Use, maintenance and inspection of waterproof roofing systems. Polymer-Modified Distilled Bitumen Membranes
|
|
|
- Gillian Dixon
- 9 years ago
- Views:
Transcription
1 Use, maintenance and inspection of waterproof roofing systems
2 2 POLYGLASS I Rev
3 CONTENTS 1. Introduction - Foreword 4 2. Maintenance agreement 5 3. Roof access 5 4. Exposed roofs and ballasted/protected roofs 5 5. Coating and maintenance of a non-surfaced bitumen covering 6 6. Maintenance of a surfaced bitumen covering (mineral-surfaced membrane) 7 7. Accessibility/walkability - Exposed roofs 9 8. Accessibility/walkability - Ballasted/protected roofs 9 9. Building services and machinery Snow loading on roofs Waterproofing membrane repair and/or alteration work Waterproofing membrane ridging - buckling effects Water or air bubbles found on roofing Periodic waterproofing membrane inspection and cleaning General inspections Specialist inspections Sample inspection and maintenance checklist for MBDP membranes 17 Rev I POLYGLASS 3
4 1. INTRODUCTION - FOREWORD Roofs require regular maintenance to ensure the waterproofing system keeps performing at its peak and retains its properties in the long term. Generally, each country has its own standards and rules for the correct maintenance of roof waterproofing systems and you must refer to these standards/rules to ensure the correct ongoing management of your roof system. In Italy, for example, a specific technical standard has been introduced, attesting to the importance of maintenance: UNI 11540:2014 Guideline for the drafting and right implementation of the maintenance program of continuous roofing made with flexible sheets for waterproofing. This standard provides useful information on drawing up and implementing a routine maintenance plan for continuous roofing produced using flexible waterproofing membranes. The standard comprises a number of parts: a) Roof user guide. This contains information aimed at users to help them understand how best to use the roof. b) Maintenance manual. This contains the information needed to maintain the roof correctly. c) Maintenance schedule. This contains information on the maintenance inspection stages and relevant intervals in order to manage the roof correctly over the course of its service life. The roofing system Designer is tasked with drawing up the maintenance manuals and schedule. This document prepared by Polyglass SpA provides information to help you use and maintain POLYGLASS modified polymer distilled bitumen membranes (MBDP) and roofing systems correctly. This information can be used as a foundation for preparing a more comprehensive and specific inspection and maintenance schedule to be drawn up by the Designer. The technical properties/performance of any product inevitably deteriorate over time as a result of stress and environmental factors, such as temperature (especially high temperatures during the summer months), the harmful effects of freeze/thaw cycles, snow, hail, etc.. Critical factors will be indicated herein along with the resulting action to be taken to avoid problems and boost the waterproofing system s service life and performance. 4 POLYGLASS I Rev
5 2. MAINTENANCE AGREEMENT The job of installing continuous roofing with MBDP membranes involves specialist work, meaning suitable expertise and equipment are required to lay and maintain the membranes correctly. Consequently, we advise the Owner and/or Manager of the building to take out a roof inspection and scheduled maintenance agreement directly with the Specialist Waterproofing Company. Maintenance performed by non-specialist personnel, in addition to not producing the desired outcome, can actually damage the roofing and put their and others safety at risk. 3. ROOF ACCESS Roof access must be granted only to authorized personnel who have received suitable training and instruction and have been advised on the hazards and risks encountered on the roof. The roof must always be accessed in full safety, in compliance with all current accident-prevention regulations. To avoid falls from heights, suitable collective protective equipment must be provided (parapets, scaffolding, etc.) and/or, as an alternative, personal protective equipment (anchor points, life lines, safety harnesses, etc.) must be used. All personnel accessing the roof must be issued with suitable PPE for the task at hand. EXPOSED ROOFS AND BALLASTED/PROTECTED ROOFS Waterproof roofing systems produced with polymer distilled bitumen membranes (MBDP) can be classified into the following categories: - Exposed roofs - Ballasted and protected roofs. EXPOSED ROOFS On exposed roofs, the waterproofing membrane is left exposed to the effects of UV rays and resulting high temperatures during the warmer months. In order to ensure the membrane offers lengthy service life and lasting performance, it must therefore be protected from this kind of stress. This protection consists in: - Surfacing with mineral slate chippings (operation performed at the manufacturing facility), producing what are commonly referred to as mineral-surfaced membranes Rev I POLYGLASS 5
6 or - Coating with protective or reflective paints (operation to be performed on site), producing what are commonly referred to as smooth membranes or black membranes. Specific maintenance for this kind of roofing generally consists in standard cleaning and inspection work, with special attention paid to the efficiency of the protective coating. BALLASTED AND PROTECTED ROOFS MBDP waterproofing membranes are used to produce ballasted and protected roofs and are formulated to withstand the stress encountered under the ballast (gravel, slabs, concrete screed, paving, roof gardens, etc.); in this type of application, they are not directly exposed to the elements and UV rays. The areas of the waterproofing membrane covered and protected with ballast are no longer accessible, while areas that are left directly exposed (generally, vertical turn-ups) are in need of protective treatments like those required for exposed roofs. Specific maintenance for this kind of roofing generally consists in standard cleaning and inspection work, with special attention paid to the efficiency of the protective coating in areas left exposed. 5. COATING AND MAINTENANCE OF A NON-SURFACED BITUMEN COVERING The coating is usually applied to the surface of a polymer bitumen membrane that is directly exposed (exposed roofs): this membrane must be an APP (plastomeric) membrane as SBS (elastomeric) products cannot be left directly exposed to the harmful effects of UV rays and hence require mineral surfacing (mineral-surfaced membranes) or ballasting (concrete covering or other ballast). In the case of traditional or APP-modified Reoxthene membranes, they must be coated with special protective or reflective paints, which are part of the POLYGLASS range (for instance, POLYVER ALU, POLYSINT SUN REFLECT, etc.) and must be compatible with the product s bituminous matrix: choose a coating to suit the individual case s specific traits and requirements. The paints are generally highly reflective coatings and often have mineral or aluminium pigments added to keep the membrane s temperature down as much as possible. We recommend, wherever possible, that you refrain from using overly dark colours. To apply and maintain the coating, we recommend you proceed as follows: A) Before coating, leave the membrane to dry long enough to allow any oily residues in the bitumen material to evaporate (approx. 2 to 3 months): when installing the roofing with very high temperatures (summer months), 6 POLYGLASS I Rev
7 this may take longer. Sometimes, before coating, you may find it best to wash down the bitumen membrane first. WARNING: Failure to comply with the above-mentioned time restrictions can result in rapid deterioration of the paint. B) You will normally need to apply two coats of protective paint, leaving a few hours between coats and, in any case, waiting until the first coat has dried completely. C) The life of the coating will vary depending on such factors as latitude, the product s exposure, environmental conditions, proper roof pitch and the amount of paint applied. Protective paints can be expected to provide effective protection for approx. 2-4 years, after which the membrane will require recoating. It is good practice to inspect the painted membrane at least once a year to check its state of repair and, where necessary, take appropriate action on any areas where it has deteriorated. WARNING: Ponding can occur on flat roofs with an incorrect or insufficient pitch. Pooling water results in the premature ageing of paints, the first sign of which is crazing on the surface, eventually culminating in the paint coming off. D) Check that drains and gutters are clean and working properly to stop water ponding on the roof. E) Check that seals produced with silicone mastic on metal trims or flashing used to finish off the waterproofing membrane at vertical turn-ups (perimeters, chimneys, skylights, etc.) are watertight. F) Where building services (chillers, air ducting, equipment, etc.) are installed on the roof, make sure their supports do not damage the bitumen membranes (tearing, support incorporated in the membrane, etc.). Reapply protection, if any, and perform any necessary repairs. G) You will need to check that vents, if any, are in proper working order: they must not be blocked by dust or any other material (e.g. wasp nests). 6. MAINTENANCE OF A SURFACED BITUMEN COVERING (Mineral-surfaced membrane) For exposed waterproof roofing systems, membranes surfaced with mineral slate (granules) are often chosen to avoid the periodic maintenance associated with paint coatings. With a layer of mineral slate on their surface, these membranes are protected from the harmful effects of UV rays and hence do not require a protective coating of paint. The mineral surfacing usually consists in natural slate chippings, meaning that there is likely to be a slight difference in colour, which is acceptable given the nature of the product. Rev I POLYGLASS 7
8 The quantity of slate applied can range from around 800 to 1,000 grammes per m2. It is entirely normal for some of these chippings to come away when the waterproofing membrane is first put into service. A loss of up to 30% is acceptable according to the standards and occurs because not all the slate chippings penetrate the bitumen material during the manufacturing process and these are likely to come loose during the membrane s installation. To minimize the loss of granules, a specific granule sealer (Polyglass MINERAL FIX) can be applied once the mineral-surfaced membrane has been laid. We recommend the following maintenance procedures for these mineral-surfaced membranes: A) Oily stains can appear on the mineral surface immediately after the membranes are laid, especially during very warm weather, due to normal migration from the bitumen material. These stains are usually washed off the surface the first few times it rains. However, should the stains persist - while they do not affect the product s efficiency - you can always wash the surface down with water, even using a medium pressure washer, being careful not to aim the jet of water against the lay of the lap selvedges, instead spraying in the same direction (to avoid the risk of them accidentally coming unstuck). B) As mentioned above, it is normal for a certain percentage of mineral granules to come off the membrane s surface, however you should check at regular intervals that granules coming off the roof do not reduce the efficiency of the roof s drains. In addition, you should check that the bitumen material is not exposed directly to sunlight as a result of the mineral surface layer thinning; if you find balding patches, you will need to coat them with relevant protective or reflective paints. C) When dealing with an exposed mineral-surfaced membrane, you will need to check sealing at overlaps at regular intervals, especially at points where the structure is subjected to the greatest stress (corners, expansion joints, fixed points, etc.). Over time, some overlaps or parts of them can tend to come unstuck if they are put under tensile stress. In such a case, even the slightest amount of water - though not resulting in leaking immediately - could cause the selvedge to detach completely if the water freezes overnight, resulting in the risk of water penetration. WARNING: The waterproof roofing system comprises several overlapping membranes with both side and end laps. Stress as a result of movements and stretching as a result of thermal expansion and movements of the actual building structure or insulation can cause the overlaps to come unstuck at certain points. This is one of the reasons why regular maintenance of waterproofing membranes is both recommended and necessary. D) You will need to check that vents, if any, are in proper working order: they must not be blocked by dust or any other material (e.g. wasp nests). E) Check that drains and gutters are clean and working properly to stop water ponding on the roof. F) Check that seals produced with silicone mastic on metal trims or flashing used to finish off the waterproofing membrane at vertical turn-ups (perimeters, chimneys, skylights, etc.) are watertight. 8 POLYGLASS I Rev
9 G) Where building services (chillers, air ducting, equipment, etc.) are installed on the roof, make sure their supports do not damage the bitumen membranes (tearing, support incorporated in the membrane, etc.). Reapply protection, if any, and perform any necessary repairs. 7. PACCESSIBILITY/WALKABILITY - EXPOSED ROOFS MBDP waterproofing membranes - whether mineral surfaced or smooth - used in fully exposed systems can take foot traffic and be accessed for maintenance purposes only, either to be performed on the membranes in question and/or on any machinery and building services that might be found on the roof. In summer, the bitumen material tends to soften with heat, making it more susceptible to surface damage, especially on sloped roofs. Membranes can nonetheless still be walked on for the purpose of performing maintenance on the roof itself or on machinery/building services, provided the following precautions are taken. A) If roofs are home to building services and machinery that require periodic maintenance or cleaning, we recommend producing walkways using concrete pavers laid on supports, or a concrete screed, to give all operators a safe preferential access route to follow. Before installing walkways, a suitable separating layer must be placed between the membrane and the in-situ concrete deck. B) When walking directly on the waterproofing membrane, special footwear must be worn, both for your own safety and to avoid damaging the membrane in question. C) If you need to walk on the waterproofing membranes, we recommend you avoid the hottest part of the day in summer and, similarly, the coldest part of the day in winter. To avoid putting membranes under particularly high mechanical stress, we advise against using footwear with very thick soles (cleated sole footwear) and instead recommend the use of footwear with smooth soles. When using cleated sole footwear, we strongly advise you always to check that no fine gravel or other abrasive material has accidentally stuck to or become lodged in the sole before walking on the waterproofing membrane to avoid the risk of scraping or piercing the membrane in question. D) If you are gaining access to a roof in driving rain or if the roof has pooling water or is icy, exercise extreme care to avoid the risk of slipping. E) Never place anything heavy or sharp directly on the waterproofing membrane unless you have prepared a suitable protective surface first to set the object down on and distribute the load (such as wooden planks or other suitable devices). 8. ACCESSIBILITY/WALKABILITY - BALLASTED/PROTECTED ROOFS Depending on the type of ballast or paving, MBDP waterproofing membranes may be suitable for foot traffic or accessible only for maintenance purposes, as specified below. Rev I POLYGLASS 9
10 - Gravel ballast: accessible only for maintenance purposes, either to be performed on the actual roof and/or on any machinery or building systems found on the roof - Ballast comprising pavers on supports (floating paving): accessible for maintenance purposes and walkable - Paving designed to take foot traffic (tiles laid on concrete substrate): accessible for maintenance purposes and walkable - Paving required to take vehicle loads (concrete screed, loose-laid paving blocks, laid stone slabs): accessible for maintenance purposes, suitable for light traffic <2 tonnes/axle accessible for maintenance purposes, suitable for heavy vehicle traffic 2 tonnes/axle - Soil ballast (roof garden or green roof): accessible for maintenance of extensive green roof accessible for maintenance of intensive green roof If roofs ballasted with gravel are home to building services and machinery that require periodic maintenance or cleaning, we recommend producing walkways using concrete pavers laid on supports to give all operators a safe preferential access route to follow. Until the ballast layer has been laid, when walking directly on the waterproofing membrane, special footwear must be worn, both for your own safety and to avoid damaging the membrane in question, taking all the precautions and measures given above in the chapter entitled ACCESSIBILITY/WALKABILITY - EXPOSED ROOFS. 9. BUILDING SERVICES AND MACHINERY Building services and machinery installed on the roof must be suitably positioned on the roof and integrated/connected with the waterproofing membrane (plinths, supporting beams, etc.). Building services and machinery must not sit directly on the waterproofing build-up system and should instead be placed on bases with a suitable supporting surface designed to distribute the load correctly. In addition, the shape and material of the bases must be designed so that they do not damage the waterproofing membrane. WARNING: Check and size bases based on the compressive strength of any thermal insulation included in the roof build-up. Building services and machinery must not release or leak aggressive, polluting or damaging substances (liquids, solids or fumes) that might compromise the waterproofing membrane s performance. In the event maintenance is performed on building services and on machinery, all work carried out while on the roof must be performed with extreme care so as not to damage the waterproofing membrane and suitable temporary 10 POLYGLASS I Rev
11 protective structures must be in place. Be careful not to spill substances or materials on the roof that could damage the waterproofing membrane In the event of accidental spills, all debris and/or leachate must be removed without delay and the waterproofing membrane must be suitably cleaned, where necessary using running water, and always acting in compliance with current safety and environmental standards. If in any doubt, seek the advice of the Specialist Waterproofing Company, who will be able to provide you with any information and support you may need. When placing new building services or new machinery on the roof, you are advised to call the Specialist Waterproofing Company first to avoid damaging the existing waterproofing membrane and ensure correct connection and sealing systems are put in place. 10. SNOW LOADING ON ROOFS Generally speaking, snow sitting directly on MBDP waterproofing membranes does not cause damage and does not require any action. In certain cases, though, it might be advisable to go up on the roof to clear drains to encourage water generated as the snow thaws to drain off the roof. Or you may want to check that snow has not built up so much that it reaches the top edge of skylights, vents, chimneys and other openings, if any, in the roof, in which case there is a risk of snow spilling over and getting inside the roof; or if there are overloading issues linked to the building s load capacity. In certain situations of this kind, you may need to reduce the thickness of the blanket of snow in specific points or areas of the roof. When accessing the roof, always exercise the utmost care and caution, using suitable personal and collective protective equipment, taking into account the added difficulty of accessing a roof covered in snow and/or ice. Snow must be removed using manual tools that will not damage the waterproofing membrane and/or ballast layers and paving. Do not use metal spades and shovels: use plastic shovels with rounded edges instead. Remove surface layers of snow, being careful not to remove layers underneath in direct contact with the waterproofing membrane and/ or ballast layers and paving to avoid accidental mechanical damage. Before winter comes, it is advisable to check overlaps as snow could cause water to go against the lay of the roof, thus generating the risk of water penetrating inside the building. When the show melts, it is best to check the condition of the waterproof build-up system so that prompt action can be taken if maintenance is required. Rev I POLYGLASS 11
12 11. WATERPROOFING MEMBRANE REPAIR AND/OR ALTERATION WORK In the event the waterproofing membranes are damaged accidentally, do not attempt makeshift repairs: always contact the Specialist Waterproofing Company. In the event of an emergency requiring urgent action, you can perform quick and simple repairs using Polyglass POLYSEAL mastic, cleaning the waterproofing membrane first. Please note that these are temporary emergency measures that are not designed to last, meaning you will still need to contact the Specialist Waterproofing Company to have proper long-lasting repairs made. In the event you are altering or extending the waterproofing membrane (e.g. to accommodate new chimneys, changes to building services, etc.), do not attempt makeshift measures and instead contact the Specialist Waterproofing Company in good time. 12. WATERPROOFING MEMBRANE RIDGING - BUCKLING EFFECTS Traditionally applied polymer distilled bitumen membranes (torched on using a propane gas torch) can be installed in different ways depending on the substrate. They can be: loose laid (not attached anywhere); partially-adhered (partially glued onto the substrate at various points); full adhered (glued on across the whole surface). Depending on the installation method, the membrane will be free, to a varying extent, to move under external stresses, such as movements due to the building s structural settling, changing temperatures (of the building, insulating layers and the actual membrane), deflection and stability/behaviour of thermal insulation, if any, etc.. In any case, the roof features fixed points - such as roof edges, corners, skylights, chimneys, outlets, etc. - and, in some cases, the combination of the waterproof build-up system s movement and the presence of fixed points can cause ridges to form in the waterproofing membrane, an issue known as buckling. With regard to this buckling issue, it is worth noting that: A) In summer and winter alike, both during the day and at night, it is normal to see a certain amount of movement in the substrate, thermal insulation and waterproofing membranes as a result of differences in temperature. If excessive, this movement translates into the formation of ridges in the waterproofing membrane, starting at the corners of the roof. B) Fully-adhered membranes that are correctly secured to the layers underneath are less likely to be affected by the 12 POLYGLASS I Rev
13 buckling issue. If a membrane is not correctly stabilized/secured to the substrate, it is more likely to be affected by buckling and the negative pressure generated by wind. C) What often happens is that it s not the waterproofing membrane that moves, rather the insulating panel underneath it. In addition to being affected by pressure generated by wind, some insulation - even at relatively low temperatures (70 C) - can experience dimensional stability problems, so it s essential that the insulating panels be perfectly stable and secured to the substrate by means of mechanical fixing or gluing systems. Check that mechanical fixings are present and that they are holding securely. D) MBDP membranes with a polyester nonwoven carrier feature good strength and ultimate elongation properties. What can happen with buckling, therefore, is that the heat-welded overlaps fail before the waterproofing membrane does if they have not been done correctly. E) Failure to use the vapour barrier, apart from creating possible interstitial condensation problems, can encourage movement in certain insulating materials as a result of damp and thus also compound the buckling problem (movement in the membranes) as a result of the membrane detaching from the insulation. In the event you encounter tension, ridging or buckling issues in the waterproofing roofing membranes, you are strongly advised to call in the Specialist Waterproofing Company without delay to have them analyse the causes and perform whatever maintenance or repair work might be required. 13. WATER OR AIR BUBBLES FOUND ON ROOFING You may see air or water bubbles in the waterproofing membranes: they can form under certain circumstances, such as in the case of buildings with thermal insulation but no suitable vapour barrier. In such a case, water vapour that migrates from inside the building to the outside can rise - in the absence of an effective vapour barrier - through to the waterproofing membrane (known for its low water vapour permeability), causing pressure to build up under the membrane, which then translates into the formation of bubbles and blisters varying in size. In a worst-case scenario, you could be faced with condensation problems. Another critical factor that can translate into the formation of bubbles and blisters in the waterproofing membrane is failing to wait the required time for the concrete substrate to cure. The moisture in the cast concrete is unable to escape through the upper surface of the slab if it has been waterproofed too soon and hence this moisture pushes up against the waterproofing membrane in question. In such cases, the recommended procedure is to: A) Check that there is a vapour barrier and ensure it is suitable and working properly. B) Check that vents are installed and are working properly as they constitute a useful device regardless of whether Rev I POLYGLASS 13
14 there is a thermal insulation panel or not. C) When dealing with bubbles, cut a cross in them and, after leaving enough time for the moisture trapped inside to evaporate/dry, apply a patch using material with suitable properties. D) Bubbles can be more evident during the hottest part of the day as the water volume increases in volume. E) Check inside the building for patches of damp that can be attributed to moisture present in the concrete structure rather than to water getting inside. This moisture, being unable to evaporate out due to the membrane s low permeability, tends to be released inside the building. F) Condensation problems are usually only encountered in certain periods of the year, i.e. when certain humidity and temperature conditions arise. Hence, if the problem recurs cyclically over the course of the year, it can often be attributed to factors relating to temperature and humidity rather than to water getting inside. In the event you encounter bubbles or blistering issues in the waterproofing roofing membranes, you are strongly advised to call in the Specialist Waterproofing Company without delay to have them analyse the causes and perform whatever maintenance or repair work might be required. 14. PERIODIC WATERPROOFING MEMBRANE INSPECTION AND CLEANING To ensure the waterproofing system keeps performing at its peak and retains its properties in the long term, it is good practice to inspect and clean the roof at regular intervals. Said work is summarized in the list below, divided up into: - General inspections - Specialist inspections Other kinds of inspections and cleaning/maintenance work may be helpful/required depending on the specific case, or you may need to perform the listed work at shorter intervals. Consequently, the Designer or specialist will need to add to our guidelines accordingly. 14 POLYGLASS I Rev
15 15. GENERAL INSPECTIONS General inspections Interval Performed by: Notes Clean leaf guards on drains Six-monthly Owner/manager (*) To avoid them becoming clogged and limiting or compromising drain performance Clean and eliminate any dirt (soil, sand, etc.) on the roof and waterproofing membrane Clean and eliminate any debris or rubbish on the roof General visual inspection of the roof and equipment installed on it to detect any evident issues (waterproofing, skylights, building services, etc.) Clean and remove any vegetation growing on the roof Six-monthly Owner/manager (*) As required Owner/manager (*) Six-monthly Owner/manager (*) Six-monthly Owner/manager (*) (*) This job can be delegated to the Specialist Company by taking out an inspection and maintenance agreement To stop a culture bed being created and promoting the growth of vegetation or micro-organisms To stop foreign materials and rubbish damaging the waterproofing membrane To ensure any issues are reported promptly to the party tasked with performing the work It is advisable to stop vegetation growing and spreading Rev I POLYGLASS 15
16 16. SPECIALIST INSPECTIONS General inspections Interval Performed by: Notes Visual inspection of trims and metal flashing Yearly Specialist Waterproofing Company Check fixings and check for leaks and corrosion Visual inspection of silicone sealing Yearly Specialist Waterproofing Company Check for leaks and check adhesion Visual inspection of waterproofing membrane and of details and accessories connected to it Yearly Specialist Waterproofing Company To detect any issues that might limit or compromise its performance Visual inspection of underside of roof deck Yearly Specialist Waterproofing Company To detect any traces of water infiltration or other issues All these jobs must be delegated to the Specialist Company by taking out an inspection and maintenance agreement 16 POLYGLASS I Rev
17 17. EXAMPLE OF INSPECTION AND MAINTENANCE CHECKLIST POLYGLASS MBDP MEMBRANES INSPECTION AND MAINTENANCE CHECKLIST - POLYGLASS MBDP MEMBRANES RE: ADDRESS: OWNER: CONTACT PERSON: MAINTENANCE MANAGER: CONTACT PERSON: SPECIALIST COMPANY: CONTACT PERSON: YEAR OF COMPLETION: REFERENCES AND ATTACHED DOCUMENTS: ROOF BUILD-UP: (indicate all layers making up the roof system) OTHER USEFUL INFORMATION: Example Note: We have compiled this draft inspection and maintenance checklist for MBDP membranes by drawing on our knowledge and experience. Nonetheless, please understand that the instructions are given as a rough guide only. It is up to the Designer and Specialist Company to assess actual site conditions and determine what inspection and maintenance work is required. Rev I POLYGLASS 17
18 GENERAL INSPECTIONS PERFORMED BY: CARRIED OUT ON: NEXT INSPECTION DUE: Checks and work carried out Clean grates on drains Clean roof surface Clean and remove debris and rubbish Clean and remove vegetation Other work carried out Visual inspections: General state of roof General state of waterproofing membrane Building services 1 Building services 2 Building services 3 Trims/flashing 1 Trims/flashing 2 Trims/flashing 3 Skylights/domes Walkways Other. Other. Pass SIGNATURE OF PERSON PERFORMING WORK: SIGNATURE OF MAINTENANCE MANAGER: Fail (see notes) Example Monitor (see notes) Notes 18 POLYGLASS I Rev
19 GENERAL INSPECTIONS PERFORMED BY: CARRIED OUT ON: NEXT INSPECTION DUE: Checks and work carried out Clean grates on drains Clean roof surface Clean and remove debris and rubbish Clean and remove vegetation Other work carried out Visual inspections: General state of roof Waterproofing membrane flat Waterprf. membrane edge turn-ups Waterprf. membrane wall turn-ups Waterprf. membrane skylight turn-ups Mechanical fixing system Thermal insulation panels Roof edge trim Wall junction trim Trim Drains Junctions between roof and pipes/vents Junctions between roof and uprights Skylights/domes Walkways Silicone sealing 1 Silicone sealing 2 Building services 1 Building services 2 Building services 3 Other. Altro. Pass SIGNATURE OF PERSON PERFORMING WORK: SIGNATURE OF MAINTENANCE MANAGER: Fail (see notes) Example Monitor (see notes) Notes Rev I POLYGLASS 19
20 We have compiled this document on the use, inspection and maintenance of POLYGLASS modified polymer distilled bitumen membranes by drawing on our knowledge and experience to date. Nonetheless, please understand that all instructions given are meant as general guidelines and feature only the most basic work prescribed. If you are planning to put together a maintenance plan for the waterproofing system, you will need to assess actual site conditions and, where necessary, supplement and add to the inspections and work featured. 20 POLYGLASS I Rev
21 Rev I POLYGLASS 21
22 POLYGLASS SPA Registered Office: Viale Jenner, Milano - Italy Head Office: Via dell Artigianato, Ponte di Piave (TV) - Italy Tel Fax [email protected] 04/15
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
Commercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
Your guide to home maintenance. Flat Roofs
Your guide to home maintenance Flat Roofs Your guide to home maintenance is a series of information leaflets that gives you all the information you need to keep your home in tiptop condition. Flat Roofs
Bituminous Sheet Flat Roofs: Their repair and maintenance
Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
BLACK JACK ALL WEATHER ROOF COATING
PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
ROOF INSPECTION & MAINTENANCE
Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long
Maintenance & Inspection Guide
ADDRESSING THE NEEDS OF OUR CUSTOMERS AND THE ENVIRONMENT ONE high Performance roofing SOLUTION AT A TIME. Maintenance & Inspection Guide TABLE OF CONTENTS Topic: Page: I. Introduction 1 II. Maintenance
Site Inspection Report
Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5
Cl Sfb (27-9) Rn7 M2 December 2004 Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Fesco, Fesco S, Retrofit, Retrofit S, Fesco Fillet, PF,
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design
Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Commercial Roof Inspection Form
Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building
BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES
BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES ABOUT POLYGLASS U.S.A., INC. MODIFIED CEMENTS & ADHESIVES MASTICS ALUMINUM COATINGS EMULSIONS & PRIMERS PROTECTIVE COATINGS Polyglass manufactures
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
RECOATING AND RENEWING SPF ROOFING SYSTEMS
RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the
How to repair your existing low slope flat roof.
How to repair your existing low slope flat roof. Recycled Rubber Roofing is not a "Roof Coating." It is a liquid emulsion used as the underlayment of a new or retrofit, built-up roofing system. One of
!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!
Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single
NEOGARD. Preventive Maintenance Manual
NEOGARD Preventive Maintenance Manual Fluid-Applied Roof Coating Systems December 2014 Notes NEOGARD luid-applied roof coating systems are designed to be long lasting, monolithic membranes which provide
POLYGLASS ROOF WATERPROOFING MEMBRANES POLYSHIELD ROOF WATERPROOFING MEMBRANES
Polyglass SpA Via dell Artigianato, 34 31047 Ponte di Piave Treviso Italy Tel: 00 39 042 27547 Fax: 00 39 042 2854118 e-mail: [email protected] website: www.polyglass.com POLYGLASS ROOF WATERPROOFING MEMBRANES
EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES
Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES FAILING WATERPROOFING
BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION
07560 BUR BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION PART 1: GENERAL 1.01 SCOPE: To extend the useful service life of the aged or new asphalt built-up roof system and to reduce cooling
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
Winterizing Your Building
Winterizing Your Building DEC Author: Steven J. Susca This article was originally published in the Hoffmann Architects Journal in Issue 3, 2009. As spring thaws uncover the ravages winter weather has wreaked
FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS
FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS Table of Contents Chapter 1: FLAT ROOF REPAIR - CUT COST WITHOUT CUTTING CORNERS Chapter 2: PVC RECOVER SYSTEM HOW IT WORKS Chapter 3: 8 STRATEGIES TO
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building
Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5. 1. Purpose
Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5 1. Purpose The purpose of this practice note is to address the incidence of deck and roof membrane
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES
METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES REFLECTICLEAN ACRYLIC/URETHANE Elastomeric Roofing Systems, Inc 6900 Bleck Dr. Rockford, MN 55373 800.403.7747 -or- 763.565.6900 fax: 763.565.6901 email:
RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012
RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new
Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS
AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings
ELASTOCEM. Technical features. Applications. Two-component flexible, waterproofing and protective cementitious grout.
Two-component flexible, waterproofing and protective cementitious grout. 1504-2 PI-MC-IR Technical features Two-component grout, based on cements, selected aggregates, special additives and synthetic polymers
Crescent Valley High School Roof Investigation
Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko
ROOFS, SNOW AND ICE DAMS
ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof
CHESTERFLEX ROOF WATERPROOFING MEMBRANES
CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Please read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description
Product Data Sheet Edition 15/10/2014 Identification no: 02 07 04 10 300 0 000002 SikaProof A Edge SikaProof A-08 Edge, A-12 Edge Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing
TARRANT COUNTY DETAIL STANDARDS
TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System
Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.
CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,
High Performance PSA in Sheet Membrane in Water Protection
High Performance PSA in Sheet Membrane in Water Protection Xia Cao, Senior R&D Chemist, W. R. Grace, Cambridge MA 02140 Jyoti Seth, Strategic Program Leader, W. R. Grace, Cambridge MA 02140 Concrete is
Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.
Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice
Epdm Flat Roofing Systems
Epdm Flat Roofing Systems EDPM can be fully bonded, loose laid and ballasted or mechanically attached depending on the existing roof and its proposed usage. This applies to roofs to be refurbished and
THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS
OPTIONAL TITLE 24 CRITICAL POINTS POLYISO THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE DESCRIPTION TORCH OVER POLYISO (5,7,9 YR) TH/BS-TH/CS 2 No 0. SUBSTRATE. THERMOTEK USA PRO 2.0 FV
METHOD STATEMENT 006 TORCH APPLIED MEMBRANE TO BASEMENT WALLS
This Document is designed to cover best practice installation procedures for a one layer torch applied sheet membrane system to basement walls. PRELIMINARY WORK Ensure that all surface preparation work,
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
ROOF CONDENSATION: A COSTLY PROBLEM
ROOF CONDENSATION: A COSTLY PROBLEM CONTENTS 1. What is it? 2. How does it form? 3. What to look for 4. Repair options 5. Owner responsibilities and proactive measures 1. WHAT IS IT? Roof condensation
Sun Vinyl New Construction Windows Homeowner's Warranty
Sun Windows Sun Vinyl New Construction Windows Homeowner's Warranty Vinyl Sun Windows, Inc. warrants for a period of 2 years that the quality of workmanship and materials of vinyl items shall be free from
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS
Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING
Soils, Foundations & Moisture Control
Soils, Foundations & Moisture Control Soil The top loose layer mineral and/or organic material on the surface of the Earth that serves as a natural medium for the growth of plants and support for the foundations
Ubiflex. Non-lead flashing system
Ubiflex Non-lead flashing system Ubiflex non-lead flashing Ubiflex is a non-lead waterproof flashing material which can be used in most applications where lead is traditionally used to provide a weatherproof
HIGHWAYS DEPARTMENT GUIDANCE NOTES ON THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE DECKS
HIGHWAYS DEPARTMENT GUIDANCE NOTES ON THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE DECKS Research & Development Division RD/GN/033 June 2008 THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE
Why is my air conditioner dripping on my customers?
De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These
Wecryl Waterproofing System under surfacing supplied by others
Brief description The Wecryl waterproofing system allows a high-quality, seamless and crack-bridging waterproofing layer to be installed under loose-laid or bonded surfacing supplied by others (stone slabs,
FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association
FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING Roofing Manufacturers Association Why is a built-up roof considered a multi-ply roof? ARMA defines a built-up roofing system as a roof where multiple
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
CHAPTER 6 ASPHALT ROLL ROOFING
CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed
Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..
Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
Reroof or Restore? The right decision can save weeks of time and thousands of dollars
APOC A DIVISION OF GARDNER - GIBSON 5903 Paramount Boulevard Long Beach, California 90805 Telephone (800) 562-5669 Fax (562) 423-9597 www.apoc.com THE FOLLOWING TECHNICAL ARTICLE WAS PUBLISHED IN A MAJOR
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
Repair of Spalling and Leaking Clay Brick Building Walls
B etter buildings Repair of Spalling and Leaking Clay Brick Building Walls Overview A few years after being built in Waterloo in 1980, a condominium of three, six-storey buildings showed severe spalling
Fact Sheet: Slips, trips and falls
Fact Sheet: Slips, trips and falls Slips, Trips & Falls Slips, Trips and Falls are one of the highest causes of workplace injuries. They include those, which occur on the same level as a result of uneven
TERMOSIGN APPLICATION INSTRUCTIONS
TERMOSIGN APPLICATION INSTRUCTIONS Product s characteristics Termosign - preformed thermoplastic pavement marking system must be applied to a completely dry surface; must be applied to a surface free of
Peel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
bout your HOUSE before you start Renovating Your Basement Moisture Problems
A bout your HOUSE before you start Renovating Your Basement Moisture Problems CE 28 c Condensation of cold surfaces, efflorescence Water leak in corner on floor Mold and decay on floor joists and sill
AND MEMBRANES ROOFING UNDERLAYS. www.fakro.com
AND MEMBRANES 010 ROOFING UNDERLAYS 1 HO DOES YOUR ROOF BREATHe? MEMBRANES THE WAY to A WARM AND DRY ROOF HO HO HO HO HO HO WATERTIGHTNESS The FAKRO Company offers a wide range of membranes and underlays
A. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE
86 :: Certificate in Construction Supervision (CIVIL) 12 ROOF 12.1 INTRODUCTION The structure provided to cover the house surface (floor) is known as roof. For different situation and requirement, it is
When considering Roof drainage design the following should be taken into account:
Roof Drainage Design The primary objective of a gutter or spouting system is to remove water from the roof catchment area and channel that water to the ground drainage. Water ingress can have detrimental
The Perfect Fit For Metal Retrofit
D u r o - S h i e l d M e t a l R e t r o f i t R o o f i n g S y s t e m The Perfect Fit For Metal Retrofit Lock out leaks. Lock in your investment. Has time caught up with your metal roof? There are
Minor Cracks in Horizontal Surfaces
Cracks, chips and broken or flaking areas in concrete are not only unsightly, they can lead to further deterioration of the surface. The result is a costly replacement project as opposed to a simple repair.
Rooflight INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Rooflight These instructions should be used for: Installing Permanent Trickle Ventilation: Constructing & Waterproofing a Timber Upstand Curb: Installing & Waterproofing Proprietary
INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles
INSTALLATION RECOMMENDATIONS Outdoor Rubber Tiles Prior to Installation: The Outdoor Rubber Tiles and accessory transition pieces intended for this installation have been shipped to you via a freight carrier
DENSO WATERPROOFING SYSTEMS
DENSO WATERPROOFING SYSTEMS Approved Quality Management System AS/NZS ISO 9001:2008 Lloyds Register Certificate N o Mel 0927759 Denso (Australia) Pty Ltd A MEMBER OF WINN & COALES INTERNATIONAL 411 413
COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE
www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com
Generic Risk Assessment: Working on Roofs (FMRA 0006)
Generic Risk Assessment: Working on Roofs (FMRA 0006) Only staff and contractors who are Authorised by Facilities Management are allowed to access roof areas. Those who need access who are not Authorised
bout your house before you start Renovating Your Basement Moisture Problems
A bout your house CE 28c before you start Renovating Your Basement Moisture Problems Mold and decay on floor joists and sill plates Stuffy air, high humidity, poor air circulation Water draining in from
Georgia State University. Urban Life Building Roof Replacement
ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
White rust on galvanized and galvanized pre-painted steel. Technical Information
Technical Information White rust on galvanised steel Prevention It is easier to prevent white rust than to cure it! Reasonable precautions to protect steel during both transport and storage can considerably