EMDX3 Multifunction meter Cat No ModbusTable LGR EN v1.01.xls

Size: px
Start display at page:

Download "EMDX3 Multifunction meter Cat No. 146 69 ModbusTable LGR EN v1.01.xls"

Transcription

1 GENERAL MODBUS TABLE ORGANIZATION Starting of the Starting of the Group s Group s System Version (Release) System Version (Build) Group Name (Text) Group Code Group Complexity Group Version C550 Measures - Metrology Affected by current and voltage transformers F040 D3 101, C C650 Measures - Energies F040 D3 101, C C750 Statistique Affected by current and voltage transformers F040 D3 101, C C850 Measures - Metrology Not Affected by current and voltage transformers F040 D3 101, C C900 Measures - Temperatures F040 D3 101, C C950 Measures - Harmonic THD F040 D3 101, C C95A Measures - Harmonic I : harmonic order F040 D3 101, C C9D7 Measures - Harmonic V PH/Ph :harmonic order F040 D3 101, C CA35 Measures - Harmonic V PH/N : harmonic order F040 D3 101, C CB00 Measures - Input/Output State F040 D3 101, C Settings F040 D3 101, C Reset to zero F040 D3 101, C Alarms F040 D3 101, C 2560 A00 Pulses Meters Values F040 D3 101, C 3088 C10 Last 10 Alarms event log F040 D3 101, C 3328 D00 Last 10 Voltage dips event log / SAG F040 D3 101, C 3584 E00 Last 10 Voltage surge event log / SWELL F040 D3 101, C 3840 F00 Minimum and Maximum Instantanious value F040 D3 101, C Last Power supply cut off F040 D3 101, C AVG Power Historical F040 D3 101, C AVG Voltage Historical F040 D3 101, C AVG Frequency Historical F040 D3 101, C E000 Network settings F040 D3 101, C E100 Hour/Date setting F040 D3 101, C E200 Action system F040 D3 101, C MODBUS PROTOCOL DETAILS Code Exception 3 01, 02, 03, 04, 05, 06, 07, , 02, 03, 04, 05, 06, 07, , 02, 03, 04, 05, 06, 07, 08 Encoding "Big Endian" (most significant byte first) MODBUS OVER SERIAL DETAILS Physical Layer Trasmission Modes Device ing Baud Rates (bit/s) Bits bits trasmission sequence Parity Stop Bits standard EIA/TIA 485 (RS-485) two-wire configuration RTU programmable (2400, 4800, 9600, 19200, 38400) 8 Least significant bit first no, odd, even 1, 2 MASTER/SLAVE COMMUNICATION TIMING Timer Descrtiption Timer Value (msec) Inter-character time-out < 1,5 character times Response delay (from master request) 250 Delay Time (between two master trasmissions) - File and printed copies of this document are not subject to document change control. Page 1/40

2 GENERAL REFER ALSO TO: - MODBUS over serial line specification and implementation guide V MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b NOTE: File and printed copies of this document are not subject to document change control. File and printed copies of this document are not subject to document change control. Page 2/40

3 DISCRETE INPUT Bits (R) [bit] Description Note Read (no DISCRETE INPUTS availables) File and printed copies of this document are not subject to document change control. Page 3/40

4 COILS Bits (R&W) [bit] Description Note Read (no COILS availables) Write File and printed copies of this document are not subject to document change control. Page 4/40

5 INPUT REGISTERS Words (R) Code Alarms OUT1: Current alarm on lower threshold cause: 0 : No Alarm / 1 : I1 / 2 : I2 / 3 : I3 / 4 : IN / 5 : U12 / 6 : U23 / 7 : U31 / 8 : P+ / 9 : Q+ / 10 : S / 11 : F / 12 : PFL / 15: thdi1 / 16: thdi2 / 17 : thdi3 / 18 : thdu12 / 19 : thdu23 / 20 : thdu31 / 21 : Hour / 22: V1 / 23 : V2 / 24 : V3 / 25 : thdin 26: thdv1 / 27 : thdv2 / 28 : thd V3 / 29 : P / 30 : Q / 31 : PFC / 32 : T C 1 / 33 : T C 2 / 34 : T C 3 / 35 : T C internal / 36 : P predicted / 37 : Q predicted / 38 : S predicted 0 : 1 / 2 / 3 / 4 : ma 5 / 6 / 7 : mv 8 : mw 9 : mvar 10 : mva 11 : Hz/ : 15 / 16 / 17 : / / 19 / 20 : / : Hour/ / 23 / 24 : mv 25 : / / 27 / 28 : / : 32 / 33 / 34 / 35 : C/10 36 : mw 37 : mvar 38 : mva OUT1: Current alarm on lower threshold : min value (same 500) OUT1: Current alarm on upper threshold cause: 0 : No Alarm / 1 : I1 / 2 : I2 / 3 : I3 / 4 : IN / 5 : U12 / 6 : U23 / 7 : U31 / 8 : P+ / 9 : Q+ / 10 : S / 11 : F / 12 : PFL / 15: thdi1 / 16: thdi2 / 17 : thdi3 / 18 : thdu12 / 19 : thdu23 / 20 : thdu31 / 21 : Hour / 22: V1 / 23 : V2 / 24 : V3 / 25 : thdin 26: thdv1 / 27 : thdv2 / 28 : thd V3 / 29 : P / 30 : Q / 31 : PFC / 32 : T C 1 / 33 : T C 2 / 34 : T C 3 / 35 : T C internal / 36 : P predicted / 37 : Q predicted / 38 : S predicted 0 : 1 / 2 / 3 / 4 : ma 5 / 6 / 7 : mv 8 : mw 9 : mvar 10 : mva 11 : Hz/ : 15 / 16 / 17 : / / 19 / 20 : / : Hour/ / 23 / 24 : mv 25 : / / 27 / 28 : / : 32 / 33 / 34 / 35 : C/10 36 : mw 37 : mvar 38 : mva OUT1: Current alarm on upper threshold : max value (same 503) 3 File and printed copies of this document are not subject to document change control. Page 5/40

6 INPUT REGISTERS Words (R) Code OUT1: Current alarm duration s OUT1: Previous (n-1) alarm on lower threshold cause (same 500) OUT1: Previous (n-1) alarm on lower threshold min value (same 500) A 1 OUT1: Previous (n-1) alarm on upper threshold cause (same 503) B 2 OUT1: Previous (n-1) alarm on upper threshold max value (same 503) D 1 OUT1: Previous (n-1) alarm duration s E 1 OUT1: Previous (n-2) alarm on lower threshold cause (same 500) F 2 OUT1: Previous (n-2) alarm on lower threshold min value (same 500) OUT1: Previous (n-2) alarm on upper threshold cause (same 503) OUT1: Previous (n-2) alarm on upper threshold max value (same 503) OUT1: Previous (n-2) alarm duration s OUT1: Previous (n-3) alarm on lower threshold cause (same 500) OUT1: Previous (n-3) alarm on lower threshold min value (same 500) OUT1: Previous (n-3) alarm on upper threshold cause (same 503) OUT1: Previous (n-3) alarm on upper threshold max value (same 503) B 1 OUT1: Previous (n-3) alarm duration C 28 OUT 2: (same descriptions that OUTPUT 1) OUT 2: status inputs 1,2,3, 4, 5, OUT 3: (same descriptions that OUTPUT 1) OUT 4: (same descriptions that OUTPUT 1) OUT 5: (same descriptions that OUTPUT 1) E 7 OUT 6: (same descriptions that OUTPUT 1) A00 12 Pulse Meters Values A00 2 input E1 Option ES A02 2 input E2 Option ES A04 2 input E3 Option ES A06 2 input E4 Option ES A08 2 input E5 Option ES A0A 2 input E6 Option ES C Last 10 Alarms event log C10 1 Alarm Level n-1 : output number (1 à 6) 3 File and printed copies of this document are not subject to document change control. Page 6/40

7 INPUT REGISTERS Words (R) Code C11 1 Alarm Level n-1 on lower threshold cause: 0 : No Alarm / 1 : I1 / 2 : I2 / 3 : I3 / 4 : IN / 5 : U12 / 6 : U23 / 7 : U31 / 8 : P+ / 9 : Q+ / 10 : S / 11 : F / 12 : PFL / 15: thdi1 / 16: thdi2 / 17 : thdi3 / 18 : thdu12 / 19 : thdu23 / 20 : thdu31 / 21 : Hour / 22: V1 / 23 : V2 / 24 : V3 / 26: thdv1 / 27 : thdv2 / 28 : thd V3 / 29 : P / 30 : Q / 31 : PFC / 32 : T C 1 / 33 : T C 2 / 34 : T C 3 / 35 : T C internal / 36 : P predicted / 37 : Q predicted / 38 : S predicted 0 : 1 / 2 / 3 / 4 : ma 5 / 6 / 7 : mv 8 : mw 9 : mvar 10 : mva 11 : Hz/ : 15 / 16 / 17 : / / 19 / 20 : / : Hour/ / 23 / 24 : mv 26 / 27 / 28 : / : 32 / 33 / 34 / 35 : C/10 36 : mw 37 : mvar 38 : mva C12 2 Alarm Level n-1 on lower threshold : min value (same C11) C14 1 Alarm Level n-1 on upper threshold cause: 0 : No Alarm / 1 : I1 / 2 : I2 / 3 : I3 / 4 : IN / 5 : U12 / 6 : U23 / 7 : U31 / 8 : P+ / 9 : Q+ / 10 : S / 11 : F / 12 : PFL / 15: thdi1 / 16: thdi2 / 17 : thdi3 / 18 : thdu12 / 19 : thdu23 / 20 : thdu31 / 21 : Hour / 22: V1 / 23 : V2 / 24 : V3 / 26: thdv1 / 27 : thdv2 / 28 : thd V3 / 29 : P / 30 : Q / 31 : PFC / 32 : T C 1 / 33 : T C 2 / 34 : T C 3 / 35 : T C internal / 36 : P predicted / 37 : Q predicted / 38 : S predicted 0 : 1 / 2 / 3 / 4 : ma 5 / 6 / 7 : mv 8 : mw 9 : mvar 10 : mva 11 : Hz/ : 15 / 16 / 17 : / / 19 / 20 : / : Hour/ / 23 / 24 : mv 26 / 27 / 28 : / : 32 / 33 / 34 / 35 : C/10 36 : mw 37 : mvar 38 : mva C15 2 Alarm Level n-1 on upper threshold : max value (same C14) C17 1 Alarm Level n-1: duration C18 1 Alarm Level n-1: Month C19 1 Alarm Level n-1: Day C1A 1 Alarm Level n-1: Year C1B 1 Alarm Level n-1: Hour C1C 1 Alarm Level n-1: Minute C1D 1 Alarm Level n-1: Second C1E 14 Alarm Level n-2 see Level n C2C 14 Alarm Level n-3 see Level n C3A 14 Alarm Level n-4 see Level n C48 14 Alarm Level n-5 see Level n C56 14 Alarm Level n-6 see Level n C64 14 Alarm Level n-7 see Level n File and printed copies of this document are not subject to document change control. Page 7/40

8 INPUT REGISTERS Words (R) Code C72 14 Alarm Level n-8 see Level n C80 14 Alarm Level n-9 see Level n C8E 14 Alarm Level n-10 see Level n D00 14 Last 10 Voltage dips event log / SAG Voltage SAG Level n-1: root cause on phase to phase voltage D : none, 5: U12, 3 6: U23, 7: U D01 2 Voltage SAG Level n-1: Value 0,01 V D03 1 Voltage SAG Level n-1: Root cause on phase to neutral voltage 0 : none, 22 : V1, 3 23 : V2, 24 : V D04 2 Voltage SAG Level n-1: Value 0,01 V D06 2 Voltage SAG Level n-1: duration 1 msec D08 1 Voltage SAG Level n-1: Month D09 1 Voltage SAG Level n-1: Day D0A 1 Voltage SAG Level n-1: Year D0B 1 Voltage SAG Level n-1: Hour D0C 1 Voltage SAG Level n-1: Minute D0D 1 Voltage SAG Level n-1: Second D0E 14 Voltage SAG Level n-2 see Level n D1C 14 Voltage SAG Level n-3 see Level n D2A 14 Voltage SAG Level n-4 see Level n D38 14 Voltage SAG Level n-5 see Level n D46 14 Voltage SAG Level n-6 see Level n D54 14 Voltage SAG Level n-7 see Level n D62 14 Voltage SAG Level n-8 see Level n D70 14 Voltage SAG Level n-9 see Level n D7E 14 Voltage SAG Level n-10 see Level n E00 14 Last 10 Voltage surge event log / SWELL E00 1 Voltage SWELL Level n-1: root cause on phase to phase voltage 0 : none, 5: U12, 3 6: U23, 7: U E01 2 Voltage SWELL Level n-1: Value 0,01 V E03 1 Voltage SWELL Level n-1: Root cause on phase to neutral voltage 0 : none, 22 : V1, 3 23 : V2, 24 : V E04 2 Voltage SWELL Level n-1: Value 0,01 V E06 2 Voltage SWELL Level n-1: duration 1 msec E08 1 Voltage SWELL Level n-1: Month E09 1 Voltage SWELL Level n-1: Day E0A 1 Voltage SWELL Level n-1: Year E0B 1 Voltage SWELL Level n-1: Hour E0C 1 Voltage SWELL Level n-1: Minute E0E 1 Voltage SWELL Level n-1: Second E0E 14 Voltage SWELL Level n-2 see Level n-1 3 File and printed copies of this document are not subject to document change control. Page 8/40

9 INPUT REGISTERS Words (R) Code E1C 14 Voltage SWELL Level n-3 see Level n E2A 14 Voltage SWELL Level n-4 see Level n E38 14 Voltage SWELL Level n-5 see Level n E46 14 Voltage SWELL Level n-6 see Level n E54 14 Voltage SWELL Level n-7 see Level n E62 14 Voltage SWELL Level n-8 see Level n E70 14 Voltage SWELL Level n-9 see Level n E7E 14 Voltage SWELL Level n-10 see Level n F Minimum and Maximum Instantanious value F00 2 3I Minimum 1 ma F02 1 Month F03 1 Day F04 1 Year F05 1 Hour F06 1 Minute F07 1 Second F08 2 3I Maximum 1 ma F0A 1 Month F0B 1 Day F0C 1 Year F0D 1 Hour F0E 1 Minute F0F 1 Second F10 2 IN Minimum 1 ma F12 1 Month F13 1 Day F14 1 Year F15 1 Hour F16 1 Minute F17 1 Second F18 2 In Maximum 1 ma F1A 1 Month F1B 1 Day F1C 1 Year F1D 1 Hour F1E 1 Minute F1F 1 Second F20 2 3U Minimum 0,01 V F22 1 Month F23 1 Day F24 1 Year F25 1 Hour F26 1 Minute F27 1 Second F28 2 3U Maximum 0,01 V F2A 1 Month F2B 1 Day F2C 1 Year F2D 1 Hour F2E 1 Minute F2F 1 Second F30 2 3V Minimum 0,01 V F32 1 Month F33 1 Day F34 1 Year F35 1 Hour 3 File and printed copies of this document are not subject to document change control. Page 9/40

10 INPUT REGISTERS Words (R) Code F36 1 Minute F37 1 Second F38 2 3V Maximum 0,01 V F3A 1 Month F3B 1 Day F3C 1 Year F3D 1 Hour F3E 1 Minute F3F 1 Second F40 2 F Minimum 0,01 Hz F42 1 Month F43 1 Day F44 1 Year F45 1 Hour F46 1 Minute F47 1 Second F48 2 F Maximum 0,01 Hz F4A 1 Month F4B 1 Day F4C 1 Year F4D 1 Hour F4E 1 Minute F4F 1 Second F50 2 PF Minimum 0,01 Hz F52 1 Month F53 1 Day F54 1 Year F55 1 Hour F56 1 Minute F57 1 Second F58 2 PF Maximum 0, F5A 1 Month F5B 1 Day F5C 1 Year F5D 1 Hour F5E 1 Minute F5F 1 Second F60 2 P+ Minimum 0,01 kw F62 1 Month F63 1 Day F64 1 Year F65 1 Hour F66 1 Minute F67 1 Second F68 2 P+ Maximum 0,01 kw F6A 1 Month F6B 1 Day F6C 1 Year F6D 1 Hour F6E 1 Minute F6F 1 Second F70 2 P- Minimum 0,01 kw F72 1 Month F73 1 Day F74 1 Year F75 1 Hour 3 File and printed copies of this document are not subject to document change control. Page 10/40

11 INPUT REGISTERS Words (R) Code F76 1 Minute F77 1 Second F78 2 P- Maximum 0,01 kw F7A 1 Month F7B 1 Day F7C 1 Year F7D 1 Hour F7E 1 Minute F7F 1 Second F80 2 Q+ Minimum 0,01 kvar F82 1 Month F83 1 Day F84 1 Year F85 1 Hour F86 1 Minute F87 1 Second F88 2 Q+ Maximum 0,01 kvar F8A 1 Month F8B 1 Day F8C 1 Year F8D 1 Hour F8E 1 Minute F8F 1 Second F90 2 Q- Minimum 0,01 kvar F92 1 Month F93 1 Day F94 1 Year F95 1 Hour F96 1 Minute F97 1 Second F98 2 Q- Maximum 0,01 kvar F9A 1 Month F9B 1 Day F9C 1 Year F9D 1 Hour F9E 1 Minute F9F 1 Second FA0 2 S Minimum 0,01 kva FA2 1 Month FA3 1 Day FA4 1 Year FA5 1 Hour FA6 1 Minute FA7 1 Second FA8 2 S Maximum 0,01 kva FAA 1 Month FAB 1 Day FAC 1 Year FAD 1 Hour FAE 1 Minute FAF 1 Second FB0 2 THD 3I Minimum 0,1 % FB2 1 Month FB3 1 Day FB4 1 Year FB5 1 Hour 3 File and printed copies of this document are not subject to document change control. Page 11/40

12 INPUT REGISTERS Words (R) Code FB6 1 Minute FB7 1 Second FB8 2 THD 3I Maximum 0,1 % FBA 1 Month FBB 1 Day FBC 1 Year FBD 1 Hour FBE 1 Minute FBF 1 Second FC0 2 THD IN Minimum 0,1 % FC2 1 Month FC3 1 Day FC4 1 Year FC5 1 Hour FC6 1 Minute FC7 1 Second FC8 2 THD IN Maximum 0,1 % FCA 1 Month FCB 1 Day FCC 1 Year FCD 1 Hour FCE 1 Minute FCF 1 Second FD0 2 THD 3U Minimum 0,1 % FD2 1 Month FD3 1 Day FD4 1 Year FD5 1 Hour FD6 1 Minute FD7 1 Second FD8 2 THD 3U Maximum 0,1 % FDA 1 Month FDB 1 Day FDC 1 Year FDD 1 Hour FDE 1 Minute FDF 1 Second FE0 2 THD 3V Minimum 0,1 % FE2 1 Month FE3 1 Day FE4 1 Year FE5 1 Hour FE6 1 Minute FE7 1 Second FE8 2 THD 3V Maximum 0,1 % FEA 1 Month FEB 1 Day FEC 1 Year FED 1 Hour FEE 1 Minute FEF 1 Second Last Power supply cut off Power CUT-OFF Level n-1: Month Power CUT-OFF Level n-1: Day Power CUT-OFF Level n-1: Year Power CUT-OFF Level n-1: Hour 3 File and printed copies of this document are not subject to document change control. Page 12/40

13 INPUT REGISTERS Words (R) Code Power CUT-OFF Level n-1: Minute Power CUT-OFF Level n-1: Second Power CUT-OFF Level n-2 see Level n C 6 Power CUT-OFF Level n-3 see Level n Power CUT-OFF Level n-4 see Level n Power CUT-OFF Level n-5 see Level n E 6 Power CUT-OFF Level n-6 see Level n Power CUT-OFF Level n-7 see Level n A 6 Power CUT-OFF Level n-8 see Level n Power CUT-OFF Level n-9 see Level n Power CUT-OFF Level n-10 see Level n AVG Power Historical PHIS : pointer on the most recent P value in the Historical table QHIS : pointer on the most recent Q value in the Historical table Pointer update Date&Time Zone P.1 P+ / P- values 0,1 Wh Zone P.2 P+ / P- values 0,1 Wh D 4500 Zone Q.1 Q+ / Q- values 0,1 varh C Zone Q.2 Q+ / Q- values 0,1 varh AVG Voltage Historical Voltage Pointer VHIS Update Date&Time U, 3V values 0,1 V AVG Frequency Historical Frequency Pointer FHIS Update DateTime F Value 0,01 Hz C Measure - Metrology Affected by current and voltage transformers C550 2 Hour Meter unsigned long 0,01 h NOTE C552 2 Phase to Phase Voltage: U12 unsigned long 0,01 V NOTE C554 2 Phase to Phase Voltage: U23 unsigned long 0,01 V NOTE C556 2 Phase to Phase Voltage: U31 unsigned long 0,01 V NOTE C558 2 Simple voltage : V1 unsigned long 0,01 V NOTE C55A 2 Simple voltage : V2 unsigned long 0,01 V NOTE C55C 2 Simple voltage : V3 unsigned long 0,01 V NOTE C55E 2 Frequency : F unsigned long 0,01 Hz NOTE C560 2 Current : I1 unsigned long 1 ma NOTE C562 2 Current : I2 unsigned long 1 ma NOTE C564 2 Current : I3 unsigned long 1 ma NOTE C566 2 Neutral Current : In unsigned long 1 ma NOTE C568 2 active Power +/- : P signed long 0,01 kw NOTE C56A 2 reactive Power +/- : Q signed long 0,01 kvar NOTE C56C 2 apparent power : S unsigned long 0,01 kva NOTE C56E 2 power factor : -: leading et + : lagging : PF signed long 0,001 NOTE C570 2 Active Power phase 1 +/- : P1 signed long 0,01 kw NOTE C572 2 Active Power phase 2 +/- : P2 signed long 0,01 kw NOTE C574 2 Active Power phase 3 +/- : P3 signed long 0,01 kw NOTE C576 2 Reactive Power phase 1 +/- : Q1 signed long 0,01 kvar NOTE C578 2 Reactive Power phase 2 +/- : Q2 signed long 0,01 kvar NOTE C57A 2 Reactive Power phase 3 +/- : Q3 signed long 0,01 kvar NOTE C57C 2 Apparent power phase 1 : S1 unsigned long 0,01 kva NOTE C57E 2 Apparent power phase 2 : S2 unsigned long 0,01 kva NOTE C580 2 Apparent power phase 3 : S3 unsigned long 0,01 kva NOTE1 3 File and printed copies of this document are not subject to document change control. Page 13/40

14 INPUT REGISTERS Words (R) Code C582 2 Power Factor phase 1 -: leading and + : lagging : PF1 signed long 0,001 NOTE C584 2 Power Factor phase 2 -: leading and + : lagging : PF2 signed long 0,001 NOTE C586 2 Power Factor phase 3 -: leading and + : lagging : PF3 signed long 0,001 NOTE C Measure - Energies C650 2 Hour meter unsigned long 0,01 h NOTE C65C 2 Partial Positive Active Energy: Ea+ unsigned long 1 kwh NOTE C65E 2 Partial Positive Reactive Energy: Er + unsigned long 1 kvarh NOTE C660 2 Partial Apparent Energy : Es unsigned long 1 kvah NOTE C662 2 Partial Negative Active Energy : Ea- unsigned long 1 kwh NOTE C664 2 Partial Negative Reactive Energy : Er - unsigned long 1 kvarh NOTE C666 2 Impulse meter number unsigned long 1 NOTE C668 2 Impulse meter 1 unsigned long 1 NOTE C66A 2 Impulse meter 2 unsigned long 1 NOTE C66C 2 Impulse meter 3 unsigned long 1 NOTE C66E 2 Impulse meter 4 unsigned long 1 NOTE C670 2 Impulse meter 5 unsigned long 1 NOTE C672 2 Impulse meter 6 unsigned long 1 NOTE C67C 2 Predictive Active Power unsigned long 1 kwh NOTE C67E 2 Predictive Reactive Power unsigned long 1 kvarh NOTE C680 2 Predictive Apprent Power unsigned long 1 kvah NOTE C682 2 Ea+ beetwen two integration top unsigned long 0,01 kwh NOTE C684 2 Ea- beetwen two integration top unsigned long 0,01 kwh NOTE C686 2 Er+ beetwen two integration top unsigned long 0,01 kvarh NOTE C688 2 Er- beetwen two integration top unsigned long 0,01 kvarh NOTE C Measure - Statistique Affected by current and voltage transformers C750 2 Avg U12 unsigned long 0,01 V NOTE C752 2 Avg U23 unsigned long 0,01 V NOTE C754 2 Avg U31 unsigned long 0,01 V NOTE C756 2 Avg V1 unsigned long 0,01 V NOTE C758 2 Avg V2 unsigned long 0,01 V NOTE C75A 2 Avg V3 unsigned long 0,01 V NOTE C75C 2 Avg F unsigned long 0,01 Hz NOTE C75E 2 Avg I1 unsigned long 1 ma NOTE C760 2 Avg I2 unsigned long 1 ma NOTE C762 2 Avg I3 unsigned long 1 ma NOTE C764 2 Avg In unsigned long 1 ma NOTE C766 2 Avg P+ ( active power +) unsigned long 0,01 kw NOTE C768 2 Avg P- ( active power -) unsigned long 0,01 kw NOTE C76A 2 Avg Q+ ( reactive power +) unsigned long 0,01 kvar NOTE C76C 2 Avg Q-( reactive power -) unsigned long 0,01 kvar NOTE C76E 2 Avg S ( apparent power) unsigned long 0,01 kva NOTE C770 2 Max/avg U12 unsigned long 0,01 V NOTE C772 2 Max/avg U23 unsigned long 0,01 V NOTE C774 2 Max/avg U31 unsigned long 0,01 V NOTE C776 2 Max/avg V1 unsigned long 0,01 V NOTE C778 2 Max/avg V2 unsigned long 0,01 V NOTE C77A 2 Max/avg V3 unsigned long 0,01 V NOTE C77C 2 Max/avg F unsigned long 0,01 Hz NOTE C77E 2 Max/avg I1 unsigned long 1 ma NOTE C780 2 Max/avg I2 unsigned long 1 ma NOTE C782 2 Max/avg I3 unsigned long 1 ma NOTE C784 2 Max/avg In unsigned long 1 ma NOTE1 3 File and printed copies of this document are not subject to document change control. Page 14/40

15 INPUT REGISTERS Words (R) Code C786 2 Max/avg P+ unsigned long 0,01 kw NOTE C788 2 Max/avg P- unsigned long 0,01 kw NOTE C78A 2 Max/avg Q+ unsigned long 0,01 kvar NOTE C78C 2 Max/avg Q- unsigned long 0,01 kvar NOTE C78E 2 Max/avg S unsigned long 0,01 kva NOTE C Measure - Metrology Not Affected by current and voltage transformers C850 1 Hour Meter unsigned word 1 h NOTE C851 1 Phase to Phase Voltage: U12 unsigned word 0,01 V NOTE C852 1 Phase to Phase Voltage: U23 unsigned word 0,01 V NOTE C853 1 Phase to Phase Voltage: U31 unsigned word 0,01 V NOTE C854 1 Simple voltage : V1 unsigned word 0,01 V NOTE C855 1 Simple voltage : V2 unsigned word 0,01 V NOTE C856 1 Simple voltage : V3 unsigned word 0,01 V NOTE C857 1 Frequency : F unsigned word 0,01 Hz NOTE C858 1 Current : I1 unsigned word 1 ma NOTE C859 1 Current : I2 unsigned word 1 ma NOTE C85A 1 Current : I3 unsigned word 1 ma NOTE C85B 1 Neutral Current : In unsigned word 1 ma NOTE C85C 1 active Power +/- : P signed word 0,01 kw NOTE C85D 1 reactive Power +/- : Q signed word 0,01 kvar NOTE C85E 1 apparent power : S unsigned word 0,01 kva NOTE C85F 1 power factor : -: leading and + : lagging : PF signed word 0,001 NOTE C860 1 Active Power phase 1 +/- : P1 signed word 0,01 kw NOTE C861 1 Active Power phase 2 +/- : P2 signed word 0,01 kw NOTE C862 1 Active Power phase 3 +/- : P3 signed word 0,01 kw NOTE C863 1 Reactive Power phase 1 +/- : Q1 signed word 0,01 kvar NOTE C864 1 Reactive Power phase 2 +/- : Q2 signed word 0,01 kvar NOTE C865 1 Reactive Power phase 3 +/- : Q3 signed word 0,01 kvar NOTE C866 1 Apparent power phase 1 : S1 unsigned word 0,01 kva NOTE C867 1 Apparent power phase 2 : S2 unsigned word 0,01 kva NOTE C868 1 Apparent power phase 3 : S3 unsigned word 0,01 kva NOTE C869 1 Power Factor phase 1 -: leading and + : lagging : PF1 signed word 0,001 NOTE C86A 1 Power Factor phase 2 -: leading and + : lagging : PF2 signed word 0,001 NOTE C86B 1 Power Factor phase 3 -: leading and + : lagging : PF3 signed word 0,001 NOTE C86F 1 Total Positive Active Energy (no resetable) : Ea+ unsigned word 1 MWh NOTE C871 1 Total Negative Active Energy (no resetable) : Ea- unsigned word 1 MWh NOTE C900 6 Measure - Temperatures C900 1 Internal module Temperature present 0, 1 0=no, 1=yes C901 1 module Temperature 1 C C902 1 of external Temperature sensors C903 1 Temperature extern 1 1 C C904 1 Temperature extern 2 1 C C905 1 Temperature extern 3 1 C C Measure - Harmonic THD C950 1 thd U12 unsigned word 0,1 % NOTE C951 1 thd U23 unsigned word 0,1 % NOTE C952 1 thd U31 unsigned word 0,1 % NOTE C953 1 thd V1 unsigned word 0,1 % NOTE C954 1 thd V2 unsigned word 0,1 % NOTE C955 1 thd V3 unsigned word 0,1 % NOTE1 3 File and printed copies of this document are not subject to document change control. Page 15/40

16 INPUT REGISTERS Words (R) Code C956 1 thd I1 unsigned word 0,1 % NOTE C957 1 thd I2 unsigned word 0,1 % NOTE C958 1 thd I3 unsigned word 0,1 % NOTE C959 1 thd In unsigned word 0,1 % NOTE C95A 125 Measure - Harmonic I : harmonic order C95A 1 of harmonic rows 1 number of I harmonic order: max 125, value if not available: C95B 1 harmonic I1 row 3 unsigned word 0,1 % NOTE C95C 1 harmonic I2 row 3 unsigned word 0,1 % NOTE C95D 1 harmonic I3 row 3 unsigned word 0,1 % NOTE C95E 1 harmonic IN row 3 unsigned word 0,1 % NOTE C95F 1 harmonic I1 row 5 unsigned word 0,1 % NOTE C960 1 harmonic I2 row 5 unsigned word 0,1 % NOTE C961 1 harmonic I3 row 5 unsigned word 0,1 % NOTE C962 1 harmonic IN row 5 unsigned word 0,1 % NOTE C963 1 harmonic I1 row 7 unsigned word 0,1 % NOTE C964 1 harmonic I2 row 7 unsigned word 0,1 % NOTE C965 1 harmonic I3 row 7 unsigned word 0,1 % NOTE C966 1 harmonic IN row 7 unsigned word 0,1 % NOTE C967 1 harmonic I1 row 9 unsigned word 0,1 % NOTE C968 1 harmonic I2 row 9 unsigned word 0,1 % NOTE C969 1 harmonic I3 row 9 unsigned word 0,1 % NOTE C96A 1 harmonic IN row 9 unsigned word 0,1 % NOTE C96B 1 harmonic I1 row 11 unsigned word 0,1 % NOTE C96C 1 harmonic I2 row 11 unsigned word 0,1 % NOTE C96D 1 harmonic I3 row 11 unsigned word 0,1 % NOTE C96E 1 harmonic IN row 11 unsigned word 0,1 % NOTE C96F 1 harmonic I1 row 13 unsigned word 0,1 % NOTE C970 1 harmonic I2 row 13 unsigned word 0,1 % NOTE C971 1 harmonic I3 row 13 unsigned word 0,1 % NOTE C972 1 harmonic IN row 13 unsigned word 0,1 % NOTE C973 1 harmonic I1 row 15 unsigned word 0,1 % NOTE C974 1 harmonic I2 row 15 unsigned word 0,1 % NOTE C975 1 harmonic I3 row 15 unsigned word 0,1 % NOTE C976 1 harmonic IN row 15 unsigned word 0,1 % NOTE C977 1 harmonic I1 row 17 unsigned word 0,1 % NOTE C978 1 harmonic I2 row 17 unsigned word 0,1 % NOTE C979 1 harmonic I3 row 17 unsigned word 0,1 % NOTE C97A 1 harmonic IN row 17 unsigned word 0,1 % NOTE C97B 1 harmonic I1 row 19 unsigned word 0,1 % NOTE C97C 1 harmonic I2 row 19 unsigned word 0,1 % NOTE C97D 1 harmonic I3 row 19 unsigned word 0,1 % NOTE C97E 1 harmonic IN row 19 unsigned word 0,1 % NOTE C97F 1 harmonic I1 row 21 unsigned word 0,1 % NOTE C980 1 harmonic I2 row 21 unsigned word 0,1 % NOTE C981 1 harmonic I3 row 21 unsigned word 0,1 % NOTE C982 1 harmonic IN row 21 unsigned word 0,1 % NOTE C983 1 harmonic I1 row 23 unsigned word 0,1 % NOTE C984 1 harmonic I2 row 23 unsigned word 0,1 % NOTE C985 1 harmonic I3 row 23 unsigned word 0,1 % NOTE C986 1 harmonic IN row 23 unsigned word 0,1 % NOTE C987 1 harmonic I1 row 25 unsigned word 0,1 % NOTE1 3 File and printed copies of this document are not subject to document change control. Page 16/40

17 INPUT REGISTERS Words (R) Code C988 1 harmonic I2 row 25 unsigned word 0,1 % NOTE C989 1 harmonic I3 row 25 unsigned word 0,1 % NOTE C98A 1 harmonic IN row 25 unsigned word 0,1 % NOTE C98B 1 harmonic I1 row 27 unsigned word 0,1 % NOTE C98C 1 harmonic I2 row 27 unsigned word 0,1 % NOTE C98D 1 harmonic I3 row 27 unsigned word 0,1 % NOTE C98E 1 harmonic IN row 27 unsigned word 0,1 % NOTE C98F 1 harmonic I1 row 29 unsigned word 0,1 % NOTE C990 1 harmonic I2 row 29 unsigned word 0,1 % NOTE C991 1 harmonic I3 row 29 unsigned word 0,1 % NOTE C992 1 harmonic IN row 29 unsigned word 0,1 % NOTE C993 1 harmonic I1 row 31 unsigned word 0,1 % NOTE C994 1 harmonic I2 row 31 unsigned word 0,1 % NOTE C995 1 harmonic I3 row 31 unsigned word 0,1 % NOTE C996 1 harmonic IN row 31 unsigned word 0,1 % NOTE C997 1 harmonic I1 row 33 unsigned word 0,1 % NOTE C998 1 harmonic I2 row 33 unsigned word 0,1 % NOTE C999 1 harmonic I3 row 33 unsigned word 0,1 % NOTE C99A 1 harmonic IN row 33 unsigned word 0,1 % NOTE C99B 1 harmonic I1 row 35 unsigned word 0,1 % NOTE C99C 1 harmonic I2 row 35 unsigned word 0,1 % NOTE C99D 1 harmonic I3 row 35 unsigned word 0,1 % NOTE C99E 1 harmonic IN row 35 unsigned word 0,1 % NOTE C99F 1 harmonic I1 row 37 unsigned word 0,1 % NOTE C9A0 1 harmonic I2 row 37 unsigned word 0,1 % NOTE C9A1 1 harmonic I3 row 37 unsigned word 0,1 % NOTE C9A2 1 harmonic IN row 37 unsigned word 0,1 % NOTE C9A3 1 harmonic I1 row 39 unsigned word 0,1 % NOTE C9A4 1 harmonic I2 row 39 unsigned word 0,1 % NOTE C9A5 1 harmonic I3 row 39 unsigned word 0,1 % NOTE C9A6 1 harmonic IN row 39 unsigned word 0,1 % NOTE C9A7 1 harmonic I1 row 41 unsigned word 0,1 % NOTE C9A8 1 harmonic I2 row 41 unsigned word 0,1 % NOTE C9A9 1 harmonic I3 row 41 unsigned word 0,1 % NOTE C9AA 1 harmonic IN row 41 unsigned word 0,1 % NOTE C9AB 1 harmonic I1 row 43 unsigned word 0,1 % NOTE C9AC 1 harmonic I2 row 43 unsigned word 0,1 % NOTE C9AD 1 harmonic I3 row 43 unsigned word 0,1 % NOTE C9AE 1 harmonic IN row 43 unsigned word 0,1 % NOTE C9AF 1 harmonic I1 row 45 unsigned word 0,1 % NOTE C9B0 1 harmonic I2 row 45 unsigned word 0,1 % NOTE C9B1 1 harmonic I3 row 45 unsigned word 0,1 % NOTE C9B2 1 harmonic IN row 45 unsigned word 0,1 % NOTE C9B3 1 harmonic I1 row 47 unsigned word 0,1 % NOTE C9B4 1 harmonic I2 row 47 unsigned word 0,1 % NOTE C9B5 1 harmonic I3 row 47 unsigned word 0,1 % NOTE C9B6 1 harmonic IN row 47 unsigned word 0,1 % NOTE C9B7 1 harmonic I1 row 49 unsigned word 0,1 % NOTE C9B8 1 harmonic I2 row 49 unsigned word 0,1 % NOTE C9B9 1 harmonic I3 row 49 unsigned word 0,1 % NOTE C9BA 1 harmonic IN row 49 unsigned word 0,1 % NOTE C9BB 1 harmonic I1 row 51 unsigned word 0,1 % NOTE C9BC 1 harmonic I2 row 51 unsigned word 0,1 % NOTE C9BD 1 harmonic I3 row 51 unsigned word 0,1 % NOTE C9BE 1 harmonic IN row 51 unsigned word 0,1 % NOTE C9BF 1 harmonic I1 row 53 unsigned word 0,1 % NOTE1 3 File and printed copies of this document are not subject to document change control. Page 17/40

18 INPUT REGISTERS Words (R) Code C9C0 1 harmonic I2 row 53 unsigned word 0,1 % NOTE C9C1 1 harmonic I3 row 53 unsigned word 0,1 % NOTE C9C2 1 harmonic IN row 53 unsigned word 0,1 % NOTE C9C3 1 harmonic I1 row 55 unsigned word 0,1 % NOTE C9C4 1 harmonic I2 row 55 unsigned word 0,1 % NOTE C9C5 1 harmonic I3 row 55 unsigned word 0,1 % NOTE C9C6 1 harmonic IN row 55 unsigned word 0,1 % NOTE C9C7 1 harmonic I1 row 57 unsigned word 0,1 % NOTE C9C8 1 harmonic I2 row 57 unsigned word 0,1 % NOTE C9C9 1 harmonic I3 row 57 unsigned word 0,1 % NOTE C9CA 1 harmonic IN row 57 unsigned word 0,1 % NOTE C9CB 1 harmonic I1 row 59 unsigned word 0,1 % NOTE C9CC 1 harmonic I2 row 59 unsigned word 0,1 % NOTE C9CD 1 harmonic I3 row 59 unsigned word 0,1 % NOTE C9CE 1 harmonic IN row 59 unsigned word 0,1 % NOTE C9CF 1 harmonic I1 row 61 unsigned word 0,1 % NOTE C9D0 1 harmonic I2 row 61 unsigned word 0,1 % NOTE C9D1 1 harmonic I3 row 61 unsigned word 0,1 % NOTE C9D2 1 harmonic IN row 61 unsigned word 0,1 % NOTE C9D3 1 harmonic I1 row 63 unsigned word 0,1 % NOTE C9D4 1 harmonic I2 row 63 unsigned word 0,1 % NOTE C9D5 1 harmonic I3 row 63 unsigned word 0,1 % NOTE C9D6 1 harmonic IN row 63 unsigned word 0,1 % NOTE C9D7 94 Measure - Harmonic V PH/Ph :harmonic order C9D7 1 of harmonic rows 1 number of V Ph/Ph harmonic order: max 94, value if not available: C9D8 1 harmonic U12 row 3 unsigned word 0,1 % NOTE C9D9 1 harmonic U23 row 3 unsigned word 0,1 % NOTE C9DA 1 harmonic U31 row 3 unsigned word 0,1 % NOTE C9DB 1 harmonic U12 row 5 unsigned word 0,1 % NOTE C9DC 1 harmonic U23 row 5 unsigned word 0,1 % NOTE C9DD 1 harmonic U31 row 5 unsigned word 0,1 % NOTE C9DE 1 harmonic U12 row 7 unsigned word 0,1 % NOTE C9DF 1 harmonic U23 row 7 unsigned word 0,1 % NOTE C9E0 1 harmonic U31 row 7 unsigned word 0,1 % NOTE C9E1 1 harmonic U12 row 9 unsigned word 0,1 % NOTE C9E2 1 harmonic U23 row 9 unsigned word 0,1 % NOTE C9E3 1 harmonic U31 row 9 unsigned word 0,1 % NOTE C9E4 1 harmonic U12 row 11 unsigned word 0,1 % NOTE C9E5 1 harmonic U23 row 11 unsigned word 0,1 % NOTE C9E6 1 harmonic U31 row 11 unsigned word 0,1 % NOTE C9E7 1 harmonic U12 row 13 unsigned word 0,1 % NOTE C9E8 1 harmonic U23 row 13 unsigned word 0,1 % NOTE C9E9 1 harmonic U31 row 13 unsigned word 0,1 % NOTE C9EA 1 harmonic U12 row 15 unsigned word 0,1 % NOTE C9EB 1 harmonic U23 row 15 unsigned word 0,1 % NOTE C9EC 1 harmonic U31 row 15 unsigned word 0,1 % NOTE C9ED 1 harmonic U12 row 17 unsigned word 0,1 % NOTE C9EE 1 harmonic U23 row 17 unsigned word 0,1 % NOTE C9EF 1 harmonic U31 row 17 unsigned word 0,1 % NOTE C9F0 1 harmonic U12 row 19 unsigned word 0,1 % NOTE1 3 File and printed copies of this document are not subject to document change control. Page 18/40

19 INPUT REGISTERS Words (R) Code C9F1 1 harmonic U23 row 19 unsigned word 0,1 % NOTE C9F2 1 harmonic U31 row 19 unsigned word 0,1 % NOTE C9F3 1 harmonic U12 row 21 unsigned word 0,1 % NOTE C9F4 1 harmonic U23 row 21 unsigned word 0,1 % NOTE C9F5 1 harmonic U31 row 21 unsigned word 0,1 % NOTE C9F6 1 harmonic U12 row 23 unsigned word 0,1 % NOTE C9F7 1 harmonic U23 row 23 unsigned word 0,1 % NOTE C9F8 1 harmonic U31 row 23 unsigned word 0,1 % NOTE C9F9 1 harmonic U12 row 25 unsigned word 0,1 % NOTE C9FA 1 harmonic U23 row 25 unsigned word 0,1 % NOTE C9FB 1 harmonic U31 row 25 unsigned word 0,1 % NOTE C9FC 1 harmonic U12 row 27 unsigned word 0,1 % NOTE C9FD 1 harmonic U23 row 27 unsigned word 0,1 % NOTE C9FE 1 harmonic U31 row 27 unsigned word 0,1 % NOTE C9FF 1 harmonic U12 row 29 unsigned word 0,1 % NOTE CA00 1 harmonic U23 row 29 unsigned word 0,1 % NOTE CA01 1 harmonic U31 row 29 unsigned word 0,1 % NOTE CA02 1 harmonic U12 row 31 unsigned word 0,1 % NOTE CA03 1 harmonic U23 row 31 unsigned word 0,1 % NOTE CA04 1 harmonic U31 row 31 unsigned word 0,1 % NOTE CA05 1 harmonic U12 row 33 unsigned word 0,1 % NOTE CA06 1 harmonic U23 row 33 unsigned word 0,1 % NOTE CA07 1 harmonic U31 row 33 unsigned word 0,1 % NOTE CA08 1 harmonic U12 row 35 unsigned word 0,1 % NOTE CA09 1 harmonic U23 row 35 unsigned word 0,1 % NOTE CA0A 1 harmonic U31 row 35 unsigned word 0,1 % NOTE CA0B 1 harmonic U12 row 37 unsigned word 0,1 % NOTE CA0C 1 harmonic U23 row 37 unsigned word 0,1 % NOTE CA0D 1 harmonic U31 row 37 unsigned word 0,1 % NOTE CA0E 1 harmonic U12 row 39 unsigned word 0,1 % NOTE CA0F 1 harmonic U23 row 39 unsigned word 0,1 % NOTE CA10 1 harmonic U31 row 39 unsigned word 0,1 % NOTE CA11 1 harmonic U12 row 41 unsigned word 0,1 % NOTE CA12 1 harmonic U23 row 41 unsigned word 0,1 % NOTE CA13 1 harmonic U31 row 41 unsigned word 0,1 % NOTE CA14 1 harmonic U12 row 43 unsigned word 0,1 % NOTE CA15 1 harmonic U23 row 43 unsigned word 0,1 % NOTE CA16 1 harmonic U31 row 43 unsigned word 0,1 % NOTE CA17 1 harmonic U12 row 45 unsigned word 0,1 % NOTE CA18 1 harmonic U23 row 45 unsigned word 0,1 % NOTE CA19 1 harmonic U31 row 45 unsigned word 0,1 % NOTE CA1A 1 harmonic U12 row 47 unsigned word 0,1 % NOTE CA1B 1 harmonic U23 row 47 unsigned word 0,1 % NOTE CA1C 1 harmonic U31 row 47 unsigned word 0,1 % NOTE CA1D 1 harmonic U12 row 49 unsigned word 0,1 % NOTE CA1E 1 harmonic U23 row 49 unsigned word 0,1 % NOTE CA1F 1 harmonic U31 row 49 unsigned word 0,1 % NOTE CA20 1 harmonic U12 row 51 unsigned word 0,1 % NOTE CA21 1 harmonic U23 row 51 unsigned word 0,1 % NOTE CA22 1 harmonic U31 row 51 unsigned word 0,1 % NOTE CA23 1 harmonic U12 row 53 unsigned word 0,1 % NOTE CA24 1 harmonic U23 row 53 unsigned word 0,1 % NOTE CA25 1 harmonic U31 row 53 unsigned word 0,1 % NOTE CA26 1 harmonic U12 row 55 unsigned word 0,1 % NOTE CA27 1 harmonic U23 row 55 unsigned word 0,1 % NOTE CA28 1 harmonic U31 row 55 unsigned word 0,1 % NOTE1 3 File and printed copies of this document are not subject to document change control. Page 19/40

20 INPUT REGISTERS Words (R) Code CA29 1 harmonic U12 row 57 unsigned word 0,1 % NOTE CA2A 1 harmonic U23 row 57 unsigned word 0,1 % NOTE CA2B 1 harmonic U31 row 57 unsigned word 0,1 % NOTE CA2C 1 harmonic U12 row 59 unsigned word 0,1 % NOTE CA2D 1 harmonic U23 row 59 unsigned word 0,1 % NOTE CA2E 1 harmonic U31 row 59 unsigned word 0,1 % NOTE CA2F 1 harmonic U12 row 61 unsigned word 0,1 % NOTE CA30 1 harmonic U23 row 61 unsigned word 0,1 % NOTE CA31 1 harmonic U31 row 61 unsigned word 0,1 % NOTE CA32 1 harmonic U12 row 63 unsigned word 0,1 % NOTE CA33 1 harmonic U23 row 63 unsigned word 0,1 % NOTE CA34 1 harmonic U31 row 63 unsigned word 0,1 % NOTE CA35 94 Measure - Harmonic V PH/N : harmonic order CA35 1 of harmonic rows 1 number of V Ph/N harmonic order: max 94, value if not available: CA36 1 harmonic V1 row 3 unsigned word 0,1 % NOTE CA37 1 harmonic V2 row 3 unsigned word 0,1 % NOTE CA38 1 harmonic V3 row 3 unsigned word 0,1 % NOTE CA39 1 harmonic V1 row 5 unsigned word 0,1 % NOTE CA3A 1 harmonic V2 row 5 unsigned word 0,1 % NOTE CA3B 1 harmonic V3 row 5 unsigned word 0,1 % NOTE CA3C 1 harmonic V1 row 7 unsigned word 0,1 % NOTE CA3D 1 harmonic V2 row 7 unsigned word 0,1 % NOTE CA3E 1 harmonic V3 row 7 unsigned word 0,1 % NOTE CA3F 1 harmonic V1 row 9 unsigned word 0,1 % NOTE CA40 1 harmonic V2 row 9 unsigned word 0,1 % NOTE CA41 1 harmonic V3 row 9 unsigned word 0,1 % NOTE CA42 1 harmonic V1 row 11 unsigned word 0,1 % NOTE CA43 1 harmonic V2 row 11 unsigned word 0,1 % NOTE CA44 1 harmonic V3 row 11 unsigned word 0,1 % NOTE CA45 1 harmonic V1 row 13 unsigned word 0,1 % NOTE CA46 1 harmonic V2 row 13 unsigned word 0,1 % NOTE CA47 1 harmonic V3 row 13 unsigned word 0,1 % NOTE CA48 1 harmonic V1 row 15 unsigned word 0,1 % NOTE CA49 1 harmonic V2 row 15 unsigned word 0,1 % NOTE CA4A 1 harmonic V3 row 15 unsigned word 0,1 % NOTE CA4B 1 harmonic V1 row 17 unsigned word 0,1 % NOTE CA4C 1 harmonic V2 row 17 unsigned word 0,1 % NOTE CA4D 1 harmonic V3 row 17 unsigned word 0,1 % NOTE CA4E 1 harmonic V1 row 19 unsigned word 0,1 % NOTE CA4F 1 harmonic V2 row 19 unsigned word 0,1 % NOTE CA50 1 harmonic V3 row 19 unsigned word 0,1 % NOTE CA51 1 harmonic V1 row 21 unsigned word 0,1 % NOTE CA52 1 harmonic V2 row 21 unsigned word 0,1 % NOTE CA53 1 harmonic V3 row 21 unsigned word 0,1 % NOTE CA54 1 harmonic V1 row 23 unsigned word 0,1 % NOTE CA55 1 harmonic V2 row 23 unsigned word 0,1 % NOTE CA56 1 harmonic V3 row 23 unsigned word 0,1 % NOTE CA57 1 harmonic V1 row 25 unsigned word 0,1 % NOTE CA58 1 harmonic V2 row 25 unsigned word 0,1 % NOTE CA59 1 harmonic V3 row 25 unsigned word 0,1 % NOTE CA5A 1 harmonic V1 row 27 unsigned word 0,1 % NOTE1 3 File and printed copies of this document are not subject to document change control. Page 20/40

21 INPUT REGISTERS Words (R) Code CA5B 1 harmonic V2 row 27 unsigned word 0,1 % NOTE CA5C 1 harmonic V3 row 27 unsigned word 0,1 % NOTE CA5D 1 harmonic V1 row 29 unsigned word 0,1 % NOTE CA5E 1 harmonic V2 row 29 unsigned word 0,1 % NOTE CA5F 1 harmonic V3 row 29 unsigned word 0,1 % NOTE CA60 1 harmonic V1 row 31 unsigned word 0,1 % NOTE CA61 1 harmonic V2 row 31 unsigned word 0,1 % NOTE CA62 1 harmonic V3 row 31 unsigned word 0,1 % NOTE CA63 1 harmonic V1 row 33 unsigned word 0,1 % NOTE CA64 1 harmonic V2 row 33 unsigned word 0,1 % NOTE CA65 1 harmonic V3 row 33 unsigned word 0,1 % NOTE CA66 1 harmonic V1 row 35 unsigned word 0,1 % NOTE CA67 1 harmonic V2 row 35 unsigned word 0,1 % NOTE CA68 1 harmonic V3 row 35 unsigned word 0,1 % NOTE CA69 1 harmonic V1 row 37 unsigned word 0,1 % NOTE CA6A 1 harmonic V2 row 37 unsigned word 0,1 % NOTE CA6B 1 harmonic V3 row 37 unsigned word 0,1 % NOTE CA6C 1 harmonic V1 row 39 unsigned word 0,1 % NOTE CA6D 1 harmonic V2 row 39 unsigned word 0,1 % NOTE CA6E 1 harmonic V3 row 39 unsigned word 0,1 % NOTE CA6F 1 harmonic V1 row 41 unsigned word 0,1 % NOTE CA70 1 harmonic V2 row 41 unsigned word 0,1 % NOTE CA71 1 harmonic V3 row 41 unsigned word 0,1 % NOTE CA72 1 harmonic V1 row 43 unsigned word 0,1 % NOTE CA73 1 harmonic V2 row 43 unsigned word 0,1 % NOTE CA74 1 harmonic V3 row 43 unsigned word 0,1 % NOTE CA75 1 harmonic V1 row 45 unsigned word 0,1 % NOTE CA76 1 harmonic V2 row 45 unsigned word 0,1 % NOTE CA77 1 harmonic V3 row 45 unsigned word 0,1 % NOTE CA78 1 harmonic V1 row 47 unsigned word 0,1 % NOTE CA79 1 harmonic V2 row 47 unsigned word 0,1 % NOTE CA7A 1 harmonic V3 row 47 unsigned word 0,1 % NOTE CA7B 1 harmonic V1 row 49 unsigned word 0,1 % NOTE CA7C 1 harmonic V2 row 49 unsigned word 0,1 % NOTE CA7D 1 harmonic V3 row 49 unsigned word 0,1 % NOTE CA7E 1 harmonic V1 row 51 unsigned word 0,1 % NOTE CA7F 1 harmonic V2 row 51 unsigned word 0,1 % NOTE CA80 1 harmonic V3 row 51 unsigned word 0,1 % NOTE CA81 1 harmonic V1 row 53 unsigned word 0,1 % NOTE CA82 1 harmonic V2 row 53 unsigned word 0,1 % NOTE CA83 1 harmonic V3 row 53 unsigned word 0,1 % NOTE CA84 1 harmonic V1 row 55 unsigned word 0,1 % NOTE CA85 1 harmonic V2 row 55 unsigned word 0,1 % NOTE CA86 1 harmonic V3 row 55 unsigned word 0,1 % NOTE CA87 1 harmonic V1 row 57 unsigned word 0,1 % NOTE CA88 1 harmonic V2 row 57 unsigned word 0,1 % NOTE CA89 1 harmonic V3 row 57 unsigned word 0,1 % NOTE CA8A 1 harmonic V1 row 59 unsigned word 0,1 % NOTE CA8B 1 harmonic V2 row 59 unsigned word 0,1 % NOTE CA8C 1 harmonic V3 row 59 unsigned word 0,1 % NOTE CA8D 1 harmonic V1 row 61 unsigned word 0,1 % NOTE CA8E 1 harmonic V2 row 61 unsigned word 0,1 % NOTE CA8F 1 harmonic V3 row 61 unsigned word 0,1 % NOTE CA90 1 harmonic V1 row 63 unsigned word 0,1 % NOTE CA91 1 harmonic V2 row 63 unsigned word 0,1 % NOTE CA92 1 harmonic V3 row 63 unsigned word 0,1 % NOTE1 3 File and printed copies of this document are not subject to document change control. Page 21/40

DIRIS A40/A41 RS485 JBUS/MODBUS. Operating instructions F GB D I NL E P

DIRIS A40/A41 RS485 JBUS/MODBUS. Operating instructions F GB D I NL E P DIRIS A40/A41 RS485 JBUS/MODBUS Operating instructions F GB D I NL E P COM DIRIS A40/A41 - Ref.: 536 103 A GB GB Contents PRELIMINARY OPERATIONS 4 GENERAL INFORMATION 4 INSTALLATION 5 CONNECTION 5 PROGRAMMING

More information

DIRIS A40/A41 ETHERNET. Operating instructions F GB D I NL E P

DIRIS A40/A41 ETHERNET. Operating instructions F GB D I NL E P DIRIS A40/A41 ETHERNET Operating instructions F GB D I NL E P 2 DIRIS A40/A41 - Ref.: 536 181 B GB GB Contents PRELIMINARY OPERATIONS 4 GENERAL INFORMATION 4 INSTALLATION 5 CONNECTION 5 VISUAL DIAGNOSTIC

More information

Visa Smart Debit/Credit Certificate Authority Public Keys

Visa Smart Debit/Credit Certificate Authority Public Keys CHIP AND NEW TECHNOLOGIES Visa Smart Debit/Credit Certificate Authority Public Keys Overview The EMV standard calls for the use of Public Key technology for offline authentication, for aspects of online

More information

Nemo 96HD/HD+ MODBUS

Nemo 96HD/HD+ MODBUS 18/12/12 Pagina 1 di 28 MULTIFUNCTION FIRMWARE 2.30 Nemo 96HD/HD+ MODBUS COMMUNICATION PROTOCOL CONTENTS 1.0 ABSTRACT 2.0 DATA MESSAGE DESCRIPTION 2.1 Parameters description 2.2 Data format 2.3 Description

More information

ANR-PRF. INSTRUCTION MANUAL IM157-U-A v0.5 COMMUNICATION PROTOCOL ANR MULTIFUNCTION ANALYZER PROFIBUS DP-V0

ANR-PRF. INSTRUCTION MANUAL IM157-U-A v0.5 COMMUNICATION PROTOCOL ANR MULTIFUNCTION ANALYZER PROFIBUS DP-V0 INSTRUCTION MANUAL IM157-U-A v0.5 ANR-PRF COMMUNICATION PROTOCOL ANR MULTIFUNCTION ANALYZER PROFIBUS DP-V0 PROFIBUS AND ANR-PRF Profibus-DP is a multi-master systems. In the networks it s possible to have

More information

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1 Softstarters Type PSTX Fieldbus communication, Built-in Modbus RTU 1SFC132089M0201 April 2015 1SFC132089M0201 1 1 Modbus RTU The Modbus protocol is a fieldbus protocol that provides full control and status

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters

User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters SDM220MODBUS Single-Phase Two Module DIN rail Meters Measures kwh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc. Di-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting 36mm

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Applications. diris_826_a_1_gb_cat

Applications. diris_826_a_1_gb_cat Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered

More information

8 data bits, least significant bit sent first 1 bit for even/odd parity (or no parity) 1 stop bit if parity is used; 1 or 2 bits if no parity

8 data bits, least significant bit sent first 1 bit for even/odd parity (or no parity) 1 stop bit if parity is used; 1 or 2 bits if no parity 1.Eastron SDM630 Smart Meter Modbus Protocol Implementation 1.1 Modbus Protocol Overview This section provides basic information for interfacing the Eastron Smart meter to a Modbus Protocol network. If

More information

Metering Devices IQ Analyzer 6400/6600 Series

Metering Devices IQ Analyzer 6400/6600 Series Metering Devices IQ Analyzer 6400/6600 Series Technical Data Supersedes TD.17.02A.T.E pages 1-8 dated May 2000 Description Page General Description............................................. 2 Applications....................................................

More information

Digital and Analog I/O

Digital and Analog I/O 70072-0127-07 TECHNICAL NOTE 02/2007 Digital and Analog I/O This document discusses the application and configuration of digital and analog inputs/outputs (I/O). Details are for both onboard I/O and external

More information

Managing. Energy management and power analysis

Managing. Energy management and power analysis management and power analysis Power monitors IN 96 and 144 - Selection table... 68 - IN 96, recdigit NOUS... 70 - IN 144, recdigit POWER... 72 - Multi-display recisplay... 73 Winthor software... 74 Managing

More information

Electronic Multi-Measuring Instrument

Electronic Multi-Measuring Instrument MITSUBISHI Electronic Multi-Measuring Instrument Programming Manual (CC-Link) Model ME96NSR-MB or ME96NSR with optional Plug-in Module : ME-0040C-NS96 CONTENTS 1. General Description... 2 2. Specification...

More information

Energy Management Energy Meter Type EM23 DIN

Energy Management Energy Meter Type EM23 DIN Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy

More information

Power Electronics Testings

Power Electronics Testings Power Electronics Testings PV Inverter Test Solution www.chromaate.com Turnkey Test & Automation Solution Provider w w w.chromaate.com A PV system is an energy system which directly converts energy from

More information

D7024 Fire Alarm Control Panels Software Version V2.06

D7024 Fire Alarm Control Panels Software Version V2.06 D7024 Fire Alarm Control Panels Software Version V2.06 Program Record Sheet Account Information: Account: Date: Name: Address: Panel Phone #: Contact Phone #: Contact Person: Comments: Panel Location:

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

SERVER CERTIFICATES OF THE VETUMA SERVICE

SERVER CERTIFICATES OF THE VETUMA SERVICE Page 1 Version: 3.4, 19.12.2014 SERVER CERTIFICATES OF THE VETUMA SERVICE 1 (18) Page 2 Version: 3.4, 19.12.2014 Table of Contents 1. Introduction... 3 2. Test Environment... 3 2.1 Vetuma test environment...

More information

Parallax Serial LCD 2 rows x 16 characters Non-backlit (#27976) 2 rows x 16 characters Backlit (#27977) 4 rows x 20 characters Backlit (#27979)

Parallax Serial LCD 2 rows x 16 characters Non-backlit (#27976) 2 rows x 16 characters Backlit (#27977) 4 rows x 20 characters Backlit (#27979) 599 Menlo Drive, Suite 100 Rocklin, California 95765, USA Office: (916) 624-8333 Fax: (916) 624-8003 General: info@parallax.com Technical: support@parallax.com Web Site: www.parallax.com Educational: www.stampsinclass.com

More information

POWERLOGIC Circuit Monitor Series 2000

POWERLOGIC Circuit Monitor Series 2000 Class POWERLOGIC Circuit Monitor Series 2000 Features True rms metering Certified ANSI C2.6 revenue accuracy High accuracy 0.2% current and voltage Power quality readings THD, k-factor, crest factor Over

More information

PowerLogic ION7550 / ION7650

PowerLogic ION7550 / ION7650 70002-0248-06 02/2009 PowerLogic ION7550 / ION7650 Energy and power quality meter User Guide 7 Third-party Protocols This chapter explains how third party protocols Modbus, DNP 3.0 and SNMP are implemented

More information

SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI User Guide

SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI User Guide SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI Simplay-UG-02003-A July 2015 Contents 1. Overview... 4 1.1. SL-8800 HDCP Protocol Analyzer Test Equipment... 4 1.2. HDCP 2.2/HDCP 1.x Protocol Analyzer

More information

URL encoding uses hex code prefixed by %. Quoted Printable encoding uses hex code prefixed by =.

URL encoding uses hex code prefixed by %. Quoted Printable encoding uses hex code prefixed by =. ASCII = American National Standard Code for Information Interchange ANSI X3.4 1986 (R1997) (PDF), ANSI INCITS 4 1986 (R1997) (Printed Edition) Coded Character Set 7 Bit American National Standard Code

More information

SensyCal FCU200, FCU400 Universal measuring computer MODBUS protocol

SensyCal FCU200, FCU400 Universal measuring computer MODBUS protocol Protocol description COM/FCU/MODBUS-EN SensyCal FCU200, FCU400 Universal measuring computer MODBUS protocol Measurement made easy Contents Blinder Text Universal measuring computer SensyCal FCU200, FCU400

More information

A project to optimise quality and energy efficiency must include metering

A project to optimise quality and energy efficiency must include metering EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,

More information

ROC Protocol Specifications Manual

ROC Protocol Specifications Manual Part Number D301053X012 June 2015 ROC Protocol Specifications Manual Remote Automation Solutions ROC Protocol Specifications Manual Revision Tracking Sheet June 2015 This manual may be revised periodically

More information

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800 Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement

More information

Multilin EPM 6000. GE Grid Solutions. High Accuracy Power & Energy Measurement. Monitoring & Metering. Advanced Communications.

Multilin EPM 6000. GE Grid Solutions. High Accuracy Power & Energy Measurement. Monitoring & Metering. Advanced Communications. GE Grid Solutions Multilin EPM 6000 High Accuracy Power & Energy Measurement The Multilin EPM 6000 is one of the industry s highest performance revenue grade panel meters with superior cost to performance

More information

SOFTWARE EasyComm (Code 775 044) USER S MANUAL (Code M 981 357/00 - A) 1997-2000 CIRCUTOR, S.A. All rights reserved

SOFTWARE EasyComm (Code 775 044) USER S MANUAL (Code M 981 357/00 - A) 1997-2000 CIRCUTOR, S.A. All rights reserved SOFTWARE EasyComm (Code 775 044) USER S MANUAL (Code M 981 357/00 - A) 1997-2000 CIRCUTOR, S.A. All rights reserved EasyComm INDEX 1. Introduction... Page 2 2. EasyComm contents... Page 2 3. Main features...

More information

DOCA0006EN-02 06/2013. PM3200 Series. Power Meters User Manual 06/2013 DOCA0006EN-02. www.schneider-electric.com

DOCA0006EN-02 06/2013. PM3200 Series. Power Meters User Manual 06/2013 DOCA0006EN-02. www.schneider-electric.com PM3200 Series PM3200 Series Power Meters User Manual 06/2013 DOCA0006EN-02 www.schneider-electric.com The information provided in this documentation contains general descriptions and/or technical characteristics

More information

SERVER CERTIFICATES OF THE VETUMA SERVICE

SERVER CERTIFICATES OF THE VETUMA SERVICE Page 1 Version: 3.5, 4.11.2015 SERVER CERTIFICATES OF THE VETUMA SERVICE 1 (18) Page 2 Version: 3.5, 4.11.2015 Table of Contents 1. Introduction... 3 2. Test Environment... 3 2.1 Vetuma test environment...

More information

User s Manual. Multifunction Transducer MT440

User s Manual. Multifunction Transducer MT440 User s Manual GB Multifunction Transducer MT440 Table of contents Table of Contents 1. SECURITY ADVICE AND WARNINGS 1 1.1 Welcome ---------------------------------------------------------------------------------------------

More information

Eaton s E-Series protective relay family

Eaton s E-Series protective relay family E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family

More information

The Answer to the 14 Most Frequently Asked Modbus Questions

The Answer to the 14 Most Frequently Asked Modbus Questions Modbus Frequently Asked Questions WP-34-REV0-0609-1/7 The Answer to the 14 Most Frequently Asked Modbus Questions Exactly what is Modbus? Modbus is an open serial communications protocol widely used in

More information

NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter

NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter Description: The NTE2053 is a CMOS 8 bit successive approximation Analog to Digital converter in a 20 Lead DIP type package which uses a differential

More information

Electronic Multi-Measuring Instrument

Electronic Multi-Measuring Instrument MITSUBISHI Electronic Multi-Measuring Instrument Programming Manual (CC-Link) For ver.1 remote device station Model ME96NSR-MB or ME96NSR with Optional Plug-in Module : ME-0040C-NS96 ME96SSH-MB or ME96SSR-MB

More information

M2M The measure of efficiency

M2M The measure of efficiency M2M The measure of efficiency The importance of control Measurement and advanced analysis of electrical parameters To make equipment as efficient as possible, it is essential to know the details of its

More information

The ASCII Character Set

The ASCII Character Set The ASCII Character Set The American Standard Code for Information Interchange or ASCII assigns values between 0 and 255 for upper and lower case letters, numeric digits, punctuation marks and other symbols.

More information

DME4 V1.23 (06-1999) V1.30 (06-2000) V1.31 (04-2001) V1.32 (09-2001) V1.33 (03-2002) V1.34 (06-2003) V1.35 (05-2004) V2.00 (12-2005) V2.

DME4 V1.23 (06-1999) V1.30 (06-2000) V1.31 (04-2001) V1.32 (09-2001) V1.33 (03-2002) V1.34 (06-2003) V1.35 (05-2004) V2.00 (12-2005) V2. DME4 V1.23 (06-1999) - Correction of unfounded error message 'No measurements configured' when reading measurements from DME440 (MODBUS) if special measurands hadn't been selected to be calculated. - Correction

More information

Power monitoring unit type VAMP 260

Power monitoring unit type VAMP 260 Power monitoring unit type VAMP 260 formerly known as VMAC 260 Slide 1 / 18 The complete source of information Slide 2 / 18 The complete source of information Users - utilities -industry - power plants

More information

Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107 Controllers)

Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107 Controllers) Part D301753X012 May 2016 Micro Motion Coriolis Interface Module User Manual (for ROC800-Series and FloBoss 107 Controllers) Remote Automation Solutions Revision Tracking Sheet May 2016 This manual may

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

COMMUNICATION PROTOCOL pag. 1/7. BACnet Protocol Implementation Conformance Statement

COMMUNICATION PROTOCOL pag. 1/7. BACnet Protocol Implementation Conformance Statement COMMUNICATION PROTOCOL pag. 1/7 NEMO 96HD NEMO 96HD+ 08 / 07 / 2009 BACnet Protocol Implementation Conformance Statement Date: February, 17 th 2009 Vendor Name: IME Product Name: NEMO Product Model Number:

More information

PLA 44. Power quality analyzer. User and service manual. BMR trading

PLA 44. Power quality analyzer. User and service manual. BMR trading PLA 44 Power quality analyzer User and service manual version 1.2 BMR Lipovka 17 516 01 Rychnov n. Kn. 1 Tel: +420 774 415 703 Fax: +420 494 533 602 Content 1. Front panel...3 5.6.1. List of events...8

More information

Device Support in PowerLogic ION Enterprise 5.6 Service Pack 2

Device Support in PowerLogic ION Enterprise 5.6 Service Pack 2 70072-0189-00 TECHNICAL 08/2008 Device Support in PowerLogic ION Enterprise 5.6 Service Pack 2 This document outlines support in ION Enterprise 5.6 Service Pack 2 for PowerLogic CM3000 series/cm4000 series,

More information

Energy Management Power Analyzer Type WM14-96 Basic Version

Energy Management Power Analyzer Type WM14-96 Basic Version Energy Management Power Analyzer Type WM-96 Basic Version Optional dual pulse output Alarms (visual only) V, An Optional galvanically insulated measuring inputs Product Description 3-phase power analyzer

More information

INSTRUCTION MANUAL IPM 3600 3 Phase Power Analyser EN FR IT DE ES

INSTRUCTION MANUAL IPM 3600 3 Phase Power Analyser EN FR IT DE ES INSTRUCTION MANUAL IPM 3600 3 Phase Power Analyser EN FR IT DE ES CONTENTS / EN CONTENTS Title Page I. SAFETY INFORMATION...1 II. INTRODUCTION...3 III. SPECIFICATIONS...4 3-1 Environmental Conditions...4

More information

Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications

Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications By Michael Bearden Introduction In 1982 Raymond Ray Stevens published a paper Power Flow Direction Definitions for

More information

Modbus and ION Technology

Modbus and ION Technology 70072-0104-14 TECHNICAL 06/2009 Modbus and ION Technology Modicon Modbus is a communications protocol widely used in process control industries such as manufacturing. PowerLogic ION meters are compatible

More information

RS-485 Protocol Manual

RS-485 Protocol Manual RS-485 Protocol Manual Revision: 1.0 January 11, 2000 RS-485 Protocol Guidelines and Description Page i Table of Contents 1.0 COMMUNICATIONS BUS OVERVIEW... 1 2.0 DESIGN GUIDELINES... 1 2.1 Hardware Design

More information

NEXGEN Cloud Cloud Software Services and Hosting for NEXGEN Smart Meters

NEXGEN Cloud Cloud Software Services and Hosting for NEXGEN Smart Meters NEXGEN Cloud Cloud Software Services and Hosting for NEXGEN Smart Meters NEXGEN Cloud Software Automated data collection, storage, processing and delivery Core AMR/AMI applications Two way communications

More information

1. INTRODUCTION FEATURES 2. PROGRAMMING

1. INTRODUCTION FEATURES 2. PROGRAMMING 1. INTRODUCTION Mono phase compensation systems are not useful in plants where unbalanced loads exist. In such plants compensation has to be done by measuring all 3 phase parameters individually. Devices,

More information

Model 8220. POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter

Model 8220. POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter Special product features '''' ENERGY METER ''' MEASURES RPM POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter Model A measurement tool for electrical parameters and distribution network disturbances

More information

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor

More information

Softstarters. Type PST/PSTB Fieldbus communication CANopen for PST sw CU 06.00.00. 1SFC132070M0201 February 2011 1SFC132070M0201 1

Softstarters. Type PST/PSTB Fieldbus communication CANopen for PST sw CU 06.00.00. 1SFC132070M0201 February 2011 1SFC132070M0201 1 Softstarters Type PST/PSTB Fieldbus communication CANopen for PST sw CU 06.00.00 1SFC132070M0201 February 2011 1SFC132070M0201 1 CANopen The CANopen protocol is a fieldbus protocol that provides full control

More information

EM-PQ 1500 Power Quality Monitor. Operating Manual

EM-PQ 1500 Power Quality Monitor. Operating Manual EM-PQ 1500 Power Quality Monitor Operating Manual 1 User notes: 2 Contents Page Page 1. Quick start... 5 2. Description... 6 2.1 Operating principle... 6 3. Installation... 8 3.1 Mounting... 8 3.2 Electrical

More information

Appendix C: Keyboard Scan Codes

Appendix C: Keyboard Scan Codes Thi d t t d ith F M k 4 0 2 Appendix C: Keyboard Scan Codes Table 90: PC Keyboard Scan Codes (in hex) Key Down Up Key Down Up Key Down Up Key Down Up Esc 1 81 [ { 1A 9A, < 33 B3 center 4C CC 1! 2 82 ]

More information

Unidirectional Transmitter/ Receiver Units Introduction

Unidirectional Transmitter/ Receiver Units Introduction Unidirectional Transmitter/ Receiver Units Introduction Wireless Input/Output (I/O) connects directly to analog, discrete and pulse transducer signals. The signals are transmitted by radio and either re-created

More information

Interface Protocol v1.2

Interface Protocol v1.2 Interface Protocol v1.2 Uart Configure on PC Baud Rate Bits Stop bits Parity 9600 bps 8 Bits 1 Bit No Parity Basic Uart Transfer Format Start 0/1 : These bytes are both 0x55. Control : This byte is controling

More information

1.Eastron SDM220Modbus Smart Meter Modbus Protocol Implementation V1.0

1.Eastron SDM220Modbus Smart Meter Modbus Protocol Implementation V1.0 1.Eastron SDM220Modbus Smart Meter Modbus Protocol Implementation V1.0 1.1 Modbus Protocol Overview This section provides basic information for interfacing the Eastron Smart meter to a Modbus Protocol

More information

Power Meter Series 800

Power Meter Series 800 PowerLogic power-monitoring units Power Meter Series 800 Technical data sheet 2007 Functions and characteristics E90463 PB101813-51 PB101823-50 DB111799 Front view of Power Meter Series 800 meter with

More information

USB HID to PS/2 Scan Code Translation Table

USB HID to PS/2 Scan Code Translation Table Key Name HID Usage Page HID Usage ID PS/2 Set 1 Make* PS/2 Set 1 Break* PS/2 Set 2 Make PS/2 Set 2 Break System Power 01 81 E0 5E E0 DE E0 37 E0 F0 37 System Sleep 01 82 E0 5F E0 DF E0 3F E0 F0 3F System

More information

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 16400(LED TYPES) EXAMINED BY : FILE NO. CAS-10068 ISSUE : JAN.19,2000 TOTAL PAGE : 7 APPROVED BY:

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 16400(LED TYPES) EXAMINED BY : FILE NO. CAS-10068 ISSUE : JAN.19,2000 TOTAL PAGE : 7 APPROVED BY: EXAMINED BY : FILE NO. CAS-10068 APPROVED BY: EMERGING DISPLAY TECHNOLOGIES CORPORATION ISSUE : JAN.19,2000 TOTAL PAGE : 7 VERSION : 3 CUSTOMER ACCEPTANCE SPECIFICATIONS MODEL NO. : 16400(LED TYPES) FOR

More information

Xi2000 Series Configuration Guide

Xi2000 Series Configuration Guide U.S. Default Settings Sequence Reset Scanner Xi2000 Series Configuration Guide Auto-Sense Mode ON UPC-A Convert to EAN-13 OFF UPC-E Lead Zero ON Save Changes POS-X, Inc. 2130 Grant St. Bellingham, WA 98225

More information

Modbus Register Map: Environmental Management System and Environmental Monitoring Unit 990-0589A 02/2005

Modbus Register Map: Environmental Management System and Environmental Monitoring Unit 990-0589A 02/2005 // Version 102 //Absolute Starting Register Number, (Hexadecimal) Modbus Register Map: Environmental Management System and Environmental Monitoring Unit 990-0589A 02/2005 Absolute Starting Register Number,

More information

PRODUCT LIST Facility DDC Access WebXL DDC

PRODUCT LIST Facility DDC Access WebXL DDC PRODUCT LIST Facility DDC Access WebXL DDC Effective from 01/10/2014 Sphere Systems Pty Ltd Unit 6 / 9 Mirra Crt Bundoora Victoria Australia 3083 ABN 98 006 579 004 Phone +61 3 9470 8844 Fax +61 3 9470

More information

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide 1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

PowerLogic power-monitoring units. PM5350 power meter. Technical data sheet

PowerLogic power-monitoring units. PM5350 power meter. Technical data sheet PowerLogic power-monitoring units PM5350 power meter Technical data sheet Mid-range metering PM5350 Functions and characteristics PE86278 The PowerLogic PM5350 power meter offers all the measurement capailities

More information

CE8301 Series. Introduction. Features. Ordering Information. Applications SMALL PACKAGE PFM CONTROL STEP-UP DC/DC CONVERTER

CE8301 Series. Introduction. Features. Ordering Information. Applications SMALL PACKAGE PFM CONTROL STEP-UP DC/DC CONVERTER SMALL PACKAGE PFM CONTROL STEP-UP DC/DC CONVERTER Introduction The is a CMOS PFM-control step-up switching DC/DC converter that mainly consists of a reference voltage source, an oscillator, and a comparator.

More information

Digital Clamp-on DMMs with uncompromising performance

Digital Clamp-on DMMs with uncompromising performance Digital Clamp-on DMMs with uncompromising performance With this new range of clamp-on meters, Metrix introduces practical and inexpensive instruments with uncompromising performance. Designed to satisfy

More information

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001 Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.

More information

How to create OpenDocument URL s with SAP BusinessObjects BI 4.0

How to create OpenDocument URL s with SAP BusinessObjects BI 4.0 How to create OpenDocument URL s with SAP BusinessObjects BI 4.0 Creator: Twitter: Blog: Pieter Verstraeten http://www.twitter.com/pverstraeten http://www.pieterverstraeten.com/blog Hi, Thanks for downloading

More information

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB i-bus KNX Fan Coil Controller FC/S 1.1 Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation

More information

Modbus and ION Technology

Modbus and ION Technology Modbus and ION Technology Modicon Modbus is a communications protocol widely used in process control industries such as manufacturing. ACCESS meters are compatible with Modbus networks as both slaves and

More information

Panel Meters and Controllers Modular Panel Meter Type EDM 35

Panel Meters and Controllers Modular Panel Meter Type EDM 35 Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming

More information

Luxembourg (Luxembourg): Trusted List

Luxembourg (Luxembourg): Trusted List Luxembourg (Luxembourg): Trusted List Institut Luxembourgeois de la Normalisation, de l'accréditation de la Sécurité et qualité des produits et services Scheme Information TSL Version 4 TSL Sequence Number

More information

NEW APC Smart-UPS. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS.

NEW APC Smart-UPS. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS. NEW APC Smart-UPS Advanced line interactive power protection for servers and network equipment. > The world s most popular network and server UPS. Award-winning Smart-UPS protects critical data by supplying

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

TNM96-ETL. Electrical Measurements & Power Quality. TNM96-ED (without Energy)

TNM96-ETL. Electrical Measurements & Power Quality. TNM96-ED (without Energy) TNM96-ETL Electrical Measurements & Power Quality TNM96-ED (without Energy) Celsa Messgeräte GmbH Barthelsmühlring 16, 76870 Kande - Germany Telefon: +49 7275 9883-0; Telefax: +49 7275 9883-33 Web: www.celsagermany.com;

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h

More information

Technical note NT588 NT604 NT695 NT782

Technical note NT588 NT604 NT695 NT782 Multifunction 1.01 Model Nemo D4-b Nemo D4-L Nemo D4-L+ Codes MF6GT MF6FT0 MF6FTU MF6FT4 MF6HTU... MF6HT4... MF6HB... Ordering codes see page: 08 08 08 08 08 08 08 Connection on line single phase, 3-phase

More information

DS1307ZN. 64 x 8 Serial Real-Time Clock

DS1307ZN. 64 x 8 Serial Real-Time Clock DS137 64 x 8 Serial Real-Time Clock www.maxim-ic.com FEATURES Real-time clock (RTC) counts seconds, minutes, hours, date of the month, month, day of the week, and year with leap-year compensation valid

More information

One Meter Works for Both Energy Saving and Power Quality Surveillance

One Meter Works for Both Energy Saving and Power Quality Surveillance Multi-Function Meter Eco-POWER METER W9M SERIES Conforming to ow Voltage and EMC Directives One Meter Works for Both Energy Saving and Quality Surveillance High accuracy: 0.2 %* Harmonic measurement* Simple

More information

TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS

TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS Capacity Technology Inverter Technology Noise Level Operating Temperature Humidity Harmonic Distortion Total DC bus voltage Battery recharge time (After Complete discharge) to 100% charge Crest Factor

More information

Advanced Encryption Standard by Example. 1.0 Preface. 2.0 Terminology. Written By: Adam Berent V.1.7

Advanced Encryption Standard by Example. 1.0 Preface. 2.0 Terminology. Written By: Adam Berent V.1.7 Written By: Adam Berent Advanced Encryption Standard by Example V.1.7 1.0 Preface The following document provides a detailed and easy to understand explanation of the implementation of the AES (RIJNDAEL)

More information

Modbus Communications for PanelView Terminals

Modbus Communications for PanelView Terminals User Guide Modbus Communications for PanelView Terminals Introduction This document describes how to connect and configure communications for the Modbus versions of the PanelView terminals. This document

More information

RS485 & Modbus Protocol Guide

RS485 & Modbus Protocol Guide RS485 & Modbus Protocol Guide Products Covered Quadratic Integra 1000 Switchboard Integra 1000 Integra 1540 Integra 1560 Integra 1580 Quadratic Integra 2000 System Protection Relay (SPR) Tyco Electronics

More information

Advanced Encryption Standard by Example. 1.0 Preface. 2.0 Terminology. Written By: Adam Berent V.1.5

Advanced Encryption Standard by Example. 1.0 Preface. 2.0 Terminology. Written By: Adam Berent V.1.5 Written By: Adam Berent Advanced Encryption Standard by Example V.1.5 1.0 Preface The following document provides a detailed and easy to understand explanation of the implementation of the AES (RIJNDAEL)

More information

FP-4000 Feeder Protection

FP-4000 Feeder Protection FP-4000 Feeder Protection Technical Data TD02602007E Effective September 2007 Supersedes TD02602003E Pages 1 8, Dated March 2006 FP-4000 FP-4000 Product Description........................... 2 Application

More information

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 20400 (LED TYPES) EXAMINED BY : FILE NO. CAS-10184 ISSUE : DEC.01,1999 TOTAL PAGE : 7 APPROVED BY:

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 20400 (LED TYPES) EXAMINED BY : FILE NO. CAS-10184 ISSUE : DEC.01,1999 TOTAL PAGE : 7 APPROVED BY: EXAMINED BY : FILE NO. CAS-10184 APPROVED BY: EMERGING DISPLAY TECHNOLOGIES CORPORATION ISSUE : DEC.01,1999 TOTAL PAGE : 7 VERSION : 2 CUSTOMER ACCEPTANCE SPECIFICATIONS MODEL NO. : 20400 (LED TYPES) FOR

More information

PNSPO! Modbus Solution CP1H / CP1L / CJ1 / CJ2 / CS1. Version 2.05 6/18/2009

PNSPO! Modbus Solution CP1H / CP1L / CJ1 / CJ2 / CS1. Version 2.05 6/18/2009 PNSPO!! Modbus Solution CP1H / CP1L / CJ1 / CJ2 / CS1 Version 2.05 6/18/2009 Section 1. Overview The Omron CP1H and CP1L PLCs offer a built in function called Easy Modbus, that performs a Modbus RTU Master

More information

Master-Touch and ValuMass. Modbus Communications. INSTRUCTION MANUAL 80202201 (Rev. 2.1)

Master-Touch and ValuMass. Modbus Communications. INSTRUCTION MANUAL 80202201 (Rev. 2.1) Master-Touch and ValuMass Modbus Communications INSTRUCTION MANUAL 80202201 (Rev. 2.1) Eldridge Products, Inc. 2700 Garden Road, Building A Monterey, CA 93940 Tel: 800/321-3569 or 831/648-7777 Fax: 831/648-7780

More information

How Do You Reduce Energy Costs And Prolong The Life Of Your Equipment?

How Do You Reduce Energy Costs And Prolong The Life Of Your Equipment? How Do You Reduce Energy Costs And Prolong The Life Of Your Equipment? PowerLogic PM800 series power meters Buildings Industry Data Center Compact power, energy and power quality meters The Square D PowerLogic

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

ABB i-bus EIB Logic Module LM/S 1.1

ABB i-bus EIB Logic Module LM/S 1.1 Product Manual ABB i-bus EIB Logic Module LM/S 1.1 Intelligent Installation System Contents page 1 General... 3 1.1 About this manual... 3 1.2 Product and functional overview... 3 2 Device technology...

More information

How To Use A Kv2C Meter

How To Use A Kv2C Meter . GEH-7285 GE kv2c TM Encompass Electronic Meter Product Description, Operating Instructions, Maintenance Instructions, Upgrading, Site Analysis Guides, Diagrams. Price: $ 30.00 Notice The information

More information