Electronic Multi-Measuring Instrument
|
|
|
- Gavin Foster
- 9 years ago
- Views:
Transcription
1 MITSUBISHI Electronic Multi-Measuring Instrument Programming Manual (CC-Link) Model ME96NSR-MB or ME96NSR with optional Plug-in Module : ME-0040C-NS96
2 CONTENTS 1. General Description Specification Configuration Conditions of CC-Link System Parameter Settings Procedure from Parameter Settings to Data Link Startup CPU Parameter Area and Master Module Parameter Memory Procedure for Parameter Settings to Data Link Startup with GX Developer Parameter Setting Items Example of Parameter Settings with GX Developer Master Station Network Parameter Settings Master Station Automatic Refresh Parameter Settings Communication Between the Master Station and ME96NSR Communication Guideline Initial Communication Normal Communication Error Communication Remote I/O and Remote Register Remote Input RX, Remote Output RY Remote input RX Remote Output RY Remote Register (RWr, RWw) Supported Command Details of Commands About Error Occurrence Abbreviations and Special Terms Program Example Program Content System Configuration Device Allocation Parameter Settings Network Parameter Settings and Auto Refresh Parameter Settings Operational Settings Station Information Settings Program Example Test Function Mode How to Test Reply Data (1/n)
3 1. General Description This manual describes the programming methods that should be created by the user for monitoring measurement value of the Electronic Multi-Measuring Instrument (called ME96NSR from here on) with the PC CPU through Control & Communication Link (abbreviated as CC-Link from here on). In programming, read the following related manuals in addition to this mannual. Table 1.1 Related Manuals Manual Name CC-Link System Master/Local Module User s Manual Type:QJ61BT11 CC-Link System Master/Local Module User s Manual Type:QJ61BT11N User s Manual for ME96NSR Manual No. SH(NA) SH(NA) Supplied with product 2. Specification ME96NSR specification is shown in Table 2.1. Table 2.1 ME96NSR Specification Item Station type Number of occupied stations Maximum number of stations per master station Transmission speed RX, Ry RWw, RWr Specification Remote device station 1 station 42 stations ( In case of connecting only remote device station occupied by 1 station.) 156kbps/625kbps/2.5Mbps/5Mbps/10Mbps 32 points each 4 points each Master station ME96NSR ME96NSR ME96NSR Maximum number of connection is 42. (In case of ME96NSR connection.) ME96NSR ME96NSR ME96NSR System Configration (CC-Link) (2/n)
4 3. Configuration Conditions of CC-Link System A total of 64 remote I/O stations, remote device stations, or local stations can be connected for one master station. Station type of ME96NSR is remote device station, and the number of occupied stations is 1 station. However, the following conditions must be satisfied: (1) { (1 a) + (2 b) + (3 c) + (4 d) } 64 a:number of modules occupying 1 station (ME96NSR is applied.) b:number of modules occupying 2 stations c:number of modules occupying 3 stations d:number of modules occupying 4 stations (2) { (16 A) + (54 B) + (88 C) } 2304 A:Number of remote I/O stations 64 B:Number of remote device stations (ME96NSR is applied.) 42 C:Number of local stations, standby master stations and intelligent device stations 26 ME96NSR (3/n)
5 4. Parameter Settings 4.1 Procedure from Parameter Settings to Data Link Startup The following explains the procedure from setting the parameters to stating the data link CPU Parameter Area and Master Module Parameter Memory (1) CPU Parameter Area This area is used to set the basic values for controlling the programmable controller system and the network parameters that control the CC-Link system. (2) Master Station Parameter Memory This area stores the network parameters for the CC-Link system. When the module is powered OFF or the programmable controller CPU is reset, the network parameters are erased. Programmable controller CPU Parameter area CC-Link system network parameter area Power ON CPU reset Master station Parameter memory CC-Link system network parameter area Procedure for Parameter Settings to Data Link Startup with GX Developer Follow the procedure below for parameter settings to data link startup: GX Developer Programmable controller CPU Master station The GX Developer is used to create network parameters and automatic refresh parameters, which are then written to the programmable controller CPU. Network parameters Automatic refresh parameters CC-Link system parameter area Network parameters Automatic refresh parameters Parameter memory Network parameters When the programmable controller system is powered ON or the programmable controller CPU is reset, the network parameters in the programmable controller CPU are transferred to the master station and the data link is automatically started. GX Developer Network parameters Automatic refresh parameters Programmable controller CPU CC-Link system parameter area Network parameters Automatic refresh parameters Master station Parameter memory Network parameters (4/n)
6 4.2 Parameter Setting Items The following lists the items to be stored in the master station parameter memory. Setting item Number of connected modules Number of retries Number of automatic return modules Standby master station specification Operation specification when CPU is down Scan mode specification Delay setting Reserved station specification Error invalid station specification Station information Description Sets the total number of remote stations, local stations, intelligent device stations and standby master station that are connected to the master station (including reserved stations). Default value : 64 (modules) Setting range : 1 to 64 (modules) Sets the number of retries when a communication error occurs. Default value : 3 (times) Setting range : 1 to 7 (times) Sets the total number of remote stations, local stations, intelligent device stations and standby master stations that can be returned to system operation by a single link scan. Default value : 1 (module) Setting range : 1 to 10 (modules) Specifies the station number of the standby master station. Default value : Blank (no standby master station specified) Setting range : Blank, 1 to 64 (Blank: No standby master station specified) Specifies the data link status when a master station programmable controller CPU error occurs. Default value : Stop Setting range : Stop, Continue Specifies either synchronous or asynchronous mode for sequence scan. Default value : Asynchronous Setting range : Asynchronous, Synchronous Sets 0 for the delay time. Specifies the reserved station. Default value : Not specified Setting range : Not specified, Specified Specifies the error invaled station. Default value : Not specified Setting range : Not specified, Specified Sets the station information according to the connected remote station, local station, intelligent device station, and standby master station. Default value : Ver.1 remote I/O station, occupies 1 station, Station number 1 to Ver.1 remote I/O station, occupies 1 station, station number 64 Setting range station type : Remote I/O station, remote device station, intelligent device station/ver.1, Ver.2 (single, double, quadruple, octuple) Number of occupied stations : 1 to 4 Station number : 1 to 64 (5/n)
7 4.3 Example of Parameter Settings with GX Developer This section explains the parameter settings using the GX Developer. In the setting parameters used with GX Developer, the setting of master station network parameters and the setting of automatic refresh parameters are done. For more details on the GX Developer operation, refer to the GX Developer Operating Manual. The explanations in this section are based on the follwing example of the system configuration. Master station (X00 to X1F) (Y00 to Y1F) Station number 1 Station number 2 ME96NSR (occupies 1 station) ME96NSR (occupies 1 station) Master Station Network Parameter Settings (1) The follwing describes an example of the parameter settings. See (2) for actual settings. (2) Set the network parameters using the following procedure. (a) Set the No. of boards in module for which the network parameters are to be set. Default value : None Setting range : 0~8 (Boards) Modules for the parameter setting with the G(P).RLPASET instruction should not be included in the setting for No. of boards in module. Example) Set 1 (Board). (6/n)
8 (b) Set the Start I/O No. for the master station. Default value : None Setting range : 0000~0FE0 Example) Set (c) Set the Parameter name in Operational Settings. Even if the Parameter name is not set, this will not affect the operation of the CC-Link system. Default value : None Setting range : 8 characters or less Example) Set None. (d) Set the input status for the data link error station in Operation settings. Default value : Clear ( Hold input data not checked) Setting range : Hold ( Hold input data checked) Clear ( Hold input data not checked) Example) Set to Clear ( Hold input data not checked). (e) Set the slave station refresh/compulsory clear setting at programmable controller CPU STOP in Operational settings. Default value : Refresh ( Clears compulsorily not checked) Setting range : Refresh ( Clears compulsorily not checked) Clears compulsorily ( Clears compulsorily checked) Example) Set to Refresh ( Clears compulsorily not checked). (f) Set the station type for Type. Default value : Master station Setting range : Master station, Mastar station(duplex function), Local station, Standby master station Example) Set the Master station. (7/n)
9 (g) Set the CC-Link mode for Mode. Default value : Remote net (Ver.1 mode) Setting range : Remote net (Ver.1 mode), Remote net (Ver.2 mode), Remote net (Additional mode), Remote I/O net mode, Off line Example) Set to Remote net (Ver.1 mode). (h) Set the total number of connected stations in the CC-Link system including reserved stations for All connect count. Default value : 64 (modules) Setting range : 1 to 64 (modules) Example) Set to 2 (modules). (i) Set the number of retries for Retry count, when communication error occurs. Default value : 3 (times) Setting range : 1 to 7 (times) Example) Set to 3 (times). (j) Set the number of modules that can return to system operation by a single link scan for Automatic reconnection station count. Default value : 1 (module) Setting range : 1 to 10 (modules) Example) Set to 1 (module). (k) Set the station number for the standby master station for Standby master station No.. Default value : Blank (No standby master station specified) Setting range : Blank, 1 to 64 (Blank: No standby master station specified) Example) Set to Blank (No standby master station specified). (l) Set the data link status for PLC down select, when a master station programmable controller CPU error occurs. Default value : Stop Setting range : Stop, Continue Example) Set to Stop. (m) Set whether the link scan for the sequence scan is synchronous or asynchronous for Scan mode setting. Default value : Asynchronous Setting range : Asynchronous, Synchronous Example) Set to Asynchronous. (n) Set 0 for the delay time. (8/n)
10 (o) Set the station data for Station information settings. Dafault value : Remote I/O station, single, Occupies 1 station, 32 points, or no setting for reserved stations/error invalid. Setting range : Station type - No setting Remote I/O station Remote device station Intelligent device station (including local staton and standby master station) Expanded cyclic setting (cannot be changed) - single Number of occupied stations - No setting Occupies 1 station Occupies 2 stations Occupies 3 stations Occupies 4 stations Remote station points (cannot be changed) - 32 points [when occupies 1 station] 64 points [when occupies 2 station] 96 points [when occupies 3 station] 128 points [when occupies 4 station] Reserved/invalid station select - No setting Reserved station Invalid station (error invalid station) Intelligent buffer select - No setting Send 0, 64 to 4096 Receive 0, 64 to 4096 Automatic 0, 128 to 4096 Example) Set the station data according to the system configuration specified in Section 4.3. As ME96NSR is remote device station, and the number of occupied stations is 1 station, it becomes the following. (9/n)
11 4.3.2 Master Station Automatic Refresh Parameter Settings (1) The following shows an example of the parameter settings. See (2) for actual settings. (2) Set the automatic refresh parameters using the following procedure. (a) Set the remote input (RX) refresh device for Remote input (RX). Default value : None Setting range : Device name Select from X, M, L, B, D, W, R or ZR. Device number Within the range of the device points that the CPU has. Example) Set to X100 (b) Set the remote output (RY) refresh device for Remote output (RY). Default value : None Setting range : Device name Select from Y, M, L, B, T, C, ST, D, W, R or ZR. Device number Within the range of the device points that the CPU has. Example) Set to Y100. (c) Set the remote register (RWr) refresh device for Remote register (RWr). Default value : None Setting range : Device name Select from M, L, B, D, W, R or ZR. Device number Within the range of the device points that the CPU has. Example) Set to W300. (10/n)
12 (d) Set the remote register (RWw) refresh device for Remote register (RWw). Default value : None Setting range : Device name Select from M, L, B, T, C, ST, D, W, R or ZR. Device number Within the range of the device points that the CPU has. Example) Set to W400. (e) Set the link special relay (SB) refresh device for Special relay (SB). Default value : None Setting range : Device name Select from M, L, B, D, W, R, SB or ZR. Device number Within the range of the device points that the CPU has. Example) Set to SB0. (f) Set the link special register (SW) refresh device for Special register (SW). Default value : None Setting range : Device name Select from M, L, B, D, W, R, SW or ZR. Device number Within the range of the device points that the CPU has. Example) Set to SW0. POINT (1) For the automatic refresh parameter setting, set the start device only. Devices are automatically assigned until the last station number including reserved stations and occupied stations. (2) When setting X, Y, B, W, SB and SW as refresh devices, make setting so that they do not overlap with the device numbers used on the other networks, etc. (11/n)
13 5. Communication Between the Master Station and ME96NSR 5.1 Communication Guideline There are three communication statuses (Initial Communication, Normal Communication, Error Communication) between the Master station and ME96NSR. The following can be performed at normal communication. Monitoring of the measurement values such as the current, voltage and energy, etc. Monitoring of the bit data of the alarm state and the digital input state. Setting the set data of the time constant for current demand. ME96NSR has a special-purpose command for each measurement items and each setting items. It becomes possible to monitor measurement value or to set the setting value by writing the command into the remote register RWw of the master station. Overview of the Command Communication to ME96NSR PLC CPU Master station ME96NSR Word device(ex:w) Command/Data 1 Remote register(rww) Command/Data 2 Remote register (RWw) Command/Data Bit device(ex:y) Command 3 Remote output(ry) Command 4 Remote output(ry) Command execution request Bit device(ex:x) Automatic refresh execution request Remote input(rx) Link scan execution request Command execute Remote input(rx) Command 6 Command 5 Command completion reply completion reply completion reply Word device(ex:w) Remote register(rwr) Remote register(rwr) Reply data to command 8 Reply data to command 7 Reply data to command 1 By automatic refresh, command and data stored in the word device of PLC CPU are stored in the remote register RWw of the master station. 2 By link scan, command and data stored in the remote register RWw of the master station are sent to ME96NSR, and is stored in the remote register RWw of the ME96NSR. 3 By automatic refresh, command execution request stored in the bit device of PLC CPU is stored in the remote output RY of the master station. 4 By link scan, command execution request stored in the remote output RY of the master station is sent to ME96NSR, and is stored in the remote output RY of the ME96NSR. And then ME96NSR executes the command and data. 5 By link scan, command completion reply stored in the remote input RX of the ME96NSR is sent to the master station, and is stored in the remote input RX of the master station. 6 By automatic refresh, command completion reply stored in the remote input RX of the master station is stored in the bit device of the PLC CPU. 7 By link scan, reply data to command stored in the remote register RWr of the ME96NSR is sent to the master station, and is stored in the remote register RWr of the master station. 8 By automatic refresh, reply data to command stored in the remote register RWr of the master station is stored in the word device of the PLC CPU. (12/n)
14 5.2 Initial Communication Initial communication is performed at the beginning after the power supply is turned on or hardware is reset. Refer to section 6.1 about the remote input RX and the remote output RY. RX(n+1)8 (Initial data processing request flag) RY(n+1)8 (Initial data setting copletion flag) 3 RX(n+1)B (Remote READY) 1After the power supply is turned on, or hardware is reset, the initial data processing request flag is turned on by ME96NSR. 2After the initial data processing request flag is turned on, turn on the initial data setting completion flag. 3After the initial data setting completion flag is turned on, the initial data processing request flag is turned off and the remote READY is turned on. 4After the initial data processing request flag is turned off, turned off the initial data setting completion flag. (13/n)
15 5.3 Normal Communication After initial data processing is complete, the normally communication is performed to monitor the measurement values and to set the parameters. Remote register (RWw) RYnF (Command execution request flag) Command and related data RXnF (Command completion reply flag) Remote register (RWr) 3 Reply data 1After writing the command and related data into the remote register RWw, turn on the command execution request flag. 2After receiving the reply data corresponding to the command, the command completion reply flag turned on. 3After the command completion reply flag is turned on, read the reply data from the remote register RWw. 4After reading the reply data, cancel the command execution request by turning off the command execution request flag. 5After the command execution request flag is turned off, the command completion reply flag is turned off. Note: When sending commands successively, repeat 1 to 5 above. The command can be sent only when the remote READY is ON. 5.4 Error Communication RX(n+1)A (Error status flag) Error occurrence RY(n+1)A (Error reset request flag) Remote register (RWr) 2 2 Error code 5 RX(n+1)B Remote READY 1 1When an error occurs in ME96NSR, error status flag is turned on and the remote READY is turned off. 2When the error status flag is turned on, read the error code from the remote register RWr. Eliminate the cause of the error while referring to the red error code. When resuming communication with ME96NSR, turn on the error reset request flag. 3After the error reset request flag is turned on, the error status flag is turned off. 4After the error status flag is turned off, turn off the error reset request flag. 5After the error reset request flag is turned off, the remote READY is turned on and normal communication is resumed. Note: Refer to About error occurrence for error code. (14/n)
16 6. Remote I/O and Remote Register 6.1 Remote Input RX, Remote Output RY The remote input RX and remote output RY are used to communicate for bit data between the master station and ME96NSR Remote input RX The allocation of the remote input RX of ME96NSR is shown in the table below. Device Description Signal name No. OFF(0) ON(1) Note RXn0 Digital input 1 (DI1) OFF ON RXn1 Digital input 2 (DI2) OFF ON RXn2 Digital input 3 (DI3) OFF ON RXn3 Digital input 4 (DI4) OFF ON RXn4 Unusable - - RXn5 Alarm (total) Non-Alarm state Alarm state Note 2 RXn6 Alarm of Demmand current Non-Alarm state Alarm state Note 2 RXn7 Unusable - - RXn8 Alarm of Voltage Non-Alarm state Alarm state Note 2 RXn9 Alarm of Current Non-Alarm state Alarm state Note 2 RXnA Alarm of Active power Non-Alarm state Alarm state Note 2 RXnB Alarm of Reactive power Non-Alarm state Alarm state Note 2 RXnC Alarm of Frequency Non-Alarm state Alarm state Note 2 RXnD Alarm of Power factor Non-Alarm state Alarm state Note 2 RXnE Alarm of T.H.D (Voltage) Non-Alarm state Alarm state Note 2 RXnF Command completion reply flag No receiving of reply date Receiving of reply data Note 1, 4 RX(n+1)0 Unusable - - RX(n+1)1 Unusable - - RX(n+1)2 Unusable - - RX(n+1)3 Unusable - - RX(n+1)4 Unusable - - RX(n+1)5 Unusable - - RX(n+1)6 Unusable - - RX(n+1)7 Unusable - - RX(n+1)8 Initial data processing Power OFF, remote READY Power supply is turned ON or request flag ON, or error status flag ON hardware reset Note 1 RX(n+1)9 Unusable - - RX(n+1)A Error status flag No error occurrence Error occurrence Note 1 RX(n+1)B Remote READY Command sending not Normally communication status possible (Command sending possible) Note 1 RX(n+1)C Unusable - - RX(n+1)D Unusable - - RX(n+1)E Unusable - - RX(n+1)F Unusable - - n: it can be obtained by converting (station number -1) 2 to hexadecimal. Note 1: For the details, refer to 5.Communication Between the Master Station and ME96NSR Note 2: ON(1) shows the state where the upper limit or the lower limit is exceeded. Note 3: The number of alarms which can monitor are 4 items set up at ME96NSR. Note 4: Alarm of harmonics current cannot be shown by remote input RX. (15/n)
17 6.1.2 Remote Output RY Device No. The allocation of the remote output RY of ME96NSR is shown in the table below. Signal name ON(1) OFF(0) Description OFF(0) ON(1) RYn0 Unusable - - RYn1 Unusable - - RYn2 Unusable - - RYn3 Unusable - - RYn4 Unusable - - RYn5 Unusable - - RYn6 Unusable - - RYn7 Unusable - - RYn8 Unusable - - RYn9 Unusable - - RYnA Unusable - - RYnB Unusable - - RYnC Unusable - - RYnD Unusable - - RYnE Unusable - - RYnF Command execution request flag Cancel command request Command request Note 1 RY(n+1)0 Unusable - - RY(n+1)1 Unusable - - RY(n+1)2 Unusable - - RY(n+1)3 Unusable - - RY(n+1)4 Unusable - - RY(n+1)5 Unusable - - RY(n+1)6 Unusable - - RY(n+1)7 Unusable - - RY(n+1)8 Initial data Cancel normal communication Normal communication setting completion flag request request Note 1 RY(n+1)9 Unusable - - RY(n+1)A Error reset request flag Cancel error reset request Error reset request Note 1 RY(n+1)B Unusable - - RY(n+1)C Unusable - - RY(n+1)D Unusable - - RY(n+1)E Unusable - - RY(n+1)F Unusable - - n: it can be obtained by converting (station number -1) 2 to hexadecimal. Note Note 1: For the details, refet to 5.Communication Between the Master Station and ME96NSR Point Do not read or write to unusable remote registers. If reading or writing is performed, the functions of ME96NSR are not guaranteed. (16/n)
18 6.2 Remote Register (RWr, RWw) The remote register RWr and RWw are used to communicate word data between the master station and ME96NSR. Because it occupiers 1 station, the remote registers RWr and RWw each have 4 words in length. ME96NSR has the special-purpose commands for each measurement items and setting items.it becomes possible to monitor each measurement values or set each parameters by writing into the remote register RWw of the master station command and the related data allocated to the item you want to monitor or set Supported Command The commands supported by ME96NSR are listed in the table below. For the details of each commands, refer to Details of Commands. Table 6.1 Suppoted Commands Command Name Descriprion Note page 1H Data Monitor For monitoring measurement 19 2H Data Set For setting measurement 31 Note) 1: The command can be sent only when the remote READY is ON. 2: The command execution request flag and command completion reply flag are used to send the command and receive replay data. For details of each flag, refer to 5.3 Normal Communication. 3: In case of monitoring the present value and its maximum continuously according to the renewal data timing of ME96NSR, the maximum may be smaller than the present value. (17/n)
19 6.2.2 Details of Commands The details of the command and reply data supported by ME96NSR are described here. How to view the details of each command described is the following page is shown below. Command value Command name Description 1H Data Monitor After writing the command as shown below into the remote register RWwm, set the command execution request flag to ON(1). When the command completion reply flag turned on, the specified item is reset. The details of data written into the remote resister RWwm are shown in the table below. Remote register RWwm(PLC ME96NSR) b15 b8 b7 b4 b3 b0 m Group No. Unit No. 1H *1 m+1 00H Channel No. m+2 00H 00H m+3 00H 00H Remote register RWrn(ME96NSR PLC) b15 b8 b7 b0 n Channnel No. Group No. n+1 Index number 00H n+2 Low data n+3 High data m, n: Address is allocated to the master module by the station number setting. Command Contents of the resister sent from the master station to the remote device station (ME96NSR). The command value should be stored in the 1st byte of the resister to be transmitted. Because the length of transmission data is fixed to 4 words, 00H should be stored in areas in which no data is contained. Contents of the resister received by the master station from the remote device station (ME96NSR). Because the length of receive data is fixed to 4 words, 00H is stored in areas in which no reply data is contained. *1: It is described as 8 bits data by combining the unit No. (high 4 bits) and the command (low 4 bits). b7 b4 b3 b0 Command: data range 0H~7H Unit No.: data range 0H~7H 0H and 1H are used in ME96NSR For example, When the unit No. is 0H and the command is 1H, it becomes 01H. (18/n)
20 (1) Data Monitor Command (1H) 1H Data Monitor After writing the command as shown below into the remote register RWwm, set the command excution request flag to ON(1). When the command completion reply frag is turned on, the item specified is reset. The details of the data written into the remote resister RWwm are shown in the table Table 6.2 to Table The item can carry out monitor changes with phase and wiring types. (Refer to Table 6.2 to Table 6.4) Remote register RWwm(PLC ME96NSR) b15 b8 b7 b4 b3 b0 m Group No. Unit No. 1H m+1 00H Channel No. m+2 00H 00H m+3 00H 00H ( )0H and 1H is used in the unit No. of ME96NSR Remote register RWrn(ME96NSR PLC) b15 b8 b7 b0 n Channel No. Group No. n+1 Index number 00H n+2 Low data n+3 High data m, n : Address is allocated to the master module by the station number setting. Note: ME96NSR can monitor the data of the measurement item which is not displayed. (19/n)
21 Unit No. Group (h) Ch. (h) Name of Channel Table 6.2 Group Channel List (1/3) Data Type Note Unit No. 0 F0 2 Model code Average L-N voltage V Inst. 1 *2 0 E0 11 Primary current N voltage V Inst. 1 *2 0 E0 12 Primary voltage(l-l) N voltage V Inst. 1 *2 0 E0 1B Primary voltage(l-n) 4 * N voltage V Inst. 1 *2 0 E0 1C Secondary voltage(l-n) Average L-N voltage V max. 1 *2 0 E0 13 Phase & Wiring N voltage V max. 1 *2 0 E0 18 Alarm Items N voltage V max. 1 *2 0 E0 19 Byte monitor N voltage V max. 1 *2 0 E0 1A reserved Average L-N voltage V min. 1 *2 0 2 E0 Time constant for DA sec N voltage V min. 1 * Average current A Inst N voltage V min. 1 * Phase 1 current A Inst N voltage V min. 1 * Phase 2 current A Inst Total active power kw Inst Phase 3 current A Inst Phase 1 active power kw Inst. 1 * Phase N current A Inst. 1 * Phase 2 active power kw Inst. 1 * Average current A max Phase 3 active power kw Inst. 1 * Phase 1 current A max Total active power kw max Phase 2 current A max Phase 1 active power kw max. 1 * Phase 3 current A max Phase 2 active power kw max. 1 * Phase N current A max. 1 * Phase 3 active power kw max. 1 * Average current A min Total active power kw min Phase 1 current A min Phase 1 active power kw min. 1 * Phase 2 current A min Phase 2 active power kw min. 1 * Phase 3 current A min Phase 3 active power kw min. 1 * Phase N current A min. 1 * Total reactive power kvar Inst Average current demand A Inst Phase 1 reactive power kvar Inst. 1 * Phase 1 current demand A Inst Phase 2 reactive power kvar Inst. 1 * Phase 2 current demand A Inst Phase 3 reactive power kvar Inst. 1 * Phase 3 current demand A Inst Total reactive power kvar max Phase N current demand A Inst. 1 * Phase 1 reactive power kvar max. 1 * Average current demand A max Phase 2 reactive power kvar max. 1 * Phase 1 current demand A max Phase 3 reactive power kvar max. 1 * Phase 2 current demand A max Total reactive power kvar min Phase 3 current demand A max Phase 1 reactive power kvar min. 1 * Phase N current demand A max. 1 * Phase 2 reactive power kvar min. 1 * Average current demand A min Phase 3 reactive power kvar min. 1 * Phase 1 current demand A min B 1 Total apparent power kva Inst. 1 * Phase 2 current demand A min B 21 Phase 1 apparent power kva Inst. 1 * Phase 3 current demand A min B 41 Phase 2 apparent power kva Inst. 1 * Phase N current demand A min. 1 *2 1 0B 61 Phase 3 apparent power kva Inst. 1 * Average L-L voltage V Inst B 2 Total apparent power kva max. 1 * voltage V Inst B 22 Phase 1 apparent power kva max. 1 * voltage V Inst B 42 Phase 2 apparent power kva max. 1 * voltage V Inst B 62 Phase 3 apparent power kva max. 1 * Average L-L voltage V max B 5 Total apparent power kva min. 1 * voltage V max B 25 Phase 1 apparent power kva min. 1 * voltage V max B 45 Phase 2 apparent power kva min. 1 * voltage V max B 65 Phase 3 apparent power kva min. 1 * Average L-L voltage V min voltage V min voltage V min voltage V min. 1 Group (h) Ch. (h) Name of Channel Data Type Note *1: Cannot be used by 3P4W. *2: Can only be used by 3P4W. H.A: Current Harmonics H.V: Voltage Harmonics D.ratio: Distortion ratio Inst.: Instantaneous value (20/n)
22 Unit No. Group (h) Ch. (h) Name of Channel Table 6.3 Group Channel List (2/3) Data Type Note Unit No. Group (h) Ch. (h) Name of Channel 0 0D 1 Total power factor % Inst B 21 1-N H.V V Inst. Total 1 *2 0 0D 21 Phase 1 power factor % Inst. 1 * N H.V V Inst. 1st 1 *2 0 0D 41 Phase 2 power factor % Inst. 1 * N H.V V Inst. 3rd 1 *2 0 0D 61 Phase 3 power factor % Inst. 1 * N H.V V Inst. 5th 1 *2 0 0D 2 Total power factor % max B 21 1-N H.V V Inst. 7th 1 *2 0 0D 22 Phase 1 power factor % max. 1 *2 1 3D 21 1-N H.V V Inst. 9th 1 *2 0 0D 42 Phase 2 power factor % max. 1 *2 1 3F 21 1-N H.V V Inst. 11th 1 *2 0 0D 62 Phase 3 power factor % max. 1 * N H.V V Inst. 13th 1 *2 0 0D 5 Total power factor % min N H.V D. ratio % Inst. Total 1 *2 0 0D 25 Phase 1 power factor % min. 1 * N H.V D. ratio % Inst. 3rd 1 *2 0 0D 45 Phase 2 power factor % min. 1 * N H.V D. ratio % Inst. 5th 1 *2 0 0D 65 Phase 3 power factor % min. 1 * N H.V D. ratio % Inst. 7th 1 *2 0 0F 1 Frequency Hz Inst N H.V D. ratio % Inst. 9th 1 *2 0 0F 2 Frequency Hz max B 1-N H.V D. ratio % Inst. 11th 1 *2 0 0F 5 Frequency Hz min D 1-N H.V D. ratio % Inst. 13th 1 * H.V V Inst. Total 1 *1 0 4B 41 2-N H.V V Inst. Total 1 *2 0 4D H.V V Inst. 1st 1 * N H.V V Inst. 1st 1 *2 0 4F H.V V Inst. 3rd 1 * N H.V V Inst. 3rd 1 * H.V V Inst. 5th 1 * N H.V V Inst. 5th 1 * H.V V Inst. 7th 1 *1 1 3B 41 2-N H.V V Inst. 7th 1 * H.V V Inst. 9th 1 *1 1 3D 41 2-N H.V V Inst. 9th 1 * H.V V Inst. 11th 1 *1 1 3F 41 2-N H.V V Inst. 11th 1 * H.V V Inst. 13th 1 * N H.V V Inst. 13th 1 * H.V D. ratio % Inst. Total 1 * C 2-N H.V D. ratio % Inst. Total 1 * H.V D. ratio % Inst. 3rd 1 * N H.V D. ratio % Inst. 3rd 1 * H.V D. ratio % Inst. 5th 1 * B 2-N H.V D. ratio % Inst. 5th 1 * H.V D. ratio % Inst. 7th 1 * D 2-N H.V D. ratio % Inst. 7th 1 * H.V D. ratio % Inst. 9th 1 * F 2-N H.V D. ratio % Inst. 9th 1 * B 1-2 H.V D. ratio % Inst. 11th 1 * N H.V D. ratio % Inst. 11th 1 * D 1-2 H.V D. ratio % Inst. 13th 1 * N H.V D. ratio % Inst. 13th 1 * H.V V Inst. Total 1 *1 0 4B 61 3-N H.V V Inst. Total 1 *2 0 4D H.V V Inst. 1st 1 * N H.V V Inst. 1st 1 *2 0 4F H.V V Inst. 3rd 1 * N H.V V Inst. 3rd 1 * H.V V Inst. 5th 1 * N H.V V Inst. 5th 1 * H.V V Inst. 7th 1 *1 1 3B 61 3-N H.V V Inst. 7th 1 * H.V V Inst. 9th 1 *1 1 3D 61 3-N H.V V Inst. 9th 1 * H.V V Inst. 11th 1 *1 1 3F 61 3-N H.V V Inst. 11th 1 * H.V V Inst. 13th 1 * N H.V V Inst. 13th 1 * C 2-3 H.V D. ratio % Inst. Total 1 * B2 3-N H.V D. ratio % Inst. Total 1 * H.V D. ratio % Inst. 3rd 1 * F 3-N H.V D. ratio % Inst. 3rd 1 * B 2-3 H.V D. ratio % Inst. 5th 1 * A1 3-N H.V D. ratio % Inst. 5th 1 * D 2-3 H.V D. ratio % Inst. 7th 1 * A3 3-N H.V D. ratio % Inst. 7th 1 * F 2-3 H.V D. ratio % Inst. 9th 1 * A5 3-N H.V D. ratio % Inst. 9th 1 * H.V D. ratio % Inst. 11th 1 * A7 3-N H.V D. ratio % Inst. 11th 1 * H.V D. ratio % Inst. 13th 1 * A9 3-N H.V D. ratio % Inst. 13th 1 * DE L-L H.V D. ratio % max. Total 1 * DE L-N H.V D. ratio % max. Total 1 *2 0 4D A2 L-L H.V V max. 1st 1 * A2 L-N H.V V max. 1st 1 * CB L-L H.V D. ratio % max. 3rd 1 * CB L-N H.V D. ratio % max. 3rd 1 * CD L-L H.V D. ratio % max. 5th 1 * CD L-N H.V D. ratio % max. 5th 1 * CF L-L H.V D. ratio % max. 7th 1 * CF L-N H.V D. ratio % max. 7th 1 * D1 L-L H.V D. ratio % max. 9th 1 * D1 L-N H.V D. ratio % max. 9th 1 * D3 L-L H.V D. ratio % max. 11th 1 * D3 L-N H.V D. ratio % max. 11th 1 * D5 L-L H.V D. ratio % max. 13th 1 * D5 L-N H.V D. ratio % max. 13th 1 *2 Data Type Note *1: Cannot be used by 3P4W. *2: Can only be used by 3P4W. H.A: Current Harmonics H.V: Voltage Harmonics D.ratio: Distortion ratio Inst.: Instantaneous value (21/n)
23 Unit No. Group (h) Ch. (h) Name of Channel Table 6.4 Group Channel List (3/3) Data Type Note Unit No. Group (h) Ch. (h) Name of Channel Phase 1 H.A A Inst. Total A2 H.A A max. Total 1 0 1D 21 Phase 1 H.A A Inst. 1st 1 0 1D A2 H.A A max. 1st 1 0 1F 21 Phase 1 H.A A Inst. 3rd 1 0 1F A2 H.A A max. 3rd Phase 1 H.A A Inst. 5th A2 H.A A max. 5th Phase 1 H.A A Inst. 7th A2 H.A A max. 7th Phase 1 H.A A Inst. 9th A2 H.A A max. 9th Phase 1 H.A A Inst. 11th A2 H.A A max. 11th Phase 1 H.A A Inst. 13th A2 H.A A max. 13th Phase 1 H.A D. ratio % Inst. Total Phase N H.A A max. Total 1 * Phase 1 H.A D. ratio % Inst. 3rd 1 1 1D 82 Phase N H.A A max. 1st 1 * Phase 1 H.A D. ratio % Inst. 5th 1 1 1F 82 Phase N H.A A max. 3rd 1 * Phase 1 H.A D. ratio % Inst. 7th Phase N H.A A max. 5th 1 * Phase 1 H.A D. ratio % Inst. 9th Phase N H.A A max. 7th 1 * B Phase 1 H.A D. ratio % Inst. 11th Phase N H.A A max. 9th 1 * D Phase 1 H.A D. ratio % Inst. 13th Phase N H.A A max. 11th 1 * Phase 2 H.A A Inst. Total Phase N H.A A max. 13th 1 *2 0 1D 41 Phase 2 H.A A Inst. 1st active energy import kwh count 2 0 1F 41 Phase 2 H.A A Inst. 3rd active energy export kwh count Phase 2 H.A A Inst. 5th active energy import kwh count expand Phase 2 H.A A Inst. 7th active energy export kwh count expand Phase 2 H.A A Inst. 9th reactive energy import lag kvar count Phase 2 H.A A Inst. 11th reactive energy export lag kvar count Phase 2 H.A A Inst. 13th reactive energy import lead kvar count C Phase 2 H.A D. ratio % Inst. Total reactive energy export lead kvar count Phase 2 H.A D. ratio % Inst. 3rd reactive energy import lag kvar count expand B Phase 2 H.A D. ratio % Inst. 5th reactive energy export lag kvar count expand D Phase 2 H.A D. ratio % Inst. 7th reactive energy import lead kvar count expand F Phase 2 H.A D. ratio % Inst. 9th reactive energy export lead kvar count expand Phase 2 H.A D. ratio % Inst. 11th current upper limit A Alarm Phase 2 H.A D. ratio % Inst. 13th current lower limit A Alarm Phase 3 H.A A Inst. Total current upper limit A Alarm PhaseN 1 *2 0 1D 61 Phase 3 H.A A Inst. 1st current demand upper limit A Alarm 1 0 1F 61 Phase 3 H.A A Inst. 3rd current demand lower limit A Alarm Phase 3 H.A A Inst. 5th current demand upper limit A Alarm PhaseN 1 * Phase 3 H.A A Inst. 7th voltage upper limit(l-l) V Alarm Phase 3 H.A A Inst. 9th voltage lower limit(l-l) V Alarm Phase 3 H.A A Inst. 11th voltage upper limit(l-n) V Alarm 1 * Phase 3 H.A A Inst. 13th voltage lower limit(l-n) V Alarm 1 * B2 Phase 3 H.A D. ratio % Inst. Total active power upper limit kw Alarm F Phase 3 H.A D. ratio % Inst. 3rd active power lower limit kw Alarm A1 Phase 3 H.A D. ratio % Inst. 5th reactive power upper limit kvar Alarm A3 Phase 3 H.A D. ratio % Inst. 7th reactive power lower limit kvar Alarm A5 Phase 3 H.A D. ratio % Inst. 9th 1 0 0D 14 power factor upper limit % Alarm A7 Phase 3 H.A D. ratio % Inst. 11th 1 0 0D 15 power factor lower limit % Alarm A9 Phase 3 H.A D. ratio % Inst. 13th 1 0 0F 14 Frequency upper limit Hz Alarm Phase N H.A A Inst. Total 1 *2 0 0F 15 Frequency lower limit Hz Alarm 1 0 1D 81 Phase N H.A A Inst. 1st 1 * E1 H.V(L-N) upper limit % Alarm Total 1 *2 0 1F 81 Phase N H.A A Inst. 3rd 1 * E1 H.V(L-L) upper limit % Alarm Total 1 * Phase N H.A A Inst. 5th 1 * E1 H.A upper limit A Alarm Total Phase N H.A A Inst. 7th 1 * F1 H.A upper limit(phase N) A Alarm Total 1 * Phase N H.A A Inst. 9th 1 *2 0 A0 31 Alarm state Alarm Phase N H.A A Inst. 11th 1 *2 0 A0 35 Alarm state2 Alarm Phase N H.A A Inst. 13th 1 * C8 Phase N H.A D. ratio % Inst. Total 1 * B5 Phase N H.A D. ratio % Inst. 3rd 1 *2 *1: Cannot be used by 3P4W B7 Phase N H.A D. ratio % Inst. 5th 1 *2 *2: Can only be used by 3P4W B9 Phase N H.A D. ratio % Inst. 7th 1 *2 H.A: Current Harmonics 1 75 BB Phase N H.A D. ratio % Inst. 9th 1 *2 H.V: Voltage Harmonics 1 75 BD Phase N H.A D. ratio % Inst. 11th 1 *2 D.ratio: Distortion ratio 1 75 BF Phase N H.A D. ratio % Inst. 13th 1 *2 Inst.: Instantaneous value Data Type Note (22/n)
24 Table 6.5 Data Format (1/6) Data Measurement Items Index number High data Data Format 1 Low data Current, Voltage, Active power, Reactive power, Apparent power, Power factor, Frequency, etc. b7 Multiplicand b0 b31 b24 b23 b16 Numeric value: 32-bit integer with a sign ~ ( H~7FFFFFFFH) b15 b8 b7 b0 <Multiplicand> Format1 Multiplicand is fixed for every item according to primary current, primary voltage, and phase wiring. (Refer to p. 30.) Index number = 03H: The actual value is 1000 times the numeric value. Index number = 02H: The actual value is 100 times the numeric value. Index number = 01H: The actual value is 10 times the numeric value. Index number = 00H: The actual value is the numeric value. Index number = FFH: The actual value is 1/10 times the numeric value. Index number = FEH: The actual value is 1/100 times the numeric value. Index number = FDH: The actual value is 1/1000 times the numeric value. <Example: Active power> Data Multiplicand Numeric value Actual value FF000000FFH FFH 1/ FFH /10 = 25.5[kW] FFH 00H FFH = 255[kW] FFFFFFFF01H FFH 1/10 FFFFFF01H /10 = -25.5[kW] 00FFFFFF01H 00H 1 FFFFFF01H = -255[kW] Note: When the elements are active power and reactive power in case of a data monitor, ±1638.3MW becomes the upper(lower) value. (23/n)
25 Table 6.6 Data Format (2/6) Data Measurement Items Index number High data Data Format 2 Low data Active energy Reactive energy b7 b0 b31 b24 b23 b16 b15 b8 b7 b0 Format2 Multiplicand Numeric value: 32-bit integer with a sign However, the effective numerical value is 0~ (0H~F423FH) <Multiplicand> Multiplicand is fixed for every item according to primary current, primary voltage, and phase wiring. (Refer to p. 30.) Index number = 03H: The actual value is 1000 times the numeric value. Index number = 02H: The actual value is 100 times the numeric value. Index number = 01H: The actual value is 10 times the numeric value. Index number = 00H: The actual value is the numeric value. Index number = FFH: The actual value is 1/10 times the numeric value. Index number = FEH: The actual value is 1/100 times the numeric value. Index number = FDH: The actual value is 1/1000 times the numeric value. Index number = FCH: The actual value is 1/10000 times the numeric value. Index number = FBH: The actual value is 1/ times the numeric value. <Example: Active Energy> Data Multiplicand Numeric value Actual value FF000000FFH FFH 1/ FFH /10 = 25.5[kWh] FFH 00H FFH = 255[kWh] (24/n)
26 Data Alarm state Table 6.7 Data Format (3/6) Data Format 3 Index number High data Low data Format3 b7 b0 b31 b24 b23 b16 b15 b8 b7 b0 Multiplicand (=00H (fixed)) Alarm state Unused (=0000H (fixed)) <The allocation of the alarm state 1> Bit Data Content OFF(0) ON(1) b16 Digital input 1 (DI1) OFF ON b17 Digital input 2 (DI2) OFF ON b18 Digital input 3 (DI3) OFF ON b19 Digital input 4 (DI4) OFF ON b20 Unusable - - b21 Alarm (total) Non-Alarm Alarm b22 Alarm of Demand current (*1) Non-Alarm Alarm b23 Unusable - - b24 Alarm of Voltage (*1) Non-Alarm Alarm b25 Alarm of Current (*1) Non-Alarm Alarm b26 Alarm of Active power (*1) Non-Alarm Alarm b27 Alarm of Reactive power (*1) Non-Alarm Alarm b28 Alarm of Frequency Non-Alarm Alarm b29 Alarm of Power factor (*1) Non-Alarm Alarm b30 Alarm of T.H.D(Voltage) (*1) Non-Alarm Alarm b31 Alarm of Harmonics current (*1) Non-Alarm Alarm *1: As for the alarm judging items, refer to next page. <The allocation of the alarm state 2> Bit Data Content OFF(0) ON(1) b16 Upper limit alarm of current (phase 1) Non-Alarm Alarm b17 Upper limit alarm of current (phase 2) Non-Alarm Alarm b18 Upper limit alarm of current (phase 3) Non-Alarm Alarm b19 Upper limit alarm of current (phase N) Non-Alarm Alarm b20 Upper limit alarm of current (total) (*2) Non-Alarm Alarm b21 Lower limit alarm of current (total) (*2) Non-Alarm Alarm b22 Upper limit alarm of L-L Voltage (total) Non-Alarm Alarm b23 Lower limit alarm of L-L Voltage (total) Non-Alarm Alarm b24 Upper limit alarm of L-N Voltage (1-N) Non-Alarm Alarm b25 Upper limit alarm of L-N Voltage (2-N) Non-Alarm Alarm b26 Upper limit alarm of L-N Voltage (3-N) Non-Alarm Alarm b27 Upper limit alarm of L-N Voltage (total) Non-Alarm Alarm b28 Lower limit alarm of L-N Voltage (1-N) Non-Alarm Alarm b29 Lower limit alarm of L-N Voltage (2-N) Non-Alarm Alarm b30 Lower limit alarm of L-N Voltage (3-N) Non-Alarm Alarm b31 Lower limit alarm of L-N Voltage (total) Non-Alarm Alarm *2: As for the alarm judging items, refer to next page. (25/n)
27 <Continuation> Data Alarm state Data Format 3 Alarm judging items of each phase wiring is shown in the following. Format3 Alarm judging items for 3P3W Upper limit Lower limit Demand current Phase 1, 2, 3 Phase 1, 2, 3 Voltage Phase 1-2, 2-3, 3-1 Phase 1-2, 2-3, 3-1 Current Phase 1, 2, 3 Phase 1, 2, 3 Active power ΣW ΣW Reactive power Σvar Σvar Power factor ΣPF ΣPF Harmonics voltage Phase 1-2, Harmonics current Phase 1, 2, 3 - Alarm judging items for 3P4W Upper limit Lower limit Demand current Phase 1, 2, 3, N Phase 1, 2, 3 Voltage Phase 1-2, 2-3, 3-1, Phase 1-2, 2-3, 3-1, Phase 1-N, 2-N, 3-N Phase 1-N, 2-N, 3-N Current Phase 1, 2, 3, N Phase 1, 2, 3 Active power ΣW ΣW Reactive power Σvar Σvar Power factor ΣPF ΣPF Harmonics voltage Phase 1-N, 2-N, 3-N - Harmonics current Phase 1, 2, 3, N - (26/n)
28 Data Set-up Primary current Primari voltage (L-L) Primary voltage (L-N) Secondary volatage (L-N) Index number Table 6.8 Data Format (4/6) High data Data Format 4 b7 b0 b31 b24 b23 b16 b15 b8 b7 b0 Multiplicand Numeric value: 32-bit integer with a sign ~ ( H~7FFFFFFFH) Low data <Multiplicand> Format4 Multiplicand is fixed for every item according to primary current, primary voltage, and phase wiring. (Refer to p. 30.) Index number = 00H: The actual value is the numeric value. Index number = FFH: The actual value is 1/10 times the numeric value. <Example: Primary current, Primary voltage> Set-up value Multiplicand Numeric value Data Set-up value = 100.0A 1/10times FFH E8H FF000003E8H (Effective range = one place of decimals) Set-up value = 400A 1 times 00H H H (Effective range = Integer) Set-up value = 110.0V 1/10times FFH CH FF00000FFCH (Effective range = one place of decimals) Set-up value = 3300V 1 times 00H CE4H CE4H (Effective range = Integer) (27/n)
29 Data Set-up Phase wiring Time constant for DA Model code 16bit set register Format5 Index number <Data(Numeric value)> Phase wiring Table 6.9 Data Format (5/6) High data Data Format 5 b7 b0 b31 b24 b23 b16 b15 b8 b7 b0 Multiplicand (=00H(fixed)) Numeric value: 32-bit integer with a sign ~ ( H~7FFFFFFFH) :3P3W_2CT = 03H :3P4W = 04H :3P3W_3CT = 06H b31~b8: 0 fixed Low data Time constant for demand :The range of 0(= 0H) to 1800 seconds(= 708H)can be set up per second Model code : 10H Model code of ME96NSR.(Fixed data) b31~b8: 0 fixed 16bit set register Bit Data Content OFF(0) ON(1) b16 Reset of all alarm executed b17 Reset of all max/min value and counting of energy executed b18 Reset of all max/min value executed b19 Unusable b20 Unusable b21 Unusable b22 Unusable b23 Unusable b24 Reset of all digital input latch executed b25 Unusable b26 Unusable b27 Unusable b28 Unusable b29 Unusable b30 Reset of counting of all energy executed b31 Unusable (28/n)
30 Table 6.10 Data Format (6/6) Data Set-up Alarm item Index number Data Format 6 High data Low data b7 b0 b31 b24 b23 b16 b15 b8 b7 b0 Format6 00H(fixed) Alarm item 1 Alarm item 2 Alarm item 3 Alarm item 4 Note: The numbers of alarms which can set are 4 items. <Content of alarm items> Data 00H 01H 02H 03H 09H 0AH 0BH 11H 12H 13H 14H 15H 16H 19H 1AH 1BH 1CH 1DH 1EH 1FH 20H 21H Explanation No alarm The upper limit alarm of current The lower limit alarm of current The upper limit alarm of phase N current The upper limit alarm of current demand The lower limit alarm of current demand The upper limit alarm of phase N current demand The upper limit alarm of L-L voltage The lower limit alarm of L-L voltage The upper limit alarm of L-N voltage The lower limit alarm of L-N voltage The upper limit alarm of active power The lower limit alarm of active power The upper limit alarm of reactive power The lower limit alarm of reactive power The upper limit alarm of power factor The lower limit alarm of power factor The upper limit alarm of frequency The lower limit alarm of frequency The upper limit alarm of current harmonics The upper limit alarm of voltage harmonics The upper limit alarm of phase N current harmonics (29/n)
31 Effective Range and Multiplicand The conditions of multiplying factor by setup of each element are shown befow. Element Condition Multiplying factor 0V~440V less than 0.1 Primary voltage 440V or more 1 0A~4A less than A~40A less than 0.01 Primary current 40A~400A less than 0.1 Voltage Harmonics voltage Current Current demand Harmonics current Actige power Reactive power Apparent power Active energy Reactive energy Active energy (extended) Reactive energy (extended) Primary rated power Primary rated power Primary rated power 400A or more 1 0kW~1.2kW less than kW~12kW less than kW~120kW less than kW~1200kW less than kW~12000kW less than kW~120000kW less than kW or more 100 0kW~10kW less than kW~100kW less than kW~1000kW less than kW~10000kW less than kW~100000kW less than kW or more kW~10kW less than kW~100kW less than kW~1000kW less than kW~10000kW less than kW~100000kW less than kW or more 1 Frequency 0.1 Power foctor 0.1 Harmonics distortion 0.1 How to calculate primary rated power. Primary rated power[kw]= α (Primary voltage) (Primary current) 1000 α: 3 3P3W_2CT,3P3W_3CT 3 3P4W (30/n)
32 (2) Data Set Command (2H) 2H Data Set After writing the command as shown below into the remote register RWwm, set the command execution request flag to ON (1). When the command completion reply flag is turned on, the specified item is reset. The details of the data written into the remote resister RWwm are shown in the Table 6.5 to Table After writing the set-up value, about 0.5 seconds ( max 2 seconds) is needed to restart the measurement based on new set-up value. If you write the set-up value continuously, please give about 0.5 seconds ( max 2 seconds) between the set up value. Remote register RWwm (PLC ME96NSR) b15 b8 b7 b4 b3 b0 m Group No. 0H (Unit.No) 2H m+1 Index number Channel No. m+2 Low data m+3 High data ( )At data set, Unit No. is fixed 0H in ME96NSR. Remote register RWrn (ME96NSR PLC) b15 b8 b7 b0 n Channel No. Group No. n+1 00H 00H n+2 00H 00H n+3 00H 00H m, n : Address is allocated to the master module by the station number setting. (31/n)
33 Table 6.11 List of Group and Channel for Set-up Hex. Group Channel Content name Range Setting unit E0 11 Primary current (Note1) 4 E0 12 Primary voltage(l-l) (Note2) 4 E0 1B Primary voltage(l-n) (Note3) 4 E0 1C Secondary voltage 63.5V,100V,110V,115V,120V,220V 3P3W:100V,110V,220V 3P4W:Except for 220V E0 13 Phase & Wiring 3P3W_2CT,3P3W_3CT,3P4W 5 E0 18 Alarm Items Refer to Table E0 Time constant for DA 0~1800s (Note4) active energy import 0~ Multiplicand(Note5) 1 Multiplicand active energy expoer 0~ Multiplicand(Note5) 1 Multiplicand reactive energy import LAG 0~ Multiplicand(Note5) 1 Multiplicand reactive energy export LAG 0~ Multiplicand(Note5) 1 Multiplicand reactive energy import LEAD 0~ Multiplicand(Note5) 1 Multiplicand reactive energy export LEAD 0~ Multiplicand(Note5) 1 Multiplicand current upper limit 5% to 120% of primary current 1%step Initial value: 100% current lower limit 3% to 95% of primary current 1%step Initial value: 10% current upper limit(phase N) 5% to 120% of primary current 1%step Initial value: 100% current demand upper limit 5% to 120% of primary current 1%step Initial value: 100% current demand lower limit 3% to 95% of primary current 1%step Initial value: 10% current demand upper limit (Phase N) 5% to 120% of primary current 1%step Initial value: 100% voltage upper limit (L-L) 25% to 135% of primary voltage 1%step Initial value: 110% voltage lower limit (L-L) 20% to 95% of primary voltage 1%step Initial value: 70% voltage upper limit (L-N) 25% to 135% of primary voltage 1%step Initial value: 110% voltage lower limit (L-N) 20% to 95% of primary voltage 1%step Initial value: 70% active power upper limit -95% to 120% of rated active power 1%step Initial value: 100% active power lower limit -120% to 95% of rated active power 1%step Initial value: 3% reactive power upper limit -95% to 120% of rated reactive power 1%step Initial value: 100% reactive power lower limit -120% to 95% of rated reactive power 1%step Initial value: 3% 1 0D 14 power factor upper limit to to step Initial value: D 15 power factor lower limit to to step Initial value: F 14 Frequency upper limit 45.0 to 65.0Hz 1Hz step Initial value: 65Hz 1 0F 15 Frequency lower limit 45.0 to 65.0Hz 1Hz step Initial value: 45Hz 1 77 E1 H.V(L-N) upper limit 0.5% to 20.0% 0.5%step Initial value: 3.5% 1 76 E1 H.V(L-L) upper limit 0.5% to 20.0% 0.5%step Initial value: 3.5% 1 75 E1 H.A upper limit 5% to 120% 1%step Initial value:35% 1 75 F1 H.A upper limit (Phase N) 5% to 120% 1%step Initial value:35% 1 A1 3A 16bit set register Refer to Table When the group No. or channel No. of the above is not specified, the error code of invalid number is replied. When out of the range is set, the error code of invalid data is replied, and set-up value is not changed. Data Type 4 (32/n)
34 Note1: From the most significant digit to 2 figures can be freely set up in the range of 5A to 30000A. Note2: The set-up range is different by setting of phase wiring. At 3P4W Corresponds to only 190V, 415V, 440V, setting vaule is changed as follows. Setting value Using VT/ Direct input Direct Voltage VT secondary Voltage VT primary Voltage 190V Direct input 110V/190V 415V Using VT 63.5V/110V 240V/415V 440V Using VT 63.5V/110V 254V/440V At 3P3W_2CT,3P3W_3CT When set in the range from 221V to V It is set Using VT, and sets the primary voltage which is transmitted. From the most significant digit to 3 figures can be freely set up in the range of 221V to V. At 110V or 220V It is set Direct input, and sets the primary voltage which is transmitted as the direct input voltage. Note3: The set-up range is different by setting of phase wiring. At 3P4W When set in the range from 278V to V It is set Using VT, and sets the primary voltage which is transmitted. From the most significant digit to 3 figures can be freely set up in the range of 278V to V. At the 63.5V, 100V, 110V, 220V, 240V, 254V or 277V It is set Direct input, and sets the primary voltage which is transmitted as the direct input voltage. At 3P3W_2CT,3P3W_3CT The error code of invalid channel number is replied. Note4: The range of time constant is as follows. It is set by seconds. 0s, 10s, 20s, 30s, 40s, 50s, 1min, 2min, 3min, 4min, 5min, 6min, 7min, 8min, 9min, 10min, 15min, 20min, 25min, 30min. Note5: The multiplicand value is changed by the set-up value of phase wiring, primary voltage, and primary current. (Refer to P. 30) (33/n)
35 6.2.3 About Error Occurrence When the command and related data transmitted to ME96NSR is improper or ME96NSR is in H/W error, RX(n+1)A (Error status flag) becomes 1(ON), the error code shown in Table 6.12 is returned as reply data. Table 6.12 Error Code Error Description Error Code (Hex.) Illegal command or packet length Invalid group number Invalid channel number ME96NSR is in set-up mode or test mode Invalid data for set-up It is not set the item of alarm 40h 41h 42h 43h,44h 51h 55h If an error occurs, the error code is written into the RWrn as shown in the figure below, and RX(n+1)A (error status flag) is turned on (error occurrence) and RX(n+1)B (remote READY) is turned off (normal communication stop). For the error resetting method, refer to 5.4 Error Communication. (1) At the command No. is in range Remote register RWrn b15 b8 b7 b0 n Channel No. Group No. n+1 00H 00H n+2 00H Error code n+3 00H 00H (2) At the command No. is out of range Remote register RWrn b15 b8 b7 b0 n 00H Error code n+1 00H 00H n+2 00H 00H n+3 00H 00H (34/n)
36 7. Abbreviations and Special Terms Abbreviations and special terms used in this manual are shown below: Abbreviation and Special Terms Master station Local station Remote I/O station Remote device station Remote station Intelligent device station RX RY RWw RWr Command Demand value Description Station which controls remote stations and local stations. One station is required for one system. Station with the CPU which can communicate with master station and other local stations. Remote station which deals with bit information only. Remote station which deals with bit information and word information. General name for remote I/O station and remote device station. Controlled by a master station. Station that can perfom transient transmission. Remote input Remote output Remote resister (write area) Remote resister (read area) Identification code allocated to items to be monitored or set. ME96NSR uses a special-purpose command that is transmitted to monitor each measurement value or set each parameter. The demand value is an approximate average value during the demand time period. When it is set to 0, each demand present value becomes equivalent to the present value. (35/n)
37 8. Program Example 8.1 Program Content This program example is assumed the system configuration in below. In the program, at first, the parameters of the linked number and station information are set, and the data link with the parameter of buffer memory startes up. Next, the reading data shown in below is monitored continuously. Also, this program is made by using SW8D5C-GPPW GX Developer. 8.2 System Configuration Q series programmable controller Slot No.0 Power Unit CPU Unit CC-Link Master Unit CC-Link dedicated cable Terminal resistor Terminal resistor Station number: 1 ME96NSR Station number: 2 ME96NSR Reading data Station number 1: ME96NSR Station number 2: ME96NSR Phase 1 current, Phase 2 current, Phase 3 current, 1-N voltage, 2-N voltage, 3-N voltage, Phase 1 active power, Phase 2 active power, Phase 3 active power Active energy (import), Average current, Average L-N voltage, Total active power, Total reactive power, Total power factor, Frequency (36/n)
38 8.3 Device Allocation Allocation of transmitted device Items Contents Device No. Note Station number 1:Remote input (RX00 to RX1F) X100 to X11F Set X100 to remote Remote input(rx) input(rx) refresh Station number 2:Remote input (RX20 to RX3F) X120 to X13F device. Remote output(ry) Station number 1:Remote output (RY00 to RY1F) Y100 to Y11F Set Y100 to remote output(ry) refresh Station number 2:Remote output (RY20 to RY3F) Y120 to Y13F device. Remote register(rwr) Station number 1:Remote register(rwr0 to RWr3) W300 to W303 Set W300 to remote register(rwr) Station number 2:Remote register (RWr4 to RWr7) W304 to W307 refresh device. Remote register(rww) Station number 1:Remote register (RWw0 to RWw3) W400 to W403 Set W400 to remote register(rww) Station number 2:Remote register (RWw4 to RWw7) W404 to W407 refresh device. Set SB0 to link Link special relay(sb) Link special relay of master station(sb0 to SB01FF) SB0 to SB01FF special relay(sb) refresh device. Link special register(sw) Number of taking items Number of taken items Send data items Writing send data Reading recive data Error code Monitor data Data link status Command setting Transmitting completion Link special register of master station (SW0 to SW01FF) Station number 1: Number of monitoring items Station number 2: Number of monitoring items Station number 1: For calculation of number of taken items. Station number 2: For calculation of number of taken items. Station number 1: Send data for monitoring Station number 2: Send data for monitoring Station number 1: Data for writing RWw Station number 2: Data for writing RWw Station number 1: Data for reading RWr Station number 2: Data for reading RWr Station number 1: Error code Station number 2: Error code Station number 1: Monitor data (only numeric value) Station number 2: Monitor data (only numeric value) Station number 1: Data link status Station number 2: Data link status Station number 1: Command setting completion flag Station number 2: Command setting completion flag Station number 1: Transmitting completion flag Station number 2: Transmitting completion flag SW0 to SW01FF D0 D1 D10 D11 D100 to D117 D120 to D133 D400 to D403 D404 to D407 D300 to D303 D304 to D307 D500 to D503 D504 to D504 R0 to R17 R40 to R33 M0 M1 M100 M110 M101 M111 Set SW0 to link special register(sw) refresh device. Number of items are mentioned in section 8.2. Content of items are mentioned in section 8.2. (37/n)
39 8.4 Parameter Settings Parameter settings are set as following with GX Developer Network Parameter Settings and Auto Refresh Parameter Settings The following is shown CC-Link network parameter settings and auto refresh parameter settings. (38/n)
40 8.4.2 Operational Settings Operational settings are as follows Station Information Settings Station information settings are as follows. (39/n)
41 8.5 Program Example (40/n)
42 (41/n)
43 (42/n)
44 (43/n)
45 (44/n)
46 (45/n)
47 (46/n)
48 (47/n)
49 (48/n)
50 9. Test Function Mode ME96NSR has the test function mode which the fixed values are replied if there is no input. It can be used to check the communication to PLC. 9.1 How to Test To do the test, it is necessary to operate the main device. Operate as follows. 1At the state of power failure, turn on the power supply while pressing the DISPLAY of main device. 2After display on the right shows up, take the normal communication. 3Data shown in the next section is replied. When the test is finished, turn off the power supply. 9.2 Reply Data The reply data at test function mode is shown in the next page or later. The reply data takes the value of primary side, but the data of table 9.1 is described the secondary side. It is necessary to convert to the value of primary side using the VT ratio and CT ratio. (Example)At three phase 3-wire, Phase 1 current (Inst.) VT: 6600V/110V, CT: 100A/5A = reply data(secondary side) CT ratio. = 4.11A 100A/5A = 82.2A 1-2 voltage (Inst.) = reply data(secondary side) VT ratio. = 101.1V 6600V/110V = 6066V Total active power (Inst.) = reply data(secondary side) VT ratio CT ratio. = 1041W 6600V/110V 100A/5A = kW (49/n)
51 Table 9.1 Reply data Unit Group Ch. Data No. (h) (h) Name of Channel Type 3P4W reply data (Secondary side) 3P3W_2CT reply data (Secondary side) 3P3W_3CT reply data (Secondary side) Note Data Unit Data Unit Data Unit 0 F0 2 Model code 5 0 E0 11 Primary current 4 0 E0 12 Primary voltage(l-l) 4 0 E0 1B Primary voltage(l-n) 4 0 E0 1C Secondary voltage(l-n) 4 0 E0 13 Phase & Wiring 5 0 E0 18 Alarm Items 6 0 E0 19 Byte monitor 5 0 E0 1A reserved 0 2 E0 Time constant for DA sec Average current A Inst A 4.41 A 4.31 A Phase 1 current A Inst A 4.11 A 4.11 A Phase 2 current A Inst A 4.51 A 4.21 A Phase 3 current A Inst A 4.61 A 4.61 A Phase N current A Inst A Average current A max A 4.42 A 4.32 A Phase 1 current A max A 4.12 A 4.12 A Phase 2 current A max A 4.52 A 4.22 A Phase 3 current A max A 4.62 A 4.62 A Phase N current A max A Average current A min A 4.40 A 4.30 A Phase 1 current A min A 4.10 A 4.10 A Phase 2 current A min A 4.50 A 4.20 A Phase 3 current A min A 4.60 A 4.60 A Phase N current A min A Average current demand A Inst A 4.41 A 4.31 A Phase 1 current demand A Inst A 4.11 A 4.11 A Phase 2 current demand A Inst A 4.51 A 4.21 A Phase 3 current demand A Inst A 4.61 A 4.61 A Phase N current demand A Inst A Average current demand A max A 4.42 A 4.32 A Phase 1 current demand A max A 4.12 A 4.12 A Phase 2 current demand A max A 4.52 A 4.22 A Phase 3 current demand A max A 4.62 A 4.62 A Phase N current demand A max A Average current demand A min A 4.40 A 4.30 A Phase 1 current demand A min A 4.10 A 4.10 A Phase 2 current demand A min A 4.50 A 4.20 A Phase 3 current demand A min A 4.60 A 4.60 A Phase N current demand A min A Average L-L voltage V Inst V V V voltage V Inst V V V voltage V Inst V V V voltage V Inst V V V Average L-L voltage V max V V V voltage V max V V V voltage V max V V V voltage V max V V V Average L-L voltage V min V V V voltage V min V V V voltage V min V V V voltage V min V V V (50/n)
52 3P4W reply data (Secondary side) 3P3W_2CT reply data (Secondary side) 3P3W_3CT reply data (Secondary side) Unit Group Ch. Data No. (h) (h) Name of Channel Type Data Unit Data Unit Data Unit Average L-N voltage V Inst V N voltage V Inst V N voltage V Inst V N voltage V Inst V Average L-N voltage V max V N voltage V max V N voltage V max V N voltage V max V Average L-N voltage V min V N voltage V min V N voltage V min V N voltage V min V Total active power kw Inst W 1041 W 1041 W Phase 1 active power kw Inst W Phase 2 active power kw Inst W Phase 3 active power kw Inst W Total active power kw max W 1042 W 1042 W Phase 1 active power kw max W Phase 2 active power kw max W Phase 3 active power kw max W Total active power kw min W 1040 W 1040 W Phase 1 active power kw min W Phase 2 active power kw min W Phase 3 active power kw min W Total reactive power kvar Inst var 741 var 741 var Phase 1 reactive power kvar Inst var Phase 2 reactive power kvar Inst var Phase 3 reactive power kvar Inst var Total reactive power kvar max var 742 var 742 var Phase 1 reactive power kvar max var Phase 2 reactive power kvar max var Phase 3 reactive power kvar max var Total reactive power kvar min var 740 var 740 var Phase 1 reactive power kvar min var Phase 2 reactive power kvar min var Phase 3 reactive power kvar min var 1 0B 1 Total apparent power kva Inst VA 1 0B 21 Phase 1 apparent power kva Inst VA 1 0B 41 Phase 2 apparent power kva Inst VA 1 0B 61 Phase 3 apparent power kva Inst VA 1 0B 2 Total apparent power kva max VA 1 0B 22 Phase 1 apparent power kva max VA 1 0B 42 Phase 2 apparent power kva max VA 1 0B 62 Phase 3 apparent power kva max VA 1 0B 5 Total apparent power kva min VA 1 0B 25 Phase 1 apparent power kva min VA 1 0B 45 Phase 2 apparent power kva min VA 1 0B 65 Phase 3 apparent power kva min VA Note (51/n)
53 3P4W reply data (Secondary side) 3P3W_2CT reply data (Secondary side) 3P3W_3CT reply data (Secondary side) Unit Group Ch. Data No. (h) (h) Name of Channel Type Data Unit Data Unit Data Unit 0 0D 1 Total power factor % Inst % 84.1 % 84.1 % 0 0D 21 Phase 1 power factor % Inst % 0 0D 41 Phase 2 power factor % Inst % 0 0D 61 Phase 3 power factor % Inst % 0 0D 2 Total power factor % max % 84.0 % 84.0 % 0 0D 22 Phase 1 power factor % max % 0 0D 42 Phase 2 power factor % max % 0 0D 62 Phase 3 power factor % max % 0 0D 5 Total power factor % min % 84.2 % 84.2 % 0 0D 25 Phase 1 power factor % min % 0 0D 45 Phase 2 power factor % min % 0 0D 65 Phase 3 power factor % min % 0 0F 1 Frequency Hz Inst Hz 50.0 Hz 50.0 Hz 0 0F 2 Frequency Hz max Hz 51.0 Hz 51.0 Hz 0 0F 5 Frequency Hz min Hz 49.0 Hz 49.0 Hz H.V V Inst. Total V 78.9 V 0 4D H.V V Inst. 1st V 91.1 V 0 4F H.V V Inst. 3rd V 36.1 V H.V V Inst. 5th V 35.1 V H.V V Inst. 7th V 34.1 V H.V V Inst. 9th V 33.1 V H.V V Inst. 11th V 32.1 V H.V V Inst. 13th V 20.1 V H.V D. ratio % Inst. Total % 86.6 % H.V D. ratio % Inst. 3rd % 39.6 % H.V D. ratio % Inst. 5th % 38.5 % H.V D. ratio % Inst. 7th % 37.4 % H.V D. ratio % Inst. 9th % 36.3 % B 1-2 H.V D. ratio % Inst. 11th % 35.2 % D 1-2 H.V D. ratio % Inst. 13th % 22.1 % H.V V Inst. Total V 79.3 V 0 4D H.V V Inst. 1st V 91.3 V 0 4F H.V V Inst. 3rd V 35.9 V H.V V Inst. 5th V 34.9 V H.V V Inst. 7th V 34.3 V H.V V Inst. 9th V 33.3 V H.V V Inst. 11th V 32.3 V H.V V Inst. 13th V 21.3 V C 2-3 H.V D. ratio % Inst. Total % 86.9 % H.V D. ratio % Inst. 3rd % 39.3 % B 2-3 H.V D. ratio % Inst. 5th % 38.2 % D 2-3 H.V D. ratio % Inst. 7th % 37.6 % F 2-3 H.V D. ratio % Inst. 9th % 36.5 % H.V D. ratio % Inst. 11th % 35.4 % H.V D. ratio % Inst. 13th % 23.3 % 0 76 DE L-L H.V D. ratio % max. Total % 91.7 % 0 4D A2 L-L H.V V max. 1st V 91.8 V 0 76 CB L-L H.V D. ratio % max. 3rd % 40.1 % 0 76 CD L-L H.V D. ratio % max. 5th % 39.1 % 0 76 CF L-L H.V D. ratio % max. 7th % 37.9 % 0 76 D1 L-L H.V D. ratio % max. 9th % 36.8 % 0 76 D3 L-L H.V D. ratio % max. 11th % 35.7 % 0 76 D5 L-L H.V D. ratio % max. 13th % 34.8 % Note (52/n)
54 Unit Group Ch. Data No. (h) (h) Name of Channel Type 3P4W reply data (Secondary side) 3P3W_2CT reply data (Secondary side) 3P3W_3CT reply data (Secondary side) Note Data Unit Data Unit Data Unit 0 4B 21 1-N H.V V Inst. Total V N H.V V Inst. 1st V N H.V V Inst. 3rd V N H.V V Inst. 5th V 1 3B 21 1-N H.V V Inst. 7th V 1 3D 21 1-N H.V V Inst. 9th V 1 3F 21 1-N H.V V Inst. 11th V N H.V V Inst. 13th V N H.V D. ratio % Inst. Total % N H.V D. ratio % Inst. 3rd % N H.V D. ratio % Inst. 5th % N H.V D. ratio % Inst. 7th % N H.V D. ratio % Inst. 9th % B 1-N H.V D. ratio % Inst. 11th % D 1-N H.V D. ratio % Inst. 13th % 0 4B 41 2-N H.V V Inst. Total V N H.V V Inst. 1st V N H.V V Inst. 3rd V N H.V V Inst. 5th V 1 3B 41 2-N H.V V Inst. 7th V 1 3D 41 2-N H.V V Inst. 9th V 1 3F 41 2-N H.V V Inst. 11th V N H.V V Inst. 13th V C 2-N H.V D. ratio % Inst. Total % N H.V D. ratio % Inst. 3rd % B 2-N H.V D. ratio % Inst. 5th % D 2-N H.V D. ratio % Inst. 7th % F 2-N H.V D. ratio % Inst. 9th % N H.V D. ratio % Inst. 11th % N H.V D. ratio % Inst. 13th % 0 4B 61 3-N H.V V Inst. Total V N H.V V Inst. 1st V N H.V V Inst. 3rd V N H.V V Inst. 5th V 1 3B 61 3-N H.V V Inst. 7th V 1 3D 61 3-N H.V V Inst. 9th V 1 3F 61 3-N H.V V Inst. 11th V N H.V V Inst. 13th V 0 77 B2 3-N H.V D. ratio % Inst. Total % F 3-N H.V D. ratio % Inst. 3rd % 0 77 A1 3-N H.V D. ratio % Inst. 5th % 0 77 A3 3-N H.V D. ratio % Inst. 7th % 0 77 A5 3-N H.V D. ratio % Inst. 9th % 0 77 A7 3-N H.V D. ratio % Inst. 11th % 0 77 A9 3-N H.V D. ratio % Inst. 13th % 0 77 DE L-N H.V D. ratio % max. Total % 0 35 A2 L-N H.V V max. 1st V 0 77 CB L-N H.V D. ratio % max. 3rd % 0 77 CD L-N H.V D. ratio % max. 5th % 0 77 CF L-N H.V D. ratio % max. 7th % 0 77 D1 L-N H.V D. ratio % max. 9th % 0 77 D3 L-N H.V D. ratio % max. 11th % 0 77 D5 L-N H.V D. ratio % max. 13th % (53/n)
55 3P4W reply data (Secondary side) 3P3W_2CT reply data (Secondary side) 3P3W_3CT reply data (Secondary side) Unit Group Ch. Data No. (h) (h) Name of Channel Type Data Unit Data Unit Data Unit Phase 1 H.A A Inst. Total A 3.15 A 3.15 A 0 1D 21 Phase 1 H.A A Inst. 1st A 3.71 A 3.71 A 0 1F 21 Phase 1 H.A A Inst. 3rd A 1.63 A 1.63 A Phase 1 H.A A Inst. 5th A 1.48 A 1.48 A Phase 1 H.A A Inst. 7th A 1.34 A 1.34 A Phase 1 H.A A Inst. 9th A 1.19 A 1.19 A Phase 1 H.A A Inst. 11th A 1.04 A 1.04 A Phase 1 H.A A Inst. 13th A 0.89 A 0.89 A Phase 1 H.A D. ratio % Inst. Total % 85.0 % 85.0 % Phase 1 H.A D. ratio % Inst. 3rd % 44.0 % 44.0 % Phase 1 H.A D. ratio % Inst. 5th % 40.0 % 40.0 % Phase 1 H.A D. ratio % Inst. 7th % 36.0 % 36.0 % Phase 1 H.A D. ratio % Inst. 9th % 32.0 % 32.0 % B Phase 1 H.A D. ratio % Inst. 11th % 28.0 % 28.0 % D Phase 1 H.A D. ratio % Inst. 13th % 24.0 % 24.0 % Phase 2 H.A A Inst. Total A 2.92 A 3.07 A 0 1D 41 Phase 2 H.A A Inst. 1st A 3.75 A 3.72 A 0 1F 41 Phase 2 H.A A Inst. 3rd A 1.54 A 1.60 A Phase 2 H.A A Inst. 5th A 1.39 A 1.45 A Phase 2 H.A A Inst. 7th A 1.24 A 1.30 A Phase 2 H.A A Inst. 9th A 1.09 A 1.15 A Phase 2 H.A A Inst. 11th A 0.94 A 1.00 A Phase 2 H.A A Inst. 13th A 0.79 A 0.86 A C Phase 2 H.A D. ratio % Inst. Total % 78.0 % 82.0 % Phase 2 H.A D. ratio % Inst. 3rd % 41.0 % 43.0 % B Phase 2 H.A D. ratio % Inst. 5th % 37.0 % 39.0 % D Phase 2 H.A D. ratio % Inst. 7th % 33.0 % 35.0 % F Phase 2 H.A D. ratio % Inst. 9th % 29.0 % 31.0 % Phase 2 H.A D. ratio % Inst. 11th % 25.0 % 27.0 % Phase 2 H.A D. ratio % Inst. 13th % 21.0 % 23.0 % Phase 3 H.A A Inst. Total A 2.99 A 2.99 A 0 1D 61 Phase 3 H.A A Inst. 1st A 3.73 A 3.73 A 0 1F 61 Phase 3 H.A A Inst. 3rd A 1.57 A 1.57 A Phase 3 H.A A Inst. 5th A 1.42 A 1.42 A Phase 3 H.A A Inst. 7th A 1.27 A 1.27 A Phase 3 H.A A Inst. 9th A 1.12 A 1.12 A Phase 3 H.A A Inst. 11th A 0.97 A 0.97 A Phase 3 H.A A Inst. 13th A 0.82 A 0.82 A 0 75 B2 Phase 3 H.A D. ratio % Inst. Total % 80.0 % 80.0 % F Phase 3 H.A D. ratio % Inst. 3rd % 42.0 % 42.0 % 1 75 A1 Phase 3 H.A D. ratio % Inst. 5th % 38.0 % 38.0 % 1 75 A3 Phase 3 H.A D. ratio % Inst. 7th % 34.0 % 34.0 % 1 75 A5 Phase 3 H.A D. ratio % Inst. 9th % 30.0 % 30.0 % 1 75 A7 Phase 3 H.A D. ratio % Inst. 11th % 26.0 % 26.0 % 1 75 A9 Phase 3 H.A D. ratio % Inst. 13th % 22.0 % 22.0 % Phase N H.A A Inst. Total A 0 1D 81 Phase N H.A A Inst. 1st A 0 1F 81 Phase N H.A A Inst. 3rd A Phase N H.A A Inst. 5th A Phase N H.A A Inst. 7th A Phase N H.A A Inst. 9th A Phase N H.A A Inst. 11th A Phase N H.A A Inst. 13th A 0 75 C8 Phase N H.A D. ratio % Inst. Total % 1 75 B5 Phase N H.A D. ratio % Inst. 3rd % 1 75 B7 Phase N H.A D. ratio % Inst. 5th % 1 75 B9 Phase N H.A D. ratio % Inst. 7th % 1 75 BB Phase N H.A D. ratio % Inst. 9th % 1 75 BD Phase N H.A D. ratio % Inst. 11th % 1 75 BF Phase N H.A D. ratio % Inst. 13th % Note (54/n)
56 Unit No. Group (h) Ch. (h) Data Type 3P4W reply data (Secondary side) 3P3W_2CT reply data (Secondary side) 3P3W_3CT reply data (Secondary side) Name of Channel Note Data Unit Data Unit Data Unit 0 33 A2 H.A A max. Total A 3.48 A 3.48 A 0 1D A2 H.A A max. 1st A 3.76 A 3.76 A 0 1F A2 H.A A max. 3rd A 1.66 A 1.66 A 0 21 A2 H.A A max. 5th A 1.56 A 1.56 A 0 23 A2 H.A A max. 7th A 1.46 A 1.46 A 0 25 A2 H.A A max. 9th A 1.36 A 1.36 A 0 27 A2 H.A A max. 11th A 1.26 A 1.26 A 0 29 A2 H.A A max. 13th A 1.16 A 1.16 A Phase N H.A A max. Total A 1 1D 82 Phase N H.A A max. 1st A 1 1F 82 Phase N H.A A max. 3rd A Phase N H.A A max. 5th A Phase N H.A A max. 7th A Phase N H.A A max. 9th A Phase N H.A A max. 11th A Phase N H.A A max. 13th A active energy import k W count kwh kwh kwh Note active energy export k W count kwh kwh kwh Note active energy import k W count expand kwh kwh kwh Note active energy export k W count expand kwh kwh kwh Note reactive energy import lag kvar count kvar kvar kvar Note reactive energy export lag kvar count kvar kvar kvar Note reactive energy import kvar count kvar kvar kvar Note reactive energy export kvar count kvar kvar kvar Note reactive energy import lag kvar count expand kvar kvar kvar Note reactive energy export lag kvar count expand kvar kvar kvar Note reactive energy import kvar count expand kvar kvar kvar Note reactive energy export kvar count expand kvar kvar kvar Note current upper limit A Alarm current lower limit A Alarm current upper limit A Alarm PhaseN current demand upper limit A Alarm current demand lower limit A Alarm current demand upper limit A Alarm PhaseN voltage upper limit(l-l) V Alarm voltage lower limit(l-l) V Alarm voltage upper limit(l-n) V Alarm voltage lower limit(l-n) V Alarm active power upper limit kw Alarm active power lower limit kw Alarm reactive power upper limit kvar Alarm reactive power lower limit kvar Alarm 1 0 0D 14 power factor upper limit % Alarm 1 0 0D 15 power factor lower limit % Alarm 1 0 0F 14 Frequency upper limit Hz Alarm 1 0 0F 15 Frequency lower limit Hz Alarm E1 H.V(L-N) upper limit % Alarm Total E1 H.V(L-L) upper limit % Alarm Total E1 H.A upper limit A Alarm Total F1 H.A upper limit(phase N) A Alarm Total 1 0 A0 31 Alarm state Alarm 3 Note2 Note2 Note2 0 A0 35 Alarm state2 Alarm 3 Note3 Note3 Note3 Note1. Counting values are replied on the values of primary side. Note2. b21 and b24 become ON(1). b16 to b19 of digital inputs are reflected at the present state. Note3. b23, b28 to b31 become ON(1). (55/n)
Electronic Multi-Measuring Instrument
MITSUBISHI Electronic Multi-Measuring Instrument Programming Manual (CC-Link) For ver.1 remote device station Model ME96NSR-MB or ME96NSR with Optional Plug-in Module : ME-0040C-NS96 ME96SSH-MB or ME96SSR-MB
Setup and Programming of the. Master Module R72-11Z-SLSASG-028
Setup and Programming of the FX3U-16CCL-M eth1000_large.jpg FX3U CC-LINK Master Module R72-11Z-SLSASG-028 Contents Contents... i FURTHER READING REFERENCE LIST... ii Chapter 1 Introduction... 1-1 Chapter
Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1
Softstarters Type PSTX Fieldbus communication, Built-in Modbus RTU 1SFC132089M0201 April 2015 1SFC132089M0201 1 1 Modbus RTU The Modbus protocol is a fieldbus protocol that provides full control and status
Open Field Network CC-Link Troubleshooting Guide
2006 Mar Open Field etwork CC-Link Troubleshooting Guide Mitsubishi Electric Corporation agoya Works is a factory certified for ISO14001 (standards for environmental management systems) and ISO9001 (standards
MELSEC-QS CC-Link IE Field Network Master/ Local Module User's Manual -QS0J71GF11-T2
MELSEC-QS CC-Link IE Field Network Master/ Local Module User's Manual -QS0J71GF11-T2 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this
CC-Link Network Monitor Function
CC-Link Network Monitor Function Sample Screen Manual Mitsubishi Electric Corporation Using the Samples The sample screen data and files such as the instruction manual can be used upon agreement to the
Nemo 96HD/HD+ MODBUS
18/12/12 Pagina 1 di 28 MULTIFUNCTION FIRMWARE 2.30 Nemo 96HD/HD+ MODBUS COMMUNICATION PROTOCOL CONTENTS 1.0 ABSTRACT 2.0 DATA MESSAGE DESCRIPTION 2.1 Parameters description 2.2 Data format 2.3 Description
NC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
DIRIS A40/A41 RS485 JBUS/MODBUS. Operating instructions F GB D I NL E P
DIRIS A40/A41 RS485 JBUS/MODBUS Operating instructions F GB D I NL E P COM DIRIS A40/A41 - Ref.: 536 103 A GB GB Contents PRELIMINARY OPERATIONS 4 GENERAL INFORMATION 4 INSTALLATION 5 CONNECTION 5 PROGRAMMING
Eco-POWER METER Data Collection Software KW Monitor Operation Manual
Eco-POWER METER Data Collection Software KW Monitor Operation Manual Software version: KW Monitor V2.70 Issued on January 2014 Table of Contents Chapter 1 Introduction...1 Chapter 2 Main functions of KW
MEMOBUS/Modbus Communications
2 2.1 MEMOBUS/MODBUS CONFIGURATION............260 2.2 COMMUNICATION SPECIFICATIONS..............261 2.3 COMMUNICATION TERMINAL RESISTANCE........262 2.4 CONNECTING A PLC...........................263 2.5
Projector Control Command Reference Manual
Projector Control Reference Manual Copyright (C) NEC Display Solutions, Ltd. 2014-2015 BDT140013 Revision 4.0 Introduction This manual describes the commands used to control an NEC-made projector from
CC-Link Ver.1.10 Compatible
Model Title CC-Link Ver.1.10 Compatible CC-Link Flexible Cable Conformance Test Specifications Management number : BAP-C0401-009 CC-Link Partner Association (1/12) Revisions Revision item Revision Description
CRE Monitor Instructions Manual
CRE Monitor Instructions Manual CRE TECHNOLOGY believes that all information provided herein is correct and reliable and reserves the right to update at anytime. CRE TECHNOLOGY does not assume any responsibility
W25Q80, W25Q16, W25Q32 8M-BIT, 16M-BIT AND 32M-BIT SERIAL FLASH MEMORY WITH DUAL AND QUAD SPI
8M-BIT, 16M-BIT AND 32M-BIT SERIAL FLASH MEMORY WITH DUAL AND QUAD SPI - 1 - Preliminary - Revision B Table of Contents 1. GENERAL DESCRIPTION... 5 2. FEATURES... 5 3. PIN CONFIGURATION SOIC 208-MIL...
Examples of Automation. X-SEL Serial Communication
Examples of Automation X-SEL Serial Communication Overview of Networks Examples of Automation Table of Contents DeviceNet Confectionery Sizer/Sorter...5 1. Explanation of Application...5 (1) System configuration...5
2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode:
COMMUNICATION INSTRUCTION MANUAL TEMPERATURE CONTROLLER KT4, KT8 and KT9 No.KTC1E6 2009.05 To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide
WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide Version 2.1, 4/2010 Disclaimer While every effort has been made to ensure that the information in this guide is accurate
MTS Master Custom Communications Protocol APPLICATION NOTES
MTS Master Custom Communications Protocol APPLICATION NOTES Rev. 0 12/6/94 Contents INTRODUCTION... 1 ACCOL TERMINAL ASSIGNMENTS... 1 MTS PROTOCOL SIGNAL LIST... 2 COMMUNICATIONS INTERFACE... 3 Line Parameter
DS1721 2-Wire Digital Thermometer and Thermostat
www.dalsemi.com FEATURES Temperature measurements require no external components with ±1 C accuracy Measures temperatures from -55 C to +125 C; Fahrenheit equivalent is -67 F to +257 F Temperature resolution
SD Specifications Part A2 SD Host Controller Simplified Specification
SD Specifications Part A2 SD Host Controller Simplified Specification Version 2.00 February 8, 2007 Technical Committee SD Association Revision History Date Version Changes compared to previous issue April
SMS GSM Alarm Messenger
SMS GSM Alarm Messenger Data Logging Alarm Input Relay Output Voice Temperature Humidity Analog Input Capture and Send Data via SMS Report triggered alarm via SMS Output triggered via SMS Auto pick up
LENORD. +BAUER... automates motion. Fieldbus connection absolute encoders CANopen. Reference. Communication profile DS-301 Device profile DS-406
Fieldbus connection absolute encoders CANopen Communication profile DS-30 Device profile DS-406 LENORD +BAUER... automates motion. Reference D-0R-xCO (.) Right to technical changes and errors reserved.
Appendix C: Keyboard Scan Codes
Thi d t t d ith F M k 4 0 2 Appendix C: Keyboard Scan Codes Table 90: PC Keyboard Scan Codes (in hex) Key Down Up Key Down Up Key Down Up Key Down Up Esc 1 81 [ { 1A 9A, < 33 B3 center 4C CC 1! 2 82 ]
Softstarters. Type PST/PSTB Fieldbus communication CANopen for PST sw CU 06.00.00. 1SFC132070M0201 February 2011 1SFC132070M0201 1
Softstarters Type PST/PSTB Fieldbus communication CANopen for PST sw CU 06.00.00 1SFC132070M0201 February 2011 1SFC132070M0201 1 CANopen The CANopen protocol is a fieldbus protocol that provides full control
Modbus and ION Technology
70072-0104-14 TECHNICAL 06/2009 Modbus and ION Technology Modicon Modbus is a communications protocol widely used in process control industries such as manufacturing. PowerLogic ION meters are compatible
MBP_MSTR: Modbus Plus Master 12
Unity Pro MBP_MSTR 33002527 07/2011 MBP_MSTR: Modbus Plus Master 12 Introduction This chapter describes the MBP_MSTR block. What s in this Chapter? This chapter contains the following topics: Topic Page
2CSG445012D0201 M2M ETHERNET. ETHERNET interface user manual M2M ABB
2CSG445012D0201 ETHERNET interface user manual M2M 1 GERAL INFORMATION 4 1.1 ETHERNET NETORK CONNECTION...4 1.2 SELF-DIAGNOSIS...4 2 CONFIGURATION 5 2.1 PAGES ACCESS...5 2.2 INSTRUMT SETUP...6 2.3 DEFAULT
SOFTWARE EasyComm (Code 775 044) USER S MANUAL (Code M 981 357/00 - A) 1997-2000 CIRCUTOR, S.A. All rights reserved
SOFTWARE EasyComm (Code 775 044) USER S MANUAL (Code M 981 357/00 - A) 1997-2000 CIRCUTOR, S.A. All rights reserved EasyComm INDEX 1. Introduction... Page 2 2. EasyComm contents... Page 2 3. Main features...
ENTBUS PLUS SOFTWARE FOR ENERGY MONITORING AND RECORDING INSTALLATION AND OPERATING MANUAL
ENTBUS PLUS SOFTWARE FOR ENERGY MONITORING AND RECORDING INSTALLATION AND OPERATING MANUAL Foreword Entbus services manage the collection of information and storing this information in the database. Services
Technical Note. SFDP for MT25Q Family. Introduction. TN-25-06: Serial Flash Discovery Parameters for MT25Q Family. Introduction
Technical Note SFDP for MT25Q Family TN-25-06: Serial Flash Discovery Parameters for MT25Q Family Introduction Introduction The serial Flash discoverable parameter (SFDP) standard enables a consistent
SAFETY PRECAUTION. (Always read these instructions before using the products.)
SAFETY PRECAUTION (Always read these instructions before using the products.) When designing the system, always read the relevant manuals and give sufficient consideration to safety. During the exercise,
Programmer s Reference
Programmer s Reference 1 Introduction This manual describes Launchpad s MIDI communication format. This is all the proprietary information you need to be able to write patches and applications that are
HT1632C 32 8 &24 16 LED Driver
328 &216 LED Driver Features Operating voltage: 2.V~5.5V Multiple LED display 32 ROW /8 COM and 2 ROW & 16 COM Integrated display RAM select 32 ROW & 8 COM for 6 display RAM, or select 2 ROW & 16 COM for
CPUs - CPU 315-2 PN/DP
Overview The CPU with a medium program memory and quantity framework High processing performance in binary and floating-point arithmetic Used as a central controller on production lines with central and
DeviceNet Bus Software Help for Programming an Allen Bradley Control System
FBP FieldBusPlug V7 DeviceNet Bus Software Help for Programming an Allen Bradley Control System DeviceNet Software Help for Programming an Allen Bradley Control System Contents Page General Purpose...
DS1621 Digital Thermometer and Thermostat
Digital Thermometer and Thermostat www.dalsemi.com FEATURES Temperature measurements require no external components Measures temperatures from 55 C to +125 C in 0.5 C increments. Fahrenheit equivalent
DS18B20 Programmable Resolution 1-Wire Digital Thermometer
www.dalsemi.com FEATURES Unique 1-Wire interface requires only one port pin for communication Multidrop capability simplifies distributed temperature sensing applications Requires no external components
Objectives. Basics of Serial Communication. Simplex vs Duplex. CMPE328 Microprocessors (Spring 2007-08) Serial Interfacing. By Dr.
CMPE328 Microprocessors (Spring 27-8) Serial Interfacing By Dr. Mehmet Bodur Objectives Upon completion of this chapter, you will be able to: List the advantages of serial communication over parallel communication
DS1621 Digital Thermometer and Thermostat
www.maxim-ic.com FEATURES Temperature measurements require no external components Measures temperatures from -55 C to +125 C in 0.5 C increments. Fahrenheit equivalent is -67 F to 257 F in 0.9 F increments
Configuring PROFINET
CHAPTER 9 This chapter describes how to configure the PROFINET feature on the Cisco IE 3000 switch. Understanding PROFINET, page 9-1, page 9-4 Displaying the PROFINET Configuration, page 9-5 Troubleshooting
Disturbance Recoder SPCR 8C27. Product Guide
Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power
ESPA 4.4.4 Nov 1984 PROPOSAL FOR SERIAL DATA INTERFACE FOR PAGING EQUIPMENT CONTENTS 1. INTRODUCTION 2. CHARACTER DESCRIPTION
PROPOSAL FOR SERIAL DATA INTERFACE FOR PAGING EQUIPMENT CONTENTS 1. INTRODUCTION 2. CHARACTER DESCRIPTION 2.1 CHARACTER STRUCTURE 2.2 THE CHARACTER SET 2.3 CONTROL CHARACTERS 2.3.1 Transmission control
2 ASCII TABLE (DOS) 3 ASCII TABLE (Window)
1 ASCII TABLE 2 ASCII TABLE (DOS) 3 ASCII TABLE (Window) 4 Keyboard Codes The Diagram below shows the codes that are returned when a key is pressed. For example, pressing a would return 0x61. If it is
Modbus RTU Communications RX/WX and MRX/MWX
15 Modbus RTU Communications RX/WX and MRX/MWX In This Chapter.... Network Slave Operation Network Master Operation: RX / WX Network Master Operation: DL06 MRX / MWX 5 2 D0 Modbus Network Slave Operation
S4000TH HART. HART Communication Manual
HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General
DNP Points List and Implementation
S&C Electric Company BankGuard Plus DNP Points List and Implementation This appendix describes the DNP points and DNP implementation for the BankGuard PLUS Control, using software UPPD106S. DNP Points
1. INTRODUCTION FEATURES 2. PROGRAMMING
1. INTRODUCTION Mono phase compensation systems are not useful in plants where unbalanced loads exist. In such plants compensation has to be done by measuring all 3 phase parameters individually. Devices,
Process Control and Automation using Modbus Protocol
Process Control and Automation using Modbus Protocol Modbus is the fundamental network protocol used in most industrial applications today. It is universal, open and an easy to use protocol. Modbus has
Combi switchbox with integrated 3/2 way pilot valve
H Combi switchbox with integrated 3/2 way pilot valve Construction The GEMÜ combi switchbox with integrated 3/2 way pilot valve for pneumatically operated quarter turn actuators has a micro-processor controlled
I.S. 1 remote I/O system Redundant coupling via PROFIBUS DP
I.S. 1 remote I/O system Redundant coupling via PROFIBUS DP 1. Functions An I. S. 1 fieldstation can be equipped with a primary and a redundant central unit (), whereby each has its own independent PROFIBUS
Programming Interface. for. Bus Master IDE Controller. Revision 1.0
Programming Interface for Bus Master IDE Controller Revision 1.0 5/16/94 Until this specification is ratified, it is solely owned and maintained by: Brad Hosler, Intel Corporation [email protected] (please
Serial Communications
Serial Communications 1 Serial Communication Introduction Serial communication buses Asynchronous and synchronous communication UART block diagram UART clock requirements Programming the UARTs Operation
The Answer to the 14 Most Frequently Asked Modbus Questions
Modbus Frequently Asked Questions WP-34-REV0-0609-1/7 The Answer to the 14 Most Frequently Asked Modbus Questions Exactly what is Modbus? Modbus is an open serial communications protocol widely used in
Start-up of IVI-KHD2-4HRX, IVI-KHA6-4HRX at S7-300 V1.1. Table of Contents TABLE OF CONTENTS... 1
Table of Contents TABLE OF CONTENTS... 1 1. DESCRIPTION OF HARDWARE... 2 1.1 Modules and devices... 2 1.2 Set-up and installation... 2 2. SETTING UP PARAMETERS... 2 2.1 Setting up parameters in accordance
Single channel data transceiver module WIZ2-434
Single channel data transceiver module WIZ2-434 Available models: WIZ2-434-RS: data input by RS232 (±12V) logic, 9-15V supply WIZ2-434-RSB: same as above, but in a plastic shell. The WIZ2-434-x modules
Parallel NOR Flash Automotive Memory
Features Parallel NOR Flash Automotive Memory MT28EW512ABA1xJS-0AAT, MT28EW512ABA1xPC-0AAT Features Single-level cell (SLC) process technology Density: 512Mb Supply voltage V CC = 2.7 3.6V (program, erase,
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
RS-485 Protocol Manual
RS-485 Protocol Manual Revision: 1.0 January 11, 2000 RS-485 Protocol Guidelines and Description Page i Table of Contents 1.0 COMMUNICATIONS BUS OVERVIEW... 1 2.0 DESIGN GUIDELINES... 1 2.1 Hardware Design
EMDX3 Multifunction meter Cat No. 146 69 ModbusTable LGR EN v1.01.xls
GENERAL MODBUS TABLE ORGANIZATION Starting of the Starting of the Group s Group s System Version (Release) System Version (Build) Group Name (Text) Group Code Group Complexity Group Version 50512 C550
Applications. diris_826_a_1_gb_cat
Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered
Omron I/O Driver (Series 2) Programmable Serial Interface Card
Omron I/O Driver (Series 2) Programmable Serial Interface Card USER MANUAL Rev. P1.55 June 8, 2012 DeltaV is a trademark of Emerson Process Management, Inc Emerson Process Management, Inc. 1998, 1999.
SYMETRIX SOLUTIONS: TECH TIP August 2015
String Output Modules The purpose of this document is to provide an understanding of operation and configuration of the two different String Output modules available within SymNet Composer. The two different
Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP
Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE T I A Training Document Page 1 of 25 Module This document has been written by Siemens AG for training
Temperature & Humidity SMS Alert Controller
Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal
Custom Solutions Center. Users Guide. Low Cost OEM PackML Templates L02 Release. Version LC-1.0
Users Guide Low Cost OEM PackML Templates L02 Release Version LC-1.0 Users Guide Low Cost OEM PackML Templates L02 Release: Part 1 - Overview Version LC-1.0 Content 1 Introduction...1 2 Low Cost PackML
SUPPLY NETWORK ANALYZER
SUPPLY NETWORK ANALYZER AR5-L (Code 7 71 501 ) INSTRUCTION MANUAL ( M98151101-03 / 03E ) (c) CIRCUTOR S.A. -------------- SUPPLY NETWORK ANALYZER AR5-L ----------- Page nº 2 CONTENTS page 1.- BASIC INSTRUCTIONS...4
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
User s Guide for version 5 Page
Network Management Interface Catalog VPi 32.15E For use with these ATS products: 7000 & 4000 Series (Group 5 Controller) Series 300 (Group 1 Controller), and 940, 962, 436, 434, 447, 448 (Group 6A/7A Control
How many high-speed counters (HSCs) are provided by the SIMATIC S7-1200 PLC? SIMATIC S7-1200. FAQ March 2010. Service & Support. Answers for industry.
How many high-speed counters (HSCs) are provided by the SIMATIC S7-1200 PLC? SIMATIC S7-1200 FAQ March 2010 Service & Support Answers for industry. Question This entry is from the Service&Support portal
Install the DeviceNet Module using the following procedure:
Installation INSTALLATION INSTRUCTIONS: MCD DEVICENET MODULE Order Code: 175G9002 1. Installation Install the DeviceNet Module using the following procedure: 1. Remove control power and mains supply from
How to read this guide
How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information
Wireless USB Adapter
Wireless USB Adapter User s Manual 1 Table of Contents USER S MANUAL... 1 WELCOME... 3 PACKAGE CONTENTS... 3 WIRELESS USB ADAPTER OVERVIEW... 4 INTERFACE... 4 LED DESCRIPTION... 4 WPS BUTTON... 4 WIRELESS
Site Master S251B Antenna and Cable Analyzer
Site Master S251B Antenna and Cable Analyzer Programming Manual Hand-Held Tester For Antennas, Transmission Lines And Other RF Components WARRANTY The Anritsu product(s) listed on the title page is (are)
RS - SPM. Serial parallel translator module
ReSatron GmbH Boisheimer Str. 162 D-41751 Viersen Telefon (+49) 02162-45 06 80 Telefax (+49) 02162-45 03 04 email: [email protected] RS - SPM Serial parallel translator module RSSPM000215SPM-021 - Subject
SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program
Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves
CAM-VGA100 User Manual
CAM-VGA100 User Manual Release Note: 1. Jan 28, 2004 official released v1.0 2. Feb 24, 2004 official released v1.1 Fix the definition of verify code Fix the bug of unable jump to power save mode Fix the
User Manual. AS-Interface Programmer
AS-Interface Programmer Notice: RESTRICTIONS THE ZMD AS-INTERFACE PROGRAMMER HARDWARE AND ZMD AS-INTERFACE PROGRAMMER SOFTWARE IS DESIGNED FOR IC EVALUATION, LABORATORY SETUP AND MODULE DEVELOPMENT ONLY.
EN25P64 EN25P64. 64 Megabit Uniform Sector, Serial Flash Memory FEATURES GENERAL DESCRIPTION
64 Megabit Uniform Sector, Serial Flash Memory EN25P64 FEATURES Single power supply operation - Full voltage range: 2.7-3.6 volt 64 M-bit Serial Flash - 64 M-bit/8192 K-byte/32768 pages - 256 bytes per
Programmable Logic Controllers
Programmable Logic Controllers PLC Basics Dr. D. J. Jackson Lecture 2-1 Operating systems and application programs A PLC contains a basic operating system that allows for: Downloading and executing user
W25Q128FV 3V 128M-BIT SERIAL FLASH MEMORY WITH DUAL/QUAD SPI & QPI. Publication Release Date: August 24, 2015 Revision L
3V 128M-BIT SERIAL FLASH MEMORY WITH DUAL/QUAD SPI & QPI Publication Release Date: August 24, 2015 Revision L Table of Contents 1. GENERAL DESCRIPTIONS... 5 2. FEATURES... 5 3. PACKAGE TYPES AND PIN CONFIGURATIONS...
Light scene push button 8gang comfort flush-mounted 751688xx
751688xx Documentation Product name: Light scene push button 8gang comfort Design: flush-mounting type (Up) ETS search path: Push button / Push button general / Light scene push button 8gang comfort Functional
SAFETY PRECAUTIONS (Read these precautions before using this product.)
SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the
Documentation. M-Bus 130-mbx
Documentation M-Bus 130-mbx Introduction The mx M-Bus module is part of the mx Smart Slot communications family. With the integrated SmartSlot technology, mx systems ag offers automatic consumer data read-out
Parallax Serial LCD 2 rows x 16 characters Non-backlit (#27976) 2 rows x 16 characters Backlit (#27977) 4 rows x 20 characters Backlit (#27979)
599 Menlo Drive, Suite 100 Rocklin, California 95765, USA Office: (916) 624-8333 Fax: (916) 624-8003 General: [email protected] Technical: [email protected] Web Site: www.parallax.com Educational: www.stampsinclass.com
Soft-Starter SSW-06 V1.6X
Motors Energy Automation Coatings Soft-Starter SSW-06 V1.6X Serial Communication Manual Language: English Document: 0899.5731 / 04 Serial Communication Manual Series: SSW-06 V1.6X Language: English Document
(Cat. No. 6008-SI) Product Data
(Cat. No. 6008-SI) Product Data 1 Because of the variety of uses for this product and because of the differences between solid state products and electromechanical products, those responsible for applying
PACKAGE OUTLINE DALLAS DS2434 DS2434 GND. PR 35 PACKAGE See Mech. Drawings Section
PRELIMINARY DS2434 Battery Identification Chip FEATURES Provides unique ID number to battery packs PACKAGE OUTLINE Eliminates thermistors by sensing battery temperature on chip DALLAS DS2434 1 2 3 256
S88XPressNetLI v1.0. Installation, user and reference manual. 2008 KDesign Electronics, PCB design by RoSoft
S88XPressNetLI v1.0 Installation, user and reference manual 2008 KDesign Electronics, PCB design by RoSoft Table of contents 1 Introduction... 3 2 Specifications... 4 3 Installation... 5 3.1 Connecting
GE Power Controls FIELDBUS APPENDIX PROFIBUS DP. Doc. No.: ASTAT Plus PB_Appendix-v0
GE Power Controls = FIELDBUS APPENDIX PROFIBUS DP = Doc. No.: ASTAT Plus PB_Appendix-v0 Fieldbus Appendix: PROFIBUS DP 1 Fieldbus Introduction...... 2 1.1 Introduction to Profibus-DP... 2 1.2 Network Overview...
Using Xbee 802.15.4 in Serial Communication
Using Xbee 802.15.4 in Serial Communication Jason Grimes April 2, 2010 Abstract Instances where wireless serial communication is required to connect devices, Xbee RF modules are effective in linking Universal
7.7 Ethernet Communication (AFPX-COM5)
7.7 Ethernet Communication (AFPX-COM5) 7.7.1 AFPX-COM5 Overview The communication cassette AFPX-COM5 has an Ethernet interface at the COM1 port and a 3-wire RS232C interface at the COM2 port. The Ethernet
Operational Overview and Controls Guide
DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)
PROPERTY MANAGEMENT SYSTEM
PROPERTY MANAGEMENT SYSTEM COMMUNICATION INTERFACE SPECIFICATION NEC America, Inc. NDA-305-00 Revision.0 June, 998 Stock # 24727 LIABILITY DISCLAIMER NEC America reserves the right to change the specifications,
TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
SensyCal FCU200, FCU400 Universal measuring computer M-Bus protocol
Protocol description COM/FCU/MBUS-EN SensyCal FCU200, FCU400 Universal measuring computer M-Bus protocol Measurement made easy Contents Contents Universal measuring computer SensyCal FCU200, FCU400 Protocol
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
HTML Code Generator V 1.0 For Simatic IT Modules CP 443-1 IT, 343-1 IT, 243-1 IT
HTML Code Generator V 1.0 For Simatic IT Modules CP 443-1 IT, 343-1 IT, 243-1 IT Manual This manual and program are freeware. Every user can use, copy or forward this program and documentation FREE OF
Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: 5204183. www.guentner.de. Data sheet GIOD.1 V_3.0
Data sheet GIOD.1 Input/output module with CAN bus ERP no.: 5204183 www.guentner.de Page 2 / 10 Contents 1 GIOD.1... 3 1.1 Functional description...3 1.2 Connections... 5 1.3 Electrical properties of...