Designing the Data Center
|
|
|
- Jane Mason
- 10 years ago
- Views:
Transcription
1 Designing the Data Center Asef Baddar, RCDD May -, 00
2 Talking points What are Data Centers? Why Data Centers? The components of the Data Center Approaching the Data Center design Breakdown of the components Nuggets of information from TIA- Forward looking designs for Data Centers
3 What is a Data Center? A place to locate computer, storage and networking devices safely and securely A place that provides un-interruptible power needed to power a Company s mission critical devices A place that provides a temperature controlled environment for equipment to operate properly A place that provides connectivity to other devices inside and outside the data center
4 Components of the Data Center Physical space Raised flooring Electrical Standby Power Cooling Fire Suppression Physical security Physical access Cabling
5 Why Data Centers?
6 Why are Data Centers Important? Wiring Closet Passive connectivity Pass-through Cross-connect CEO s, CFO s, CIO s and other senior mgmt don t spend much time and focus on closets Data Center Critical Applications ERP CRM SCM Back office ecommerce Critical Computing Systems Servers Storage Networking
7 Why are Data Centers Important? 0-0% of all IT dollars are spent in the data center! Because that s where the money is! Willie Sutton
8 The Approach
9 The Approach to designing a Data Center KISS Keep it simple sir Flexibility equipment changes Scalability K sq.ft. or M sq.ft. Modularity logical and master plan for equipment Standardize consistency and uniformity The Human Factor promote good habits Don t lose your sanity! Oops will happen.
10 What is tiering? Tier Basic Tier Redundant Components Tier Concurrently Maintainable Tier Fault Tolerant
11 Tiering look
12 What is N? N = Maximum capacity needs N+ = Max. plus extra device(s) N+ = Max. plus extra device(s) N= = Max. plus extra device(s) N* (N) = doubles need N* (N) = triples need Balance Need versus cost and complexity of redundant systems
13 Tiering for availability Level of availability Percent Downtime per year Six nines. seconds Five nines. minutes and seconds Four nines. minutes and seconds Three nines. hours and minutes Two nines days, hours and 0 minutes Downtime affects productivity and business functions
14 Flexibility Data Centers are not static use products that can be easily changed or moved Cabinets that can accept various equipment Panels that accept copper or fiber Outlets that can be changed with a cord
15 vertical Scalability 0
16 Modularity
17 Standardize
18 The Human Factor
19 Hope for the best and plan for the worst
20 Understanding the components
21 Physical space Data Center selection should consider: Seismic areas use earthquake resistant technologies Ice storms ensure backup generators can run for extended periods Hurricanes shelter against high winds Tornadoes no windows Flooding build on elevated ground Landslides have retention walls Fires install fire resistant walls and suppression systems
22 Physical space continued Polluted air limit outside air or use high filtration air systems EMI build away from sources of EMI Vibration stay away from railroads, airports, major thoroughfares Political climate labor issues and materials delay Flight paths distribute servers Service provider can you get enough bandwidth
23 Raised flooring Floor height for plenum is average Ensure there is enough ceiling height for heat exhaust Weight bearing capacity should be rated with same strength as sub-floor Sub-floor shall be sealed to prevent concrete dust ESD floors shall have static control No perforated tiles in main pathways heavy equipment being transported over them can break them Ramps should have a in incline, be in width and have landings on both ends or square for maneuvering equipment
24 Electrical Electrical specification should consider: Separate power sources building system power feed shall be isolated from server equipment power feed Bypass have maintenance bypass options for normal maintenance without taking down equipment Pre-wire cabinet locations adds more upfront cost but less disruptive PDU loads do not load circuits more than 0 percent Use whips flexibility for moving power
25 Electrical continued Receptacles limit to per circuit Heavy guage wire 0 AWG is better than AWG Run six 0 AWG wires phase conductors, neutral, equipment ground and isolated ground Labeling label the circuit and location in circuit panel Convenience outlets do not tie into equipment power feed
26 Standby power Standby power should be specified with the following considerations: Sizing of UPS Use peak load and not operating load Uptime should be a minimum of 0 minutes at full load with generator backup or hours without a generator backup Generators should be designed into your Data Center if uptime will be critical for extended outages in the area Battery room ensure adequate ventilation Monitoring lights utilize color coded domes and wire the lights into the various backup systems for instant visual clues such as red for UPS and blue for generator
27 Heat is destructive to electronics For every degrees above ambient temp. (F-F) reduces equipment life by ½ Intel
28 Cooling Specifying cooling should consider: Fans balance air flow with noise Ton of cooling melting of,000 pounds of ice in hours ton =, 000 BTUs watt =. BTUs Perforated tile can displace approximately KW of heat Ideal temperature degrees is ideal Ideal static pressure in. water column
29 Cooling continued Containing pressure seal all tile cutouts, walls and doors Ideal humidity 0 percent plus or minus 0% Air handlers have a buffer space around air handlers Cabinets use solid side doors and install blanking panels on cold side intake to increase pressure Air change design for 0 air changes per hour Chilled water pipes insulate them to prevent condensation
30 Overhead discharge
31 Hot and cold aisle discharge
32 Hot and cold aisles Front Power bank HOT tile can output KW BTU s Front
33 Cooling needs chart Watts/sq.ft BTUs/sq.ft. DC size (sq.ft.) Total BTUs Tons of cooling # of air handlers ,000,0, ,000,, ,000,0, ,000,, ,000,, ,000,, ,000,0,000. -
34 Fire Suppression Fire suppression specification needs to address: Gases Inergen (IG-) removes oxygen from the air and ozone friendly Argonite (IG-) reduces oxygen in the air and ozone friendly FM-00 or HFC- absorbs heat energy and ozone friendly FE or HFC- absorbs heat energy and not ozone friendly Sprinklers has a threshold rating of degrees on the bulbs and you should utilize a dry system in the server room Smoke and heat detection allows a proactive approach Handheld extinguishers use Class C which is CO or dry foam
35 Physical security Physical security specification needs to address: Door controls use badge access or combination door locks Cages additional physical security of sensitive equipment Locking cabinets key or combination but be aware of cooling implications CCTV place at entrances into DC and at sensitive equipment Access Policies have a policy on how access is granted
36 Physical space Physical space specification needs to address: Aisle size for main thoroughfare Door size shall be a minimum of ft wide and ft high, without doorsill, hinged to open outward (code permitting) or slide side-toside, or be removable. Doors shall be fitted with a lock and have either no center post or a removable center post to facilitate access for large equipment The minimum ceiling height shall be. m (. ft) from the finished floor to any obstruction such as sprinklers, lighting fixtures, or cameras. Cooling requirements or racks/cabinets taller than ft may dictate higher ceiling heights. A minimum of in clearance shall be maintained from water sprinkler heads.
37 Cabling
38 TIA Telecommunications Infrastructure Standard for Data Centers What kind of information can I find in the document? Scope Definition Design Overview Cabling system overview Cabling system infrastructure Telecommunications spaces and Related Topologies DC cabling systems DC cabling pathways DC redundancy Multiple Annexes
39 Cabling Topologies Direct Connect Distributed
40 THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY Sample Application SD SD SD SD SD SD SD SD WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX 0 STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0
41 THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY Patch Cord into Server Sample Application SD SD SD SD SD SD SD SD WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET
42 Switch STAT Power Power Supply Supply Catalyst 00 SERI Zone Distribution Area FA N US STATUS PHONE STATUS PHONE STATUS PHONE STATUS PHONE STATUS PHONE STATUS PHONE STATUS PHONE THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY THE SIEMON COMPANY -Port Patch Panels Servers Patch Cord into Switch Patch Cord into Server Horizontal Cabling ES SD SD SD SD SD SD SD SD WS-X-GE-TX WS-X-GE-TX P O R T 0 0/00/000 BASE-T ETHERNET SWITCHING MODULE WS-X-GE-TX P O R T 0 0/00/000 BASE-T ETHERNET SWITCHING MODULE STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX STATUS P O R T 0/00/000 BASE-T SWITCHING MODULE PHONE ETHERNET 0 WS-X-GE-TX WS-X-GE-TX P O R T 0 0/00/000 BASE-T ETHERNET SWITCHING MODULE P O R T 0 WS-X-GE-TX 0/00/000 BASE-T ETHERNET SWITCHING MODULE P O R T 0 WS-X-GE-TX 0/00/000 BASE-T ETHERNET SWITCHING MODULE P O R T 0 WS-X-GE-TX 0/00/000 BASE-T ETHERNET SWITCHING MODULE P O R T 0/00/000 BASE-T ETHERNET SWITCHING MODULE 0
43 Data Center topology
44 Sample of Panel Identifiers on Rack
45 design guidelines In addition to satisfying today s telecommunication requirements, the horizontal cabling should be planned to reduce ongoing maintenance and relocation. It should also accommodate future equipment and service changes. Consideration should be given to accommodating a diversity of user applications in order to reduce or eliminate the probability of requiring changes to the horizontal cabling as equipment needs evolve. Change your equipment and not your cabling!!! Minimum of Category is recommended. Minimum of Laser Optimized 0 micron is recommended.
46 design guidelines continued For copper cabling, in order to reduce the effect of multiple connections in close proximity on NEXT loss and return loss, the horizontal distribution area termination should be located at least m (0 ft) from the main distribution area termination. *NOT necessary! Overhead cable trays should be suspended from the ceiling ohm cable (type, ) is allowed for application specific applications such as DS- Use a minimum of wide vertical management on both sides of racks and a minimum of 0 wide vertical between racks
47 design guideline continued Power strips shall be labeled with the PDU/panel identifier and circuit breaker number. Racks that are supported by the access floor shall be bolted to the cement slab or a metal channel secured to the slab by threaded rods that penetrate through the floor tiles. Sharp edges on the top of the threaded rods shall be covered using domed nuts or other method. Exposed threads under the access floor should be covered using split tubing or other method. Power strips with indicators but no on/off switch or breaker reset button should be used to minimize accidental shut-off.
48 Forward looking design
49 Overhead conveyance or under floor?
50 Utilize pre-terminated Category A systems Great for quick network deployment Excellent Channel to Channel characteristics Ideal for data center Server Row designs Lifetime System Warranty No field testing required at all 00% performance tested at factory to TIA CATA UTP or STP cables secured in braided sleeve Jack-to-Jack or Jack-to-Open configurations
51 Utilize pre-terminated MTP design Consider OM fiber or better Great for quick network deployment Cabling harness can be changed for new equipment Excellent Channel to Channel characteristics Ideal for data center connector low loss channels Lifetime System Warranty No field testing required at all 00% performance tested at Factory MTP - SC Duplex MTP - LC Duplex
52 Switch or Server Cabinet Options x CATA UTP ports in U Minimizes server or switch cabinet rack space panel options Standard Flat Angled Recessed Angled
53 Server Cabinet Panel Option VertiGO Patch Panel x CATA ports Consumes zero rack space Provides easy access to servers Improves airflow Improves cable management
54 Never worry about wiring cabinets again Reduces cabling/congestion inside of cabinet Allows for copper and/or fiber connectivity Supports 0G connectivity No need to wait on cabinets for your data center projects!!
55 Summary Simplify Build it for scalability Build it using modularity Changes to your design can impact other areas Remove the oops factor by planning
56 Thanks you for your time!
TIA-942: Data Center Standards
plantemoran.com TIA-942: Data Center Standards Sri Chalasani Merit 2010 Conference May 25, 2010 Objectives What are concerns in the data center? Data center standards & best Practices Data Center Definition
Data Center Cabling Design Trends
Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:
Data Center Designs and Hospital Operations
Data Center Designs and Hospital Operations Designing for Data Center Availability and the Effect on Daily Operations Joe Harris, PE, RCDD Senior Engineer, AECOM Data Centers and Hospitals June 10, 2015
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
TIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc [email protected]
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc [email protected] J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
LEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew [email protected] J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.
Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
Data Center Management
Data Center Management How Cisco IT Operates, Manages, and Protects Its Data Center A Cisco on Cisco Case Study: Inside Cisco IT 1 Overview The Cisco IT Operations Data Center on the San Jose, California
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial
Telecommunications Infrastructure Standard for Data Centers 802.3 Tutorial Prepared by: Jonathan Jew - J&M Consultants and Chris DiMinico - MC Communications - Co-chairs TR42.1.1 TR42: Data Center Standard
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Building a Tier 4 Data Center on a Tier 1 Budget
Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
What is a Datacenter?
What is a Datacenter? Telecom Room Primarily Cross Connect Equipment and switches. Computer room A room whose primary function is to house computer equipment. (Servers, Storage) 5 or less cabinets Small
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Zone Distribution in the Data Center
Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling
IBM Twin Data Center Complex Ehningen Peter John IBM BS [email protected]. 2011 IBM Corporation
IBM Twin Data Center Complex Ehningen Peter John IBM BS [email protected] Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power
InstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3
19 Site Location, Design and Attributes. Site Location, Design and Attributes
1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
Data Centers and Mission Critical Facilities Operations Procedures
Planning & Facilities Data Centers and Mission Critical Facilities Operations Procedures Attachment A (Referenced in UW Information Technology Data Centers and Mission Critical Facilities Operations Policy)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
Data Center Presentation
Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA
Best Practices for Wire-free Environmental Monitoring in the Data Center
White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com [email protected] Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
Energy-efficient & scalable data center infrastructure design
Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable
Electrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
How To Write An Infrastructural Standard For Data Center Infrastructure
Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
InstaPATCH ZERO Solution Guide
SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
Racks & Enclosures. Deliver. Design. Define. Three simple words that clearly describe how we approach a Data Center project.
Three simple words that clearly describe how we approach a Data Center project. Eclipse Racks & Enclosures DELIVERING THE RIGHT INFRASTRUCTURE FOR YOUR MISSION-CRITICAL NEEDS SERVER RACKS & NETWORKING
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services
About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier
OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers
Layer Zero, the Infrastructure Layer, and The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds
Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS
Upgrading the PRS datacentres: space requirement S. S. Mathur, GM-IT, CRIS PRS / UTS scenario: then and now Year 2000 PRS: 600 locations UTS: 0 locations Year 2008 PRS 1600 locations E-ticketing Passengers
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE
DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE Molex Premise Networks EXECUTIVE SUMMARY The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Rittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture By Neil Rasmussen White Paper #129 Executive Summary Significant improvements in efficiency, power density, power monitoring,
ADC-APC Integrated Cisco Data Center Solutions
Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the
Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8
Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,
OPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
UC Berkeley Data Center Overview
UC Berkeley Data Center Overview Shelton Waggener Associate Vice Chancellor & Chief Information Office [email protected] August 2006 Berkeley s Data Center Opened July 2004 Our Previous Facility (don
CANNON T4 MODULAR DATA CENTRE HALLS
CANNON T4 MODULAR DATA CENTRE HALLS Halve up-front investment, use a Modular fit out approach Highly efficient, Low PUE, Scalable system with reduced Capex and Opex Turnkey solutions available complete,
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
DATA CENTER SOLUTIONS GUIDE
DATA CENTER SOLUTIONS GUIDE designed to be better. Power Cabinets Racks Pathways Aisle Containment Connectivity and Cabling RACKS AND CABINETS Legrand s cabinets and racks, designed for all your network
singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
THE IMPACT OF CURRENT TRENDS ON THE DATA CENTER COMMUNICATIONS CABLING INFRASTRUCTURE
THE IMPACT OF CURRENT TRENDS ON THE DATA CENTER COMMUNICATIONS CABLING INFRASTRUCTURE Prepared by Michael Wood Senior Product Manager Data Center Infrastructure Systems Hubbell Premise Wiring www.hubbell-premise.com
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
NeuStar Ultra Services Physical Security Overview
NeuStar Ultra Services Physical Security Overview Mission-critical network operations must have the highest standards of quality, security and reliability. NeuStar Ultra Services currently locates its
Virtual Data Centre Design A blueprint for success
Virtual Data Centre Design A blueprint for success IT has become the back bone of every business. Advances in computing have resulted in economies of scale, allowing large companies to integrate business
Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
DESIGN GUIDELINES. Local Area Network
DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA
Containment Solutions
Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) Site Biography Market Area: Washington, DC Area Location: Ashburn, VA 20147-6011 Address: All deliveries should be sent to
How To Visit An Internet Data Center
AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina
Subject: County of Los Angeles Data Center Space Requirement
Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
OPERATIONS MANUAL DATA CENTER COLOCATION
Section I: Introduction and Service Description. OPERATIONS MANUAL DATA CENTER COLOCATION Company means MCI Communications Services, Inc., d/b/a Verizon Business Services, or any affiliated entity designated
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Technical specifications. Containerized data centre NTR CDC 40f+
Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
Intelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center