OCTOBER Layer Zero, the Infrastructure Layer, and High-Performance Data Centers
|
|
|
- Clement Powell
- 10 years ago
- Views:
Transcription
1 Layer Zero, the Infrastructure Layer, and
2 The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds between servers, switches, and other active devices are increasing from 1 Gb/s to 10 Gb/s, and up 40 Gb/s to 100 Gb/s in the not too distant future. To support these speeds, copper and fiber structured cabling has also evolved to keep pace. Higher interconnection speeds, virtualization, and other factors make the design of data centers and the cabling systems more complex all in an environment where downtime and errors remain unacceptable. Within today s data center, the role of structured cable management products the passive infrastructure of racks, cabinets, enclosures, patch panels, cable trays, and cable routing components as shown in Figure 1 is receiving more attention for their role in creating a flexible, reliable data center. While the ubiquitous 7-layer OSI model begins at Layer 1 with the physical layer of cabling, Legrand Ortronics has introduced the concept of Layer Zero to the OSI model to accommodate cable management and physical support infrastructure. Layer Zero encompasses the entire physical infrastructure that supports your network: not only racks and cabinets with advanced cable management, but underfloor and overhead systems, pathways, and more. The Layer Zero concept derives from the recognition that the physical infrastructure can play an important role in creating data centers that are more robust and manageable. Properly selected and deployed infrastructure products can Reduce power consumption and cooling costs Reduce the risk of equipment failure Improve overall system performance Provide an easier path for network equipment upgrades Drivers of Network Evolution Greater demand for data security. Higher data security is mandated both by business needs and by regulation. In the healthcare industry, for example, both HIPAA and Joint Commission programs require tight security to protect patient records. As a consequence, storage networks and devices are more complex. Greater demand on the data storage. Not only does data need to be stored for longer periods, 2 Figure 1. The passive infrastructure Layer Zero is a critical layer in achieving a high-performance, reliable network.
3 the need for real-time availability of enormous amounts of data is commonplace. Storage capacity grows rapidly, and tape drive farms are being replaced by storage area networks (SANs), which support high-speed access and data transfers. Media-rich and high-bandwidth applications. Serving up videos, social networking, on-line collaboration, and similar media-rich applications requires high bandwidth and flexible access to storage. Applications like and social networking, while typically not large for individual transactions, are sent in extremely high volumes. These all require availability of the network servers and storage, along with more demand on the service providers in the residential space to provide faster connection speeds. Converged networks. The days of deploying separate networks for data, voice, building automation, or building security are long past. A single IP-based network allows convergence of voice, video, data, and automation onto a single network. The vision of an IP-centric network allows a single network to handle a wide range of applications. Virtualization. The consolidation of multiple operating systems and applications onto virtualized servers places great demand on the input/output I/O for faster speeds. Virtualized servers are migrating to 10 Gb/s I/O to ensure each virtual server has adequate bandwidth and access. Power Over Ethernet (PoE). POE delivers power to devices over the copper network data cables. The obvious advantage is to eliminate a separate power feed, which is especially useful for remotely situated devices such as wireless access points, security cameras, access controls, building automation devices, and even VoIP phones. PoE can be deployed as an end-point device, where the power is sourced from the port of network equipment, and as a midspan device, where power is injected at some point in the cabling system. The changing roles of the IT and facility managers. As the networks are converging, so are the roles. The IT manager s responsibilities extend Electricity, beyond Transformer/UPS just the network (10%) to concern over power and cooling management. The facility Air Movement manager (12%) is now tasked with using existing systems to support the demand on the facility itself. For a new build, it is critical that facility design and network design are considered together. The Role of Layer Zero in Supporting the Physical Layer The remainder of this paper looks at the role of Layer Zero in supporting the structured cabling system. The costs of a structured cabling system including Layer Zero and Layer 1 is a small part Cooling of the (25%) overall cost of the data center, Lighting typically (7%) 5% or less (Figure 2). Considering the modest costs of the cabling system versus the enormous costs of downtime because of cable failure or mismanagement, little is to be gained by shaving costs or not applying the system according to best practices. IT Equipment (46%) Raised Floor (2.1%) Security (1.7%) Fire Protection (4%) Commissioning (1%) Data Cabling (4.6%) Electrical (42.4%) Mechanical (21.2%) Figure 2. Typical data center cost breakdown General Construction (10%) Contractor (5%) Engineering/Design (8%) Another consideration in planning IT infrastructure support is the life of the network and its components. The design needs to address the short- and long-term goals of the network and the owner. A good rule of thumb when considering the life of the components is as follows: 3
4 Servers 3 to 5 years Network Equipment 5 to 7 years Physical Infrastructure 10+ The structured cabling could see up to three upgrades in equipment before being considered for replacement. It is critical to specify structured cabling to support not only today s applications but tomorrow s as well. It becomes a wiser investment to deploy Category 6a for copper cable and OM3 or OM4 multimode fiber with an eye toward tomorrow s needs. The additional cost will always be less than the cost of replacing and removing old cable because you specified only for today s needs. Electricity, Transformer/UPS (10%) IT Equipment (46%) Lighting (7%) Air Movement (12%) Cooling (25%) 4 7 Key Elements for an Effective Network Legrand Ortronics has identified seven key elements that are critical to the effectiveness of the network. Without the proper management and optimization of these elements networks lose effectiveness, bandwidth, speed and quality. Managing these elements with Layer Zero infrastructure solutions will help maximize your network s potential and performance. The seven key elements are: Airflow management Energy efficiency Network performance Flexibility Density Protection Scalability We ll look at each one individually. Airflow Management As shown in Figure 3, cooling the data center accounts for 25% of the total costs. The costs related to power consumption are a large part of the overall costs for the operation of a data center. The Layer Zero infrastructure can enhance airflow and cooling efficiency to help control power and cooling costs. Figure 3. Data center operating costs ANSI/TIA-942 recommends a hot aisle/cold aisle configuration for air flow management as shown in Figure 4. The key aspect of any air flow management design is to get the conditioned air to the switch intakes Raised Floor (2.1%) and manage the exhaust Security (1.7%) air so it does Fire not Protection re-circulate (4%) back into the Commissioning switch intake. (1%) In a typical configuration, cooling air comes from the underfloor plenum up into the room through perforated floor tiles. This cool air is drawn through the equipment, where it picks up the heat generated by equipment, and exits the rear of the rack into the hot aisle. This warm air is then directed openly or through ducts for recirculation through the CRAC units. Racks are positioned to face each other, intakes on the cold and exhausts on the hot aisle. It is important that the cold aisles remain cold and hot aisles hot: mixing air from the two should be avoided. Electrical (42.4%) Mechanical (21.2%) General Construction (10%) Data Cabling (4.6%) Contractor (5%) Engineering/Design (8%) Figure 4. Hot aisle/cold aisle cooling efficiency depends on managing the airflow
5 Cisco and other switch/server manufactures have developed side-to-side airflow within the chassis of some larger units. This arrangement is growing in popularity because it allows easier access to the switch components and aids in the changing out of equipment as needed. Legrand Ortronics has developed accessories for the Mighty Mo 10 racks and Mighty Mo cabinets to facilitate the setup of hot/cold aisle air handling. This is accomplished with a baffle that directs the cold conditioned air into the switch intake and directs the switch exhaust into the hot aisle for dissipation as shown conceptually in Figure 5. This design allows for proper air flow management for environments with side breathing equipment. Figure 6. Airflow management in a standard EIA rack without airflow baffles Figure 7 shows the same simulation, but this time an Ortronics Mighty Mo 10 rack with the air management baffles installed. Temperature gradients are more even since the baffles facilitate hot aisle/ cold aisle airflow management. Cool, conditioned air enters the switches and is exhausted into the hot aisle. The mixing of hot and cold air seen in the baffleless example is avoided. Figure 5. Baffles help maintain proper airflow from cold aisle to hot aisle in side vented equipment The importance of the baffles in enhancing cooling is demonstrated in Figures 10 and 11, which show thermal imaging data for setups with and without the baffles. Figure 6 illustrates the air flow management with no baffles installed. Here, exhaust from the switch on the right is directed into the intake of switch to its left and so on down the line. In other words, hot exhaust air is mixed with the cold air, raising the temperature of the intake of switches down the line. By the time the air reaches the last switch on the left, the intake air temperature can be as high as 100 F, which not only stresses the switch but also means the air conditioning system will work harder and consume more power. Figure 7. Airflow management in a rack with baffles The use of baffles allows the air conditioning s setpoint to be raised 15 from 50 F to 65 F while maintaining proper temperature levels in the active equipment. Sun Microsystems has calculated that every 1 F the cold-aisle temperature can be raised translates into a 4% reduction in energy costs. Thus, airflow management in this case study allowed a 60% reduction in costs related to the cooling of the switches. 5
6 6 Energy Efficiency As you have seen, passive airflow management can effectively lower the costs of cooling without requiring fans or other additional power-consuming sources. Additional airflow management is achievable with accessories to separate hot and cold aisle spaces, particularly in the space between racks and ceiling. For example, an air containment system (Figure 8) effectively partitions hot and cold aisles. Figure 8. Partitioning hot aisles and cold aisles from rack to ceiling increases cooling efficiency Careful cable routing in pathways can also improve cooling efficiency and lower costs. Using cable management systems is another way to improve airflow. The important thing is to avoid blocking airflow paths. Design the route based on other obstacles within that space and environment. Network cables must be a minimum of 2 inches from power cables. Route cables away from electrically noisy environments. Reducing the number of 90 degree bends within the same pathway will limit the stress on the cable during installation or changes. Network Performance The performance of the structured cabling has a direct effect on the network performance. Poor cabling performance either through underspecifying or through poor installation and management degrades network performance. Network errors, fragmented frames, and excessive retransmissions can degrade performance and, at worst, cause expensive downtime. The performance of the cabling is expected to perform to its TIA category rating for up to 25 years after installation. The support of the structured cabling is critical to maintain the performance levels and needs to be properly addressed in the design. Tight bends, kinking, and unsupported weight must be avoided to ensure that cable performance remains with specification. Even worse is the possibility of inadequately managed patch cords causing lateral stress on ports and damaging them over time. Replacing a damaged switch port is a costly and preventable event. To maintain network performance, pay attention to the details in routing and supporting the cabling system. For example, channel bend limiters protect the integrity of the cable by providing the proper bend radius as cables enter or exit the channel and prevent damage to the cable from sharp cabinet edges. Similarly, cable management spools effectively manage excess copper or fiber cable slack. They mount at rack unit intervals, providing flexibility and ensuring proper bend radius for cables. Flexibility Moves, adds, and changes (MACs) are a constant part of a network s administration. The cabling system should have the ability to support MACs at the rack and cabinet levels. Vertical and horizontal cable management must properly support both the horizontal cables into the patch panels and also the patchcord routing at the front of the panels. Modular cable management systems increase flexibility. The easier it is to adjust or add individual components, such as patch panels or server/switch mounting rails, the more flexible and scalable is the network. Scalability Related to flexibility is scalability the ability to accommodate growth and changes to equipment. The faster new equipment can be deployed and brought online, the greater the cost savings to the network manager. Sometimes the growth is simply a matter of duplicating existing setups; other times it involves
7 new configurations as the data center moves to higher density servers and other significant changes in topology and architecture. In either case, scalability can bring great benefits in easy deployment and minimal disruption to network operations. Modularity aids scalability. By ensuring different components can work together and often are interchangeable, modularity not only offers a mix-andmatch approach to providing the building blocks to support scalability. Density The triple combination of convergence, virtualization, and high-density servers means that racks need to accommodate both more equipment and more interconnections. A Mighty Mo rack, for example, can support up to 1340 Cat 6 network ports. It also allows up to 48 patchcords per vertical rack unit on each side to ensure availability of cabling without clutter or mess. Figure 9 shows a typical high-density installation. In designing for high-density configurations, look for racks and cabinets with generous cable-routing capabilities on each side. Deep management channels not only accommodate a larger number of cables, they make them easier to manage such as tracing an individual cable or adding new cables. Choosing the right rack and cable pathway components can save money in the long run. Design cable pathways to handle not only today s weight & density requirements, but also tomorrow s. A fully loaded enterprise-level switch can weigh 900+ pounds. While a two-post rack might be fine for patch panels, a four-post rack is the better choice for equipment. Figure 9. Effective cable management in high-density configuration must prevent stresses on equipment ports while still accommodating MACs Protection From physical security, such as preventing unauthorized access to servers, to protecting network performance by safeguarding the integrity of the cables, to monitoring current and temperature for power surges and heat spikes, Layer Zero solutions offer a comprehensive way to protect your network equipment. Each product complements each other, creating a unified system that provides complete protection from threats to your network. Conclusion The proper design of facilities is critical to support the life of the network, protect the investment, and to provide best in class service to the users. Legrand Ortronics offers facilities infrastructure support with well-designed Layer Zero solutions. Through the combined use of industry standards, best practices, and innovative products a Layer Zero solution will fully support the network demands not only today, but also tomorrow. 7
8 REV 12/10 CANADA 125 Eugene O Neill Drive 570 Applewood Crescent New London, CT Vaughan, Ontario L4K4B (sales) (fax)
Layer Zero. for the data center
Layer Zero for the data center Preparefor the Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,
Layer Zero. for the data center
Layer Zero for the data center PREPAREFOR THE Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,
DATA CENTER SOLUTIONS GUIDE
DATA CENTER SOLUTIONS GUIDE designed to be better. Power Cabinets Racks Pathways Aisle Containment Connectivity and Cabling RACKS AND CABINETS Legrand s cabinets and racks, designed for all your network
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
ADC-APC Integrated Cisco Data Center Solutions
Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the
DATA CENTER DESIGN BEST PRACTICES: EFFICIENCIES BEYOND POWER AND COOLING
ORTRONICS DATA CENTER DESIGN BEST PRACTICES: EFFICIENCIES BEYOND POWER AND COOLING Cindy Montstream, RCDD/NTS, EE, CPLP Director of elearning and Standards DATA COMMUNICATIONS Legrand, North America designed
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Energy-efficient & scalable data center infrastructure design
Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Unified Physical Infrastructure (UPI) Strategies for Data Center Networking
Unified Physical Infrastructure (UPI) Strategies for Data Center Networking Physical Infrastructure Considerations for Smart Data Center Consolidation www.panduit.com WP-08 February 2009 Introduction Improving
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
WHITE PAPER. Creating the Green Data Center. Simple Measures to Reduce Energy Consumption
WHITE PAPER Creating the Green Data Center Simple Measures to Reduce Energy Consumption Introduction Energy Awareness Driving Decisions in the DataCenter The continued thirst for energy is a recurring
The Three Principles of Data Center Infrastructure Design WHITE PAPER
The Three Principles of Data Center Infrastructure Design WHITE PAPER The Three Principles of Data Center Infrastructure Design Understand These Three Principles and You ll: Lower your total cost of ownership
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
SIEMON Data Center Solutions. www.siemon.com
SIEMON Data Center Solutions www.siemon.com DATA CENTER SOLUTIONS 8 Future Proof Performance 8 Space Saving Through Optimum Density 8 Robust Security and Regulatory Compliance 8 Asset Management 8 Downtime
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
Rack Hygiene. Data Center White Paper. Executive Summary
Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,
DATA CENTER RACK SYSTEMS: KEY CONSIDERATIONS IN TODAY S HIGH-DENSITY ENVIRONMENTS WHITEPAPER
DATA CENTER RACK SYSTEMS: KEY CONSIDERATIONS IN TODAY S HIGH-DENSITY ENVIRONMENTS WHITEPAPER EXECUTIVE SUMMARY Data center racks were once viewed as simple platforms in which to neatly stack equipment.
Data Center Cabling Design Trends
Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
TIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
Organizing and Managing Equipment Rooms
Organizing and Managing Equipment Rooms How you organize and maintain your equipment room can be just as important as maintaining the operating systems on the boxes themselves. Although many companies
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration Bill Charuk, SR Product Manager, Data Center Solutions Introduction With the advent of data centers in communication infrastructure, various
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect Introduction The primary
Smart Data Center Solutions
Smart Data Center Solutions New Data Center Challenges Require New Solutions Data Center Architecture. Inside and Out. Data centers are mission-critical facilities. A silo-based approach to designing,
Creating Order from Chaos in Data Centers and Server Rooms
Creating from in Data Centers and Server Rooms By Dennis Bouley White Paper #119 Executive Summary Data center professionals can rid themselves of messy racks, sub-standard under floor air distribution,
Physical Infrastructure Management PanView iq (PViQ ) System Hardware
Physical Infrastructure Management PanView iq (PViQ ) System Hardware Because we are concerned about access to our network, audit ability, and the capacity to detect unauthorized connectivity as it relates
Fiber in the Data Center
Fiber in the Data Center A NetClear White Paper Rudy Montgelas Senior Fiber Product Manager Ortronics/Legrand Lisa Huff Data Center Applications Engineer Berk-Tek, A Nexans Company March 2008 A New Generation
2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8
Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,
Data Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc.
Data Center Design Considerations Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc. Data Center Design: Overall Expectations Need: Prime vs. Redundant vs. Mirrored
Racks & Enclosures. Deliver. Design. Define. Three simple words that clearly describe how we approach a Data Center project.
Three simple words that clearly describe how we approach a Data Center project. Eclipse Racks & Enclosures DELIVERING THE RIGHT INFRASTRUCTURE FOR YOUR MISSION-CRITICAL NEEDS SERVER RACKS & NETWORKING
InstaPATCH ZERO Solution Guide
SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING
Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc [email protected]
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc [email protected] J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
Creating Order from Chaos in Data Centers and Server Rooms
Creating from in Data Centers and Server Rooms White Paper 119 Revision 1 by Dennis Bouley > Executive summary Data center professionals can rid themselves of messy racks, sub-standard under floor air
Chapter 1 Reading Organizer
Chapter 1 Reading Organizer After completion of this chapter, you should be able to: Describe convergence of data, voice and video in the context of switched networks Describe a switched network in a small
Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC
IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: [email protected] www.itisltd.com Introducing Computational
Cabcon. Data Centre Solutions. www.cabcon.co.uk. an acal group company UK +44 (0)1189 122980 IRE (00353) 1 629 2640
Data Centre Solutions www.cabcon.co.uk UK +44 (0)1189 122980 IRE (00353) 1 629 2640 About Us are a specialist distributor of copper, fibre, power, security, active and cable management products for the
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures
Great Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
Rittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
Arista and Leviton Technology in the Data Center
Visit: www.leviton.com/aristanetworks Arista and Leviton Technology in the Data Center Customer Support: 1-408-547-5502 1-866-476-0000 Product Inquiries: 1-408-547-5501 1-866-497-0000 General Inquiries:
Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers
C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use
DATA CENTER NETWORK INFRASTRUCTURE. Cable and Connectivity for the Most Demanding Networks. BerkTekLevitonTechnologies.com
DATA CENTER NETWORK INFRASTRUCTURE Cable and Connectivity for the Most Demanding Networks Customer-focused, technology-driven, quality-assured for an unparalleled RETURN ON infrastructure investment DATA
Intelligent Data Center Solutions
Intelligent Data Center Solutions Panduit s Unified Physical Infrastructure (UPI): a Guiding Vision A unified approach to physical and logical systems architecture is imperative for solutions to fully
Colocation and Cloud Hosting Solutions. Build a strong and efficient physical infrastructure that delivers service reliability and profitability
Colocation and Cloud Hosting Solutions Build a strong and efficient physical infrastructure that delivers service reliability and profitability 2 Dependability and Deployment Speed that Improves Your Bottom
Health Care Solutions
Health Care Solutions Increase Service Levels, Meet Expectations A Unified Approach to Health Care Automation Processes Hospitals, clinics, extended care facilities, and physician s offices are facing
SMARTPLAY7. Increase your Deal Size and Profitability with SmartPlays
SMARTPLAY7 Increase your Deal Size and Profitability with SmartPlays - Comstor and Panduit have joined forces to promote the power and flexibility of UCS combined with market leading energy efficient enclosures.
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER
ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect Introduction
Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
Cable management for rack-mounted systems
Cable management for rack-mounted systems technology brief, 2 nd edition Abstract... 2 Introduction... 2 Cable routing guidelines... 3 Separation of power and data cables... 3 Retention of excess cable...
Center Thermal Management Can Live Together
Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots
InstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3
Cisco Nexus 7000 Series.
Data Sheet Cisco Nexus 7000 Series Chassis Product Overview The Cisco Nexus 7000 Series Switches combine the highest levels of scalability with operational flexibility. The Cisco Nexus 7000 Series Switches
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Data Center Solutions
Data Center Solutions New Data Center Challenges Require New Solutions Data Center Architecture. Inside and Out. Data centers are mission-critical facilities. A silo-based approach to designing, deploying
in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center Doug Coleman, Manager, Technology & Standards, Corning Cable Systems Optical connectivity with OM3/OM4 laser-optimized
Data Center Network Evolution: Increase the Value of IT in Your Organization
White Paper Data Center Network Evolution: Increase the Value of IT in Your Organization What You Will Learn New operating demands and technology trends are changing the role of IT and introducing new
Thermal Optimisation in the Data Centre
Thermal Optimisation in the Data Centre Best Practices for achieving optimal cooling performance and significant energy savings in your data centre 1. Thermal analysis 2. Cold-Aisle-Containment 3. Seal
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures
Using a Fabric Extender with a Cisco Nexus 5000 Series Switch
CHAPTER Using a Fabric Extender with a Cisco Nexus 5000 Series Switch This chapter describes the Cisco Nexus 000 Series Fabric Extenders (FEXs) and includes these sections: Information About, page - Cisco
Strategies for Deploying Blade Servers in Existing Data Centers
Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling
Small Data / Telecommunications Room on Slab Floor
Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
Top of Rack: An Analysis of a Cabling Architecture in the Data Center
SYSTIMAX Solutions Top of Rack: An Analysis of a Cabling Architecture in the Data Center White paper Matthew Baldassano, Data Center Business Unit CommScope, Inc, June 2010 www.commscope.com Contents I.
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
How To Power And Cool A Data Center
Architecting the Green Data Center Viktor Hagen Field Business Development Data Center & High Performance Computing 1 Where we are Today Environmental sustainability is a major global trend for the 21st
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Data center lifecycle and energy efficiency
Data center lifecycle and energy efficiency White Paper Lifecycle management, thermal management, and simulation solutions enable data center energy modernization Introduction Data centers are coming under
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
Healthcare: Network and infrastructure solutions for an evolving industry. Healthcare Solutions
Healthcare: Network and infrastructure solutions for an evolving industry Healthcare Solutions The business of healthcare is evolving faster than ever. Are your network and data center infrastructure up
Mejora la Eficiencia Operativa en Centros de Datos
Mejora la Eficiencia Operativa en Centros de Datos Marco Antonio Damián Data Center Specialist Panduit Data Center Operational Efficiency Operational Efficiency is done through: Cabinets and racks Cable
EAGLE Power over Ethernet Products for IP Powering Applications. Flexibility, Simplicity and Value LAN POWER SYSTEMS. Trend Datacom USA, Inc.
EAGLE Power over Ethernet Products for IP Powering Applications Flexibility, Simplicity and Value LAN POWER SYSTEMS Trend Datacom USA, Inc. Presentation Agenda IEEE802.3af PoE Technology Definitions and
Using CFD for optimal thermal management and cooling design in data centers
www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,
Data Center Racks. Vantage S2. Enclosure System. Switch N to Eaton.
Data Center Racks Vantage S2 Enclosure System Switch N to Eaton. The Lean Data Center Data center managers are constantly moving, adding and changing IT equipment and electrical circuits all while trying
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
Re-examining the Suitability of the Raised Floor for Data Center Applications
Re-examining the Suitability of the Raised Floor for Data Center Applications By Neil Rasmussen White Paper #19 Revision 1 Executive Summary The circumstances that gave rise to the development and use
Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs
WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level
Cabinet V800 V800 CABINETS
V800 Cabinet Siemon s V800 cabinets provide a robust, cost-effective enclosure solution that provides valuable Zero-U space on each side of the equipment rails for cable management, PDU mounting or connectivity
Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth
Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth Integrated Cabinet Solutions For Business-Critical Continuity Why Proper Cable Management Is So Important Your rack
Living Infrastructure Solution Guide. www.commscope.com
Living Infrastructure Solution Guide Transform your data center into a living infrastructure One-size-fits-all practices and increased pressure affect data center performance In today s data center environment,