1 Facilities Maintenance Standards rev Purpose The purpose of these standards is to outline the minimum requirements for maintaining state owned facilities and infrastructures in a manner that will maximize the usefulness and cost effectiveness of these facilities in enhancing the quality of life of Utah state employees, citizens, and visitors. Additional work may be required to satisfy code or judicial requirements. All agencies and institutions shall comply and will be audited against these standards by the Utah State Building Board. Exempt agencies are to review their maintenance programs against these standards and to report the degree of compliance of each of their complexes to the legislature through the Utah State Building Board. 1.0 Documentation 1.1 Architectural and Mechanical At least one copy of the Operations and Maintenance Manuals shall be maintained at the facility or complex At least one copy of the architectural, mechanical, and electrical as built drawings shall be maintained at the facility or complex A mechanism shall be provided whereby as built drawings are promptly updated upon changes in the structural, mechanical, electrical, or plumbing systems As built drawings shall be reviewed periodically to assure that they reflect the current building or infrastructure configuration to be maintained at the facility or complex Reserve copies of all building documentation shall be archived in an appropriate and separate location from the facility. 2.0 Equipment Data Base and Tagging 2.1 An appropriate equipment numbering system shall be utilized and metal, plastic tags or labels placed on all building equipment and electrical panels. 2.2 All equipment name plate data shall be collected, documented, and filed in a computerized data base/computerized maintenance management system (CMMS). 3.0 Corrective Maintenance 3.1 A work request system shall be defined and made available to the user of the facility/infrastructure so that maintenance problems can be reported and logged promptly by the maintenance department. A log of all requests shall be maintained indicating the date of the request and the date of completion. 3.2 A work order system shall be established to govern the procedures for corrective maintenance work. The work order system shall capture maintenance time, costs, nature of repair, and shall provide a basis for identifying maintenance backlog on the facility/infrastructure.
2 3.3 Maintenance backlogs on the facility/infrastructure shall be regularly reviewed and older requests processed so that no request goes unheeded and all requests are acted upon in a timely manner. 3.4 A priority system for corrective maintenance shall be established so that maintenance work is accomplished in an orderly and systematic manner. The facility user shall be made aware of the priority of requested maintenance and the time expected to accomplish the correction. If the stated goal cannot be met, the user shall be informed of the new goal for completing the request. 3.5 The agency and institution shall report to the Utah State Building Board Director a current and accurate operations and maintenance costs tracked to the individual building level for any facility measuring 3,000 GSF or greater. For locations consisting of multiple facilities that individually do not meet the minimum GSF requirement shall be required to report operations and maintenance costs at the campus/complex level. Reporting for Individual building O&M cost shall be reported no later than December 31, of each year. 3.6 All operations and maintenance expenditure reports for both direct and indirect cost shall contain current and accurate costs including but not limited to: Utilities (, Electrical, Gas/Fuel, and Water in certain cases Steam, High Temp Water, Chilled Water and Sewer may need reporting), Labor, Materials, Custodial, Landscape & Grounds services, Insurance, travel, leasing and rent. 4.0 Preventive Maintenance 4.1 State facilities managers shall automate preventive maintenance scheduling and equipment data bases. 4.2 All equipment (e.g. chillers, boilers, air handlers and associated controls, air compressors, restroom exhaust fans, domestic hot water circulating pumps, automatic door operators, temperature control devices, etc.) shall be on a computer based preventive maintenance schedule the frequency of preventive maintenance procedures shall be determined by manufacturer's recommendations and local craft expertise and site specific conditions. 4.3 A filter maintenance schedule shall be established for HVAC filters and a record of filter changes maintained. 4.4 Preventive maintenance work orders shall be issued for both contract and in house preventive maintenance and the completion of the prescribed maintenance requirements documented. 4.5 Emergency generators shall be test run at least monthly. If test runs are not automatic, records of these test runs shall be maintained at the site. At least yearly, the transfer from outside power to emergency power shall be scheduled and successfully performed.
3 5.0 Boilers 5.1 Steam Boilers Steam boilers shall be checked daily when operational or on a automated system that tracks them Low water cut off devices shall be checked for actual boiler shut down at the beginning of the heating season and at least quarterly thereafter by duplicating an actual low-water condition Boiler relief valves shall be tested for proper operation at least annually A record of these tests shall be maintained near the location of the boiler A daily log of the operating parameters shall be maintained on boilers when they are operational to include pressures, temperatures, water levels, condition of makeup and boiler feed water, and name of individual checking parameters.\ 5.2 Hot Water And Steam Boilers All boilers shall receive inspections and certification as required from an authorized state agent or insurance inspector. The certificate of compliance shall be maintained at the boiler. 6.0 Life Safety Monthly tests of boiler water ph and Total Dissolved Solids shall constitute the basis upon which to add water treatment chemicals. A log of these tests shall be maintained in the boiler room. 6.1 All elevators shall receive regular inspections and maintenance by certified elevator maintenance contractors. Records of such maintenance shall be maintained at the site. Telephones within elevators shall be checked monthly for proper operation All elevators shall have current Permits to Operate posted near the elevator equipment as required by the Utah State Labor Commission. 6.2 Fire Protection Equipment Detection and notification systems (e.g. control panel, smoke detection devices, heat sensing devices, strobe alarm lights, audible alarm indicating devices, phone line communication module, etc.) shall be inspected annually and tested for operation at least semi-annually by a properly certified technician. A record of these inspections shall be maintained and FACP needs to be properly tagged as required by the Utah State Fire Marshal Halon/Ansulor pre-action systems shall be inspected and tested by a certified inspector semi-annually to assure their readiness in the event of a fire. Testing and inspection of these systems shall be documented Fire extinguishers shall be inspected monthly and tagged annually by a certified inspector and all tags should be properly and legibly completed
4 6.2.4 Automatic fire sprinkler systems, standpipes and fire pumps shall be inspected annually by a certified technician. Tags should be properly and completely filled out including the type of inspection, month and year those inspections were performed, the person who performed the inspection, and the person performing the inspections certificate of registration number. 6.3 Uninterruptible power supply systems for data processing centers shall be inspected and tested appropriately to assure their readiness in the event of external power interruptions. Maintenance on these systems shall be documented. 6.4 Emergency directional and exit devices (e.g. exit signs, emergency lights, ADA assist equipment, alarm communicators, etc.) shall be inspected at least quarterly for proper operation. 7.0 Air Conditioning and Refrigerated Equipment 7.1 Chillers A daily log or computerized log of important data (e.g. chilled water supply and return temperature, condenser water supply and return temperature, current draw, outside air temperature, oil level and pressure, etc.) should be kept, and the information trended to identify changes in the system operation; the causes should then be determined and corrected to prevent possible system damage The systems shall be leak checked on a quarterly basis during the operating season and once during the winter A factory trained technician should perform a service inspection annually to include an oil analysis. Any abnormal results should be discussed with the chiller manufacturer to determine a proper course of action Chillers shall not be permitted to leak in excess of 15% of their total charge annually. Losses exceeding this amount are in violation of the law and may result in costly fines Should refrigerant need to be added to a system, the amount of refrigerant added should be carefully documented and record the cause of the loss and type of work done to repair it An adequate supply of refrigerant for the uninterrupted operation of existing CFC chillers shall be maintained until the chiller is converted or replaced. Examples of CFCs are R11, R12, R113, R502, etc Maintenance personnel who perform work other than daily logs and visual inspections on CFC chillers or refrigeration equipment containing CFCs or HCFCs must by law have an EPA certification matching the type of equipment being worked on The condition of refrigerant cooling water systems such as cooling towers shall be checked visually at least weekly for algae growth and scaling and appropriate treatment administered. 7.2 Roof Top and Package Units Annually check and clean as needed the condenser coil and evaporator coil.
5 8.0 Plumbing The following preventive maintenance items should be completed annually: tighten belts, oil motors, leak check, clean evaporator pans and drains Quarterly check filters and replace where necessary. 7.3 Small Refrigerated Equipment Annually clean condenser coil Annually oil the condenser fan motor and visually inspect the equipment and make necessary repairs as needed. 8.1 All Backflow Prevention Devices shall be tested by a certified technician at least annually and proper documentation shall be filed with the appropriate agency. Proper documentation shall be kept on site and readily available. 8.2 Cross-connection control shall be provided on any water operated equipment or mechanism using water treating chemicals or substances that may cause pollution or contamination of domestic water supply. 8.3 Any water system containing storage water heating equipment shall be provided with an approved, UL listed, adequately sized combination temperature and pressure relief valve, and must also be seismically strapped 8.4 Pressure vessels must be tested annually or as required and all certificates must be kept current and available on site. 9.0 Electrical Systems 9.1 All electrical panels shall have a thermal-scan test performed bi-annually on all components to identify hot spots or abnormal temperatures. The results of the test shall be documented. 9.2 A clearance of three feet, or as required by NEC shall be maintained around all electrical panels and electrical rooms shall not be used for general storage. 9.3 Every electrical panel shall be properly labeled identifying the following: panel identifier, area being serviced by each individual breaker, equipment being serviced by each breaker or disconnect. 9.4 All pull boxes, junction boxes, electrical termination boxes shall have proper covers in place and panels accessible to persons other that maintenance personnel shall remain locked to guard against vandalism or personal injury. 9.5 Only qualified electrical personnel shall be permitted to work on electrical equipment Facility Inspections 10.1 The facility shall periodically receive a detailed and comprehensive maintenance audit. The audit shall include HVAC filter condition, mechanical room cleanliness and condition, corrective and preventive maintenance programs, facility condition, ADA compliance, level of performance of the janitorial service, condition of the grounds, and a customer survey to determine the level of user satisfaction with the facility and the facility management and maintenance services.
6 10.2 A copy of the above audit shall be maintained at the facility Each year a Facility Risk Management Inspection shall be conducted, documented, and filed with the Risk Management Section of the Department of Administrative Services Actions necessary to bring the facility into compliance with Risk Management Standards shall be completed within two months following the above Risk Management Inspection for routine maintenance items. Items requiring capital expenditures shall be budgeted and accomplished as funds can be obtained Every five years the facility shall be inspected and evaluated by an Architect/Engineer (A/E), qualified third party or qualified in-house personnel to determine structural and infrastructural maintenance and preventive maintenance needs The structural inspection and evaluation may include interior and exterior painting, foundations, walls, carpeting, windows, roofs, doors, ADA and OSHA compliance, brick work, landscaping, sidewalks, structural integrity, and exterior surface cleanliness The mechanical and electrical evaluation shall include the HVAC systems, plumbing systems, security, fire prevention and warning systems, and electrical distribution systems The above inspection shall be documented and shall serve as a basis for budgeting for needed capital improvements Intrusion alarm systems that communicate via phone line shall be tested monthly to assure proper operation Periodic inspections of facilities may be requested of local fire departments and the identified deficiencies promptly corrected. These inspections and corrections shall be documented and kept on file at the facility Indoor Air Quality and Energy Management 11.1 Indoor air quality shall be maintained within pertinent ASHRAE, OSHA, and State of Utah guidelines All individual building utility costs (gas, electric, water, etc.) at facilities meeting the criteria listed in section 3.5 of the Facility Maintenance Standards shall be metered and reported back to the Building Board Director annually by December 31, of each year and made available at the facility so that energy usage can be accurately determined and optimized Based on the ongoing analysis of energy usage, appropriate energy conservation measures shall be budgeted for, implemented, and the resulting energy savings documented The following documents shall be on hand at the facility (where applicable) in an upto-date condition: 12.1 A Hazardous Materials Management Plan 12.2 An Asbestos Control and Management Plan
7 12.3 A Laboratory Hygiene Plan 12.4 A Lockout/Tag out Procedure for Performing Maintenance on Building Equipment 12.5 A Blood Born Pathogen Program 12.6 An Emergency Management Plan to include emergency evacuation and disaster recovery A Respirator Program
8 12.8 A Hearing Conservation Program 12.9 A Permit Confined Space Entry Program A Lead Exposure Program A Trenching Standard Available DFCM Maintenance Management Services DFCM can provide certain maintenance management, energy management, and preventive maintenance services to agencies at cost. The following services are available: maintenance management consulting maintenance audits of facilities energy management audits and energy management consulting development of the documents listed in 12.0 above.
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
Print Shop/Mail Room
Chapter XVIII Print Shop/Mail Room Page 110 CHAPTER XVIII Print Shop/Mail Room ARCHITECTURAL/STRUCTURAL A. BUILDING EXTERIOR 1.0 EXTERIOR WALLS The exterior walls are comprised of stone veneer. There were
Chris Clement 701 Bayou Lane Thibodaux, LA 70301 985.446.7320
Chris Clement 701 Bayou Lane Thibodaux, LA 70301 985.446.7320 Position: Facility Assistant Maintenance Manager B Date: May 17, 2010 - present 70% OF TIME- is spent on following duties. Assist the Facility
Mechanical, Plumbing, and Fire Protection Conditions
Mechanical, Plumbing, and Fire Protection Conditions Mechanical Conditions The mechanical systems within the building consist of a combination of the original 1926 systems and renovations that occurred
COOLING WATER MANAGEMENT
COOLING WATER MANAGEMENT Intent To minimize the carbon-footprint, water usage and environmental impact of HVAC cooling systems and process cooling systems, generally by optimizing the control of water
HVAC MAINTENANCE SUPERVISOR (Range 121)
(Range 121) DEFINITION Supervises, plans, coordinates and performs a variety of fundamental and skilled work in the building and mechanical trades to ensure the overall physical integrity of District Locations.
Maintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
NYC Department of Education Building Condition Assessment Survey 2014-2015 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004
School: InspectionId Asset Data Inspection Type Building Assessment Survey 204-205 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 0004 Time In Last Edited 255 MECHANICAL 205-05-8 09:00AM
Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals
Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals Les Butler Associate Commissioner for Business and Regional
Quality Assurance Calendar Maintenance Responsible Party Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Generator fire up Generator 1 hour load test Generator 4 hour load test Fire extinguisher integrity checks Fire extinguisher certification Fire drills Fire door integrity Fire signage lighting Fire alarm
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
Guide Specification SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY
SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. HVAC Commissioning description. 2. HVAC Commissioning responsibilities. 1.2 REFERENCES A. American Society
Planned, Limited Notice and Emergency Outage Guidelines
Applies to: All Facilities Management Employees GUIDELINES: Issued: April 22, 2014 Revised: February 24, 2015 Author: Communications Coordinator PURPOSE: The purpose of these guidelines is to define roles
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
ASME QRO Certification Program
ASME QRO Certification Program ASME QRO Certification For Operators of Resource Recovery Facilities Applicant Information Table of Contents Table of Contents Page QRO Certification Overview...1 Types of
Radford University. Indoor Air Quality Management Plan
Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings
Board Seminar Facilities. School Year 2012-2013. Submitted by Joseph L. Lisa-Director of Facilities
Board Seminar Facilities School Year 2012-2013 Submitted by Joseph L. Lisa-Director of Facilities High School Installed new fence for Pre-K activities by weight room. Installed new rails and side walks
Trace Electric Trace Fire Protection
ELECTRIC AL FIRE PROTECTION ACTIVE IN THE FOLLOWING AREAS: Multi-Unit Residential Apartment Buildings Industrial Commercial Institutional & Long Term Care Facilities Trace Electric Trace Fire Protection
Automatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
How To Prevent And Manage A Flood And Mold
Flood Response and Mold Prevention Program Prepared by the Berea College Department of Environmental Health and Safety Revised May 2010 Contents I. Introduction II. III. IV. Flood and Mold Hazards Roles
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
Number Northern Arizona University Facility Services Section Page. Effective April 1, 2011
Facility Services Section Page Recharge Services, Maintenance and Construction PURPOSE 1 of 6 The purpose of this policy is to set forth standards for chargeable services for maintenance and construction
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Planned and Emergency Utility Outage Guidelines
Revised: April 4, 2014 GUIDELINES: PURPOSE: The purpose of these guidelines is to define roles and responsibilities in requesting, coordinating scheduling, and executing utility outages and restoration
A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.
DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly
Ductless Heat Pumps. Gary Nordeen January 2009. www.nwbuildings.org/dhp.aspx [email protected]
Ductless Heat Pumps Gary Nordeen January 2009 www.nwbuildings.org/dhp.aspx [email protected] Outline Heat Pump Basics Ductless Heat Pumps Efficiency Advantages Commercial installations Planning (applications,
SAFETY AND HEALTH PROGRAM
PROGRAM NUMBER NO. PAGES 05-005 10 REVISION ISSUE DATE Revision 2 11/1/2005 SAFETY AND HEALTH PROGRAM Confined Space Entry 1.0 INTRODUCTION Confined Space Entry is a serious workplace hazard, capable of
Disaster Prevention and Protection Checklist
Preservation Services Leaflet 1438 West Peachtree Street, Suite 200/Atlanta, GA 30309 Phone: 404-892-0943/Fax: 404-892-7879 Website: Disaster Prevention and Protection Checklist The inspection
PLP - TERMS AND CONDITIONS
PLP - TERMS AND CONDITIONS 2014-2015 Philadelphia Gas Works Residential Parts & Labor Plan Contract This Residential Parts & Labor Plan Contract (this Plan ) is available to customers of the Philadelphia
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A
COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A (All unshaded skill sets must be demonstrated/completed) PROTECT SELF AND OTHERS Identify, interpret, and
KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS
KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS By Jerome E. Spear, CSP, CIH Effective January 1, 2005, consultants who prepare mold management plans for buildings located in Texas must be licensed
WHEN IS A PERMIT REQUIRED?
WHEN IS A PERMIT REQUIRED? Any owner, builder, contractor, or other authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
Attachment J-C18.1. HVAC Work Instructions
. RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.
ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS DATE: May 6, 2016 HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport BIDS CLOSE: May 12, 2016, at 2:30 p.m., Local Time TO ALL BIDDERS
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
Element D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
We ve got you covered.
Mechanical & Plumbing We ve got you covered. Energy Savings Maintenance Contracts Cooling Towers Re-piping Air-conditioning Building Automated Systems Boiler Retrofits Sewer Cleaning Drain Systems THE ONLY
BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES
Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
Classification and Qualification STANDARDS
Classification and Qualification STANDARDS HVAC Series Classification Title Class Code Date Established Date Revised Operating Engineer Building Service Engineer Air Conditioning/Refrigeration Mechanic
CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance
CIBSE Guide M: Maintenance engineering and management compliance legislation and guidance Types of System/Plant Action required Frequency by Type of Fire and Smoke Fire extinguishers Discharge (not CO
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
ADDENDUM No. 2. RFP No. 14-15/27, Oakland Maintenance Center Facility Management Services
Purchasing Department 530 Water Street Oakland, CA 94607 March 6, 2015 ADDENDUM No. 2 RFP No. 14-15/27, Oakland Maintenance Center Facility Management Services This Addendum modifies the original RFP Documents
Protect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement.
Protect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement. The benefits of a Home Service Agreement Provides peace of mind Regularly scheduled maintenance will keep
How To Check For A Deficiency
UPCS in Pictures The following pictures are not all inclusive nor does it cover every deficiency. The pictures, however are some of the most commonly cited deficiencies on REAC inspections. Erosion The
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
ENERGY AUDITS AND RETRO- COMMISSIONING Local Law 87
ENERGY AUDITS AND RETRO- COMMISSIONING Local Law 87 Overview Although energy-efficiency retrofits generally result in major cost and energy savings, many buildings are not participating in the audits that
Nominal Life Expectancy for Building Components
Nominal Life Expectancy for Building Components Building System Page A. HVAC 2 B. Elevator/Escalator 6 C. Plumbing 7 D. Roofing 8 E. Electrical 10 F. Fire/Life/Safety/Security System 11 G. Interior Finishes
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.
Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)
Attachment #23 Health Safety Table. Client Education Inform issue and document. How to clean & maintain gutters. How to adjust sprinklers
Exterior Visual Health & Safety Issue Allowable Action Site Drainage Exterior grade does not slope 2% within the first 10' Site drainage causing bulk moisture in crawl space or basement Repairs to existing
Revised April (May) 2015
Section 19.0 Cross Connection Control Policy 19.1 Responsibility 19.1.1 The Elkhart Water Utility has the responsibility to supply safe, potable water from the source to the point of delivery defined as
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
COLUMBUS STATE COMMUNITY COLLEGE EMPLOYEE SAFETY MANUAL
COLUMBUS STATE COMMUNITY COLLEGE EMPLOYEE SAFETY MANUAL HAZARDOUS MATERIAL MANAGEMENT Effective October 15, 1995 Page 1 of 4 Updated August, 2008 Revised August, 2009 A. Columbus State Community College
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
CONTRACTOR INDUCTION HANDBOOK
CONTRACTOR INDUCTION HANDBOOK POLICY The health and safety of all school employees and contractor employees is a vital concern at the school. Contract personnel will be treated in a manner consistent with
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
Environment of Care Utility Systems Management Plan 2014 Updated 4.18.2014
Environment of Care Utility Systems Management Plan 2014 Updated 4.18.2014 PURPOSE The objectives of the Utility Systems Management plan is to establish, maintain, and continually provide a reliable utility
Basics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
How To Handle An Emergency
Company Name Address Telephone Contact Name Title Last Revision Date Policy and Organizational Statements Identify the goals and objectives for the emergency response plan. Define what your emergency response
Comfort you can count on.
Comfort you can count on. Your home s indoor temperature should feel just right in any season. We ll make sure it does. Installation Repairs Maintenance w ww.ssihvac.c om (703) 968-0 6 0 6 Proudly Serving
Water Treatment Services Specifications Department of Intellectual and Developmental Disabilities 11437 Milton Wilson Road. Arlington, TN 38002
Water Treatment Services Specifications Department of Intellectual and Developmental Disabilities 11437 Milton Wilson Road Arlington, TN. 38002 General Scope of Contract I. General Information II. Bidder/Contractor
Sample Written Program. For. Flammable Liquids
Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and
SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
Plan Number. 1624- A Cross Beam Dr. Charlotte, NC 28217 704.771.1020. www.charlottemechanical.com. Simplified Service Plan. Air Conditioning.
Plan Number 1624- A Cross Beam Dr. Charlotte, NC 28217 704.771.1020 www.charlottemechanical.com Simplified Service Plan Air Conditioning And Heating System PARTS, LABOR, & EMERGENCY REPAIR Effective Date:
The Orange County Farmers Museum Emergency Preparedness Plan
The Orange County Farmers Museum Emergency Preparedness Plan TABLE OF CONTENTS Section Page Introduction. 2 1. Coordination with an Emergency Response Agency. 2 2. Policies of the Board 2 3. Procedures
610-6-MURPHY 610-461-6502 PRIORITY SERVICE AGREEMENTS. 610-461-6502 PLUMBING HEATING COOLING DUCT CLEANING BATHS TILE Thank You. Richard G.
Contractor License PA#022799 PA#022799 PLUMBING, HEATING & AIR CONDITIONING 610-6-MURPHY OR 610-461-6502 PRIORITY SERVICE AGREEMENTS A staff of professionals waiting to serve you 24 hours a day 365 days
SECTION A... 3 SECTION B... 7
BRITISH COLUMBIA SAFETY AUTHORITY Manual for Owners and Operators of Special Status Plants Risk Assessed and General Supervision Date: March 12, 2012 Controlled Document: MAN -4000-03 I TABLE OF CONTENTS
Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
SECTION 105 PERMITS. Gas:
SECTION 105 PERMITS SECTION 105 PERMITS 105.1 Required. Any owner or authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,
Sample - Existing Building Commissioning Plan
Sample - Existing Building Commissioning Plan Version: Draft for Review Final Approved: Owner Site Address: Primary Site Contact Name and Telephone Number: Date Building Description The site consists of
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
Post Occupancy Evaluation (POE) Technical Instructions
1.0 Purpose These technical instructions define the typical steps required by HHS personnel in the use of the. The POE consists of a detailed and systematic assessment of a facility that is operational
Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant
Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant Health and Safety Safe management of industrial steam and
DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE
1.0 Introduction DESERT RESEARCH INSTITUTE This Desert Research Institute (DRI) Mold Assessment and Remediation Procedure was established to assure that consistent and uniform information is provided to
COMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
HOUSTON ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1962 BUILDING AREA 59,900 SF CURRENT PROGRAM CAPACITY 507 ENROLLMENT 2008 291 WARD 7 PROPOSED PROGRAM CAPACITY 325 Site Plan HOUSTON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
RULE 1102. DRY CLEANERS USING SOLVENT OTHER THAN PERCHLOROETHYLENE
(Adopted January 6, 1978)(Amended August 3, 1979)(Amended July 11, 1980) (Amended August 3, 1990)(Amended December 7, 1990) (Amended November 17, 2000) RULE 1102. DRY CLEANERS USING SOLVENT OTHER THAN
HVAC Claims: Repair vs. Replacement
HVAC Claims: Repair vs. Replacement Curtis M. VanNess Field Operations Manager Outline Brief history of HVAC How do HVAC systems work? Types of systems and equipment Causes of failure Repair vs. Replace
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809