Data Center Design for 40/100G
|
|
|
- Mercy Elfrieda Peters
- 10 years ago
- Views:
Transcription
1 Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an optical connectivity solution allows for an infrastructure that meets these requirements for current and future data rates. A key factor when choosing the type of optical connectivity is scalability. Scalability refers to not only the physical expansion of the data center with respect to additional servers, switches or storage devices, but also to the scalability of the infrastructure to support a migration path for increasing data rates. As technology evolves and standards are completed to define data rates such as 40/ 100G Ethernet, Fibre Channel (32G and beyond) and InfiniBand (40G and beyond), the infrastructures installed today must provide scalability to accommodate the need for more bandwidth in support of future applications. The Need for Speed 1G and 10G data rates are not adequate to meet the future needs of high-bandwidth applications. The requirement for higher data rates is being driven by many factors. Switching and routing, virtualization, convergence and high-performance computing environments are examples of where these higher network speeds will be required within the data center environment. Additionally, Internet exchanges and service provider peering points and high-bandwidth applications, such as video-on-demand will drive the need for a migration from 10G to 40/100G interfaces. IEEE 802.3ba 40G and 100G Ethernet Standard Ratified The Institute of Electrical and Electronics Engineers (IEEE) 802.3ba 40/100G Ethernet Standard was ratified in June The standard provides detailed guidance for 40/100G transmission with multimode and single-mode fibers. The standard does not have guidance for CAT UTP/STP copper cable. OM3 and OM4 are the only multimode fibers included in the standard. Multimode fiber utilizes parallel optics transmission instead of serial transmission due to the 850 nm VCSEL modulation limits at the time the guidance was developed. Single-mode fiber guidance utilizes duplex fiber wave division multiplexing (WDM) serial transmission. 40/100G multimode fiber physical media dependent (PMD) variants continue to offer a significant value proposition compared to single-mode fiber PMDs for short length interconnects in the data center. Parallel optics transmission, compared to traditional serial transmission, uses a parallel optical interface where data is simultaneously transmitted and received over multiple fibers. The 40/100G Ethernet interfaces are 4 x 10G (Figure 1) channels on four fibers per direction and 10 x 10G (Figure 2) channels on 10 fibers per direction, respectively. Litcode-##-EN LAN-1379-EN Page 1
2 Figure 1: 40G Parallel Optic Transmission Figure 2: 100G Parallel Optic Transmission Table 1 provides the OM3 and OM4 specified distances for Ethernet. Each distance assumes 1.5 db total connector loss with the exception of OM4 40/100G, which assumes 1.0 db total connector loss. OM3 and OM4 are fully capable of supporting legacy and emerging data rates, as an expected 15- to 20-year service life is expected for the physical layer. When evaluating the performance needed for the OM3 and OM4 infrastructure to meet the requirements for 40/100G Ethernet channel insertion loss transmissions, three criteria should be considered: bandwidth, total connector insertion loss and skew. Each of these factors can impact the infrastructure s ability to meet the standard s specified transmission distances. LAN-1379-EN Page 2
3 850 nm Ethernet Distance (m) 1G 10G 40G 100G OM OM */550** *Proposed distances for 10G Standard. **Engineered length. Table 1. OM3 and OM4 Specified Distances from the Ethernet Standards 1. Bandwidth OM3 and OM4 fibers were selected as the only multimode fiber for 40/100G consideration. The fibers are optimized for 850 nm transmission and have a minimum 2000 MHz km and 4700 MHz km effective modal bandwidth (EMB), respectively. Two EMB measurement techniques are utilized today for the bandwidth measurement. The minimum effective modal bandwidth calculated (EMBc) method offers the most reliable and precise measurement compared to the differential modal delay (DMD) mask technique. With minembc, a true scalable bandwidth value is calculated that can reliably predict performance for different data rates and link lengths. With a connectivity solution using OM3 and OM4 fibers that have been measured using the minembc technique, the optical infrastructure deployed in the data center will meet the performance criteria set forth by IEEE, Fibre Channel and InfiniBand for bandwidth. 2. Insertion Loss Insertion loss is a critical performance parameter in current data center deployments. Total connector loss within a system channel impacts the ability of a system to operate over the maximum supportable distance for a given data rate. The 40/100G Ethernet standard specifies the OM3 fiber 100 m distance maximum channel loss to be 1.9 db, which includes a 1.5 db total connector loss. The OM4 fiber 150 m distance maximum channel loss is 1.5 db, which includes a 1.0 db total connector loss budget. The insertion loss specifications of the MPO connectivity components should be evaluated when designing data center infrastructures. With low-loss MPO connectivity components, maximum flexibility can be achieved with the ability to introduce multiple connector matings into the connectivity link such that structured architectures can be supported. 3. Skew The IEEE 802.3ba standard includes an optical media skew of 79 ns. Optical skew, the difference in time of flight between light signals traveling on different fibers, is an essential consideration for parallel optics transmission. With excessive skew, or delay, across the various channels, transmission errors can occur. Skew testing on MPO connectivity solutions has demonstrated compliance to a strict 0.75 ns skew requirement as defined in the InfiniBand standard. Deployment of a connectivity solution with strict skew performance ensures compatibility of the infrastructure across a variety of applications. When evaluating optical infrastructure solutions for 40/100G applications, selecting one that meets the 0.75 ns skew requirement ensures performance not only for 40/100G, but also for InfiniBand. Additionally, low skew connectivity solutions validate the quality and consistency of cable designs and terminations to provide long-term reliable operation. LAN-1379-EN Page 3
4 Deploying An Optical Cabling Infrastructure in the Data Center for 40/100G Recommended infrastructure deployments in the data center are based upon guidance found in TIA-942, Telecommunications Infrastructure Standard for Data Centers. Utilizing a distributed star topology in a structured implementation provides the most flexible and manageable infrastructure. Many data center deployments today utilize the reduced topology described in TIA-942, where the s (HDAs) shown are collapsed to the Main (MDA). In this collapsed architecture, the is installed between the MDA and the s (Figure 3). Collapsed/Reduced Star Topology Access Providers Access Providers Offices, Operations Center, Support Rooms Primary Entrance Room (Carrier & Demarcation) Secondary Entrance Room (Carrier & Demarcation) Telecom Room (Office & Operations Center LAN switches) Zone Main (Routers, LAN/SAN Switches, PBX, M13 Muxes) Intermediate (LAN/SAN Intermediate (LAN/SAN Computer Room Figure 3: Collapsed/Reduced Star Topology ZA-3789 For optimized performance in meeting data center requirements, the topology of the infrastructure should not be selected alone; infrastructure topology and product solutions must be considered in unison. Cabling deployed in the data center today must be selected to support data rate applications of the future, such as 100G Ethernet, Fibre Channel 32G and InfiniBand 40G. To do this, OM3 or OM4 fiber is a must. In addition to being the only multimode fibers included in the 40/100G Ethernet standard, OM3 and OM4 fibers provide the highest performance, as well as the extended reach often required for structured installations in the data center. LAN-1379-EN Page 4
5 In addition to the performance requirements discussed, the choice in physical connectivity is also important. Because parallel optics technology requires data transmission across multiple fibers simultaneously, a multifiber (or array) connector is required. Utilizing MPO-based connectivity in today s installations provides the means to migrate to this multifiber parallel optic interface, when needed. Factory-terminated MPO solutions allow connectivity to be achieved through a simple plug & play system. To meet the needs of today s serial Ethernet applications, MPOterminated backbone/horizontal is simply installed into preterminated modules, panels or harnesses (Figure 4). Figure 4: Preterminated Solutions Cabling migration from 10G to 40G to 100G in an MPO-based system is a simple and easy deployment. Starting with 10G, a 12-fiber MPO cable is deployed between the two 10G switches. Modules are used at the end to transition from the 12-fiber MPO to LC duplex. This enables connectivity into the switch (Figure 5). 10G Over 12-fiber MPO Cabling Module MPO Cable MPO MPO Module 10G Switch 10G Switch Figure 5: 10G Over 12-Fiber MPO Cabling ZA-3776 When the switches migrate to 40G, the module is removed and is replaced by a 12-fiber MPO adapter panel. The use of a 12-fiber MPO jumper is needed to establish connectivity between the switches (Figure 6). 40G Over 12-fiber MPO Cabling MPO Cable 40G Switch 40G Switch Figure 6: 40G Over 12-Fiber MPO Cabling ZA-3777 LAN-1379-EN Page 5
6 Future 100G networks will require a 24-fiber MPO jumper to establish a link. Systems that use 12-fiber MPO backbone will need a 24-fiber to two 12-fiber MPO jumpers (Figure 7). 100G Over 12-fiber MPO Cabling MPO Cable 24F 24F 100G Switch 100G Switch Figure 7: 100G Over 12-Fiber MPO Cabling ZA-3778 Multiple loss performance tiers are available for MPO connectivity solutions. Just as connector loss must be considered with current, deployed applications such as 10G Ethernet, insertion loss is also a critical factor for 40/100G Ethernet applications. For example, IEEE 802.3ae defines a maximum distance of 300 m on OM3 multimode fiber for 10G Ethernet (10GBASE-SR). To achieve this distance, a total link loss of 2.6 db is needed with a maximum total connector loss of 1.5 db. As the total connector loss in the channel increases above 1.5 db, the supportable distance decreases and channel loss increases. When extended distances or multiple connector matings are required, low-loss performance modules and connectivity may be necessary. Likewise, with the total connector loss for 40/100G Ethernet, similar considerations must be evaluated. MPO connector matings with maximum connector loss specifications of 0.5 db and 0.35 db provide alternatives for variations in the infrastructure design as the physical connectivity and channel distance are taken into account to make a final selection in product performance. Table 2 summarizes the IEEE G/40G/100G standards for distance and link loss. Table 2. IEEE Link-loss migration from 10G to 40G to 100G in an MPO-based system is a simple and easy deployment. In this example, two 50 m links are connected from the MDA to the HDA. 10G switches are deployed, and the link loss is calculated from the HDA to the MDA and from the HDA to HDA. The losses are then compared to Table 2. In this case, both links are below the 2.6 db max for 10G (Figure 8). LAN-1379-EN Page 6
7 10G Link Loss Over 12-fiber MPO Cabling 50 m OM3 50 m OM3 MPO HDA MDA MDA HDA = Fibers Lit 10G Switch 10G Switch Module Module Module Module db 50 m Cable 50 m Cable db Total (db) HDA-HDA HDA-MDA Total (db) Link Ck Figure 8: 10G Link Loss Over 12-fiber MPO Cabling As the network migrates to 40G, the link-loss requirements get tighter. In this example, two 50 m links are connected from the MDA to the HDA. 40G switches are deployed, and the link loss is calculated from the HDA to the MDA and from the HDA to HDA. The losses are then compared to Table 2. In this case, both links are below the 1.9 db max for 40G on OM3 fiber (Figure 9). 40G Link Loss Over 12-fiber MPO Cabling ZA m OM3 50 m OM3 HDA MDA MDA HDA = Fibers Lit 40G Switch 40G Switch db 50 m Cable 50 m Cable db Total (db) HDA-HDA HDA-MDA Figure 9: 40G Link Loss Over 12-fiber MPO Cabling Total (db) Link Ck ZA-3774 LAN-1379-EN Page 7
8 As the network migrates to 100G, the link-loss requirements are the same as 40G. In this scenario, two 50 m links are connected from the MDA to the HDA. 100G switches are deployed, and the link loss is calculated from the HDA to the MDA and from the HDA to HDA. The losses are then compared to Table 2. In this case, both links are below the 1.9 db max for 100G on OM3 fiber (Figure 10). 100G Link Loss Over 12-fiber MPO Cabling 50 m OM3 50 m OM3 24F HDA MDA MDA HDA 24F = Fibers Lit 100G Switch 100G Switch db 50 m Cable 50 m Cable db Total (db) HDA-HDA HDA-MDA Figure 10: 100G Link Loss Over 12-fiber MPO Cabling Total (db) Link Ck Preparing for the Future ZA-3775 To best meet the needs of the future, MPO-based connectivity utilizing OM3 or OM4 fiber is the ideal solution in the data center. With inherent modularity and optimization for a flexible, TIA-942-compliant structured installation, MPO-based optical fiber systems can be installed for use in today s applications, while providing an easy migration path to future higher-speed technologies such as 40/100G Ethernet. Corning Cable Systems LLC PO Box 489 Hickory, NC USA FAX: International: Corning Cable Systems reserves the right to improve, enhance, and modify the features and specifications of Corning Cable Systems products without prior notification. LANscape and Pretium are registered trademarks of Corning Cable Systems Brands, Inc. All other trademarks are the properties of their respective owners. Corning Cable Systems is ISO 9001 certified Corning Cable Systems. All rights reserved. Published in the USA. LAN-1379-EN / March 2012 LAN-1379-EN Litcode-EN Page 82
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center Doug Coleman, Manager, Technology & Standards, Corning Cable Systems Optical connectivity with OM3/OM4 laser-optimized
Corning Cable Systems Optical Cabling Solutions for Brocade
Corning Cable Systems Optical Cabling Solutions for Brocade Building high-density, high-port-count, structured cabling solutions to scale storage area networks to thousands of ports Contents Executive
Zone Distribution in the Data Center
Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling
Migration Strategy for 40G and 100G Ethernet over Multimode Fiber
Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer [email protected] Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards Optical Fiber
Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure
Data Center Optimization: Component Choice and Innovative Design Combine to Allow the Creation of an Enabling Infrastructure Data Center Spaces Data Center Spaces as Defined by the TIA 942 Standard Source:
The Need for Low-Loss Multifiber Connectivity
WP_LowLoss_D_B 10/13/14 2:08 PM Page 2 The Need for Low-Loss Multifiber Connectivity In Today s Data Center Optical insertion loss budgets are now one of the top concerns among data center managers, especially
Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices
Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices Robert Reid (Panduit) Frank Yang (CommScope, Inc) 1 The Presenters Robert Reid Sr. Product Development Manager at Panduit Frank Yang Marketing
TIA Releases Guidelines for Maintaining Polarity Using Array Connectors
Corning Cable Systems TIA Releases Guidelines for Maintaining Polarity Using Array Connectors What is new? ANSI/TIA-568-B.1-7-2006 Commercial Building Telecommunications Cabling Standard, Part 1 General
Optimizing Infrastructure Support For Storage Area Networks
Optimizing Infrastructure Support For Storage Area Networks December 2008 Optimizing infrastructure support for Storage Area Networks Mission critical IT systems increasingly rely on the ability to handle
How To Make A Data Center More Efficient
Data Center: Technology Drivers Infrastructure Trends 40G / 100G Migration Maurice F. Zetena III Vice President Leviton Technology Data Center Group Leviton Network Solutions Technology Drivers Convergence
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer [email protected] Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards 40G & 100G
Corning Cable Systems Optical Cabling Solutions for Brocade
Corning Cable Systems Optical Cabling Solutions for Brocade Building high-density, high-port-count, structured cabling solutions to scale Storage Area Networks (SANs) to thousands of ports. CONTENTS Executive
Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram
Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram www.psiberdata.com Agenda Market Market Trend and Trend business and and business case for case higher
Obsolete Fiber Technology? Not in my Data Center!
Obsolete Fiber Technology? Not in my Data Center! White Paper October 2011 Author: James Young Technical Director, Asia Pacific www.commscope.com Do you remember when people used to say fiber optics are
Enterprise Networks EMEA. Core Products FOR DATA CENTRES
Enterprise Networks EMEA Core Products FOR DATA CENTRES EMEA Data Centre Core Products 1 Data Centres GET IT RIGHT, Right Now. Corning Cable Systems offers tens of thousands of fibre optic products for
Upgrading Path to High Speed Fiber Optic Networks
SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method
Optical Trends in the Data Center. Doug Coleman Manager, Technology & Standards Distinguished Associate Corning Cable Systems
Optical Trends in the Data Center Doug Coleman Manager, Technology & Standards Distinguished Associate Corning Cable Systems Data Center Environment Data Center Environment Higher speeds Higher density
Plug & Play Gigabit Ethernet Media Conversion Module. Application Note
Plug & Play Gigabit Ethernet Media Conversion Module Application Note The Plug & Play Universal Systems Media Converter Module offers the best of both worlds easy fiber optic scalability and future proofing
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration Bill Charuk, SR Product Manager, Data Center Solutions Introduction With the advent of data centers in communication infrastructure, various
Fiber in the Data Center
Fiber in the Data Center A NetClear White Paper Rudy Montgelas Senior Fiber Product Manager Ortronics/Legrand Lisa Huff Data Center Applications Engineer Berk-Tek, A Nexans Company March 2008 A New Generation
AMP NETCONNECT Data Center Cabling Solutions
AMP NETCONNECT Data Center Cabling Solutions Modern business and administrative environments require today more and more sophisticated IT services, what leads to an increasing demand for data provision
The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper
The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper Optical Fiber WP1150 Issued: October 2007 Supersedes: October 2006 ISO 9001 Registered
www.commscope.com Data Center Topology Guide
www.commscope.com Data Center Topology Guide Data Center Areas 1 Network Operations Center (NOC) The network operations center or NOC is the location where control of all data center networking, server
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
Plug & Play Universal Systems
Plug & Play Universal Systems A LANscape Pretium Plug & Play Universal Systems for Data Centers and Storage Area Networks (SANs) Corning Plug & Play universal systems create a fiber optic tip-to-tip solution
Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network
Optical Fiber Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network Carl Roberts [email protected] Cabling considerations for DCs and
Overcoming OM3 Performance Challenges
White Paper Overcoming OM3 Performance Challenges First Third-Party Test of Pre-terminated OM3 MTP System Demonstrates Flexibility in 10G Network Designs Gary Bernstein, RCDD Director of Product Management
Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com
Design Guide SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution www.commscope.com Contents Introduction 3 How Does a TAP Work? 3 The TAP Ecosystem 4 InstaPATCH 360 TAP Module Family 4 InstaPATCH
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations White Paper www.commscope.com Contents Introduction 3 CommScope solution overview 3 InstaPATCH
HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks
HIGHSPEED ETHERNET THE NEED FOR SPEED Jim Duran, Product Manager - Americas WHITE PAPER Molex Premise Networks EXECUTIVE SUMMARY Over the years structured cabling systems have evolved significantly. This
Cable Assemblies. Features and Benefits
Features and Benefits Flame-retardant jacket Rugged and durable Superior Performance Testing Every termination is tested to ensure the highest in network performance State-Of-The-Art Manufacturing Processes
Pretium EDGE HD Solutions
Pretium EDGE HD Solutions for Enterprise Data Centers and Storage Area Networks Corning Cable Systems Pretium EDGE HD Solutions create a fiber optic tip-to-tip solution for Data Centers and Storage Area
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect Introduction The primary
Network Topologies and Distances
Network Topologies and Distances Chris Di Minico MC Communications [email protected] 1 Presentation objectives Considerations for 802.3ba fiber link distance objectives 2 HSSG Objectives Support full-duplex
Patch Cords for Data Center Applications
Applications General use of patch cords includes the interconnection of the optical fiber cable plant with opto-electronic equipment, and/or the cross-connection between cable plant segments. Pigtails
TIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8
Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,
12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)
1 1 9.41 115 0 Patch cables are used 143 12 Fibre MTP Jumper, MTP (non-pinned) to Patch cables are used for non -permanent connections between patch panels, transmission equipment, etc. Pre -assembled
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew [email protected] J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards
CISCO 10GBASE X2 MODULES
DATA SHEET CISCO 10GBASE X2 MODULES Figure 1. Cisco 10GBASE X2 and Xenpak Module PRODUCT OVERVIEW The Cisco 10GBASE X2 modules (Figure 1) offers customers a wide variety of 10 Gigabit Ethernet connectivity
Enterprise Networks EMEA. Core Products FOR DATA CENTRES
Enterprise Networks EMEA Core Products FOR DATA CENTRES EMEA Data Centre Core Products 1 Data Centres GET IT RIGHT, Right Now. Corning Cable Systems offers tens of thousands of fibre optic products for
Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc [email protected]
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc [email protected] J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company
Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs
Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial
Telecommunications Infrastructure Standard for Data Centers 802.3 Tutorial Prepared by: Jonathan Jew - J&M Consultants and Chris DiMinico - MC Communications - Co-chairs TR42.1.1 TR42: Data Center Standard
The ABC of Direct Attach Cables
The ABC of Direct Attach Cables Thomas Ko, RCDD Product Manager TE Connectivity Network Speed and Technology 10/40/100 Gbps the transition is occurring right now What are Customers Saying about their 10/40/100
Your Network. Our Connection. 10 Gigabit Ethernet
Your Network. Our Connection. 10 Gigabit Ethernet t Agenda Why 10G? Applicable 10GbE Standards Distance Restrictions Copper Fiber Fiber Repeaters 3R s Fiber Module Types Form Factors of 10G modules Future
Security & Surveillance Cabling Systems
Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.
10G and Beyond in the Data Center with OM3 Fiber
10G and Beyond in the Data Center with OM3 Fiber Doug Coleman, Manager Technology and Standards [email protected] Overview Optical Trends in Data Center Networks The time is NOW for 10G optical
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G FIBER POLARITY: 10G and 40/100G OPTIONS Why is this significant in the data center? Data centers will be one of the first places where we
Uncompromising Integrity. Making 100Gb/s deployments as easy as 10Gb/s
Uncompromising Integrity Making 100Gb/s deployments as easy as 10Gb/s Supporting Data Rates up to 100Gb/s Mellanox 100Gb/s LinkX cables and transceivers make 100Gb/s deployments as easy as 10Gb/s. A wide
Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network
Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network WP4270 Issued: June 2011 Authors: Carl Roberts and Merrion Edwards Introduction
INTRODUCTION TO MEDIA CONVERSION
WHITE PAPER INTRODUCTION TO MEDIA CONVERSION Table of Contents Introduction 1 What is a Media Converter? 1 Advantages of Media Conversion Technology 1 Benefits of Fiber Optic Cabling 2 Types of Media Converters
Keyed LC Connector Solution
features and benefits Eight color-coded mechanical key positions Meets TIA/EIA-568-B requirements Keyed connectors and adapters Full solution availability Keyed LC Connectors Photo LAN758 SPECIFICATION
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER
ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect Introduction
MIGRATING TO A 40 GBPS DATA CENTER
White Paper MIGRATING TO A 40 GBPS DATA CENTER Juniper QSFP+ LX4 technology removes cabling cost barriers for migrating from 10 Gbps to in data center networks Copyright 2014, Juniper Networks, Inc. 1
40 Gigabit Ethernet and 100 Gigabit Ethernet Technology Overview
40 Gigabit Ethernet and 100 Gigabit Ethernet Technology Overview June 2010 Authors: John D Ambrosia, Force10 Networks David Law, 3COM Mark Nowell, Cisco Systems 1. This work represents the opinions of
HP Multimode OM3 LC/LC Optical Cables Overview. Models HP 50 m Multimode OM3 LC/LC Optical Cable
Overview Models HP 0.5 m Multimode OM3 LC/LC Optical Cable HP 1 m Multimode OM3 LC/LC Optical Cable HP 2 m Multimode OM3 LC/LC Optical Cable HP 5 m Multimode OM3 LC/LC Optical Cable HP 15 m Multimode OM3
DATA CENTER APPLICATIONS REFERENCE GUIDE Networking & Storage
DATA CENTER APPLICATIONS REFERENCE GUIDE Scope This technical paper provides an overview about the most dominant networking and storage applications in modern data centers. Additionally, it offers information
Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications
Data Sheet Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output
Unified Storage Networking
Unified Storage Networking Dennis Martin President Demartek Demartek Company Overview Industry analysis with on-site test lab Lab includes servers, networking and storage infrastructure Fibre Channel:
40/100 Gigabit Ethernet: The Foundation of Virtualized Data Center and Campus Networks
40/100 Gigabit Ethernet: The Foundation of Virtualized Data Center and Campus Networks Yinglin (Frank) Yang, CommScope, Inc Gautam Chanda, Cisco Systems White Paper www.commscope.com Contents Contents
Enabling 21 st Century Connectivity
Enabling 21 st Century Connectivity First MXC Adopters meeting March 11, 2014 MXC is a trademark of US Conec Presenters Victor Krutul Director Marketing, Intel Corp Mike Hughes Director, Product Management,
HUBER+SUHNER AG Phil Ward
The challenges of building and maintaining Fiber Optic connectivity in the modern Data Center HUBER+SUHNER AG Phil Ward What is our common Global Objective? To connect different types of equipment together
How To Properly Maintain A Fiber Optic Infrastructure
How To Properly Maintain A Fiber Optic Infrastructure Best Practices to Minimize Damage and Failures in Fiber Optic Infrastructures White Paper Rodney Casteel, RCDD, NTS, OSP, Technical Manager, CommScope
DATA CENTER NETWORK INFRASTRUCTURE. Cable and Connectivity for the Most Demanding Networks. BerkTekLevitonTechnologies.com
DATA CENTER NETWORK INFRASTRUCTURE Cable and Connectivity for the Most Demanding Networks Customer-focused, technology-driven, quality-assured for an unparalleled RETURN ON infrastructure investment DATA
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009 Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made
Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications
3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition
The 8-Fiber Solution for Today s Data Center
The 8-Fiber Solution for Today s Data Center Bill Charuk, SR Product Manager, Data Center Solutions Introduction Data center infrastructure is constantly evolving. Fiber optic installations have used the
Gigabit Passive Optical Networks
White Paper Gigabit Passive Optical Networks Passive Optical LAN Solutions (POLS) Theory, Design, and Installation Considerations Sean McCloud, RCDD Senior Applications Engineer, Leviton Network Solutions
The Three Principles of Data Center Infrastructure Design WHITE PAPER
The Three Principles of Data Center Infrastructure Design WHITE PAPER The Three Principles of Data Center Infrastructure Design Understand These Three Principles and You ll: Lower your total cost of ownership
over Ethernet (FCoE) Dennis Martin President, Demartek
A Practical Guide to Fibre Channel over Ethernet (FCoE) Dennis Martin President, Demartek Demartek Company Overview Industry analysis with on-site test lab Lab includes servers, networking and storage
Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...
LANscape Solutions Recommended Fiber Optic Test Guidelines Table of Contents 1. Introduction...1 2. Why Test?...1 3. Tier 1 and Tier 2 Testing...2 4. Encircled Flux...3 5. Link-Loss Budgets...4 6. Proper
High Speed Ethernet. Dr. Sanjay P. Ahuja, Ph.D. Professor School of Computing, UNF
High Speed Ethernet Dr. Sanjay P. Ahuja, Ph.D. Professor School of Computing, UNF Hubs and Switches Hubs and Switches Shared Medium Hub The total capacity in the shared medium hub configuration (figure
Data Center Cabling Design Trends
Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:
Structured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
Network Monitoring - Fibre TAP Modules
Network Monitoring - Fibre TAP Modules It all started with. Bend insensitive MM fibre Smaller diameter cables Cable with tighter bend radius Less space in the DC, More organised cable management Greater
Cabling & Test Considerations for 10 Gigabit Ethernet LAN
Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit
CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE
ORTRONICS : UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE Cindy Montstream, RCDD/NTS, EE, CPLP Director of elearning and Standards DATA COMMUNICATIONS Legrand, North America
Fiber Selection and Standards Guide for Premises Networks
Fiber Selection and Standards Guide for Premises Networks WP1160 Issued: November 2013 Supersedes: November 2012 Authors: Carl Roberts and Dr. Russell Ellis Introduction There are several main types of
Cable Assemblies. Pretium EDGE Reverse Polarity Uniboots Photo LAN2217-2218. ST Compatible Ultra PC 12-Fiber Cable Assembly Photo LAN2784
Corning offers the most complete line of connectors and factory-terminated cables, from single-fiber jumpers to high-fiber-count assemblies. As the industry s leading supplier of cable assemblies, Corning
Top of Rack: An Analysis of a Cabling Architecture in the Data Center
SYSTIMAX Solutions Top of Rack: An Analysis of a Cabling Architecture in the Data Center White paper Matthew Baldassano, Data Center Business Unit CommScope, Inc, June 2010 www.commscope.com Contents I.
Cisco SFP Optics for Gigabit Ethernet Applications
Cisco SFP Optics for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output device that plugs into a Gigabit
40 and 100 Gigabit Ethernet Overview
40 and 100 Gigabit Ethernet Overview Abstract: This paper takes a look at the main forces that are driving Ethernet bandwidth upwards. It looks at the standards and architectural practices adopted by the
Upgrading Data Center Network Architecture to 10 Gigabit Ethernet
Intel IT IT Best Practices Data Centers January 2011 Upgrading Data Center Network Architecture to 10 Gigabit Ethernet Executive Overview Upgrading our network architecture will optimize our data center
Oracle Virtual Networking Overview and Frequently Asked Questions March 26, 2013
Oracle Virtual Networking Overview and Frequently Asked Questions March 26, 2013 Overview Oracle Virtual Networking revolutionizes data center economics by creating an agile, highly efficient infrastructure
How To Get A Better Signal From A Fiber To A Coax Cable
Gigabit Transmission What s the Limit? Fanny Mlinarsky Page 1 What s the Limit? Speed Faster higher frequency higher attenuation less headroom Distance Longer higher attenuation more jitter less headroom
Implementing Fast Ethernet
Implementing Fast Ethernet R The Next Generation of Ethernet Fast Ethernet (also known as IEEE 802.3u or 100BASE-T) is quickly becoming the successor to Ethernet as the network topology of choice. Fast
Preparing Infrastructure for 10 Gigabit Ethernet Applications
Preparing Infrastructure for 10 Gigabit Ethernet Applications Christopher T. Di Minico, Cable Design Technologies (CDT) Corporation, Bruce Tolley, Cisco Systems Background The Internet will continue to
Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD
Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,
Sustaining the Cloud with a Faster, Greener and Uptime-Optimized Data Center
Sustaining the Cloud with a Faster, Greener and Uptime-Optimized Data Center WP6046 Issued: June 2012 Introduction Our world is in a rapid state of change in terms of the way we communicate and are connected
Data Centre Design ready for your future
Data Centre Design ready for your future Introduction to Data Centres What is a Data Centre? The definition of a Data Centre according to TIA-942 is a building or portion of a building whose primary function
Parallel SMF (PSM) in the Data Centre
1 Parallel SMF (PSM) in the Data Centre - End User Survey - Alan Flatman, Independent + Brad Booth, Independent 2 Contributors A big thank you to the following people who provided introductions to end
100BASE-SX Fast Ethernet:
100BASE-SX Fast Ethernet: A Cost Effective Migration Path for Fiber in the Horizontal Prepared by the Fiber Optics LAN Section of the Telecommunications Industry Association February 2000 2000 TIA Fiber