IT Services Converged Network Installation Specification:
|
|
|
- Norah Byrd
- 9 years ago
- Views:
Transcription
1 IT Services Converged Network Installation Specification: Author: Phil Gregory Status: Published Last Modified: 21 August 2015 Last Modified by: Phil Gregory Updates: Version Date (Initial) Comments /01/2014 (PG) First Draft /05/2015 (PG) Restructure, Updates, Address /08/2015 (PG) Reviewed for publication Document published at: Any comments or queries related to this specification should be directed to Aston IT Services; or telephone
2 Contents Objective... 3 Scope... 3 Approved Contractors... 4 Cabling systems:... 4 Standards... 5 Outlets in the Work Area... 5 Horizontal Cabling System... 6 Containment... 7 Wiring Centres... 8 Connection to the University Backbone Fibre Optics Labelling Labelling Scheme Commissioning and Testing Documentation Warranty Maintenance... 13
3 Objective This document identifies the scope, standards and installation guidelines for extensions and changes to the Universities ICT infrastructure. This is for the purpose of achieving a consistent and reliable installation and operation. This document is intended to be adhered to by all those involved with works in the University which impact the ICT infrastructure. Scope This document provides a system specification of the University s converged IP network. All details apply unless specifically agreed with the authorised representative of the University in advance. In overview the University network comprises: Structured cabling system linking user outlets back to Wiring Centres Wiring Centres that house the active network equipment e.g. switches, UPS Core locations that interconnect the Wiring Centres Resiliency, e.g. switch stacks with dual fibre optic links to the network core This specification covers the design, supply, installation, testing and warranty of: Wiring Centres Category 6 or 6a structured cabling system Containment systems Ethernet Switches Resilient power supply to ICT network equipment Connections to the University Backbone Expansion: The design shall allow for a growth of at least 50% in the number of outlets and The design shall allow for all outlets to be activated by dedicated switch ports. Specific contracts and approved building plans will detail the quantities and locations of equipment e.g. of outlets, wiring centres and cable containment/support. The following is out-of-scope of this specification: Campus Ducting Core Equipment The Universities approved contractor and components shall be used for all works unless by agreement with IT Services Management. This document identifies specific makes and models of equipment that should be used and is correct at the time of issue. These details may change from time to time, resulting in a new issue of this document; suppliers should ensure they have the latest version.
4 Some areas of the University may have specialised requirements for installation etc, such as an Aseptic area or the Aston Academy of Life Sciences; these shall be identified in the specific contracts. All designs must be approved by the ISA department within Aston University prior to installation. Any changes to this specification shall be subject to change control procedures. Approved Contractors The following approved companies shall be used for all works relating to networking installations: Cabling systems: Electron Technical Services Ltd 1ST FLOOR, BLOCK A BRIDGE COURT, BRIDGE STREET, LONG EATON, NOTTINGHAM, NG10 4QQ Tel: Fax: [email protected] These contractor s personnel must: Hold current accreditation for installing the proposed structured cabling system. Hold current BICSI RCDD accreditation Provide documentary evidence of the Manufacturer Accreditation and level.
5 Standards All equipment and materials must comply with the most recent issues and revisions of all relevant British Standards current at the time of tender, and/or such other recognised standards as may be stated. The design of the structured cabling system shall comply with the requirements of BS EN 50173:2011 Information technology - Generic cabling systems. The Quality Assurance provisions applied to the installation shall be compliant with PR BS EN :2009+A1:2011 Information technology - Cabling installation. Installation specification and quality assurance. Installation practices shall be generally compliant with PR BS EN :2009+A1:2011 Information technology - Cabling installation. Installation planning and practices inside buildings and shall be wholly compliant with the installation practices laid down by the system manufacturer of choice. Installation practices shall also meet ISO/IEC 11801:2011 and all applicable local and national codes, standards and ordinances. Please note: The latest edition of any of the above standards (including any amendments) applies. All cables must be manufactured from LSZH (Low Smoke Zero Halogen) materials and shall be flame retardant. Where a conflict exists between these standards, it is the responsibility of the contractor to detail these conflicts to the client prior to installation commencing. Outlets in the Work Area Outlets shall be presented into the work area as an RJ45 connector. The outlet shall have a sprung shuttered cover to prevent the ingress of dust and other contaminants. Outlets may be of the modular or fixed-plate variety and can be provided in single, double or quad arrangements, as agreed in the contract and must meet the relevant standards for the cabling system being installed. All outlets should include cable management facilities as standard.
6 All outlets shall have facilities for labelling and be labelled according to the labelling scheme identified in this document. The labelling must be robust to withstand some abuse; this could be protected by means of a clear plastic window if necessary to protect the label. Horizontal Cabling System The horizontal cabling installation is standardised on the Brand Rex Structured Cabling solution and shall follow all of the manufacturers and industry recommendations for installation e.g. observing bend radius, length, termination, bundling etc. The cabling system must be component and channel level compliant to the full cabling system standard employed i.e. TIA/EIA 568B-1 & 2 and their appendices. The horizontal cabling system shall use all components from the Brand Rex Structured Cabling solution, end-end and independently verified for compliance. The system that shall be used is: Brand-Rex Millennium Cat6Plus LSZH or 10GPlus S/FTP Brand-Rex 1U Cat6Plus 24 port patch panels or 10GPlus 1U 24 Port Patch Panel (use of Brand-Rex ½U 24 Port panels, or 1U 48 port panels, may be used with agreement from IT Services) Brand-Rex Millennium Cat6Plus or 10GPlus grey Fly leads, in a mix of lengths of 1m, 3m or 5m as appropriate to suite the location The horizontal cable system comprises: RJ45 network outlets in the work-area Unshielded Cat 6 twisted pair cable, or shielded Cat 6a Outlets to be cabled back to an appropriate Wiring Centre (WC), WC patch panel presentation to be RJ45, Each patch panel must have its own dedicated cable management bar All cross-connect patch-cords shall be of the matching type for the Patch panels and are to be included, the length of each to be agreed with the University All work-area fly leads are to be provided, for each outlet, the length of each to be agreed with the University, The copper cabling system to be tested and passed for compliance with the relevant cabling standard and a 25 year manufacturer s warranty issued One cable shall be run to each work area outlet. Sheath sharing is not permitted. During and after installation all cables shall be protected to avoid damage.
7 Horizontal cable runs shall be continuous, from network outlets to the patch panel, without joins or splices, except where the use of a consolidation point has been approved. No run shall exceed 90 metres in length. All cables used in the horizontal cable runs shall be flame retardant. Low Smoke, Zero Halogen (LSZH) cables are specified for this installation. LSZH cables shall be compliant with IEC 332-1c as a minimum. The cabling must be kept appropriately separated from any other cables. Ensure that where power and information technology cables are installed in parallel, in accordance with EN at minimum:- Containment All containment systems used shall be appropriate for use with a Cat 6 and Cat 6a cabling systems and observe all relevant guidelines e.g. bend radius. Reuse of any existing containment must be agreed with the University prior to commencement of works. The MK Powerlink dado containment shall NOT be used to carry the cables unless explicitly agreed in advance. The structured cabling system shall be run within its own dedicated containment (or compartment in multi-compartment trunking systems) provided within the building. Where structured cables are installed and supported on cable tray, cables will be secured by broad cable ties at intervals of not more than 600mm horizontally and not more than 300mm vertically. Bundles of cable will not contain more that 24 cables. Strain relief to be provided for all cables at their termination to patch panels or outlets. Cables in cable trays will not be installed to a depth greater than 50mm. Cables will be installed with a minimum of 200mm slack at each end to allow for re-termination; the slack is to be supported in the patch panel equipment cabinet. Within dado containment all internal bend fillets shall be installed in each compartment. All appropriate matching bends shall be used to move around corners and divert vertically. Within two compartment dado containment, data cables shall be run in the data section and the outlet mounted on back-boxes in the same compartment as the power sockets. All back-boxes used to mount outlets (as part of the dado system or direct wall mount etc) shall be more than 35mm deep (non adjustable) to ensure that the cabling system can be installed to observe correct bend radii and be fully warranted. Other surface Containment must be suitably sized not to infringe bend radius requirements.
8 The contractors designing/installing containment shall finalise the containment fully with the data cable installers for suitability and to ensure installation practices for the cable are followed and the system can be fully warranted. Wiring Centres Environmental, electrical, security and safety issues have to be considered in the design and installation of a Wiring Centre (WC). The equipment in a WC (e.g. patching, switches and UPS) should be housed in either cabinets; the specific choice shall be agreed with the University in advance. The layout of equipment in the WC must be agreed with the University prior to installation. Doors to rooms dedicated to a WC shall have the University standard lock fitted. Services and preparation of a WC includes: Installation of the cabinets. Positioning of all equipment such as cabinets must allow sufficient space for safe working access. After equipment (such as switches and UPSs) has been mounted in the cabinets and frames, a minimum clearance of 1m must be provided at the front and rear of the cabinets and frames unless specifically agreed with the University in advance. Safety earth. Installation of appropriate electrical power. Typically this is: o A distribution board in the area with individual breakers, minimum of 2 spare positions after initial installation. o One key switch operated outlet on its own power breaker (rated at least 20A type C), for each load o One fused, non-switched spur outlets on its own power breaker (rated at 20A type B), for each PDU strip in each cabinet Each cabinet/frame o All panels, doors, frames etc to be connected to the safety earth. o Cabinets to be key matched to University standard Suitable air-treatment to avoid excess of temp, humidity etc Suitable lighting. Any windows to have shading applied to prevent direct sunlight. Appropriate security to ensure authorised access only. The entry door into the WC must minimise loss of floor space and maximise the space available for locating the cabinets and frames etc Cable management system, specifics to be approved by the University Suitable anti-static floor preparation. Appropriate level of decoration. Walls, flooring and ceilings to be dust free TO INSERT HERE - ADD ADDITIONAL ROOM REQUIREMENTS FROM ROOM SPEC DOC.
9 The WC s contain electronic equipment and cabling connection strips which are sensitive to the abrasive, clogging etc effects of air-borne dust, therefore air-borne dust must be avoided once such equipment has been installed. Thus cabinets and equipment cannot be installed until all building works have been completed and the area cleaned and secured. The cabinet shall be sized to cater for the growth indicated, as a minimum. Cabinets shall be designed to facilitate ease of access and installation and the maintenance of a controlled bend radius for incoming cables. They will include all vertical & horizontal cable management for copper and fibre cables. Fibre optic cables terminating within the Wiring Centre shall be terminated onto patch panels mounted within the cabinets/frames. Adequate horizontal and vertical cable management must be included for all cables. These should allow easy access to the cables for changes etc and not hinder access to plugs or sight of patch panel indicators/labels. It is anticipated that a minimum of 1U of horizontal cable management shall be required for every 24 ports of copper patch panel. A minimum of 1U of horizontal cable management shall be provided for every 1U of fibre patch panel. Appropriate hardware required to dress and mount the panels shall be supplied. Correct bend radii on the installed cables must be observed. All panels and racks are to be earth bonded in accordance with IEE regulations, good working practice, pren and any applicable local and national codes, standards and ordinances. Plinths are to be provided to cover any cables crossing the floor. It is the contractor s responsibility in siting the racks to ensure that there is adequate airflow and advise if additional ventilation is required into the Wiring Centre. There should be adequate clearance around the racks, to allow access for inspection and maintenance and meet safety requirements. Separation between mains and telecommunications cables shall be maintained in accordance with good working practice and pren50174.
10 Connection to the University Backbone Each stack of switches shall be individually dual-home connected to appropriate campus core nodes, using fibre optic links. Diverse cable routing to the core nodes is preferred, options for this must be identified. All patch cords and fly leads are to be included Fibre Optics All cores shall be terminated onto patch panels in the WC s. An appropriate number of fibres shall be provided to each WC to support the dual-homing of each of the network switch stacks, as identified in the section discussing network switches, with spare capacity for an additional 2 stacks minimum. The contractor shall make allowances for the diverse resilient routing of fibre optic backbone cables, where possible, to enable a service to be maintained in the event of a cable being damaged. The fibre cables shall be BrandRex CST type: OM3 (multi, for intra building routes up to 300m) or OS1 (mono, for >300m and any inter building / external routes) Labelling There is a requirement to include a labelling scheme which will aid the end user in the maintenance and administration of the installed cabling system. Contractors shall make allowance for the labelling of all cables at both ends, and for the full labelling of all switches, frames, patch panels and outlets with a unique circuit identifier. Labelling should be of a high quality and permanently attached to the outlet, frame, patch panel, switch etc (to prevent being picked off ) - hand written labels are not acceptable. Labelling Scheme The objective is that the labelling scheme embeds minimal information relating to physical location; is to be regarded as a type of indirect reference. Room boundaries and naming changes over time; such information in a label could become incorrect and the burden of changing a labelling system is too great. Documentation, via a maintained database, shall identify the actual physical location from the label. Outlets: Outlets shall be labelled with the following four part code to identify the WC they are cabled to:
11 MB06 / C / 06 / 19 One Char Two digit Two digit Building WC ID Patch panel ID Patch Panel Port reference and floor of WC within WC A-Z (1-99) (1-24) The first two parts identify the WC where the outlet is terminated. In this example the outlet is connected to WC C on 6th floor of the Main Building. The next part identifies the specific patch panel within the WC (patch panel no 6). The last part is the port number (19) on the patch panel. Horizontal Cabling Patch Panels: Each patch panel used to terminate the horizontal cabling shall be labelled with a one part code: 06 Two digit Patch Panel ID (1-99) This number identifies the specific patch panel within the WC and starts from 1. Each port on the panel does not need its own label as it is already labelled 1-24 from manufacture. Service Cross-Connect Patch Panels: Where provided each patch panel used to present services shall be labelled with a two part code: DP 06 Two char Two digit Service Identifier: DP Data Panel ID Data Panel (1-99) The number identifies the specific patch panel offering the identified service within the WC and starts from 1.
12 Each port on the panel does not need its own label as it is already labelled 1-24 from manufacture. Cabinets/Frames: Cabinets and frames shall be labelled with the following three part code: MB / 06 / C Two char Two digit One char Building ID Floor of WC WC ID (0-99)(LG+GD) (A-Z) The two letter building identification shall be used e.g. SW South Wing NW North Wing NB Nelson Building MB Main Building Switches: Switches shall be labelled and dns named with the following code: SW MB / 06 / C / S 02 Two char Two digit One char Two digit Building ID Floor of WC WC ID Denote stack Switch ID (0-99) (A-Z) (1-99) Commissioning and Testing The installed systems (e.g. switches and UPSs) shall be commissioned into the University management systems, ensuring configurations are monitored, alarms reported. All system shall be configured and the configurations to meet University standards, policies and local requirements. This shall include: The installed copper cabling system will be thoroughly tested to confirm that the components and installation practices meet the defined standards. Test all copper horizontal and riser cables, following installation, for: pair polarity, crossed pairs, continuity, short circuits, length, attenuation, cross talk (near and far end), PS-NEXT, EL FEXT, PS-ELFEX, Propagation delay, Delay skew. All tests to be carried out in accordance with an agreed methodology. Full records shall be maintained of all testing carried out and the results of the tests. Ensure each pair in each link is tested from both ends and the worst pair results used as the test result.
13 A valid calibration certificate to be provided, which is less than six months old, for each item of test equipment which is brought to site to measure performance data; the calibration certificate may be inspected on site. All cables and components or a random selection will be witness tested. The extent of the witness testing will be at the discretion of the IT Engineer. Rectify each failure identified during testing by replacing the faulty cable or component. Ensure that all personnel who carry out any testing are demonstrably qualified, either by experience or by training for the test equipment to be employed. Documentation The system installation must be documented and be available in paper and machine readable formats detailing: Cabling schematics, Cable records, As installed drawings noting the location of all floor outlets and their circuit identifier, all cable runs to be marked on these drawings, Copper and fibre Cable test results, Patch schedules, Patch frame/cabinet layouts. Warranty The copper cabling system must be provided with a 25 year warranty (minimum), shown by the Cabling System Manufacturer s backed certificate to confirm the installation conforms to the relevant category performance specification. Equipment and system warranty must be clearly stated. Maintenance All equipment must be added to the standard maintenance contract that the University has in place and arranged so that renewal dates are all co-terminus.
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and
Cat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards.
Cat 5, 6 or 7? A University Standard for Structured Wiring. Background isolutions recently formed Incorporates all IT service providers within the University. Focus on all ICT needs of the user and the
Information and Communication Technology Network Cabling Infrastructure Standard
Approved on Dec-2005 by Eugene Formato Manager, Communications Services Last Amended Aug-2009 by Jarren Beveridge Network Engineer, Communications Services Scheduled for Review Jan-2010 Information and
NTU Data Communications Cabling Specification
NTU Networking Standards Document Circulation List NTU Data Communications Cabling Specification Purpose of this Document This document sets out the specification required for NTU data communications cabling
ADC Structured Cabling Solutions
ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution
Structured Cabling, Earthing & Equipotential Bonding
White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,
Accelerating Light. Copper Cabling Solutions. Category 6A
Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity
IT&T Infrastructure Standards
Technology Services IT&T Infrastructure Standards Version 1.5 17 th April 2015 Page 1 Table of contents 1 CHANGE HISTORY... 3 1.1 DOCUMENT HISTORY... 3 1.2 REVIEWERS... 3 1.3 APPROVALS... 3 2 INTRODUCTION...
ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
Category 6 UTP - Cabling System
AMP NETCONNECT Category 6 UTP Cabling System...... real Category 6 Performance, both on Component as well as on System level! Owing to the extreme high performance of the AMP NETCONNECT Category 6 UTP
InstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3
2301.1 Scope: Communications and Electronic Systems addressed in this section include:
Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and
Standard Comms Rooms Specification
Standard Comms Rooms Specification Room Configuration Electrical General Distribution Boards Small Power Lighting Containment Fire Detection General To be defined in the project brief but should meet requirements
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
Cabling Standards Update 2014
Cabling Standards Update 2014 Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of Greek National Committee, CENELEC
Installation Manual For Support Call 01704 807114 or email [email protected]
Installation Manual Hip Smart Hub (Standard BT and BT FTTP Sites) The Home Network Hub houses the Home Owner s Broadband Router and connects the hardwired network ports on that Router to three network
Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.
Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s
ANSI/TIA/EIA-570. 570-A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD
BICS I CABLING INSTALLATION PROGRAM ANSI/TIA/EIA-570 Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD Copyright BICSI, October 1999 -A Revisited 1.1 Purpose standardize
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
How To Set Up A Minipatch System For A Small Office Or Home Use
Issue : 4 Wood Communications Networking Products Catalogue Small Office & Home Solution Small Office / Home Solution Min LAN Comms Cabinets - Multimedia Panel - Soho Ethernet Switches - Multiroom Audio/Video,
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
Construction Services. Building Strategy. Standards for Wiring Telecommunications Networks in Cornwall Council Buildings. Version 4.
Construction Services Building Strategy Standards for Wiring Telecommunications Networks in Cornwall Council Buildings Version 4.2 April 12 th 2012 Environment Building Strategy Standards for Wiring Telecommunications
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
Structured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
TIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)
Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems) Introduction The purpose of this document is to: 1) provide background information beneficial to specifiers
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors
C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution
How To Make A Fibre Cable For A Data Centre
LANmark-OF Fibre Optic Solutions for Data Centres Complex Data Centres require fibre solutions CORE SWITCH ACCESS SWITCH SERVER SAN SWITCH LANmark-OF Slimflex Patch Cords LANmark-OF Single Mode LANmark-OF
A guide to connecting to fibre optic networks for homeowners, architects, builders and developers.
A guide to connecting to fibre optic networks for homeowners, architects, builders and developers. Chorus is New Zealand s largest telecommunications utility company. We maintain and build the local access
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING
SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
Terminating 25-Pair Cable and 4-Pair Cross Connects
Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.
Copper Pre-terminated Assemblies
Copper Pre-terminated Assemblies Copper Pre-Terminated Trunk Assemblies Overview Copper Pre-Terminated trunk assemblies are the perfect solution for Enterprise / Premise & Data Centre applications where
Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair
Presentation; Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair 5 th April 2010 Paul Mathews MInstSMM, CCNA, MIEEE Global Channel Manager Media Types Physical Layer Cabling;
Cable Installation Project
Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA
Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications
3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition
Data Center Cabling Design Trends
Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:
STANDARDS FOR STRUCTURED CABLING FOR GOVERNMENT, MINISTRIES, DEPARTMENTS AND AGENCIES
STANDARDS FOR STRUCTURED CABLING FOR GOVERNMENT, MINISTRIES, DEPARTMENTS AND AGENCIES 2013 DOCUMENT DETAILS Security Classification Authority Author Documentation Status Government/Public National Information
Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc [email protected]
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc [email protected] J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
Communications Infrastructure Standards & Specifications
Communications Infrastructure Standards & Specifications Copper and Optical Fibre Cabling Specification Revisioning version date Author 1.0 2/4/2013 Sean McHugh 1.1 9/7/2013 Sean McHugh Page 1 Table of
Networks. The two main network types are: Peer networks
Networks Networking is all about sharing information and resources. Computers connected to a network can avail of many facilities not available to standalone computers: Share a printer or a plotter among
LIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
What is a Datacenter?
What is a Datacenter? Telecom Room Primarily Cross Connect Equipment and switches. Computer room A room whose primary function is to house computer equipment. (Servers, Storage) 5 or less cabinets Small
SECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
Excel Pre-terminated Copper and Fibre Optic Systems
Excel Pre-terminated Copper and Fibre Optic Systems Excel is a world-class premium performing end-to-end infrastructure solution - designed, manufactured, supported and delivered - without compromise.
DATA CENTRES POWERED BY EXCEL
DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,
Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer
SYSTIMAX Solutions Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer Issue 2 Draft 1 June 2010 Contents Overview 3 GigaSPEED X10D Guaranteed Channel Performance
Information Communications Technology Structured Cabling Infrastructure Guidelines
Information Communications Technology Structured Cabling Infrastructure Guidelines (Version 2.2, Nov 2011) Network Team I.T. Infrastructure Division Information Services The University of Edinburgh James
DIGITUS Network & Server Cabinets. UNIQUE Series
DIGITUS Network & Server Cabinets UNIQUE Series Benefits - Server Rack 4-Point locking system front door 3-point locking system rear door Swing handle lock with profile zylinder in front and rear door
DATA CENTER CABLING DESIGN FUNDAMENTALS
DATA CENTER CABLING DESIGN FUNDAMENTALS Telecommunications Cabling Infrastructure Requirements according to the Availability Classes I-IV of Abstract INTRODUCTION With the completion by end of 2015, the
6000 Series Buccaneer
Robust, instant connections for harsh environments 6000 Series Buccaneer - circular connectors that combine the ease of use of a push/pull coupling mechanism with proven environmental sealing. Available
DESIGN GUIDELINES. Local Area Network
DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA
UT Southwestern Medical Center Information Resources Cable Installation Standard
UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system
Cat7/Class F New Installation Concept New infrastructure. Handbook
Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle
TCTC Cabling Specifications
TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,
1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
T1 Backhaul Connectivity Solution All Products :: Application Note
Telect 1 RU Customer Interface Panel (CIP) Enables Demarcation, Remote Circuit Maintenance and Trouble Isolation at the Backhaul Node The Application: T1 Demarcation and Testing in Backhaul Environments
Technical Information and System Application Guide
Technical Information and System Application Guide Table of Contents A STRUCTURED CABLING DESIGN CONCEPT B BACKBONE CABLING C HORIZONTAL DISTRIBUTION D CABLING SPECIFICATIONS E APPLICATION DESIGNS F TECHNICAL
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS
. HARTING RJ INDUSTRIAL ETHERNET CONNECTORS Ethernet is is coming up to standard industrial interface. Therefore, automation devices such as controllers, sensors and actuators feature possess on one or
Cabcon. Data Centre Solutions. www.cabcon.co.uk. an acal group company UK +44 (0)1189 122980 IRE (00353) 1 629 2640
Data Centre Solutions www.cabcon.co.uk UK +44 (0)1189 122980 IRE (00353) 1 629 2640 About Us are a specialist distributor of copper, fibre, power, security, active and cable management products for the
Standard Buccaneer - Ethernet
IP6 rated compliant PUR jacket on cable Shielded system shielded coupler Shroud on RJ45 Screw coupling Rewireable flex connector PCB mounted panel connector IDC termination panel connector Earth lead version
Facilities Access Service OVERVIEW OF THE NBN CO FACILITIES ACCESS SERVICE
Facilities Access Service OVERVIEW OF THE NBN CO FACILITIES ACCESS SERVICE NBN Co Limited Overview of the NBN Co Facilities Access Service April 2012 Copyright This document is subject to copyright and
ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER
ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect Introduction
Emergency Telephone Systems
Standard Issued Date: 22 May 2014 Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the NSW Government and its
Building Telecommunications Infrastructure Requirements
Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,
AMP NETCONNECT Data Center Cabling Solutions
AMP NETCONNECT Data Center Cabling Solutions Modern business and administrative environments require today more and more sophisticated IT services, what leads to an increasing demand for data provision
Enable Networks UFB Services Agreement Service Description for Central Office and POI Co-location Service
Enable Networks UFB Services Agreement Service Description for Central Office and POI Co-location Service 1 Interpretation 1.1 The Central Office and POI Co-location Service described in this Service Description
Migration Strategy for 40G and 100G Ethernet over Multimode Fiber
Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year
Policy Title-Aquia Data Center Operational Policy & Procedure. Policy ID - TSD-ADC001. Version - Version: 1.0. Supersedes Version 1.
Policy Title-Aquia Data Center Operational Policy & Procedure Policy ID - TSD-ADC001 Version - Version: 1.0 Supersedes Version 1.0 Review Date One (1) year from effective date. Policy & Procedure - Provides
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect Introduction The primary
Spec Sheet. Cisco R42610 Rack CISCO SYSTEMS PUBLICATION HISTORY 170 WEST TASMAN DR. SAN JOSE, CA, 95134 REV A.6 DECEMBER 9, 2014 WWW.CISCO.
Spec Sheet CISCO SYSTEMS PUBLICATION HISTORY 170 WEST TASMAN DR. SAN JOSE, CA, 95134 REV A.6 DECEMBER 9, 2014 WWW.CISCO.COM Overview................................................ 3 Rack Certifications
Screened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
Communications Cabling Installation Standards
Communications Cabling Installation Standards 2 Contents Purpose... 4 Version Control... 5 Reference Documents... 6 Definitions and Abbreviations... 7 DEFINITIONS... 7 WAN services into DoE Sites... 8
Intelligent Cable Management Systems
Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication
SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING
PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation
SYSTIMAX Solutions. GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions. www.commscope.
SYSTIMAX Solutions GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions www.commscope.com The SYSTIMAX GigaSPEED X10D Shielded Solution provides unprecedented performance
Power Separation Guidelines for SYSTIMAX Installations
SYSTIMAX Solutions Power Separation Guidelines for SYSTIMAX Installations Design and installation guidelines August 2011 www.commscope.com 1.0 General These guidelines are based on extensive testing and
BX7000 Multi-Access Gateway Getting Started Guide
BX7000 Multi-Access Gateway Getting Started Guide This guide provides instructions on connecting the Juniper Networks BX Series 7000 Multi-Access Gateway to a network. For more information, see the BX7000
Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8
Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,
Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD
Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,
Rack & Stack 123 TM. Enterprise Education Government Telecommunications Service Providers Tel: 408-586-8800
Rack & Stack 123 TM Enterprise Education Government Telecommunications Service Providers Tel: 408-586-8800 Rack & Stack 123 TM Introduction Simplicity Scope of Work Rack & Stack 123 TM Benefits 2 toll-free:
Enable Networks UFB Services Agreement Service Description for Central Office and POI Co-location Service
Enable Networks UFB s Agreement Description for Central Office and POI Co-location 1 Interpretation 1.1 The Central Office and POI Co-location described in this Description will be available from the date
TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE
TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means
Data Centers and Mission Critical Facilities Operations Procedures
Planning & Facilities Data Centers and Mission Critical Facilities Operations Procedures Attachment A (Referenced in UW Information Technology Data Centers and Mission Critical Facilities Operations Policy)
SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
Flexible and safe solutions, for decades. Cables for alarmand safety systems
Flexible and safe solutions, for decades. Cables for alarmand safety systems 2 We offer the widest range of cables on the market for every kind of installation. It s all about reliability. It is always