1 FOAM CHAMBER MODEL - FC TECHNICAL DATA : MODEL SIZE WORKING PRESSURE FC 50, 65, 80, 100 &150 NB inlet Minimum 2.8 Kg. / sq. cm. (40 PSI) Maximum 7 Kg. / sq.cm. (100 PSI) FLANGE CONNECTION ANSI B16.5 Class 150# APPROXIMATE FC Kg. WEIGHT FC Kg. FC Kg. FC Kg. FC Kg. VAPOUR SEAL RUPTURE PRESSURE MAXIMUM PERMISSIBLE BACK PRESSURE ON VAPOUR SEAL FINISH 0.7 to 1.75 Kg./sq.cm.(10 PSI TO 25 PSI) Running water/water foam solution pressure at the inlet of Foam Chamber Kg./sq.cm. (0.9 PSI) Red epoxy painted ORDERING a) Model and size INFORMATION b) Inlet pressure. c) Foam solution flow reqd. d) Inlet, outlet flange specification. e) Type of foam concentrate used. APPLICATION Foam Chamber is used in one of the most common application to protect vertical fixed roof (cone) liquid storage tanks, with or without internal floating roof with the low expansion foam system. The application of foam is on the basis that the risk comprises the total surface area of the fuel. The foam system design guidelines generally used are in accordance with NFPA-11, standard. Foam Chambers are defined by NFPA-11 as Type II discharge outlets for delivering the foam to the surface of a flammable liquid. The Foam Chambers are widely used with the In-line foam inductor, Balance pressure foam proportioning system, Bladder tank proportioner or Foam tender. SPECIFICATION Foam chamber is an air aspirating foam discharge device, covering wide range of flow from 75 to 3600 litres per minute at 2.8 to 7 kg/sq.cm inlet pressure. The foam chamber contains a vapour seal to prevent the entry of vapour into the foam chamber and the foam solution pipe. Each foam chamber is supplied with an orifice plate, designed for the required flow and inlet pressure. The orifice is field replaceable in the event of change in design parameters. The foam is produced by introducing air into the foam solution stream. The inlet of foam chamber is designed to create venturi jet which draws air into the foam solution stream. The air is drawn into the foam solution through the holes located on the foam chamber covered with stainless steel screen to exclude nesting birds and insects. The aerated foam is directed into the deflector for the gentle application of the expanded foam. The deflectors are available in different models. On removal of cover plate from the top of the chamber allows the system to be tested and to draw a sample of the expanded foam, without removing the vapour seal or disconnecting the foam chamber from the tank. Frangible glass bursting disc (vapour seal) can be replaced very easily. SYSTEM DESIGN REQUIREMENT The NFPA-11, a standard for low expansion foam, provides the essential requirement of an appropriate designed foam pouring system, which are identified and outlined as below: The Foam Deflector is used with the Foam Chamber. The aerated foam from the Foam Chamber is directed in to the deflector for the gentle application of the expanded foam. The deflector reduces the expanded foam velocity and allows the foam to slide down the tank wall. PAGE 1 OF 6
2 a) Number of Foam Chamber The number of foam chambers required is determined by the tank diameter. Where two or more foam chambers are required, they shall be spaced equally around the tank periphery and each Foam Chamber shall be sized to deliver foam at an approximately same rate. Please refer graph to select the unit that will provide the required minimum foam solution application rate at the available operating pressure of the Foam Chamber. For minimum number of Foam Chamber requirement, kindly follow the recommendations as per NFPA/OISD/TAC or as per the governmental codes or ordinances wherever applicable. b) Minimum Foam Solution Application Rate The minimum foam solution application rate is the rate at which the water and foam concentrate in correctly proportioned ratio should be delivered to the surface of a storage tank under protection to control and extinguish the fire. For minimum application rate requirement follow the recommendations as per NFPA/OISD/TAC or governmental codes or ordinances wherever applicable. Testing And Maintenance Qualified and trained person must commission the system. After few initial successful tesst an authorized person must be trained to perform inspection and testing of the system. It is recommended to carry out physical inspection of the system regularly. The system must be fully tested at least once in a year or in accordance with applicable NFPA/OISD/ TAC standards or in accordance with standards of the organization having local jurisdiction. Do not turn off the system or any valve to make repair or test the system, without placing a roving Fire Patrol in the area covered by the system. The Patrol should continue until the system is put back in service. Also inform the local security guard and control alarm station, so as to avoid false alarm. Each system is to be flushed properly. The vapour seal must be replaced if the system has been operated. Normal testing of the chamber can be carried out by removing the cover plate from the top of the chamber. This allows the system to draw a sample of the expanded foam without removing the vapour seal or disconnecting the Foam Chamber from the tank. The air screen is to be inspected periodically for the obstruction of air inlet holes. If any obstruction is noticed, remove the same and flush if necessary. It is recommended to have regular maintenance programme to inspect the Vapour Seal Chamber discharge area and deflector for possible deposit or obstruction. NOTE A PROVISION IS TO BE MADE FOR PRESSURE GAUGE MOUNTING AT INLET OF FOAM CHAMBER, WHICH CAN BE PLUGGED AFTER SUCCESSFUL COMMISSIONING OF THE SYSTEM. THIS WILL HELP TO ANALYSE THE SYS- TEM WHILE COMMISSIONING. Selection Of KV Foam Chamber SIZE OF FOAM K-FACTOR CHAMBER 50 NB 43.4 to NB to NB to NB to NB to To select the size of the Foam Chamber use the following formula Q = K P Q = Total solution flow in litres per minute. K = Constant for Foam Chamber P = Inlet pressure in kg/sq.cm. Example To find K-Factor Q = 300 LPM P = 3.5 Kg/sq.cm. K = = This K-Factor falls within the range of the Foam Chamber having 65 NB size. Hense 65 NB size of Foam Chamber should be selected. The Foam Chamber size may also be selected with the help of the graph. Calculation example Tank type : Fixed roof storage tank Tank diameter : 40 meters. Foam concentrate to be used : AFFF 3% Pressure at inlet of Foam Chamber : 3.5 kg/sq.cm. Flash point of liquid stored in tank : - 27 C. Surface area = d 2 4 = ( 3.14 X 40 2.) 4 = 1256 Sq. mts. a) Foam solution application rate = *4.1 LPM /Sq. mts. X Surface area = 4.1 X 1256 = 5150 LPM *4.1 LPM is as per NFPA-11 ( 5 LPM as per OISD recommendations ) or it should be as per prevailing rules of local authority having jurisdiction. b) Number of Foam Chamber required for 40 metres diameter tank = 3 nos. minimum (Reference NFPA-11) Capacity of Foam Chamber required = = 1717 LPM The K-Factor for flow of 1718 LPM at 3.5 kg./sq.cm. K = Q P = = PAGE 2 OF 6
3 The K-Factor (918.30) falls within the K-Factor of 100 NB size of the Foam Chamber. Hence three numbers of 100 NB Foam Chamber with 1717 LPM capacity at 3.5 kg./sq.cm inlet pressure are to be selected. Note THE ABOVE ARE THEORETICAL CALCULATIONS. IT IS, THEREFORE, RECOMENDED THAT SYSTEM DESIGNER CONSIDERS AN APPROPRIATE FACTOR OF SAFETY c) Foam Concentrate Requirement : The fuel stored has flash point of 27 C. So the minimum system running duration recommended is 55 minutes. (Reference NFPA-11) The foam concentrate required = foam solution application rate in LPM = 5154 X 3 X = 8505 litres. Add 5% = 8930 litres. percentage of foam concentrate system running time The supplementary hose stream requirement is also to be considered and 100% reserve stock to be maintained or as per local authority having jurisdiction. The additional quantity of 5% is general guideline, however system designer has to work-out this percentage considering factor of safety, pipeline, minimum level for induction in storage tanks etc. Note 1. It is recommended to select next higher size of Foam Chamber when the K-Factor is very much close to upper limit of the model. 2. For the best performance the inlet pressure at the Foam Chamber should be 2.8 kg/sq.cm. or higher. X X PAGE 3 OF 6
4 FOAM CHAMBER DIMENSION in millimetre ( Approximate ) INLET OUTLET ( F1 ) (F2) A B C 50 NB 80 NB NB 100 NB NB 150 NB NB 200 NB NB 250 NB Dimension of inlet / outlet flanges ( F1 / F2 ) are as per ANSI B Pipes used are ERW (Seamless Pipes are optional on request) PART LIST ITEM DESCRIPTION MATERIAL SPECIFICATION NO. 1 ORIFICE PLATE S.S INLET FLANGE STEEL ASTM A105 3 AERATING PIPE STEEL PIPE 4 FOAM MAKING CHAMBER STEEL PIPE 5 FOAM CHAMBER STEEL PIPE 6 CHAMBER FLANGE STEEL 7 GASKET NEOPRENE 8 INSPECTION HATCH STEEL 9 BOLT STEEL 10 VAPOUR SEAL RING & SEAT STEEL 11 VAPOUR SEAL GLASS 12 WING NUT & STUD S.S DISCHARGE PIPE STEEL PIPE 14 OUTLET FLANGE STEEL ASTM A AIR STRAINER S.S CHAMBER PLATE STEEL PAGE 4 OF 6
5 PRESSURE VS FLOW PERFORMANCE CHARACTERISTIC INLET PRESSURE (KG./SQ.CM.) INLET PRESSURE (KG./SQ.CM.) SIZE 50NB SIZE 100NB INLET PRESSURE (KG/SQCM) (KG/CM ) SIZE 65NB INLET PRESSURE (KG./SQ.CM) SIZE 150NB INLET PRESSURE (KG./SQ.CM) SIZE 80NB PAGE 5 OF 6
6 TYPICAL FOAM CHAMBER INSTALLATION WITH DEFLECTOR Note : Above dimension are general guideline only. The system designer can adopt the dimensions as per NFPA/ TAC/OISD or as per the governing rules & ordinances having local jurisdiction. LIMITED WARRANTY Products manufactured by K.V. FIRE CHEMICALS (I) PVT.LTD.. are warranted against defects in material and workmanship for a period of Two (2) years from the date of shipment. KV's obligation under this warranty is limited to replace or repair the products or its parts, which are shown to KV's examination to be in a defective condition attributable to KV. No warranty is given for products or components which have been subject, to misuse, improper installation, corrosion, wear and tear, improper storage, modification or repaired. If the defect attributable to KV cannot be rectified by repair or replacement, then KV may elect to refund the purchase price of the equipment in complete discharge of its obligation under this Limited Warranty. IN NO EVENT SHALL K.V. FIRE CHEMICALS (I) PVT. LTD. BE LIABLE IN CONTRACT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY, FOR INCIDENTAL, IN-DIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING DAMAGES. FOR INJURY TO PERSON OR DEATH OR DAMAGE TO PROPERTY AND OR PENALTIES RESULTING FROM ANY PRODUCTS OR COMPONENT MANUFACTURED OR ASSEMBLED BY KV. THIS IS LIMITED WARRANTY ONLY. KV DISCLAIMS WITH RESPECT TO THE PRODUCTS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. THERE IS NO WARRANTY OF ANY NATURE MADE BY KV BEYOND AS STATED ABOVE. NOTICE : The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the provision of government codes or ordinances wherever applicable. The information provided by us are to the best of our knowledge and belief, and are general guidelines only. Site handling and installation control is beyond our reach. Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or damages due to our product. Product development is a continuous programme of K.V. FIRE CHEMICALS (I) PVT. LTD. and hence the right to modify any specification without prior notice is reserved with the company. KAMALA NIWAS, PLOT NO. 32, LANE D, SECTOR 8, VASHI, NAVI MUMBAI INDIA. PHONE : +(91) FAX : +(91) [email protected] WEBSITE : PAGE 6 OF 6
FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100
MODEL - FCA & FCA-S HD FIRE PROTECT TECHNICAL DATA MODELS FCA-65, FCA-80 & FCA-100 Carbon Steel Construction FCA-S 65, FCA-S 80 & FCA-S 100 Stainless Steel Construction INLET SIZE 65, 80, 100 NB WORKING
HIGH VELOCITY WATER SPRAY NOZZLE
HIGH VELOCITY WATER SPRAY NOZZLE MODELS HV-AS & HV-BS HD FIRE PROTECT TECHNICAL DATA MODEL HV-AS & HV-BS MAXIMUM WORKING 12 Bar (175 PSI) PRESSURE EFFECTIVE 3.5 Bar to 10.5 Bar WORKING PRESSURE (50-150
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style
PETROLEUM STORAGE TANK FIRE PROTECTION SECTION INDEX
PETROLEUM SECTION INDEX Foam Application Method: Fixed Surface Systems (Design Reference NFPA 11)... K2 Fixed, Full Surface Foam Application...K3-K4 BFC Series Custom Fitted Foam Chambers...K5-K6 BFC-HC
Installation and Operating Instructions Installation Instructions for SS EPE-316L Series
INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This
Fixed or Semi-Fixed Fire Protection Systems for Storage Tanks
Fixed or Semi-Fixed Fire Protection Systems for Storage Tanks In the early years of the oil industry, fire in a storage tank was a common occurrence. Virtually all products were stored in cone roof tanks
HotLok Pass Through Blanking Panel
HotLok Pass Through Blanking Panel Part Numbers 1U - 10112 2U - 10113 Table of Contents Tools Required for Installation Page 2 Dimensions and Rack Requirements Page 2 Installation Procedures Page 3 Removal
Operator s Manual. Pressure Injection Cell Model PC8500. Congratulations! Contents
Operator s Manual Pressure Injection Cell Model PC8500 Congratulations! Congratulations on your purchase of a Next Advance Pressure Injection Cell. Please read this operator s manual which explains proper
3M Housings DS Series
Lenntech [email protected] Tel. +1-15-610-900 www.lenntech.com Fax. +1-15-616-89 M Housings For Filters Filter Housings, constructed of durable stainless steel, meet general-purpose industrial, chemical,
SE-100-1, SE-200-1, SE-500-1, and SE-1000-1 AIR CHAMP PRODUCTS. User Manual SE BRAKE MODELS: (i) MTY (81) 83 54 10 18 ventas@industrialmagza.
AIR CHAMP PRODUCTS User Manual SE BRAKE MODELS: SE-00-, SE-200-, SE-500-, and SE-000- (i) FORM NO. L-20084-E-040 In accordance with Nexen s established policy of constant product improvement, the specifications
Technical Data. Installation
Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems General Description The Figure 51 (1) Riser Manifolds
Model/Sprinkler Identification Numbers
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-L 5.6 and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description
Installation, Maintenance, & Repair Series 4000B/LF4000B
Installation, Maintenance, & Repair Series 4000B/LF4000B Reduced Pressure Zone Assemblies Sizes: 1 2" 2" (15 50mm) RP/IS-A-4000B 4000B/LF4000B Size: 3 /4"! WARNING Testing Read this Manual BEFORE using
Installation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of
Diameter 3" 4" 6" 8" Flange type PN 16 PN 16 PN 16 PN 16. Orange-red ( RAL 2002) Height (cm) 27,70 26,30 28,70 29.70
Description Usually, a wet alarm valve station comprise: a Rolland wet alarm valve linked to the water motor gong. a set of valves and by pass used to test the system. a drain valve. a test valve gauges
TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.
May 3, 2013 Foam 138a 1. DESCRIPTION Chemguard Water Powered Oscillating Monitors are designed to automatically discharge over a specific design area upon system activation. These are suitable for use
V47 Series Temperature Actuated Modulating Water Valves
V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate
Wet alarm valves. Wet alarm valves. FM trim
Description Usually, a wet alarm valve station comprise: - a Rolland wet alarm valve linked to the water motor gong. - a set of valves and by pass used to test the system. - a drain valve. - a test valve
MODEL VG08008 CONTENT PACKING LIST / TOOLS NEEDED PANEL DIMENSIONS FITTINGS / TECHNICAL DATA WALL/CORNER INSTALLATION CARE AND TROUBLE SHOOTING
CONTENT PACKING LIST / TOOLS NEEDED PANEL DIMENSIONS FITTINGS / TECHNICAL DATA WALL/CORNER INSTALLATION CARE AND TROUBLE SHOOTING WARRANTY 1 PACKING LIST DESCRIPTION MODEL NUMBER - PANEL HOUSING 88062
Installation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK Safety Instructions Installation Warranty IN-LINE SERIES: 2-5 & 7 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON VERTICAL SERIES: 14-20-32-36-52-86-96-119 GALLON KEEP
TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER 1.800.591.9360 TECHNICAL ASSISTANCE FAX: 1.626.855.4894
ACORN SAFETY P.O. BOX 3527 CITY OF INDUSTRY, CA 9744-0527 UNITED STATES OF AMERICA WWW.ACORNSAFETY.COM INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FREEZE RESISTANT WALL MOUNTED EMERGENCY EYEWASH
Class A Foam Mixing and Application Equipment
Class A Foam Mixing and Application Equipment Adding Phos-Chek Class A foam concentrate to water: There are many methods of adding Phos-Chek Class A foam concentrate to water. The different methods have
3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA
December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas
Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description The TYCO Type EA-1 PROTECTO- SPRAY Directional Spray Nozzles are automatic
Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual
Speedflow Undersink Unvented Water Heater Models SF10K and SF15K Instruction Manual Version 2.0 May 2009 Hyco SpeedFLOW UnVENTED WATER HEATER Models SF10K (10 Litres) and SF15K (15 Litres) 1. Introduction
MODEL G300 BRAKE BLEEDER
MODEL G300 BRAKE BLEEDER Installation, Operation & Repair Parts Information Branick Industries, Inc. 4245 Main Avenue P.O. Box 1937 Fargo, North Dakota 58103 REV060616 P/N: 81-0035G 1 THIS PAGE INTENTIONALLY
4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX
Butterfly Valves 4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com MAY 2013 L-1 BULLETIN BUTTERFLY REV. #5 GLOBE BUTTERFLY VALVE INSTALLATION
Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
SINGLE STAGE INLINE FIRE PUMP
MODEL 383 SINGLE STAGE INLINE FIRE PUMP INSTRUCTION AND REPAIR MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains
AT&T. PARTNER Plus Door Phone. Installation and Operation Manual
AT&T PARTNER Plus Door Phone Installation and Operation Manual Copyright 1990 AT&T All Rights Reserved Printed in U.S.A. CIC# 999-500-317 OII722050-051 Issue 1 October 1990 PARTNER Plus Door Phone is a
American Fireglass Outdoor Fire pit kit information. General instructions/warnings for outdoor gas pan and burner systems
American Fireglass Outdoor Fire pit kit information General instructions/warnings for outdoor gas pan and burner systems We strongly recommend that our burner products be installed by a licensed and certified
Model RV-1 Pressure Relief Valve 2 to 8 Inch (DN50 to DN200), 250 psi (17,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description
Technical Services 00-3-932 +-0-7-220 www.tyco-fire.com Model RV- Pressure Relief Valve 2 to Inch (DN50 to DN200), 250 psi (7,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description The
Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description The TYCO Type D3 PROTECTO- SPRAY Nozzles are open (non-automatic) directional
Retractable Screen. Replacement Screen Instructions
Retractable Screen Patent Pending Replacement Screen Instructions For RTS, RET, & RTM Products ATTENTION! Retractable screens are not intended to provide security or provide for the retention of objects,
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
Instructions. Complete RPS 2900 Pump Kit for RoadLazer RoadPak Line Striping System 3A1304A ENG. Pressure Relief Procedure.
Instructions Complete RPS 2900 Pump Kit for RoadLazer RoadPak Line Striping System 3A1304A ENG Model 24G766 Important Safety Instructions For complete warnings and safety instructions see RoadLazer RoadPak
INSTRUCTION MANUAL IM042. Slide Rail Systems - Series A10 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
INSTRUCTION MANUAL IM042 Slide Rail Systems - Series A10 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS SUBJECT PAGE Safety Instructions... 3 Descriptions and Specifications...
SunMaxx Solar Filling Station Operating Instructions
SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...
BY MCI SOLUTIONS SECONDARY CONTAINMENT ADAPTOR
BY MCI SOLUTIONS SECONDARY CONTAINMENT ADAPTOR www.mcisolutions.ca Company Profile About Us MCI Solutions (MCI) is a manufacturing leader in chemical injection technologies, providing unique solutions
Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
PRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
ITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name.
ITE Indirect calorifier ITE - 400/500/600/750/1000 0310 117 Installation, User and Service Manual Innovation has a name. Read this manual carefully Warning Read this manual carefully before starting the
Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
FLASH TANK ECONOMIZER PRODUCT GUIDE
FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.
PAINT SPRAY GUN WASHER
PAINT SPRAY GUN WASHER 94996 ASSEMBLY AND OPERATING INSTRUCTIONS Visit our website at: http://www.harborfreight.com Read this material before using this product. Failure to do so can result in serious
RZ Guardrail System Installation Manual
TM RZ Guardrail System Installation Manual RZ Guardrail System Compliance is based on OSHA standards: (Standards - 29 CFR) 1910.23 (e) and (Standards - 29 CFR) 1926.502 (b) Failure to read, understand
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS ODEON IN-WALL TANK K-6283K/ K-6284K/ K-6286K Read installation guide in illustration and word file carefully, and install the tank according to instructions in the guide to avoid
Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger
Digital echo-charge Owner s Manual Xantrex Digital echo-charge Battery Charger Thank you for purchasing a Xantrex Digital echo-charge. Xantrex Technology Inc. takes pride in manufacturing quality products
Installation Instructions / Warranty
Installation Instructions / Warranty Downpour 10 27474XX1 7 27476XX1 Raindance AIR 12 27493XX1 Shower Arm 15 27413XX1 9 27422XX1 Extension Pipe for Ceiling Mount 27479XX0 Downpour 10 Showerhead 27474XX1
BERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
4 in 1 Air Compressor
4 in 1 Air Compressor Operating Instructions and Parts Manual Model W-1704! This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
Digital Fingerprint safe
Digital Fingerprint safe Model 96846 Operation Instructions Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ slightly from the product
Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS
Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The
DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual
DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR Installation and Operation Manual 1 ENGLISH Safety Instructions 2 Features 2-3 Specifications 3 Installation 4-5 Wiring Diagrams 6-7 Warranty 8
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
BERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID
TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
SF15K SF05KSS, SF10KSS
Product Instruction Manual Speedflow SF05K, SF10K & SF15K SF05KSS, SF10KSS & SF15KSS Undersink unvented water heater V15.6/6 Version 3.2 Jan 2015 Thank you for purchasing a Hyco Speedflow unvented water
KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850
INSTALLATION AND OPERATING INSTRUCTIONS KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850 Product advantages Automatic float switch as water
Installation Instructions
7.3L & 6.0L 5/8 FUEL TANK PICKUP KIT Fits 94-07 7.3L & 6.0L Powerstroke Diesel Trucks & Excursions Installation Instructions These instructions are intended simply to be a guide for the installation of
HELI-DECKS & HELI-PORTS
1 HELI-DECKS & HELI-PORTS GENERAL FOAM INFORMATION DESCRIPTION Helicopters provide a level of convenience that is probably unequaled by other forms of transport. While helicopters can land in the middle
ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL
ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER TABLE OF CONTENTS: INSTALLATION USE & CARE MANUAL IMPORTANT INFORMATION Assembly Instructions 2 Wiring Instructions 2 Outdoor Installation
In-Line Filters and Coalescers with Automatic Drains
Instructions/Parts In-Line Filters and Coalescers with Automatic Drains 310611G EN Air Filter with Automatic Drain Part No. 22601, Series B Maintenance To maintain maximum filtering efficiency and to avoid
Installation Instructions
PUSH Installation Instructions A DA C O M PLIA NT shown with optional Bradley 90-75 faucet Front-Mounted Barrier Free Rectangular Bowl Stainless Steel Lav Table of Contents Pre-Installation Information...........2
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
Blowdown vessels Meeting the requirements of HSE PM60
Blowdown vessels Meeting the requirements of HSE PM60 BDV60 blowdown vessels complete range of equipment for the safe disposal of boiler blowdown Boiler blowdown Steam boilers must be blown down to remove
Installation and Maintenance Instructions
Installation and Maintenance Instructions Limited One Year Warranty T&S warrants to the original purchaser (other than for purposes of resale) that such product is free from defects in material and workmanship
TYPE E Main Valve Sizes 3 /8 through 12
SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,
MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS
MASTER Water Conditioning Corp. www.masterwater.com Installation and Operation Manual MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS with the 263/742 Logix Control Valve June 2010 Table of Contents Page No.
Hydraulic Punch Driver Kit
Hydraulic Punch Driver Kit Item 96718 Instructions and precautions Visit our website at: http://www.harborfreight.com Read this material before using this product. Failure to do so can result in serious
Type K current limiting fuse canister Technical information and installation guide
Transformer components Type K current limiting fuse canister Technical information and installation guide The Type K current limiting fuse canister provides an air-insulated receptacle for general-purpose
tire inflator with pressure gauge
tire inflator with pressure gauge Model 95583 Assembly And Operation Instructions Due to continuing improvements, actual product may differ slightly from the product described herein. 3491 Mission Oaks
OWNER S MANUAL. Certified to NSF/ANSI 61. This product is covered by one or more of the following US patent US D692, 524 S
OWNER S MANUAL Certified to NSF/ANSI 61 This product is covered by one or more of the following US patent US D692, 524 S CONTENTS INTRODUCTION CUSTOMER SUPPORT IMPORTANT NOTES SPECIFICATIONS INSTALLATION
MEDION LIMITED WARRANTY Medion warrants that the product accompanied by this limited warranty is free from manufacturing defects in material or workmanship for a period of 12 months from the date of original
Installation Instructions / Warranty
Installation Instructions / Warranty Vertical Spray Bidet Fitting Rough 1322X181 Citterio 39224xx0 Citterio 39225xx0 Starck 10220xx0 Steel 35220800 Uno 38220xx0 Terrano 37224xx0 Terrano 37225xx0 Carlton
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
Utility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
DREAMLINE EXCLUSIVE LIMITED WARRANTY
DREAMLINE EXCLUSIVE LIMITED WARRANTY This warranty applies to DreamLine products purchase after June 1, 2015. DreamLine offers the following warranty for its products and components thereof. This warranty
VW TDI (Golf, Jetta, New Beetle) Upgrade Turbocharger
VW TDI (Golf, Jetta, New Beetle) Upgrade Turbocharger Bill of Materials & Precautions.9L TDI BEW-code: 2003.5-2006 A4 New Beetle TDI 2003.5-2006.0 A4 Golf 2003.5-2005.0 A4 Jetta Item 2 Parts List Description
VERTICAL / FIXED BEAM CLAMP I-BEAM ANCHOR ADJUSTABLE FROM 4-14 Model # HD26249
VERTICAL / FIXED BEAM CLAMP I-BEAM ANCHOR ADJUSTABLE FROM 4-14 Model # HD26249 IMPORTANT!!! ALL PERSONS USING THIS EQUIPMENT MUST READ AND UNDERSTAND ALL INSTRUCTIONS. FAILURE TO DO SO MAY RESULT IN SERIOUS
Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).
Fittings for CO 2 Pipe Threads Pipe thread references quoted in this catalogue conform with the requirements specified in the latest issue and amendments of the following ISO Standards: ISO 7-1 (BS21)
Mini Tank water heater Electric undersink Water heaters GL 2.5 - GL 4 - GL 6+
Mini Tank water heater Electric undersink Water heaters GL 2.5 - GL 4 - GL 6+ IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, safety precautions to reduce the risk of fire, electric
INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS
INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS HEAT-FLO HOT WATER STORAGE / BOOSTER TANKS MODELS 30-ST, 40-ST, 40L-ST, 60-ST, 60L-ST, 80-ST, 115-ST, 80-ST-C, 115-ST-C FOR SINGLE TANK INSTALLATIONS For
STREAMLINE. Products for the Pure Water Cleaning Industry INSTRUCTION MANUAL
STREAMLINE Products for the Pure Water Cleaning Industry INSTRUCTION MANUAL PRODUCT DENVER Honda Powered Pressure Washing Bowser. TANK SIZES 450Ltr, 600Ltr, 800Ltr WARRANTY Covered for one year from recorded
Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
Fig B36 Stainless Steel 'T' Type or Basket Type Strainers
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
VW TDI (Golf, Jetta, New Beetle) Upgrade Turbocharger
VW TDI (Golf, Jetta, New Beetle) Upgrade Turbocharger Bill of Materials & Precautions 1.9L TDI BEW-code: 2003.5-2006 A4 New Beetle TDI 2003.5-2006.0 A4 Golf 2003.5-2005.0 A4 Jetta Parts List Item Description
Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description
Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and
FAUCET SPECIFICATIONS. Vessel Bathroom Faucet Model VG03023 MODEL VG03023
FAUCET SECIFICATIONS Vessel Bathroom Faucet Model VG03023 MODEL VG03023 FEATURES Solid brass construction Single hole construction Ceramic disk cartridge Single lever faucet Standard plumbing connections
OP300S / OP350 2:1 RATIO TRANSFER PUMP
OP300S / OP350 2:1 RATIO TRANSFER PUMP OPERATING MANUAL WITH PARTS IDENTIFICATION Copyright 2013 International Pump Manufacturing, Inc. This manual contains IMPORTANT WARNINGS and INSTRUCTIONS. Read and
PATHWAY Classic Series with Handrails Portable Wheelchair Ramp INSTRUCTIONS FOR USE 6428 REV A 05-21-09
PATHWAY Classic Series with Handrails Portable Wheelchair Ramp INSTRUCTIONS FOR USE. INSTRUCTIONS 1) FOR EZ-ACCESS PATHWAY RAMP WITH HANDRAILS 850 pound weight capacity. Available in 4, 6, 8 & 10 lengths.
Extrusion Flo-Valve INSTRUCTIONS-PARTS LIST. 3000 psi (210 bar) Maximum Working Pressure. Model 204 355, Series K. Rev.
INSTRUCTIONS-PARTS LIST INSTRUCTIONS This manual contains important warnings and information. READ AND KEEP FOR REFERENCE. 306 586 Rev. D Supercedes B Extrusion Flo-Valve Model 204 355, Series K 3000 psi
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
PLATE HEAT EXCHANGER. Installation Manual. Customer Name: Serial number: Purchase order number: Project:
PLATE HEAT EXCHANGER Installation Manual Customer Name: Serial number: Purchase order number: Project: Table of Contents ----------------------------------------------------------------- Page: 2 3 Name
ELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested