IT&T Infrastructure Standards
|
|
|
- Dulcie Burke
- 10 years ago
- Views:
Transcription
1 Technology Services IT&T Infrastructure Standards Version th April 2015 Page 1
2 Table of contents 1 CHANGE HISTORY DOCUMENT HISTORY REVIEWERS APPROVALS INTRODUCTION OVERVIEW MANDATORY REQUIREMENTS INTERNAL AND EXTERNAL CABLING PLANT STRUCTURED CABLING SYSTEM COPPER INTERNAL Category Category 6 A Workstation Outlets Internal Voice Grade Cable Cable pathways STRUCTURED CABLING SYSTEM FIBRE - INTERNAL EXTERNAL CABLING SYSTEM - COPPER EXTERNAL CABLING PLANT - FIBRE EXTERNAL COMMUNICATIONS INFRASTRUCTURE COMMUNICATION ROOMS & DATA CENTRES Communication Rooms Data Centres ENGAGING TS & AUTHORISATION OF WORKS ENGAGING TS AUTHORISATION OF WORKS QA & POST CONSTRUCTION DOCUMENTATION APPENDICES Appendix A: References A.1 Consultants Package A.2 Krone Specifications A.3 Copy of TS Approval stamp A.4 URLs A.5 Reference to Standards A.6 Contractor Selection Appendix B: Acronyms and Abbreviations B.1 Insert Text Here Page 2
3 1 Change History 1.1 Document History Version Date Description Changed By Initial Document Hans Muller Minor Updates Hans Muller Minor Updates Hans Muller Technical Updates Minor Hans Muller Transferred content to new template Linda Timbs Minor Update to section 5 Linda Timbs Minor Update to Approvals/Url s Jerry Gibson Minor Update to section 3 and Approvals Jerry Gibson Minor update to reference TE and removal of multi mode fibre Jerry Gibson 1.2 Reviewers The following subject matter experts will be invited to the review the document content for accuracy and/or relevance. Reviewers will be asked to provide feedback to the author but may not be required to provide formal sign-off. Version Date Name / Title 1.3 Approvals The following recipients will be required to review this document and provide formal signoff which includes the endorsement of the recommendations. Version Date Name / Title Approval Phil Manning Manager Production Services Page 3
4 2 Introduction 2.1 Overview The Technology Services (TS) Department has sole responsibility for Communications Infrastructure on and within all University of Adelaide owned and leased Properties. This document intends to describe the University of Adelaide IT&T infrastructure standards. It is to be read in conjunction with the University of Adelaide Building standards and all relevant Australian Standards. This document shall be seen as a supplement to the Australian Standards and shall prevail unless there is a conflict between this document and Australian Standards relating to binding mandatory requirements. This document shall be seen as a supplement to the TE Generic Category 6 or 6A if applicable specification (see Appendix) and shall prevail unless it causes the installation not being certifiable. 2.2 Mandatory Requirements TS shall be consulted for any works relating to new communications infrastructure works as well as any modification and/or addition of communications infrastructure. This may also include related works like restricting access to or relocation of IT&T infrastructure by other trades. It is imperative that TS is consulted early to allow for the identification of capacity and cost implications. It is the responsibility of the Consultant/Project Officer to contact TS and to ensure that relevant information is obtained. Non-compliance with these mandatory requirements may result in the refusal by TS to connect services. Page 4
5 3 Internal and External Cabling Plant 3.1 Structured Cabling System Copper Internal The University has selected TE 25 System as the preferred solutions provider for structured cabling systems. All installations shall comply with the TE Network design integrator system Structured Cabling System. TS shall be approached in the early design stages to validate the choice of the TE Copper Ten Cat6A cabling solution for the specific application Category 6 This Category 6 solution shall utilise the Highband Ultim8 Disconnection modules, Category 6-4 pair copper UTP cable and category 6 flush mount outlets. The cable colour shall be grey and the outlet colour shall be black. Wall plates shall be the window model type allowing for machine printed outlet identification. The installation shall utilise wall mount distribution frames Profil type only. All flyleads and system leads (leads between active equipment and termination frames) shall be white in colour. The installation shall be carried out by TE Network design integrator 25 and shall carry a 25-year Te25Enterprise Networks system warranty. Cable and TO numbering shall be the same and as per below; Levels with multiple communications rooms feeding the same level COMMS ROOM-NUMBER CC / CC Levels with a single communications room NUMBER 251 / Category 6 A TE Copper Ten 10 Gigabit solution is the preferred cabling solution for Greenfield sites. This Category 6A Solution shall utilise the TE Copper Ten 20 Pair Modules and backmount frames. The cable colour shall be grey and the outlet colour shall be black. Wall plates shall be the window model type allowing for machine printed outlet identification. This installation of the backmount frames shall utilise a false wall and the design needs to be approved by TS and TE before proceeding. All flyleads and systems leads (leads between active equipment and termination frames) shall be yellow in colour except when using TE weather proof outlet the cable shall be green in colour. Cable and TO numbering shall be the same and as per below; Levels with multiple communications rooms feeding the same level COMMS ROOM-NUMBER CC / CC Levels with a single communications room NUMBER 251 / a Category 6.a S/FTP (Av cabling) TE Copper Ten 10 Gigabit solution is the preferred cabling solution for Av Page 5
6 solutions This Category 6A Solution shall utilise the TE Copper. The cable colour shall be orange and the outlet colour shall be black with an orange faceplate. All flyleads shall be orange in colour Cable and TO numbering shall be the same and as per below; Levels with multiple communications rooms feeding the same level COMMS ROOM-NUMBER CC / CC Levels with a single communications room NUMBER 251 / Workstation Outlets The reticulation of cabling within the workstation and the Workstation outlets need to be approved by TE unless matching existing workstations Internal Voice Grade Cable Internal multi core voice grade copper cable shall be a PVC type. Conductor size shall be a minimum of 0.5mm square. Cable runs shall be contiguous between wall mounted distribution frames. Joints shall not be used. Cable termination shall be via TE disconnection modules. Colour coding shall comply with manufacturer recommended schemes Cable pathways Main pathways shall be within accessible ceiling spaces above public areas e.g. Passageways, not office or other occupied space. Accessible means that sufficient access to cable pathways is given to ensure that cables can be installed and secured to comply with both, Australian Standards and the TE Network design integrator 25. Cable pathways shall utilise cable tray along the main trunk and catenary wire for branches. Cable tray shall be of sufficient size for the anticipated quantity of cables to be supported plus 50% spare capacity for future growth. There shall be no more than 20 cables per catenary wire. Communications support infrastructure is for the sole use of communications cabling only hence no other services shall utilise communications infrastructure in any form. 3.2 Structured Cabling System Fibre - Internal The University has selected TE as the preferred solutions provider for internal Fibre Cabling Systems The preferred internal Structured Fibre Cabling System is custom design, TE 25 System solution based on Tyco RTC -Series fibre enclosures utilising TE Krone Optic Fibre including LC connectors with pigtails. Fibre cable shall be TE Single Mode (SM) ITU G652.d compliant cable. LC connectors shall be blue in colour for SM cable. Fibre Patch cords shall yellow in colour for SM. Page 6
7 Cable runs shall be contiguous with joints only allowed for pigtails within Patch Panels. External or internal joints shall not be used. All Patch Panels and fibres shall be labelled. The labelling scheme will be made available on request. All cable shall be tested as per TE 25 System specification and a 25% sample (selected by client) of the installation shall random tested by OTDR. OTDR test results shall be provided in both printed and electronic format. 3.3 External Cabling System - Copper The University has selected TE Krone as the preferred solutions provider for external copper cabling plant. External multi core copper cable shall be a polyester type with an internal moisture barrier. Conductor size shall be 0.64mm square. Cable runs shall be contiguous between wall mounted distribution frames. External or internal joints shall not be used. Cable termination shall be via TE Krone disconnection modules. Colour coding shall comply with manufacturer recommended schemes. The external cabling system shall be fully TE compliant and certified. 3.4 External Cabling Plant - Fibre The University has selected TE Krone as the preferred solutions provider for internal Fibre Cabling Systems. The preferred external Structured Fibre Cabling System is custom design, TE 25 System solution based on Tyco RTC -Series fibre enclosures utilising TE Krone Optic Fibre including LC connectors with pigtails. Fibre cable shall be Single Mode (SM) ITU G652.d compliant cable. LC connectors shall be blue in colour for SM cable. Fibre Patch cords shall be yellow in colour for SM. Cable runs shall be contiguous with joints only allowed for pigtails within Patch Panels. External or internal joints shall not be used. All Patch Panels and fibres shall be labelled. The labelling scheme will be made available on request. All cable shall be tested as per TE 25 System specification and a 25% sample (selected by client) of the installation shall random tested by OTDR. OTDR test results shall be provided in both printed and electronic format. Cables shall be permanently labelled at both ends and within pits, showing both origin and destination of cable. The labelling scheme will be made available on request. Cables shall have service loops (2 off) within each pit. Page 7
8 4 External Communications Infrastructure External communications infrastructure consists of compliant communications conduit and pits. Conduits shall have a minimum of 100mm diameter. Pits are required at any change of direction exceeding 30 degrees, however if bends exceeding 30 degrees are required for building entry, they shall be 90 degree bends of the large sweep type. Minimum Pits size shall be 900x900x900mm inner. Lids shall be Gatic, Class D compliant, regardless of pit location. The maximum lid size shall be 900x450mm with a minimum of 2 lids per pit. All pit lids shall be installed as per manufacturer s recommendation to ensure proper moisture sealing. Pit bases shall be of solid construction, concrete or bricked types with a provision for drainage. All conduit entries into pits or buildings shall be properly sealed and sleeved to prevent the ingress of moisture. Each building entry conduit shall be sealed within the pit with the Tyco T-Dux product. Pit lids shall be permanently marked with 100mm diameter engraved stainless steel plates. The engraving shall contain the wording Communications and indicate conduit directions. Page 8
9 5 Communication Rooms & Data Centres Communication Rooms Communications rooms shall be constructed as per Building Standards. They typically require: Power/UPS, Minimum of 2 x 15 amp under floor circuits using orange Clipsal 56C315 outlets Cooling Access Floor Security Access Lighting Fire Detection Environmental Monitoring Good cable access. 19 inch Rittal Rack consisting of the following items: Adelaide Uni Rack Part No XAU QT Y XAUPQ21EFEBK XAUCT42830B 2 S U E A Description 42U 800*2000*1000 ADL UNI SVD FRONT&REAR- RAL 9005 (black) Vertically Divided Vented doors front and rear. Comfort handle with 3524 lock, levelling feet and castors E A Side panel divided WD 2000x1000 RAL9005 E A DK POWERRAIL VERTICAL 21 WAY GPO 15AMP E A Cable duct 36U for H2000 RAL9005 E A DK 42RU * 300 CABLE TRAY- Black TS shall be consulted for the design of new communication rooms as well as for any proposed addition or modification to existing facilities Data Centres Data Centres shall be constructed on an individual basis. They require: Power Cooling Access Floor Security Access Lighting Fire Suppression and Detection Environmental Monitoring Good cable access. TS shall be consulted for the design of new facilities as well as for any proposed addition or modification to existing facilities. Page 9
10 6 Engaging TS & Authorisation of Works 6.1 Engaging TS The call centre should be contacted via a x33000 or The call centre will log this call and provide a reference number, which shall be used in any further correspondence with TS. An assigned TS Project Officer will make contact with the requestor within 72 hours of the request being lodged. 6.2 Authorisation of Works No IT&T Infrastructure work shall be tendered for until the relevant tender document has been authorised by TS. Authorisation will be via formal sign off in form of stamped and signed tender documents. 6.3 QA & Post construction documentation TS may conduct QA site inspections during construction to ensure compliance of works with the tender document. The Consultant, Project Officer or Contractor shall give TS 5 working days notice to take up the option of 1 st fix inspections during the construction stage. All work requires a formal handover sign off. The Consultant or Project Officer shall give ITS 5 days notice for handover inspections. TS reserves the right not to connect services if the handover sign off has not been completed. Written and electronic test results (in PDF or Microsoft Excel format) shall be submitted together with as installed documentation for all work carried out. Page 10
11 Appendices A E References Acronyms and Abbreviations Page 11
12 Appendix A: References A.1 Consultants Package Refer to the TS Communications Services Homepage for further information. {Insert link} A.2 Krone Specifications Refer to the TS Communications Services Homepage for further information. {Insert link} A.3 Copy of TS Approval stamp A.4 URLs TE 25 System Tyco Gatic Racks TS Helpdesk A.5 Reference to Standards The below is an indication of relevant, applicable standards. It is a guide only and not intended to be a complete list: Page 12
13 A.6 Contractor Selection The TE 25 System solution requires TE Network design integrator 25 authorized installers to be appointed. Although external fibre and external copper installations may not require the TE 25 System certification, any such works shall be carried out by TE Network design integrator 25 authorized installers. Page 13
14 Appendix B: Insert Text Here Acronyms and Abbreviations B.1 Insert Text Here Term TS Description Technology Services Page 14
Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.
Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s
Information and Communication Technology Network Cabling Infrastructure Standard
Approved on Dec-2005 by Eugene Formato Manager, Communications Services Last Amended Aug-2009 by Jarren Beveridge Network Engineer, Communications Services Scheduled for Review Jan-2010 Information and
TCTC Cabling Specifications
TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,
ADC Structured Cabling Solutions
ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution
Communications Infrastructure Standards & Specifications
Communications Infrastructure Standards & Specifications Copper and Optical Fibre Cabling Specification Revisioning version date Author 1.0 2/4/2013 Sean McHugh 1.1 9/7/2013 Sean McHugh Page 1 Table of
Monash University. Communications Cabling Manual. (Sites running VoIP only)
Monash University Communications Cabling Manual (Sites running VoIP only) Communications & Networks Information Technology Services Monash University Monash Cabling Specifications (VOIP sites)doc Page
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
NTU Data Communications Cabling Specification
NTU Networking Standards Document Circulation List NTU Data Communications Cabling Specification Purpose of this Document This document sets out the specification required for NTU data communications cabling
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
InstaPATCH ZERO Solution Guide
SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving
TELEPHONE CABLING TECHNOLOGY INFINITY CABLING
TELEPHONE CABLING TECHNOLOGY Main Types Outdoor Voice Grade Telephone Cable Heavy Duty Type, Weatherproof, Sun Protected, Mechanical protection from damage. Some types can be buried in the ground. Cable
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6
050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
Reliable, Consistent, Quality
Reliable, Consistent, Quality 1-877-320-3143 www.fibertronics.com Reliable, Consistent, Quality Welcome To Fibertronics Inc. Reliability, consistency, and quality is what we put behind every Fiber optic
HARTING Ethernet Cabling 8-poles Overview
Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based
Vertical Phone System Upgrades 2014. Scope of Work
Vertical Phone System Upgrades 2014 Scope of Work Project Overview Install new Vertical phone system and phones on site. Complete testing with API helpdesk. Remove old phone system, phones and box up for
1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
AT&T. PARTNER Plus Door Phone. Installation and Operation Manual
AT&T PARTNER Plus Door Phone Installation and Operation Manual Copyright 1990 AT&T All Rights Reserved Printed in U.S.A. CIC# 999-500-317 OII722050-051 Issue 1 October 1990 PARTNER Plus Door Phone is a
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
Infrastructure Services
Infrastructure Services Standards for the installation of Telecommunication Networks Version 3.0 Copyright The University of Melbourne Table of Contents Standards for the Installation of Telecommunication
Structured Cabling Statement of Work
Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure
UT Southwestern Medical Center Information Resources Cable Installation Standard
UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system
A guide to connecting to fibre optic networks for homeowners, architects, builders and developers.
A guide to connecting to fibre optic networks for homeowners, architects, builders and developers. Chorus is New Zealand s largest telecommunications utility company. We maintain and build the local access
How To Set Up A Minipatch System For A Small Office Or Home Use
Issue : 4 Wood Communications Networking Products Catalogue Small Office & Home Solution Small Office / Home Solution Min LAN Comms Cabinets - Multimedia Panel - Soho Ethernet Switches - Multiroom Audio/Video,
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities
1 TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities Beginning in January 2010 TELUS began designing new subdivisions within the Top 48 population
STANDARDS FOR STRUCTURED CABLING FOR GOVERNMENT, MINISTRIES, DEPARTMENTS AND AGENCIES
STANDARDS FOR STRUCTURED CABLING FOR GOVERNMENT, MINISTRIES, DEPARTMENTS AND AGENCIES 2013 DOCUMENT DETAILS Security Classification Authority Author Documentation Status Government/Public National Information
Facilities Access Service OVERVIEW OF THE NBN CO FACILITIES ACCESS SERVICE
Facilities Access Service OVERVIEW OF THE NBN CO FACILITIES ACCESS SERVICE NBN Co Limited Overview of the NBN Co Facilities Access Service April 2012 Copyright This document is subject to copyright and
DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
DIGITUS Network & Server Cabinets. UNIQUE Series
DIGITUS Network & Server Cabinets UNIQUE Series Benefits - Server Rack 4-Point locking system front door 3-point locking system rear door Swing handle lock with profile zylinder in front and rear door
BID TABULATION Fiber Optic Cable Materials Bid #0111-147 March 16, 2011 at 11:00 am CDT
1 251,200 LF 2 HDPE-SDR 13.5 with pull tape Unit Price $0.5679 $0.527 $0.593 $0.630 Extended Price $142,656.48 $0.00 $132,382.40 $148,961.60 $158,256.00 2 251,200 LF 2 HDPE-SDR 13.5 without pull tape Unit
Terminating 25-Pair Cable and 4-Pair Cross Connects
Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.
Utilities and existing services
Construction Services Building standards for mechanical and electrical installations Utilities and existing services October 2012 Directorate: Environment Construction Services - Building standards for
IT Services Converged Network Installation Specification:
IT Services Converged Network Installation Specification: Author: Phil Gregory Status: Published Last Modified: 21 August 2015 Last Modified by: Phil Gregory Updates: Version Date (Initial) Comments 1.1401
FITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223
FITNESS FACILITY WIRING SPECIFICATIONS NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223 CONTENTS: - Scope of work Summary - Equipment list - Technical specifications - Map of data
Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
BryComm, LLC -SDD-1901 Cabling Services (per pull) - Labor Only STANDARD TIME The price per cable pull represents all labor to include fishing walls, running cable through modular furniture, terminating,
Cable Installation Project
Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280
Data Center Cabling Design Trends
Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
PRE-OWNED MOBILE / MANUFACTURED HOME PRE-INSPECTION
PRE-OWNED MOBILE / MANUFACTURED HOME PRE-INSPECTION Receipt # Official Use Only Date: Owner name: Phone #: Check One The home is currently located in the following City or County,, and I have attached
Undercarpet Cabling Products Undercarpet Power, Voice and Data Distribution
Undercarpet Cabling Products TE Connectivity Enterprise Networks Warranty Power Distribution Product Coverage* TE Connectivity warrants that all Undercarpet cabling system products within this catalog
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
OWNERS MANUAL CONTENTS: Introduction.. 2. Definitions.. 2. Smartwire.. 4. Computing Network 7. Working diagram. 8. Television Antennas 9
OWNERS MANUAL CONTENTS: Introduction.. 2 Definitions.. 2 Smartwire.. 4 Computing Network 7 Working diagram. 8 Television Antennas 9 File: Owners Information version: Jan13 1 INTRODUCTION Congratulations
1 Campus Cabling Systems Introduction
1 Campus Cabling Systems Introduction This document represents the campus cable and infrastructure standards adopted and supported by the XXXX. All new construction and renovation should conform to these
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
DEPARTMENTAL REGULATION
U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies
LIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
Data Centers and Mission Critical Facilities Operations Procedures
Planning & Facilities Data Centers and Mission Critical Facilities Operations Procedures Attachment A (Referenced in UW Information Technology Data Centers and Mission Critical Facilities Operations Policy)
Emergency Telephone Systems
Standard Issued Date: 22 May 2014 Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the NSW Government and its
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels
TIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
InstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3
2301.1 Scope: Communications and Electronic Systems addressed in this section include:
Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and
Addendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
HARTING Ethernet Cabling 4-poles Overview
Ethernet Cabling 4-poles Overview RJ45 Connectors [on page 8] System cables [on page 10] Distribution modules and Outlets [on page 20] Connectors [on page 22] System cables [on page 24] Panel feed-throughs
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
FIBER OPTIC CABLE PLANT DOCUMENTATION
C H A P T E R 13 FIBER OPTIC CABLE PLANT DOCUMENTATION JIM HAYES Documenting the fiber optic cable plant is a necessary part of the design and installation process for the fiber optic network. Documenting
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT. YOU COULD PUT YOUR FAMILY AND WORLDLY POSSESSIONS IN DANGER!!!
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
Data Centre Solutions
Issue 6 Data Centre Solutions RACKS POWER COOLING MONITORING SECURITY SERVICE & SUPPORT The simple route to the perfect data centre Data centres are complex systems. Software, hardware and IT infrastructure
Electrical Service Guidelines
Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow
Solar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
The AMP NETCONNECT Cabling System Products
The AMP NETCONNECT Cabling System Products About the AMP NETCONNECT Business Unit The AMP NETCONNECT business unit of Tyco Electronics develops, manufactures and supplies a comprehensive range of communications
TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012
TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications
How To Build A T7 Rack For Information Technology
THE NEXT GENERATION RACK FOR INFORMATION TECHNOLOGY THE RACK CABINET FOR INFORMATION TECHNOLOGY T7, THE HI-TECH HEART OF THE BLADESHELTER SYSTEM The real answer to the requirements of: Safety Versatility
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
19" Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted.
19" Data Racks Attractive design and high quality are characteristic. Basic framework is welded from multiple bent metal plate, which assures great rigidity suitable for heavier equipment. All profile
SEAGATE SOFTWARE. About Seagate Software. IBDN Success Stories Technology. Currently, Seagate Software has customers in more than 75 countries
About Seagate Software Seagate Software is an international software corporation headquartered in Scotts Valley, California. Established in 1984 as Crystal Services Inc., Seagate Software was purchased
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
Security Systems Intrusion Alarm
Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted
BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors
C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution
E Series. E Series. Category 6 and 5e. Features
E Series Category 6 and 5e CommScope, world leader in copper and fiber connectivity, offers the E Series product line as the ideal solution to all your infrastructure needs for safe and reliable data transmission.
A. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
Rack Cabinets. Rack Configuration. 19 inch
Rack Cabinets Rack Configuration 19 inch 19 RACK COMPONENTS FEATURES Hallam Manufacturing s range of 19 inch racks and cabinets for today s data/communications installations are designed and manufactured
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
USB 3.0 Cables. Color. Black Black Black Black Black 3021003-03 3021009-06 3021015-10 3021021-16 3021027-16. Black Black Black Black Black
USB.0 CableS USB.0 and backwards compatible for USB.0 and. Supports high speed, 480Mbps Twisted-pair construction reduces cross talk to ensure error free transfer USB A male to USB B male 00-0 007-0 0-09-
Installation Manual For Support Call 01704 807114 or email [email protected]
Installation Manual Hip Smart Hub (Standard BT and BT FTTP Sites) The Home Network Hub houses the Home Owner s Broadband Router and connects the hardwired network ports on that Router to three network
Standard Comms Rooms Specification
Standard Comms Rooms Specification Room Configuration Electrical General Distribution Boards Small Power Lighting Containment Fire Detection General To be defined in the project brief but should meet requirements
Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010)
Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010) I. Introduction This document presents the current Northwestern University
SECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
QUOTATION FOR THE SUPPLY AND INSTALLATION OF FIBER OPTIC CABLES AT THE CIVIC CENTRE AND THE 24HR CENTRE
Your ref. Version 2 Our ref. Marius Britz x7376 202-05-07 e-mail : [email protected] Telephone (03) 249 7000 Fax (03) 243 2550 P.O. Box 4 MIDDELBURG, MPUMALANGA 050 www.stevetshwetelm.gov.za