ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

Size: px
Start display at page:

Download "ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS"

Transcription

1 ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered fire suppression system using CO 2 as extinguishing agents and where the flexible pneumatic, thermally sensitive tubing is used as a detection device. The thermally sensitive tubing shall be installed as linear detection capability before the suppression takes place by the nozzles. The pre-engineered fire suppression system shall be used to protect enclosed hazard such as electrical board, cabinets and compartment (enclosed) containing electrical or electronic components. II. APPLICABLE STANDARDS AND PUBLICATIONS The FireDETEC pre-engineered system shall be designed, installed, tested and maintained in accordance with applicable requirements set forth in the latest edition of the Local Authorities Having Jurisdiction. Mass of agent calculation method must follow the codes and standards stated below: A. VdS CO2 Fire Extinguishing Systems, Planning and Installation B. CEA CO2 Systems - Planning and Installation C. APSAD R13 Installation of Automatic Gaseous Extinguishing Systems The standards listed, as well as other applicable codes, standards, and good engineering practices shall be used as minimum calculation standards. I. REQUIREMENTS The suppression system installation shall be made in accordance with the drawings, specifications and applicable standards. Should a conflict occur between the drawing and specifications, the specifications shall prevail.

2 II. EXCLUSIONS The work listed below shall be provided by others, or under other sections of this specification: A. 120 VAC or 220 VAC power supply to the system control panel. B. Interlock wiring and conduit for shutdown of Heating, Ventilation and Air-Conditioning (HVAC), dampers and/or electric power supplies, relays or shunt trip breakers. C. Connection to local/remote fire alarm systems or listed central alarm station(s). III. QUALITY ASSURANCE A. MANUFACTURER 1. The valves, cylinders, detection tubing, ends of line, discharge tubing, fittings and nozzles shall be supplied by CEODEUX-EXTINGUISHER VALVES TECHNOLOGY S.A. or one of its direct representatives. 2. The name of the brand FireDETEC or the Rotarex three-star logo shall appear on all major components. 3. All devices, components and equipment shall be approved by the CEODEUX- EXTINGUISHER VALVES TECHNOLOGY S.A. 4. All devices, components and equipment shall be new, standard products of the manufacturer s latest design and suitable to perform the functions intended. B. INSTALLER 1. The installing contractor shall be trained by the supplier to design, install, test and maintain fire suppression systems and be in possession of the corresponding training certificate (valid 3 years). 2. The installing contractor shall be an experienced firm regularly engaged in the installation of automatic CO2, or similar, fire suppression systems in strict accordance with all applicable codes and standards. 3. The contractor shall specifically prepare plans according to the common standards and easily reproducible. These plans will show the quantity, location, and marking of all system components. Included shall be a description and routing of all piping / tubing. Care should be taken to locate all agent storage containers as close to the protected area as possible to ensure complete liquid discharge of the suppression agent within 60 seconds.

3 4. The installing contractor shall have access to a CO2 recharging station. The installing contractor shall provide proof of this ability to recharge the largest CO2 system within 24 hours. 5. The installing contractor shall be an authorized stocking distributor of the CO2 system equipment so that immediate replacement parts are available from inventory. SECTION 2 TECHNICAL REQUIREMENTS I. SYSTEM DESCRIPTION AND OPERATION A. The FireDETEC indirect high pressure (IHP) pre-engineered extinguishing system is used for total flooding applications. Total flooding protection is applicable to enclosed special hazards such as rooms or space containing flammable liquid, electrical equipment, records, or other combustibles where the agent may be used for extinguishment. The hazard area must have no outside air flow present in order to successfully achieve the extinguishing concentration within the enclosure. B. The system shall provide a minimum agent design concentration, as defined by VdS Directive 2093, in all areas and/or protected spaces. The system should be designed to discharge its contents in 60 seconds or less. Final concentration inside the room shall not exceed 5% for normally occupied spaces. Concentration may vary depending on the Authorities Having Jurisdiction (AHJ) but may never be less than the one defined by VdS Directive C. The system shall be complete according to the design manual. It shall include all system components, all detection equipment, agent storage cylinders, discharge nozzles, pipe and fittings, manual release, audible and visual alarm devices, caution/advisory signs, functional checkout and testing, training and all other operations necessary for a functional Fire Suppression System for use with CO2. D. The FireDETEC systems are indirect automatic type systems which utilize flexible, pneumatic, thermally sensitive tubing to activate the system. This tubing is connected to the discharge valve assembly and is pressurized with nitrogen along with the cylinder contents. When the pressure in this tubing is vented, the valve piston moves up, the valve opens and the extinguishing agent is discharged through a separate piping network. There are three ways of venting the pressure in the tubing in order to actuate the system:

4 - Manual operation by use of end of line manual actuator - Electrical operation by use of end of line solenoid actuator - Automatic operation when a sufficient temperature is reached to burst the tubing E. The Installation and Maintenance Manual FireDETEC Pre-Engineered CO2 System Kit for Electrical Cabinets, describes the design, installation, usage, maintenance, and limitations for these systems. These systems are to be designed, installed, used, and maintained explicitly as described in the system manual identified above. II. MATERIAL AND EQUIPMENT A. GENERAL REQUIREMENTS 1. The FireDETEC pre-engineered fire suppression system materials and equipment shall be standard products of the supplier s latest design and suitable to perform the functions intended. When one or more pieces of equipment must perform the same function(s), they shall be duplicates produced by one manufacturer. 2. The extinguishing system unit shall be designed to operate between -4 F (-20 C) and 130 F (55 C). B. CO2 STORAGE 1. Each system shall have its own cylinder of CO2. 2. Systems shall be designed in accordance with the manufacturer s guidelines. 3. Each supply shall be located out of the hazard area, as near as possible, to reduce the amount of pipe and fittings required to install the system. 4. The FireDETEC indirect pre-engineered fire suppression system shall suitable for applications where the cylinder ambient storage temperature is between -4 F (-20 C) and 130 F (55 C). 5. The FireDETEC indirect pre-engineered extinguishing system is available in six capacities, each having its own article number. Details are provided in the table below. System Model Number Digital Measuring System Max. Fill, Kg Discharge Valve Part Number Discharge Valve Outlet, In. B No 2 B ,7x1/14 SI B No 5 B ,7x1/14 SI B No 10 B ,7x1/14 SI

5 B No 10 B ,7x1/14 SI B No 20 B ,7x1/14 SI B No 30 B ,7x1/14 SI B No 50 B ,7x1/14 SI B Yes 2 B ,7x1/14 SI B Yes 5 B ,7x1/14 SI B Yes 10 B ,7x1/14 SI B Yes 10 B ,7x1/14 SI B Yes 20 B ,7x1/14 SI B Yes 30 B ,7x1/14 SI B Yes 50 B ,7x1/14 SI 6. CO2 cylinders shall be π marked, in accordance with Directive EN 2010/35/EU: Transportable Pressure Equipment Directive (TPED) 2010 and ADR/RID: A complete traceability system shall be set up and the following documents shall be accessible for all cylinder batch series: - Certificate of conformity of manufacture according to Directive. 2010/35/EU and ADR/RID Thermal control report from the cylinder supplier including information on the heat treatment, compliance with heat parameters and results of the material tests. - Material test report including results of the material tests, impact tests, bend tests and bursting tests. - Ultrasonic test results. - Hydraulic test report. C. VALVE 1. The valve shall be made of brass, equipped with a pressure gauge to monitor the system pressure, with a ball valve interfacing the tubing and the cylinder, and with a burst disc for protection against over pressure. 2. Each discharge and filling port shall be fitted with hexagonal safety nuts for safety purposes during transportation and intended to prevent uncontrolled discharge of a cylinder in the event of accidental system activation. 3. All valves shall be delivered with a safety clip preventing from unauthorized manipulation of the ball valve when sealed.

6 4. A contact reed device shall be mounted on each safety clip of ball valves when the system is armed. It shall generate an electric signal in case of unauthorized manipulation of the sealed ball valve. 5. All FireDETEC valves shall be π marked, in accordance with Directive EN 2010/35/EU: Transportable Pressure Equipment Directive (TPED) All valves shall be tested against leakage prior to be validated for sales. The maximum leak rate authorized shall be 5x10-6 mbar.l/s. 7. A complete traceability system shall be set up and an inspection certificate 3.1 according to EN 10204:2004 shall be available on demand for all valve bodies and give the following information: - Chemical Analysis - Tensile strength test results - Adjustement of regulator verification - External leak tightness test results - Internal leak tightness test results - Dimensional and visual inspection, Cleanliness, Identification and marking control 8. The valve must present a digital measurement port, in order to get a signal continually indicating the CO2 quantity inside the cylinder (for monitoring and maintenance). The valve shall be able to generate an alarm signal when the quantity of CO2 goes above a defined level, chosen by the end user. D. MOUNTING BRACKETS 1. The cylinder wall mounting brackets shall be in powder coated steel and must be used to mount the cylinder in vertical position. 2. Cylinders and brackets shall be arranged to allow cylinder removal. E. BURST DISC 1. Burst disc shall be provided to protect the cylinders against overpressure. 2. A traceability system shall be set up for all burst discs, and linked to valves where they re mounted on. F. PRESSURE GAUGE

7 1. Each system shall have a pressure gauge on its detection line to indicate internal sensor tubing pressure. The pressure gauge shall be color coded to display the acceptable operating range, under and over pressure range. 2. Each system shall have a pressure switch plugged on its detection line to provide electrical supervision of the sensor tubing pressure, where the system requires digital monitoring. The low pressure switch shall be wired to an alarm device to provide an audible and visual supervisory condition signal in the event the sensor tubing pressure drops below 8 bar (+/- 0,3 bar) of working pressure. 3. Pressure switch shall be easily assembled and disassembled when the cylinder is pressurized. G. END OF LINE (EOL) 1. The End of Line (EOL) shall be required to pressurize the thermal activation tubing. 2. EOL Manual Actuator shall be used where the system shall be manually activated and without external power require. 3. EOL Manual Actuator shall use piston technology. No diaphragm technology (or technologies requiring replacement of components after actuation) shall be used. 4. EOL Manual Actuator shall be provided with a seal or other device to minimize the potential for accidental discharge. 5. EOL Solenoid Actuator (an electro mechanical device) shall be used where the system required relay signal to actuate electrically from control panel or other electric signal. H. LINEAR THERMAL DETECTOR AND ACTUATION TUBING 1. Linear Thermal Detector and Actuation Tubing shall be designed to meet the following requirement: - Max. Working pressure 20 bar (at 20 C) - Internal diameter 4 mm - Outside diameter 6 mm - Temperature range - 30 C C - Permeability: min mbar. l/s (100% Helium testing) 2. The sensor tubing shall be made of multiple layers for enhanced resistance to UV and chemicals. 3. The week and year of production shall be marked on the sensor tubing. 4. The sensor tubing should be CE compliant, according to construction products directive

8 5. The compatibility between most widespread chemicals and sensor tubing shall have been tested and results shall be accessible to end-users. 6. All devices and equipment shall be tested and validated by UL and FM during the certification process of complete systems. The following tests shall have been processed and validated: - One year leakage test, in accordance with FM Approvals - Air-Oven Aging Test, in accordance with FM Approvals and UL Day Extreme Temperature Leakage Test, in accordance with FM Approvals - Corrosion Salt Spray, in accordance with ASTM B117, Standard for Salt Spray Testing. 7. The Linear Thermal Detector shall be validated and considered as a mean of detection by UL. I. DISCHARGE NOZZLE 1. The discharge nozzle used to control the flow of and distribute the agent into the hazard area shall be stainless steel construction. J. PIPING REQUIREMENT 1. Piping must be stainless steel pipe. 2. Distribution piping and fittings shall be installed in accordance with the manufacturer s requirements and approved piping standards and guidelines. All distribution piping shall be installed by qualified individuals using accepted practices and quality procedures. All piping shall be adequately supported and anchored at all directional changes and before nozzle locations. The piping shall be laid out to give maximum flow and to avoid possible mechanical, chemical or other damage. Installation shall follow drawings as closely as possible. System designer must be consulted for anything other than minor deviations in pipe routing. 3. The discharge line shall be connected to the ground to avoid the accumulation of static electricity during discharge. K. DISCHARGE PIPE FITTINGS 1. Pipe fittings shall be compression tube fittings only made of stainless steel 316L, according to ASTM A276 and ASTM A182. They shall have a minimum working pressure of 4350 psi (300 bar). Temperature ratings of the fittings must not be exceeded.

9 III. SEQUENCE OF OPERATION The system shall be designed and installed such that it activated the discharge valve by any one of the following: A. MANUAL ACTUATION VIA MANUAL RELEASE VALVE The pre-engineered Fire suppression system can be manually activated by installing the manual release device at the end of the linear sensor tubing. The manual release device shall depressurize the linear sensor tube and open the valve to activate the CO2 discharge through the discharge nozzle installed within the protected area. Pressure switch is activated and opens (or closes) electric contacts to switch on/switch off electric devices. B. ELECTRIC ACTUATION VIA ELECTRIC RELEASE DEVICE The pre-engineered Fire suppression system can be electrically activated by installing the solenoid actuator at the end of the linear sensor tube. The electro-mechanical device allows actuation of the pre-engineered Fire suppression system from control panel or other electronic sensor. C. AUTOMATIC ACTUATION VIA TEMPERATURE SENSITIVE TUBING The system automatically operates when the thermal temperature sensitive tubing installed as linear detection capability bursts because of heating. Heat or direct flame impingement during a fire situation will cause the tubing to rupture. The tubing ruptures at the hottest point along its entire length, and then the CO2 is discharged through the piping network and nozzles to extinguish fire. Pressure switch is activated and opens (or closes) electric contacts to switch on/switch off electric devices. SECTION 3 DOCUMENTATION AND TESTING I. SYSTEM INSPECTION AND CHECKOUT Upon completion of installation, a meeting shall be held at the site with the contractor. Equipment supplier and owner personnel shall be present. The contractor shall familiarize owner s personnel with system components, system functions, and recommend procedures. The contractor will provide the owner with a complete operation and maintenance manual as well as written summary of any functional tests conducted.

10 The check-out procedures is intended to represent the minimum requirement for the extinguishing portion of the system. Additional procedures may be required by the applicable governmental or regulatory authorities. A. COMPARTMENT (HAZARD) AREA CHECK A good review of the hazard area shall be made. Certain aspects about the hazard may have changed, or been overlooked, which could affect overall system performance. B. AREA CONFIGURATION The hazard area dimensions shall be checked against those shown on the system plan(s). If the area volume or geometry has changed, the agent weight shall be recalculated and compared with the agent weight supplied. The area shall also be checked for bulkheads or movable partitions, which have been added or changed. If partitions have been added, installer shall check to see that all areas within the compartment still receive adequate agent distribution. C. CONTAINERS 1. Installer must check to ensure all cylinders and brackets are securely fastened. 2. Installer must check inside pressure of all containers. It can be measured directly through the digital measurement port of the valve. 3. Installer must verify that cylinders of correct weight and pressure are installed in accordance with the design drawings. E. AUXILIARY FUNCTIONS Operation of auxiliary functions such as door closures, damper closures, air handling shutdown, etc. shall be verified when the pressure switch is activated. II. TRAINING REQUIREMENTS Prior to final acceptance, the installing contractor shall provide operational training to each shift of the owner s personnel. Each training session shall include manual and (optional) abort functions, trouble procedures, supervisory procedures, auxiliary functions and emergency procedures. The following shall be included in the contractor s quotation: A. Duration of training B. Location of training (on site if feasible)

11 C. Material covered and training aids available III. MAINTENANCE The maintenance procedures and intervals are indicated in the The Installation and Maintenance Manual FireDETEC Pre-Engineered CO2 System Kit for Electrical Cabinets, and are meant to represent the minimum requirements for FireDETEC CO2 systems. These procedures do not preclude those required by the applicable governmental or regulatory authority. More frequent service intervals may be necessary if systems are installed in more severe service applications. A regular maintenance program must be established for the continuous operation of all fire suppression systems. A periodic maintenance program shall be established and followed. A maintenance log must be maintained for ready reference. The log must include the following accumulated data: A. Inspection Interval B. Inspection procedure performed C. Maintenance performed as a result of the inspection D. Name of inspector performing the task Any time rust or corrosion is found on a fire suppression cylinder it should be taken out of service and replaced. IV. INSTALLATION Installation procedures shall be performed in accordance with The Installation and Maintenance Manual FireDETEC Pre-Engineered CO2 System Kit for Electrical Cabinets, by fire protection personnel qualified and trained by CEODEUX Extinguisher Valves Technology S.A. in accordance with existing regulations, rules and guidelines including requirements of the Governmental and/or Local authority and other regulatory authorities. V. WARRANTY System shall be warranted for parts and labour for not less than a period of one (1) year from date of installation. The contractor shall specify the maintenance to be performed during the warranty period to maintain warranty conditions. The standard life time for the tube must be (5) years under the normal operating condition and within the stated specification of the tubing.

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section

More information

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this

More information

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in

More information

FIRE DETECTION AND FM-200 SUPPRESSION SYSTEM

FIRE DETECTION AND FM-200 SUPPRESSION SYSTEM FIRE DETECTION AND FM-200 SUPPRESSION SYSTEM A. SCOPE: This specification outlines the requirements for a cross-zoned detection and total flooding FM-200 fire suppression system. The work described in

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

Alarm and Detection/Suppression

Alarm and Detection/Suppression Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

Certificate of Conformity Certificate num. Registration date Version Valid until

Certificate of Conformity Certificate num. Registration date Version Valid until CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 5 Issued by Product designation Thorn Security, FM-200, engineered gaseous 'total flooding',

More information

Recommended Practice for Installation of Transit Vehicle Fire Protection Systems

Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around

More information

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC) Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC) VPS 504 S06 (120 VAC) is: CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter R-15 (Canada) UL

More information

Custom configuration such as modified angle dimensions, other flange standards, 3-way function, alternative materials.are available on request.

Custom configuration such as modified angle dimensions, other flange standards, 3-way function, alternative materials.are available on request. LEAKVALVE: HIGHLIGHTS The core of this valve is a diaphragm in stainless steel 316L, gold plated. Robust, it cannot be damaged with any normal methods. The dead volume is kept as small as possible. There

More information

Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230

Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec

More information

NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY

NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY Presented by: James Goerl Metro Protection Systems, Inc. jgoerl@metroprotectionsystems.com Agenda Introduction & Learning Objectives History

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

Transformer Deluge Systems

Transformer Deluge Systems Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is

More information

Integrated Custom Systems

Integrated Custom Systems Integrated Custom Systems Compact panels Standard Manifolds & Assemblies Electronic pressure control Custom manifolds & Assemblies Automated test benches S t r e a m l i n e y o u r p r o c e s s Complete

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE

FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE ACCEPTANCE INSPECTION AND TESTING PROCEDURE Wet Pipe Sprinkler Systems...2 Dry Pipe Sprinkler Systems...2 Clean Agent Fire Extinguishing System...4 Total Flooding Systems...4 Fire Dampers...5 Smoke Dampers...5

More information

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed

More information

TECHNICAL DATA. Dry 122a. November 12, 2013

TECHNICAL DATA. Dry 122a. November 12, 2013 Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model

More information

System Accessories Pricing. Page 0 Effective 7/02

System Accessories Pricing. Page 0 Effective 7/02 System Accessories Pricing Page 0 Effective 7/02 Firetrace Tubing 200005 Firetrace Detection Tubing (FDT) (Per Foot) (Available in continuous lengths up to 333 ft.) Accessories 400001 400004 400061 400060

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

167D Series Switching Valves

167D Series Switching Valves June 2011 167D Series Switching Valves P1185 P1184 167D TWO-WAY SWITCHING VALVE 167DA THREE-WAY SWITCHING VALVE Figure 1. 167D Series Switching Valves Introduction The 167D Series switching valves are

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

Fire Alarm System Monitoring - CAN/ULC-S561-03

Fire Alarm System Monitoring - CAN/ULC-S561-03 Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

KNC Model 3666 Automatic Pressure Calibration System

KNC Model 3666 Automatic Pressure Calibration System KNC Model 3666 Automatic Pressure Calibration System Product Description The Model 3666 Automatic Pressure Calibration (APC) System by King Nutronics Corporation is a portable secondary standards laboratory

More information

Integrated Fire Protection System. Owner's Operation and Maintenance Manual Engineered Novec 1230 500 Psi

Integrated Fire Protection System. Owner's Operation and Maintenance Manual Engineered Novec 1230 500 Psi 1230 Owner's Operation and Maintenance Manual Engineered Novec 1230 500 Psi Remotely Controlled May 2012 Page ii 1230 Copyright 2009-2012 FIREFLEX Systems Inc. All Rights Reserved Reproduction or use,

More information

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions

More information

APPENDIX 2-3 PCAPP EDS INSPECTION LOG SHEETS

APPENDIX 2-3 PCAPP EDS INSPECTION LOG SHEETS APPENDIX 2-3 PCAPP EDS INSPECTION LOG SHEETS Pueblo Chemical Depot Pueblo Chemical Depot (This page intentionally left blank.) PCAPP EDS Daily (When in Use) Operational Inspection Checklist EXAMPLE Inspected

More information

IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR E Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G IMO Ref. T4/4.03 MSC/Circ.848 8 June 1998 REVISED GUIDELINES FOR

More information

2014 Limited Plan Submittal Checklist

2014 Limited Plan Submittal Checklist City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

Element D Services Plumbing

Element D Services Plumbing Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

Accumulators and Receivers

Accumulators and Receivers aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding Accumulators and Receivers Catalog C-1, October 2007 Page 2 / Catalog

More information

S GATE KNIFE GATE VALVE WITH PNEUMATIC ACTUATOR

S GATE KNIFE GATE VALVE WITH PNEUMATIC ACTUATOR MAIN FEATURES The pneumatic S GATE knife gate valve is intended for the automatic shut off of pipes of the heavy fluids like slurries and powders. The main fields of application are the water treatment,

More information

INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303

INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303 WATER MIST HAND PORTABLE FIRE EXTINGUISHERS Model B270 ¾ Gallon Model B272 2 ½ Gallon INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 6303 All fire extinguishers should be installed, inspected

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Series 510 Submersible Level Transmitters

Series 510 Submersible Level Transmitters Series 510 Submersible Level Transmitters The Series 510 Submersible Level Transmitters are solid state instruments designed for direct submergence into many types of liquid for quick, accurate and reliable

More information

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS INTRODUCTION Rupture discs are often used as primary pressure relief devices and to isolate pressure relief valves. When used as a primary pressure relief

More information

FIRE DETECTION/INERGEN SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS

FIRE DETECTION/INERGEN SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS PART 1 - GENERAL FIRE DETECTION/INERGEN SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS 1.01 DESCRIPTION OF WORK: A. Design and installation of an engineered fire detection and INERGEN total flooding, gaseous

More information

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use. Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections

More information

FOAM CHAMBER MODEL - FC

FOAM CHAMBER MODEL - FC FOAM CHAMBER MODEL - FC TECHNICAL DATA : MODEL SIZE WORKING PRESSURE FC 50, 65, 80, 100 &150 NB inlet Minimum 2.8 Kg. / sq. cm. (40 PSI) Maximum 7 Kg. / sq.cm. (100 PSI) FLANGE CONNECTION ANSI B16.5 Class

More information

STORED PRESSURE STAINLESS STEEL

STORED PRESSURE STAINLESS STEEL STORED PRESSURE STAINLESS STEEL WATER FIRE EXTINGUISHERS Model 240-2-1/2 Gallon OWNER'S SERVICE MANUAL NO. 05601 INSPECTION, MAINTENANCE AND RECHARGE All fire extinguishers should be installed, inspected

More information

VdS 2100-09en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS 2100-09en : 2011-05 (01)

VdS 2100-09en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS 2100-09en : 2011-05 (01) VdS Guidelines for water extinguishing systems VdS 2100-09en Requirements and test methods VdS 2100-09en : 2011-05 (01) Publishing house: VdS Schadenverhütung GmbH Amsterdamer Str. 172-174 50735 Köln,

More information

HIGH PRESSURE TECHNOLOGY HYDRAULICS PNEUMATICS TESTING EQUIPMENT

HIGH PRESSURE TECHNOLOGY HYDRAULICS PNEUMATICS TESTING EQUIPMENT HIGH PRESSURE TECHNOLOGY HYDRAULICS PNEUMATICS TESTING EQUIPMENT MAXIMATOR GmbH 2 MAXIMATOR has an extensive know-how concerning concept, development, construction and manufacturing of test benches and

More information

Morrison Bros. Co. General Product Specifications

Morrison Bros. Co. General Product Specifications Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage

More information

NATIONAL FIRE ALARM AND SIGNALING CODE

NATIONAL FIRE ALARM AND SIGNALING CODE GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

SELECTION, APPLICATION AND MAINTENANCE

SELECTION, APPLICATION AND MAINTENANCE DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine

More information

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Arapahoe County Residential Water Heater Installation and Inspection Guide

Arapahoe County Residential Water Heater Installation and Inspection Guide Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

COMITÉ EUROPÉEN DES ASSURANCES

COMITÉ EUROPÉEN DES ASSURANCES COMITÉ EUROPÉEN DES ASSURANCES SECRETARIAT GENERAL 3bis, rue de la Chaussée d'antin F 75009 Paris Tél. : +33 1 44 83 11 73 Fax : +33 1 44 83 11 85 Web : cea.assur.org DELEGATION A BRUXELLES Square de Meeûs,

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities

More information

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Ergo-Pro Single Line Solar Station Installation and Operating Instructions Rp 3/4 Ergo-Pro Single Line Solar Station Installation and Operating Instructions Item No Pump type 677.21.70 WILO ST 15/6 13 2 4 11 Technical Specifications Max. operating pressure: 6 bar Max. operating

More information

Flamco. Flexcon M. Installation and operating instructions. 2002 Flamco 18501067

Flamco. Flexcon M. Installation and operating instructions. 2002 Flamco 18501067 Flexcon M E Installation and operating instructions 2002 Flamco 1801067 Flamco b.v. P.O. Box 11 2800 AC Gouda - Holland Industriestraat 6 2802 AC Gouda - Holland Tel.: +31(0)182 91800 Fax: +31(0)182 227

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13 presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve

More information

Baumann 87000 Flexsleev Sanitary Control Valve

Baumann 87000 Flexsleev Sanitary Control Valve Product Bulletin D103345X012 Baumann 87000 Flexsleev Sanitary Control Valve The Baumann 87000 control valve (figures 1 and 2) is excellent for throttling high purity liquid or gaseous media commonly found

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations; (1979) (Rev.1 1990) (Rev.2 1996) (Rev.3 Jan 2012) Safety features.1 Fire protection and extinction.1.1 General Fire protection arrangements and fire extinguishing systems are to be in accordance with the

More information

Life Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers

Life Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers May 2014 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER APPLICATION

More information

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico

More information

Lockout - Tagout. Control of Hazardous Energy OSHA Standard 1910.147

Lockout - Tagout. Control of Hazardous Energy OSHA Standard 1910.147 Lockout - Tagout Control of Hazardous Energy OSHA Standard 1910.147 You will learn Purpose of Lockout-Tagout Requirements for LOTO Types of Hazardous Energy Procedures for LOTO Types of Energy Electrical

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

IOM SERIES 820-E/P Electro-Pneumatic Positioner

IOM SERIES 820-E/P Electro-Pneumatic Positioner FLUID CONTROL DIVISION Parker Hannifin Corporation 95 Edgewood Avenue New Britain, CT 06051 Telephone (860) 827-2300 IOM SERIES 820-E/P Electro-Pneumatic Positioner INSTALLATION, OPERATING & MAINTENANCE

More information