm) 8.5" (. cm)." (0. cm) None.5" (.5 cm).5" (. cm) (#8 hardware Optional Panel mounting Mount one (max.) TAC baseplate unit Options: Transformer Junction box Yes RS Serial Expansion Module The RS Serial Expansion Module provides a fourth serial interface. It provides a full complement of modem control, data, and clock signals on an RS port. It provides two-way dial or dedicated line communication as currently supplied by TAC s 80 or 805 Tap. This interface supports user-selected data rates up to,00 baud. This optional interface can be connected to: External auto-dial/auto-answer (AD/AA) modem When connected to a Hayescompatible AD/AA modem, the 5 will provide the functionality of the 80 Tap. The following types of modems are supported: Synchronous Use a synchronous modem when the controller is loaded with a TAC I/NET version.x or earlier binary file. The controller must also have TAC I/NET version.x boot firmware (EPROM). Asynchronous Use an asynchronous modem when the controller is loaded with a TAC I/NET 000 or later binary file. The controller must also have TAC I/NET 000 or later boot firmware (EPROM) Schneider Electric. All rights reserved.

15 5 Installation Guide Physical Description Note: Ensure that all AD/AA Taps within your TAC I/NET system are configured to use the same communication protocol either synchronous, or asynchronous. Mixing AD/AA protocols will cause communication errors. TAC I/NET 000 is compatible with TAC I/NET version.x Tap and controller binary loads. Therefore, when synchronous AD/AA communication is required on a TAC I/NET 000 system (for example, when using a 800, 8050, or 800 Tap), you must continue to use TAC I/NET version.x Tap and controller binary loads. External synchronous dedicated line modem When connected to an external Hayes-compatible dedicated line modem, the 5 provides the functionality of a TAC 805 Tap. Refer to TCON0, TAC I/NET Tap and Repeater Installation Guide, for a complete description the 805 Tap function. Another RS data communication device. 00 Schneider Electric. All rights reserved.

16 Installation Procedures 5 Installation Guide Installation Procedures This section provides instructions for installing the 5 PCU. Field checkout procedures using an HHC are also included in this section. Note: Operational errors may occur if equipment is inadequately grounded. Symptoms may include, but are not limited to: intermittent LAN communication, improper control actions, or loss of NOVRAM contents. Refer to Grounding Requirements on page during equipment installation. Initial Installation Procedures Use the following steps to install the 5 controller. This procedure allows you to set up the 5 with the proper DCU address, perform a field checkout on the hardware, and set Tap emulation, baud rate and controller LAN baud rate.. Disconnect power to the 5 PCU.. Disconnect power to all devices that will be connected to the 5 PCU. Warning: Failure to disconnect power from all interconnected equipment when performing electrical installation may result in electrical shock or burns.. Mount universal enclosure on a wall.. Bring conduit into box (conduit contains power, sensor cables, etc.). 5. Attach the double-layer metal baseplate (and its attached PCBs) into the universal enclosure box (keyhole mount).. If using the optional RS serial expansion module, install the module on the 5 upper motherboard at port P.. Terminate wires at PCBs. Refer to Installing the Input Field Connections on page and Installing the Output Field Connections on page. 8. Connect the modem or external PC.. Connect the power supply to the 5. Remember to set the power line frequency (50/0 Hz) using Setting the Power Line Frequency on page. 0. Reconnect power to devices that are connected to the 5 PCU.. Perform field checkout. (Refer to Field Hardware Checkout and Addressing on page.) 0 00 Schneider Electric. All rights reserved.

17 5 Installation Guide Installation Procedures Grounding Requirements Earth Ground To ensure proper operation of the controller, it is imperative that the unit be correctly grounded. Depending on the mounting location and mounting method used to install the unit, the controller chassis may not necessarily provide adequate ground for the input power circuit and interconnected sensors/devices: therefore, use the following grounding requirements during unit installation. Note: You must establish a proper earth ground connection point prior to connecting ground wires to electrical equipment. Baseplate Ground Electrical Service Earth Ground must be securely connected to the equipment chassis. The Electrical Service Earth Ground must then be connected to the ground terminal on the controller power input terminal block (TB5A pin ). Note: Baseplate grounding requirements apply to all controllers having a baseplate. Good contact must exist between the baseplate and chassis. Ensure that all mounting screws are tight. Attach a -AWG (. mm ) ground wire from the Electrical Service Earth Ground to the baseplate. Attach the ground wire to the baseplate grounding post in the lower right corner. LAN Ground Note: This procedure applies to all LAN controller connections. Shield drain wire continuity must be maintained as the LAN cable passes through each controller. Shield drain wires from each controller LAN cable must be bonded together, insulated, and tied back such that wires do not come in contact with ground or any conductive surface within a controller. Connect the shield drain wire directly to Electrical Service Earth Ground at only one end of the cable. Setting the 5 PCU Address. Connect the Model HC0 HHC and set the 5 s LAN address. Press [DCU ADDR]. The current 5 address displays in the two right-most digits of the HHC display.. Enter the desired address using the numeric keys. The address displays as it is entered.. Press [Enter]. The 5 NOVRAM is updated with the new address. 00 Schneider Electric. All rights reserved.

18 Installation Procedures 5 Installation Guide Setting the Tap Emulation. Press [Code].. Press 0 and then press [Enter]. The emulated device type model number displays in the read out.. Press [Inc] or [Dec] to select 80, 805 or 80 Tap emulation. Refer to Table for Tap emulation as it appears on the HHC. Table. HC0 Tap Emulation Selection Tap Model HC0 Display No Tap Emulation Press [Enter] to accept your choice. Setting the Tap Baud Rate. Press [Code]. Setting the Controller LAN Baud Rate Setting the Power Line Frequency. Enter and then press [Enter] to set the Tap baud rate.. Press [Inc] or [Dec] to cycle through the available PC port baud rates, typically 00.. Press [Enter] to accept your choice.. Press [Code].. Enter and then press [Enter] to set the controller LAN baud rate.. Press [Inc] or [Dec] to toggle between 00 baud and.k baud rates.. Press [Enter] to accept your choice.. Press [Code].. Enter and then press [Enter] to select the AC line frequency.. Press [Inc] or [Dec] to switch between 50 and 0 Hz.. Press [Enter] to accept your choice. 5. Connect the 5 to the LAN.. Program the PCU from the host PC. Refer to the TAC I/NET Operator Guide for instructions. 00 Schneider Electric. All rights reserved.

19 5 Installation Guide Installation Procedures Setting the Maximum Pulse Input Rate Installing the Input Field Connections. Press [Code].. Enter 0, press [Enter] to display the current rate, and press [Enter].. Enter 0 to set for a pulse rate of per second.. Enter to set for a pulse rate of 0 per second. 5. Press [Enter] to accept your selection. The 5 supports several types of inputs, each using different field connections. Use the procedures shown below to connect the sensors you use to the 5. The illustrations and procedures describe connection to the upper motherboard and to the lower I/O board. Warning: Caution: Note: Ensure that no power is connected to the 5 and all interconnected equipment when performing the following procedures. Failure to disconnect power from the 5 and all interconnected equipment when performing electrical installation may result in damage to the components and electrical shock or burns. The input, output and power wiring must be routed along the side of the controller. The wiring is not to lay across the controller. When field wiring the upper motherboard, wires should be bundled and routed up along the edge of the upper baseplate, and a service loop in the wiring should be provided in the area of the upper baseplate hinge. Proper wire routing will permit access to the lower I/O board without disconnection of the upper motherboard termination blocks. 0 0 V Sensor Connection Refer to Resistor Installation on page 8, to determine the correct resistor configuration for your inputs. A 0 0 V sensor uses three leads to connect to an input. The upper motherboard provides eight inputs with excitation voltages selectable between +5 volts DC and + volts DC. The lower I/O board provides support for an additional twenty-four 0 0 volt inputs with a fixed excitation voltage of + volts DC. Refer to Resistor Installation on page 8 for resistor configuration. Connection is identical for the upper motherboard and the lower I/O board.. Connect the out lead of the 0 0 V sensor to a signal (UI-x) terminal on TB or TB on the upper motherboard or on TBA/B, TBA/B or TBA/B on the lower I/O board.. Connect the negative lead of the sensor to the GND terminal.. Connect the +V lead of the sensor to the +V terminal (see Figure ). Note: Sensors requiring more than 0 ma should be wired to an external power supply. 00 Schneider Electric. All rights reserved.

20 Installation Procedures 5 Installation Guide 0 0V Sensor Signal Out GND +V In TB C Sensor connected at TB-: 00K ohm, /8 W, % resistor in C (on upper board). Strap J to +5V or +V as required (on upper board). 0 5 V Sensor Connection Figure. 0 0 Volt Sensor Connections. If connecting to the upper motherboard, install a 00K Ohm, 8 W, % resistor in the corresponding resistor C position. If connecting to the lower I/O board, no resistor is required. 5. If connecting to the upper motherboard, ensure that the variable voltage selection is set on J of the upper motherboard to the appropriate voltage (refer to Variable Voltage Selection on page 8). A 0 5 V sensor uses three leads to connect to an expansion board input. The upper motherboard provides eight inputs with excitation voltages selectable between +5 volts DC and + volts DC. The lower I/O board provides support for an additional twentyfour 0 5 volt inputs with a fixed excitation voltage of + volts DC. Refer to Resistor Installation on page 8 for resistor configuration. Connection is identical for the upper motherboard and the lower I/O board.. Connect the out lead of the 0 5 V sensor to a signal (UI-x) terminal on TB or TB on the upper motherboard or on TBA/B, TBA/B or TBA/B on the lower I/O board.. Connect the negative lead of the sensor to the GND terminal.. Connect the +V lead of the sensor to the +V terminal (see Figure ). Note: Sensors requiring more than 0 ma should be wired to an external power supply. 0 5V Sensor Signal Out GND +V In TB Sensor connected at TB-: Strap J to +5V or +V as required (on upper board). Figure. 0 5 Volt Sensor Connections. If connecting to the upper motherboard, ensure that the variable voltage selection is set on J of the upper motherboard to the appropriate voltage (refer to Variable Voltage Selection on page 8). 00 Schneider Electric. All rights reserved.

21 5 Installation Guide Installation Procedures 0 0 Milliampere Sensor Connection 0 0 milliampere sensors can be connected as shown in Figure 5. The upper motherboard provides eight inputs with excitation voltages selectable between +5 volts DC and + volts DC. The lower I/O board provides additional inputs for up to twenty-four 0 ma loops with a fixed excitation voltage of + volts DC. Refer to Resistor Installation on page 8 for resistor configuration. See Figure on page 0 for resistor installation.. Connect the output lead from the sensor to a SIGNAL terminal on TB or TB on the upper motherboard or on TBA/B, TBA/B or TBA/B on the lower I/O board.. Connect the output lead of the sensor to the +V terminal of the input set. 0 0mA, 0mA Sensor In Out (+) ( ) 0 0mA, 0mA In Out Sensor (+) ( ) Input Power External Power Supply + Output TB/TB A A Sensor connected at TB-: ohm, /8 W, 0.% resistor in A Sensor connected at TB-: ohm, /8 W, 0.% resistor in A Note: Use external power supply if more than eight (combined, upper and lower board) 0 0 or 0 ma sensors are used. Connecting Discrete Input Points Figure ma Sensor Connections. If connecting to the upper motherboard, ensure that the variable voltage selection is set on J of the upper motherboard to the appropriate voltage (refer to Variable Voltage Selection on page 8). For contact sensing on the upper motherboard or lower I/O board, either DI or PI, the excitation current for the field contact is achieved by placing a K ohm, W, 5% resistor in the appropriately numbered B position. The B position provides a pull-up on the input to 5 volts DC for dry contact excitation.. Connect one lead from the field contact to the signal (UI-x) terminal on TB or TB on the upper motherboard or on TBA/B, TBA/B or TBA/B on the lower I/O board.. Connect the other lead of the sensor to the GND terminal (see Figure ).. Install a K Ohm, W, 5% resistor in the corresponding resistor B position. Dry Contact For DI or PI Note: Contact closed = logical st or nd of state description pair. TB B Dry Contact connected at TB-: K ohm, / W, 5% resistor in B Figure. Dry Contact Connections 00 Schneider Electric. All rights reserved. 5

22 Installation Procedures 5 Installation Guide Installing Supervised Field Inputs Configure the field inputs for supervision in the resident I/O points editor of the host. You may supervise a single switch or contact in a normally-closed or normally-open configuration, or you may supervise multiple normally open switches or contacts connected in parallel. The contact/switch may be normally-open or normally-closed (see Figure and Figure 8). Single resistor supervision with a parallel resistor. Configuration is the same for normally closed switch/contact. Entire circuit is supervised for line cuts ( open wire) Double resistor supervision with a parallel and a series resistor. Entire circuit is supervised for line cuts ( open wire) K K K Parallel Resistor Parallel Resistor Series Resistor Normally Open Switch/Contact Figure. Supervised Single Switches/Contacts Portion of circuit is supervised for jumpers ( shorts in wiring) Normally Closed Switch/Contact Note: The components shown inside the dashed boxes should be in close physical proximity. Multiple switches or contacts connected to a supervised input (see Figure 8) must consist of normally-open switches or contacts wired in parallel. Single resistor supervision with a parallel resistor. Entire circuit is supervised for line cuts ( open wire) Double resistor supervision with a parallel and a series resistor. Entire circuit is supervised for line cuts ( open wire) Parallel Resistor Parallel Resistor Note: The components shown in the dashed box should be in close physical proximity. Figure 8. Supervised Multiple Switches/Contacts Series Resistor Portion of circuit is supervised for jumpers ( shorts in wiring) 00 Schneider Electric. All rights reserved.

23 5 Installation Guide Installation Procedures Connecting Thermistor Inputs The inputs on the lower I/O board are shipped in a thermistor input configuration with a 0K ohm, 8 W, 0.% resistor in the B position for each input.. Connect one lead from the thermistor to the signal (UI-x) terminal on TBA/B, TBA/B or TBA/B on the lower I/O board.. Connect the other lead of the sensor to the GND terminal (see Figure ). 0K Ohm Thermistor TBA Signal Ground VDC TBB B 0K Ohm Thermister at TBA-: 0K ohm, /8 W, 0.% resistor in B. Figure. Thermistor Connections on Lower I/O Board Note: For units containing upper motherboard assembly 05-0 Revision F or later, the upper motherboard may also use the 0K ohm thermistor. The connection method is the same as that described above for the lower I/O board. Connecting Lini-Temp Inputs Note: The lower I/O board should not be used for Lini-Temp sensor inputs. Only the upper motherboard allows selection of the +5 volts DC excitation voltage required for Lini-Temp sensors. The lower I/O board provides a fixed + volts DC excitation voltage. Signal inputs are provided along the upper left side of the upper motherboard in two groups of four inputs. Three screw terminations are provided for each input (Signal, Ground and +5/V) as shown in Figure 0. The LTS80 temperature sensors can be connected in a -wire or -wire configuration as shown in Figure 0. Refer to Resistor Installation on page 8 for resistor configuration. The -wire configuration does not require any resistor configuration. See Figure on page 0 for resistor installation.. Connect the white lead to a signal (UI-x) terminal on TB or TB on the upper motherboard.. Connect the orange lead to one of the +5 V terminals of terminal blocks TB or TB on the upper motherboard.. For -wire sensors, connect the blue lead to the GND terminal (see Figure 0).. When using a -wire sensor configuration, place a 0K, 8 W, 0.% resistor in the corresponding resistor A position. 5. Ensure that the variable voltage selection is set on J of the upper motherboard to +5 V (refer to Variable Voltage Selection on page 8). 00 Schneider Electric. All rights reserved.

24 Installation Procedures 5 Installation Guide WHT LTS Sensor ORN Typical -wire Sensor connection LTS Sensor Typical -wire Sensor connection WHT BLU ORN Signal +5 V Signal Ground +5 V TB A -Wire Connection: 0K ohm, /8 W, 0.% resistor in A. Strap J to 5V. -Wire Connection: No resistor required. Strap J to 5V. Variable Voltage Selection Figure 0. Lini-Temp Input Sensor Connections (Upper Motherboard) You may select either +5 or + volt DC power provided by the upper motherboard to a connected sensor by positioning a jumper on J (see Figure ). To achieve +5 volts, position the jumper on posts B and C. Position the jumper on posts A and B to achieve + volts. Refer to Table 5 for details. Table 5. Upper Motherboard Variable Voltage Selection Jumper Setting Result J B to C A to B +5 volts DC excitation on terminal blocks + volts DC excitation on terminal blocks Resistor Installation The eight inputs on the upper motherboard are shipped in a 0 0 ma configuration. The 0 0 ma configuration is achieved by placing ohm 0.% resistors in the appropriate plug-in position for each input. These positions are labeled A through A8, A corresponding to input UI- and A8 to UI-8. Table. Resistor Configurations Location Function Resistor Upper Motherboard ( bit A/D converter) 0 5 volts None 0 0 volts 00K ohm, 8 W, % in position C 0 0 ma ohm, 8 W, 0.% in position A, remove any resistor in position B Thermistor 0K ohm, 8 W, 0.% in position B Note: Thermistor may be used only on upper board assembly 05-0 Revision F or later. Discrete K ohm, 8 W, 5% in position B Low-speed pulse input (PI) K ohm, 8 W, 5% in position B Discrete Supervised Lini-Temp (-wire configuration only) K ohm, 8 W, 5% in position B and end-of-line resistor(s) (K ohm, W, %) 0K ohm, 8 W, 0.% in position A 8 00 Schneider Electric. All rights reserved.

25 5 Installation Guide Installation Procedures Lower I/O Board ( bit A/D converter) Note: Table. Resistor Configurations (Continued) Location Function Resistor 0 5 volts None (see note) 0 0 volts None 0 0 ma 0 0 ma Thermistor Discrete Low-speed pulse input (PI) High-speed pulse input ohm, 8 W, 0.% in position A, remove any resistor in position B (see note) ohm, 8 W, 0.% in position A, remove any resistor in position B 0K ohm, 8 W, 0.% in position B K ohm, 8 W, 5% in position B K ohm, 8 W, 5% in position B K ohm, 8 W, 5% in positions B and D K ohm, 8 W, 5% in position B and end-of-line Discrete Supervised resistor(s) (K ohm, W, %) Using 0 5 VDC or 0 0 ma inputs on the lower I/O board of the 5 PCU only uses half of the available A/D counts (0, counts rather than 0 5,55 counts). Keep this in mind when calculating conversion coefficients. The inputs on the lower I/O board are shipped in a thermistor configuration. The thermistor configuration is achieved by placing 0K ohm 0.% resistors in the appropriate plug-in position for each input. These positions are labeled B through B; B corresponding to input UI- and B corresponding to input UI-. The A positions provide a pull-down to DC ground on the input signal for analog input current sensing. The B positions provide a pull-up on the input to 5 volts DC. On the upper motherboard, the 5 volt source is suitable for the excitation of discrete contacts. On the lower I/O board, the 5 volt source is provided by a precision reference and is suitable for exciting thermistors as well as discrete contacts. The C positions allow you to configure the upper motherboard for 0- to 0-volt inputs. The lower I/O board accepts 0 0 V as a standard configuration (no resistor required). The D positions are used only on the lower I/O board to reduce input filtering to allow high-speed pulse input (up to 0 Hz) processing. Position D is not used on upper motherboard. In order to configure an input for 0 0 ma, insert a ohm 8 W, 0.% current sensing resistor in the corresponding resistor position (A through A8 or A through A). The position numbers (A A8) correspond to the inputs through 8 on the upper motherboard (see Figure ). The position numbers A A correspond to the inputs through on the lower I/O board (see Figure ). For -wire Lini-Temp, install a 0K Ohm 8 W, 0.% resistor in an A position. For 0 0 V on the upper motherboard, install a 00K Ohm, 8 W, % resistor in a C position. For 0 0 V on the lower I/O board, no resistor is required. Dry contact inputs (DI or PI) require a K Ohm, 8 W, 5% resistor in a B position. To configure an input for 0 0 ma, insert a ohm 8 W, 0.% current sensing resistor in the corresponding resistor A position. Remove any resistor in the corresponding B position for 0 0 ma or 0 0 ma inputs. Figure shows connection examples for -wire Lini-Temp, 0 0 V, 0 0 ma, and dry contact inputs. For high-speed processing of pulse inputs on the lower I/O board, install a K Ohm, 8 W, 5% resistor in a D position. See Figure for details of installation. 00 Schneider Electric. All rights reserved.

26 Installation Procedures 5 Installation Guide TB TB UI- GND +V UI- GND +V UI- GND +V UI- GND +V UI-5 GND +V UI- GND +V UI- GND +V UI-8 GND +V A A A A B B B B A5 A A A8 B5 B B B8 C C C C D D D D C5 C C C8 D5 D D D8 TBA UI- UI- 5 UI- 8 0 UI- UI- UI-0 UI- UI- UI- UI-8 UI- UI-0 TBA TBA TBB A B C D UI-5 5 UI- 8 UI- 0 UI-8 TBB A B C D UI- 5 UI- 8 UI-5 0 UI- TBB A B C D UI- 5 UI- 8 UI- 0 UI Upper Motherboard Lower I/O Board Figure. Input Configuration Resistors A A A A B B B B C C C C 0K, / 8W, 0.% For -Wire Lini-Temp, Part Number 00-00, W, 0.% For 0-0 ma Input, Part Number / 8 K, / W, 5% For Dry Contact Input (DI or PI) Part Number K, /8 W, % For 0-0V Input on Upper Motherboard Part Number Figure. Resistor Installation on Upper Motherboard 0 00 Schneider Electric. All rights reserved.

27 5 Installation Guide Installation Procedures A B C D 0 K, /8 W, 0.% For Thermistor on lower I/O board Part Number For 0Hz (high speed) pulse input on lower I/O board Part Number K,/8 W, 5% Required for low or high speed pulse inputs on lower I/O board K, /8 W, 5% resistor Figure. Resistor Installation on Lower I/O Board Installing the Output Field Connections Form-C Relay (Universal) Output Connection Form-C relay (universal) output terminations are provided along the upper right side of the upper motherboard (see Figure ). Each output consists of a Form-C relay contact capable of handling 0.5 amp at volts AC/DC. Each output provides discrete control of a field contactor or a proportional control via pulse-width-modulation (PWM) of the output contact. Analog output terminations are provided along the upper right side of the lower I/O board (see Figure 5). The eight high-resolution, -bit analog output points provide a 0- to 0-volt span and can each drive up to 5 ma. Discrete triac output terminations are also provided along the right side of the lower I/O board (see Figure ). Each discrete output consists of a voltage-sourcing ( VAC) triac contact capable of handling 0.5 amperes at volts AC. Each output provides discrete control of a field contactor or a proportional control via PWM of the output contact. When connecting a device to the upper motherboard universal output, first determine whether the device is normally open (NO) or normally closed (NC). Connect one wire to the middle terminal of the set (numbered through 8) and one wire to the terminal designated NO or NC (see Figure ).. Connect one lead from the device to the desired NO or NC terminal.. Connect the other lead to the corresponding Common terminal on the upper motherboard. 00 Schneider Electric. All rights reserved.

28 Installation Procedures 5 Installation Guide TB TB NC 8 NO NC NO NC NO NC 5 NO NC NO NC NO NC NO NC NO Note: When possible, ground the common side of the VAC source. Normally Closed Common Normally Open VAC Source MOV VAC Relay Coil Analog Output Connection Figure. Output Terminal Locations on Upper Motherboard When connecting an analog device to the lower I/O board, connect one lead to the signal output (AO-x) terminal and the other lead to the GND terminal (see Figure 5).. Connect the positive control lead from the device to the desired AO-x voltage output terminal.. Connect the negative control lead to the GND terminal(s) on the expansion module. TB Ground 0 0 V Control Actuator + Typical Voltage-Sourcing Triac Output Connection Figure 5. Analog Output Location on Lower I/O Board When connecting a discrete device to the lower I/O board triac output, connect one lead to the signal output (DO-x) terminal ( through 8) and the other lead to ground (see Figure ).. Connect one lead from the device to the desired DO-x terminal.. Repeat as required for additional connections. 00 Schneider Electric. All rights reserved.

viii TAC I/NET Seven Installation Guide Process Control Unit for TAC I/NET Building Automation Systems TCON106. 09/10

viii TAC I/NET Seven Installation Guide Process Control Unit for TAC I/NET Building Automation Systems TCON106. 09/10 viii TAC I/NET Seven Installation Guide Process Control Unit 7718 for TAC I/NET Building Automation Systems TCON106. 09/10 We at Schneider Electric have tried to make the information contained in this

More information

TAC I/NETTM. Process Control Unit

TAC I/NETTM. Process Control Unit TAC I/NETTM 7756 Process Control Unit TAC s 7756 Process Control Unit (PCU), part of the TAC I/NETTM family of products, provides direct control and monitoring of process functions from a Peer-to-Peer

More information

TAC I/NET. Installation Guide. Seven. LAN Interface Unit 7790A TCON109. 09/10. for TAC I/NET Building Automation Systems

TAC I/NET. Installation Guide. Seven. LAN Interface Unit 7790A TCON109. 09/10. for TAC I/NET Building Automation Systems vi TAC I/NET Seven Installation Guide LAN Interface Unit 7790A for TAC I/NET Building Automation Systems TCON109. 09/10 We at Schneider Electric have tried to make the information contained in this manual

More information

TAC I/NETTM MR-AHU-HP. Application Specific Controller

TAC I/NETTM MR-AHU-HP. Application Specific Controller TAC I/NETTM MR-AHU-HP Both the MR-AHU and MR-HP controllers are application specific controllers (ASCs). The intention of the design is to reduce total install cost through pre-engineered control algorithms

More information

Troubleshooting and Diagnostics

Troubleshooting and Diagnostics Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only

More information

EQUIPMENT SPECIFICATIONS

EQUIPMENT SPECIFICATIONS EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access

More information

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to

More information

Operation and Installation Manual

Operation and Installation Manual Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control

More information

EMBEDDED ACCESS CONTROL Hardware Installation Guide

EMBEDDED ACCESS CONTROL Hardware Installation Guide EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

M68EVB908QL4 Development Board for Motorola MC68HC908QL4

M68EVB908QL4 Development Board for Motorola MC68HC908QL4 M68EVB908QL4 Development Board for Motorola MC68HC908QL4! Axiom Manufacturing 2813 Industrial Lane Garland, TX 75041 Email: Sales@axman.com Web: http://www.axman.com! CONTENTS CAUTIONARY NOTES...3 TERMINOLOGY...3

More information

110244-003. PrintPAD CN3/4/3e/4e. User Guide

110244-003. PrintPAD CN3/4/3e/4e. User Guide 110244-003 PrintPAD CN3/4/3e/4e User Guide TABLE OF CONTENTS PrintPAD CN3/4 & PrintPAD CN3e/4e Printer Views...1 Open View...1 Closed View...1 Using Batteries: General Guidelines...1 Installing and/or

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

UniPi technical documentation REV 1.1

UniPi technical documentation REV 1.1 technical documentation REV 1.1 Contents Overview... 2 Description... 3 GPIO port map... 4 Power Requirements... 5 Connecting Raspberry Pi to UniPi... 5 Building blocks... 5 Relays... 5 Digital Inputs...

More information

BroadBand PowerShield. User Manual

BroadBand PowerShield. User Manual BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

CONSOLE REMOTE I /O AC 9V

CONSOLE REMOTE I /O AC 9V CONSOLE CONSOLE REMOTE I /O AC 9V AC 9V REMOTE I /O User Manual CE-220 Read this guide thoroughly and follow the installation and operation procedures carefully in order to prevent any damage to the units

More information

ELK-MM443. Magic Module Automation Controller

ELK-MM443. Magic Module Automation Controller ELK-MM443 Magic Module Automation Controller Features Re-Programmable Logic Controller Four (4) supervised inputs with analog or digital sensing. Four (4) dry contact SPDT relay outputs. Two relay outputs

More information

Web Site: www.parallax.com Forums: forums.parallax.com Sales: sales@parallax.com Technical: support@parallax.com

Web Site: www.parallax.com Forums: forums.parallax.com Sales: sales@parallax.com Technical: support@parallax.com Web Site: www.parallax.com Forums: forums.parallax.com Sales: sales@parallax.com Technical: support@parallax.com Office: (916) 624-8333 Fax: (916) 624-8003 Sales: (888) 512-1024 Tech Support: (888) 997-8267

More information

Applied Electronics. Commercial Dimming System UPDATE NOTICE

Applied Electronics. Commercial Dimming System UPDATE NOTICE REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with

More information

BACnet Automation Interface Module (Network Version)

BACnet Automation Interface Module (Network Version) Sense +V Tx Rx LAN LINK Over ARCNET KBaud BACnet Rx BACnet Tx Archive Valid Port S Tx Port S Rx Low Battery Network- Enhanced Access Default MSTP PTP = Download Required on Rnet and Port S IP Address IP

More information

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation. This quick start guide provides, basic installation information, drawings, first time power-on instructions, and short descriptions of key terms and concepts for installing the EntraGuard Platinum Telephone

More information

EDI Distributor Control Interface Wiring and Setup Instructions

EDI Distributor Control Interface Wiring and Setup Instructions Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls

More information

SYSTEM 4C. C R H Electronics Design

SYSTEM 4C. C R H Electronics Design SYSTEM 4C C R H Electronics Design SYSTEM 4C All in one modular 4 axis CNC drive board By C R Harding Specifications Main PCB & Input PCB Available with up to 4 Axis X, Y, Z, A outputs. Independent 25

More information

InnoMedia ESBC 9580-4B. Quick Install Guide. www.innomedia.com 1

InnoMedia ESBC 9580-4B. Quick Install Guide. www.innomedia.com 1 InnoMedia ESBC 9580-4B Quick Install Guide www.innomedia.com 1 Table of Contents Introduction 2 Package Contents 2 CAUTION 2 Installation 3 Wall-Mounting Instructions 5 Troubleshooting 6 Appendix A. LED

More information

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 TABLE OF CONTENTS DESCRIPTION 2 MOUNTING INSTRUCTIONS 2 HOW TO CABLE THE IPX 2/3 POWER SUPPLY INSTALLATION 3 OPERATION 3 CARE

More information

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01 ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

AXIS 291 1U Video Server Rack Installation Guide

AXIS 291 1U Video Server Rack Installation Guide AXIS 291 1U Video Server Rack Installation Guide About This Document This document describes how to install Axis blade video servers in the AXIS 291 1U Video Server Rack. Updated versions of this document

More information

HDMI Switch USER MANUAL VS481A

HDMI Switch USER MANUAL VS481A HDMI Switch USER MANUAL VS481A FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed

More information

UniStream CPU-for-Panel

UniStream CPU-for-Panel UniStream CPU-for-Panel Installation Guide USC-P-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic

More information

USER MANUAL. Model 6103 3U ForeFront Alarm Card SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007. An ISO-9001 Certified Company

USER MANUAL. Model 6103 3U ForeFront Alarm Card SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007. An ISO-9001 Certified Company USER MANUAL Model 6103 3U ForeFront Alarm Card An ISO-9001 Certified Company Part# 07M6103 Doc# 123011U Rev. A Revised 7/15/03 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007 CONTENTS 1.0

More information

AXIS T81B22 DC 30W Midspan

AXIS T81B22 DC 30W Midspan INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial

More information

2100 POS System. 2100 User Guide

2100 POS System. 2100 User Guide 2100 POS System 2100 User Guide Thank you for selecting UTC RETAIL s innovative Model 2100 Point of Sale solution! This guide is designed to acquaint you with the features and functionality of the 2100

More information

OPLC Installation Guide

OPLC Installation Guide Samba OPLC SM43-J-T20/ SM35-J-T20 OPLC Installation Guide 12 Digital Inputs, include 1 HSC/Shaft-encoder Input, 2 Analog inputs (only when the digital inputs are set to pnp), 8 Relay Outputs 12 Digital

More information

8-Port HDMI Switch USER MANUAL VS0801H

8-Port HDMI Switch USER MANUAL VS0801H 8-Port HDMI Switch USER MANUAL VS0801H FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits

More information

HDMI Matrix Switch USER MANUAL VM0404H

HDMI Matrix Switch USER MANUAL VM0404H HDMI Matrix Switch USER MANUAL VM0404H FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits

More information

PowerLogic Sub Meter Display (SMD and SMDOPN)

PowerLogic Sub Meter Display (SMD and SMDOPN) Instruction Bulletin Z203742-0B PowerLogic Sub Display (SMD and SMDOPN) CONTENTS Introduction... 2 Parts of the Sub Display... 3 Dimensional Drawing... 4 Installation... 5 Mounting the SMD... 5 Mounting

More information

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire) FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control

More information

ABB Drives. User s Manual HTL Encoder Interface FEN-31

ABB Drives. User s Manual HTL Encoder Interface FEN-31 ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions

More information

Programming Logic controllers

Programming Logic controllers Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,

More information

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT FOR INTELLITOUCH AND EASYTOUCH CONTROL SYSTEMS INSTALLATION GUIDE IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Technical

More information

A+ Guide to Managing and Maintaining Your PC, 7e. Chapter 1 Introducing Hardware

A+ Guide to Managing and Maintaining Your PC, 7e. Chapter 1 Introducing Hardware A+ Guide to Managing and Maintaining Your PC, 7e Chapter 1 Introducing Hardware Objectives Learn that a computer requires both hardware and software to work Learn about the many different hardware components

More information

3M Wrist Strap and Footwear Tester 740. User s Guide

3M Wrist Strap and Footwear Tester 740. User s Guide 3M Wrist Strap and Footwear Tester 740 User s Guide Table of Contents Section Page Safety Information...3 1.0 General...4 2.0 Description...4 3.0 Operation...5 4.0 Wall Mounting...5 5.0 Wrist Strap Test...6

More information

TAC I/NETTM. Intrusion Alarm System

TAC I/NETTM. Intrusion Alarm System TAC I/NETTM Intrusion Alarm System The TAC I/NET intrusion alarm system (IAS) consists of a mix of security control products that can be combined and configured to provide intruder detection and alarm

More information

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...

More information

InnoMedia ESBC 9380-4B. Quick Install Guide. www.innomedia.com 1

InnoMedia ESBC 9380-4B. Quick Install Guide. www.innomedia.com 1 InnoMedia ESBC 9380-4B Quick Install Guide www.innomedia.com 1 Table of Contents Introduction 2 Package Contents 2 CAUTION 2 Installation 3 Wall-Mounting Instructions 5 Troubleshooting 6 Appendix A. LED

More information

SYSTEM 45. C R H Electronics Design

SYSTEM 45. C R H Electronics Design SYSTEM 45 C R H Electronics Design SYSTEM 45 All in one modular 4 axis CNC drive board By C R Harding Specifications Main PCB & Input PCB Available with up to 4 Axis X, Y, Z, & A outputs. Independent 25

More information

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS 1. Description and Phone Number Dialing: The dialer shall be a solid state component capable of dialing up to 16 telephone numbers, each up to 60 digits

More information

ScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system

ScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system pool/spa control system ScreenLogic Wireless Connection Kit Installation Guide P/N 520663 - Rev B 8 Technical Support Contact Technical Support at: Sanford, North Carolina (8 A.M. to 5 P.M.) Phone: (800)

More information

INTELLIGENT CONTROL MODULE SA-2000-II HARDWARE MANUAL. Access Technologies International, Inc.

INTELLIGENT CONTROL MODULE SA-2000-II HARDWARE MANUAL. Access Technologies International, Inc. SA-2000-II HARDWARE MANUAL Access Technologies International, Inc. 1 Table of Contents 1. Introduction 3 2. Features 3 3. Specification 4 4. Identifying Supplied Parts 4 5. Panel Description 5 6. Connection

More information

VS-0202 VS-0204. User Manual

VS-0202 VS-0204. User Manual User Manual VS-0202 VS-0204 Read this guide thoroughly and follow the installation and operation procedures carefully in order to prevent any damage to the units and/or any devices that connect to them.

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Screen 3.5" Color Touch 4.3" Color Touch Keypad or Function Keys Programming Com Port, Built-in

Screen 3.5 Color Touch 4.3 Color Touch Keypad or Function Keys Programming Com Port, Built-in Samba PLC+HMI SM35-J-RA22 SM43-J-RA22 Installation Guide 12 Digital Inputs, including 1 HSC/Shaft-encoder Inputs, 2 Analog Inputs, 2 PT100/TC inputs 8 Relay Outputs 2 Analog Outputs General Description

More information

Model 201 Wiegand Touchpad Reader Installation Guide

Model 201 Wiegand Touchpad Reader Installation Guide Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without

More information

9,'(2 #6(3$5$725 8VHU V#0DQXDO 96043;

9,'(2 #6(3$5$725 8VHU V#0DQXDO 96043; 9,'(2 #6(3$5$725 8VHU V#0DQXDO 96043; Introduction 3 Features 3 Specifications 4 Installation 4 Stand-Alone Installation 4 Daisy-Chain Installation 5 Preventing Radio & TV Interference 6 Limited Warranty

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

Single Channel Loop Detector

Single Channel Loop Detector Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

Secure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual

Secure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual Secure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual Section 1: Introduction SECURITY WARNING: New SEG's shipped after April 2008 will have Telnet setup option enabled by

More information

USBSPYDER08 Discovery Kit for Freescale MC9RS08KA, MC9S08QD and MC9S08QG Microcontrollers User s Manual

USBSPYDER08 Discovery Kit for Freescale MC9RS08KA, MC9S08QD and MC9S08QG Microcontrollers User s Manual USBSPYDER08 Discovery Kit for Freescale MC9RS08KA, MC9S08QD and MC9S08QG Microcontrollers User s Manual Copyright 2007 SofTec Microsystems DC01197 We want your feedback! SofTec Microsystems is always on

More information

Fire Fighter Phone System Installation Instructions

Fire Fighter Phone System Installation Instructions Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the Fire Fighter s Phone on a 4100U or a 4100ES Fire Alarm Control Panel (FACP).

More information

Compaq Presario Desktop Products. Upgrading and Servicing Guide

Compaq Presario Desktop Products. Upgrading and Servicing Guide Compaq Presario Desktop Products Upgrading and Servicing Guide The information in this document is subject to change without notice. Hewlett-Packard Company makes no warranty of any kind with regard to

More information

FAQ s on Siemens Magmeters

FAQ s on Siemens Magmeters FAQ s on Siemens Magmeters 1. The cables for the coils and electrodes for the magmeters look the same. Does it matter which cable is used for coils and which one is used for the electrodes? Both cables

More information

xpico Wi-Fi Embedded Device Server Evaluation Kit Quick Start Guide

xpico Wi-Fi Embedded Device Server Evaluation Kit Quick Start Guide xpico Wi-Fi Embedded Device Server Evaluation Kit Quick Start Guide Part Number 900-685 Revision A June 2013 Copyright and Trademark Contacts 2013 Lantronix, Inc.. All rights reserved. No part of the contents

More information

UPS PIco. to be used with. Raspberry Pi B+, A+, B, and A. HAT Compliant. Raspberry Pi is a trademark of the Raspberry Pi Foundation

UPS PIco. to be used with. Raspberry Pi B+, A+, B, and A. HAT Compliant. Raspberry Pi is a trademark of the Raspberry Pi Foundation UPS PIco Uninterruptible Power Supply with Peripherals and I 2 C control Interface to be used with Raspberry Pi B+, A+, B, and A HAT Compliant Raspberry Pi is a trademark of the Raspberry Pi Foundation

More information

Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: 5204183. www.guentner.de. Data sheet GIOD.1 V_3.0

Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: 5204183. www.guentner.de. Data sheet GIOD.1 V_3.0 Data sheet GIOD.1 Input/output module with CAN bus ERP no.: 5204183 www.guentner.de Page 2 / 10 Contents 1 GIOD.1... 3 1.1 Functional description...3 1.2 Connections... 5 1.3 Electrical properties of...

More information

VARIO PROX CARD READER INSTALLATION MANUAL

VARIO PROX CARD READER INSTALLATION MANUAL VARIO PROX CARD READER INSTALLATION MANUAL TABLE OF CONTENTS 1.0 INTRODUCTION...2 1.1 Legend...3 1.2 Terminology...4 2.0 MOUNTING...5 3.0 WIEGAND CONNECTION...6 4.0 AUX BUTTON INPUT...7 5.0 INSTALLER PROGRAMMING...8

More information

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX INSTALLATION INSTRUCTIONS Step 1. Determine the position for the Hands-free phone in the elevator phone

More information

DVI Video Splitter USER MANUAL VS-162 / VS-164

DVI Video Splitter USER MANUAL VS-162 / VS-164 DVI Video Splitter USER MANUAL VS-162 / VS-164 FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These

More information

Installation & Operation Manual HANDS-FREE BLUETOOTH MEDIA INTEGRATION KIT. Perfect for ANDROID TM

Installation & Operation Manual HANDS-FREE BLUETOOTH MEDIA INTEGRATION KIT. Perfect for ANDROID TM GET CONNECTED Installation & Operation Manual HANDS-FREE BLUETOOTH MEDIA INTEGRATION KIT TranzIt BLU HF ISFM2351 Perfect for ANDROID TM Note to Readers, The information contained within the following documentation

More information

4 Port VGA Video Audio Switch with RS232 control

4 Port VGA Video Audio Switch with RS232 control 4 Port VGA Video Audio Switch with RS232 control VS410RVGAA *actual product may vary from photos DE: Bedienungsanleitung - de.startech.com FR: Guide de l'utilisateur - fr.startech.com ES: Guía del usuario

More information

Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers

Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers Analog Data Links Multi-Channel Contact Closures Multiplexers Digital Data Links - Contact Closures Power Supply

More information

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported PCIe Cards 1.2 PACKAGE

More information

USER MANUAL VS92A / VS94A / VS98A

USER MANUAL VS92A / VS94A / VS98A Video Splitter USER MANUAL VS92A / VS94A / VS98A FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These

More information

e-ask electronic Access Security Keyless-entry

e-ask electronic Access Security Keyless-entry e-ask electronic Access Security Keyless-entry e-fob Keyless-entry entry System Full-Function Function Installation Manual FCC ID: TV2EFOB1 (UM20 ~ 22793-02) Table of Contents Introduction... 1 e-fob Operation

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual 0RQLWRU Pulse Monitor Software Version 1 0 1 Pulse Monitor Card Software Revision 1 4 0 Pulse Monitor Card Product Revision 0 1 0 0 February, 2007 Copyright 2007,

More information

430 Power/Electronics Replacement

430 Power/Electronics Replacement Replacing the main board WARNING Before proceeding, turn off the main power switch and unplug the power cord. Caution Make sure you are properly grounded with an ESD strap before continuing. The main printed

More information

LDG DTS-4/4R Desktop Coaxial Switch / Remote

LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 ldg@ldgelectronics.com www.ldgelectronics.com

More information

8-Port PoE Network Switch

8-Port PoE Network Switch Page 1 of 12 8-Port PoE Network Switch User s Guide Document Number 91I00-1 Rev A August, 2009 FCC Warning: Page 2 of 12 This devices has been tested and found to comply with the regulations for Class

More information

Model 70A00-1. GSM Cellular Communications Center

Model 70A00-1. GSM Cellular Communications Center Home Automation, Inc. Model 70A00-1 GSM Cellular Communications Center Operation Manual Document Number 70I00-1 Rev A August, 2009 Contents Description... 1 Use with security systems...1 Everyday use...2

More information

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM Section TELEPHONE AUTOMATIC DIALER SYSTEM PART 1 GENERAL 1.01 SYSTEM DESCRIPTION A. Design Requirements: 1. Electronic monitoring system shall interface plant alarms to public telephone system or cellular

More information

RC2200DK Demonstration Kit User Manual

RC2200DK Demonstration Kit User Manual Demonstration Kit User Manual Table of contents TABLE OF CONTENTS... 1 QUICK INTRODUCTION... 2 INTRODUCTION... 3 DEMONSTRATION BOARD... 4 POWER SUPPLY SECTION... 5 RS-232 INTERFACE... 6 CONNECTORS... 7

More information

Options for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface

Options for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface Options for ABB drives, converters and inverters User s manual FDPI-02 diagnostics and panel interface Table of contents Table of contents 3 1. FDPI-02 diagnostics and panel interface Safety..............................................

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

How To Wire Wireline Cable To A Cell Phone (New Zealand)

How To Wire Wireline Cable To A Cell Phone (New Zealand) Installation Guide EnerNOC Site Server - S2 Installation Guide - AUS, NZ v 1.7 EnerNOC New Zealand Limited 2 Collina Terrace PO Box 12-202 Thorndon Wellington NZ 6144 +64 4 909 7546 1 Table of Contents

More information

WxGoos-1 Climate Monitor Installation Instructions Page 1. Connections. Setting an IP Address

WxGoos-1 Climate Monitor Installation Instructions Page 1. Connections. Setting an IP Address Instructions Page 1 Connections The WxGoos-1 is a self-contained web server and requires 6vdc of power at 300ma. A center-positive 2.1 mm plug is used. There are five ports: 1. 10/100 Ethernet RJ-45 receptacle

More information

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

Product Description. Onboard Security I/O. Expansion Modules

Product Description. Onboard Security I/O. Expansion Modules 3951 Westerre Parkway, Suite 350 Richmond, Virginia 23233 USA Security JACE (SEC-J-601) Mounting & Wiring Guide This document covers the mounting and wiring of the Vykon Security JACE (SEC-J-601) controller.

More information