1 Electrical Systems Commissioning Catherine Melander, Questions & Solutions Engineering 21 st National Conference on Building Commissioning
2 AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of this program will be reported to AIA/CES for AIA members. Certificates of Completion for both AIA members and non-aia members are available upon request. This program is registered with AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation. 21 st NCBC Conference
3 Presentation Description This presentation will explore the what, when why and how of common issues found during commissioning of electrical power systems, many of which are not detectible until a failure or fault occurs. In addition, the presentation will look at the electrical/mechanical system interfaces that are critical in the emergency power system testing and provide examples of the types of mechanical problems discovered during emergency power system testing.. 21 st NCBC Conference
4 Learning Objectives At the end of this session, participants will be able to: 1. Identify common failures found during electrical system functional testing. 2. Identify where in the commissioning process common failures could be avoided during future commissioning. 3. Understand common mechanical systems interface issues found during electrical testing. 4. Apply electrical system commissioning lessons learned to future projects. 21 st NCBC Conference
5 MAJOR HOSPITAL PROJECTS Mechanical and Electrical Systems Commissioned Maple Grove Hospital Maple Grove, MN University of Minnesota Amplatz Children s Hospital, Minneapolis, MN 21 st NCBC Conference
6 MAJOR HOSPITAL PROJECTS Mechanical and Electrical Systems Commissioned University of Chicago Medical Center - Chicago, IL Owensboro Medical Health Center Owensboro, KY 21 st NCBC Conference
7 Electrical Power System Commissioning Commissioning of Electrical Power systems is important because most electrical failures often occur as catastrophic events and are not detected until a fault or failure occurs. National Electrical Code now requires commissioning of Critical Operations Power Systems (COPS). Ref: NEC Code, Article 708.
8 Electrical Power System Commissioning What, When, How & Where We will discuss electrical failures and issues we have found when commissioning electrical and emergency power systems. We will review some project examples to demonstrate:
9 Electrical Power System Commissioning WHAT failure or issue occurred WHEN did failure occur HOW was the problem resolved WHERE in the Cx process can we best affect these electrical issues.
10 Introduction Electrical and Mechanical Integration We will also discuss some common mechanical systems interface issues found during electrical testing. 21 st NCBC Conference
11 Essential Power System Essential Power system Four 2000kW Generators Paralleling Switchgear Multiple Automatic Transfer Switches serving Priority 1 and Priority 2 loads Priority 1 loads Life Safety and Critical nonshed-able loads required to be transferred to Essential (Generator) power within 10 seconds. Priority 2 loads Loads requiring restoration of power but not within a specified maximum time interval like Priority 1 loads. These are shed-able loads and consist of Equipment Branch system loads.
12 Essential Power System What failure occurred Case Study: The sequence was not defined prior to testing thus the system was not programmed. During the overload test a P1 load was shed When Failure occurred during sequence of operations testing. Why Sequence of Operations not provided or poorly defined. Load shed sequence not clearly defined. Where in Cx process Define sequence of operations early in project during Design Phase Test sequence of operations including load shed sequence. Verify Priority 1 loads don t shed
13 Normal Power System Main Tie Main Switchgear 480 Volt Double Ended Switchgear Main Tie Main Configuration Mains normally open, Tie Closed Upon loss of power, affected main trips open and tie closes automatically restoring normal power to loads. Switchgear shipped in sections equipment and control wiring field connections required
14 Normal Power System What failure occurred Upon loss of utility side A, control voltage throwover scheme failed to transfer control power to A Bus, causing sustained loss of normal power to A Bus loads. When Failure occurred during functional testing by simulating loss of side A and side B utility power. Why During field connection of shipping splits, control wiring harness connector was not connected or wiring connections were incorrectly made by field installer. Where in Cx process Field observation and testing phase is only place to find this error and prevent a failure.
15 Fuel Oil System What failure occurred Fuel leaks, one large enough to delay essential power system testing for one month When Failure occurred during prior to functional testing of emergency power system. Fuel Oil system was started up but not functionally tested. Why System left on auto mode and cold temperatures cause fuel recirculation to start. Undersized fuel pump could not remove fuel oil from day tanks fast enough to keep up with supply pumps.
16 Fuel Oil System Where in Cx process Design/Submittal Review process Functional Testing Mechanical/Electrical Lessons Learned. Critical to functionally test fuel oil system and other supporting systems prior to load bank testing of generators. Building Automation System (BAS network ideally too) must be ready early Early coordination with Controls Contractor Electrical testing usually scheduled relatively early in construction schedule. Early scheduling effort particularly for systems with heavy mechanical/electrical interface.
17 Loss of Power Response (LOPR or Blackout) Test What is a LOPR Test? Not just an electrical systems test but a Building Wide test. LOPR Confirms: Emergency Power system responds as expected upon loss of Utility power. Mechanical equipment, electrical and life safety loads restore to normal operation upon restoration of alternate power source.
18 Loss of Power Response (Blackout) Test What is a LOPR Response Test? Other special building systems (BAS, Nurse Call, Security & Access, Med Gas, lighting, Information Technology, telecom, critical outlets, etc.) restore to normal operation as building is transferred to emergency power Occupant equipment responds as expected under emergency power. Mechanical and other building systems recover as expected upon restoration of Utility/Normal power source.
19 Loss of Power Response (Blackout) Test When Loss of Power Response test should be conducted after all electrical & mechanical systems have been commissioned. Why System interactions and issues are observed that often would not be observed when conducting functional testing of individual systems.
20 Loss of Power Response (Blackout) Test Lessons Learned What Mechanical system restart sequences did not function as the Building Automation System (BAS) did not know that it was operating under alternate power source. When Consider observing mechanical systems operation and proper restart during earlier interim Essential Power System testing.
21 Loss of Power Response (Blackout) Test Lessons Learned What Operating Rooms were unable to maintain proper pressurization during and following a power outage. When Define the requirements early in the project as part of the Owner s Project Requirements (OPR) documentation. Do all parties (including the design professional) understand the requirements of the system? Functionally test during mechanical testing and during Loss Of Power Response testing.
22 Loss of Power Response (Blackout) Test Lessons Learned What Security access system not operable as not powered by Essential Power System When Discovered during LOPR test. Ideally, as part of functional testing of the Security/Access systems, would perform a mini LOPR test. When planning LOPR test, make sure to provide for access to spaces with hard keys in case of failure of security and other electronic systems.
23 Loss of Power Response (Blackout) Test Lessons Learned What Chillers were driven to 100% since controls were operating on UPS and chillers were non responsive. Once chiller emergency power restored they drove to 100%. Why BAS is powered off of an Uninterruptible Power Supply (UPS) and does not know that systems it is controlling are without power. When Discovered during mini LOPR test.
24 Electrical Power System Commissioning Questions?
25 THANK YOU
The Future in Fire Protection and Life Safety Cx. David J. LeBlanc, PE, FSFPE
The Future in Fire Protection and Life Safety Cx David J. LeBlanc, PE, FSFPE AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects
More informationCommissioning of Mission Critical Facilities
Commissioning of Mission Critical Facilities Terry L. Rodgers, CPE, CPMP VP of Sustainable Operations Primary Integration Solutions Paul Liesman SVP of FM & Commissioning Syska Hennessy Group AIA Quality
More informationData Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
More informationOPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
More informationRouch, Jean. Cine-Ethnography. Minneapolis, MN, USA: University of Minnesota Press, 2003. p 238
Minneapolis, MN, USA: University of Minnesota Press, 2003. p 238 http://site.ebrary.com/lib/uchicago/doc?id=10151154&ppg=238 Minneapolis, MN, USA: University of Minnesota Press, 2003. p 239 http://site.ebrary.com/lib/uchicago/doc?id=10151154&ppg=239
More informationEmergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
More informationMinimizing Impact of Electric Utility Outages with Backup Generation
Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility
More informationOPERATIONS CAPITAL. The Operations Capital program for the test years is divided into two categories:
Filed: September 0, 00 EB-00-0 Tab Schedule Page of OPERATIONS CAPITAL.0 INTRODUCTION Operations Capital funds enhancements and replacements to the facilities required to operate the Hydro One Transmission
More informationProvider: Conference for Catholic Facility Management
Provider: Conference for Catholic Facility Management Provider Number: G460 Course Title: Hiring a Mechanical Engineer or a Mechanical Design-Build Contractor: HVAC, Mechanical and Boiler Issues, and Implementing
More informationConsiderations for Building Controls
Considerations for Building Controls Does Nighttime Setback really save energy? Natalia Camblor, CEM Project Engineer Sustainable Engineering Group LLC AIA Quality Assurance Learning Objectives 1. Recognize
More informationModel #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: saleshelp@tripplite.com Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
More informationIs the Grass Greener on the other side? Examples of Cx south of the border. Jorge Torres Coto, Empirical Engineering
Is the Grass Greener on the other side? Examples of Cx south of the border Jorge Torres Coto, Empirical Engineering 21 st National Conference on Building Commissioning AIA Quality Assurance The Building
More informationSustainable water heating solutions through solar systems
VIESMANN Sustainable water heating solutions through solar systems Murat Aydemir Managing Director Viessmann Middle East FZE Viessmann is a Registered Provider with The American Institute of Architects
More informationSNMP Web card. User s Manual. Management Software for Uninterruptible Power Supply Systems
SNMP Web card User s Manual Management Software for Uninterruptible Power Supply Systems Table of Contents 1. Overview... 3 1.1 Introduction... 3 1.2 Features... 3 1.3 Overlook... 3 1.4 Installation and
More informationFFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
More informationSWITCHGEAR. EGP Switchgear
SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all
More informationCx for the Forgotten Resource: Water. Daniel Forino, PE, LEED AP BD+C
Cx for the Forgotten Resource: Water Daniel Forino, PE, LEED AP BD+C AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects Continuing
More informationFor a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationPMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
More information..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
More informationChilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates
Chilled Water System Commissioning: Variable Primary Flow John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. History of chilled water system configurations
More informationBypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
More informationParalleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
More informationSmart Pro Rack/Tower UPS Intelligent, line interactive network power management system
Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system Model #: SMART500RT1U 500VA line interactive 1U rack/tower UPS 7 outlets with 1 switchable load bank Simultaneous
More informationANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
More informationD. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
More informationSCADA. The Heart of an Energy Management System. Presented by: Doug Van Slyke SCADA Specialist
SCADA The Heart of an Energy Management System Presented by: Doug Van Slyke SCADA Specialist What is SCADA/EMS? SCADA: Supervisory Control and Data Acquisition Retrieves data and alarms from remote sites
More informationSmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMARTINT3000VS Highlights 3kVA / 3000VA / 2250W line interactive tower UPS system 230V
More informationFundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationSmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications
More informationSMM. Installation Operation Maintenance
SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation Foreword These installation,
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationBC Pro UPS System Standby UPS System
BC Pro UPS System Standby UPS System Model #: BCPRO1400 1400VA standby, tower UPS system Offers battery derived AC output during blackouts and brownouts starting at 99V 6 protected AC outlets (NEMA 5-15R)
More informationQualitative Analysis of Power Distribution Configurations for Data Centers
Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
More informationIncreased power protection with parallel UPS configurations
Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton
More informationCONSULTANT REPORT. Behavior of Two Capstone 30kW Microturbines Operating in Parallel with Impedance Between Them CALIFORNIA ENERGY COMMISSION
CALIFORNIA ENERGY COMMISSION Behavior of Two Capstone 3kW Microturbines Operating in Parallel with Impedance Between Them CONSULTANT REPORT MARCH 2 CEC-2-2 Arnold Schwarzenegger, Governor CALIFORNIA ENERGY
More informationEnergy-efficient data center achieves 2N reliability; MTU Onsite Energy generator sets provide critical backup
Press Release Contact: Gary Mason Tognum America Inc. Phone: +1 248 560 8480 E-mail: gary.mason@tognum.com Agency contact: Robert E. Sheldon, APR Creative Communications Consultants, Inc. Phone: +1 210
More informationA reasonable, new furnace (mid efficiency) has the following electrical requirements:
June 2007 Power Backup Systems for Your Home. As promised from a previous safety meeting, a couple of options to protect you home in the event of a power failure. These options are for the most serious,
More informationElectrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
More informationInternet Office UPS System Standby UPS for PCs, workstations and more
Internet Office UPS System Standby UPS for PCs, workstations and more Model #: INTERNETOFFICE500 500VA standby tower UPS system Offers battery-derived AC output during blackouts and brownouts starting
More informationSUFFOLK COUNTY CODE OF RULES GOVERNING RESTRICTED LICENSED ELECTRICIAN S
SUFFOLK COUNTY CODE OF RULES GOVERNING RESTRICTED LICENSED ELECTRICIAN S Including: 1. Heating, Ventilating and Air Conditioning (HVAC) 2. Irrigation Systems 3. Oil and Gas Burning Equipment 4. Signs and
More informationGuide Specification SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY
SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. HVAC Commissioning description. 2. HVAC Commissioning responsibilities. 1.2 REFERENCES A. American Society
More informationCx for Enhanced Healthcare Project Delivery. Presentation Format. Project features and timeline
Cx for Enhanced Healthcare Project Delivery Rick Staley Sr. Construction Manager PH&S Joe Webb Construction Manager PH&S Richard Beam Director, Energy Management Services PH&S Todd McGuire, PE - Sr. Project
More informationUTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN
Page 1 of 27 UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN Page 2 of 27 Table of Contents 1. OBJECTIVE... 4 2. SCOPE... 4 3. COMMUNICATION... 4 4. LOSS OF NATURAL GAS SUPPLY... 5 5. LOSS OF
More informationSOUTH CAROLINA. Standard for Interconnecting Small Generation 100 kw or Less with Electric Power Systems (EPS) (Interconnection Standard)
SOUTH CAROLINA Standard for Interconnecting Small Generation 100 kw or Less with Electric Power Systems (EPS) (Interconnection Standard) 1. Overview: This Standard contains the requirements, in addition
More informationCommissioning and Maintenance: Two Sides of the Same Coin? Kristin Heinemeier, PE, PhD Principal Engineer UC Davis WCEC
Commissioning and Maintenance: Two Sides of the Same Coin? Kristin Heinemeier, PE, PhD Principal Engineer UC Davis WCEC AIA Quality Assurance The Building Commissioning Association is a Registered Provider
More informationWater Priming Mode Purge air from plumbing system. How do I solve ER-3 WATER PRIME: TIPS ON FILLING SPA IMPORTANT NOTE WARNING
Water Priming Mode Purge air from plumbing system TIPS ON FILLING SPA Before filling remove spa skirt and be sure that all valves in the plumbing system are fully open to maximise the amount of air that
More informationUSER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat
Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage
More informationModel #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V
SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79
More informationCloud-Based Commissioning. Dale Davis Mark Walter Keithly Barber Associates
Cloud-Based Commissioning Dale Davis Mark Walter Keithly Barber Associates AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects
More informationTechnician High Pressure Pump Guide for the 7.3 Power Stroke Engine
Technician High Pressure Pump Guide for the 7.3 Power Stroke Engine HIGH PRESSURE PUMP. PUMP LEAKS. ICP SYSTEM DIAGNOSTICS. REPAIR PARTS. TOOLS IPR TEST TOOLS AND ICP PUMP LEAK REPAIR High pressure pumps
More informationNational Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
More informationThe reliability of the grid
Power topic #9019 Technical information from Cummins Power Generation Power system considerations for cell tower applications White Paper By Wissam Balshe, Group Leader, Sales Application Engineering Industry
More information21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
More informationABC-1000 Automatic Boiler Level Controller Operation and Installation Manual
QUALITY STEAM SPECIALTIES SINCE ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual Section: C500 Bulletin: C500.40 Date: 06-26-01 Supersedes: New PRODUCT DESCRIPTION: The Clark-Reliance
More informationAETNA FIRE ALARM SERVICE CO., INC.
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the inspection or test. It shall be permitted to modify this form as needed
More informationSiteRanger tm. Power quality / site monitoring. Comm/net Systems, Inc.
SiteRanger tm Comprehensive Broadband/ Enterprise site monitoring device for Headend s, Hub Sites. Power quality / site monitoring Focus on power system infrastructure Retrofit legacy devices for remote
More informationCyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.
Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M
More informationENGINEERING COMPETENCIES ENTRY LEVEL ENGINEER. Occupation Specific Technical Requirements
ENGINEERING COMPETENCIES ENTRY LEVEL ENGINEER Responsible for performing entry level engineering analysis, design, plan, review and inspection for small to medium projects and/or designated segments of
More informationCase Study -Sandy Grove Middle School First Net Positive Energy P3 School In North Carolina
Case Study -Sandy Grove Middle School First Net Positive Energy P3 School In North Carolina Public-Private Partnership (P3) Government - provides incentive(s): transfer of asset (land), one time grant,
More informationHome Inspection Report
4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:
More informationGenerator 101: Buying and Installing a Generator for Your Home or Office. bruniandcampisi.com 914-946-5558
Generator 101: Buying and Installing a Generator for Your Home or Office 1 Generator 101: Buying and Installing a Generator for Your Home or Office bruniandcampisi.com 914-946-5558 Introduction: An automatic
More informationTECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Tankless Electric (RTE) Troubleshooting
Sequence of Operations 1 Power supply and field wiring block 2 Energy Cut Off (ECO) 3 Water flow plunger and cold inlet 4 Magnetic flow switch 5 Water temperature thermistor 6 Control panel and circuit
More informationIntroduction to PowerWorld Simulator: Interface and Common Tools
Introduction to PowerWorld Simulator: Interface and Common Tools 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com Fault Analysis Analysis
More informationBackup Fuel Oil System Decommissioning & Restoration Plan
Backup Fuel Oil System Page 1 of 19 Overview of Physical Fuel Oil System and Decommissioning Steps The fuel oil system at Milford Power consists of a number of subsystems. These include the following:
More informationADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES
ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES by Kazuhiro Takeda Research Manager, Research and Development Center and Kengo Hirano Instrument and Control Engineer,
More informationManual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
More informationData Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
More informationMonitoring Underground Power Networks
Monitoring Underground Power Networks By Mark Stiles Merve Cankaya ABSTRACT Underground electric distribution systems are common in large cities throughout the United States. Power usage for the entire
More informationController Automation, Model II+
Controller Automation Page 2 of 2 Automation with the RADAK II+ power controller II+ I/O Points: Inputs 5 Programmable Digital inputs 2 Dedicated digital inputs (Channel select and External SCR control
More informationSWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
More informationCase Study of Emergency Disconnect Sequence in the Gulf of Mexico
Case Study of Emergency Disconnect Sequence in the Gulf of Mexico Trent Fleece Subsea BOP Operations Team Lead May 8, 2015 Case Study of Emergency Disconnect Sequence in Gulf of Mexico Industry Standards
More informationTwo-Phase Evaporative Precision Cooling Systems
Two-Phase Evaporative Precision Cooling Systems For heat loads from 3 to 300kW Using non-conductive refrigerant fluid, our patented Next-generation, two-phase evaporative precision cooling systems enable
More informationHeat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
More informationGENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control
More informationSuitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
More informationIT@Intel. Thermal Storage System Provides Emergency Data Center Cooling
White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that
More informationENGINEERING REPORT. XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613
ENGINEERING REPORT XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613 PERFORMED BY: MIDWEST ELECTRICAL CONSULTANTS, INC 18055 UPLAND DRIVE TINLEY PARK, ILLINOIS 60487 (708) 444-0001 fax: 444-0003
More informationATTACHMENT G. Network Operating Agreement
ATTACHMENT G Network Operating Agreement 1. PURPOSE OF NETWORK OPERATING AGREEMENT The purpose of this Agreement is to identify contractual requirements related to Network Integration Transmission Service
More informationOperational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives
DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)
More informationLiebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
More informationSafety Requirements Specification Guideline
Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se -1- Summary Safety Requirement
More informationThe Aftertreatment System Technician's Guide has been revised.
NUMBER: 1 ATS 07 S.M. REF.: Listed in Table 1 ENGINE: ATS DATE: April 2007 SUBJECT: CHANGES IN TROUBLESHOOTING PUBLICATION: 7SE63 The Aftertreatment System Technician's Guide has been revised. MANUAL REFERENCE
More informationUser Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed
More informationB. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related
More informationApplication of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
More informationHow To Get A Power Line Extension
GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs
More information"Big Data", Better Choices: Data Tools for EBCx Impact
"Big Data", Better Choices: Data Tools for EBCx Impact Terry Bickham, CEM, LEED AP, CDSM,CSDP Director, Energy Services and Solutions, Trane AIA Quality Assurance The Building Commissioning Association
More informationGPD 506/P5 Start-up Procedure and Checklist
GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass
More informationStroom voor elke toepassing
ELECTRICITY: ALWAYS & EVERYWHERE With VICTRON Phoenix MultiPlus and a HONDA Generator An intelligent combination with endless possibilities! Electrical appliances that increase on board comfort, such as
More informationDesign Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)
Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) 1. In addition to the information scheduled below, the pre-tender designer is responsible for: (i)
More informationMetering for today s systems
Metering for today s systems The sub-meter gathers data on the building side of the utility company meter. This allows us to break out usage so data can be collected from individual circuits, a single
More informationINSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS
3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS INSTALLATION MANUAL Before you begin the installation Read the INSTRUCTIONS! Always use a multi-meter when verifying vehicle wiring. Before mounting the
More informationEnergy Design Resources Commissioning Plan Outline Template
IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended
More informationDesigned for uptime. Defining data center availability via a tier classification system
Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center
More informationThe State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities
Generator Testing in Nursing Facilities Introduction Recent emergencies and natural disasters have emphasized the need to ensure that nursing facilities have an adequate EPSS in place should the loss of
More informationCAUTION. CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or moderate injury.
Product Description The APC by Schneider Electric Smart-UPS is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts,
More informationREAD AND SAVE THESE INSTRUCTIONS. INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC, NEC AND LOCAL ELECTRICAL CODES.
16EC SERIES UPFLOW PACKAGED TERMINAL AIR CONDITIONERS Electric Heating and Cooling Unit Cooling - Only Unit INSTALLATION & OPERATION MANUAL IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. INSTALLATION AND
More information