FIRE DETECTION/INERGEN SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS
|
|
|
- Darren Russell
- 10 years ago
- Views:
Transcription
1 PART 1 - GENERAL FIRE DETECTION/INERGEN SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS 1.01 DESCRIPTION OF WORK: A. Design and installation of an engineered fire detection and INERGEN total flooding, gaseous agent, fire suppression system as manufactured by Ansul Fire Protection, Marinette, Wisconsin. B. Drawings: The contract drawings indicate the general arrangements of the areas to receive detection and INERGEN protection. Contractor is to review all drawings so that all items affecting the operation of the fire detection/inergen suppression system (such as equipment location, air diffusers, damper closures, and door openings) are considered in the design of the engineered system APPLICABLE PUBLICATIONS: A. The following publications of the issues listed below, but referred to thereafter by basic designation only, form a part of this specification to the extent indicated by the reference thereto (latest edition): 1. National Fire Protection Association (NFPA) Standards: No Clean Agent Fire Extinguishing Systems No. 70 National Electric Code No. 72 National Fire Alarm Code 2. Factory Mutual Systems (FM) Publication Factory Mutual Approval Guide 3. Underwriters Laboratories, Inc. (UL) Publication Fire Protection Equipment Directory with quarterly supplements 4. Department of Transportation (DOT) Title 49 Code of Federal Regulations Parts 100 to 199 Transportation of Hazardous Materials, DOT3AAZ300 or 3AAZ15T 5. National Electrical Manufacturers Association (NEMA) Publication Enclosures for Industrial Controls and Systems 6. Industrial Risk Insurers Interpretive Guide (Detection & Controls) 7. U.S. Environmental Protection Agency, Protection of Stratospheric Ozone 59 FR 13044, March 18, 1994 (Final SNAP Ruling)
2 8. Requirements of the Authority Having Jurisdiction (AHJ) 1.03 REQUIREMENTS: A. This installation shall be made in strict accordance with the drawings, specifications and applicable National Fire Protection Association Standards. All equipment and devices used shall be listed in both the UL Fire Equipment Directory and the Factory Mutual Approval Guide. B. Design and installation of the fire detection/inergen suppression system will be in strict accordance with the following guidelines and regulatory agencies: 1.04 GENERAL: 1. NFPA 2001 Clean Agent Fire Extinguishing Systems 2. NFPA 72 National Fire Alarm Code, Latest Edition 3. NFPA 70 National Electric Codes, Latest Edition 4. Americans with Disabilities Act, Title 24, Latest Edition 1. Furnish all engineering design and materials for a complete fire detection/inergen suppression system including charged INERGEN storage cylinders, nozzles, control panel, detectors, wiring, alarm and all other equipment necessary for a complete operational system. 2. Major system components shall be produced by Ansul Fire Protection (no alternatives) and shall be installed by Interstate Fire Protection of North Conway, NH and Gardiner, ME an authorized Ansul distributor certified for the design and installation and service of INERGEN suppression systems. 3. Contractor shall, as a minimum, provide 24-hour emergency service, 7 days a week and shall be able to respond to an emergency situation within 4 hours of receiving an emergency trouble call. In addition, contractor shall maintain no less than $2 million liability insurance SUBMITTAL: 1. The following shall be submitted for approval prior to delivery of materials: A. Material and equipment information shall include manufacturer s catalog cut sheet and technical data for each component or device used in the system. This shall include, but not be limited to, the following: a. Detectors b. Manual discharge switches c. Control panel d. Release devices e. Alarm devices f. Agent storage cylinders g. Mounting brackets
3 h. Discharge Nozzles i. Abort stations j. Piping isometrics k. Flow calculations B. Provide information outlining the warranty of each component or device used in the system. C. Provide information outlining the operation and maintenance procedures that will be required of the owner. This information shall explain any special knowledge or tools the owner will be required to employ and all spare parts that should be readily available. D. Drawings shall indicate locations, installation details and operation details of all equipment associated with the INERGEN system. Floor plans shall be provided showing equipment locations, piping, point-to-point wiring and other details as required. Isometric piping layouts shall be provided with the shop drawings. In addition, point-to-point electrical layout drawings shall be provided. E. Sequence of operation, electrical schematics and connection diagrams shall be provided to completely describe the operation of the INERGEN system controls. PART 2 PRODUCTS 2.01 SYSTEM DESCRIPTION AND OPERATION: 1. The system shall be an INERGEN total flooding, gaseous, clean agent; fire suppression system designed to provide a uniform concentration of INERGEN for the protected area. A. The amount of INERGEN to be provided shall be the amount required to obtain a uniform (minimum) concentration as required by the design manual for ten (10) minutes. (Ansul INERGEN design, installation, recharge & maintenance manual part # ; U.L. file # EX 4510.) Take into consideration such factors as un-closable openings (if any), rundown time of fans, time required for dampers to close (and requirements for any additional dampers), and any other feature of the facility that could affect concentration. The design concentration shall be by volume at 70 F. B. Cross-Zone Smoke Detection: The INERGEN system shall be automatically actuated by cross-zoned detection circuits. Smoke detectors shall be ionization detectors and photoelectric with compatibility listings for use with the control unit. Smoke detectors shall be installed at no more than 250 square feet (37 m) of coverage per detector. The detectors shall be alternated throughout the protected area with the system requiring two (2) detectors in alarm prior to automatic agent release.
4 2.02 SEQUENCE OF OPERATION: A. Activation of any single detector in any detection zone shall: 1. Cause a first-stage alarm (Horn/Strobe slow cadence). 2. Operate relay contacts for building alarm annunciation. Relay contacts are provided by two onboard relays, one for each protected zone. Wiring and termination to owner s equipment shall be provided by others. 3. Energize a corresponding lamp on the activated detector and control panel. B. Activation of a detector on the second zone shall: 1. Cause a second-stage (pre-discharge) alarm to operate, Horn/Strobe and Strobe. The horn shall sound at March Time cadence and a strobe at the protected area entrance shall illuminate. 2. Initiate a programmable time delay (INERGEN agent release). 3. Operate auxiliary relay contacts to operate interconnected equipment such as HVAC shutdown and/or power off. Wiring and termination to owner s equipment shall be provided by others. C. Upon completion of the time delay the INERGEN system shall: 1. Cause a discharge alarm to be activated, Horn/Strobe and Strobe. Horn shall sound a steady tone 2. Energize release actuator for INERGEN cylinders releasing gaseous agent into the protected area AUXILIARY COMPONENTS: A. Double action manual releasing stations shall be provided at each exit of the protected area and shall, when activated, immediately release the INERGEN agent and cause all audible/visual alarms to activate. In addition, activation of the manual releasing stations shall cause immediate shutdown of interconnected electrical circuits.
5 B. Abort stations shall be provided at each exit of the protected area and shall, when operated, interrupt the discharge of INERGEN agent and emergency power-off functions. The abort stations shall be momentary devices (dead-man) requiring constant pressure to maintain contact closure. Note: Manual Releasing Station activation shall override any abort station. Abort station operation shall be per IRI and FM guidelines. PART 3 - MATERIAL AND EQUIPMENT 3.01 GENERAL REQUIREMENTS: A. Materials and equipment shall be of a single manufacturer (Ansul Fire Protection). Alternates will not be accepted. The name of the manufacturer and the serial numbers shall appear on all major components GENERAL MATERIALS - ELECTRICAL: A. All electrical enclosures, raceways and conduits shall be employed in accordance with applicable codes and intended use and contain only those electrical circuits associated with the fire detection and control system and shall not contain any circuit that is unrelated to the system. B. Unless specifically provided otherwise in each case, all conductors may be U.L approved, plenum rated fire wire, run without a conduit or raceway. C. Any conduit or raceway exposed to weather or other similar conditions shall be properly sealed and installed to prevent damage. Provisions for draining and/or drying shall be employed. D. NEMA rating and/or electrically hazardous classifications shall be observed and any equipment or materials installed must meet or exceed the requirements of service. E. Any wiring shall be of the proper size to conduct the circuit current but shall not be smaller than #18 AWG unless otherwise specified for a given purpose. Wire that has scrapes, nicks, gouges or crushed insulation shall not be used. The use of aluminum wire is strictly prohibited. F. Splicing of circuits shall be kept to a minimum and are only to be found in an electrical device suited for the purpose. G. Wire spliced together shall have the same color insulation. H. Wire splices shall be made with appropriate devices suited for the purpose.
6 I. White colored wire shall be used exclusively for the identification of the neutral conductor of an alternating current circuit. J. Green colored wire shall be used exclusively for the identification of the earth ground conductor of an AC or DC circuit CONTROL SYSTEMS - GENERAL: A. All control systems shall be UL Listed or FM approved and be utilized with listed or approved compatible operating devices and shall be capable of the following features: 1. Ground fault indication 2. Supervised detection circuit(s) 3. Supervised alarm circuit(s) 4. Supervised release circuit(s) 5. Supervised manual pull circuit 6. Supervised primary power circuit 7. Alarm overrides trouble logic 8. Battery standby 9. Front panel indicating lamps (LEDs) 10. Key lock steel enclosure 11. Programmable time delay 12. Programmable detection logic 13. Prioritized trouble logic 14. Microprocessor based logic 15. History buffer 3.04 CONTROL PANEL ANSUL Z-10 CONTROL SYSTEM: A. The control panel shall be an Ansul model Z-10 and shall communicate with and control the following types of equipment used to make up the system: smoke detectors, manual release/abort stations, alarm notification appliances, releasing components and other system controlled devices. B. System Capacity - The control panel shall include two Style Y/Z (Class A/B) notification circuits, two releasing circuits, two Form- C alarm and one trouble contacts, four Style B/D (Class A/B) initiating circuits, two Style B/D (Class A/B) manual release circuits, and two Style B/D (Class A/B) abort circuits. For two zone applications, manual release & abort circuits are combined on one special purpose monitor circuits, and are controlled via an abort supervision module. (Current limiter). For class A wiring, onboard class A adapter modules are available. C. System Display - The system display shall indicate the status of the following system parameters: AC POWER: Green LED
7 SYSTEM ALARM: Red LED RELEASE: Red LED SUPERVISORY: Yellow LED SYSTEM TROUBLE: Yellow LED ALARM SILENCED: Yellow LED D. System Control Switch Operation 1. Acknowledge Switch: Activation of the control panel acknowledge switch acknowledges system status during normal operation. 2. Alarm Silence Switch: Activation of the alarm signal silence switch shall cause all alarm notification appliances to return to the normal condition after an alarm condition except after discharge time delay. 3. System Reset Switch: Activation of the system reset switch shall cause all electronically-latched initiating devices, appliances as well as all associated output devices and circuits, to return to their normal condition. Holding system reset down shall perform a LAMP TEST function and will activate the piezo sounder. E. System Operation 1. Zone Status LEDs: The alarm, supervisory or trouble LED(s) shall flash until event(s) has been acknowledged. Any subsequent new alarm, supervisory or trouble condition will resound all indications and flash new events. 2. Supervisory: A short circuit on this zone shall cause the supervisory LED to flash. The tone silence switch shall silence the piezo causing the supervisory LED to illuminate steady. An open circuit shall report as a zone trouble. F. Optional modules shall include: Relay module includes four relays, form C 120VAC, VDC, unsupervised contacts. G. The control panel shall also include the following functions: 1. Output circuits shall be protected against false activation by using a 2-step electronic activation circuit. 2. Battery/earth fault supervision shall be provided.
8 3. Adjustable delay timer shall be available, zero to thirty seconds. 4. Cross-zone option shall be selectable (two zones in alarm before release). 5. Three abort functions options shall be selectable: (1) Standard UL method; (2) IRI method; and (3) local AHJ method. 6. A second release zone and circuit are available and fully programmable. 7. A supervised manual release circuit shall be provided which, when activated, shall override the Abort AH to 12 AH battery options shall be available providing up to 90 hours standby. 9. A watchdog timer to supervise microprocessor shall be provided. 10. Slide-in zone identification labels shall be provided. H. Power Supply 1. The power supply shall be integral to the control panel and provide all control panel and peripheral device power needs. 2. Input power shall be 120 VAC, 60 Hz. The power supply shall provide an integral battery charger for use with batteries up to 12 AH. 3. The power supply shall also provide 2 amperes of regulated 24 VDC power for each release circuit and alarm notification circuits, (3A max. per panel). Aux power output for four-wire smoke detectors or other is rated at 24 VDC up to 750 ma, resettable or non-resettable. 4. The power supply shall be designed to meet UL and NFPA requirements for power-limited operation on all notification and initiating circuits. 5. Positive-temperature-coefficient thermistors, circuit breakers, fuses, or other over-current protection shall be provided on all power outputs. I. Mechanical Design The control panel shall be housed in a cabinet designed for mounting directly to a wall or vertical surface. The back box and door shall be constructed of.060 steel with provisions for electrical conduit connections
9 into the sides and top. The door shall provide a key lock and include a glass or other transparent opening for viewing of all indicators. The cabinet shall be approximately 4.25 inches (127 mm) deep, and 14.5 inches (368 mm) wide, and 16 inches (406 mm) high. An optional trim ring shall be used for flush mounting of the cabinet. Space shall be provided in the cabinet for 7 AH or 12 AH batteries. J. Batteries 1. Batteries shall be 2-12 volt, Gel-Cell type providing 24 VDC. 2. Batteries shall have sufficient capacity to power the fire alarm system for not less than 24 hours in standby plus 10 minutes of alarm upon a normal AC power failure. 3. The batteries are to be completely maintenance free. No liquids are required. Fluid level checks, refilling, spills and leakage shall not be accepted MANUAL PULL STATION A. A manual pull station shall, when operated, cause an immediate release of the INERGEN suppression agent. They shall use a key operated test-reset lock and shall be designed so that after actual emergency operation, they cannot be restored to normal use except by the use of a key. B. All operated stations shall have a positive, visual indication of operation. C. Manual stations shall be metal with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front and both sides of the stations. D. Stations shall be suitable for surface mounting or semi-flush mounting as shown on the plans, and shall be installed not less than 42 inches (1.06 m), nor more than 48 inches (1.22 m) above the finished floor. E. Operation shall require two (2) actions SMOKE DETECTORS A. Smoke detectors shall be 24 VDC and shall be UL listed and FM approved. B. Each detector shall include a visual status indicator, provide remote LED output, and include a built-in test capability. C. The sensitivity shall be factory set per UL 268. D. The detector cover and screen shall be easily removable for field cleaning.
10 E. The head-to-base connection shall be made by use of bifurcated contacts. Terminal connections to the base shall be the screw type that are accessible with the base installed on the mounting box. F. Ionization-type smoke detector shall be the dual chamber type and compatible with the Ansul control system. The detector shall have an LED in its base, which is illuminated in a steady-on mode when in alarm, and pulse mode when in standby. Reset of the detector shall be performed by the control unit reset switch. G. The design of the ionization detector compensating circuits shall provide stable operation with regard to minor changes in temperature, humidity and atmospheric conditions H. Photoelectric type smoke detector shall be the light reflective type and compatible with the Ansul control system. The detector shall have an LED in its base, which is illuminated in a steady-on mode when in alarm, and pulse mode when in standby. Reset of the detector shall be performed by the control unit reset switch I. The design of the photoelectric detector compensating circuits shall provide stable operation with regard to minor changes in temperature, humidity and atmospheric conditions. J. Photoelectric-type smoke detector with heat detector shall be the light reflective type and compatible with the Ansul control system. The detector shall have an LED in its base, which is illuminated in a steady-on mode when in alarm, and pulse mode when in standby. Reset of the detector shall be performed by the control unit reset switch INDICATING APPLIANCES: A. Sounder/Strobe Combination 1. The sounder/strobe combination shall operate on 24 VDC and shall be approved for use with the listed control system. 2. The sounder/strobe combination shall be polarized and powered from the control unit. 3. The device shall be UL listed or FM approved. 4. The strobe shall be listed to UL Standard 1971 for the Hearing- Impaired, approved for Fire Protective Service, and rated at either 15 cd or 75 cd.
11 5. The sounder shall have eight (8) tone options selected by means of programming clips. B. Strobe 1. The strobe shall operate at 24 VDC and shall be approved for use with the listed control system. 2. The strobe shall be polarized and powered from the control unit. 3. The strobe shall be UL listed or FM approved. 4. The strobe shall be listed to UL Standard 1971 for the Hearing- Impaired, approved for Fire Protective Service, and rated at either 15 cd or 75 cd ABORT SWITCH: A. The abort switch shall be used where an investigative delay is desired between detection and actuation of the fire suppression system. B. This switch shall be a momentary contact "dead-man" type switch requiring constant pressure to transfer one set of contacts. Clear operating instructions shall be provided at the abort switch. C. This switch shall be rated at amp make/break or 6 amp continuous carry. D. The terminal connections shall be of the screw type MAINTENANCE LOCK-OUT SWITCH: A. The maintenance lock-out switch shall be used where it is desired to disable the fire suppression system during routine maintenance. B. This switch shall be key operated allowing removal of the key in either the "Normal" or "Lock-Out" position. A red indicator lamp shall be included on the switch assembly to be illuminated when in the "Lock-Out" position. The control unit is to indicate a trouble condition when in the "Lock-Out" position. C. The switch shall include one (1) set of normally open and one (1) set of normally closed contacts rated at amp make/break or 6 amp continuous carry. D. The terminal connections shall be of the screw type.
12 3.10 SELECTOR SWITCH: PART 4 - SYSTEM ARRANGEMENT NOT APPLICABLE TO THIS INSTALLATION INERGEN SUPPRESSION SYSTEM: A. INERGEN fire suppression system shall be of the engineered, permanently piped, fixed nozzle type with all pertinent components provided by Ansul Fire Protection. B. All agent storage cylinders shall be centrally located as vertical, freestanding cylinders with wall and/or floor mounted retaining brackets. Where multiple cylinders are required for the same hazard, a common manifold shall be employed. (Cylinders mounted horizontally shall be installed in accordance to the manufacturer's design manual.) C. On multiple cylinder arrangements (discharging into a common hazard), one cylinder shall be designated as the pilot cylinder and employ the restorable electric actuator, mechanical manual actuators, or both. All remaining cylinders shall be pneumatically operated from the INERGEN agent. D. Manifolded cylinders shall employ a flexible discharge hose to facilitate installation and system maintenance. Each cylinder on a manifold shall also include an agent check valve installed to the manifold inlet FLOW CALCULATIONS: A. Computerized verification of flow calculations shall be submitted for each INERGEN fire suppression system and include the following data as a minimum: 1. Quantity of agent per nozzle 2. Orifice union/nipple and nozzle orifice diameters 3. Pressure at nozzle (psi) 4. Nozzle body nominal pipe size (inch) 5. Number and size of cylinders 6. Total agent 7. Pipe size per pipe section 8. Pipe schedule per pipe section 9. Number, size and type of fitting per pipe section 10. Actual length per pipe section (feet) 11. Equivalent length per pipe section (feet)
13 12. Discharge time (seconds) PART 5 - EQUIPMENT AND MATERIAL (MECHANICAL) 5.01 PIPE MATERIAL - INERGEN SYSTEM: A. System piping shall be of non-combustible materials having physical and chemical characteristics such that its integrity under stress can be predicted with reliability. B. As a minimum, piping materials shall be black steel pipe conforming to ASTM A-53A ERW or ASTM A-106A seamless. C. Under no conditions shall ordinary cast iron pipe, steel pipe conforming to ASTM A-120 or ASTM A-53/A-120 be used. D. Piping joints shall be suitable for the design conditions and shall be selected with consideration of joint tightness and mechanical strength. E. As a minimum, fittings beyond the orifice union/nipple shall be black, 300 lb. class fittings conforming to ANSI B Ordinary cast iron fittings shall not be used. Distribution piping downstream of the orifice union must be a minimum of Schedule 40. F. The system manifold up to the orifice union/nipple must be constructed of Schedule 80 piping and 2000 lb. or 3000 lb. forged steel fittings. G. All piping shall comply with NFPA H. Piping shall be installed in accordance with good commercial practice to the appropriate codes, securely supported with UL Listed hangers and arranged with close attention to the design layout since deviations may alter the design flow performance as calculated. I. Piping shall be bracketed within 12" (.3 m) of all discharge nozzles. J. All piping shall be reamed, blown clear and swabbed with appropriate solvent to remove mill varnish and cutting oils before assembly. K. Multi-outlet fittings other than tees shall not be permitted. L. Assembly of all joints shall conform to the appropriate standards. Threaded pipe joints shall utilize Teflon tape applied to the male threads only EXTINGUISHING AGENT: A. The agent shall be INERGEN, a trademark name registered to Ansul Fire Protection.
14 5.03 INERGEN STORAGE CYLINDERS: A. Cylinder assemblies shall be of steel construction with a standard RED epoxy paint finish. Each cylinder shall be equipped with a pressure seattype valve and gauge. The system shall utilize Ansul's CV-98 valve assemblies. When the system's capacity exceeds 40 cylinders, a second pilot valve shall be provided and used for cylinder activation. Each valve shall be constructed of forged brass and shall attach to the cylinder providing a leak tight seal. Each valve shall also include a safety pressure relief device that provides relief at PSI per CGA test methods. B. Filling of the cylinder assembly shall be by Ansul Fire Protection or an authorized INERGEN systems distributor in conjunction with a factory authorized INERGEN agent filling station. Initial filling and recharge shall be performed in accordance with the manufacturer's established procedures and shall not require replacement components for normal service CYLINDER BRACKET: A. Each cylinder assembly shall be furnished with a bracket made from welded steel. The bracket shall hold the cylinders in a saddle with a front bracket piece that secures the cylinders. The brackets shall be modular in design to allow added bracketing or stacking of cylinders depending on installation requirements. B. Cylinder brackets shall be UL listed and/or FM approved for use with the INERGEN system VALVE ACTUATORS: A. Electric valve actuators shall be of brass construction and stackable design with swivel connections to allow removal of actuators for maintenance or testing. B. Operation of actuators shall not require replacement of components. NO ELECTRO-EXPLOSIVE DEVICES may be used to actuate the valve assembly. C. Electric actuators shall be continuous duty type for 24 VDC operation. D. Actuation devices shall be UL listed and/or FM approved for use with the INERGEN system DISCHARGE HOSE/CHECK VALVE:
15 A. When manifolding, all cylinder assemblies shall include a flexible discharge hose and check valve for connection to the manifold inlet. B. All hose/check valves shall be UL listed and/or FM approved for use with the CV-90 or CV-98 INERGEN valves as manufactured by Ansul Fire Protection DISCHARGE NOZZLES: A. Discharge nozzles shall be of two-piece construction and sized to provide flow rates in accordance with system design flow calculations. B. A nozzle inlet orifice plate shall be included. A computerized UL listed flow calculation program shall determine the orifice size. C. Orifice(s) shall be machined in the nozzle body to provide a horizontal discharge pattern based upon the approved coverage arrangements. D. Nozzles shall be permanently marked with the manufacturer's part number. The nozzles shall be threaded directly to the discharge piping without the use of special adapters. E. Nozzles shall be UL listed as manufactured by Ansul Fire Protection ORIFICE UNION/NIPPLE ASSEMBLIES: A. An orifice union/nipple shall be included in the manifold to reduce pressure in the downstream pipe network. B. Orifice union/nipple assemblies shall be rated at 2000 lb. Class minimum. C. Orifice union/nipple assemblies shall be permanently marked with the manufacturer's orifice code. The orifice union/nipple shall be threaded directly to the manifold piping without the use of special adapters. D. Orifice union/nipple assemblies shall be UL Listed and/or FM Approved for use with the INERGEN system SYSTEM CHECKOUT AND TESTING: A. The completed installation shall be inspected by factory authorized and trained personnel (Interstate Fire Protection of North Conway, NH or Augusta, Me.) The inspection shall include a full operational test of all components per the equipment manufacturer's recommendations. A full discharge test, including concentration testing will not be conducted unless specifically requested by the A.H.J.
16 PART 6 - WARRANTY B. Inspection shall be performed in the presence of the owner's representative, architect or engineer's representative, insuring authority and/or the local authority having jurisdiction. C. All mechanical and electrical components shall be tested according to the manufacturer's recommended procedure to verify system integrity. D. Inspection shall include a complete checkout of the detection/control system and certification of cylinder pressure. A written report shall be filed with the owner. E. As-built drawings shall be provided by the contractor (2 copies) indicating the installation details. All routing of piping and accessories shall be noted. F. Equipment installation and maintenance manuals shall be provided in addition to the as-built drawings. G. Prior to final acceptance, the contractor shall provide operational training in all concepts of the system to the owner's key personnel. Training shall consist of: 1. Control system operation 2. Trouble procedures 3. Abort procedures 4. Emergency procedures 5. Safety requirements 6. Demonstration of the system (excluding INERGEN release) H. The quantity of agent shall reflect the actual design quantity of INERGEN agent. I. A functional test shall be completed consisting of detection, release, alarm, accessories related to the system, control unit and a review of the cylinders, piping, fittings, hangers and cylinder pressure WARRANTY: A. All INERGEN system components furnished under this contract shall be guaranteed against defect in design, material and workmanship for the full warranty time, which is standard with the manufacturer and/or supplier but not less than one (1) year from the date of system acceptance. In addition, the installing contractor must guarantee the system against false actuation or leakage due to faulty equipment, design or workmanship for a period of one (1) year from final acceptance. In the event of INERGEN agent leakage or system discharge from any of the above conditions, the installing contractor shall completely recharge and recondition the system at no cost to the owner.
17 END OF SECTION PART 7 -MAINTENANCE 7.01 PERIODIC MAINTENANCE: A. At least semi-annually, the INERGEN system shall be inspected by INTERSTATE FIRE PROTECTION of North Conway, NH or Gardiner, ME MAINTENANCE PROCEDURES: A. The following shall be done at least semi-annually by INTERSTATE FIRE PROTECTION of North Conway, NH or Gardiner, ME an authorized Ansul distributor certified for the design and installation and service of INERGEN suppression systems: 1. Full functions test of all Detection and Control Systems 2. Agent quantity and pressure of each cylinder shall be checked using a separate, calibrated device. If the agent cylinder shows a loss in pressure (adjusted for temperature) of more than 5 percent, it shall be refilled or replaced. B. A written report shall be submitted to the system owner upon completion of each INERGEN System inspection. It shall include the following: END OF SECTION 1. System location and size. 2. Type of Detection & Control Panel used. 3. Results of Inspection and Maintenance Procedures (Pass/Fail). 4. A record of any system defects discovered. 5. A record of any structural conditions in the protected hazard that have the potential to adversely affect system performance. PART 8 SYSTEM LOCKOUT PROTOCAL 8.01 REQUIREMENTS FOR SYSTEM LOCKOUT: A. The following are circumstances that may arise that will require the INERGEN System release circuits to be locked out: 1. INERGEN System Inspection and/or Maintenance. 2. INERGEN System modification. 3. Structural work on the protected space, or equipment in the protected space that has the potential to generate the following: a. smoke
18 8.02 PROCEDURE: b. dust or dirt c. water spillage on INERGEN System components d. excessive vibration A. Communicate the date, time, nature and expected completion of the circumstance which will require the INERGEN System to be locked-out. Advise the necessary party that a system lock-out will generate a Trouble condition on the FACP. B. Communicate the above information to the following parties: 1. INTERSTATE FIRE PROTECTION of North Conway, NH or Augusta, ME. 2. The System owner. 3. The Building Supervisor of the protected space. 4. The local Fire Department. 5. The vendor providing the Building Fire and/or Security Alarm System monitoring and maintenance service. C. The Maintenance Switch shall be key operated allowing removal of the key in either the "Normal" or "Lock-Out" position. A red indicator lamp shall be included on the switch assembly to be illuminated when in the "Lock-Out" position. The control unit is to indicate a trouble condition when in the "Lock-Out" position. A key to operate this switch shall either be on the Maintenance Switch or located inside the FACP. The key shall be tagged. D. Upon completion of any procedure requiring system lock-out, the Maintenance Switch shall be operated to return to the Normal position. The red indicator lamp shall extinguish and the trouble condition shall be automatically eliminated by the FACP. E. After the system is returned to the normal condition (no indicated faults on the FACP), all relevant parties shall be advised that the visit is complete and that the INERGEN System is no longer locked-out, and has been returned to normal stand-by condition. END OF SECTION
University of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
ENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled
SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this
NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
FIRE DETECTION AND FM-200 SUPPRESSION SYSTEM
FIRE DETECTION AND FM-200 SUPPRESSION SYSTEM A. SCOPE: This specification outlines the requirements for a cross-zoned detection and total flooding FM-200 fire suppression system. The work described in
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
SECTION 16700 FIRE ALARM SYSTEM
SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
C. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
Release Control Fire Alarm Systems
SYSTEM ABORT PUSH AND HOLD COIL SUPERVISION MODULE (2 AMP) 2081-9046 RED INSTALLATION INSTRUCTIONS 574-437 REV YEL NAC+ MAINTAIN 1/4" SEPARATION BETWEEN POW ER LIMITED (RED/) AND NONPOWER S LIMITED (YEL/)
SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
DTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification
SECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
Alarm and Detection/Suppression
Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
CalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT
Invitation to Bid FIRE ALARM & DETECTION SYSTEM
Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-28 33 00.00 40 (February 2014) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS
SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM
SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Fire alarm system requirements B. Fire alarm equipment C. Fire alarm peripheral devices 1.02 RELATED SECTIONS
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days
Fire Alarm System Accessories
Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
CB200W Water Leak Detection Panel Application Guide
Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical
FIRE ALARM SYSTEM Section 16750 Page 1
FIRE ALARM SYSTEM Section 16750 Page 1 PART 1 - GENERAL 1.1 REQUIREMENTS A. Provide a complete operational, stand-alone local protective signaling system in each defined building as indicated on the contract
INTRUSION DETECTION SYSTEM Section 281600
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION
Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
A. This Standard outlines the requirements for an addressable fire detection and alarm system.
1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
BERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM
KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as
INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description
INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's
Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work
GE Security Small Building Life Safety Solutions Affordable FireShield Conventional Fire Alarm Control Panels imagination at work cost Location: Environment: Solution: Flower shop Finely decorated, gentle
16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC
1. GENERAL 1. Fire alarm system shall be manufactured by Simplex, Autocall or Edwards. Simplex part numbers are provided in this spec for clarification only and do not exclude equivalent part numbers of
FIRE DETECTION AND ALARM
Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description
SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped
SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE
SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors
D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
Life Alarm Fire Alarm Controls
FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
NATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank
Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic
Security Systems Intrusion Alarm
Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted
1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.
GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES
4-Wire Air Duct Smoke Detector Models DH-60 F-70.05 FEATURES Approvals/Listing UL 268A Listed File S1064 Factory Mutual Approved CSFM Listed #3240-1076:121 NYC MEA Listed #134-95-E City of Los Angeles
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
SECTION 16620 FIRE ALARM SYSTEM
SECTION 16620 PART 1 GENERAL FIRE ALARM SYSTEM 1.01 SUMMARY A. Work included: Labor, materials and equipment necessary to complete the installation required for the item specified under this Division,
HOW TO ORDER SAFETY PRODUCTS/SAFETY CONTROL SYSTEMS ELECTRICAL SAFETY CONTROLS
HOW TO ORDER SAFETY PRODUCTS/SAFETY CONTROL SYSTEMS PNEUMATIC SAFETY CONTROLS BASIC CONTROLS SC3000 - SELF CONTAINED 2 HAND CONTROL - STAND ALONE MODEL SC3300 - SELF CONTAINED 2 HAND CONTROL - PRESS READY
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
BERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
TrueAlarm Fire Alarm Systems
TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es
The Pennsylvania State University ------------- Physical Security Office. Intrusion Alarm. Performance Specification
The Pennsylvania State University ------------- Physical Security Office Intrusion Alarm Performance Specification By PHYSICAL SECURITY OFFICE Group (Access Controls & Electronic Security Programs) and
Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
VFR-400 Installation, Operation, and Instruction Manual
VFR-400 Installation, Operation, and Instruction Manual Releasing Panel for Sprinkler Systems All specifications subject to revision. Manual #5403548 Rev. Q 10/11 NOTES: i Table of Contents Operating