FAQ s on Siemens Magmeters
|
|
|
- Lesley Jeremy Curtis
- 9 years ago
- Views:
Transcription
1 FAQ s on Siemens Magmeters 1. The cables for the coils and electrodes for the magmeters look the same. Does it matter which cable is used for coils and which one is used for the electrodes? Both cables are the same outside diameter. When they are cut back, both have an overall braided shield. The heavier gage wire is used for the coils, and only 2 of the three conductors are used. The lighter gage wire is used for the electrodes, and all three conductors are used. As each of the three electrode wires are revealed, cut into them and you will find that each wire again has its own shield and another center conductor. The wires for the coils and electrodes from the mag body are terminated in black molded plugs with the correct conductor number corresponding to each pin of the plug. 2. Can the electode cable and the coil cable run in the same conduit in a remote transmitter configuration? It is suggested that 1 standard cable be used for the coils and one special double shielded cable is used for the electrodes. In this case, both cable can run in the same conduit from the mag body to the remote transmitter. If two standard cables are used without the double shielding for the electrode connection, the empty pipe detection capability is gone and separate conduits are suggested. 3. What do I do with the Shields? The overall braids of the both cables are tied to ground in the termination chamber of the mag body. When you get to the transmitter end, ONLY THE COIL CABLE (LARGER GAGE WIRE) has the shield tied to ground, while the overall braid of the electrode cable (lighter gage wire) is cut off and taped, not grounded. The shields of the three individual conductors of the electrode cable are tied on both ends, with the 0 terminal having both the conductor and shield under the same terminal.
2 4. How long can the cables be from the mag body to the transmitter for a remote transmitter, and can they be spliced? The length of the cable is determined by the conductivity of the fluid being measured. The higher the conductivity, the longer the allowable cable length, up to 600ft and more for most conductive fluids. The MagFlo Handbook includes a conductivity vs. cable length chart. Splices are discouraged to avoid moisture ingress. Both cables may be run in the same conduit. 5. Where is the SensorProm to be located? The SENSORPROM is shipped in the housing on top of the mag body. If it is to be an integral mounted transmitter, the SENSORPROM stays in the mag termination chamber. If the transmitter is to be remote, the SENSORPROM MUST BE MOVED. The SENSORPROM must be located wherever you mount your transmitter. 6. When the meter is turned on, flow readings are present but I have no ma output. The 4 20mA output of the magmeter is default as off. It must be turned on as it is one of the many variables that are monitored, and will be flagged as an error if loop continuity is not detected. The 4 20mA signal is sourced and will drive up to 800 ohms, with selection of unidirectional or bidirectional. Unidirectional will only detect forward flow, and will stay at 4mA when a negative flow value appears. Another cause for a ma output to stay at 4ma even with a flowrate present in that a 5000 series transmitter may have been purchased with built in HART, or the 6000 series with an add on Hart module. To operate with Hart in the ma output mode, the HART address must be set to 00. With a HART address of 01 thru 15, the ma output will stay at 4mA and expect to communicate the process data digitally over a multi drop HART wiring configuration.
3 7. A rate of flow value is shown, but my totalizer does not register. There are two totalizers available on the 5000 and 6000 series transmitters. Each totalizer acts independently of the other and may be set for forward flow, reverse flow, or net flow, where forward flow adds to the total, and reverse flow subtracts. If a totalizer is set for negative flow and forward flow occurs, the totalizer will appear to be not operating. The totalizer may be assigned to a scaled pulse with a programmable on time duration, or to the relay. 8. The flowmeter shows rate and total, but it appears to be reading invalid flow values, and will not allow me to configure a full scale value any higher than a flow value much lower than my line size dictates I should be able to read. Each meter is shipped with a SENSORPROM with the information as to the size and calibration factors for a specific body. If the SENSORPROM is not seated properly to allow the transmitter to read it, or if in a remote configuration the SENSORPROM was not moved from the mag body to be located with its now remote transmitter, the meter will default to a 2 meter, that has a max flow around 300 to 400 GPM. It is a good practice to check to make sure the transmitter is making good connection with, and is able to read the SENSORPROM. In the configuration menu go to SENSORPROM and an installed or not present indication will be displayed. Make sure the SENSORPROM is there, and reseat it to the wiring termination board. 9. The display show a flashing box with a diagonal line, and I am getting a P40 error code to replace my SENSORPROM The SENSORPROM could get corrupted by removing the transmitter with power on or from unclean power to the transmitter, either due to power surges or harmonics on the AC line of the primary power. The nameplate information is needed and your local Gilson office should be contacted to get a quote on a new SENSORPROM specific to your mag body.
4 To get by, even with the SENSORPROM not read, you can enter the configuration mode and manually program the meter size. This value is programmed in METERS. From the nameplate on the side of the meter body junction box get the DN number that states the size in mm. Take the DN number and simply divide by 1000 to get what you need so a 2 meter = DN50. DN50 / 1000 = size of METERS. When the meter starts up, it looks for the SENSORPROM. When it doesn t read a valid data set, it goes to the transmitters default. The above step is reprogramming the transmitters DEFAULT to your actual size. Do get the new SENSORPROM ordered and installed to keep the interchangeability of transmitters without the need to reprogram, and maintain the ability to perform a re verification of accuracy with the Siemens VERIFICATOR by comparing present mag body parameters to those when the meter was first built as stored on the valid SENSORPROM. 10. Can the transmitter be removed with power on the unit? The transmitters do have short circuit protection so the coil driver will not blow if removed with power on, although removing the transmitter with power on is not recommended as it may result in corruption of the SENSORPROM should this occur during a period when data is being written to the chip. 11. The meter is installed reading accurate rate and total, but shows an overflow error. The transmitter offers a 4 20mA output for remote rate, but has multiple outputs like scaled pulse, relay, or frequency for remote totalization. Any outputs not being used should be turned off in the configuration to avoid having to make sure the important parameters being used are not causing the additional outputs to go into overflow, or exceed their configured output response.
5 12. The transmitter was ordered with HART, but I cannot communicate with the meter. The device being used to communicate HART (HART Handheld or a Laptop with a HART Modem and a configuration software package like Siemens PDM) first must have the correct Device Descriptor and the loop must have between 250 and 1100 ohms to allow HART communications. As far as the transmitters are concerned, the 5000 Series is purchased with or without HART, while the 6000 Series has an add on module that is plugged into a socket on the bottom of the transmitter. The 5000 has the same molded body as the 6000 but will not read the add on module. In addition to having HART, two wiring jumpers must be added to the wiring board as indicated by a decal on the module or on the bottom of the 5000 HART transmitter, shorting terminal 31 to 91, and 32 to 92. Terminal 31 if the positive current connection while 32 is the negative current output connection. The HART capability is wired into the loop in parallel. You are not creating a parallel current path, but allowing the HART frequency to be read off the loop. Any other components in your loop must be wired in series as with all current sensing devices. 13. I have configured my meter and it reads and totalizes accurately, but the 4 20mA output is locked at 4mA, and cannot even be forced in the maintenance section of the configuration menu. When a transmitter has HART, it can be set to operate in a ma output mode where HART is used primarily for configuration, or it can be set to operate in HART Digital Mode. This is determined by the HART address. If the address is set to 0, the transmitter will allow current output to fluctuate with the process variable, or to be forced in diagnostics. If the address is set to 01 thru 15, the transmitter is looking to communicate digitally over HART and will lock the current output to 4 ma in both operational mode as well as in diagnostic mode.
6 14. There is a directional arrow on the neck of the meter body, and it is opposite of my actual direction of flow. Does the meter have to be removed and turned around? The arrow actually indicated the direction the unit was tested at the factory. After the unit is installed and wired, there is a 50/50 chance you will have a negative flow value, which can also make a forward flow totalizer not register. In the Configuration menu under Basic Settings is a selection to reverse the direction the meter recognizes as forward flow, so the meter does not have to be removed and turned around. 15. I have the meter installed properly but it shows 0 or zero flow?? Open the termination box on the sensor (mag tube), either integral or remote transmitter configuration, and check to see that the electrode connector is plugged into corresponding terminals , on the termination strip. The black molded connector has the proper terminal numbers molded into the plug across from the corresponding pin. In a remote transmitter configuration make sure that the cables for the electrodes (lighter gage wire with individual shields) have their center conductors wired to the terminals directly across from the corresponding pin number and that the shield is not tied to an incorrect terminal. Also for remote configurations, make sure that the conductors follow the same color from the terminal strip in the mag body the same corresponding terminal at the remote transmitter. 16. F70 Coil resistance Error F70 indicates Coil Excitation has failed. Check your electrical connections on both the transmitter and mag body end. Another source of this error is an incorrect coil excitation frequency. Go to point to the Siemens magmeter in Gilson Flow Lab pictures on the homepage and you can download or view the instruction manual that lists the various mag body models for the correct drive frequency. Be careful as two values are stated, one for 50Hz and a different for 60Hz. Settings can be changed by entering the program menu and going to Sensor characteristics. If this does
7 not eliminate the error, then remove power and check the resistance from 85 gnd And 86 gnd. Resistance should be greater than 10 meg ohms. If less than 10 megohms, then check wiring. Also check resistance of the coil. This resistance should be in the range of ohms. 17. My flow reading is half of what it should be. One of the two electrode circuits is not functioning. Check the electrode circuits for shorts to ground (82 to ground and 83 to ground), open circuits along electrode cable in remote mount installations, and continuity with actual electrodes inside meter body (82 to one electrode inside meter tube, 83 to other electrode inside meter tube). The Verificator cannot discern between short circuits to ground on the electrodes and a meter filled with a conductive liquid. 18. The display seems dim or flickers. A dim or flickering display can be the result of the display board connector that mates to the main board of the transmitter working its way loose during shipment. Remove the bezel around the display and the screws holding the display board in place will be revealed. Remove the screws and lift the display to gain access to the interconnecting cable. Reseat the cable connection to the main board and replace the display board in the desired orientation ( may be rotated in 90 degree increments) and snap the bezel cover back in place. 19. What is empty pipe detection? (Read this if you potentially have a pipe that s not all the way full with fluid OR if you are getting a flow reading when you know the meter doesn t even have fluid in it) Empty pipe detection is an available feature only if you are using the special double shielded cable and the standard coil cable for remote wiring (feature not available when using 2 standard coil cables). When this feature is turned on, the meter will read 0 gpm until the monitoring electrodes are satisfied. The sensing electrode for this feature is at the top
8 of the pipe (at 12 o clock) on the 5100W, and this electrode must be covered by the fluid before a reading occurs. Therefore, you will not get a flow reading if your pipe is partially full, and you will not get the floating associated electrodes in air. This feature can be turned on/off in the programming. This feature is not only helpful in detecting an empty or partially full pipe but also in eliminating outside EMI/RFI interferences. 20. Why does my totalizer read #####? The totalizers each have a limit of 8 digits. You will want to double check where your decimal points are when programming. This ##### symbol means that you have gone over the 8 digit limit (i.e. 99,999,999). To display the totalizer again, you must do one of two things: 1) Reset the totalizer back to zero and start over. 2) Increase the units to accommodate the total flow (for example, 99,999,999 gallons should be increased to 99 million gallons) 21. Is the Siemens Magmeter secured for billing purposes? The Siemens Magmeter Transmitters, model 5000 or 6000, have a Configuration Menu that is password protected, and an Operator Menu that is not protected. The user can in the Configuration Menu define which of the possible 20 menu items that will be accessible to the operator, or unprotected by password including resetting of the local totalizers. Even when password protected, there is a back door entry to reset the password to the factory default This may not be acceptable when used for billing purposes as in a municipality accepting the magmeter for billing purposes. Both the 5000 and 6000 transmitters are available in the CT version, short for Custody Transfer, meaning suitably secure for billing. These units include solder pads on both sides of the termination board and a jumper key. When the key is in place, all configurable parameters may be changed. When the key is removed, all configurable parameters, including resets, are locked in place. Many municipalities will still require the securing wire rope
9 and Lead crimp. To accommodate this need, the transmitter enclosure base for both the integral and remote transmitter configurations have eyelets for the wires securing the transmitters in place by the monitoring authority. 22. I just installed my new magmeter in finished water exiting the plant and the reported flow is all over the place. The flow I expect to be 1000 gpm bounces from 1000 to 300 to 250 to 750, drifting all over the place After looking making sure all electrical cabling is away from electrical interferences on the power cables, the output cables and the sensors cables for coils and electrodes, and that all shielded cables are terminated correctly, look for a chemical addition point upstream of the flow meter inlet. Chemical addition, like Sodium Hypochlorite addition in finished water can create wild swings in conductivity of the overall fluid making it appear the magmeter is drifting. The effects can vary based upon the chemical. To be safe keep all chemical addition points downstream of the mag body. 23. My magmeter reads half flow, and I have checked the unit is set for the proper frequency (60 hz in USA), checked my coil drive frequency, and checked everything else but continue to get a crazy low reading. Double check all coil and electrode connections, especially in a remote transmitter configuration. With the clamp down style terminals, make sure that a sufficient amount of insulation has been stripped so you have a good electrical connection, at all junction point, in the mag body, as well as at the transmitter. It is easy to overlook that either a wire was not stripped far enough back leaving the terminals to clamp on insulation, or that a screw was not tightened leaving a loose conductor. 24. I have a 6000i transmitter in a metal enclosure. I have powered the mag transmitter with 120VAC as ordered, but I am getting no 4 20mA output. Like the 5000 and 6000 series compact versions in the plastic housings, the
10 4 20mA output must be turned on in the configuration menu. On the 6000i, another step may be required as the 4 20mA is standard as a sinking output. A jumper must be changed to source the 4 20 (drive the 4 20 with the internal 24VDC supply). Only the 6000i transmitter offers a field selection of sink or source. The compact 5000 and 6000 transmitters in the plastic housing only source, no sinking. 25. I have the magmeter installed and configured. Can I simulate the outputs to check my control system? Outputs can be simulated without the need for flow. Go into the Configuration menu, and scroll across to the Service Menu. Under the current output, you can select NORMAL with the current output tracking the current flow, or FORCED. With FORCED selected, you get a prompt to enter the desired forced current output. Under Digital output, If you have the digital output configured for a frequency output, change the setting from NORMAL to FORCED and you will get a prompt for the desired frequency to simulate. If the digital output is configured for any output other than frequence, like totalizer output, error detect, flow direction, flow limit, etc, you will get a prompt to drive HIGH or LOW. Under Relay Output, you can select ON or OFF. Keep in mind the relay output cannot be tied to the totalizer output. Only diagnostics, Flow Direction, or a Flow Rate Alarm.
11
SITRANS F M MAGFLO. Electromagnetic flowmeters Signal converter types MAG 5000, MAG 6000. Manual *083R9141* Order no.
s Manual SITRANS F M MAGFLO Electromagnetic flowmeters Signal converter types MAG 5000, MAG 6000 [ ] Order no.: FDK:521H0739 DKFD.PS.027.Z4.02 - A5E00253213 *083R9141* 1. Technical data 1.1 Signal converter
MTII4200 level Transmitter Installation, Operation & Maintenance Instructions
Specialists in Liquid Level Indication MTII4200 level Transmitter Installation, Operation & Maintenance Instructions Section: M500 Bulletin: M500.31 Date: 01-26-12 Supersedes: 04-22-08 1. INTRODUCTION
Short Range Wireless Switch System Handheld 8 Installation and Operations Guide
Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions
TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to
IFC 070 Technical Datasheet
IFC 070 Technical Datasheet Electromagnetic signal converter Battery driven with low energy consumption Quick and easy to install and operate External data logger and GSM module for remote data transfer
Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43
Data Sheet Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43 2-Wire Operation Significantly reduces installation costs when compared to a traditional 4-wire magmeter. ±0.5% of rate system accuracy. Patented
Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.
Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections
Quick Start Guide 00825-0100-4764, Rev DA March 2014. Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator
Quick Start Guide 00825-0100-4764, Rev DA Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator Quick Start Guide NOTICE This document provides basic guidelines for the Rosemount 8714D. It
Transmitter Interface Program
Transmitter Interface Program Operational Manual Version 3.0.4 1 Overview The transmitter interface software allows you to adjust configuration settings of your Max solid state transmitters. The following
Measurement. SITRANS F US Inline. Transmitter FUS080/FUE080 4/219
Siemens AG 2010 Flow Measurement Overview The transmitter is available in an IP67/NEMA X/6 enclosure and is designed for use in the flowmeters series: SONOKIT (1- or 2-track) FUS380 (2-track) FUE380 (2-track)
OPERATING INSTRUCTIONS
PIPELINE INSPECTION COMPANY LTD. OPERATING INSTRUCTIONS Wet Sponge Holiday Detectors 670,673, and MSRB Wet Sponge Holiday Detectors Portable and In-Plant Detectors Table of Contents General Information.......................3
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
SSW-iLM Keypad. Wire Harness Configuration. Note: This product is designed to be installed and serviced by security and lock industry professionals
SSW-iLM Keypad Note: This product is designed to be installed and serviced by security and lock industry professionals Specifications Case dimensions: 6 1/2 L x 1 3/4 W x 1 1/8 D Electrical: 5-12VDC Only
Troubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02
IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 TABLE OF CONTENTS DESCRIPTION 2 MOUNTING INSTRUCTIONS 2 HOW TO CABLE THE IPX 2/3 POWER SUPPLY INSTALLATION 3 OPERATION 3 CARE
ILISC515-A Shift Interlock (Manual Lift Door) 2015 Ford Transit, 3.7L and 3.5L
An ISO 9001:2008 Registered Company ILISC515-A Shift Interlock (Manual Lift Door) 2015 Ford Transit, 3.7L and 3.5L Introduction The ILISC515-A is a microprocessor driven system for controlling wheelchair
CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)
TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output
TC-9102 Series Surface Mount Temperature Controllers
TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may
Contents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
Model 5511 Filler Controller User s Manual Version 1.1 October 2011
Thompson Scale Company WEIGHING SYSTEMS & PACKAGING MACHINERY CONTROLS 2758 Bingle Road Houston, Texas 77055 Phone: 713/932-9071 Fax: 713/932-9379 www.thompsonscale.com Model 5511 Filler Controller User
How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER (PWM Input, 1.2A or 2A Output, Metal Box or PCB) PCB Board - P/N: PWMC-PCB-2A, PWMC-PCB-1.2A Packaged Driver (metal box with 1.5 m (5 ft.) cable)
omega.com ΩOMEGA RS232 Multi-Drop www.omega.com FMA1600-MDB Multi-Drop Box
omega.com ΩOMEGA RS232 Multi-Drop www.omega.com FMA1600-MDB Multi-Drop Box 1 3/29/2010 Rev.0 DOC-OMEGABB9MAN 2 Introduction FMA1600-MDB Multi-Drop Box Operating Bulletin The FMA1600-MDB Multi-Drop Box
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
289 SERIES FLOW METER TRANSMITTERS
289 SERIES FLOW METER TRANSMITTERS INSTRUCTION MANUAL 289 SERIES TRANSMITTER 289-763 Pickup Coil/Amplifier, Amphenol Connector 289-773 Pickup Coil/Amplifier, Weather-Tight, Explosion-Proof* TABLE OF CONTENTS
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor
CONTROL SWITCHER User s Manual (Preliminary)
CONTROL SWITCHER User s Manual (Preliminary) www.voodoolab.com Copyright 2010 by Digital Music Corporation. This publication is protected by copyright and all rights are reserved. Voodoo Lab, Control Switcher,
PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL
Rev. D PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL 10 BORIGHT AVENUE, KENILWORTH NEW JERSEY 07033 TELEPHONE: 800-524-0273 FAX: 908-686-9317 TABLE OF CONTENTS Page
Streaming Potential System (SPT1000, SPD1000)
Streaming Potential System (SPT1000, SPD1000) User's Manual Sentrol Systems, Inc. 3949 Cotswold Dr. SW, Lilburn, GA 30047-2371 Tel: 770-564-1541, Fax: 770-564-8605 www.sentrolsystems.com Since the streaming
SITRANS F M MAG 8000 Precise Metering with battery powered water meters. sitrans f
SITRANS F M MAG 8000 Precise Metering with battery powered water meters sitrans f s Compact and remote installation made simple Easy to install Simply bolt into place before operation Minimized inlet and
Modular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
TIMING SIGNALS, IRIG-B AND PULSES
TIMING SIGNALS, IRIG-B AND PULSES Document No. PD0043200B July 2013 Arbiter Systems, Inc. 1324 Vendels Circle, Suite 121 Paso Robles, CA 93446 U.S.A. (805) 237-3831, (800) 321-3831 http://www.arbiter.com
Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811
Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The
DWYER INSTRUMENTS, INC. Phone: 219/879-8000 P.O. BOX 373 MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.
Series DCT1000 Dust Collector Timer Controller Specifications Installation and Operating Instructions Bulletin E-97 Thank you for purchasing the DCT1000 Dust Collector Timer Controller. You have selected
OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE
OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &
Vehicle Alarm System With Channel 2 Auxiliary Output Installation Instructions
Model PRO 9842 Installation Manual Vehicle Alarm System With Channel 2 Auxiliary Output Installation Instructions This Unit Is Intended For Installation In Vehicles With 12 Volt Negative Ground Electrical
When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only
Siemens Energy & Automation. structured. WIRING Product Training Series: Advanced Video Session 3
s structured WIRING Product Training Series: Advanced Video Session 3 1 Table of Contents This presentation will give you a closer look at Video in Structured Wiring applications. The following Areas will
PowerLogic Sub Meter Display (SMD and SMDOPN)
Instruction Bulletin Z203742-0B PowerLogic Sub Display (SMD and SMDOPN) CONTENTS Introduction... 2 Parts of the Sub Display... 3 Dimensional Drawing... 4 Installation... 5 Mounting the SMD... 5 Mounting
Electronic Time Recorder
CP-3000 Electronic Time Recorder User s Guide PROPRIETARY NOTICE This document contains proprietary information and such information may not be reproduced in whole or in part without the written permission
SYSTEM 45. C R H Electronics Design
SYSTEM 45 C R H Electronics Design SYSTEM 45 All in one modular 4 axis CNC drive board By C R Harding Specifications Main PCB & Input PCB Available with up to 4 Axis X, Y, Z, & A outputs. Independent 25
How To Use A Flowmeter
INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection
RS-232 Communications Using BobCAD-CAM. RS-232 Introduction
RS-232 Introduction Rs-232 is a method used for transferring programs to and from the CNC machine controller using a serial cable. BobCAD-CAM includes software for both sending and receiving and running
PUSH BUTTON START INSTALLATION MANUAL
PUSH BUTTON START INSTALLATION MANUAL ALTHOUGH THIS PRODUCT HAS BEEN THOROUGHLY TESTED KPIERSON TECHNOLOGIES ASSUMES NO RESPONSIBILITY FOR ANY DAMAGE THAT MAY RESULT BY THE INSTALLATION OF THIS PRODUCT.
Digital inductive conductivity transmitter
Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
Ground Resistance Clamp On Tester
USER MANUAL Ground Resistance Clamp On Tester MODEL 382357 Introduction Congratulations on your purchase of Extech s 382357 Ground Resistance Tester. This Clamp on device allows the user to measure ground
User Manual for CH-PFC76810
AA Portable Power Corp www.batteryspace.com, Email: [email protected] User Manual for CH-PFC76810 1. Overview The CH-PFC76810 charger is suitable for charging lithium ion battery packs such as those
i ChatterBox! Motorcycle Security
i Before you Start the Installation * Please read this manual to become familiar with the requirements necessary to complete the installation. * Use a high quality multi-meter to test all wires before
22.302 Experiment 5. Strain Gage Measurements
22.302 Experiment 5 Strain Gage Measurements Introduction The design of components for many engineering systems is based on the application of theoretical models. The accuracy of these models can be verified
CONTENTS. PAGE Chapter 1 General Information 1. Chapter 2 Setup 4 DP450-VDC 7 DP450-VAC 7 DP450-DCC 7 DP450-F 8 DP450-HACC 9 DP450-HDCC 11 DP450-E 13
CONTENTS PAGE Chapter 1 General Information 1 Chapter 2 Setup 4 DP450-VDC 7 DP450-VAC 7 DP450-DCC 7 DP450-F 8 DP450-HACC 9 DP450-HDCC 11 DP450-E 13 Chapter 3 Alarm/Excitation Options 15 Wiring 17 Chapter
Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert AC4. User Manual
Infrastructure Management & Monitoring For Business-Critical Continuity Liebert AC4 User Manual TABLE OF CONTENTS 1.0 INTRODUCTION 1.1 Methods of Viewing and Configuring the Liebert AC4..............................
Single Channel Loop Detector
Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop
4.3-inch Back-Up Camera
TM 4.-inch Back-Up Camera Model No.: PKC0BU4 Owner s Manual and Warranty Information Read these instructions completely before using this product. Retain this Owner s Manual for future reference. INTRODUCTION
SYSTEM 4C. C R H Electronics Design
SYSTEM 4C C R H Electronics Design SYSTEM 4C All in one modular 4 axis CNC drive board By C R Harding Specifications Main PCB & Input PCB Available with up to 4 Axis X, Y, Z, A outputs. Independent 25
New GSM Alarm System. User s Manual. Profile For a better understanding of this product, please read this user manual thoroughly before using it.
New GSM Alarm System User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. Chapter 1. Features Chapter 2. Alarm Host Introduction Chapter
Control Box Wiring For PRSstandard Tool
888-680-4466 ShopBotTools.com Control Box Wiring For PRSstandard Tool Copyright 2016 ShopBot Tools, Inc. page 1 Copyright 2016 ShopBot Tools, Inc. page 2 Table of Contents Introduction:...5 Installation:...5
Secure Keypads for access control
torm Secure Keypads for access control Strike Master Read this manual carefully before attempting to install, program or operate the STORM AXS Strike Master Keypad. After installation the Command Summary
INSTALLATION & SERVICE MANUAL. Display Panel
INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed
Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual
Operation and Maintenance Manual Introduction Read all instructions thoroughly. Installation of the OilTector must comply with all Federal, State and Local Codes, Regulations and Practices. The OilTector
Sanitary Type Electronic Flow Switches
Industries Pharmaceutical Sanitary Type Electronic Flow Switches Food and Beverage Biotechnology Semiconductor Water Treatment S Series Ameritrol, Inc. Instruments and Controls Features No Moving Parts
8 Channel Status Input Panel model SIP-8
Description The Sine Systems model SIP-8 Status Input Panel is to be used with the RFC-1/B Remote Facilities Controller. It consists of a long PC board mounted on a 1.75 inch (1U) rack panel. The SIP-8
EH-20 20m antenna. By VE3RGW
EH-20 20m antenna By VE3RGW Equivalent circuit of EH-20 (prototype 2A) antenna system. Upper cylinder Lower cylinder Ground Counter pose Phasing coil Impedance transformer and tune circuit Tune coil Feed
MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter
Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
INSTALLATION INSTRUCTIONS
Rear Vision System Tailgate Handle Camera Mirror Display 2004-2014 Ford F-150 and 2008-2015 Ford Super Duty (Kit part numbers 9002-9521) Kit Contents: Mirror Tailgate Handle with camera and harness Interior
Combi B Alarm box. Mounting instructions
Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power
SITRANS F flowmeters SITRANS F M. Battery operated water meter MAG 8000 4/93
Overview (MAG 8000/MAG 8000 CT) Intelligent information, easy to access Advanced information on site Data logger for consumption profile Advanced statistics and diagnostics Add-on communication module
FLR 1000 & 1000-BR Series Flow Sensors & Meters For Gases
FLR 1000 & 1000-BR Series Flow Sensors & Meters For Gases READ THIS MANUAL COMPLETELY BEFORE ATTEMPTING TO CONNECT OR OPERATE YOUR FLOW SENSOR. FAILURE TO DO SO MAY RESULT IN INJURY TO YOU OR DAMAGE TO
Model 201 Wiegand Touchpad Reader Installation Guide
Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without
AC and DC Drive System Installation Information
Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS
PART 1 - INTRODUCTION...
Table of Contents PART 1 - INTRODUCTION... 3 1.1 General... 3 1.2 Sensor Features... 3 1.3 Sensor Specifications (CDE-45P)... 4 Figure 1-1 CDE-45P Sensor Dimensions (standard, convertible style)... 4 PART
How To Wire Wireline Cable To A Cell Phone (New Zealand)
Installation Guide EnerNOC Site Server - S2 Installation Guide - AUS, NZ v 1.7 EnerNOC New Zealand Limited 2 Collina Terrace PO Box 12-202 Thorndon Wellington NZ 6144 +64 4 909 7546 1 Table of Contents
DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly
DREXELBROOK A Leader In Level Measurement Solutions USonic-R Series Ultrasonic Level Measurement System User Friendly Set the measurement range directly in inches, feet, millimeters, centimeters, or meters
CMD-9000 COMMANDER SERIES REMOTE CONTROL ENTRY SYSTEM
CMD-9000 COMMANDER SERIES REMOTE CONTROL ENTRY SYSTEM INTRODUCTION Thank you for purchasing the CMD-9000 Commander from Dakota Digital. This, along with many other products that Dakota Digital has to offer,
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
Allen-Bradley/Rockwell
MANUFACTURER DATA SHEET High Speed Counter Manufacturer: Allen-radley/Rockwell Model Number: 1746-HSCE See www.geomartin.com for additional PDF datasheets Martin Part Number: E-014901-03 VendorPartNumber:
Model SETR-50 and SETR-51 Trim Tab Control
Model SETR-50 and SETR-51 Trim Tab Control Pictured above is the SETR-50 with black switches on a gray background. The SETR-51 is identical except for the color, wherein it has black switches on a black
FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1
BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -
Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English. 1-800- RAIN BIRD (800-724-6247) or visit www.rainbird.
Rain+Birdt Simple To Set r (SST) Setup & Operation Instructions English Installation...2 Tools and Supplies Needed...2 Step 1. Mount r...2 Step 2. Connect Power...2 Indoor r...2 Outdoor r...2 Step 3. Connect
RAEGuard EC FGM-13XX
RAEGuard EC FGM-13XX User s Guide P/N 033-4102-000 Rev B May 2007 - READ BEFORE OPERATING - This manual must be carefully read by all individuals who have or will have the responsibility of using, maintaining,
User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction
User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger
Multi-Protocol decoder 76 200 with Load regulation
Multi-Protocol decoder 76 2 with Load regulation For locomotives with universal motors on digital layouts operating in the DCC and Motorola data format. Features 76 2 Load regulated multi-protocol decoder
Lab E1: Introduction to Circuits
E1.1 Lab E1: Introduction to Circuits The purpose of the this lab is to introduce you to some basic instrumentation used in electrical circuits. You will learn to use a DC power supply, a digital multimeter
MP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
Troubleshooting Guide for Jacks Down LED Lights
Troubleshooting Guide for Jacks Down LED Lights Equalizer Systems Auto-Level systems manufactured after 2005 feature a pressure switch system that monitors the retracted state of leveling jacks and any
Nokeval. User's Manual Models 301 / 302 / 305
Nokeval User's Manual Models 301 / 302 / 305 No 16042010 1 Contents Contents... 2 General description... 3 Disabling front panel keys... 4 Front panel buttons and indicators... 5 Configuration mode...
Contactless Encoder RI360P0-QR24M0-INCRX2-H1181
Compact, rugged housing Many mounting possibilities Status displayed via LED Immune to electromagnetic interference 1024 pulses per revolution (default) 360, 512, 1000, 1024, 2048, 2500, 3600, 4096, parametr.
INSTALLATION MANUAL XM3 Reader
INSTALLATION MANUAL XM3 Reader Conditions Transactions, deliveries et cetera will be according to the general terms of delivery as deposited at the Chamber of Commerce at Meppel, The Netherlands. Registration
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control
Signature and ISX CM870 Electronics
Signature and ISX CM870 Electronics Cummins West Training Center System Description General Information The Signature and ISX CM870 engine control system is an electronically operated fuel control system
How to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers.
How to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers. OMEGALOG Help Page 2 Connecting Your Data Logger Page 2 Logger Set-up Page 3 Download Data Page 8 Export Data Page 11 Downloading
Installation Guide Solar Connect-11
Installation Guide Solar Connect-11 Version 1.1 Contents Important Product Information 3 System Registration Form 4 Solar Connect-11 Overview 5 Internet & Power Connections 6 Single Phase CT Connections
G-100/200 Operation & Installation
G-100/200 Operation & Installation 2 Contents 7 Installation 15 Getting Started 16 GPS Mode Setup 18 Wheel Sensor Mode Setup 20 Fuel Calibration 23 Basic Operation 24 Telemetery Screen 27 Entering a Distance
DMX-K-DRV. Integrated Step Motor Driver + (Basic Controller) Manual
DMX-K-DRV Integrated Step Motor Driver + (Basic Controller) Manual DMX-K-DRV Manual page 1 rev 1.33 COPYRIGHT 2007 ARCUS, ALL RIGHTS RESERVED First edition, June 2007 ARCUS TECHNOLOGY copyrights this document.
Combustible Gas Transmitter 65-2400RK-05
Combustible Gas Transmitter 65-2400RK-05 Overview This detection insert describes the combustible gas transmitter. This insert also describes how to install, start up, maintain, and calibrate the transmitter.
In-Line Electronic Flow Switches
In-Line Electronic Flow Switches Industries Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor
T0118 T2118 T3118. Instruction Manual
Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity
