Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection
|
|
|
- Cynthia Pierce
- 10 years ago
- Views:
Transcription
1 Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection
2 Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect high value assets and processes not possible with sprinkler-based fire protection. But this technology remains basically unchanged over the years; a supply of agent is stored under pressure, released through a piping distribution network, floods the space, and suppresses the fire. Traditional piped systems require costly installation adaptations like: n Extra space for agent containers and piping n Robust fixtures to handle weight and discharge n System isn t easily reconfigured if space changes n Extensive and frequent maintenance burden n Special measures for recharging at remote sites Water Deluge System Chemical Agent Fixed System n Water Mist (NFPA 750) n Foam-water spray (NFPA 16) n Inert Gas (NFPA 2001) n Dry Chemical (NFPA 17) n Carbon Dioxide (NFPA 12) n Halocarbon Gas (NFPA 2001) Stat-X Aerosol Technology An Effective and Economical Alternative For safety professionals who need effective and economical special hazard fire protection, Stat-X aerosol technology delivers up to 35% savings in equipment and lifecycle costs compared to traditional systems. This is due to lower initial expense plus minimal ongoing service costs. Stat-X aerosol technology is different: n NO distribution piping, manifold, or nozzles n NO floor space requirement or shoring up for weight n NO special handling for compressed gas cylinders n NO venting or ceiling tile clips for discharge forces n NO solenoid actuators, control heads, or hoses n NO water drains or pipe freeze protection n NO system pressurization or room integrity tests Stat-X Aerosol Fire Suppression n Fixed Areosol Fire-extinguishing System (NFPA 2010)
3 How it Works Stat-X devices are termed condensed aerosol agent generators because they generate an ultra-fine suspension of highly ionized potassium fire-fighting particles upon actuation. The key elements in the generation process are: n Device is sealed and stable until actuated n Actuator at top energizes proprietary compound, creating aerosol agent by exothermic oxidation n Build-up of ultra-fine particles and nitrogen gas breaks membrane seal and exits through ports n Discharge fills protected area with a soft suspension of Stat-X agent without super-pressurizing space n Potassium ions combine with fragments of combustion, inhibiting the fire chain reaction n Agent particles also absorb heat from the fire and form inert gases upon decomposition n Minute Stat-X agent particles ( 2 µm) remain in suspension afterwards, helping check re-ignition n Post-fire area is easily vented and cleaned, with no harmful byproducts generated The superior effectiveness of condensed aerosols is due to a unique set of characteristics unmatched by other special hazard agents. This is why it is by far the most efficient fire suppression agent by weight. LESS AGENT FOR THE SAME HAZARD SPACE For a 2,550 ft 3 (72.2 m 3 ) hazard volume: n Most efficient fire suppression by weight n Effective on A, B & C Class fires n Negligible residue, minimal clean-up (11 lb/5 kg) Dry Chemical (50 lb/22.7 kg) Halocarbon (130 lb/59 kg) CO 2 (160 lb/73 kg) Inert Gas (114 lb/52 kg) n Non-toxic, EPA listed halon substitute Key Approvals Worldwide Aerosol fire suppression technology is well-known throughout Europe and Asia. In the past few years, more fire protection engineers in the Americas are recognizing its worth for protecting special hazards. Norms such as NFPA 2010: Standard for Fixed Aerosol Fire Extinguishing Systems and UL 2775: Fixed Aerosol Extinguishing Systems Units now govern its use in a wide variety of applications. Stat-X technology is also listed by the USA Environmental Protection Agency as a Halon alternative under its Significant New Alternatives Policy (SNAP) program. It has no Ozone Depletion Potential (ODP) and zero effective Global Warming Potential (GWP) meaning Stat-X agent is not prone to future bans like many halocarbon agents.
4 Wide Range of Solutions By Size and Activation Type Electrical Series Stat-X Room Protection Control Panel Thermal Series Stat-X Cabinet Protection Thermal Head Manual Series Stat-X Engine Protection Manual Pull Stat-X First Responder Stat-X Confined Space Protection Hand-deployed Compatible With Popular Control Panels Stat-X aerosol generators use the same actuation methods as other special hazard fire systems: n simple manual release, n automatic thermal release, or n sophisticated electronic detection and control Compatibility with many manufactuers UL listed agent release panels means Stat-X fire suppression can integrate into networks for central reporting or to mass notification systems per NFPA 72 National Fire Alarm and Signaling Code.
5 Low Cost of Ownership NFPA standards and manufacturer guidelines all require regular system maintenance. This is essential to help ensure your suppression system is ready to respond in a fire emergency. But maintenance costs can be significant over the life of a system and must be considered early on. Because Stat-X fire suppression has no distribution piping or pressurized agent vessels, maintenance activity is minimized. This dramatically decreases total cost of ownership compared to other systems. TECHNOLOGY KEY MAINTENANCE TASKS Water Mist Halocarbon Dry Chemical CO2 Flow alarm & drain test Clean or replace screens Nozzle water test flow Valve tear-down, inspect Test FACP actuation, weigh cylinders Blow out piping Hydrostatic test hose Test FACP actuation, blow out piping Tear-down & replace agent Test FACP actuation, check pressure & agent quantity Hydrostatic test cylinder, refill unrecovered agent INTERVALS Quarterly Annual 2-years 6-years MAINTENANCE COSTS OVER 10 YEARS (Service call: $785/day) Stat-X Dry Chemical Inert Gas Stat-X Test FACP actuation, check pressure & agent quantity Hydrostatic test cylinders, refill unrecovered agent Test FACP actuation, examine Stat-X hardware CO2 Halocarbon Inert Gas Water Mist 0 $5,000 $10,000 $15,000 $20,000 $25,000 $30,000 The number of required maintenance tasks, their complexity and frequency determine costs over time. Tasks shown above are taken from UL-listed design, installation, operation and maintenance manuals from various manufacturers. By comparison, Stat-X system inspection and maintenance has fewer tasks, saving both time and labor. Fire Professionals Are Switching to Stat-X! Fire safety professionals who do cost-to-benefit risk analysis quickly realize Stat-X fire suppression is the most economical system, offering the most effective fire protection, for many special hazard applications. What Our Customers Are Saying The inherent flexibility of design combined with equipment and labor savings allows them to enhance coverage for currently protected assets and add coverage to previously neglected areas. }Stat-X protecting one of our CNC machines discharged due to fire, suppressing it. The area was unmanned and the automatic system stopped the fire from spreading. We were up and running again fast! ~ - Manufacturer, Geneva, IL }It works wonders. One Stat-X First Responder knocked down the fire. They are life savers.~ - Firefighter, Deer Park, NY }After researching available special hazard systems for the very best protection as well as compliance with safety and environmental issues we found Stat-X technology as the product leader.~ Engineer, Leicestershire, UK
6 Quality You Can Count On Our high quality aerosol fire suppression generators are built to last and built to be effective. Their outstanding fire suppression performance and long service life is rooted in meticulous manufacturing practices. n Proprietary fire suppression compound is precisely formulated, milled and blended from the best reagent grade chemicals n Architectural grade stainless steel and an impervious metallized membrane create a highly corrosion and oxidation resistant housing n Manufacture to the tightest engineering tolerances and tested to MIL-STD-810 so units resist environmental effects and temperature extremes n Partner with leading fire panel makers to ensure full detection and control integration with Stat-X hardware n State-of-the-art processes are regularly audited and inspected by certified third parties n ISO-9001 n American Bureau of Shipping n Bureau Veritas n Underwriters Laboratories Our Mission: Protect Lives and Property This is what we do. Our team has decades of experience in special hazard fire protection and is dedicated to finding the most effective and economical ways to apply aerosol fire suppression technology in the widest range of applications. Contact us. Let s work together to protect lives, property, and fight off the disruptive costs of fire at your business. Scan for video Fireaway Inc Baker Road Minnetonka, MN USA Fireaway Inc. All rights reserved Made in USA PN /13 Stat-X and Stat-X First Responder are registered trademarks of Fireaway Inc.
Alarm and Detection/Suppression
Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent
Automatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY
NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY Presented by: James Goerl Metro Protection Systems, Inc. [email protected] Agenda Introduction & Learning Objectives History
3M Novec 1230 Fire Protection Fluid For Telecommunications and Data Center Applications. Stay
3M Novec 1230 Fire Protection Fluid For Telecommunications and Data Center Applications Stay in Touch 3M Novec 1230 Fire Protection Fluid For Telecommunications and Data Center Applications Engineered
For Data Center and Control Room Applications
For Data Center and Control Room Applications Nearly zero wetting No costly clean up or equipment replacement Sustainable design Quick system recharge, minimal downtime No need for assurance of tight room
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days
All You Ever Wanted to Know About Fire Extinguishers...
All You Ever Wanted to Know About Fire Extinguishers... There are basically four different types or classes of fire extinguishers, each of which extinguishes specific types of fire. Newer fire extinguishers
ANSUL. Restaurant Fire Suppression Systems ANSUL UL 300 ANSUL. LOW ph
Restaurant Fire Suppression Systems UL 300 LOW ph The Ansul R-102 System. State-of-the-art in restaurant fire protection. Meeting the fire protection challenge. In 1962, Ansul recognized that there was
ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
For Data Center and Control Room Applications
For Data Center and Control Room Applications Nearly zero wetting No costly clean up or equipment replacement Sustainable design Quick system recharge, minimal downtime No need for assurance of tight room
How intelligent must an extinguishing solution be to keep fire virtual?
How intelligent must an extinguishing solution be to keep fire virtual? Intelligent means: fire protection from Siemens. Sinorix intelligent extinguishing solutions. Answers for infrastructure. Sinorix
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust / 2 / / 3 / Trust in Tyco Tyco s AquaMist Systems Tyco Fire Protection Products helps to keep people, property and the environment
PANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-281
PANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-281 PanCanal Building Albrook, Panama City Republic of Panama Tel: (507) 501-5355 [email protected] To: Ship-owners/Operators, Company Security
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
F.Y.I. Specifying Fire Protection Systems Using Division 13
F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes
Fire Extinguishers. A Health and Safety Guideline for Your Workplace. Fire Extinguishing Methods. Introduction. Types of Extinguishers
A Health and Safety Guideline for Your Workplace Introduction Fire extinguishers are designed to put out or control small fires. A small fire, if not checked immediately, will soon spread out of control.
DATA CENTER FIRE PROTECTION
DATA CENTER FIRE PROTECTION DATA CENTER FIRE PROTECTION The following is a summary of a few key fire protection, detection, and suppression technologies used by Minimax Fire Solutions in data centers and
BRANCH SOLUTION. Automatic fire extinguishing systems for paint spraying plants. Safe for certain.
BRANCH SOLUTION Automatic fire extinguishing systems for paint spraying plants Safe for certain. ISK IDENTIFYING With the extreme high degree of automation in painting technology, the risk of fire has
Fire Protection Options for Data Centres
Fire Protection Options for Data Centres Mark L. Robin, PhD DuPont Chemicals & Fluoroproducts [email protected] Introduction Modern data centres are characterized by spaces filled with ever-increasing
Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS
Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS DO YOU CONTROL THE RISK OF FIRE AT
P/N 90-FM200M-000 2004 FM-200 ECS
P/N 90-FM200M-000 FM-200 ECS Series Engineered Fire Suppression Systems Design, Installation, Operation and Maintenance Manual R LISTED FM APPROVED UL Listing File No. EX 4674 FM File 3014861 P/N 90-FM200M-000
mobile pipeline Bulk transportation and storage of energy gases
mobile pipeline Bulk transportation and storage of energy gases 1 An advanced pipeline to supply energy gases over long distances at competitive costs capacity matters Your mobile pipeline In 2006, Hexagon
University of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
ENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY
Office of Deputy Commissioner of Maritime Affairs THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY Marine Notice FIR-001 Rev. 06/12 TO: SUBJECT: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303
WATER MIST HAND PORTABLE FIRE EXTINGUISHERS Model B270 ¾ Gallon Model B272 2 ½ Gallon INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 6303 All fire extinguishers should be installed, inspected
2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230
Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec
THE F-GAS REGULATION AND ITS IMPLICATIONS IN FIRE SUPPRESSION APPLICATIONS
THE F-GAS REGULATION AND ITS IMPLICATIONS IN FIRE SUPPRESSION APPLICATIONS Mark L. Robin, Ph.D. DuPont Fluoroproducts P.O. Box 80711, Wilmington, DE 19880-0711 Tel: 302-999-5002; Fax 302-999-2093 [email protected]
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
CBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
To: All Shipowners, Ship Managers, Ship Masters and Classification Societies
海 事 處 船 舶 事 務 科 香 港 中 環 統 一 碼 頭 道 38 號 海 港 政 府 大 樓 ---------- 香 港 郵 箱 4155 號 MARINE DEPARTMENT Shipping Division Harbour Building 38 Pier Road, Central, Hong Kong ----------- G.P.O.Box 4155 網 站 Website
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
melbourne//australia data center specifications internet + intellectual property + intelligence tel: +61 2 9948 8888 fax: +61 2 9948 1111
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Melbourne,. We can colocate standard rack-mountable servers or other
CO 2. fire extinguishing systems
fire extinguishing systems Extinguishing technique is a colourless, odourless and electrical non-conductive gas. In systems the is mixed with a special identifiable odour. The extinguishing effect of is
Kompressoren. Adsorption Dryer AD
Kompressoren Adsorption Dryer AD Adsorption Drying: why? Modern industries require compressed air that is increasingly filtered with low dew point and condensate. Today, the equipment is more sophisticated
Question: How effective is Tundra Fire Extinguishing Spray vs. a Traditional Fire Extinguisher?
Introduction First Alert has launched Tundra Fire Extinguishing Spray, a Strong, Accurate, Fast and Effective new home-safety tool to extinguish fires. Tundra Fire Extinguishing Spray contains a powerful,
GAS EXTINGUISHING SYSTEMS INERT GAS EXTINGUISHING SYSTEMS. Argotec Liquid Argon Gas Extinguishing Technology (LAR)
GAS EXTINGUISHING SYSTEMS INERT GAS EXTINGUISHING SYSTEMS Argotec Liquid Argon Gas Extinguishing Technology (LAR) INNOVATION modern technologie snuffed out cold Argotec liquid argon gas ex tinguishing
IWMC 2015, Amsterdam, October 28-29, 2015 Practical experience from actual water mist installations. What can be learnt?
IWMC 2015, Amsterdam, October 28-29, 2015 Practical experience from actual water mist installations. What can be learnt? Magnus Arvidson Fire Research SP Technical Research Institute of Sweden [email protected]
singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
Description of Thermal Oxidizers
Description of Thermal Oxidizers NESTEC, Inc. is a full service equipment supplier specializing in solutions for plant emission problems. The benefit in working with NESTEC, Inc. is we bring 25+ years
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
PANAMA MARITIME AUTHORITY
PANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-226 PanCanal Building Albrook, Panama City Republic of Panama Tel: (507) 501-5000 [email protected] To: Ship-owners/Operators, CSO, Legal Representatives
Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems
Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration
OSHA Combustible Dust Inspections Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration Overview Background Information OSHA Combustible
FOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS
EXAMINATION REQUIREMENTS FOR FIRE SUPPRESSION SYSTEM CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS REGULATION
MATHESON REFINERY PROGRAM for Specialty Gas Supply. Experience the MATHESON Commitment to Supply Chain Excellence
MATHESON REFINERY PROGRAM for Specialty Gas Supply MATHESON REFINERY PROGRAM for Specialty Gas Supply MATHESON is a single source for industrial, medical, specialty, and electronics gases as well as gas
Technical Information
Subject Maintenance, Testing and Inspection of Fire Protection Systems and Fire Fighting Systems and appliances on board the Singapore flag ships To whom it may concern Technical Information No. TEC-0977
FLAMMABLE AND COMBUSTIBLE LIQUIDS
GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
Corrosion Inhibition of Dry and Pre-Action Fire Suppression Systems Using Nitrogen Gas
Corrosion Inhibition of Dry and Pre-Action Fire Suppression Systems Using Nitrogen Gas Josh Tihen Corrosion Product Manager Potter Electric Signal Company, LLC 1609 Park 370 Place St. Louis, MO 63042 (800)
SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR E Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G IMO Ref. T4/4.03 MSC/Circ.848 8 June 1998 REVISED GUIDELINES FOR
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
MATERIAL SAFETY DATA SHEET
MATERIAL SAFETY DATA SHEET SECTION 1. PRODUCT IDENTIFICATION PRODUCT NAME: CHEMICAL NAME: Nitrogen, compressed Nitrogen FORMULA: N 2 SYNONYMS: Nitrogen gas, Gaseous Nitrogen, GAN August 1997 MANUFACTURER:
BERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
HELI-DECKS & HELI-PORTS
1 HELI-DECKS & HELI-PORTS GENERAL FOAM INFORMATION DESCRIPTION Helicopters provide a level of convenience that is probably unequaled by other forms of transport. While helicopters can land in the middle
Breakthrough Solenoid Valve Technology for Upstream Oil and Gas Heating Equipment
Breakthrough Solenoid Valve Technology for Upstream Oil and Gas Heating Equipment by Bob Cadwell, Gerry Longinetti, and James Chiu A White Paper From ASCO Introduction Low-temperature stainless steel fuel
Safety data sheet for product
Safety data sheet for product 1. PRODUCT AND COMPANY IDENTIFICATION Product name: Lithium ion rechargeable battery cell Product code: None (All cylindrical models Sanyo manufactured and whose capacity
FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES
FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES Fire and Life-Safety Group (FLS) FLS has organized the following information to act as a guideline/checklist for any inspection, maintenance,
Maximum uptime and optimum fire safety for your data center
Maximum uptime and optimum fire safety for your data center Integrated and tailored fire safety solutions from one partner Answers for infrastructure. Complete solutions for a safe data center with a single
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Medical Air Systems: Scroll
GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing
Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
E2-E3: ELECTRICAL CHAPTER-13 FIRE PROTECTION SYSTEM- EVOLVING TRENDS AND APPLICABILITY TO DATA CENTRE
E2-E3: ELECTRICAL CHAPTER-13 FIRE PROTECTION SYSTEM- EVOLVING TRENDS AND APPLICABILITY TO DATA CENTRE BSNL, India For Internal Circulation Only Page: 1 Fire Protection System- Evolving Trends & Applicability
PERFORMANCE AT HAND. RED LINE Hand Portable Fire Extinguishers
PERFORMANCE AT HAND RED LINE Hand Portable Fire Extinguishers MODEL 5 The Model 5 has a slim design for use on vehicles and machinery where space is limited. Typical applications include small trucks,
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
globe reactions made easy Process perfection
globe reactions made easy Process perfection Benefits More reactions in less time: The Globe oil drain unit and quick clamp allow single hand vessel changes in seconds Space saving: 50ml, 100ml, 250ml,
Transformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
REPUBLIC OF ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT SHIPS, AND RECOGNIZED ORGANIZATIONS
REPUBLIC OF Marine Notice THE MARSHALL ISLANDS No. 2-011-14 OFFICE OF THE MARITIME ADMINISTRATOR Rev. 2/12 TO: SUBJECT: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT SHIPS, AND RECOGNIZED
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
Potential problems with computer hard disks when fire extinguishing systems are released
Extinguishing White Paper Potential problems with computer hard disks when fire extinguishing systems are released Disclaimer All statements, information and recommendations in this document are believed
MATERIAL SAFETY DATA SHEET (MSDS)/SAFETY DATA SHEET (SDS)
I. Product and Company Identification Product Name: VetScan FeLV-FIV Test A point of care blood diagnostic product Part Numbers: 250-0000-5, 250-0000-25 Manufactured For Abaxis By: SA Scientific, Inc.
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
Element D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
Ethanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES
New York City Administrative Code - Title 29 New York City Fire Code SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES 2706.1 Scope. This section shall govern the storage, handling and use of laboratory
Engineered Carbon Dioxide (CO 2 )
P/N 81-CO2MAN-001 February 2007 Engineered Carbon Dioxide (CO 2 ) Fire Suppression Systems Design, Installation, Operation and Maintenance Manual R LISTED UL Listing File No. EX 4674 FM APPROVED FMRC J.I.OX6A2.AF
C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).
SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE
LASER CUTTING OF STAINLESS STEEL
LASER CUTTING OF STAINLESS STEEL Laser inert gas cutting is the most applicable process type used for cutting of stainless steel. Laser oxygen cutting is also applied in cases where the cut face oxidation
Enclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: [email protected]. The Passive Fire Protection Specialists
Enclosures Sturdy single and double wall fire protection construction Impact resistant Fast & easy installation Pre-manufactured and modular Available in galvanized, stainless steel & other specialty metals
Pressure Vessels (Air Compressors) and LPG Tanks
Pressure Vessels (Air Compressors) and LPG Tanks 1. Identification of Workplace Hazard Any container, tank or vessel that contains pressurized material is a potential hazard to employees due to the force
STORED PRESSURE STAINLESS STEEL
STORED PRESSURE STAINLESS STEEL WATER FIRE EXTINGUISHERS Model 240-2-1/2 Gallon OWNER'S SERVICE MANUAL NO. 05601 INSPECTION, MAINTENANCE AND RECHARGE All fire extinguishers should be installed, inspected
TECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
Portable Fire Extinguisher Presentation
Slide 1 Fire Extinguisher Training A requirement of all Clemson University Employees as mandated by OSHA: Portable fire extinguishers. - 1910.157 Welcome to the Clemson University Online Fire Extinguisher
EVAPCO ENGINEERING. Commercial HVAC. District Energy. Industrial Process. Industrial Refrigeration. Power
Since its founding in 1976, EVAPCO, Incorporated has become an industry leader in the engineering and manufacturing of quality heat transfer products around the world. EVAPCO s mission is to provide first
MATERIAL SAFETY DATA SHEET
MATERIAL SAFETY DATA SHEET SECTION 1. PRODUCT IDENTIFICATION PRODUCT NAME: CHEMICAL NAME: FORMULA: SYNONYMS: Helium, compressed Helium He Helium gas, Gaseous helium, Balloon gas MANUFACTURER: Air Products