PRE-LEASE SURVEY OF THE ENGINEERING SERVICES. XXXX London

Size: px
Start display at page:

Download "PRE-LEASE SURVEY OF THE ENGINEERING SERVICES. XXXX London"

Transcription

1 PRE-LEASE SURVEY OF THE ENGINEERING SERVICES AT London

2 Client: Clients Representative: For the Attention of: Telephone N o Site Address: London Report prepared by: Contact Name: FHP Engineering Services Solutions, Woburn Place, London, WC1H 0JR Jarrod Griffiths Direct Dial N o Date of Report: July 2010 Report N o Checked By One Report July 2010

3 CONTENTS SECTION DESCRIPTION PAGE NOS Introduction 1/1 1/ Executive Summary 2/1 2/ Technical Findings 3/1 3/7 Appendix 1.00 Photographic Schedule Report Contents July 2010

4 SECTION 1.00 INTRODUCTION FHP Engineering Services Solutions (FHP ESS) were commissioned by on behalf of their Client to carry out a pre-lease survey of the engineering services of the 3 rd Floor,, London. It is not clear when the building was originally constructed, however we can confirm the building is currently undergoing a refurbishment. During the refurbishment it would appear a number of engineering services were replaced. The property is set across basement, ground and three upper levels. The building currently has one Tenant on the 1 st floor with the 2 nd and 3 rd floors vacant, the ground floor includes the main entrance and common reception. The Client is considering occupation of the 3 rd floor with the view of 15 year lease term with a 5 and 10 year break option. We understand the floor area of the 3 rd floor is approximately 696m2 respectively. The main items of plant and equipment inspected comprise: Heating & Cooling Installations and Distribution System Ventilation Services Electrical Services Fire Safety Systems Public Health Installations Domestic Water Services Lift Installations The survey was carried out on a visual basis and did not involve an intrusive examination of the plant and various systems within the property. No plant testing or removal of covers or inspection hatches took place unless specifically indicated within the report. While the plant and equipment was viewed in operation where possible, it is common for plant to have historical operating problems, which are not apparent during a visual study Report 1/1 July 2010

5 This Report indicates the general condition of the plant and standard of the installation however, it would be necessary to carry out a more detailed validation study to determine whether all of the components of the systems are operational. The report does however; indicate if it is known that components have failed. If there are areas where further examination of the building or its services would be required or recommended to further identify problems in detail, then the need for any further investigation is detailed within the report. This Survey did not include any examination of deleterious materials within the property and the findings summarised within this Report do not allow for the treatment of such materials to affect any recommendations. Under the Energy Performance in Buildings Directive an Energy Performance Certificate (EPC) is required under Government legislation for a building of more than 50m 2 which is subject to sale or lease after 1st July A copy of the certificate was not provided at the time of the survey and the full report should be requested from the Vendor. In addition to this, there did not appear to be any evidence of an Air Conditioning Inspection (ACI) in accordance with CIBSE TM44. The survey was carried out on Tuesday 20 th July 2010 when the weather was bright and dry Report 1/2 July 2010

6 SECTION 2.00 EXECUTIVE SUMMARY This Executive Summary section is intended as a broad overview only and should be read in conjunction with the remaining sections of the Report to understand the full implications of the findings. The central plant such as the boilers, chillers and air handling units (AHU s) were installed in The chillers have subsequently been decommissioned and replaced with a variable refrigerant flow (VRF) system installed in late With this in mind, the service charge expenditure taking into account the age and condition of the services of large items including the boilers and ventilation plant will likely require replacing within the latter part of the term of the proposed lease. It was noted a number of redundant chiller plant located in basement plant room and roof area was still in situ. We would normally expect the plant and equipment to have been removed and recommend that the landlord is asked for further clarification on removal. The office area of the building inspected for the Client (prospective Tenant) included the 3 rd floor and additionally landlord core areas, roof areas and services plantrooms were inspected. The office and toilet ventilation plant was operational at the time of the survey and was found to be in good condition. The newly installed VRF system was not witness in operation at the time of survey due to refurbishment works. Given the very close proximity of the residential accommodation to the VRF system roof equipment it is recommended that the landlord is asked to confirm that there are no current issues or restrictions on use of the VRF systems. It would appear from information provided the design parameters (heating and cooling loads) for the VRF installation are insufficient in accordance to the recommendations stated in the British Council For Offices (BCO) guidelines. This should be raised with the designers for further clarification as it could mean the system capacity is inadequate. The operation and maintenance information indicates an indoor design temperature of 27.0 C which is considered to be high Report 2/1 July 2010

7 Limited maintenance and statutory document was available at the time of the survey. A maintenance contractor is currently in place and the incumbent maintenance contractor is Polytech Building Services. We noted numerous redundant plant in the form of outdoor condenser units dedicated to the previous 2 nd and 3 rd floor Tenants which have been left in situ. We would normally expect the plant and equipment to have been removed under the dilapidations obligations of the previous Tenant. We strongly recommend these items are identified within the lease so that the Client considering taking the space is not liable for removal of this equipment at the end of the proposed agreement. There is some available space (subject to confirmation from the landlord) on the roof area for condensers should the Tenant wish to install supplementary cooling for a comms room etc. The office lighting was found to be to a good standard with LG3 indirect 600x600mm recessed modular florescent fittings commonly used. We believe the lift was modernised in 2000 and understand that the lift car will undergo further modernisation with in the refurbishment works currently taking place. In general the lift was found to be of a good standard. TABLE OF COSTS TABLE 1 Item Description Cost 1.0 LTHW Boilers Replace due to age (Years 8-10) 110, Toilet and Office Ventilation Plant Replace due to age (Years 8-10) 40, Lifts modernise in Years 8-10 due to age. 55,000 TOTALS 205,000 All costs detailed above are as at 2010, are for budget purposes and exclude taxes Report 2/2 July 2010

8 SECTION 3.00 TECHNICAL FINDINGS 3.01 Heating Ventilation and Air Conditioning.01 Ventilation The office areas are ventilated by air handling units (AHUs) located at the basement level and noted to be manufactured by VES Andover. The supply AHU unit comprises a re-heat coil, fan and motor. The extract AHU unit comprises a fan and motor only. Fresh tempered air is delivered to each floor via a main vertical duct which branches at each floor level. Air is then ducted to the suction section of the fan coil unit (FCU). The air is then drawn into the FCU and locally tempered again before being delivered in to the office space. The AHUs were noted to be operational at the time of the survey and considering the age, replacement may be required in the latter part of the lease term (Year 8-10) due to age..02 Cooling Comfort cooling to the office areas is supplied by a variable refrigerant flow (VRF) system. The system consists of 6 No. outdoor heat pumps located on the roof level and a number of indoor FCU units located above the suspended ceiling void. Each Tenanted floor is supplied with its own VRF system. The 2 No. outdoor heat pumps condenser units for 3 rd floor provide either chilled or heating to the 19 No. indoor FCU units which modulate to the desired temperature of each individual unit and delivers tempered air via swirl diffusers. The system manufactured by LG is controlled via wall mounted controllers and commissioned in October Report 3/1 July 2010

9 From the information provided it would appear the design parameters for the VRF installation are below that recommended in the British Council For Offices (BCO) guidelines. We recommend the Vendor provides some further clarification on the design intent for the 3 rd floor as it would appear the design is not adequate..03 Heating Low temperature hot water (LTHW) is generated from two natural gas forced draught boilers, manufactured by Potterton Commercial and each rated at 250kW. The boilers are located in a basement plant room and date from The LTHW is circulated to the AHUs and wall mounted radiators located in the staircase via a series of circulation pumps. Associated heating plant includes pressurisation unit, expansion vessel and chemical dosing pot. We noted that at the time of survey boiler number one was isolated. The building manager informed this was due to a reduced heating demand in the summer months. The LTHW plant and equipment appeared to be in a reasonable condition. Replacement of the boiler plant may be required in Year 8 to 10 due to age as the installed plant would have reached its economical life expectancy..04 Fan Coil Units The fan coil unit installation to the 3 rd floor comprises concealed ceiling mounted units. Each unit is equipped with a fresh air supply, fan motor, filter, associated controls and the facility to provide heating and cooling. The building manager confirmed the 1 st, 2 nd and 3 rd floor units were replaced during the recent refurbishment works Report 3/2 July 2010

10 The FCU s modulate to the required air temperature using refrigerant medium via an outdoor condenser unit and heat pump. Fresh air is drawn through a filter section then dispersed through the unit to be delivered to the floor via a ceiling mounted grille. Control of the FCU s is via 2 No. localised controllers on each floor. Commissioning certificate was noted on site dated October 2009 and no defects were recorded..05 Miscellaneous Ventilation Toilets are supplied with an extract system only located on the roof area. Ventilation to the boiler room is achieved via a supply fan located at high level within the boiler plant room. The equipment was noted to be operational during the survey. The condition of the external toilet ventilation plant is satisfactory..06 Incoming Gas Supply The main incoming gas supply enters the building at basement level where the gas supply is metered and transferred to the heating plant only. There does not appear to be a gas line schematic located at the main meter and the room appears to be dirty. It is required to place a gas line schematic diagram at the point of entry Domestic Water Services.01 Domestic Cold Water Mains cold water enters the building at basement level and rises to feed a water storage tank located on the roof. The storage tank supplies water under gravity to sanitary appliances, expansion units, closed loop make-up systems and future Tenant kitchenettes. There is no evidence to indicate when the system was last cleaned and chlorinated; in addition to this we did not view any water treatment records Report 3/3 July 2010

11 In general the domestic cold water systems appear to be in fair condition with no major defects noted..02 Domestic Hot Water Domestic hot water (DHW) is generated by a large calorifier located on each floor and is heated via 2 No. electrical elements. The water is circulated around the various DHW outlets via a two-pipe flow and return method which is pumped by a Grundfos pump. In general the DHW systems appear to be in fair condition with no major defects noted..03 Sanitary ware Toilet facilities are located on each tenanted floor and consist of male, female and disabled toilet. The male toilet is fitted with 2 No. W/C, 2 No. wash hand basin and 2 No. urinals and the female toilets have 2No. W/C and 2 No. wash hand basin. The disabled toilet is fitted with a W/C and a wash hand basin. It was noted there are no shower facilities on site. The installation was renewed under the current refurbishment works and appears in good condition Electrical Services 3.01 Electrical Supply and Distribution The electricity supply enters the property and terminates into the mains distribution centre located in the first floor electrical riser cupboard. The supplies then distribute to the various sub main distribution boards and plant equipment located throughout the property. We believe each tenanted power supply is metered by the utility supplier and terminates into its own distribution board Report 3/4 July 2010

12 The main and sub main cabling is generally distributed in steel wired armoured (SWA) cables mounted on tray or clipped directly to the building fabric. The system appeared to be in reasonable condition commensurate with age. There is some evidence that test and inspection in accordance with BS7671 is current although we have not seen any supporting documentation. It was noted that a number of low voltage (LV) distribution switches and fuse boxes contained asbestos. Although there was evidence that an asbestos survey had been carried out no asbestos register provided at the time of the inspection Lighting and Emergency Lighting Lighting to the 3 rd floor office area was renewed as part of the recent refurbishment works and is provided by LG3 type 600 x 600 mm recessed fluorescent luminaires and recessed down lighting. The operation of the fittings is achieved by motion sensors and light switches can be found at either entrance of the floor which are used in conjunction with the motion sensors. The lighting installation appeared to be to a good standard. Decorative lighting is generally used in common areas, reception and toilets. Plantroom lighting is provided by linear fluorescent batten fittings. Emergency lighting is provided within select luminaires across the 3 rd floor utilising separate inverters and battery packs Small Power and Data A small power distribution board with spare ways is provided in the electrical riser on each floor. It should be noted the boards are metered locally and these are understood to be supply authority meters and not landlord check meters. The 3 rd floor distribution board is a Merlin Gerin 3 phase type having 72 ways with 28 in use is rated 125 Ampere 3 phase Report 3/5 July 2010

13 A perimeter mounted skirting trunking system is in use for the small power as well as 7 No. floor boxes which are served via a shallow cable duct recessed into the floor screed. There is no raised floor. Data risers are provided for communications cabling for Tenant use. The small power installations and provisions to the 3 rd floor appear to be adequate for typical office utilisation with no major defects noted. A protective door cover was missing from the distribution board located on the 3 rd floor. We recommend the cover is replaced. Please note, the door cover will not open due to door frame so will remain with very awkward access unless board is lowered Fire Safety Systems The property is monitored using a fully automated addressable system as manufactured by Morley Fire Systems. The system comprises smoke/heat detectors with integrated sounders and manual call points. We were advised the fire alarm system along with the field devices and cabling was replaced in the recent refurbishment works. In general the fire alarm system appeared to be in good working order with no major defects noted at the time of the survey Lifts There is 1 No. electric traction top drive lift installed to the property this being manufactured by Kone. The lift is located in the main staircore of the property and travels between ground and three upper levels. The lift is maintained on a regular basis. however Lifting Operations & Lighting Equipment Regulations (LOLER) certificates were not provided at the time of survey. The lift did not appear to be fully DDA compliant. The lift appears to have been modernised in 2000 and looks to be in reasonable condition however, the lift may require some modernisation within 8 to 10 years Report 3/6 July 2010

14 3.06 Drainage The drainage system comprises vertical stacks collecting the rain water toilet and general waste. The majority of the drainage system consists of cast iron and discharges into the local sewer connection at ground and basement levels. The drainage where visible appears to be in reasonable condition Security Systems The main entrance is manned during normal working hours and admission outside normal working hours is provided by access control and intercom system installed to the main entrance with intercom door release devices located on each floor for access. A CCTV system is installed with cameras monitoring numerous locations of the property. The security systems appear to be in reasonable condition with no reportable deficiencies Lightning Protection System Information relating to a lightning protection system was not witnessed. We recommend further clarification is sought from the landlord in respect of this deficit Report 3/7 July 2010

15 APPENDIX 1.00 PHOTOGRAPHIC SURVEY 1. Gas fired boilers in basement. 2. AHU s in basement Report Appendix 1/1 July 2010

16 3. 3 rd floor plan. 4. Typical roof layout Report Appendix 1/2 July 2010

17 5. Asbestos switches and fuse boxes located 1 st floor switch room Report Appendix 1/3 July 2010

CONDUIT MAYFAIR READY FOR OCCUPATION SPRING 2014 GLINSMANWELLER.CO.UK A DEVELOPMENT BY LONDON PROPERTY PARTNERSHIP LTD

CONDUIT MAYFAIR READY FOR OCCUPATION SPRING 2014 GLINSMANWELLER.CO.UK A DEVELOPMENT BY LONDON PROPERTY PARTNERSHIP LTD 12 CONDUIT S T R E E T MAYFAIR READY FOR OCCUPATION SPRING 2014 020 7495 2728 GLINSMANWELLER.CO.UK A DEVELOPMENT BY LONDON PROPERTY PARTNERSHIP LTD 12 CONDUIT STREET The entire building is undergoing a

More information

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) 1. In addition to the information scheduled below, the pre-tender designer is responsible for: (i)

More information

B-1 Buildings & Service Maintenance

B-1 Buildings & Service Maintenance B-1 Buildings & Service Maintenance B-1 Buildings & Service Maintenance SAFETY, HEALTH AND ENVIRONMENTAL POLICY: B-1 DATE OF ISSUE: AUGUST 1994. BUILDINGS AND SERVICES MAINTENANCE 1. Introduction It is

More information

COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23

COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23 COMMERCIAL REPORT / STOCK CONDITION SURVEY For Sydenham Hill Estate Sydenham Hill London SE 23 Submission Prepared by Gas Advisory Services Limited Date: 4 th June 2013 Gas Advisory Services Limited Phoenix

More information

50 St Mary Axe London EC3

50 St Mary Axe London EC3 50 St Mary Axe London EC3 Letting specification 1.Structure and Envelope The main superstructure comprises of a braced steel fame (app 7m span / 90min fire rated) and the elevations are formed from a series

More information

Commercial Property Tenants Your rights and responsibilities

Commercial Property Tenants Your rights and responsibilities Commercial Property Tenants Your rights and responsibilities nihe.gov.uk 03448 920 900 This booklet is intended to help you understand what being a tenant means and give information and guidance on the

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building. MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating

More information

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary January 2013 TABLE OF CONTENTS INTRODUCTION... 3 GENERAL RECOMMENDATIONS... 3 Communication with customers in the field of environmental sustainability...

More information

Building Services Engineering Technician

Building Services Engineering Technician Building Services Engineering Technician A competent Building Services Engineering Technician is expected to be able to demonstrate the following skills and competences: Systems design in the building

More information

RESPONSIBILITY FOR REPAIRS AND MAINTENANCE FAIR FUNDING: April 2002

RESPONSIBILITY FOR REPAIRS AND MAINTENANCE FAIR FUNDING: April 2002 RESPONSIBILITY FOR REPAIRS AND MAINTENANCE FAIR FUNDING: April 2002 INDEX New Build Flat and Pitched Roofs Rainwater Goods Porches to Existing Buildings / Covered Links etc, Between Buildings Floors /

More information

Turnkey Projects, Conversions, Restorations & Property Management. Marsalforn - Gozo APARTMENT FINISHING EXCLUSIVE PACKAGE

Turnkey Projects, Conversions, Restorations & Property Management. Marsalforn - Gozo APARTMENT FINISHING EXCLUSIVE PACKAGE Turnkey Projects, Conversions, Restorations & Property Management Marsalforn - Gozo APARTMENT FINISHING EXCLUSIVE PACKAGE Reg. Office: Karlu Galea Street, Victoria, Gozo Malta. T. 2155 6600 M. 9943 4391

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

LONDON BOROUGH OF HACKNEY BUILDING SERVICES ENGINEER REPORT GAS HOUSE, SPRINGFIELD PARK, HACKNEY

LONDON BOROUGH OF HACKNEY BUILDING SERVICES ENGINEER REPORT GAS HOUSE, SPRINGFIELD PARK, HACKNEY LONDON BOROUGH OF HACKNEY BUILDING SERVICES ENGINEER REPORT GAS HOUSE, SPRINGFIELD PARK, HACKNEY 10 TH JUNE 2011 London Borough of Hackney Page 1 of 6 Brief Description of the Proposed Works The existing

More information

case studies Safely applied, Environmentally creative and effective engineering solutions

case studies Safely applied, Environmentally creative and effective engineering solutions Safely applied, Environmentally creative and effective engineering solutions T: 02392 435050 @: [email protected] www.itdconsultants.co.uk case studies Churchill House Main Features: A 1.5m refurbishment

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

NYC Department of Education Building Condition Assessment Survey 2014-2015 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004

NYC Department of Education Building Condition Assessment Survey 2014-2015 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004 School: InspectionId Asset Data Inspection Type Building Assessment Survey 204-205 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 0004 Time In Last Edited 255 MECHANICAL 205-05-8 09:00AM

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

Balderton Mayfair London W1 Tenants Guide

Balderton Mayfair London W1 Tenants Guide Balderton Mayfair London W1 Tenants Guide Contents 01 Executive Summary 02 Location 03 Floor areas 03.1 Ground Floor 03.2 1st Floor 03.3 2nd 5th Floor 03.4 6th Floor 03.5 7th Floor 03.6 8th Floor 04 Space

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

Apartment and Communal Heating Solutions

Apartment and Communal Heating Solutions Apartment and Communal Heating Solutions Apartment and Communal Heating Due to the increasing requirements for more energy efficient buildings and changes to the Code for Sustainable Homes Legislation,

More information

SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request

SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

Building Condition Assessment Report

Building Condition Assessment Report Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland

Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC

More information

CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance

CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance CIBSE Guide M: Maintenance engineering and management compliance legislation and guidance Types of System/Plant Action required Frequency by Type of Fire and Smoke Fire extinguishers Discharge (not CO

More information

Restaurant & café guide

Restaurant & café guide 'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers

More information

Energy Efficiency HOSPITALITY. www.energia.ie

Energy Efficiency HOSPITALITY. www.energia.ie Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real

More information

Service Level Agreement (SLA)

Service Level Agreement (SLA) Hertford College, Oxford Service Level Agreement (SLA) For Maintenance, Risk Management, and Domestic Accommodation Services At Hertford College, its residential annexes and non- residential properties

More information

21.1 Functions, Basic Configuration, and Interfaces

21.1 Functions, Basic Configuration, and Interfaces 21 (6.2.M) Site Services Building 21.1 Functions, Basic Configuration, and Interfaces 21.1.1 Functions The primary functions performed by the site services building are to house, support, provide a suitable

More information

SPECIFICATION ARE YOU? 77 SHAFTESBURY SOHO FLOOR TO CEILING HEIGHTS GROUND FLOOR RECEPTION 3,200 MM FIRST FLOOR OFFICE 3,000 MM

SPECIFICATION ARE YOU? 77 SHAFTESBURY SOHO FLOOR TO CEILING HEIGHTS GROUND FLOOR RECEPTION 3,200 MM FIRST FLOOR OFFICE 3,000 MM 77SHAFTESBURY.COM FLOOR TO CEILING HEIGHTS GROUND FLOOR RECEPTION 3,200 MM RETAIL 3,200 MM FIRST FLOOR OFFICE 3,000 MM SECOND FLOOR OFFICE 2,600 MM THIRD FLOOR OFFICE 2,600 MM FOURTH FLOOR OFFICE 2,600

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Minimum Housing and Health Standards

Minimum Housing and Health Standards APPENDIX M.O. 57/2012 Minimum Housing and Health Standards Original version July 20, 1999. Revisions to Part lll, Housing Premises, sections 3 and 4, June 30, 2012 (all revisions are bolded and underlined).

More information

Energy Efficiency. Bars & RestauRants. www.energia.ie

Energy Efficiency. Bars & RestauRants. www.energia.ie Energy Efficiency Bars & RestauRants www.energia.ie 2 Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could

More information

Mechanical &Electrical Services Modernisation. Presentation to The Commons & Lords Management Boards 26 th November 2008

Mechanical &Electrical Services Modernisation. Presentation to The Commons & Lords Management Boards 26 th November 2008 Mechanical &Electrical Services Modernisation Presentation to The Commons & Lords Management Boards 26 th November 2008 M&E Services Modernisation Context M&E Modernisation Overview Next Steps M&E Modernisation

More information

SCHEDULE OF CONDITION

SCHEDULE OF CONDITION JOB REFERENCE: SCHEDULE OF CONDITION Islington, London. N1 XXX FOR Miss X Prepared by: INDEPENDENT CHARTERED SURVEYORS Marketing by: Islington, London. N1 XXX CONTENTS SCHEDULE OF CONDITION Elevations

More information

Heating and Hot Water Services Controls General Technical Specification

Heating and Hot Water Services Controls General Technical Specification Construction Services Heating and Hot Water Services Controls General Technical Specification Version 1.0 Environment Heating and Hot Water Services Controls General Technical Specification Contents 1.

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

HEATING, VENTILATION & AIR CONDITIONING

HEATING, VENTILATION & AIR CONDITIONING HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating

More information

75 Davies Street Mayfair

75 Davies Street Mayfair 75 Davies Street Mayfair 75 Davies Street Mayfair 75 Davies Street offers up to 32,185 sq ft of newly refurbished office space arranged over 3 floors. The building benefits from a new enlarged entrance

More information

Mechanical Systems Proposal revised

Mechanical Systems Proposal revised Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option

More information

Aurora Mall. Aurora (Denver), Colorado

Aurora Mall. Aurora (Denver), Colorado is the largest superregional mall in the city of Aurora, and it s only getting bigger and better. The mall is currently undergoing a significant interior and exterior renovation, scheduled for completion

More information

OPTIONS. for. Replacing Boiler Plant. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

OPTIONS. for. Replacing Boiler Plant. Sussex Lodge London W2 & 16 Stanhope Terrace London W2 OPTIONS for Replacing Boiler Plant Report to Tenants Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers Tel: 01932 873 653 13 JULY 2003. Replacing Boiler Plant... 1 1. Existing

More information

ridgway office ParK progress WAy, denton, manchester, m34 2gp

ridgway office ParK progress WAy, denton, manchester, m34 2gp Home ridgway House millenium House availability site PLaN gallery LocaTioN contact ridgway office ParK progress WAy, denton, manchester, m34 2gp To LeT / may sell To LeT HIgH QuALITy, AIR CondITIonEd offices

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Repairs and looking after your home

Repairs and looking after your home A guide to Repairs and looking after your home Contents Page No. Introduction 1 Information for tenants 2 Information for homeowners 3-4 Information for onsite NHS workers 5 Information for students 5

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Mechanical, Plumbing, and Fire Protection Conditions

Mechanical, Plumbing, and Fire Protection Conditions Mechanical, Plumbing, and Fire Protection Conditions Mechanical Conditions The mechanical systems within the building consist of a combination of the original 1926 systems and renovations that occurred

More information

WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1

WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 Wallet card photocopy Inspection Authority: Signature: Date: / / Submitted For: ( Owner ) Name Address City Prov Postal code Phone ( ) Fax ( ) Designer/Signature:

More information

Board Seminar Facilities. School Year 2012-2013. Submitted by Joseph L. Lisa-Director of Facilities

Board Seminar Facilities. School Year 2012-2013. Submitted by Joseph L. Lisa-Director of Facilities Board Seminar Facilities School Year 2012-2013 Submitted by Joseph L. Lisa-Director of Facilities High School Installed new fence for Pre-K activities by weight room. Installed new rails and side walks

More information

RPV - RP - RA air handling units

RPV - RP - RA air handling units APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP

More information

EXAMPLE OF A DATA CENTRE BUILD

EXAMPLE OF A DATA CENTRE BUILD EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist

More information

HomeServices Terms and Conditions

HomeServices Terms and Conditions HomeServices Terms and Conditions Contents Definitions 03 The Contract 04 Start date 04 General Exclusions 11 Payment 12 Cancellation 13 Appointments 16 Product Renewal 16 Changes to contract 16 Safety

More information

TO LET. Modern Office Suites in comprehensively refurbished building. 62 Brandon Parade Holly Walk, Leamington Spa, CV32 4JE

TO LET. Modern Office Suites in comprehensively refurbished building. 62 Brandon Parade Holly Walk, Leamington Spa, CV32 4JE TO LET Modern Office Suites in comprehensively refurbished building 62 Brandon Parade Holly Walk, Leamington Spa, CV32 4JE First floor - 1,260 sq ft (117.05 sq m) Second Floor 1,500 sq ft (139.35 sq m)

More information

250 St Georges Tce, Perth, WA (QV1)

250 St Georges Tce, Perth, WA (QV1) 250 St Georges Tce, Perth, WA (QV1) Building Profile Building Construction date 1991 Refurbishment date Owner Building Size Refurbishment Team Building Management Awards Ratings QV.1, 250 St Georges Terrace,

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency Randy Mead, C.E.M, CMVP Introduction Chilled water plant efficiency refers to the total electrical energy it

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information

TENANT AND LANDLORD REPAIR RESPONSIBILITIES

TENANT AND LANDLORD REPAIR RESPONSIBILITIES TENANT AND LANDLORD REPAIR RESPONSIBILITIES REPAIR LANDLORD TENANT Notifying Repairs Any alteration or improvement you have carried out to the property Permission required Water damage caused by push-on

More information

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units

More information

NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS

NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS NUstudenthomes Student Services Newcastle University King s Gate Newcastle upon Tyne NE1 7RU Tel 0191 208 3333 WHAT IS THE NUstudenthomes

More information

Home Inspection Report

Home Inspection Report 4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 [email protected] Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:

More information

Accurate data and the whole life costing culture. Kathryn Bourke Whole Life Ltd [email protected]

Accurate data and the whole life costing culture. Kathryn Bourke Whole Life Ltd Kathryn.bourke@wholelifeltd.co.uk Accurate data and the whole life costing culture Kathryn Bourke Whole Life Ltd [email protected] Overview Part 1 Why Bother about LCC? Standards - BS/ISO 15686-5 and UK Standardised Method

More information

1 Stratford Place 2 Oxford Street 3 New Bond Street 4 Wigmore Street 5 Grosvenor Street

1 Stratford Place 2 Oxford Street 3 New Bond Street 4 Wigmore Street 5 Grosvenor Street 4 1 2 3 5 1 Stratford Place 2 Oxford Street 3 New Bond Street 4 Wigmore Street 5 Grosvenor Street 1 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 COMMUNICATIONS LOCATION SUMMARY FLOOR

More information

Facilities Maintenance Standards rev 9-1-2015

Facilities Maintenance Standards rev 9-1-2015 Facilities Maintenance Standards rev 9-1-2015 Purpose The purpose of these standards is to outline the minimum requirements for maintaining state owned facilities and infrastructures in a manner that will

More information

BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad

BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad PLEASE MARK TICK ON LEFT BOX WHICH EQUIPMENT YOU HAVE QUOTED PROPOSAL BASED ON CHINESE EQUIPMENT

More information

The natural ombination

The natural ombination The natural ombination DAikin Altherma Hybrid heat pump system The future is now The new hybrid system Heat pump solution for gas boiler replacement market Daikin Altherma hybrid combines heat pump technology

More information

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)

More information

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations

More information

Capital Expenditure. The common definition of capital expenditure is

Capital Expenditure. The common definition of capital expenditure is Capital Expenditure Under standard accounting practices local authorities are required to account for revenue expenditure and capital expenditure differently. Capital expenditure is defined in the Local

More information

Our repairs and maintenance service

Our repairs and maintenance service Your repairs Being a GHA tenant gives you special rights when it comes to getting things fixed. This is called your Right to Repair. Here you ll find all you need to know about that, and much more. If

More information

Nordic Heat Pump Product Guide

Nordic Heat Pump Product Guide Nordic Heat Pump Product Guide About Maritime Geothermal Maritime Geothermal is a privately owned, Canadian based manufacturer of geothermal heat pumps. We began manufacturing the Nordic line of heat pumps

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough

More information

Session 2: Hot Water Supply

Session 2: Hot Water Supply MEBS6000 Utility Services http://www.hku.hk/mech/msc-courses/mebs6000/index.html Session 2: Hot Water Supply Dr. Benjamin P.L. Ho Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

Fire Safety Risk Assessment

Fire Safety Risk Assessment 1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

Link-Up. Solid Fuel Association Guide to Central Heating. www.solidfuel.co.uk

Link-Up. Solid Fuel Association Guide to Central Heating. www.solidfuel.co.uk Solid Fuel Association Guide to Central Heating Link-Up Combining solid fuel with other central heating technologies using various methods ranging from a simple link-up to a fully integrated thermal store

More information

Energy-Saving Tips. Energy Saving Tips

Energy-Saving Tips. Energy Saving Tips Energy-Saving Tips Energy Saving Tips TABLE OF CONTENTS How Do You Spend Your Energy Dollars?.. 1 Easy Ways to Save... 2 Investing in Energy Savings... 6 EarthCents... 7 How Do You Spend Your Energy Dollars?

More information

Combi Unit Genius. The energy efficient Building Service Centre

Combi Unit Genius. The energy efficient Building Service Centre Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Combi Unit Genius The energy efficient Building Service Centre systemair Central Building Services

More information

Nominal Life Expectancy for Building Components

Nominal Life Expectancy for Building Components Nominal Life Expectancy for Building Components Building System Page A. HVAC 2 B. Elevator/Escalator 6 C. Plumbing 7 D. Roofing 8 E. Electrical 10 F. Fire/Life/Safety/Security System 11 G. Interior Finishes

More information

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy LG Air conditioning Company Multi V Water Ⅱ Air Conditioning Academy 1.1 What is Multi V Water II? High Performance Prospect rights Water pipe Refrigerant pipe Indoor unit Beautiful Exterior Convenience

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

Center for Energy Education Laboratory

Center for Energy Education Laboratory Paper ID #7072 Center for Energy Education Laboratory Dr. Robert Gilbert, Sinclair Community College Robert B. Gilbert, Ph.D., LEED AP, BA, is an Associate Professor of Energy Management Technology, and

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information