C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).
|
|
- Willa Hill
- 8 years ago
- Views:
Transcription
1 SECTION PART 1 - GENERAL 1.01 RELATED WORK A. Section : Common Work Results for HVAC B. Section : Chemical Water Treatment C. Section : Flue Piping 1.02 QUALITY ASSURANCE A. Factory test in accordance with ASME code. 1. ASME Section IV heat exchanger rated for 160-PSI working pressure. 2. Fire test to verify operation and function of all controls. B. Standard for Manufacture: ASME Code for Boilers and Pressure Vessels and state and local boiler codes, and shall be UL listed for zero side clearance. C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). D. Boiler plant shall comply with ASHRAE Standard 90.1 Energy Standard for Building SUBMITTALS A. Submit manufacturer's product data for review DOCUMENTS A. Provide the following documents to be delivered to the Owner upon completion of work: 1. Test Reports: 2. Factory Test 3. Performance Test 4. Certificates/Permits 5. ASME Certificate 6. National Board of Pressure Vessels Inspectors Certificate 7. Guarantee 8. Construction and Operating Permits, as required by state and local regulations, from Air Pollution Control Authorities. 9. Certificate of Acceptance or Boiler Operating Permit from State Boiler Inspector or insurance company PERMITS A. Obtain applicable construction and operating permits from local EPA, boiler, and insurance inspectors. PART 2 - PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS A. Aerco International B. Patterson Kelly Page 1
2 2.02 BOILER - GENERAL A. Boiler shall be complete with all controls and accessories ready to operate on natural gas. B. Condensing Boiler Requirement: 1. Operating performance shall be no less than 86+ACU-thermal efficiency at all operating conditions; the efficiency shall increase as the firing rate decreases. The efficiency shall be in excess of 90+ACU- with low return water temperatures (100 degrees F). The manufacturer shall publish part-load efficiency curves showing multiple firing rates in relation to changing return water temperatures. The part-load efficiency shall be independently certified by Underwriter's Laboratory (UL). 2. Working Pressure: ASME rated for 160-psi maximum working pressure. 3. Heat exchanger fire tubes and tube sheets shall be constructed of 316L stainless steel. Vessel shall not have a pressure drop of more than 2 psig at 150 GPM. Boiler shall be capable of handling return water temperatures down to 40 degrees F without failure due to thermal shock or fireside condensation. 4. Individual boiler capacity shall not exceed 2MMBtu input to ensure conformance with Permit by Rule regulations. C. Boiler shall be of low mass, low water content and maintain header temperature to within 2 degrees F of set point at any point of operation and shall function without the need for dedicated supply pumps. D. Each boiler shall have a minimum turndown, 10:1 for 2 MMBH or less to prevent boiler cycling and aid in load matching to use the minimum amount of fuel necessary. E. Provide complete unit, skid-mounted on a steel base frame, complete with lifting lugs. F. Finish: Prime coat and finish coat with manufacturer's standard colors. G. Insulate vessel and other heat dissipating surfaces with fiberglass insulation. H. Provide necessary piping connections. I. Access to the tubesheets and heat exchangers are available by burner and exhaust manifold removal. Minimum access opening shall be no less than 10 in. diameter. J. The boiler shall be capable of sealed combustion operation BOILER TRIM A. Each boiler shall utilize an electric single seated combination safety shutoff valve/regulator with proof of closure switch in its gas train and incorporate dual over-temperature protection with manual reset in accordance with ASME Section IV and CSD-1. B. Pressure relief valves of a type and size required by ASME code. C. Drain valve, located at rear drain connection LOW NOx BOILER BURNER A. Construct burner and safety controls and sequence to meet local gas company codes and regulations Page 2
3 B. Include electric safety fuel cutoff valves, gas electric ignition system, air pump assembly, pressure regulating devices, pressure and temperature indication. C. All burner material exposed to the combustion zone shall be stainless steel. D. Provide regulation required to reduce gas supply pressure from 2 psig to manufacturer's inlet design pressure. Verify gas supply pressure to burner controls. E. Low NOx Gas Burner: Fiber mesh with stainless steel body, spark ignition and flame rectification INTEGRAL FORCED DRAFT BLOWER A. The forced draft blower shall be factory assembled, wired, and mounted. 1. Forced draft fan. 2. Direct drive motor. B. The boiler plant shall be able to utilize a common stack without the use of remote fan assist devices BOILER CONTROL PANEL (EACH BOILER) A. Electrical equipment and wiring to conform to NEC and UL. B. Include current protection for all motors, magnetic starting switches, thermal overload and under voltage protection. C. Locate control devices and relays in splash-proof steel cabinet mounted on front of boiler. D. Motors 1/2 HP and over: 460/3/60. E. The control panel shall utilize individual circuit boards with a PID control system including an LED display board for temperature indication, fault message board and firing rate indication. All boards shall be field replaceable. F. The panel hardware shall support both RS-232 and RS-485 remote communications via BACnet open protocol. When the Building Automation System (BAS) does not have BACnet protocol capability and interoperability is required, the installing contractor shall provide a BACnet Gateway to act as interface/translator between the BAS via either the RS-485 port of the boiler control panel or the RS-232 port of the boiler plant master control panel. G. Combustion Safeguard: Electronic type detector for monitoring main flame and pilot. H. The control panel shall incorporate three self-governing selectable features designed to enhance operation in modes where it receives an external control signal by eliminating nuisance faults due to over-temperature, improper external signal or loss of external signal. These features include: Setpoint High Limit - allows for a selectable maximum boiler outlet temperature and acts as temperature limiting governor. Setpoint Low Limit - selectable minimum operating temperature and Failsafe Mode - to operate the boiler on internal set point upon loss of external control signal. I. Automatic recycling after power failure or normal operation of operating control. J. Lock out control, requiring manual reset, after pilot or main flame interruption, low water cutout, or high limit operation Page 3
4 K. Control sequence of operation by boiler control panel on each boiler which is coordinated by a Boiler Management System (BMS) panel when multiple boilers are utilized. L. Provide pre-purge and post-purge cycles with full protection against flame failure during both ignition and normal burning periods. M. Conform to local gas company codes and regulations. N. Gas solenoid valves, diaphragm valves, hydraulic valves, regulators, etc., UL and IRI approved components and labeled individually. O. Manual/Automatic Switch in the control panel shall permit continuous firing at the selected rate when automatic firing not desired BOILER MANAGEMENT SYSTEM (BMS) A. Provide a master control panel when one or more boilers are utilized in the boiler plant. B. The BMS shall control up to 32 boilers and shall operate them simultaneously to maximize efficiency. C. The BMS shall be a standalone microprocessor based device used to efficiently operate one or more boilers in response to building load, weather or calendar functions. D. The BMS shall be equipped with open protocol serial connection port, RS-232 or RS-485, to report key operating parameters to the facility management system (FMS). Provide gateway connection as required to convert to building FMS. E. The BMS shall at a minimum have the following control: 1. Sequential or parallel boiler operation 2. Control signal for start/stop of auxiliary equipment 3. Time delay between individual unit start-up to limit utility peaks 4. Start next available unit if boiler malfunctions or is turne off 5. Adjustable programming for night, weekend, holiday setbacks 6. Safety interlock for make-up air dampers, pumps, etc. 7. Non volatile memory to store programming during power failures 8. Fault alarms for boilers and BMS 9. Programmable minimum and maximum temperatures and resets based on outside air temperature 10. Provided with PID and adaptive loops to allow for tight control of boiler firing and loop temperatures 11. Runtime equalization 12. Ability to allow for boiler operation in a continuous mode without being required to cycle on and off 13. Ability to accept commands from the FMS through the gateway connection for programming, setpoint adjustment or turning on/off boiler 2.08 GAS PIPING A. Provide all necessary gas piping properly valved between main and connection to burner and pilot. B. Size in accordance with national, state, and local ordinances and codes, and NFPA recommendations Page 4
5 C. Gas cocks: Lubricated plug cocks with operating handles for manual shutoff. D. Gas burner piping assembly, including pilot, shall meet requirements of IRI. E. Provide vent-less gas regulator to reduce gas pressure from 2 psig to equipment operating pressure POLLUTION CONTROL A. Boiler shall be certified to meet South Coast Air Quality Management District (SCAQMD) and the Texas Commission on Environmental Quality (TECO) standards. PART 3 - EXECUTION 3.01 INSTALLATION A. Install boilers, boiler accessories and piping in accordance with NFPA, ASME, local codes, and manufacturer's instructions, insuring agency requirements. B. Boilers and accessories shall be installed and piped per manufacturer's recommendations and under his supervision. C. Pipe drains on boiler to the nearest drain, full size of the connection. D. Pipe relief valves and vents to outside the building. Size in accordance with manufacturer's recommendations and ASME code but not less than connection size. E. Pipe gas vent connections on gas controls to outside of the building. F. Install boiler stacks constructed of UL listed stainless steel AL-29-4-C positive pressure material. The manufacturer shall provide stack layout and bear the responsibility of proper operation. G. Each boiler shall have individual isolation valves for service and maintenance DUTIES OF SERVICE REPRESENTATIVE A. Boiler and burner manufacturer's factory trained service representative(s) to perform services described. 1. Work with installing Contractor, including site visits, to ensure proper equipment installation and piping. 2. Instruct personnel designated by maintenance personnel in operation and maintenance of equipment. B. Service representative shall supervise the following: 1. Adjustment of firing equipment. a. Representative shall have the test equipment, tools, and instruments necessary to accomplish this work. 1) Boiler performance demonstration. 2) Adjustment of firing equipment. 2. Setup of BMS with reset slopes, outside air temperature data and time of day schedules in conjunction with the building control system. 3. Coordination of owner s water treatment vendor startup activities for heating water loops Page 5
6 3.03 CLEANING (WASH OUT) A. Insure maintenance personnel and water treatment company representative are present, the required chemicals are present for the procedures required herein, and water treatment equipment is installed and functioning. B. Before boilers and heating system are placed in service, either for temporary or permanent use, clean and flush piping system prior to boiler connection and start-up START-UP A. Verify safety relief valve is installed properly. B. Adjust firing equipment. C. Operate each boiler for a minimum of one hour at each 1/4, 1/2, 3/4, and full loads. D. Take readings every half hour during the above operation for the following: 1. Stack temperature. 2. Boiler water temperature in and out. 3. Percent carbon dioxide and oxygen readings. E. Adjust fuel/air mix to maximum combustion efficiency while meeting low nitrous oxide emissions set forth by the State of Texas OPERATING DEMONSTRATION A. Demonstrate to Owner the operation of the system over entire range. B. Demonstrate to Owner the operation of total system as a unit boilers and control system WARRANTY A. The pressure vessel/heat exchanger of the boiler shall carry a non-prorated 7-year warranty against failure due to condensate corrosion, thermal stress, mechanical defects or workmanship. The control panel assembly shall carry a 2-year warranty against failure due to defective materials or workmanship. The BMS assembly shall carry a 2-year warranty against failure due to defective materials or workmanship A Warranty Certificate must be issued to the owner from the manufacturer and a copy of warranty must be submitted for engineer's approval. END OF SECTION Page 6
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationCentauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH
Centauri Condensing Fire Tube Water Boiler 399 to 1000 MBH Pre-mix surface burner with up to a 7-to-1 turndown NOx levels as low a 5 ppm at full rate Operates on 4" gas pressure shown with optional gauges
More informationCommercial Gas Water Heaters
POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600
More informationCommercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
More informationLAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
More informationHigh Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR
High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR The heat transfer innovators. THE RELIANCE COPPER FINNED TUBE HYDRONIC BOILER FEATURES Copper Fin-Tube Heat Exchanger Up to 88% Thermal
More informationSECTION 23 52 01 HOT WATER BOILER HEATING PLANT
SECTION 23 52 01 HOT WATER BOILER HEATING PLANT PART 1 GENERAL 1.1 PROJECT DESCRIPTION A. The project consists of the demolition and removal of the existing hot water boiler heating plant and providing
More informationCommercial Boiler Systems and Controls
Commercial Boiler Systems and Controls Condensing Non-condensing Hybrid Systems Steel Medium Mass Copper Instantaneous Electric Riverside R HYDRONICS An introduction to hybrid boiler systems What is a
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationOriginators of the Flexible Water Tube design
BRYAN FLEXIBLE WATER TUBE AB SERIES STEAM AND WATER BOILER 900,000 TO 3,000,000 BTUH FORCED DRAFT GAS, OIL OR DUAL FUEL FIRED Water Boiler AB120-W-FDGO Steam Boiler AB250-S-150-FDG Originators of the Flexible
More informationD Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00
SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air
More informationThe city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers
The city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers Table of Contents Introduction... 1 Intention... 2 Authority and responsibility letter... 3 Organizational
More informationTANKLESS WATER HEATER INSTALLATION DIAGRAMS
TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water
More informationBoiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationELECTRODE BOILERS VAPOR POWER INTERNATIONAL
ELECTRODE BOILERS WITH JET-FLO Technology VAPOR POWER INTERNATIONAL ELECTRODE boilers The Electrode Steam Boiler with Jet-Flo technology consists of an insulated pressure vessel and is fully enclosed in
More informationFactory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
More informationHot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE
Hot Water Boilers and Controls Why Condensing Boilers are Different Presented Oct. 14, 2008 Long Island Chapter, ASHRAE H.W. Boilers and Controls Major types of boilers Advantages and disadvantages Resistance
More informationEvaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
More informationElement D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
More informationRESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00
RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls
More informationSECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
More informationRules for construction of heating boilers, Boiler and Pressure Vessel Code, Section IV-2007
Boilers Introduction How Boilers Work Types of Boilers Key Components of Boilers Safety Issues Best Practices for Efficient Operation Best Practices for Maintenance References Introduction Boilers are
More informationRECON WATER HEATER INSTALLATION FORM
RECON WATER HEATER INSTALLATION FORM Please complete ONE (1) form for each SITE and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: STARTUP@AERCO.COM.
More informationPLP - TERMS AND CONDITIONS
PLP - TERMS AND CONDITIONS 2014-2015 Philadelphia Gas Works Residential Parts & Labor Plan Contract This Residential Parts & Labor Plan Contract (this Plan ) is available to customers of the Philadelphia
More informationPump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationDepartment of Veterans Affairs VHA DIRECTIVE 2008-062 Veterans Health Administration Washington, DC 20420 October 15, 2008 BOILER PLANT OPERATIONS
CORRECTED COPY Department of Veterans Affairs VHA DIRECTIVE 2008-062 Veterans Health Administration Washington, DC 20420 BOILER PLANT OPERATIONS 1. PURPOSE: This Veterans Health Administration (VHA) Directive
More informationDesign & Construction Standards, Revised January 2013 5.21.30-1
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.
More informationFossil fuel heating equipment
Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating
More informationBoiler and Burner Cleaning and Servicing Specifications
Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service
More informationNAVIEN AMERICA INC. 17855 FITCH AVENUE
Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:
More informationIndirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
More informationCHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.
More informationMedical Air Systems: Scroll
GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing
More informationMODEL FLX PACKAGED BOILER
MODEL FLX PACKAGED BOILER 1,500,000 to 12,000,000 Btu/hr Hot Water and Steam Fuel: Light Oil, Gas or Combination Manual Part No. 750-177 R5 10/2009 MODEL FLX PACKAGED BOILER Operation, Service, and Parts
More informationLANDFILL GAS ENCLOSED FLARE SYSTEM
LANDFILL GAS ENCLOSED FLARE SYSTEM Part 1. General 1.01 Description A. Information within this specification describes an enclosed flare system designed specifically for the combustion of landfill gas.
More informationDescription of Thermal Oxidizers
Description of Thermal Oxidizers NESTEC, Inc. is a full service equipment supplier specializing in solutions for plant emission problems. The benefit in working with NESTEC, Inc. is we bring 25+ years
More informationRVL470. Heating Controller. Building Technologies HVAC Products. Series B
2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones
More informationCOMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
More informationFAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com
FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationCommercial Gas Water Heater
Commercial Gas Water Heater 3-Year Limited Tank/1-Year Limited Parts Warranty* The Polaris has a high grade 444 stainless steel tank with brass connections for years of dependable, trouble-free service
More informationService Manual Models: 502, 752, 1002, 1302,
PBX-PFX-SER Rev D Service Manual Models: 502, 752, 1002, 1302, 1501, 1701, and 2001 Up To 5:1 Turndown WARNING This manual must only be used by a qualified heating installer / service technician. Read
More informationGUIDELINES FOR LOGBOOKS COMPLIANCE TO BOILER REGULATIONS N.J.A.C. 12:90
GUIDELINES FOR LOGBOOKS COMPLIANCE TO BOILER REGULATIONS N.J.A.C. 12:90 Department of Labor and Workforce Development Labor Standards & Safety Enforcement Division of Public Safety and Occupational Safety
More informationReplacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS
Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The
More informationOROT RABIN POWER STATION UNITS 1-4. 4 x 350 MW
ISRAEL ELECTRIC OROT RABIN POWER STATION UNITS 1-4 4 x 350 MW COAL BOILER CONVERSION TO LOW NO X NATURAL GAS AND COAL FIRING BY PRIMARY AND SECONDARY MEASURES INSTALLATION Replacing the Burner Management
More informationREQUEST FOR QUOTATIONS
Metropolitan Washington Airports Authority Materials Management, MA-133 Terminal A, Room 278 Washington, DC 20001-4901 REQUEST FOR QUOTATIONS 1. FOR INFORMATION CONTACT NAME: Regina Leigh 2. REQUEST FOR
More informationRecommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank
Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic
More informationModel CFC ClearFire Condensing Boiler
ClearFire Condensing Boiler Table of Contents MODEL CFC FEATURES AND BENEFITS.................................................................3 MODEL CFC PRODUCT OFFERING.....................................................................5
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationCommercial Gas Water Heaters
CYCLONE Mxi MODULATING MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable
More informationOWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationBLADDER SURGE CONTROL SYSTEM
PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures
More informationCommercial Semi-Instantaneous Water Heaters
FEATURES HWI Models A. O. Smith s HWI models are available for operation with steam or boiler water as the energy source. They are factory assembled with components sized, piped and checked at the factory
More informationELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
More informationprestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10
prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4
More informationKC Series Gas Fired Water Heating System
KC series Gas Fired Water Heater (Massachusetts) Operation and Maintenance Manual AERCO International, Inc. 159 Paris Ave. Northvale, New Jersey 07647 Phone: 201-768-2400 FAX: 201-768-7789 Applicable to
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationGas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard
LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled
More information! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
More informationResidential/Commercial Gas Condensing High Efficiency Tankless Water Heaters
Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationGeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control
PARTS & ACCESSORIES GeniSys 12V Model 7556 Advanced 12 Vdc Burner Control Description / Applications The Beckett GeniSys TM 12V Advanced Burner Control is a 12 Vdc primary safety control for oil burners
More informationwith MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
More informationEnergy Saving Solutions. Bob Montgomery Technical Solutions Specialist Waterloo Manufacturing
Energy Saving Solutions Bob Montgomery Technical Solutions Specialist Waterloo Manufacturing Combustion Efficiency Measure Heat Recovery Energy Saving Solutions Upgrade Repair Replace Audits Financial
More informationG26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
More informationGuidelines for Preparing for a Temporary Steam Plant
Guidelines for Preparing for a Temporary Steam Plant Trailer-Mounted Boilers Skid Mounted Boilers Mobile Boiler Rooms Mobile Feedwater Vans Mobile Steam Plants Emergency Preparedness Plan Table of Contents
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationASME Packaged Indirect Fired Water Heater
Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining
More informationVersatility ::::::::::::::::::::::::::::::::::::::: the best. mod/con Performance. and UP TO. www.knightheatingboiler.com
the best mod/con Performance UP TO 96 % DOE AFUE Efficiency and Versatility Now with Floor and Wall Mount Models www.knightheatingboiler.com ::::::::::::::::::::::::::::::::::::::: a Legendary Performer
More informationElectric Panel Pump Control System. Operation, Maintenance and Installation Manual
Manual No. 5EP-OM1-1 Electric Panel Pump Control System Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION... 2 SEQUENCE
More informationSECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
More informationFVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
More informationPACKAGED FIRE TUBE BOILER
SAMPLE PREVENTIVE MAINTENANCE MANUAL PACKAGED FIRE TUBE BOILER 1 CONTENTS Introduction 1 Intention 2 Organisational setup 3 Boiler Fault reporting & Repair progression 4 Preventive Maintenance Schedules
More informationBC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
More informationBring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
More informationSIOUX HYBRID WATER HEATER
SIOUX Hybrid Water Heater for the Concrete Industry SIOUX HYBRID WATER HEATER Patent Pending Maximizing the Benefits of Coil and Direct-Fired Heating Technologies Higher Discharge Temperature True High-Efficiency
More informationPump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International
ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International Presentation Overview Water Heater Piping Strategies How to size a water heater?
More informationMustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationUp To 99% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY
HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY 7 INPUTS FROM 1.5 TO 5.0 MILLION BTU/HR FIRING RATE MODULATION UP TO 25:1 DIRECT-VENT FLEXIBILITY
More informationCeiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
More informationSAM HOUSTON STATE UNIVERSITY
PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the
More informationFundamentals of HVAC Control Systems
ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
More informationM7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace
TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationCARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
More informationPRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller
BLZPTS-1 NOVEMBER 19, 2013 TS350 TS752 BLPS PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller DESCRIPTION The BLPS, TS350
More informationSome Criteria for Choosing a Steam Boiler for a Microbrewery
Some Criteria for Choosing a Steam Boiler for a Microbrewery Jack Coe Rite Engineering and Manufacturing Corporation Breweries rely on steam heating for a number of functions, primarily to heat the brew
More informationFIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
More informationArapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
More information