GOT-A900 Series Operating Manual
|
|
|
- Michael Mitchell
- 10 years ago
- Views:
Transcription
1 GOT-A9 Series Operating Manual (SW4D5C-GOTR-PACKE compatible Extended Option Functions Manual) MITSUBISHI Graphic Operation Terminal
2 SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. The instructions given in this manual are concerned with this product. For the safety instructions of the programmable controller system, please read the CPU module user's manual. In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".! DANGER Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.! CAUTION Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage. Note that the! CAUTION level may lead to a serious consequence according to the circumstances. Always follow the instructions of both levels because they are important to personal safety. Please save this manual to make it accessible when required and always forward it to the end user. [PRECAUTION WHEN PERFORMING THE TEST OPERATION]! CAUTION Read the manual carefully and fully understand the operation before the test operation (ON/OFF of bit devices, modifying current value of a word device, modifying timer/counter setting, modifying the current value, or modifying the current value of a buffer memory) of system monitor, special function module monitor, and ladder monitor. In addition, never modify data in a test operation to a device which performs a crucial operation to the system. It may cause an accident by a false output or malfunction. A -
3 Revisions *The manual number is given on the bottom left of the back cover. Print Date *Manual Number Revision Jan.,2 SH(NA)-869-A First edition May.,2 SH(NA)-869-B Partial additions Section.2, 4., 4.5 This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual. 2 MITSUBISHI ELECTRIC CORPORATION A - 2
4 INTRODUCTION Thank you for choosing the Mitsubishi Graphic Operation Terminal. Before using the equipment, please read this manual carefully to use the equipment to its optimum. Please forward a copy of this manual to the end user. Whereabouts and Usage of This Manual The manuals relating to SW4D5C-GOTR-PACKE are available in the following types. The manuals are classified according to their purposes. Please read the proper manuals to understand the handling, operation and functions of the GOT unit and SW4D5C-GOTR-PACKE. [ A985GOT Graphic Operation Terminal User s Manual(Hardware) ] To know the features of A985GOT unit. To confirm the specifications of A985GOT unit. To know the part names of A985GOT unit. To know how to install and wire A985GOT unit. To know the outline dimension drawing of A985GOT unit. A985GOT Graphic Operation Terminal User's Manual (Hardware) Found in the packing of the A985GOT unit. [ A975GOT-TBA/TBD(-B), A97GOT-TBA/TBD(-B), A97GOT-SBA/SBD, A97GOT-LBA/LBD, A96GOT- EBA/EBD User s Manual(Hardware) ] To know the features of A975GOT/A97GOT/A96GOT unit. To confirm the specifications of A975GOT/A97GOT/A96GOT unit. To know the part names of A975GOT/A97GOT/A96GOT unit. To know how to install and wire A975GOT/A97GOT/A96GOT unit. To know the outline dimension drawing of A975GOT/A97GOT/A96GOT unit. A975GOT-TBA/TBD(-B) A97GOT-TBA/TBD(-B) A97GOT-SBA/SBD A97GOT-LBA/LBD A96GOT-EBA/EBD user's Manual (Hardware) Found in the packing of the A975GOT/ A97GOT/A96GOT unit. [ A985GOT-TBA-EU, A975GOT-TBA-EU, A97GOT-TBA-EU, A97GOT-SBA-EU, A96GOT-EBA-EU User s Manual(Hardware) ] To know the features of the GOT-A9 series EMC directive Low voltage directive compliant unit. To confirm the specifications of the GOT-A9 series EMC directive Low voltage directive compliant unit. To know the part names of the GOT-A9 series EMC directive Low voltage directive compliant unit. To know how to install and wire the GOT-A9 series EMC directive Low voltage directive compliant unit. To know the outline dimension drawing of the GOT-A9 series EMC directive Low voltage directive compliant unit. A985GOT-TBA-EU A975GOT-TBA-EU A97GOT-TBA-EU A97GOT-SBA-EU A96GOT-EBA-EU User's Manual (Hardware) Found in the packing of the A985GOT-TBA-EU, A975GOT-TBA-EU, A97GOT-TBA-EU, A97GOT-SBA-EU, A96GOT-EBA-EU unit. A - 3
5 [ A95GOT-TBD/SBD/LBD (-M3), A95GOT-QTBD/QSBD/QLBD (-M3), A95GOT-TBD/SBD/LBD (-M3), A953GOT-TBD/SBD/LBD (-M3), A956GOT-TBD/SBD/LBD (-M3) User's Manual(Hardware) ] To know the features of A95GOT/A95GOT/A953GOT/A956GOT unit. To confirm the specifications of A95GOT/A95GOT/A953GOT/A956GOT unit. To know the part names of A95GOT/A95GOT/A953GOT/A956GOT unit. To know how to install and wire A95GOT/A95GOT/A953GOT/A956GOT unit. To know the outline dimension drawing of A95GOT/A95GOT/A953GOT/A956GOT unit. A95GOT-TBD/SBD/LBD(-M3) A95GOT-QTBD/QSBD/QLBD(-M3) A95GOT-TBD/SBD/LBD(-M3) A953GOT-TBD/SBD/LBD(-M3) A956GOT-TBD/SBD/LBD(-M3) User's Manual (Hardware) Found in the packing of the A95GOT/ A95GOT/A953GOT/ A956GOT unit. [ GOT-A9 Series Option Unit User's Manuals ] To know the features of the corresponding GOT-A9 series option unit. To confirm the specifications of the corresponding GOT-A9 series option unit. To know the part names of the corresponding GOT-A9 series option unit. To know the outline dimension drawing of the corresponding GOT-A9 series option unit. GOT-A9 Series Option Unit User's Manuals Found in the packing of the corresponding GOT-A9 series option unit. [ A985GOT/ A975GOT/ A97GOT/ A96GOT User s Manual ] To know the features of A985GOT/ A975GOT/ A97GOT/ A96GOT unit. To confirm the component devices of A985GOT/ A975GOT/ A97GOT/ A96GOT unit. To confirm the specifications of A985GOT/ A975GOT/ A97GOT/ A96GOT unit. To know the part names of A985GOT/ A975GOT/ A97GOT/ A96GOT unit. To fit various units to A985GOT/ A975GOT/ A97GOT/ A96GOT unit. To know how to install and wire A985GOT/ A975GOT/ A97GOT/ A96GOT unit. To know how to maintain and inspect A985GOT/ A975GOT/ A97GOT/ A96GOT unit. To confirm the error codes of A985GOT/ A975GOT/ A97GOT/ A96GOT unit. To know the outline dimension drawing of A985GOT/ A975GOT/ A97GOT/ A96GOT unit. A985GOT/A975GOT /A97GOT/A96GOT User's Manual Available as an option. [ A95GOT/ A95GOT/ A953GOT/ A956GOT User s Manual ] To know the features of A95GOT/ A95GOT/ 953GOT/ A956GOT unit. To confirm the component devices of A95GOT/ A95GOT/ 953GOT/ A956GOT unit. To confirm the specifications of A95GOT/ A95GOT/ 953GOT/ A956GOT unit. To know the part names of A95GOT/ A95GOT/ 953GOT/ A956GOT unit. To fit various units to A95GOT/ A95GOT/ 953GOT/ A956GOT unit. To know how to install and wire A95GOT/ A95GOT/ 953GOT/ A956GOT unit. To know how to maintain and inspect A95GOT/ A95GOT/ 953GOT/ A956GOT unit. To confirm the error codes of A95GOT/ A95GOT/ 953GOT/ A956GOT unit. To know the outline dimension drawing of A95GOT/ A95GOT/ 953GOT/ A956GOT unit. A95GOT/A95GOT /A953GOT/A956GOT User's Manual Available as an option. A - 4
6 [ GOT-A9 Series User s Manual(SW4D5C-GOTR-PACKE compatible Connection System Manual) ] To know the connection forms available for the GOT-A9 series. To confirm the specifications of each connection form. To know the system configuration of each connection form. To know how to set the unit used. To confirm the connection diagrams of the connection cables. SW4D5C-GOTR-PACKE Contained in the SW4D5C-GOTR-PACKE as PDF data. * The printed matter is also available as an option. [ SW4D5C-GOTR-PACKE(V) Operating Manual ] To install the software into the personal computer. To start each software. To know how to connect the personal computer and GOT. To know the screen makeup of the software. To grasp the outline of various monitoring functions. To know the procedure of displaying the monitor screen. To know how to use the help function. SW4D5C-GOTR-PACKE(v) Operating Manual Found in the packing of SW4D5C-GOTR-PACKE. * Contained also in the SW4D5C-GOTR- PACKE as PDF data. [ SW4D5C-GOTR-PACKE Help Functions] To confirm how to operate each software of SW4D5C-GOTR- PACKE. To confirm how to set various object functions. SW4D5C-GOTR-PACKE Incorporated in each software of SW4D5C-GOTR-PACKE [ GOT-A9 Series Operating Manual (SW4D5C-GOTR-PACKE compatible Extended Option Functions Manual ) ] To perform the utility function. To perform the system monitoring function. To perform the ladder monitoring function. To perform the special function unit monitoring function. To perform the network monitoring function. To perform the list editor function. SW4D5C-GOTR-PACKE Contained in the SW4D5C-GOTR-PACKE as PDF data. * The printed matter is also available as an option. [ GOT Operations Guide ] To learn the sequence of operations by creating a simple screen using the drawing software (the screen displays of the drawing software introduced in the GOT Operations Guide are partly different from those of SW4D5C-GOTR-PACKE). GOT Operations Guide Contained in the GOT Operations Guide. A - 5
7 Abbreviations, generic terms and special terms used in this manual Abbreviations, generic terms and special terms used in this manual are described as follows: Abbreviations, generic terms and special terms A985GOT A975GOT A97GOT A97*GOT A96GOT A956GOT A953GOT A95GOT A95GOT-Q A95GOT A95 handy GOT A95*GOT GOT Memory OS A9GT-QBUSS A9GT-QBUS2S A9GT-BUSS A9GT-BUS2S Bus connection board A9GT-RS4 A9GT-RS2 A9GT-RS2T Serial communication board Communication board A9GT-QBUS2SU A9GT-BUSSU A9GT-BUS2SU A7GT-BUSS A7GT-BUS2S Bus connection unit A7GT-J7AP23 A7GT-J7AR23 A7GT-J7AT23B Data link unit A7GT-J7LP23 A7GT-J7BR3 Network unit A8GT-J6BT3 A8GT-J6BT5 CC-Link communication unit Communication unit Protection sheet Backlight Debug stand PC card ( memory card ) Memory board Description Generic term of A985GOT-TBA, A985GOT-TBD and A985GOT-TBA-EU Generic term of A975GOT-TBA-B, A975GOT-TBD-B, A975GOT-TBA, A975GOT-TBD and A975GOT-TBA-EU Generic term of A97GOT-TBA-B A97GOT-TBD-B, A97GOT-TBA, A97GOT-TBD, A97GOT- SBA, A97GOT-SBD, A97GOT-LBA, A97GOT-LBD, A97GOT-TBA-EU and A97GOT-SBA-EU Generic term of A975GOT and A97GOT Generic term of A96GOT-EBA, A96GOT-EBD and A96GOT-EBA-EU Generic term of A956GOT-TBD, A956GOT-SBD, A956GOT-LBD, A956GOT-TBD-M3, A956GOT- SBD-M3 and A956GOT-LBD-M3 Generic term of A953GOT-TBD, A953GOT-SBD, A953GOT-LBD, A953GOT-TBD-M3, A953GOT- SBD-M3 and A953GOT-LBD-M3 Generic term of A95GOT-TBD, A95GOT-SBD, A95GOT-LBD, A95GOT-TBD-M3, A95GOT- SBD-M3 and A95GOT-LBD-M3 Generic term of A95GOT-QTBD, A95GOT-QSBD, A95GOT-QLBD, A95GOT-QTBD-M3, A95GOT- QSBD-M3 and A95GOT-QLBD-M3 Generic term of A95GOT-TBD, A95GOT-SBD, A95GOT-LBD, A95GOT-TBD-M3, A95GOT- SBD-M3 and A95GOT-LBD-M3 Generic term of A953GOT-SBD-M3-H and A953GOT-LBD-M3-H Generic term of A956GOT, A953GOT, A95GOT, A95GOT-Q, A95GOT and A95 handy GOT Generic term of A985GOT, A97*GOT, A96GOT and A95*GOT Abbreviation of memory (flash memory) in the GOT Abbreviation of GOT system software Abbreviation of A9GT-QBUSS type bus connection board Abbreviation of A9GT-QBUS2S type multi-drop bus connection board Abbreviation of A9GT-BUSS type bus connection board Abbreviation of A9GT-BUS2S type multi-drop bus connection board Generic term of A9GT-QBUSS, A9GT-QBUS2S, A9GT-BUSS and A9GT-BUS2S Abbreviation of A9GT-RS4 type serial communication board Abbreviation of A9GT-RS2 type serial communication board Abbreviation of A9GT-RS2T type serial communication board Generic term of A9GT-RS4, A9GT-RS2 and A9GT-RS2T Generic term of bus connection board and serial communication board Abbreviation of A9GT-QBUS2SU type multi-drop bus connection unit Abbreviation of A9GT-BUSSU type bus connection unit Abbreviation of A9GT-BUS2SU type multi-drop bus connection unit Abbreviation of A7GT-BUSS type bus connection unit Abbreviation of A7GT-BUS2S multi-drop bus connection unit Generic term of A9GT-QBUS2SU, A9GT-BUS2SU, A9GT-BUS2SU, A7GT-BUSS and A7GT-BUS2S Abbreviation of A7GT-J7AP23 type data link unit Abbreviation of A7GT-J7AR23 type data link unit Abbreviation of A7GT-J7AT23B type data link unit Generic term of A7GT-J7AP23, A7GT-J7AR23 and A7GT-J7AT23B Abbreviation of A7GT-J7LP23 type network unit Abbreviation of A7GT-J7BR3 type network unit Generic term of A7GT-J7LP23 and A7GT-J7BR3 Abbreviation of A8GT-J6B3 CC-Link communication unit Abbreviation of A8GT-J6B5 CC-Link communication unit Generic term of A8GT-J6BT3 and A8GT-J6BT5 Generic term of bus connection unit, data link unit, network unit and CC-Link communication unit Abbreviation of A9GT-8PSC, A9GT-7PSC, A9GT-6PSC and A9GT-5PSC type transparent protection sheets Abbreviation of A9GT-8LTT, A9GT-7LTTB, A9GT-7LTT, A9GT-7LTS and A9GT-5LT type backlights Abbreviation of A9GT-8STAND, A9GT-7STAND and A9GT-5STAND type debug stand Abbreviation of PC card with PCMCIA Ver.2. Abbreviation of A9GT-FNB, A9GT-FNBM, A9GT-FNB2M, A9GT-FNB4M, A9GT-FNB8M, A9GT- QFNB, A9GT-QFNB4M, A9GT-QFNB8M type option function memory board A - 6
8 Abbreviations, generic terms and special terms External I/O unit Printer interface unit Memory card interface unit Attachment QCPU (Q Mode) QCPU (A Mode) QCPU QnACPU (Large Type) QnACPU (Small Type) QnACPU AnUCPU AnACPU AnNCPU ACPU (Large Type) A2US(H)CPU AnS(H)CPU ASJ(H)CPU ACPU (Small Type) ACPU FX series FXN series FXS series FX series FXS series FX2 series FX2C series FX2N series FX2NC series FXCPU Motion controller CPU FA controller Omron PLC Yasukawa PLC Allen-Bradley PLC Sharp PLC Toshiba PLC SIEMENS PLC Other PLC SW4D5C-GOTR-PACKE Drawing software Data conversion software Debug software Object Windows95 Windows98 Windows NT4. Windows Acrobat Reader Personal Computer Description Abbreviation of A9GT-7KBF and A8GT-5KBF type external I/O interface unit Abbreviation of A9GT-5PRF type printer interface unit Abbreviation of ASD59J-MIF memory card interface unit Generic term of A77GT-96ATT/A85GT-95ATT/A87GT-96ATT/A87GT-97ATT attachments Generic term of Q2CPU, Q2HCPU, Q6HCPU, Q2HCPU and Q25HCPU CPU units Generic term of Q2CPU-A, Q2HCPU-A and Q6HCPU-A CPU units Generic term of QCPU (Q Mode) and QCPU (A Mode) Generic term of Q2ACPU, Q2ACPU-S, Q3ACPU, Q4ACPU and Q4ARCPU CPU units Generic term of Q2ASCPU, Q2ASCPU-S, Q2ASHCPU and Q2ASHCPU-S CPU units Generic term of QnACPU (Large Type) and QnACPU (Small Type) Generic term of A2UCPU, A2UCPU-S, A3UCPU and A4UCPU CPU units Generic term of A2ACPU, A2ACPU-S and A3ACPU CPU units Generic term of ANCPU, A2NCPU, A2NCPU-S and A3NCPU CPU units Generic term of AnUCPU, AnACPU and AnNCPU CPU units Generic term of A2USCPU, A2USCPU-S and A2USHCPU-S CPU units Generic term of ASCPU, ASHCPU, A2SCPU and A2SHCPU CPU units Generic term of ASJCPU-S3 and ASJHCPU CPU units Generic term of A2US(H)CPU, AnS(H)CPU and ASJ(H)CPU CPU units Generic term of ACPU (Large Type), ACPU (Small Type) and AFXCPU CPU units Generic term of FX series CPU unit Generic term of FXN series CPU unit Generic term of FXS series CPU unit Generic term of FX series CPU unit Generic term of FXS series CPU unit Generic term of FX2 series CPU unit Generic term of FX2C series CPU unit Generic term of FX2N series CPU unit Generic term of FX2NC series CPU unit Generic term of FX series, FXN series, FXS series, FX series, FXS series, FX2 series, FX2C series, FX2N series, FX2NC series CPU unit Generic term of A373UCPU, A373UCPU-S3, A273UCPU, A273UHCPU, A273UHCPU-S3, A7SCPU-S3, A7SHCPU, A72SHCPU CPU unit Generic term of LM6, LM76, LM8 CPU unit Generic term of C2HS, C2H, C2HX, C2HG, C2HE, CQM, CH,C2H,CV CPU unit Generic term of GL6S, GL6H, GL7H, GL2, GL3, CP-92SH, CP-93MS, MP-92, MP-93, CP-92(H) and PROGIC-8 CPU unit Generic term of SLC 5/3, SLC 5/4 CPU unit Generic term of JW-2CU, JW-22CU, JW-3CUH, JW-32CUH, JW-33CUH, JW-5CUH, JW-7CUH, JW-CUH CPU unit Generic term of T3, T3H CPU unit Generic term of SIMATIC S7-3 Series and SIMATIC S7-4 Series CPU unit Generic term of Omron PLC, Yasukawa PLC, Allen-Bradley PLC, Sharp PLC, Toshiba PLC and SIEMENS PLC CPU unit Generic term of SW4D5C-GOTR-PACKE software package and SW4D5C-GOTR-PACKEV software package Abbreviation of image creation software GOT Screen Designer for GOT9 Abbreviation of data conversion software GOT Converter for GOT9 Abbreviation of debugging software GOT Debugger Setting data for dynamic image Abbreviation of Microsoft Windows95 Abbreviation of Microsoft Windows98 Abbreviation of Microsoft Windows NT Workstation 4. Generic term of Windows95, Windows98 and Windows NT4. Abbreviation of Adobe Acrobat Reader3. 2 Windows compatible Personal Computer that can install SW4D5C-GOTR-PACKE * Microsoft Windows95, Microsoft Windows98 and Microsoft Windows NT Workstation 4. are the trademarks of Microsoft Corporation, U.S. *2 Adobe and Adobe Acrobat are the trademarks of Adobe Systems Incorporated. (C)998 Adobe Systems Incorporated. All right reserved. A - 7
9 Manual Related manual The following manuals related to this product are available. Obtain the manuals as required the according to this table. Manual name A985GOT/A975GOT/A97GOT/A96GOT User s Manual Explains the specifications, general system configuration, component devices, part names, option unit loading methods, installation and wiring methods, maintenance and inspection methods, and error codes of A985GOT/A975GOT/A97GOT/A96GOT unit. (Available as option) A95GOT/A95GOT/A953GOT/A956GOT User s Manual Explains the specifications, general system configuration, component devices, part names, option unit loading methods, installation and wiring methods, maintenance and inspection methods, and error codes of A95GOT/A95GOT/A953GOT/A956GOT unit. (Available as option) GOT-A9 Series User s Manual (SW4D5C-GOTR-PACKE compatible Connection System Manual) Gives the specifications, system configuration, setting method and connection diagram of each connection form available for the GOT-A9 series. (Available as option) GOT-A9 Series Operating Manual (SW4D5C-GOTR-PACKE compatible Extended Option Functions Manual) Provides the specifications of the utility, system monitoring, ladder monitoring, special function unit monitoring, network monitoring functions and list editor functions available for the GOT-A9 series and how to operate the dedicated monitor screen. (Available as option) SW4D5C-GOTR-PACKE(V) Operating Manual Deals with how to install and start the SW4D5C-GOTR-PACKE, its system configuration, the screen makeup of the software package, the general description of various monitoring functions, the procedure for displaying the monitor screen on the GOT, and how to use the help function. (Found in the packing of the SW4D5C-GOTR-PACKE) A9GT-QBUSS Type Bus Connection Board User's Manual Describes specifications, part names and installation of A9GT-QBUSS. (with A9GT-QBUSS) A9GT-QBUS2S Type Multi-Drop Bus Connection Board User's Manual Describes specifications, part names and installation of A9GT-QBUS2S. (with A9GT-QBUS2S) A9GT-QBUS2SU Type Multi-Drop Bus connection unit User's Manual Describes specifications, part names and installation of A9GT- QBUS2SU. (with A9GT- QBUS2SU) A9GT-BUSSU Type Bus connection unit User's Manual Describes specifications, part names and installation of A9GT-BUSSU. (with A9GT-BUSSU) A9GT-BUS2SU Type Multi-Drop Bus connection unit User's Manual Describes specifications, part names and installation of A9GT-BUS2SU. (with A9GT-BUS2SU) A9GT-BUSS Type Bus Connection Board User's Manual Describes specifications, part names and installation of A9GT-BUSS. (with A9GT-BUSS) A9GT-BUS2S Type Multi-Drop Bus Connection Board User's Manual Describes specifications, part names and installation of A9GT-BUS2S. (with A9GT-BUS2S) A7GT-BUSS Type bus connection unit User's Manual Describes specifications, part names and operation of A7GT-BUSS. (with A7GT-BUSS) Manual number (Model code) SH-45 (3JL7) SH-88 (3JL92) SH-87 (3JR SH-869 (3J979) IB-894 (3J978) IB-873 (3JQ75) IB-874 (3JQ76) IB-883 (3JQ83) IB-876 (3JQ78) IB-877 (3JQ79) IB (3JM87) IB (3JM88) IB-6676 (3JL7) A - 8
10 Manual name A7GT-BUS2S Type multi-drop bus connection unit User's Manual Describes specifications, part names and operation of A7GT-BUS2S. (with A7GT-BUS2S) A9GT-RS4 Type Serial Communication Board User's Manual Describes specifications, part names and installation of A9GT-RS4. (with A9GT-RS4) A9GT-RS2 Type Serial Communication Board User's Manual Describes specifications, part names and installation of A9GT-RS2. (with A9GT-RS2) A9GT-RS2T Type Serial Communication Board User's Manual Describes specifications, part names and installation of A9GT-RS2T. (with A9GT-RS2T) A7GT-J7AP23/R23 Type Data Link Unit User's Manual Describes specifications, part names and installation of A7GT-J7AP23/R23. (with A7GT-J7AP23/R23) A7GT-J7AT23B Type Data Link Unit User's Manual Describes specifications, part names and installation of A7GT-J7AT23B. (with A7GT-J7AT23B) A7GT-J7LP23/BR3 Type Network Unit User's Manual Describes specifications, part names and installation of A7GT-J7LP23/BR3. (with A7GT-J7LP23/BR3) A8GT-J6BT3 Type CC-Link Communication Unit User's Manual Describes specifications, part names and installation of A8GT-J6BT3. (with A8GT-J6BT3) A8GT-J6BT5 Type CC-Link Communication Unit User's Manual Describes specifications, part names and installation of A8GT-J6BT5. (with A8GT-J6BT5) A9GT-8LTT Type Back light Unit User's Manual Describes specifications, part names and installation of A9GT-8LTT. (with A9GT-8LTT) A9GT-7LTT Type Back light Unit User's Manual Describes specifications, part names and installation of A9GT-7LTT. (with A9GT-7LTT) A9GT-7LTS Type Back light Unit User's Manual Describes specifications, part names and installation of A9GT-7LTS. (with A9GT-7LTS) A9GT-7LTTB Type Back light Unit User's Manual Describes specifications, part names and installation of A9GT-7LTTB. (with A9GT-7LTTB) A9GT-5LT type backlight User's Manual Describes specifications and operation of A9GT-5LT. (with A9GT-5LT) A9GT-8STAND User's Manual Describes specifications, part names and installation of A9GT-8STAND. (with A9GT-8STAND) A9GT-7STAND User's Manual Describes specifications, part names and installation of A9GT-7STAND. (with A9GT-7STAND) A9GT-5STAND User's Manual Describes specifications and operation of A9GT-5STAND. (with A9GT-5STAND) Manual number (Model code) IB-6676 (3JL8) IB (3JM89) IB (3JM9) IB-822 (3JQ38) IB (3JE26) IB (3JA8 IB (3JE94) IB (3JL56) IB (3JL29) IB-827 (3JQ2 IB (3JM97) IB (3JM99) IB-833 (3JQ25) IB-82 (3JQ29) IB-828 (3JQ22) IB-6898 (3JM96) IB-82 (3JQ3) A - 9
11 Manual name Add-on memory board for A9GT-FNB, A9GT-FNBM, A9GT-FNB2M, A9GT-FNB4M and A9GT- FNB8M type option function Describes specifications, part names and installation of A9GT-FNB (M/2M/4M/8M). (with A9GT-FNB (M/2M/4M/8M)) Add-on memory board for A9GT-QFNB, A9GT-QFNB4M and A9GT-QFNB8M type option function Describes specifications, part names and installation of A9GT-QFNB (4M/8M). (with A9GT- QFNB (4M/8M)) A9GT-7KBF Type External I/O Interface Unit User's Manual Describes specifications, system configurations, part names and installation/wiring methods of A9GT-7KBF. (with A9GT-7KBF) A8GT-5KBF Type External I/O Interface Unit User's Manual Describes specifications, system configurations, part names and installation/wiring methods of A8GT-5KBF. (with A8GT-5KBF) A9GT-5PRF type printer interface unit user's manual Describes specifications, system configuration, part names, installation method and external dimensions of A9GT-5PRF. (with A9GT-5PRF) A8GT-TK Type Numerical Keypad Panel User's Manual Describes specifications, part names and installation of A8GT-TK. (with A8GT-TK) A9GT-QCNB Type bus connector conversion box User's Manual Describes specifications, part names and installation of A9GT-QCNB. (with A9GT-QCNB) A7GT-CNB Type bus connector conversion box User's Manual Describes specifications, part names and installation of A7GT-CNB. (with A7GT-CNB) Manual number (Model code) IB (3JM9 IB-85 (3JQ62) IB-88 (3JQ4) IB (3JL28) IB-89 (3JQ28) IB (3JL5 IB-882 (3JQ82) BCN-P538 A -
12 CONTENTS OVERVIEW... - to - 6. Before getting started with various functions Precautions before use Features Features of the utility function Features of the ladder monitor function Features of the system monitor function Features of the special module monitor function Features of the network monitor function Features of the List editor function BEFORE BEGINNING OPERATION to Required equipment SPECIFICATIONS to Ladder monitor function specifications PLC CPUs to be monitored Access ranges to be monitored System monitor function specifications PLC CPUs to be monitored Access ranges to be monitored Names of devices to be monitored Precautions when using the system monitor function Special module monitor function specifications Access ranges to be monitored Special function modules to be monitored Memory capacity required for using the special module monitor function Precautions when using the special module monitor function Network monitor function specifications Network information to be monitored Access ranges to be monitored Precautions when using the network monitor function List editor function specifications PLC CPU that allows for list edit Access range that allows for list edit Precautions for List editor function List of key arrangement and key functions Display format on the display List of List editor function A -
13 4 OPERATING THE UTILITY FUNCTION to Utility function table Selecting the utility function Selecting the required function on the utility menu screen (Adjusting the brightness/contrast of the monitor screen) Copying the monitor data/os data between the internal memory and memory card (Screen & OS copy) Setting the operating environment of the GOT (Setup) Running diagnostic checks on GOT hardware (self-test) Displaying GOT memory information (memory information) Setting the Clock (Clock) Displaying the display area cleanup screen (screen cleanup) Changing security levels (security password) Controlling limited access to the utility menu (password) Adjusting the brightness of the monitor screen on the dedicated screen (Brightness adjustment) OPERATION PROCEDURES FOR THE LADDER MONITOR FUNCTION to Operation procedures before starting ladder monitoring Operation procedures from display of user-created monitor screen to start of ladder monitoring OPERATING THE VARIOUS LADDER MONITOR SCREENS to Screen operation and screen changes when monitoring Reading data from the PLC Ladder read operation Using the defect search Changing from one screen to another Ladder monitor Ladder monitor screen display and key functions Precaution during ladder monitoring Switching the display form (decimal/hexadecimal) and turning the comment display on/off Changing the device value Printing ERROR DISPLAY AND HANDLING WITH LADDER MONITORING to OPERATION PROCEDURES FOR THE SYSTEM MONITOR FUNCTION to Operation procedures before starting system monitoring Operation procedures from user-created monitor screen display to start of system monitoring A - 2
14 9 OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS to Screen configuration, common operations and changing screens when monitoring Basic screen configuration and key functions (menu) Switching the display form (decimal/hexadecimal) and turning the comment display on/off (FORM) Specifying the monitor station and device (SET) Changing screens Entry monitor Basic operation Entry monitor screen display and key functions Deleting a registered device Batch monitor Basic operation Batch monitor screen display and key functions TC Monitor (monitor of timer and counter) Basic operation TC Monitor screen display and key functions BM Monitor (monitor of buffer memory) Basic operation BM Monitor screen display and key functions Test Basic operation Quick test function ERROR DISPLAY AND HANDLING WITH SYSTEM MONITORING... - to - 2 OPERATION PROCEDURES FOR SPECIAL MODULE MONITOR FUNCTION... - to - 2. Operation procedures before starting special module monitoring Operation procedures from user-created monitor screen display to start of special module monitor OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN to Screen configuration, common operation and changing screens when monitoring Composition of system configuration screen and key functions Monitor screen configuration and key functions Setting method for remote station monitoring Specifying monitor module and selecting monitor menu Test for special function module Changing the screen A6LS module monitor Operation monitor I/O monitor AD6 module monitor Operation monitor A - 3
15 2.4 ASD6 module monitor Operation monitor I/O monitor A62DA-S module monitor Operation monitor Graph monitor AS62DA module monitor Operation monitor A62LS module monitor Operation monitor I/O monitor AS62RD module monitor Operation monitor I/O monitor Graph monitor AS63DA module monitor Operation monitor Simple loop monitor I/O monitor AS64DA module monitor Operation monitor I/O monitor Graph monitor A68AD module monitor Operation monitor I/O monitor Graph monitor AS68AD module monitor Operation monitor I/O monitor Graph monitor A68ADN module monitor Operation monitor I/O monitor Graph monitor A68RD module monitor Operation monitor I/O monitor Graph monitor AS68DAI, AS68DAV module monitor Operation monitor I/O monitor Graph monitor A66AD module monitor Operation monitor Operation monitor (connect No. to connect No. 7 when multiplex module is used) I/O monitor A - 4
16 2.6.4 Graph monitor Graph monitor (connect No. to connect No. 7 when multiplex module is used) A66DAI, A66DAV module monitor Operation monitor I/O monitor Graph monitor A66TD module monitor Operation monitor (INPUT -F) Operation monitor (connect No. to connect No. 7 when multiplex module is used) I/O monitor Setting monitor (when A6MXT is used) Temperature monitor (connect No. to connect No. 7 when A6MXT is used) Graph monitor (INPUT -F) Graph monitor (connect No. to connect No.7 when multiplex module is used) AD7, ASD7 module monitor Positioning and parameter data monitor Zero return monitor I/O Monitor A7D module monitor Positioning monitor Zero return monitor Parameter data monitor I/O monitor AD7 Module monitor Positioning monitor Zero return monitor Parameter data monitor M code comment monitor I/O monitor Positioning data monitor AD72, ASD7 module monitor Positioning monitor Zero return monitor Parameter data monitor M code comment monitor I/O monitor Positioning data monitor AD75, ASD75 module monitor I/O monitor Operation monitor Basic parameter monitor Extended parameter monitor Zero return parameter monitor Monitoring the error history and warning history Monitoring the error termporary startup history and startup history A - 5
17 Monitoring Speed/Position Control Monitoring special startup, jogging, and manual pulser operation Monitoring an origin point return Monitoring axis control data Monitoring the output speed Monitoring the target values and machine values Monitoring external I/O signals and status signals (flags) Monitoring positioning information AJ7PT32-S3 and ASJ7PT32-S3 module monitor I/O monitor (I/O mode) Monitoring the link status Monitoring batch refreshing Monitoring separate refreshing Monitoring input and output (expansion mode) AJ7ID (ID2)-R4 and ASJ7ID (ID2)-R4 module monitor Action monitor (CH and CH 2) I/O monitor Monitoring set information A84AD module monitor Action monitor Setting monitor I/O monitor Monitoring graphs AS64TCTT(BW)-S and AS64TCRT(BW)-S module monitor Operation monitor Alert detail monitor Operation monitor (CH to CH4) OPERATING I/O MODULE MONITOR SCREENS to Specifying the module to be monitored Monitor screen configuration and key functions ERROR DISPLAY AND HANDLING WITH SPECIAL MODULE MONITORING to OPERATING THE NETWORK MONITOR FUNCTION to Steps in getting started with the network monitor function Steps in starting the network monitor function from the user-created monitor screen SWITCHING THE NETWORK MONITOR SCREENS to 6-2 A - 6
18 7 USING THE NETWORK MONITOR SCREENS to Own station monitor Display contents and keys functions: own station monitor Detailed own station monitor Display contents and keys functions: acting as a MELSECNET/B or MELSECNET (II) master station Display contents and keys functions: acting as a MELSECNET/B or MELSECNET (II) local station Display contents and keys functions: acting as a MELSECNET/ Control station/ordinary Station Display contents and keys functions: acting as a MELSECNET/ remote master station Other station monitor Display contents and keys functions: other station monitor menu Display contents and keys functions: other station communication status monitor Display contents and keys functions: other station data link status monitor Display contents and keys functions: other station parameter status monitor Display contents and keys functions: other station CPU action status monitor Display contents and keys functions: other station CPU RUN status monitor Display contents and keys functions: other station loop status monitor ERROR DISPLAYS AND COUNTERMEASURES WHEN MONITORING NETWORKS to OPERATION PROCEDURES FOR THE LIST EDITOR FUNCTION to Operation procedures before starting the list edit Operation procedures from user-created monitor screen display to starting list editing Operation of keyword input Selection and operation of mode A - 7
19 2 OPERATION OF EDITING SCREEN FOR EACH LIST to Basic operation of key input Switching of valid key (function indicated at the upper/lower part of the key) Command input procedures Action if an incorrect key is input Basic operation of list edit Reading sequence program Changing (overwriting) command Adding (inserting) command Deleting command Using Help function Operation procedure list of list edit Common operation Operation in Write mode (W) Operation in Read mode (R) Operation in Insert mode (I) Operation in Delete (D) mode Operation in Parameter mode (P) Operation in Other modes (O) ERROR DISPLAY AND CORRECTIVE ACTIONS FOR LIST EDIT to Error detected with the list editor function Error of PLC CPU Error using list editor function on the link system Index... Index - to Index - 3 A - 8
20 . OVERVIEW Chapter Overview This manual that can be used on a GOT with an operating system installed. These functions include the utility function, ladder monitor function, system monitor function, special module monitor function, network monitor function and list editor function.. Before getting started with various functions To use in this manual, such as the utility function, ladder monitor function, system monitor function, special module monitor function, and network monitor function, an operating system (OS) for each function must be installed first on your GOT by using drawing software. To install an OS for your desired function on your GOT, see SW4D5C-GOTR- PACKE(V) Operating Manual (Drawing Software Manual)..2 Precautions before use Precautions before using each function are described as follows: ( There are unavailable functions depending on the GOT. Please note that some functions require extension memory in the GOT unit. Memory is extended according to the following procedures. For A985GOT/A97*GOT/A96GOT : Memory board is installed in the GOT. For A95*GOT : A95*GOT-*BD-M3 (memory extension type) is used. Requirement for memory extension Not required Required Function category Function A985GOT A97*GOT A95*GOT A96GOT Basic function Utility function!! Extension function System monitor function!! Ladder monitor function! Special unit monitor function! Option function Network monitor function!! List editor function!!!: Applicable : Not applicable (2) Note that some functions are unavailable depending on the connection target CPU and connection form. There are the following restrictions on each function depending on the connection target CPU and connection form. Refer to Chapter 2 of the GOT-A9 Series User's Manual (SW4D5C-GOTR-PACKE compatible Connection System Manual) for the connectable CPU names and the access range for monitoring per connection form. POINTS ( Ladder monitoring is not available for sub-programs 2 and 3 of the A4UCPU (when connected to the computer link). (2) When the monitoring destination is QnACPU, Q4ARCPU, or Q2ASCPU, the CPU that can perform setup value changes to the timer/counter of the system monitor function and perform device comment displays, is that the CPU which ahs "977 B" and later in the date column of the rated plate. When changing the timer/counter setup value and performing the device comment display, use the CPU that is described above. (3) When the GOT is connected to an AnNCPU or AnACPU, the I/O No. to which a data link module or network module is installed cannot be displayed. (4) When the GOT is connected to an AnNCPU or AnACPU, a screen display shows a screen of the MELSECNET II network even when you are connected to the MELSECNET/ network (the monitor screen shows the display contents of the MELSECNET II). - <Viewing the Rated Plate> PROGRAMMBLE CONTROLLER DATE 977 B Date of manufacture Function version
21 . OVERVIEW Utility function Ladder monitor function System monitor function Brightness/ contrast adjustment Message display selection Screen & OS copy Setup Self-test Memory information Clock Screen cleanup Password Ladder monitor Display switching Device changing Print out Functions Adjusting the brightness/contrast of a monitor screen Selecting a message display. Copying the screen and OS data between the internal memory and memory card. Setting a use environment of the GOT Running diagnostic checks on GOT hardware Displaying GOT memory information. Setting the clock. Displaying the display area cleanup screen. Defining a password for limited access to the utility menu screen. Sequence program monitoring using ladder signals Decimal and hexadecimal display of word device values Device comment display Changing of device values Printing of ladder Entry Monitoring of current values by monitor pre-registering monitor devices Monitoring of n points of current Batch values subsequent to specified monitor device Monitoring of m points of current values, set values, contact points, T/C monitor and coils subsequent to specified device Monitoring of x points of current values subsequent to specified BM monitor buffer memory of specified special module (a) Connection with QCPU Ref. Section Section 4.3 Section 4.3 Section 4.4 Section 4.5 Section 4.6 Section 4.7 Section 4.8 Section 4.9 Section 4. Section 6.2. Section Section Section Section 9.2 Section 9.3 Section 9.4 Section 9.5 Bus connection CPU direct connection QCPU(Q Mode) Computer link connection MELSEC NET connection CC-Link connection CPU direct connection QCPU(A Mode) Computer link connection MELSEC NET connection CC-Link connection Setting/resetting of bit device 2 2 Data Changing of current value for buffer memory of word device editing using test operation Changing of current value for T/C (can be used while monitoring T/C) Changing of set value for T/C (can Section be used while monitoring T/C) Quick test Changing of device values using Section quick test Device comment display Display Section switching 9..2 Decimal and hexadecimal display of word device values and buffer memory values Special module monitor function Monitoring of buffer memory of special module on special screen Ch. 2 Network monitor function Monitoring of network status of MELSECNET/B, (II) or / Ch. 5 2 List editor function Sequence program in the ACPU is list edited. Ch. 9 * Subprograms 2 and 3 are not possible. *2 Can be monitored only when the A8GT-J6BT3 is used (in the intelligent device station). *3 When the A8GT-J6BT5 is used (in the remote device station), only the link devices assigned to the GOT can be monitored. *4 The T/C set values cannot be monitored if the software version of the A8GT-J6BT3 used is version W or earlier. *5 Can't change V or Z current values. *6 Cannot be monitored if the software version of the A8GT-J6BT3 used is version W or earlier. 2-2
22 . OVERVIEW Utility function Ladder monitor function System monitor function Brightness/ contrast adjustment Message display selection Screen & OS copy Setup Self-test Memory information Clock Screen cleanup Password Ladder monitor Display switching Device changing Print out Functions Adjusting the brightness/contrast of a monitor screen Selecting a message display. Copying the screen and OS data between the internal memory and memory card. Setting a use environment of the GOT Running diagnostic checks on GOT hardware Displaying GOT memory information. Setting the clock. Displaying the display area cleanup screen. Defining a password for limited access to the utility menu screen. Sequence program monitoring using ladder signals Decimal and hexadecimal display of word device values Device comment display Changing of device values Printing of ladder Entry Monitoring of current values by monitor pre-registering monitor devices Monitoring of n points of current Batch values subsequent to specified monitor device Monitoring of m points of current values, set values, contact points, T/C monitor and coils subsequent to specified device Monitoring of x points of current values subsequent to specified BM monitor buffer memory of specified special module Setting/resetting of bit device Changing of current value for buffer memory of word device Data editing using test operation Quick test Display switching Changing of current value for T/C (can be used while monitoring T/C) Changing of set value for T/C (can be used while monitoring T/C) Changing of device values using quick test (b) Connection with QnACPU or ACPU Ref. Section Section 4.3 Section 4.3 Section 4.4 Section 4.5 Section 4.6 Section 4.7 Section 4.8 Section 4.9 Section 4. Section 6.2. Section Section Section Section 9.2 Section 9.3 Section 9.4 Section 9.5 Section 9.6 Section Bus CPU direct connection connection QnACPU Computer link connection MELSEC NET connection CC-Link connection Bus CPU direct connection connection ACPU Computer link connection MELSEC NET connection CC-Link connection Device comment display 2 2 Decimal and hexadecimal display Section of word device values and buffer 9..2 memory values Special module monitor function Monitoring of buffer memory of special module on special screen Ch. 2 2 Network monitor function Monitoring of network status of MELSECNET/B, (II) or / Ch List editor function Sequence program in the ACPU is list edited. Ch. 9 * Subprograms 2 and 3 are not possible. *2 Can be monitored only when the A8GT-J6BT3 is used (in the intelligent device station). *3 When the A8GT-J6BT5 is used (in the remote device station), only the link devices assigned to the GOT can be monitored. *4 Can't monitor T/C set values. *5 Can't change V or Z current values. *6 If you modified the set value for T/C using the ladder monitor test function, you need to repeat the PC readout procedure to enable the display of the modification. 2-3
23 . OVERVIEW (c) Connection with FXCPU, third party PLC or microcomputer Utility function Ladder monitor function System monitor function Brightness/ contrast adjustment Message display selection Screen & OS copy Setup Self-test Memory information Clock Screen cleanup Password Ladder monitor Display switching Device changing Print out Functions Adjusting the brightness/contrast of a monitor screen Selecting a message display. Copying the screen and OS data between the internal memory and memory card. Setting a use environment of the GOT Running diagnostic checks on GOT hardware Displaying GOT memory information. Setting the clock. Displaying the display area cleanup screen. Defining a password for limited access to the utility menu screen. Sequence program monitoring using ladder signals Decimal and hexadecimal display of word device values Device comment display Changing of device values Printing of ladder Entry Monitoring of current values by monitor pre-registering monitor devices Monitoring of n points of current Batch values subsequent to specified monitor device Monitoring of m points of current values, set values, contact points, T/C monitor and coils subsequent to specified device Monitoring of x points of current values subsequent to specified buffer memory of specified special BM monitor module Data editing using test operation Quick test Display switching Setting/resetting of bit device Changing of current value for buffer memory of word device Changing of current value for T/C (can be used while monitoring T/C) Changing of set value for T/C (can be used while monitoring T/C) Changing of device values using quick test Device comment display Decimal and hexadecimal display of word device values and buffer memory values Ref. Section Section 4.3 Section 4.3 Section 4.4 Section 4.5 Section 4.6 Section 4.7 Section 4.8 Section 4.9 Section 4. Section 6.2. Section Section Section Section 9.2 Section 9.3 Section 9.4 Section 9.5 Section 9.6 Section Section 9..2 FXCPU Other PLC connection Microcomputer connection CPU direct connection Special module monitor function Monitoring of buffer memory of special module on special screen Ch. Network monitor function Monitoring of network status of MELSECNET/B, (II) or / Ch. 5 List editor function Sequence program in the ACPU is list edited. Ch. 9 * When connected to the PLC CPU without clock function (FX, FXN, FX, FX2NC, FXS), additional function cannot be set. Also, the clock function can be used with the FX2 and FX2N, when cassette for the realtime clock is used. *2 When connected to the PLC CPU without clock function, additional function cannot be set. *3 You can set the clock function only when you are using A9GT-RS2T, which includes a clock element. *4 T/C set values and coils cannot be monitored. - 4
24 . OVERVIEW (3) If a system program (OS) for the expanded or option functions has been installed, the following space is required in the GOT built-in internal memory to store usercreated monitor screen data. Hence, add the memory board as required. The installation of an operating system is required for the following expended or option functions: System monitor MELSEC-ACPU ladder monitor * MELSEC-FXCPU ladder monitor * MELSEC-QnACPU ladder monitor * * 2 Special unit monitor, recipe, sound Network monitor List editor* 2 ESC printer, bar code, report, external key input * 3 PCL printer, bar code, report, external key input * 3 ESC printer, bar code, report, proximity I/O * 3 PCL printer, bar code, report, proximity I/O * 3 * Any one of the 3 types can be installed. *2 The memory capacity is different from other OS. It is considered as the installation of 2 operating systems. *3 Any one of the 4 types can be installed. Number of Extended Memory Space Used functions OSs [k bytes] Free Space [k bytes] POINT If the special module monitor function is being used, enough memory space must be reserved in the internal memory to store the special module monitoring data (see Section 3.3.3). - 5
25 . OVERVIEW.3 Features The monitor functions described in this manual are intended to improve the efficiency of trouble-shooting and maintenance operations for the PLC system. The features of each monitor function are explained in the following sections..3. Features of the utility function The utility function enables you to use GOT setup and self-tests. To use the utility function, you need to install an operating system for the utility function on the GOT built-in internal memory by using drawing software. The features of the utility function are shown below. ( The brightness of a monitor screen can be adjusted (see Section 4.3 for details). (2) The screen and OS data can be copied between the internal memory and memory card (see Section 4.4 for details). The data monitored can be copied to and from the GOT built-in internal memory or a memory card installed on the GOT. The OS data can only be copied from the GOT to the memory card. - 6
26 . OVERVIEW (3) Setting a use environment of the GOT (see Section 4.5 for details). You can set the operating environment of the GOT such as the beep sound, message display language and screen saver's idle time. When using the A985GOT, you can also make settings on the Human sensor. (4) Running diagnostic checks on GOT hardware (see Section 4.6). You can run diagnostic checks on the GOT hardware, including the image check, font check, memory card check and so on. (5) Other functions (see Section 4.7 for details) Displaying data on available space in the GOT internal memory. Adjusting the clock of the PLC CPU. Displaying the display area cleanup screen. Changing security levels. Limiting access to the Utility Menu screen. - 7
27 . OVERVIEW.3.2 Features of the ladder monitor function Installing the ladder monitor function operating system into the GOT built-in memory using the drawing software enables ladder monitoring of the PLC CPU program as shown in a ladder diagram. The features of the ladder monitor function are shown below. ( Monitoring based on ladder symbols (see Section 6.2 for details) (Sample display) Ladder monitor screen P 87 M999 K = 234 D STEP : 2345/8374 K MOV D MOV K 2 D2 MOV MOV MOV RST K 9 K K V D62 D67 D72 D D2 2 V 47 D62 9 D67 DUTY D72 K 35 SET K 4 M928 M92 DATA OVERFLOWS ONE SCREEN Exit PLCRD. Mon. Menu List Print Screen Cancel Print REMARK The Print Screen and Cancel Print buttons are not displayed on the EL type screen. ( Ladder monitor screen A maximum of 8 lines (max. contact points per line; with 2 contact points or more, the line returns) of a sequence program are displayed on one screen. Also, for the current values and other settings of word devices, a maximum of 8 devices are displayed (With 9 devices or more, use the arrow keys to switch displays.). - 8
28 . OVERVIEW (2) The display format can be changed to show comments for devices (see Section for details). (Sample display) Ladder monitor screen M936 Normally ON Action X 4 Ready display T 7 25 X2 Start operation instruction STEP : 2345/8374 PLS M9 Character string display Y23 Operation ready K25 T Operation start warning Exit PCRD. Mon. Menu List Print Screen Cancel Print Switching the display format The current values monitor of the word devices at the bottom of the screen are executed in decimal or hexadecimal format. 2) Displaying device comments Comments of for the device used in the PLC program (comments that are written into the PLC CPU) are displayed. When comments are displayed, 3 lines of the program are shown. (3) Monitoring other stations Other stations in data link systems, network system or CC-Link system, including the GOT (or stations connected to the GOT), can be monitored. - 9
29 . OVERVIEW.3.3 Features of the system monitor function Installing the screen monitor function operating system into the GOT built-in memory using the drawing software enables monitoring and testing of the buffer memory for the PLC CPU program and the special functions module. The features of the system monitor function are shown below. ( Any desired device can be monitored, using 4 dedicated screens The system monitor function provides an entry monitor, a batch monitor, and a buffer memory monitor, enabling monitoring of any device, for complete flexibility in any application. Entry monitor Batch monitor DEVICE MONITOR TEST MENU FORM NETWK No. [ ] STATION[FF] SET BATCH MONITOR TEST MENU FORM NETWK No. [ ] STATION[FF] SET D DW D X M 25 Y 7 W 2 43 R DW D 3 3 Up to 8 points for a PLC CPU device registered by the user can be monitored in one window (see Section 9.2). T/C monitor TC MONITOR TEST MENU FORM SET NETWK No. [ ] STATION[FF] T PV SV [Production line A ] T PV SV [Production line B ] T 2 PV 5 SV 5 [Production line C ] T 3 PV SV [Production line D ] Up to 8 points, including the current value, set value, contact point, and coil can be monitored in a window subsequent to a PLC CPU timer (T)/counter (C) specified by the user (see Section 9.4). D D 8-5 D D D 2 D 2 D 3 - D 2 D 4 D 22 D 5 3 D D 6 D 24 D 7 D 25 Up to 6 points subsequent to a PLC CPU device specified by the user can be monitored in one window (see Section 9.3). Buffer memory monitor BM MONITOR TEST MENU FORM SET NETWK No. [ ] STATION[FF] I/O NO[ ] BM BM 8 BM 64 BM 9 BM 2 49 BM 2 5 BM 3 - BM 2 3 BM 4 26 BM BM 5 6 BM BM BM BM 7 2 BM 25 Up to 6 points subsequent to the buffer memory of a special function module specified by the user can be monitored in one window (see Section 9.5). With the GOT, the full screen can be divided into four windows and separate monitoring carried out in all four windows simultaneously. DEVICE MONITOR TEST MENU FORM SET BATCH MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] NETWK No.[ ] STATION[FF] D DW D X M 25 Y 7 W 2 43 R DW D 3 3 TC MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] SV T PV [Production line A ] PV SV T [Production line B ] 2 PV 5 SV 5 T [Production line C ] 3 PV SV T [Production line D ] D D 8-5 D D D 2 D 2 D 3 - D 2 D 4 D 22 D 5 3 D D 6 D 24 D 7 D 25 BM MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] I/O NO[ ] BM BM 8 BM 64 BM 9 BM 2 49 BM 2 5 BM 3 - BM 2 3 BM 4 26 BM BM 5 6 BM BM BM BM 7 2 BM 25 -
30 . OVERVIEW (2) Data can be changed by test operation (see Section 9.6 for details). (Test sample) When M is on When changing D present value NETWK No.[ ] STATION[FF] DEC DEVICE[ M] [ ] RST: SET:[] A C E B D F! AC DEL NETWK No.[ ] STATION[FF] DEC DEVICE[ D] [ ] VL[ K ] A C E B D F! AC DEL Test for bit device Device specified by user is turned on or off. 2) Test for word device Writes designated value into device specified by user. 3) Test for timer/counter Writes in designated value as current value or set values of device specified by user. 4) Test for buffer memory Writes designated value into buffer memory specified by user. (3) Display format can be changed and device comments can be displayed (see Section 9..2 for details). (Sample display) For entry monitor (comment display) For batch monitor (hexadecimal display) DEVICE MONITOR TEST MENU FORM SET NETWKNo.[ ] STATION[FF] D 2 3 [Line current units ] W 2 43 [Production line A ] R DW [link status ] X 3 [Input switch 3 ] BATCHMONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] D H 7FFF D 8 H FEC D H D 9 H CA2 D 2 H D 2 H D 3 H FFFF D 2 H D 4 H D 22 H D 5 H 3 D 23 H 8 D 6 H D 24 H D 7 H D 25 H Changing display format The word device values for the entry monitor, batch monitor, T/C monitor, and the buffer memory monitor are monitored in decimal or hexadecimal format. 2) Device comment display When the PLC CPU device is monitored, the comments written into the PLC CPU are displayed. (4) Other stations can be monitored. Other stations in data link systems, network systems or CC-Link systems, including the GOT (or stations connected to the GOT), can be monitored. -
31 . OVERVIEW.3.4 Features of the special module monitor function Installing (or downloading) the special module monitor function operating system and special module monitor data into the GOT built-in memory using the drawing software enables monitoring and changing of data in the special function module buffer memory, using dedicated screens. Signal statuses of I/O modules can also be monitored. The features of the special module monitor function are shown below. ( Monitoring can be done with dedicated screens (see Section 2.2 for details). Monitoring is carried out using dedicated screens provided by the manufacturer for the special function module and I/O module. It is not necessary for the user to create monitor screens. (Sample display : for special function module) Menu screen after module selection Monitor screen after menu selection A 6 8 R D Graph monitor screen Operation Monitor 2 I/O Monitor 3 Graph Monitor Menu selection * 3 * [ C] ****** ******** ******: :**JIS.DIN :**JIS ********* :*** :*** ********* :*** :*** ******/****** ****/**** :******************** :******************** CH******** CH5******** CH2 CH6 CH3 CH7 CH4 CH8 (Sample display 2: for I/O module) Monitor screen X MODULE X X A 4B 4C 4D 4E 4F " # # # "" # " # # # # # # # # A 5B 5C 5D 5E 5F # # # # # # # # # # # # # # # # A 6B 6C 6D 6E 6F " " " " " " # # # # # # # # # # A 7B 7C 7D 7E 7F # # # # # # # # # # # # # # # # Menu screen The menu is displayed classified into monitor items for the special function module only. The object monitor screen is displayed by selecting the item from the menu. 2) Monitor screen With the special function module, the buffer memory contents and the status of the PLC CPU I/O signals are monitored using text, numbers, and graphs. With the I/O module, the status of I/O signals to and from an external module is monitored. - 2
32 . OVERVIEW (2) Data can be changed by writing (see Section for details). (Writing example) Monitor screen When changing channel that can be changed A 6 8 R D Graph monitor screen AD7 Parameter Data Monitor Screen * 3 * [ C] ****** ******** ******: :**JIS.DIN :**JIS ********* :*** :*** ********* :*** :*** ******/****** ****/**** :******************** :******************** CH******** CH5******** CH2 CH6 CH3 CH7 CH4 CH8 Menu selection X Y Y Y Y2 X2 X3 X6 X7 Y3 Y4 XC XD Y7 Y9 YB YA Y5 Y6 X8 X9 X4 X5 RUSY XE XF X XA XB X Y ! DEL X ABCDDEFF Y ABCDDEFF A: :R :A B:M ON/OFF :NO :YES C:M :NO :YES DD: :ABS :INS :ABS+INS E: : : F: : : : :PLS The designated values are written into the user-specified buffer memory by writing the values from the monitor. 2) When changing the buffer memory data, input the numeric value using the auto display key window and write it into the buffer memory. (3) Special module monitor data can be allocated as user monitor screen data. The special module monitor data installed in the computer can be allocated to serve as user monitor screen data. To do this, the steps below are required. Using the Copy function, allocate special module monitor data from another project as user monitor screen data. 2) Correct the data to match the system used for the BM initial buffer memory number of the sprite function which has been set. - 3
33 . OVERVIEW.3.5 Features of the network monitor function To use the network monitor function, you first must install an operating system (OS) for the network monitor function on your GOT by using drawing software. This enables you to monitor the status of the MELSECNET/B, MELSECNET (II), and MELSECNET/ networks. The following describes the features of the network monitor function. ( Network monitor screens are selectable on the own station monitor screen to monitor the own station and other stations on a network. The own station monitor screen enables you to monitor the status of all the network lines connected to the own station. A touch of the screen will guide you through various monitor screens to monitor the status of the own station and other stations on a network. (2) Network information can be obtained from the own station monitor screen. Dedicated monitor screens are available for each category of station classification, depending on the role that is played by the own station. Network category: MELSECNET/B, MELSECNET (II) master station MELSECNET/B, MELSECNET (II) local station MELSECNET/ control station/ordinary station MELSECNET/ remote master station (Sample display) MELSECNET/B, MELSECNET (II) master station - 4
34 . OVERVIEW (3) The status of other stations can be monitored on the other-station monitor screen. The other-station monitor screen provides the following type of information on the status of other stations connected on a network: Communications status of each station Data link status of each station Parameters status of each station CPU action status of each station CPU RUN status of each station Loop status of each station (Sample display) Other station monitor menu screen Other station's communications status monitor screen - 5
35 . OVERVIEW.3.6 Features of the List editor function Installation of the List editor function OS into the memory with the drawing software allows for list edit of the sequence program in the ACPU. The following shows features of the List editor function. ( Easy parameters and sequence program maintenance Simple key operations allow checks, partial modifications, changes and additions of the parameters and the sequence program in the PLC CPU. Without peripheral equipment other than the GOT, the sequence program can be simply edited. Example of command change in the sequence program LD OUT LD X Y2 X Change LD MOV LD X D X D (2) Interlock with the ladder monitor function (only when A985/97*/96GOT is used) The list edit window can be started from the ladder monitor screen with a single touch. The list can be edited while viewing the ladder. The list can also be displayed from the step line displayed on the ladder monitor. P M = K 234 D STEP : 2345/8374 K MOV D K R 87 LD M MOVK D List 93 AND=K23 D EDITOR 98 MOVK D2 SHIFT READ INSERT WRITE DELETE PARAM OTHER HELP FROM A B B TO C D D INC E F F * G / H CALL I RET J DEC K MRD L MOV M D D2 V D62 D67 D S LD C > N - T AND D < O BCD U OR E P P BIN V MC F _ Q W W MCP W MPP R MPS X END Z Exit PLCRD. Mon. Menu List Print Screen Cansel Print LDI 8 ANI 9 ORI A MCR B SET ANB ORB PLS RST SFT CJ 2 OUT 3 Ý è ƒn ƒš ƒa SP ( ) «( ) GO (3) The list edit screen can be recorded. The hard copy function allows recording the edit screen of the list program. (4) Access to other station is available. The sequence program of the PLC CPU in other station can be list edited. (5) Useful help functions Help functions for read, write, insert and delete are available on the interactive menu selection system. Simple operation is facilitated. (6) Comment for each device can be displayed. Comment of the device at the cursor position can be displayed. W 9 OUT MOV M5 D Current value Comment of D is displayed. - 6
36 2. BEFORE BEGINNING OPERATION Chapter2 Before beginning operation The required equipment for using the monitor functions in this manual are described in this section. 2. Required equipment 2 Required equipment GOT main unit (A95*GOT- *BD-M3) Memory board * PLC drawing software *2 Connecting cables *2 The chart below shows the equipment required for using the monitor functions.!: Required : Not required Application It is required to use the option function installed on the A95*GOT. It is required to use the option function installed on the A985/97*/96GOT. Required for installing the object monitor function OS into the GOT and downloading the special module monitor data. It is necessary to install the drawing software into the PLC. Required for connecting the above PLC and the GOT when installing the object monitor function OS into the GOT and downloading the special module monitor data. Utility Ladder monitor System monitor Special function module monitor!!!! Network monitor List editor!! * The table below shows the types of memory boards available for using the option functions. Name Model Contents Memory board for option functions A9GT-FNB A9GT-QFNB For option function (applicable for A/FX ladder monitor) For option function (applicable for QnA/A/FX ladder monitor) Expanded memory board for option functions A9GT-FNBM Option function (applicable for A/FX ladder monitor) + internal memory extension MB A9GT-FNB2M Option function (applicable for A/FX ladder monitor) + internal memory extension 2MB A9GT-FNB4M Option function (applicable for A/FX ladder monitor) + internal memory extension 4MB A9GT-FNB8M Option function (applicable for A/FX ladder monitor) + internal memory extension 8MB A9GT-QFNB4M Option function (applicable for QnA/A/FX ladder monitor) + internal memory extension 4MB A9GT-QFNB8M Option function (applicable for QnA/A/FX ladder monitor) + internal memory extension 8MB *2 For information about the PLC on which to install and use drawing software and the cable to be connected between the PLC and the GOT, see SW4D5C-GOTR- PACKE(V) Operating Manual. 2 -
37 2. BEFORE BEGINNING OPERATION MEMO 2-2
38 3. SPECIFICATIONS Chapter3 Specifications In this chapter, the specifications of the ladder monitor function, system monitor function, special module monitor function, and list editor function are discussed separately. 3. Ladder monitor function specifications 3 POINTS When the ladder monitor function is used on the A985/97*/96GOT, the memory board applicable for the PLC CPU at the monitoring destination. The ladder monitor function cannot be used on the A95*GOT. 3.. PLC CPUs to be monitored The PLC CPUs that allow ladder monitoring are the QCPU (A Mode), QnACPU, ACPU, FXCPU and motion controller CPU. For details, refer to Section.2 (2). POINT Ladder monitoring is not available for sub-programs 2 and 3 of A4UCPU (when connected to the computer link) Access ranges to be monitored For access range for the ladder monitor function, see GOT-A9 Series User s manual (SW4D5C-GOTR-PACKE compatible Connection system manual). POINT When the capacity of parameter, PLC program, TC setting value, comment and extension comment is 44 kbytes or more, the comment will not be properly displayed. The local device cannot be monitored on the QnACPU. 3 -
39 3. SPECIFICATIONS 3.2 System monitor function specifications 3.2. PLC CPUs to be monitored The PLC CPUs that allow system monitoring are the QCPU, QnACPU, ACPU, FXCPU and motion controller CPU. For details, refer to Section.2 (2) Access ranges to be monitored For access range for the system monitor function, see GOT-A9 Series User s manual (SW4D5C-GOTR-PACKE compatible Connection system manual) Names of devices to be monitored For the names of devices that can be monitored with the system monitor function, see GOT-A9 Series User s manual (SW4D5C-GOTR-PACKE compatible Connection system manual) Precautions when using the system monitor function The precautions to follow when using the system monitor function are shown below. ( Monitor and test of real number data Real number data cannot be monitored or tested. Monitoring of word devices that save real number data is all done by integer data (binary data). (2) Monitoring in 32-bit modules When monitoring word devices (such as T, C, D, W) in 32-bit (2-word) modules, monitor up to the point where 32 bits remain in the monitor processing. A location where 6 bits ( word) remain cannot be monitored. This situation occurs when an odd number has been specified as the initial number in the monitor device. (Example) When monitoring the A2NCPU data register in 32-bit modules beginning with an odd number (D, D3...) Monitor display module Nothing displayed 3-2
40 3. SPECIFICATIONS (3) The "Date" column of a Rated Plate shows the date manufactured and function version number. If it reads "977 B" or a later notation, timer/counter settings can be changed and device comments can be displayed when using any of the largescale QnACPUs or small-scale QnACPUs. When changing the timer/counter setup value and performing the device comment display, use the CPU that is described above. <Viewing the Rated Plate> PROGRAMMBLE CONTROLLER DATE 977 B Date of manufacture Function version 3-3
41 3. SPECIFICATIONS 3.3 Special module monitor function specifications POINTS The memory board is required to use the special unit monitor function on the A985/97*/96GOT. The special unit monitor function cannot be used on the A95*GOT Access ranges to be monitored ( When using bus connection/cpu direct connection/computer link connection! The special function modules on the bases of the connected station and other stations can be monitored. (2) When using MELSECNET(II) connection/melsecnet/b connection! The special function module on the base of the master station can be monitored. (Cannot be monitored when the master station is the QnACPU.)! The special function modules on the bases of local stations cannot be monitored. (3) When using MELSECNET/ connection! The special function modules on the bases of the control station and normal stations can be monitored. (Cannot be monitored when the stations are the QnACPU.) (4) When using CC-Link connection (remote device station)! The special function modules cannot be monitored. (5) When using CC-Link connection (intelligent device station)! The special function modules on the bases of the master and local stations can be monitored. (6) When using the system configuration where remote I/O stations exist! The special function modules cannot be monitored in any connection form Special function modules to be monitored The modules for which special function monitoring can be done are only those types shown in Section Monitoring of special function modules other than those can be done with the system monitor function "BM Monitor". 3-4
42 3. SPECIFICATIONS Memory capacity required for using the special module monitor function The memory capacity required when saving special module monitor data to the GOT built-in memory and the memory capacity required when saving to a Personal computer hard disk are shown below. (Unit: kilobytes) Software to be saved Memory capacity required when saving to GOT built-in memory Memory capacity required when saving to a personal computer hard disk Special module monitor data 3.4 A6LS 4.5 AD6 8.4 A62DA-S 6.9 A62LS 69.8 A68AD(S2) 9.97 A68ADN 5. A68RD3 A68RD4 7.8 A66AD 23 A66DAI A66DAV 33.5 A66TD 23 AD7 2.5 AD7D 29.3 AD7(S/S2/S7) 546 AD72 ASD7-S2(S7) 562 AD75P(P2/P3)* ASD75P(P2/P3)* 2 52 AJ7PT32-S AJ7ID(ID2)-R4 ASJ7ID(ID2)-R4 4.5 A84AD 2.2 ASD AS62DA 5.2 AS62RD 2.5 AS63ADA 6.4 AS64AD 2.3 AS68AD 9.75 AS68DAI AS68DAV 25.8 ASD7 2. ASJ7JPT32-S AS64TCTT/RT-S 45.7 Input module. Output module. * The AD75M(M2/M3) can be monitored within the monitoring range of the AD75P(P2/P3). *2 The ASD75M(M2/M3) can be monitored within the monitoring range of the ASD75P(P2/P3). Remarks By merely downloading either, both sides can be monitored. By merely downloading either, both sides can be monitored. 3-5
43 3. SPECIFICATIONS Precautions when using the special module monitor function The precautions to follow when using the special module monitor function are discussed below. ( Special function modules that cannot be monitored Modules displayed as "special" on the system configuration screen cannot be monitored using the special module monitor function. To monitor these modules, use the system monitor function "BM Monitor". (2) Display when connecting the small building-block type PLC CPU This precaution pertains to a situation where an expansion base unit for a large building block type of setup is connected to a small building-block type CPU (such as the ASCPU) in a station connected to the GOT. In such a case, the special function module on the large expansion base unit is displayed on the system configuration screen with the same model name as that of the small building-block type special function module. If there is no small building-block type special function module, "special" is displayed and the object module cannot be monitored. (Example) [Module Model] AD72 AJ7ID AJ7PT32-S3 AD75P A68AND A68RD [Model Name Displayed] ASD7 ASJ7ID ASJ7PT32-S3 ASD75P AS64AD AS62RD (3) Monitoring restricted special function modules (a) When monitoring the AD7 (S, S2, S7) When the slot on front of the AD7 module is an empty slot, monitoring is done in the following way. The AD7 is treated as the AD72, and "AD72" is displayed on the system configuration screen. In this case, when monitoring the AD7, select the AD72 in the object display position. 2) The monitor screen that is displayed by above is for the AD72. The number obtained by subtracting H from the I/O signal number on the display is the number to be used when installing the AD7 in the slot. If you do not want the AD to be treated as the AD72, execute "Shift the installation position of AD7 forward" or "In the I/O assignments, assign the empty slot in front of AD7 to the 6 X-Y points." (b) When monitoring the A68AD installed in the small building-block type PLC CPU With the GOT, the A68AD that is installed in the expansion base unit for the building-block type setup connected to the small building-block type CPU (such as the ASCPU) is recognized as the AS68AD and monitored as such. Since the buffer memory composition of the A68AD and the AS68AD is not the same, different data is displayed on the screen when monitoring the A68AD(displayed as the AS68AD). An A68AD that is installed in the base unit of the building-block type PLC CPU (such as the AnUCPU) can be monitored normally. 3-6
44 3. SPECIFICATIONS (c) When monitoring the ASD75M, AD75M The ASD75M/AD75M is displayed as ASD75P/AD75P. The ASD75M/AD75M can be monitored within the monitoring range of the ASD75P/AD75P. (d) When monitoring the A8CPU The A8CPU is monitored in the following way. Treatment of A8CPU System configuration screen 64 points in first half 64 points in last half Change to module that cannot be monitored. Change to input module. Display "Special X, Y " Display "Input 64 X " Possibility of monitoring Not possible Can be monitored as input. (e) When monitoring an I/O composite module With an I/O composite module for which "Output " is displayed on the system configuration screen, only the output signal can be monitored. For the input signal, monitor X of the PLC CPU device with the system monitor function. (4) Editing and allocating of special module monitor data Data displayed on a special module monitor screen cannot be edited by modifying or adding an object, except that the data can be used on a user-created monitor screen. (5) Precaution for I/O allocation setting (a) When the QnACPU is connected, the head XY numbers are displayed in due order on the special module monitoring system configuration screen if the I/O allocation setting is random as shown below. When performing special module monitoring, always perform the I/O allocation in order from slot Slot number QnA CPU Input 32 points Input 32 points Input 32 points AD75 special 32 points A68AD special 32 points Output 32 points Open Open Head XY number Set randomly GOT system configuration screen CPU Input 32 Input 32 Input 32 Special Special Input A Module name not displayed. (b) If the slot assigned to Output in I/O allocation is not fitted with a module, the GOT displays Input. (Common to ACPU and QnACPU) (6) The system configuration including remote I/O stations cannot be monitored. 3-7
45 3. SPECIFICATIONS 3.4 Network monitor function specifications 3.4. Network information to be monitored Function Own station monitor Detailed own station monitor Own station information Controlstation information Data link information Constant link scan POINTS The memory board is required to use the network monitor function on the A985 /97*/96GOT. The A95*GOT-*BD-M3 (memory extension type) is required to use the network monitor function on the A95*GOT. When the connection target is the QCPU (Q mode), the network monitor function cannot be used. The network status of the MELSECNET/H cannot be monitored. The following table shows the types of network information that can be monitored. Table 3. Network Information To be Monitored Network Information MELSECNET (II)/B Master Station 3-8 MELSECNET (II)/B Local Station MELSECNET / Control Station MELSECNET / Ordinary Station MELSECNET / Remote Master Station Network category display!!!!! Network No. display!!! Station No. display!!!!! Own station operation mode!!!!! Own station loop line status!!!!! Loop back execution status!!!!! Link scan time display!!!! Data link system loop status!!!! Own station communications status!* Own station's station No.!!!!! Own station!! Network No.!!! Group No.!! Specified control station!! Current control station!! Communications information!! Sub-control-station link!! Remote-I/O-master-station station No.!! Total of linked stations!!!!! Largest connected station!!! Largest data-linked station!!! Communications status!!!! Causes of interrupted communications!!! Causes of data link stoppage!!! Constant link scan!!! BWY receive BWY from the master station! BW receive BW from the master station in the higher loop! F-loop status!!!* 2!* 2!* 2 Loopback Own station status Other station monitor R-loop status!!!* 2!* 2!* 2 F-loopback station!!* 2!* 2!* 2 R-loopback station!!* 2!* 2!* 2 Loop switching frequency!!* 2!* 2!* 2 Parameter settings!! Designation of reserved stations!!! Communications mode!!! Designation of transmission!* 2!* 2!* 2 Transmission status!* 2!* 2!* 2 Communications status of each station!!!! Data link status of each station!!!! Parameter status of each station!!!! CPU action status of each station!!!! CPU RUN status of each station!!!! Loop status of each station!!* 2!* 2!* 2 * Accessible only when connected to a MELSECNET(II) local station. *2 Accessible only when connected to a MELSECNET/ optical fiber cable.!: Accessible : Not accessible
46 3. SPECIFICATIONS Access ranges to be monitored For access range for monitoring, see Chapter 2 of the GOT-A9 Series User s manual (SW4D5C-GOTR-PACKE compatible Connection system manual) Precautions when using the network monitor function The following describes precautions that should be followed when using the network monitor function. ( When the GOT is connected to an AnNCPU or AnACPU, a screen display shows a screen of the MELSECNET II network even when you are connected to the MELSECNET/ network (the monitor screen shows the display contents of the MELSECNET II). (2) There may be a possibility that the network monitor function cannot be used, depending on which CPU to connect and which connection method to use. CPU to Be Connected QCPU, QnACPU, ACPU, Motion controller cpu FXCPU Connection Method Bus connection Direct CPU connection MELSECNET connection * Computer link connection * 2 CC-Link connection Other manufacture s PLC CPU direct connection Own Station Monitor Network Monitor Function Detailed Own Station Monitor Other Station Monitor!!! * When connected to a QnACPU, control and master stations cannot be monitored. *2 When connected to an AnUCPU, monitoring cannot be done with the MELSECNET/ network card being installed. (3) When connected to a QnACPU, monitoring cannot be done with the keyword being defined. 3-9
47 3. SPECIFICATIONS 3.5 List editor function specifications POINTS To use the List editor function on the A985/97*/96GOT, the memory board is required. To use the List editor function on the A95*GOT, the A95*GOT-*BD-M3 (memory extension type) is required PLC CPU that allows for list edit PLC CPUs that allow list edit are either the QCPU(A mode) or the ACPU. For details, refer to section.2 (2) (a). POINT With the computer link connection, the above PLC CPUs do not allow use of the List editor function. In using the A2USH-S/A2SH-S/A2SH/ASH/ASJHCPU, the following restrictions should be observed in the range of list edit. In using the A2USHCPU-S : In the range of the A3UCPU In using the A2SH-S/A2SH/ASH/ASJHCPU : In the range of the A3NCPU Access range that allows for list edit For information about the access range that allows for list edit, see Chapter 2 of the GOT-A9 Series User's manual (SW4D5C-GOTR-PACKE compatible Connection system manual) Precautions for List editor function Precautions for the List editor function are as follows: ( Precaution for reading with the specified command The command cannot be specified to read the ladder. (2) Precaution for use with the ladder monitor function If list edit is performed while the ladder monitor function is started, the edit details are not shown on the ladder monitor screen. To show the edit details, the ladder monitor must be read from the PLC again. (3) Precaution for list edit While the corresponding PLC is at stop status, perform list edit. The list cannot be edited during PLC running. (4) Precaution for parameter changing on the other peripheral device If parameter settings are changed on the other peripheral device during use of the list edit function, they will be different from the settings of the internal parameters of the list edit function. For this reason, reset the GOT unit or make PC No. setting again to read the parameters. 3 -
48 3. SPECIFICATIONS List of key arrangement and key functions Key arrangement and key functions of the list edit window are shown below. When the A985/97*/96GOT is used When the A95*GOT is used Control key SHIFT READ WRITE INSERT DELETE List EDITOR PARAM OTHER HELP 2) Mode key (key for selection of mode) 3) Help key FROM A * G B B / H TO C CALL I D D RET J INC E DEC K F F SHIFT List EDITOR READ INSERT WRITE DELETE PARAM OTHER HELP MRD MOV > < L M N O SET GO P P FROM A * G MOV M + S B B / H > N - T TO C CALL I < O BCD U D D RET J P P BIN V INC E DEC K = Q W W F F MRD L MPP R MPS X 4) Command key (upper character) Device key (lower character) = Q LDI 8 RST MPP R ANI 9 + S ORI A SFT CJ 2 - T MCR B OUT 3 BCD U LD C SET 4 BIN V AND D W W OR E ANB ORB 5 6 MPS X MC F PLS 7 NOP Y CLEAR SP END Z ( ) ( ) LD C AND D OR E MC F NOP Y END Z LDI 8 SET 4 ANI 9 ORI A ANB ORB 5 6 MCR B PLS 7 SET ( ) CLEAR ( ) Control key RST SFT CJ 2 OUT 3 SP GO 5)Command key (upper character) Device number/constant set key (lower character) No. Name Key General description of function Control key SET SHIFT CLEAR Key that declares start of step number input or automatic scroll. Switch key that makes the lower character valid on each key with dual functions. Whether upper or lower character is valid can be checked on the display. Switch key that makes the upper character valid on each key with dual functions. Whether upper or lower character is valid can be checked on the display. If the Clear key is pressed when the system is not in the Parameter mode, Other mode or Help function, the screen returns to the initial status of the mode selection. (The input commands or device numbers except for the mode are cleared.) This is used for repeating the procedure if incorrect keys are pressed. In the Parameter mode, the process is cancelled. After restarting, continue the operation. In the Other mode, the screen returns to the previous display. When the Help function is used, the screen returns to the display at the input of the HELP key. SP Key that provides blank space at the command and at between device names. 2) Mode key ( ), ( ) Key that moves the cursor on the display (, ) or determines scroll directions.* READ WRITE GO to PARAM OTHER Press this key at the last of a series of key operations to execute the operation. Check the details of key operations on the display before pressing this key. Key that selects each mode of the List editor function. Switch the upper/lower character mode with the SHIFT key. 3) Help key HELP Key that selects the help function in the mode supporting the help function. 4) Command key Advice key FROM A to END Z 5) Command key Device No./Constant setting key RST to MC F Key that inputs K/H at the input of command, device name and constant input. Only when the valid key of upper/lower character needs to be switched, switching is allowed with input of the SHIFT and SET keys. Key that inputs the command, device number and constant. Only when the valid key of upper/lower character needs to be switched, switching is allowed with input of the SHIFT and SET keys. 3 -
49 3. SPECIFICATIONS * Movement of the cursor key between steps, between the menu items and in the input area is explained below. ( Keep pressing the cursor key to repeat the movement toward the specified key direction. (2) Movement between steps and between menu items To display the program immediately before/after the current step number command, Input either or key. : Program immediately before the command (no change after step) : Program immediately after the command (no change after the last step) R 2 3 L A D N D O U K T 2 3 X M 2 T 5 " " moves to the specified direction (upward/downward) with or key. (3) Movement in the input area To move the cursor between command names, between sources, and between destinations, input either ( ) or ( ) key. W 5 P K L N 4 7 M 5 D P M D Input area Display example for DWOVP K D " " moves to the specified direction (left/right) with ( ) or ( ) key. 3-2
50 3. SPECIFICATIONS In this operating manual, the List editor function key is represented in the following abbreviation form. ( Expression of Key Key 2... Key n means the sequential input from Key to Key n. (2) Expression of Key + time. Key 2 means input of Key and Key 2 at the same (3) As in RST key or MOV M key, keys with dual functions for input of the command or the device/constant or control keys that control the List editor function are represented as follows: (a) The mode command or only alphanumeric characters are described. Example RST RST or, MOV M MOV or M (b) Only commands are shown for explanation of command input. (Alphanumeric characters are omitted.) Only alphanumeric characters are shown for explanation of alphanumeric characters. (Command expressions are omitted.) Example To express MOV M key When input of command is explained... When input of alphanumeric characters is explained... MOV M 3-3
51 3. SPECIFICATIONS Display format on the display The following describes the position and content of each data field in the display area provided by the List editor function. Current mode display Valid key display Step number; device name and number Program list etc. The 4th line displays data (program name, device name, etc.) entered by the user. ( Mode and valid key display The following describes the mode and valid key display. The mode display shows the list editor function mode selected by the user. The valid key display shows which of the two functions assigned to each key is currently available: the function indicated at the upper part of the key or the function indicated at the lower part of the key. R Current mode display SHIFT FROM A READ WRITE INSERT DELETE PARAM OTHER HELP B TO D INC F B C D E F * / CALL RET DEC MRD G H I J K L MOV M > N < O P P = Q MPP R + _ BCD BIN W MPS S T U V W X LD AND OR MC NOP END C D E F Y Z Valid key display (This display is not always available.) With regard to keys framed in dotted lines in the figure shown at the left, the valid key display indicates which of the two functions assigned to each key is valid: Example: (Display) (Mode) R... Read mode W... Write mode I... Insert mode D... Delete mode P... Parameter mode O... Other mode : Function indicated at the upper part of each key is available. : Function indicated at the lower part of each key is available. FROM A key Function indicated at the upper part of the key is available.... FROM Function indicated at the lower part of the key is available.... A LDI ANI ORI MCR SET 8 9 A B ( ) SET ANB ORB PLS CLEAR ( ) RST SFT CJ OUT SP GO 2 3 POINTS To switch between two functions of keys (functions indicated at upper and lower parts of the keys), press the SHIFT and SET keys. For details, see Section
52 3. SPECIFICATIONS (2) Cursor display The GOT controls the display of the cursor when the user has to input data; it displays a " " at the cursor position. For more information, see Paragraph (6) below. If the cursor overlaps the display of a character, however, the character and " " alternate on the display. (3) Indication of the selected line When a program list is displayed, the line currently selected for editing is indicated by " " appearing immediately after the step number. The 3rd line in the display area is selected for editing. R 2 3 L A D N D O U K T 2 3 X M T 2 5 You can use the and keys to move " " up and down. (4) Step number display A step number is displayed as a decimal number. On the st and 2nd lines in the display area, significant digits in the lower four digits of a step number are displayed. On the 3rd and 4th lines in the display area, up to five significant digits in a step number are displayed. Mode Line to Line 4 R L D X M O V D D 2 Step number Displays significant digits in the lower four digits of a step number. Displays up to five significant digits in a step number. (5) Device display Two or more device specifications attached to a basic or application instruction are displayed using the same step number. For information on the step numbers, see Paragraph (4) above. (6) Display of data input from the keys Data input from the keys will appear at the cursor position. As more characters are input, the cursor moves to the right. The cursor appears as " ". Example: The user enters SET R 2 3 R L D O R O U T L D SET 2 L D O R O U T X M M M X M M 3-5
53 3. SPECIFICATIONS (7) Shifting of data to the left during the input of a program When the user inputs a program, the codes entered before a touch on the GO key will appear on the 4th (bottom) line of the display area. If the codes cannot appear on a single line, the display on the 4th line only will shift by a single character position to the left each time the user touches a key. (Each character that goes out of the display area by the left-shift operation is retained in the memory.) W 5 M L N D P P K X M D The user has entered "DMOVP K D". (8) Numerical display The following describes the display of numerical values in devices and of constants in a program input by the user. Note, however, that only some examples are shown. For details, see Chapter 2. Example: D 423H Display in decimal format Only significant digits are displayed with zero-suppression. M D ) Display in hexadecimal format Four digits are displayed without zero-suppression. M D H ) Display in octal format Six digits are displayed without zero-suppression. M D 4 6 4) ASCII format A numerical value in the specified device is read in byte units and converted into associated character codes. If a value fell outside the ranges 2H through 7FH and AH through DFH, dots ".." will appear. M D a s c i i B (9) Display of an error message An error message will appear on the 4th line of the display area. If an error message appears, perform corrective action as described in Chapter 2. An error message on the display is cleared when you press any key. Then the display resumes the state before the appearance of the error message. 3-6
54 3. SPECIFICATIONS List of List editor function Mode (mode display) Write (W) Read (R) Insert (I) Delete (D) Parameter (P) Function Write program Change device Display/ Instruction select Write help instruction Help Read step NOP continuous Comment display Read program Automatic scrolling Step Instruction Read Help Device Automatic scrolling Comment display Insert program Display/sel Instruction ect help instruction Read step Insert Help Move Copy Comment display Delete program Specified block Delete Help All NOPs Comment display Clear all parameters Set parameter Action Writes, adds, or modifies a program. Changes a device used at the selected step in the program Displays a list of instructions that start with the specified character and allows the user to choose from them. Reads a program after allowing the user to specify a step number. Declares the specified part of the program NOP. Displays a comment for the specified device. Reads a program after allowing the user to specify a step number. Reads a program after allowing the user to specify an instruction used. Reads a program after allowing the user to specify a device used. Automatically scrolls the display of a program that has been read up to a specified step. Corresponds to program read and automatic scroll functions described above. Displays a comment for the specified device. Inserts a new program into the displayed program. Displays a list of instructions that start with the specified character and allows the user to choose from them. Reads a program after allowing the user to specify a step number. Moves the selected part of the program to a specified part of the program. Copies the selected part of the program to a specified part of the program. Displays a comment for the specified device. Deletes a program at the specified step. Deletes the specified block in the program. Deletes all NOP instructions found in program codes described before the END instruction. (NOPLF instructions will not be deleted.) Displays a comment for the specified device. Clears all parameters in the ACPU only. Sets or changes various parameters like those for the memory capacity, timer/counter, and latching range. Sets or changes a keyword. 3-7
55 3. SPECIFICATIONS Mode (mode display) Others (O) Function Action Change T/C set values Changes values set to timer/counter devices. Displays details of an error in the ACPU and the associated step Read erroneous step PC number. check Checks duplex coils, instruction codes, and other elements in the Program check program. Monitor Buffer memory batch monitor With regard to a special function unit of the specified I/O number, monitors the contents of the buffer memory at the specified address. Clock monitor Monitors the ACPU clock (D925 through D927). Clears all contents of the ACPU memory and resets it to the initial Monitor PC memory state. All Program Clears the program (Main/Sub) currently selected. PC clear Device memory Clears all device memories except for special-d, special-m, and R. system PC No. setup Switches the target ACPU in GOT operations in each mode. Switch Switches the target program (Main/Sub) in GOT operations in each Switch Main/Sub mode. Remote RUN/STOP Forcibly changes the ACPU running status between RUN and STOP. Others Machine language Performs a read or write operation to the ACPU memory in the read/write machine language. 3-8
56 4. OPERATING THE UTILITY FUNCTION Chapter4 Operating the utility function 4. Utility function table Functions Description Remarks Ref. section Brightness/contr ast adjustment System monitor Special module monitor Screen & OS copy Setup Self-test Memory information Ladder monitor Adjusting the brightness/contrast of a monitor screen. Monitoring or changing devices in a PLC CPU. Monitoring or changing buffer memory of a special module. Copying of screen data between internal memory and memory card Copying of OS data between internal memory and memory card The options of settings include: Language used in a message display (Japanese/English) Buzzer sound adjustment Sounds from an external speaker Idle time for a screen saver Backlighting for a screen saver Protocol and baud rate when connected to a microcomputer Reverse display Extension number and slot number for bus connection with QCPU Transmission speed for Computer link connection Transmission speed for Yasukawa PLC connection Transmission speed and address for SIEMENS PLC connection Grip switch enable/disable setting (A95 handy GOT only) The self-test include diagnostic checks on GOT hardware as follows: Drawing check Font check Memory card check User-space-in-the-internal-memory check OS-space-in-the-internal-memory check CPU communications check Touch key check The contents of GOT memory information include: OS version number Status of communications with the PLC CPU Available space in the internal memory Availability of memory cards and available space in a memory card Availability of the ladder monitor function Monitoring the sequence programs on the PLC CPU. 4 - This function changes with the GOT used. Section 4.3 This function can be executed only after installing an OS on the GOT by using drawing software. This function can be executed only when the GOT memory is extended and the OS is installed from the drawing software to the GOT. Refer to the HELP function of SW4D5C-GOTR- PACKE to install the OS (from memory card to internal memory). Chapter 9 Chapter 2 Section 4.4 Section 4.5 Section 4.6 Section 4.7 This function can be executed only when the GOT memory is extended and the OS is installed from the drawing software to the GOT. Chapter 6 Clock Setting date and time. Section 4.8 Screen cleanup Displaying the display area cleanup screen. Section 4.9 This function can be executed only when the GOT Network Monitoring the line status of MELSECNET. memory is extended and the OS is installed from monitor the drawing software to the GOT. Chapter 7 Security password Password List edit Changing the security levels of numeric input and objects. Defining a password for limited access to the utility menu screen. List editing of PLC programs in PLC CPU If a security password is defined by using drawing software, security levels can be changed. Section 4. Section 4. This function can be executed only when the GOT memory is extended and the OS is installed from the drawing software to the GOT. Chapter 9 4
57 4. OPERATING THE UTILITY FUNCTION 4.2 Selecting the utility function This section describes how to select the utility function. The utility function can be activated with a touch of the screen. To select the utility function, follow either of the following two steps. ( Touch the upper right and left corners of the screen at the same time. Touch here simultaneously. (2) Touch a touch key displayed on the monitor screen. A touch key can be set in the touch key (expanded) function settings. The following flowchart outlines the steps involved in selecting the utility function. Touch after changing the setup data. Monitor screen Touch key input * Utility menu *2 (Contrast adjustment ) Selection PLC. MON. SP UNIT. *4 DATA COPY SETUP *3 SELF CHECK MEMORY INFO. LADDER MON. *4 TIME SET CLEAN * If you have set the password for the utility menu, the utility menu will appear after you enter the password. For the way of entering the password, refer to Section 4.. *2 How to adjust the brightness/contrast differs with the GOT used. For more information, refer to Section 4.3. *3 Changing any setting in Setup and touching resets the GOT and returns to the monitor screen. *4 Not available on the A95*GOT. Simultaneous touching Touch PASSWORD NET. MON. LIST EDITOR Brightness adjustment *2 4-2
58 4. OPERATING THE UTILITY FUNCTION 4.3 Selecting the required function on the utility menu screen (Adjusting the brightness/contrast of the monitor screen) ( Display screen The display screen differs with the GOT used. Screen Example A985/97*/96GOT A95*GOT (2) Function Menu screen used to select any of the utility functions. Used to adjust the brightness/contrast of the monitor screen. 4-3
59 4. OPERATING THE UTILITY FUNCTION (3) Operation (a) Basic operation Directly touch the portion where the function you will select is being displayed. (b) Return to the monitor screen Touch to return to the monitor screen. (c) Brightness/contrast adjustment Touch and at top of the screen to make contrast adjustment. You can adjust the contrast in about 2 steps. Touch at top right of the screen to show the brightness adjustmentdedicated screen. For details of the adjustment method on the dedicated screen, refer to section 4.2. POINTS If the OS is not installed on the GOT, items are displayed on the system monitor, but they cannot be selected. If the memory board is not installed in the GOT or the OS is not installed on the GOT, items are displayed on the special unit monitor, the ladder monitor and the network monitor of the A985/97*/96GOT, but they cannot be selected. If the compatible model (A95*GOT-*BD-M3) is not used or the OS is not installed on the GOT, items are displayed on the network monitor of the A95*GOT, but they cannot be selected. If the GOT is connected to the PLC CPU without clock function, items are displayed on the clock window, but they cannot be selected. (4) On-screen error messages Message Cause Corrective Action Can t be selected (When system monitor, special module monitor, ladder monitor,or clock setting is selected) The OS is not installed on the GOT. The memory board is not installed in the A985/97*/96GOT. The A95*GOT other than the compatible model (A95*GOT-*BD- M3) is used. The GOT is connected to a PLC CPU without a clock function. Install the OS. Install the memory board in the A985/97*/96GOT. Use the compatible model (A95*GOT-*BD-M3). Replace the CPU with one with a clock function or do not use the clock setting. 4-4
60 4. OPERATING THE UTILITY FUNCTION 4.4 Copying the monitor data/os data between the internal memory and memory card (Screen & OS copy) ( Display screen Sample screen (2) Features Project data stored in the internal memory can be saved to the memory card. Project data stored in the memory card can be saved to the internal memory. OS data can be backed up by copying them from the internal memory to the memory card. (3) Procedure (a) Basic operation Touch or to select options. Touching will display a message asking you to answer the question "Do you want to execute?" If you answers Yes to the question, touch again. Touch or to select another option. To quit the backup copy, touch to return to the Utility Menu screen. (b) To return to the Utility Menu screen: Touch to return to the Utility Menu screen. (4) On-screen error messages Message Cause Corrective Action Cancel write protect function Install memory card Format memory card Write Error (M-CARD capacity shortage) Data transfer error M-CARD error Data transfer error Memory card error The memory card is write-protected. A memory card is not installed on the GOT. The installed memory card is not yet formatted. Memory card loaded has memory space less than written data. Write error occurred in the memory card during copying, or the memory card used has no free space. The hardware of the installed memory card is defective. 4-5 Release write protection of the memory card. Install a memory card on the GOT. Format the memory card. Change the memory card for the one having enough memory space. Change the memory card, or increase the free space of the memory card. Replace the memory card with a new one.
61 4. OPERATING THE UTILITY FUNCTION (5) Directory tree in a memory card The directory tree in a memory card is shown as follows. (Directory Tree) \ ALARMHST. DAṪ... Alarm history data file RECIP. CSV to... Recipe data files RECIP256. CSV DList. ini... Downloaded information data file \OS... Folder for GOT OS program files \SYSTEM \UserData... Folder for on-screen data files \SpcData... Folder for special module monitor data files Backup copies of screen data files are saved to the UserData folder. To delete a file from the memory card by operating from the GOT, perform a memory card check, one of the options of the utility function. After the memory card check is complete, the memory card will be formatted. To delete a file from the memory card by operating from the personal computer, install a memory card on the GOT and use the Explorer to delete the file. Since an OS and data are controlled by the Dlist.ini file, create a memory card by using OS Install or OS Download of drawing software. When data is copied by using the Windows explorer on the personal computer side, the data cannot be recognized by the GOT. POINTS You cannot use this function to install the OS (from memory card to internal memory). For details of OS installation, refer to the Help function of SW4D5C- GOTR-PACKE. 4-6
62 4. OPERATING THE UTILITY FUNCTION 4.5 Setting the operating environment of the GOT (Setup) POINT After changing any of the items in Setup, touching GOT and shows the monitor screen. automatically resets the ( Display screen The display screen differs with the GOT used. GOT Used Screen Example A97*GOT/ A96GOT This screen example assumes that the communication driver "Computer" has been installed. A985GOT This screen example assumes that the communication driver "Bus (Q)" has been installed. A95*GOT This screen example assumes that the communication driver other than "Computer", "Bus(Q)", "AJ7QC24", "YASUKAWA GL/CP92(SH/H)", and "SIEMENS S-3/4" has been installed. The grip switch setting and grip switch cancel-time key OFF setting are available only for use of the A95 handy GOT. 4-7
63 4. OPERATING THE UTILITY FUNCTION (2) Functions Buzzer volume You can select the length of the beep sound.(factory-set to SHORT) Outside speaker sound You can select whether or not voice output is provided from the external speaker (only the voice specified for the touch input sound on the drawing software). (Factory-set to OFF) Screen save time Set the time until the monitor screen display is switched off by the screen saver function. When this setting is "", the monitor screen is always displayed.(factory-set to ) Screen save light When this setting is OFF, the backlight goes off as soon as the display is erased by the screen saver function. When this setting is ON, the display will disappear but the backlight will not go off. Reverse display The display mode (normal display (No)/highlighted display (Yes)) is selected. (Only A95*GOT-LBD (-M3) can be selected. Normal display is set at the time of shipment.) Language You can select the language (Japanese or English) of the messages to be displayed on the screen. (Factory-set to Japanese) QBUS extension number Set the GOT extension number for bus connection to the QCPU. (Factory set to extension 7) QBUS slot number Set the slot number where the GOT is assigned for bus connection to the QCPU. (Factory set to slot ) Microcomputer connection baud rate You can select the transmission speed when the GOT is connected to a microcomputer.(factory-set to 92) Microcomputer connection communication form You can select the protocol when the GOT is connected to a microcomputer. (Factory-set to FORM- QC24 Baud rate Set the transmission speed for connection with the QC24N. (Factory-set to 92bps) Baud rate Set the transmission speed for connection with the Yaskawa PLC or SIEMENS PLC. (Factory-set to 92bps) Adapter address Specify the MPI address on PROFIBUS assigned to the HMI adapter connected to the GOT for SIEMENS PLC connection. (Factory-set to Host (FF) address Specify the MPI address on PROFIBUS assigned to the PLC CPU to which the HMI adaptor is connected for SIEMENS PLC connection. The specified PLC CPU is the "host" when monitor device setting is made on the drawing software. For details of monitor device setting, refer to the help function of SW4D5C- GOTR-PACKE. (Factory-set to 2) 4-8
64 4. OPERATING THE UTILITY FUNCTION Screen save Human sensor You can select whether the screen saver is deactivated or not when the Human sensor has detected a man's motion. (Available for the A985GOT only, factory-set to Invalid) Human sensor detection sensitivity You can select the detection sensitivity of the Human sensor in any of steps, levels to, so that the sensor will not detect a motion such as a man passing before the GOT. (Available for the A985GOT only, factory-set to ) Detection sensitivity setting Monitor time [sec] Human sensor OFF delay The Human sensor can be turned off when it does not detect a man's motion after it has turned on. You can set that period between " min. sec." and "6 min. sec.".(available for the A985GOT only, factory-set to min. sec.) Grip switch You can set whether the grip switch will be used or not. When the setting is USE, hold down the grip switch and perform operation. Setup and self-diagnostic operations can be performed independently of the grip switch. (May be set only for the A95 handy GOT, factory-set to USE) If it is released You can set whether the touch key pressed on the GOT display will be turned off or not at the time of grip switch cancel. At the setting of "NO ACTION", the pressed touch key is turned off when it is released.(may be set only for the A95 handy GOT, factory-set to KEY OFF) POINT If the touch panel is not touched within the specified time, the screen saver function switches off the display to prevent "burn-in" of the display device. Especially for the display screen type of EL, it is recommended to use this function. Dedicated to the A985GOT, the Human sensor function automatically deactivates the screen saver, without any touch on the touch panel, by means of a signal detected by the Human sensor. Using the system information function of the GOT, the signal detected by the Human sensor may also be controlled by the PLC CPU. For full information on the system information function, refer to the SW4D5C-GOTR-PACKE HELP function. Signal detection timings are shown below. System signal 2 (Human sensor detection signal) Detection No detection Human sensor (operator motion) 5) Screen saver status Activation Deactivation 3) 2) 4) 6) Operator approached Operator moved away Motion that the Human sensor cannot detect (outside the range or too low moving speed) 2) Detection error of Human sensor (approx..5 sec) + delay due to Human sensor detection sensitivity 3) Human sensor OFF delay time + communication processing time 4) Time when screen saver is being deactivated 5) Human sensor OFF delay setting is required since the Human sensor outputs Detection and No detection alternately. 6) Human sensor OFF delay + screen save time 4-9
65 4. OPERATING THE UTILITY FUNCTION (3) Operation (a) Basic operation Touch or to select the necessary item. When the A985GOT, A95 handy GOT is used, select the last item on Page /2 and touch to show Page 2/2. For the setting item whose value will be changed, highlight the digit to be set by touching, and set the value by touching or. (If you are going to select another setting item after that, return the highlight to the setting item by touching, and make selection by touching or.) After setting, touch. After touching, the GOT is automatically reset and the monitor screen appears. (b) Return to each screen If no change has been made to the Setup settings, touching returns to the utility menu screen. If any change has been made to the Setup settings, touching resets and restarts the GOT. The display returns to the utility menu or monitor screen. 4 -
66 4. OPERATING THE UTILITY FUNCTION 4.6 Running diagnostic checks on GOT hardware (self-test) ( Display screen (2) Features Diagnostic checks on GOT hardware include the following options: Graphic Check... Allows you to perform visual inspection on screen display for discoloration and lack of display. Fontrom Check... Allows you to perform visual inspection for deformation in font size. Memcard Check... Allows you to make a check on the hardware of a memory card. After checking, a memory card are initialized. Userrom Check... Allows you to check for user space in the internal memory. After checking, user space is cleared to delete any data contained in the user space. OS Area Check... Allows you to check for OS space in the internal memory. Comm. Check... Allows you to check for GOT-to-PLC CPU communications. Touchsw Check... Allows you to check for touch keys. The GOT performs these checks. (3) Procedure (a) Basic operation Select the desired button to perform a diagnostic check. Select options as instructed on-screen. You will see a message indicating that the selected diagnostic check was successfully completed. If an error is detected, you will see a message indicating the occurrence of the error. The Image Check allows you to view the following elements: The entire screen is displayed in one color. Display colors are changed in the order of red-green-blue. 2) Basic figures are displayed, including circles and squares. 3) Ellipses and checkered patterns are tiled or cascaded on-screen. 4 -
67 4. OPERATING THE UTILITY FUNCTION 4.7 Displaying GOT memory information (memory information) ( Display screen Sample screen (2) Features The contents of GOT memory information include: OS version number Status of communications with the PLC CPU Available space in the internal memory Availability of memory cards and available space in a memory card Availability of the ladder monitor function (3) Procedure (a) Basic operation Touch to scroll screens. (b) To return to the Utility Menu screen Touch to return to the Utility Menu screen. 4-2
68 4. OPERATING THE UTILITY FUNCTION 4.8 Setting the Clock (Clock) ( Display screen Sample screen The time when the Clock Settings screen was displayed is shown in the window panel. The time indicator in the upper-right corner of the screen shows the current time. After correcting the date or time, check the clock for the current time. (2) Features The date, time, and a day of the week can be set to adjust the clock of the PLC CPU and the A9GT-RS2T. (3) Procedure (a) Basic operation Touch to select the desired option. Touch or to change numeric values. Touch + or - to to change the numerical values in increments of. Touch to set the clock of the PLC CPU. (b) To return to the Utility Menu screen Touch to return to the Utility Menu screen. POINTS Adjust the clock when you start up the system. The clock cannot be properly adjusted while reading or writing clock data by running sequence programs on the PLC CPU side (or when M928 is turned on by sequence programs in the case of the ACPU). This option is not selectable from the Utility Menu screen when connected to the PLC CPU that has no clock function. This option is not selectable when the A9GT-RS2 is used for microcomputer connection. 4-3
69 4. OPERATING THE UTILITY FUNCTION 4.9 Displaying the display area cleanup screen (screen cleanup) ( Display screen (2) Features A black screen is displayed when cleaning up the display area. This makes the screen easy to view. (3) Procedure (a) Basic operation Touch the upper right and left corners of the screen at the same time to return to the Utility Menu screen. Touch at the same time. 4-4
70 4. OPERATING THE UTILITY FUNCTION 4. Changing security levels (security password) ( Screen display (2) Features If objects (numeric input or touch keys, etc.) are secured by using drawing software, their security levels can be changed by entering a password. If the characters entered match a password, a message appears on-screen, telling that the security levels have been properly changed. Touching will return to the Utility Menu screen. If the characters entered do not match a password, an error message appears on-screen. Touching will return to the Utility Menu screen. Numerical numbers and alphabets [A] to [F] can be used for a password. Details about security levels, see SW4D5C-GOTR-PACKE(V) Operating Manual (Drawing Software Manual). (3) Procedure (a) To enter a password, follow these steps: Touch to 9 and A to F to enter a password. Touch to confirm the password entered. To correct the password entered, touch DEL to delete wrong characters and enter correct characters again. (b) To quit entering a password: Touch to return to the previous monitor screen. 4-5
71 4. OPERATING THE UTILITY FUNCTION 4. Controlling limited access to the utility menu (password) ( Screen display (2) Features Password protection can be set on the GOT by using drawing software. If access to the Utility Menu screen is password-protected, a screen asking you to enter a password is displayed when you touch the upper right and left corners of the screen or when you touch a touch key on the screen. A dialog box for defining a password is contained in the common settings menu of drawing software. If the characters entered match a password, the Utility Menu screen appears. If the characters entered do not match a password, an error message appears on-screen. Touching [EXIT] will return to the previous monitor screen. Numerical numbers and alphabets [A] to [F] can be used for a password. (3) Procedure (a) To enter a password, follow these steps: Touch to 9 and A to F to enter a password. Touch to confirm the password entered. To correct the password entered, touch DEL to delete wrong characters and then enter correct characters again. (b) To quit entering a password: Touch Exit to return to the previous monitor screen. 4-6
72 4. OPERATING THE UTILITY FUNCTION 4.2 Adjusting the brightness of the monitor screen on the dedicated screen (Brightness adjustment) ( Display screen Screen Example 4-7
73 4. OPERATING THE UTILITY FUNCTION (2) Function Used to adjust the brightness of the monitor screen. (3) Operation (a) Basic operation Touch any of to to select the brightness. Touch and at top of the screen to make contrast adjustment. You can adjust the contrast in about 2 steps. Touch Enter to store the settings into the GOT. (b) Return to the utility menu screen Touching returns to the utility menu screen. 4-8
74 5. OPERATION PROCEDURES FOR THE LADDER MONITOR FUNCTION Chapter5 Operation procedures for the ladder monitor function The operation procedures to follow when using the ladder monitor function are explained in the following section. 5. Operation procedures before starting ladder monitoring This section contains a summary of the procedures for transmitting the system program (OS) for the ladder monitor function from the personal computer to the GOT until it is installed in the built-in memory. For details, please refer to the Help in Drawing Software. Details of the screen display and key operation are shown in the Help. 5 Start Connect GOT to Personal computer. Start up GOT.!!! It is not necessary to set up and operate the GOT after startup. Start up Personal computer to start drawing software. With the drawing software, transmit the system program (OS) for the ladder monitor function from the Personal computer to the GOT and install it in the built-in memory.!!! Transmit the data using the installation dialog box. When installation is finished, the ladder monitor can be operated through the GOT.!!! When installation is finished, "Completed" is displayed on the installation dialog box. The drawing software operation is finished.!!! Proceed to Section 5.2 to operate the screen monitor. End 5 -
75 5. OPERATION PROCEDURES FOR THE LADDER MONITOR FUNCTION 5.2 Operation procedures from display of user-created monitor screen to start of ladder monitoring This section shows the operation procedures for the GOT when starting each operation of the ladder monitor function after the ladder monitor function system program (OS) has been installed in the GOT built-in memory. Start The memory board applicable for the PLC CPU at the monitoring destination is installed on the GOT. Start up GOT. Display the user-created monitor screen. Start the ladder monitor function.!!! ( When not reading the sequence program from the PLC CPU Display the PLC read screen.!!!! When reading the sequence program from the PLC CPU!!! See Sec. 6.. Specify the PLC CPU for the ladder monitor and the program to be read. The PC program is read. Display the ladder monitor screen. Touch PLCRD. Touch Menu Read the sequence program that is displayed on the ladder monitor screen.!!! When you touch Mon., the circuit monitor starts. See Sec. 6.2!!! See Sec * With the drawing software, touch the key where the touch switch (expanded) function is set, and start the circuit monitor function. When the Utility screen is displayed, start the circuit monitor function by touching LADDER MON.. 5-2
76 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS Chapter6 Operating the various ladder monitor screens The following sections describe each screen operation when using the ladder monitor function. 6. Screen operation and screen changes when monitoring This section includes an explanation of the PLC read operation that reads out the sequence program from the PLC CPU when executing the ladder monitor, the ladder read operation that specifies the sequence program to be displayed on the ladder monitor screen, and the screen movement when executing the ladder monitor Reading data from the PLC The operation of reading the sequence program for the ladder monitor from the PLC CPU is described below. The operation procedures vary depending on the PLC CPU to be monitored. All of the keys used with the operation are touch keys displayed on the screen. Touch the position where the object key is displayed and enter the data. [Operation procedure] ( When the MELSEC-A/FX ladder monitor is executed UTILITY MENU When the ladder monitor function starts up, execution begins from the specified operation with the network No. and Station of the object PLC CPU noted below. LADDER MON. (Touch) When the screen below is currently displayed, it is not necessary to touch this. Exit Ladder Break Menu Print Screen NET. No [ ] READ ST. ( ) ! Cancel Print To the following page A C E AC B D F DEL Specify the network No. and station No. for the object PLC CPU.(* (For data link system, CC-Link system) NET NO : READ ST. : FF (Own station) (Master station) to 64 (Local stations) (For network system) NET NO : (Host loop) (Master station) READ ST. : FF (Own station) to 64 (Control station) to 64 (Normal station) 6 -
77 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS From the previous page : Select input area. Alphanumeric: Input network No. and station No. (*2) (Touch: Input confirmation) READ STATE PARAM PROG CMNT EX.CMNT NETWORK NO. PLC NO.FF READ SELECTION READ PROGRAM COMMENT MAIN PROGRAM SETTING SUB PROGRAM 2 (A4U) NON SETTING SUB PROGRAM 3 (A4U) : SWITCH : SEL : SET Exit Ladder Break Menu : Setting item switch (Read program comment) : Select program (Read program) Select comment read enabled/disabled (Comment) 2) In "Read Selection", specify the sequence program to be read from the object station. Specify whether or not to perform comment read. (Touch) Keyword is not registered. Keyword is registered. Alphanumeric: Enter a keyword. (* 3) Input the keyword that is registered to that station. If no keyword has been registered, nothing has to be entered. (Touch) Sequence program is read. Reading is complete. 4) The contents and capacity of the read procedure are displayed. When you touch Break, the read procedure is interrupted. When reading resumes, it stars at the beginning. 5) "Completed" is displayed. To the following page 6-2
78 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS 2) READ STATE PARAM PROG CMNT EX.CMNT NETWORK NO. PLC NO.FF READ SELECTION READ PROGRAM COMMENT MAIN PROGRAM SETTING SUB PROGRAM 2 (A4U) NON SETTING SUB PROGRAM 3 (A4U) : SWITCH : SEL : SET Exit Ladder Break Menu Change screen. Exit : Moves to screen where ladder monitor function starts. Ladder : Moves to ladder monitor screen. PLCRD. : Moves to PLC read screen. * Data being entered can be cleared by the following keys. AC : Clears all data being entered to the object area. DEL : Clears one character at the cursor position. POINT Once this data has been read from the PLC, it does not need to be read again. If data for screens created by the user is downloaded from the computer after this data has been read, however, the data will have to be read again. 6-3
79 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS [Operation procedure] (2) When the MELSEC-QnA ladder monitor is executed Touch the ladder monitor starting touch switch on the monitor screen prepared by the user or touch the LADDER MON. on the utility screen to start the ladder monitor function. POINT If ROM_BIOS is not installed, an error message is displayed. Touch the END button and install the ROM_BIOS (H version or later). 2) The key window is displayed. Set the network No./station No. of the applicable PLC CPU with the following keys. : Select the input area. Alphanumeric : Input the network No. and the station No. AC : Clear all input data to the applicable area. DEL : Clear one character at the cursor position. : Define the input. POINT Designate the network No. and the station No. of the applicable PLC CPU. (For CC-Link system) Network No. : Station No. : (mask station) (For network system) Network No. : to 255 (self-loop) Station No. : to 64 (control station) to 64 (normal station) 3) The PLC read screen appears. First, touch the Set Up key to display the setting window. To the following page 6-4
80 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS From the previous page 4) The setting window appears. Make the setting for initial ladder monitor start. Touching the MEMORY key changes the setting choice as indicated below. DISPLAY USE OF EXISTING DATA, SELECT USE OR CLEAR. CLEAR EXISTING DATA. USE OF EXISTING DATA. After the setting is over, touch the button. 5) Then, touch the Drive key to select the drive (applicable memory) which stores the applicable ladder data to be monitored. To the following page 6-5
81 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS From the previous page 6) The Drive Selection Window is displayed. Select the drive (applicable memory) with the following keys. to 4 : Input the drive number. (internal RAM) - 4 (memory card) AC : Clear all input data on the drive. : Define the input. 7) The file list of the selected drive is displayed. Select the ladder to be read with the following keys. : Move the cursor upward. : Move the cursor downward. Page : Display the previous page. Page : Display the next page. SEL. : Move the cursor and touch the key to change select (*)/cancel. READ : Start reading the selected ladder. POINT When a keyword is registered at the PLC CPU, a key window is displayed at the start of reading. Input the keyword. (It does not have to be input if it is not registered.) 8) Contents and capacity of the reading process are displayed. Touch Break to stop the reading process. To read the ladder again, start from the beginning. 9) When the message "Completed" is displayed, reading is completed. Change the screen with the following keys. Exit : Move to the screen when the ladder monitor is started. Ladder : Move to the ladder monitor screen. Menu : Start from setting window (2) for the network No./station No. POINT Once PLC reading is performed, operations for PLC reading are not required from the next time onward. 6-6
82 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS 6..2 Ladder read operation [Operation procedure] This section describes the object sequence program of the ladder monitor that is read from the PLC CPU, for the operation displayed on the ladder monitor screen. T 7 25 Exit PLCRD. Mon. Menu List * When there is a at the upper left of the screen, touch it to return to the original screen. Print Screen Cancel Print MENU (Touch) When the screen below is currently displayed, it is not necessary to touch this. T Y23 2 Y25 K3 T Y25 X5 5 T 7 T 25 5 Dev.Sea. Step.Sea. 6/32Bit Exit PLCRD. Mon. Menu Cont.Sea. End.Sea. /6Dec.Hex. Print Screen Coil.Sea. Cancel Print Fact.Sea. Test Cmnt. The ladder read operation is executed. When specifying and reading the device, contact point or coil used in the program (*4) (Touch any of these.) Dev.Sea. Cont.Sea. Coil.Sea. (When entering device name) (When entering device No.) DEVICE [ D ][ ] DEVICE [ D ][ ] X Y M L S A B B F D W R C D A Z V T C 2 3 E F E G AC DEL! AC DEL : Select input area. Alphanumeric: Enter device name and device No. (* 6-7 (Touch: Input confirmation) Move to ladder monitor screen (*2)
83 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS When specifying and reading the step number in the program. Step.Sea. (Touch) [ ] STEP A B C D 2 3 E F! AC DEL to 9 : Input step No. (* (Touch: Input confirmation) Move to ladder monitor screen When specifying and reading the final ladder in the program. End.Sea. (Touch) Move to ladder monitor screen * Data being entered can be cleared by the following keys. AC : Clears all data being entered to the target area. DEL : Clears one character at the cursor position. *2 When specifying and reading a device, contact point or coil used in the program, the search targets all programs starting from the step number displayed on the previous ladder monitor screen, to the program immediately previous to the one displayed. After moving to the screen monitor screen, continuous reading by the same device is enabled by touching on the screen. If you touch any other key but, the continuous read function is canceled. 6-8
84 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS *3 When device search, contact point search, or coil search is performed during ladder monitoring, only the ladder block which includes the read search device is displayed. Example) When the device name to be searched is entered as "X" <Ladder monitor screen> STEP : 2345/8374 X X2 4 Y25 Displayed in the top area. Exit PLCRD. Mon. Menu List Print Screen Cancel print 2) When the same search is repeated <Ladder monitor screen> STEP : 2345/8374 X Y25 X2 4 X X2 7 Y3 Y4 Displayed on the next line. Exit PLCRD. Mon. Menu List Print Screen Cancel Print *4 Please note that the indirect specification device (index register (z)) cannot be specified and read while the MELSEC-QnA ladder monitor is executed. 6-9
85 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS 6..3 Using the defect search The defect search enables you to examine an ladder block that caused a failure. It helps you to search from the ladder block backward so that you can determine why any coil was turned ON or OFF during the ladder monitoring, or whether its contact is conductive or nonconductive. POINT While the MELSEC-QnA ladder monitor is performed, the factor search function cannot be used. (The touch key of Fact.Sea. is not displayed.) [Operation procedure] STEP 67/ 932 M2 M3 M3 42 Y X 46 MOVC23 D X X2 48 Y23 K25 T T K5 52 T M M2 X25 M2 57 Y3 ( Search for and display a ladder block where a failure occurred. Example: When a valve connected to Coil Y3 does not operate properly, begin searching for Coil Y3 and view its ladder block on the screen. * Exit PLCRD. Mon. Menu List Print Screen Mon. Menu Cancel Print (2) Touch Mon. to start the ladder monitoring. (3) Touch Menu and then select Fact.Sea. from among options that appear on-screen. If you touch Fact.Sea. without executing the ladder monitor function, a message appears on-screen, telling that "No MONITORING." 8 Y25 M2 2 Exit PLCRD. Mon. (Specify a device name) -< >- DEVICE [ ][ ] X Y M L S B F D W R A Z V T C E G AC DEL Menu Print Screen Dev.Sea. Cont.Sea. Coil.Sea. Cancel Print Fact.Sea. Step.Sea. End. Sea. Fact.Sea. -< >- DEVICE [ M ][ ] ! 6/32Bit /6Dec.Hex. Test Cmnt. (Specify a device number) A B C D E F AC DEL (4) Another dialog box where you can specify a device name or device number is displayed on-screen. Specify any contact of which coil is not turned ON as a search device. Example: Specify "M2" as the search device. : Used to select a data entry field. Alphanumeric : Used to enter a device name or device number. * : Used to stop the defect search, returning to the ladder monitor screen. * Use the following touch keys if you want to delete any data entry: AC : Clears all the data entered in a specific field. DEL : Clears one character at the cursor position. STEP : 63/ 932 M2 57 Y3 M M2 X25 (5) Start searching for a device that caused a failure and view search results on the ladder monitor screen. Search from the last step number backward as displayed on the ladder monitor screen. Please note that any touch keys other than Esc and Exit are enabled until the defect search is completed. 6 -
86 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS [Search results] Search results reveal any occurrences of the search device. They are useful when you determine whether a defective device is conductive or nonconductive. If any occurrence of the search device is not found as a result of the search, a message appears on-screen, telling that "PROGRAM NOT FOUND." M2 57 Y3 M M2 X25 Exit PLCRD. Mon. Menu Print Screen M2 57 Y3 M M2 X25 ( When an occurrence of the search device is found: If an occurrence of the search device is found as a result of the search, the search for another defective device will automatically be started. Example: After searching for Device M2 that is in the OFF state, "M669" will be displayed as a device that caused a failure. STEP : 63/ 932 After searching for Coil M2 that is in the OFF state, "M669" is displayed as a device that is not conductive. Example: M669L (This automatically begins searching for the defect that caused M669 to be turned OFF.) STEP : 63/ 932 M9 8 X23 M5 List Cancel Print * * After searching for a device that is in the ON state, a device that is conductive is displayed. The entire field of the device name and number is highlighted on-screen. Example: M669 After searching for Coil M669 that is in the OFF state, "M" is displayed as a device that is not conductive. Example: M * Exit PLCRD. Mon. Menu List Print Screen Cancel Print (This automatically begins searching for the defect that caused M to be turned OFF.) A search for another defect is repeated. 6 -
87 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS STEP : 63/ 932 M2 57 Y3 M M2 X25 (2) When two occurrences of the search device are found. If two occurrences of the search device are found as a result of the search, the search will be completed and a message appears, telling that "the defect search is interrupted." Example: After searching for Device M2 that is in the OFF state, "M669" and "X25" will be displayed as devices that caused a failure. After searching for Coil M2 that is in the OFF state, "M669" and "X25" are displayed as devices that are not conductive. Example: M669L, X25 the defect search is interrupted. Exit PLCRD. Mon. Menu Print Screen List Cancel Print * * After searching for a device that is in the ON state, devices that are conductive are displayed. The entire field of the device name and number is highlighted on-screen. Example: M669, X25 MENU * * To restart the defect search, touch Menu and then select Fact.Sea. from among options that appears on-screen. Select either of Contact M669 or X25 and start the defect search again. (3) To use the defect search, follow the instructions described below. (a) If a B-contact is found defective as a result of the defect search, a search for the cause of the ON/OFF state will be automatically switched. (b) The monitoring of device data will be restarted after the defect search is completed. (c) Whether an A/B contact is conductive or nonconductive may not match its screen display during and after the defect search. This is because the monitoring is continued during the defect search. (d) After the defect search is completed, touching or will allow you to search from the ladder backward in the search results display mode. Up to ladders can be displayed on-screen. The following messages will appear at the start or the end of the search results. When viewing the start of search results: "This is the start of search results." When viewing the end of the search results: "This is the end of search results." The ON/OFF display of contacts and coils on one screen is limited to contacts per coil per ladder. If there are several coils available, the ON/OFF display of coils appears on-screen only for the device searched. If the steps of search results are related to ladders or more, the ON/OFF display does not appear on-screen. (e) Menu is replaced with Esc upon starting the defect search. Touching Esc can exit the search results display mode. Touching Esc again will replace it with Menu. When returning to the ladder mode, the last step of search results is displayed in the top of the screen. (f) If on-screen data exceeds one screenful of data, it will be displayed across automatically scrolled screens. (g) Touching Esc can stop the defect search. Search results are continuously displayed on-screen until Esc is touched. The ON/OFF display of the lastsearched ladder does not appear on-screen. 6-2
88 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS 6..4 Changing from one screen to another This section describes the screen movements when executing the ladder monitor from the status where the user-created monitor screen is displayed. Start (* User-created monitor screen * Touch the key where the touch switch (expanded) function was set with the graphics software, and start the system monitor function. Touch (* When the Utility screen is displayed, touch LADDER MON. to start the system monitor function. Utility screen!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!! The system monitor function and special module monitor function can also be started from the Utility screen. Touch Exit Touch LADDER MON. Touch PLCRD. Ladder monitor screen (see Sec. 6.2) PLC read screen (see Sec. 6.. Touch Ladder Touch / End. Sea. Touch Menu Ladder read screen (see Sec 6..2) 6-3
89 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS 6.2 Ladder monitor The ladder monitor screen display and the keys that are shown at the top of the screen are explained in this section Ladder monitor screen display and key functions 2) 3) M936 Normalily ON Action X X2 4 Ready Start display operation instruction T 7 25 Exit PLCRD. The ladder monitor screen varies depending on the type of PLC CPU to be monitored. ( When MELSEC-A/FX ladder monitor is executed (a) Display Mon. Menu Print Screen List Cancel Print 4) STEP : 2345/8374 PLS M9 Character string display Y23 Operation ready K25 T Operation start warning When comment is not displayed When comment is displayed ON/OFF status display for ladder monitor ON status OFF status : maximum 8 lines : maximum 3 lines * The MCR command is normally displayed as. Sequence program is displayed. A maximum of contact points is displayed in one line of a ladder; for 2 contact points or more, move to the next line. When a comment display is specified, a comment is also displayed; expanded comments are given priority (For the method of displaying comments, see Sec ). A maximum of eight devices is displayed for the word device current value, timer and counter current value (upper row), and set value (lower row). When the set value is an 2) indirect specification, the value of the indirectly specified device is displayed. (To switch between decimal and hexadecimal for the displayed value, see Sec ). Display the keys used with the operation on the ladder monitor screen shown in (b) 3) (Touch input). 4) The display step number (left) and the remaining step number (right) are displayed. (b) Key functions This table shows the key functions used with the operations on the ladder monitor screen. Key Function Exit Return to screen where ladder monitor function starts. Move to PLC read screen to read sequence program being monitored from PLCRD. PLC CPU (PLC read). Move to ladder monitor menu screen, to specify sequence program to be Menu displayed on ladder monitor screen (Ladder read). Mon. Start monitoring of sequence program that is displayed on ladder monitor screen. Activates the List editor function. List (For details of the List editor function, see Chapter 9.) Switch display device when there are nine or more devices displaying current values and set values. Display one ladder; scroll up or down. When reading ladder with device specification, read next program with same device specification (see *2 in Sec ). POINT After executing PLC read, if the PLC CPU comment or comment capacity is changed, the comment may not be correctly displayed on the ladder monitor screen. When changing the comment or comment capacity, re-start the GOT. 6-4
90 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS 2) 3) M936 Normalily ON Action X X2 4 Ready Start display operation instruction T 7 25 Exit PLCRD. Mon. Menu Print Screen (2) When MELSEC-QnA ladder monitor is executed (a) Display Cancel Print 4) 5) 7) O-FF PLC RAM MAIN 24STEP JUMP JUMP 6) PLS M9 Character string display Y23 Operation ready K25 T Operation start warning When comment is not displayed When comment is displayed ON/OFF status display for ladder monitor ON status OFF status : maximum 8 lines : maximum 3 lines * The MCR command is normally displayed as. Sequence program is displayed. A maximum of contact points is displayed in one line of a ladder; for 2 contact points or more, move to the next line. When a comment display is specified, a comment is also displayed; expanded comments are given priority (For the method of displaying comments, see Sec ). A maximum of eight devices is displayed for the word device current value, timer and counter current value (upper row), and set value (lower row). When the set value is an 2) indirect specification, the value of the indirectly specified device is displayed. (To switch between decimal and hexadecimal for the displayed value, see Sec ). Display the keys used with the operation on the ladder monitor screen shown in (b) 3) (Touch input). 4) The network No. and the station No. are displayed. 5) The drive is displayed. 6) The file name of the PLC program is displayed. 7) The total number of steps in the current monitor PLC program is displayed. (b) Key functions This table shows the key functions used with the operations on the ladder monitor screen. Key Function Exit Return to screen where ladder monitor function starts. PLCRD. Move to PLC read screen to read sequence program being monitored from PLC CPU (PLC read). Menu Move to ladder monitor menu screen, to specify sequence program to be displayed on ladder monitor screen (Ladder read). Mon. Start monitoring of sequence program that is displayed on ladder monitor screen. Switch display device when there are nine or more devices displaying current values and set values. Display one ladder; scroll up or down. When reading ladder with device specification, read next program with same device specification (see *2 in Sec ). JUMP JUMP Scrolls the display up or down by ten ladders. POINT After executing PLC read, if the PLC CPU comment or comment capacity is changed, the comment may not be correctly displayed on the ladder monitor screen. When changing the comment or comment capacity, re-start the GOT. 6-5
91 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS Precaution during ladder monitoring ( When making connection to the FXCPU (a) The comment display is kana comments only. (b) During PLC read operation, the PLC read can only be performed for own station only. (c) STL (step ladder), the FXCPU exclusive instruction, is not a contact point, but treated as an instruction and displayed in the following manner: When monitoring with the peripheral device for FX S STL X X SET S2 SET S2 Y When ladder monitoring with GOT STL S X X SET S2 SET S2 Y (d) When searching for STL instruction, search for "S (state)" in the device search. (2) When making connection with the motion controller CPU (a) When the OS version is "SV5**" in the SVST instruction, "J**" appears as the tag name of MC. 6-6
92 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS Switching the display form (decimal/hexadecimal) and turning the comment display on/off You can switch the display form (decimal/hexadecimal) of the word device value or the timer/counter value that is displayed on the ladder monitor screen. You can also specify whether or not to display a comment for the object device. Switching the display form (decimal/hexadecimal) When monitoring, display the word device current value, the timer/counter current value (upper row) or the set value (lower row) in decimal or hexadecimal (When decimal is displayed, the display changes to hexadecimal.). 2) Switching the comment display on and off Display the comment that is written in the object PLC CPU (When no comment is displayed, this turns on the comment display). Comment display priority order: expanded comment > Japanese character comment or Japanese kana comment The display change operation is explained below. [Operation procedure] T 7 25 * When there is a at the upper left of the screen, touch it to return to the original screen. Exit PLCRD. Mon. Menu Print Screen List Cancel Print When the screen below is currently displayed, it is not necessary to touch this. MENU (Touch) T Y23 2 Y25 K3 T Y25 X5 5 T 7 T 25 5 Exit PLCRD. Mon. Menu Print Screen Dev.Sea. Cont.Sea. Coil.Sea. Cancel Print Step.Sea. End.Sea. Fact.Sea. 6/32Bit /6Dec.Hex. Test Cmnt. Touch the appropriate display position on the ladder monitor menu.!!!!!!!! After moving to the ladder monitor screen, the word device value is Mon. when you touch Mon. (Change display form.) /6 Dec.Hex. (Touch) (Change comment display.) Cmnt. (Touch) Move to circuit monitor screen. (When changing to hexadecimal display) (When changing to comment display) P M936 X X2 4 X 8 T M936 2 K 4 = D 4 T T STEP : 2345/8374 PLS PLS CALL M9 Y23 K25 T Y5 K5 T Y25 M2 P2 M936 Normalily ON Action X X2 4 Ready Start display operation instruction T 7 25 STEP : 2345/8374 PLS M9 Character string dispaly Y23 Operation ready K25 T Operation start warning Exit PLCRD. Mon. Menu List Exit PLCRD. Mon. Menu List Print Screen Cancel Print Print Screen Cancel Print 6-7
93 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS Changing the device value CAUTION Read the manual carefully and fully understand the operation before the test operation (ON/OFF of bit devices, modifying current value of a word device, modifying timer/counter setting, modifying the current value, or modifying the current value of a buffer memory) of ladder monitor. In addition, never modify data in a test operation to a device, which performs a crucial operation to the system. It may cause an accident by a false output or malfunction. Changing the device value on the screen during ladder monitoring is described. Switches for the timer/counter value display format (decimal/hexadecimal), and the comment display for the corresponding device (on/off) can be performed. ( Device value changing method The device value changing method during ladder monitoring is described below: <Circuit monitor Screen> Display the ladder monitor screen by touching LADDER MON.. Display the screen shown in 2) by touching Menu. 2) Display the test window by touching Test. Exit PLCRD. Mon. Menu Print Screen Dev.Sea. Step.Sea. 6/32BIT 2) Cont.Sea. List Coil.Sea. Cancel Print End.Sea. Fact.Sea. /6Dec.Hex Test Cmnt. [When using A97GOT-STN TFT] 3) As the test window will open, perform the operation by seeing Sec After the device change is complete, the changed contents can be verified in the ladder monitor. NETWK NO.[ ] STATION[FF] SET/RST VALUE6 BM VAL6 I ¹ PC Ç o ÓÆÀ Menu SET VAL VALUE32 BM VAL32 Print Screen List Cancel Print 3) [When using A96GOT-EL] NETWK NO.[ ] STATION[FF] SET/RST VALUE6 BM VAL6 SET VAL VALUE32 BM VAL32 I ¹ PC Ç o ÓÆÀ Menu 3) Print Screen List Cancel Print NOTE The current value display of the word device becomes hidden from view due to the test window. Using the key entries, the hidden current value display can be displayed by scrolling to the right/left. 6-8
94 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS Printing Printing out during ladder monitoring is described. When performing printouts of the ladder monitor screen, always install the option driver to GOT. A printout on paper of a ladder monitor screen can be generated for the TFT-STN type screen display. For the EL type screen display, no printout can be produced. ( Printout method during ladder monitoring The printout method during ladder monitoring is described below: <Ladder monitor screen> STEP : 2345/8374 Display the ladder monitor screen by touching LADDER MON. Execute the printout by touching Print Screen. 2) To cancel the printout, touch Cancel Print. Exit PLCRD. Mon. Menu List Print Screen Cancel Print 6-9
95 6. OPERATING THE VARIOUS LADDER MONITOR SCREENS MEMO 6-2
96 7. ERROR DISPLAY AND HANDLING WITH LADDER MONITORING Chapter7 Error display and handling with ladder monitoring The following chart shows the error messages that are displayed during the ladder monitor operation and the method of handling them. Error Message Description Method of Handling ENTRY CODE MISMATCH FILE NOT FOUND PLC COMMUNICATION ERROR LOCK ON OTHER MACHINE. PLEASE CANSEL NOT EXISTING DRIVE, DRIVE ERROR The specified keyword is different from the keyword that is registered in the object PLC CPU. ( An attempt was made to switch to the ladder monitor screen when a sequence program had not been read. (2) When the file is selected and the Read key is pressed, the selected file does not exist in the PLC drive. ( Cannot communicate with PLC CPU of the specified network No. or station No. (2) The specified drive does not exist. File is locked with the peripheral equipment (GPPW, GPPQ). ( The specified drive does not exist. (2) The specified drive is faulty. Check the keyword that is registered in the object PLC CPU and specify again. Read the sequence program that is written in the object PLC CPU. (Ex.) A sub-sequence program can only be specified as A3 CPU/A4UCPU. Check and correct the following: ( Does the specified PLC CPU exist? (2) Is it online? (Data communication status?) (3) Has an error occurred? After reading and writing with the peripheral equipment (GPPW, GPPQ), read the file again. ( Check whether the specified drive exists or not. (2) Check whether the specified drive is faulty or not
97 7. ERROR DISPLAY AND HANDLING WITH LADDER MONITORING MEMO 7-2
98 8. OPERATION PROCEDURES FOR THE SYSTEM MONITOR FUNCTION Chapter8 Operation procedures for the system monitor function The operation procedures for using the system monitor function are explained in this section. 8. Operation procedures before starting system monitoring This section contains a summary of the procedure for transmitting the system program (OS) for the system monitor function from the Personal computer to the GOT until it is installed in the built-in memory. For details, please refer to the Help in the drawing software. Details of the screen display and key operation are shown in the Help. Start 8 Connect GOT to Personal computer. Start up GOT.!!! It is not necessary to set up and operate the GOT after startup. Start up Personal computer and drawing software. With the drawing software, transmit the system program (OS) for the system monitor function from the Personal computer to the GOT and install it in the built-in memory.!!! Transmit the data using the installation dialog box. When installation is finished, the system monitor can be operated through the GOT.!!! When installation is finished, "Completed" is displayed on the installation dialog box. Drawing software operation is finished.!!! Proceed to Section 8.2 to operate the screen monitor. End 8 -
99 8. OPERATION PROCEDURES FOR THE SYSTEM MONITOR FUNCTION 8.2 Operation procedures from user-created monitor screen display to start of system monitoring This section explains the operation procedure for the GOT when starting each operation of the system monitor function, after the system program (OS) of the system monitor function has been installed in the GOT built-in memory. Start Start up the GOT Display the user-created monitor screen. Start the system monitor function.!!! ( Display the system monitor initial scren. DEV MON BAT MON TC MON DEV MON BAT MON TC MON BM MON BM MON END END!!! The A985/97*/96GOT displays 4 divided windows. Operation for each window is described. The A95*GOT displays window. When END is selected in any window, the system monitor ends and the display moves to the original screen where the system monitor function started. DEV MON BAT MON TC MON DEV MON BAT MON TC MON BM MON BM MON END END DEV MON BAT MON TC MON BM MON!!! Touch display position of monitor function to be selected. To Sec To Sec To Sec To Sec. 9.5.!!! See Sec. 9. for common operations. Execute operation for selected monitor function. Display monitor screen of selected function. SET TEST To Sec. 9.6.!!! The procedure for testing is as follows:! Set/reset bit device.! Change current values of word device.! Change current value, set values of T or C. * Touch the key where the touch switch (expanded) function was set with the drawing software, and start the system monitor function. When the Utility screen is displayed, touch PLC. MON. to start the system monitor function. 8-2
100 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS Chapter9 Operation of the various system monitor screens This chapter contains an explanation of each screen operation when using the system monitor function. POINT With any of the four windows, when changing the station/monitor device or executing the test operation, it is not possible to do an operation with another window until that series of operations is finished. 9. Screen configuration, common operations and changing screens when monitoring The common operations of each monitor function such as screen configuration and target PLC CPU specification when executing system monitoring are described below. 9.. Basic screen configuration and key functions (menu) 9 The basic screen configuration displayed in the windows and the key functions displayed on the screen are shown below. ( Display DEV MON BAT MON TC MON BM MON END (2) Key functions The functions of keys that are used with the basic screen operation are shown in the chart below. Key DEV MON BAD MON TC MON BM MON END Function The entry monitor is executed with the applicable window (see Sec. 9.2.). The batch monitor is executed with the applicable window (see Sec. 9.3.). The timer/counter monitor is executed with the applicable window (see Sec. 9.4.). The buffer memory monitor is executed with the applicable window (see Sec. 9.5.). System monitoring ends; display returns to the screen where system monitors function started. 9 -
101 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS 9..2 Switching the display form (decimal/hexadecimal) and turning the comment display on/off (FORM) ( Switching the display form (decimal/hexadecimal) Display the word device present value or the timer/counter present value or set value in decimal or hexadecimal. (2) Switching the comment display on and off Display the comment that is written in the object PLC CPU (Comment display priority order: expanded comment > Japanese character comment or Japanese kana comment). (When changing to hexadecimal display) (When changing to comment display) DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] D 5 H 8 D H 8 X! M 25 " Y 7! W 2 H 2B R 5 H 435 C 2 H 7 DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] D 2 5 [Production line A ] W 2 43 [Production quantity ] R DW [link status ] X [Production line B ] When the monitoring destination is being operated with the following conditions using the QnA series CPU, take note that the comment display cannot be performed. <Conditions> When executing multiple programs, multiple comment files exist, and all comment files are set as "same file name being used as program." When performing the comment display, use the comment file with a set specification. 9-2
102 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS Below is an explanation of the operation for changing the display, using the Entry Monitor window as an example. The operation procedure is the same for changing the display when selecting windows other than Entry Monitor. [Operation procedure] Display Entry Monitor screen. DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] D 5 H 8 DW D H 8 X! M 25 " FORM (Touch) When you touch MENU you return to the basic screen. When you touch, SET, the monitor station and device )... can be specified. (See Sec. 9..3) When you touch FORM, you can change this display. The selected FORM display is also found on the screen displayed after selecting the monitor function with the basic screen and on each menu screen, in addition to each monitor screen. DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] NUMERIC DEC HEX )... Display monitor station network no. and station * When you touch CANCEL, the display change is interrupted and the display returns to the monitor screen. COMMENT DISPLAY CANCEL NOTHING EXECUTE (Change display form.) DEC HEX (Change comment display) YES NO ( Touch the display position of the selected menu. EXECUTE (Touch) (Return) Monitor screen POINT After starting the system monitor, if the PLC CPU comment or comment capacity is changed, the comment may not be correctly displayed on each monitor screen. When changing the comment or comment capacity, re-start the GOT. 9-3
103 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS 9..3 Specifying the monitor station and device (SET) An explanation of the procedure for specifying the monitor station and the device for executing the system monitor is explained below, using the Entry Monitor window as example. The operation procedure is the same for specifying the monitor station and device when selecting windows other than Entry Monitor. * When there is a (keywindow), touching it to returns to the monitor screen. [Operation procedure] Select monitor function with basic screen. Or, display monitor screen or menu screen....see Sec See the explanatory section for each monitor screen and the menu screen. DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] D DW D X! M 25 " T 3 2 W 2 43 R DW C When you touch MENU you return to the basic screen. When you touch FORM, you change this display. (See Sec ) When you touch SET, you can specify the monitor station and device. SET (Touch) DEVICE MONITOR MENU FORM SET NETWK No.[ ] STATION[FF] ENTRY DELETE ALL CLR TEST CANCEL ENTRY (Touch) 9-4
104 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS NETWK No.[ ] STATION[FF] DEVICE[ D] [ ] 6b: 32b: [] X Y M L S B A F Z D V W T R C E G AC DEL Specify network No. and station No. of object PLC CPU. (* (For data link system) NET WK No.: STATION : FF (Host station) (Master station) to 64 (Local station) (For network system) NET WK No.: (Host loop) to 255 (Specified loop) STATION : FF (Host station) (Control station) to 64 (Normal station) Arrow: Select input area. ( : Left / right) Character: Input network no., station, device name, device no. : Enter monitor module. (Touch: input confirmation) (*2)(*3) (2) Specify the device to be monitored. (3) When specifying the word device or buffer memory as a monitor device, specify the monitor module. : 6-bit (-word) module : 32-bit (2-word) module * Match the data to be entered; the touch key display at the bottom of the screen will change. Entry monitor for specified device (EX.) (When entering network no.) (When entering device no.) NETWK No.[ ] STATION[FF] DEVICE[ ] [ ] 6b: 32b: [] # A C E AC B D F DEL NETWK No.[ ] STATION[FF] DEVICE[ D] [ 5 ] 6b: 32b: [] A C E B D F # AC DEL * For the station, with either system, specify "FF", which shows the PLC CPU to be accessed, or "" to "64". *2 Data being entered can be cleared by the following keys. AC : Clears all data being entered to the target area. DEL : Clears one character at the cursor position. *3 The form of data to be entered is displayed at the right side of the screen. DEC : Enter in decimal HEX : Enter in hexadecimal 9-5
105 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS 9..4 Changing screens This section shows the screen changes when executing each monitoring operation of the system monitor function from the status where the user-created monitor screen is displayed. Start (* User-created monitor screen * Touch the key that sets the touch switch (expanded) function with the graphics software. and start the system monitor operation. Touch (* When the Utility screen is dislayed, touch PLC.MON. to start the system monitor function. Utility screen ####################### The circuit monitor function and special module function can also be started from the Utility screen. Touch END Touch PLC.MON. Touch STOP 2) Basic screen (Function change menu screen) Touch FORM 3) (See Sec. 9...) Touch SET 4) Touch MENU Touch MON Touch STOP 2) 2) Monitor screen for selected function (See Sec ) Touch FORM 3) Display change menu screen (See Sec ) Touch Touch Touch MENU SET 4) 2) EXEC / Test menu screen (See Sec. 9.6.) Touch SET 4) Device setting menu screen (See Sec. 9..3) Touch Touch Touch STOP 2) MENU FORM 3) 2) Touch TEST 9-6
106 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS 9.2 Entry monitor Enter the device to be monitored in advance. The function that monitors only the device that was entered is called the "entry monitor". The entry monitor operation when executing the system monitor function is explained below Basic operation The entry monitor operation procedure is shown below. [Operation procedure] Select "Device Monitor" with the basic screen. TEST MENU FORM PRESS "SET" KEY, SELECT ITEM THEN ENTER DEVICE TYPE & NO. SET See Sec When a screen other than the basic screen is displayed, touch MENU at the top of the currently displayed screen, display the basic screen, and select Device Monitor....When you touch MENU, you return to the basic screen. When you touch FORM, you can change this display (See Sec ). When you touch SET, you can specify the monitor station and device (See Sec ). (*2) Enter the monitor device. (*...Set the station and device to be monitored. For the setting method, see Sec When entry is complete, display the Device Monitor screen. DEVICE MONITOR TEST MENU FORM SET NETWK NO.[ ] STATION[FF] D DW D X! M 25 " Y 7! W 2 43 R DW D 3 * Monitor device entry is in station modules. If you change the station for the monitor device, all monitor devices entered before that are invalid. *2 A maximum of 8 entry devices can be entered. To enter more than 8, delete in order from the old entry device. The 8 most recent entry device will be monitored. As needed, re-enter after deleting the entry device. (For the method of deletion, see Sec ) Change the screen display....do if needed. For the display change method, see Sec
107 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS Entry monitor screen display and key functions In this section, the Entry Monitor screen display and the functions of the keys displayed at the top of the screen are explained. ( Display 2) 3) DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] D 2 3 [Line current units] W 2 43 [Production line A ] R DW [link status ] X 3! [Input switch 3 ] When comment is not displayed: max. 8 devices When comment is displayed : max. 4 devices Display when system monitoring #Bit device #########!:ON ": OFF #Word device #####Current value Displays the keys that are used with the operation of the Entry Monitor screen shown in (2) (Touch input). 2) Displays the monitor station network No. and station No. 3) Displays the status and current value of the device. (2) Key functions The chart below shows the functions of the keys that are used with the Entry Monitor screen operation. Key MENU FORM SET Function Move to basic screen (function change menu screen) to change to another monitor function or ending the system monitor (See Sec. 9...). Move to the display change menu screen to change the numerical display on the Entry Monitor screen (decimal, hexadecimal) or changing the comment display (on/off) (See Sec ). Move to device setting menu screen to enter the monitor device, delete the device, or execute a test. Entry of monitor device (See Sec ) Deletion of entry device (See Sec ) Test (See Sec. 9.6.) Scroll the display up or down one line, and display the monitor device that is not displayed (just before or after the current display). When five or more monitor devices are entered, operation is enabled when the monitor device comment is displayed. : Scrolls down one line. : Scrolls up one line. 9-8
108 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS Deleting a registered device The operation of deleting (erasing) the entry of the device being monitored with the Entry Monitor screen is explained below. The following two methods can be used to delete the registered device. Random deletion... Deletes only one specified device. Batch deletion... Deletes all devices that are currently registered. * If there is a at the upper left of the screen, touching the returns to the monitor screen. [Operation procedure] Display Device Monitor screen.... See Sec SET (Touch) Display device setting menu screen. DEVICE MONITOR NETWK No.[ ] TEST MENU FORM SET STATION[FF] DEVICE DELETE ALL CLR TEST CANCEL (Batch deletion) (Random deletion) ALL CLR DELETE (Touch either key.) Display device deletion screen. DEVICE [ ] [ ] X Y M S B ( Specify the device to be deleted. * Match the data to be enterd; the touch key display at the bottom of the screen will change. F D W R A Z V T C E G AC DEL : Select input area Character: Input device name and no. (* * Data being entered can be cleared by the following keys. AC : Clears all data being entered to the object area. DEL : Clears one character at the cursor position. Move (return) to Device Monitor screen. (Touch: Input confirmation) 9-9
109 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS 9.3 Batch monitor When monitoring, the function of specifying the device at the beginning of an optional device range and monitoring it is called the "batch monitor". The batch monitor operation when executing the system monitor is explained below Basic operation [Operation procedure] Select "Batch Monitor" with the basic screen. The batch operation procedure is shown below. See Sec TEST MENU FORM SET NETWK No.[ ] STATION[FF] PRESS "SET" KEY, SELECT ITEM THEN ENTER DEVICE TYPE & NO....When a screen other than the basic screen is displayed, touch MENU at the top of the currently displayed screen, display the basic screen, and select "Batch monitor"....when you touch MENU, you return to the basic screen. When you touch FORM, you can change this display (See Sec ). When you touch SET, the monitor station and device can be specified (See Sec ) Specify the first monitor device. ( Specify the station and device to be monitored. For the method of specifying, see Sec When reading is complete, display the Batch Monitor screen. BATCH MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] D D 8-5 D D D 2 D 2 D 3 - D 2 D 4 D 22 D 5 3 D D 6 D 24 D 7 D 25 Change the screen display....do if needed. For the display change method, see Sec
110 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS Batch monitor screen display and key functions In this section, the Batch Monitor screen display and the functions of keys displayed at the top of the screen are explained. ( Display 2) BATCH MONITOR TEST MENU FORM NETWK No.[ ] STATION[FF] SET 3) D 32767[ ] D [Inventory quantity ] D 2 [Shipment quantity ] D 3 -[ ] D 4 [Warehouse A temperature] D 5 3[Warehouse B temperature] D 6 [ ] D 7 [Production plan ] When comment is not displayed: max. 6 devices When comment is displayed : max. 8 devices Display when system monitoring!bit device!!!!!!!!!":on #: OFF!Word device!!!!!current value Displays the keys that are used with the operation of the Batch Monitor screen shown in (2) (Touch input). 2) Displays the monitor station network No. and station No. 3) Displays the status and current value of the monitor device (The screen above shows when the monitor module is 6 bits.). (2) Key functions The chart below shows the functions of the keys that are used with the Batch Monitor screen operation. Key MENU FORM SET Function Move to basic screen (function change menu screen) for changing to another monitor function or ending the system monitor (See Sec. 9...). Move to display change menu screen for changing the numerical display on the Batch Monitor screen (decimal/hexadecimal) or changing the comment display (on/off) (See Sec ). Move to device setting menu screen to change the monitor device or execute a test. Change of monitor device (See Sec ) Test (See Sec. 9.6.) Scroll the display up or down one line, and display the monitor device that is not displayed (just before or after the current display). : Scrolls down one line. : Scrolls up one line. 9 -
111 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS 9.4 TC Monitor (monitor of timer and counter) The function that monitors only the time (T) and counter (c) when monitoring is called the TC monitor. The TC monitor operation when executing the system monitor is explained below Basic operation [Operation procedure] Select "TC Monitor" with the basic screen. The TC operation procedure is shown below. See Sec TEST MENU FORM SET NETWK No.[ ] STATION[FF] PRESS "SET" KEY, SELECT ITEM THEN ENTER DEVICE TYPE & NO....When a screen other than the basic screen is displayed, touch MENU at the top of the currently displayed screen, display the basic screen, and select "TC Monitor"....When you touch MENU, you return to the basic screen. When you touch FORM, you can change this display (See Sec ). When you touch SET, the monitor station and device can be specified (See Sec ). Specify the initial monitor device. ( Specify the station and devised to be monitored. For the method of the specifying, see Sec When reading is complete, display the TC Monitor screen. TC MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] T PV SV T PV SV T 2 PV 5 SV 5 T 3 PV SV T 4 PV SV T 5 PV 25 SV 2 T 6 PV SV 3 T 7 PV SV Change the screen display....do if needed. For the display change method, see Sec
112 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS TC Monitor screen display and key functions In this section, the TC Monitor screen display contents and the function of keys displayed at the top of the screen are explained. ( Display 2) 3) TC MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[33] FILE [ABCDEF.PRG] T PV SV [Production line A] T PV SV [Production line B] T 2 PV 5 SV 5 [Production line C] T 3 PV SV [Production line D] When comment is not displayed: max. 8 devices When comment is displayed : max. 4 devices Display when system monitoring T/C current value, set value (Contact point, coil) :ON : OFF 2) 3) Displays the keys that are used with the operation of the TC Monitor screen shown in (2) (Touch input). Displays the monitor station network No. and station No. When connected to QnACPU, the execution file name is displayed (If there are more than one file, the first file name is displayed.). Displays the current value, set value, contact point and coil status of the monitor device (The screen above shows when the monitor module is 6 bits.). (2) Key functions The chart below shows the function of the keys that are used with the operation of the TC Monitor screen. Key MENU FORM SET Function Move to basic screen (function change menu screen) for changing to another monitor function or ending the system monitor (See Sec. 9...). Move to display change menu screen for changing the numerical display on the TC monitor screen (decimal/hexadecimal) or changing the comment display (on/off) (See Sec ). Move to device setting menu screen to change the monitor device or execute a test. Change of monitor device (See Sec. 9..3) Test (See Sec. 9.6.) Scroll the display contents up or down one line to display the monitor device that is not displayed (just before or after the current display). Operation is enabled when monitor device comment is displayed. : Scrolls down one line. : Scrolls up one line. 9-3
113 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS 9.5 BM Monitor (monitor of buffer memory) When monitoring, the function that monitors the buffer memory of the special function module is called the "BM monitor". The BM monitor screen when executing the system monitor is explained below Basic operation [Operation procedure] Select "BM Monitor" with the basic screen. The BM Monitor operation procedure is shown below. See Sec TEST MENU FORM SET NETWK No.[ ] STATION[FF] PRESS "SET" KEY, SELECT ITEM THEN ENTER DEVICE TYPE & NO....When a screen other than the basic screen is displayed, touch MENU at the top of the currently displayed screen, display the basic screen, and select "BM Monitor"....When you touch MENU, you return to the basic screen. When you touch FORM, you can change this display (See Sec ). When you touch SET, the monitor station and device can be specified (See Sec ). Specify the initial monitor device. ( Specify the station and device to be monitored, and the monitor module (6-/32-bit module). When reading is complete, display the BM Monitor screen. BM MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] I/O NO [ ] BM BM 8 BM 64 BM 9 BM 2 49 BM 2 5 BM 3 - BM 2 3 BM 4 26 BM BM 5 6 BM BM BM BM 7 2 BM 25 (2) For the method of the specifying, see Sec Specify the module to be monitored and the buffer memory as follows. Initial Y [ ] [ ] Specify the initial address of the buffer memory in decimal. When the initial I/O signal of module is displayed with three digits, specify the first two digits. Change the screen display....switching between decimal and hexadecimal display is enabled. Do this as needed. For the display change method, see Sec
114 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS BM Monitor screen display and key functions In this section, the BM Monitor screen display and the functions of keys displayed at the top of the screen are explained. ( Display 2) 3) BM MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] I/O NO[ ] BM BM 8 BM 64 BM 9 BM 2 49 BM 2 5 BM 3 - BM 2 3 BM 4 26 BM BM 5 6 BM BM BM BM 7 2 BM 25 Displays current value of a maximum of 6 devices. 2) 3) Displays the keys that are used with the operation of the BM Monitor screen shown in (2) (Touch input). Displays the monitor station network No. and station No., and the first 2 digits of the I/O signal No. of the object module. Displays the current values of the buffer memory (The screen above shows when the monitor module is 6 bits.). (2) Key functions The chart below shows the function of the keys that are used with the operation of the BM Monitor screen. Key MENU FORM SET Function This moves to basic screen (function change menu screen) for changing to another monitor function or ending the system monitor (See Sec. 9...). This moves to display change menu screen for changing the number display on the BM monitor screen (decimal/hexadecimal) (See Sec ). This moves to device setting menu screen to change the monitor device or execute a test. Change of monitor device (See Sec ) Test (See Sec. 9.6.) 9-5
115 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS 9.6 Test CAUTION Read the manual carefully and fully understand the operation before the test operation (ON/OFF of bit devices, modifying current value of a word device, modifying timer/counter setting, modifying the current value, or modifying the current value of a buffer memory) of system monitor. In addition, never modify data in a test operation to a device which performs a crucial operation to the system. It may cause an accident by a false output or malfunction. When monitoring with the system monitor function, you can specify an optional station or device to be monitored and test it. The operation of testing a bit device, word device, or special module buffer memory of the PLC CPU is explained in this section Basic operation [Operation procedure] The operation procedure for testing when monitoring with the system monitor function is shown below. See Sec When monitoring with the system monitor function, display any monitor screen. DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF]...When a screen other than the monitor screen is displayed, display any monitor screen according to the explanatory section for each monitor function....when Device Monitor screen is displayed. D DW D X! 25 " SET (Touch) Display device setting menu screen....when you touch CANCEL, the display moves (returns) to the previous monitor screen. DEVICE MONITOR TEST MENU FORM NETWK No.[ ] STATION[FF] SET DEVICE DELETE ALL CLR TEST CANCEL TEST (Touch)...When you touch CANCEL, the display moves (returns) to the previous monitor screen. Display test menu screen. DEVICE MONITOR MENU FORM NETWK No.[ ] STATION[FF] SET SET/RST SET VAL VALUE6 VALUE32 BM VAL6 BM VAL32 CANCEL 9-6
116 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS Select test item. When SET/RST is selected. NETWK No.[ ] STATION[ ] DEVICE[ ] [ ] RST: SET: X Y M L S B F G AC DEL ( Touch either, depending on test contents. SET/RST SET/RST (set/reset) bit device. VALUE6 or VALUE32 Change current value of word device. SET VALUE Change T, or C set value. BM VAL6 or BM VAL32 Change current value of buffer memory. * With VALUE6 or BM VAL6, 6 bits is the object module. With VALUE32 or BM VAL32, 32 bits is the object module. When VALUE6 / VALUE32 is selected. When SET VALUE is selected. NETWK No.[ ] STATION[ ] DEVICE[ ] [ ] VL[K ] A E Z G D V W T AC S R C DEL Arrow : Select input area. ( : Left/right) Character: Enter network No., station No., device name, device No., test value. (*(*2) Move (return) to screen where (Touch: input confirmation) SET was specified. NETWK No.[ ] STATION[ ] DEVICE [ ] [ ] VL[K ] T C AC DEL (2) Specify the network No. and station No. of the object PLC CPU (See Sec. 9..3, *.). (For data link system) Network No.: Station : FF (Own station) (Master station) to 64 (Local station) (For network system) Network No.: (Host loop) to 255 (Specify loop) Station : FF (Own station) (Control station) to 64 (Normal station) (3) Specify object device. (4) Specify test value. # With SET/RST (set/reset) of bit device, specify (RST) or (SET). # When changing current value of word device When changing T or C set value or When changing current value of buffer memory Match current display form (decimal/hexadecimal) and specify change value. (*3) 9-7
117 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS * The data being entered can be cleared by using the following keys. AC : Clear all data being entered in the object area. DEL : Clear one character from the cursor position. *2 The format for the data being entered is displayed on the right side of the screen. DEC : Enter in decimal. HEX : Enter in hexadecimal. *3 Even when the setting value/current value is changed after the timer (T) has timed out and the counter (C) has finished counting, the time-up status/count-up status do not change. The current status is maintained. (When the setting value is changed to a large value/when the current value is changed to a small value) 9-8
118 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS Quick test function In addition to the existing tests for the direct input of device, station No., etc. during monitoring with the system monitor function, this function enables the bit device SET/RESET, word device, buffer memory data to change by a single touch. Operation to set the quick test function on To perform the quick test functions, perform the following operations: [Operation procedure] Display one of the system monitor screen. DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF]...When displaying the device monitor screen. D DW ZR X! M 25 " W 2 43 R DW D W TEST (Touch) DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF]...The quick test is turned on by clicking on OK. D 5@ @ DW ZR MODE œ M W O 43K R W O K DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF]...Status when the quick test function is on. D DW ZR X! M 25 " W 2 43 R DW D W 9-9
119 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS 2) Operation to turn off the quick test function When TEST is touched when the quick test function is on, a dialog box is displayed. When OK is touched, the quick test can be canceled. DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] D DW ZR X! M 25 " W 2 43 R DW D W 3) Bit device quick test...when the device monitor screen is displayed. Touch the device name or device no. display position for the bit device to be SET/RESET. DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] D DW ZR X! M 25 " W 2 43 R DW D W...The device name and device no. touched is displayed highlighted. When the on/off display (",!) of the hihglihted display is touched, the status is SET/RESET. * When the current bit device is ON, then it is turned OFF (RESET). When OFF, it will be (SET). DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF]...The on/off display area (",!) of the X device is highlighted. D DW ZR X " M 25 " W 2 43 R DW D W 9-2
120 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS DEVICE MONITOR TEST MENU FORM SET NETWK No.[ ] STATION[FF] 4) Quick test for the word device, T/C monitor, and buffer memory...when displaying the device monitor screen. Touch the display position of the device to be changed. D DW ZR X! M 25 " W 43 R DW D 5 W NETWK No.[ ] STATION[FF] DEC DEVICE[ W] [ 2] VL [ ] A B...The change value input screen is displayed. Enter the current value to be changed in the KEY window. See Section 8..3 for the KEY window operations C D 2 3 E F # AC DEL 9-2
121 9. OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS MEMO 9-22
122 . ERROR DISPLAY AND HANDLING WITH SYSTEM MONITORING Chapter Error display and handling with system monitoring The following chart shows the error messages that may be displayed when operating the system monitor and the method of handling them. Error Message Description Method of Handling PLC communications error Communication could not be established with the PLC CPU. Check the following: Connections between the PLC CPU and the GOT (disconnected or cut cables). Has an error occurred in the PLC CPU? -
123 . ERROR DISPLAY AND HANDLING WITH SYSTEM MONITORING MEMO - 2
124 . OPERATION PROCEDURES FOR SPECIAL MODULE MONITOR FUNCTION Chapter Operation procedures for special module monitor function The operation procedure when using the special module monitor function is explained in this chapter.. Operation procedures before starting special module monitoring This section contains a summary of the procedure for transmitting the system program (OS) for the special module monitor function and the special module monitor data from the personal computer to the GOT until it is installed in built-in memory. For details, please refer to the Help in Drawing Software. Details of the screen display and key operation are shown in the Help. Start Connect GOT and personal computer. Start up GOT. Start up personal computer and start drawing software.!!! It is not necessary to set up and operate the GOT after startup. With the drawing software, transmit the OS for the special module monitor function from the personal computer to the GOT and install it in the built-in memory.!!! Transmit the data using the installation dialog box. Installation is complete. is With the drawing software, transmit the special module monitor data from the personal computer to the GOT and install it in the built-in memory. (Download)!!! When installation is finished, "Completed" is displayed on the installation dialog box.!!! Transmit the data using the download dialog box. When download is finished, the special module monitor can be operated through the GOT.!!! When download is finished, "Completed" is displayed on the download dialog box. Drawing software operation is finished. End!!! Proceed to Section 2.2 to operate the special module monitor. -
125 . OPERATION PROCEDURES FOR SPECIAL MODULE MONITOR FUNCTION.2 Operation procedures from user-created monitor screen display to start of special module monitor This section describes the operation procedure for the GOT when starting each operation of the special module monitor function after the system program (OS) of the special module monitor function has been installed in the GOT built-in memory, and downloading the special module monitor data. Start Install memory board on the GOT Start up GOT. Display the use-created monitor screen. Start the special module monitor function.!!! ( Display the system configuration screen. NET System Configuration NETWK No. [] PLC STATION [FF] PLCNo. MAIN CPU OUT64 IN 64 Ext. Y IN 6 Y2 Y 4 OUT32 Y3 AJ7 PT32-S3 X,Y 8 AJ7 X,Y5 SP X,Y A A62LS X,Y8 IN 64 Y 4 AJ7 PT32-S3 X,Y 8 A66DA X,Y END!!! When starting, the module format and related data are not displayed. When reading of module data from the PLC CPU is complete, the module format and related data is displayed. See Sec Ext.2 A66AD X,Y 2 SP X,Y23 A66TD X,Y 28 When END is selected, the special module monitoring ends and the display moves to the original screen where the special module monitor function was begun. Specify the module to be monitored.!!! See Secs. 2..3, Display the special module monitor menu.!!! See Sec Select from the menu. Display the monitor screen for the special module. Check the data for the module with the displayed contents.!!!!!! The Special Module Monitor Screen is displayed by selecting it from the menu. See Sec See Sec See Secs. 2.2 to Change the data. Change the current value of the specified area.!!! Carry out the following operation when changing the current values of the buffer memory that is displayed on the monitor screen. See Sec Touch the key where the touch switch (expanded) function was set with the drawing software, and start the system monitor function. When the Utility screen is displayed, touch SP.Mon. to start the special module monitor function. - 2
126 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Chapter2 Operation of each special module monitor screen Each screen operation when using the special module monitor function is explained in this chapter. 2. Screen configuration, common operation and changing screens when monitoring The screen configuration and common operations used when executing the special module monitor are explained in this section. 2.. Composition of system configuration screen and key functions 2) This section describes the structure of the system configuration screen that is displayed after starting the special module monitor function and the key functions displayed on the screen. ( Display The module format and related data are displayed at the end of the module data readout from the PLC CPU. (OS executes it automatically.) When connected to MELSECNET, the screen shown in Section 2..3 is displayed. 2 Displays network No. and station No.. of monitor station. 2) 3) 3) With the module installed in the monitor station, the special function module displays the format and the initial no. of the I/O signal with the sequencer CPU; the I/O module displays "Input"/"Output" and the I/O points. For a special function module that cannot be monitored, "Special" and the initial no. of the I/O signal are displayed. The display position of the module is the key for moving the special function module monitor of that module to the screen where it is executed (Touch input) The keys used for the operation with the System Configuration screen shown in (2) are displayed. (Touch input) (2) Key functions The chart below shows the functions of the keys that are used with the System Configuration screen operation. Key END Module display position Function Monitoring ends; and display returns to the screen where the special module monitor function was begun. Moves to screen where the special module monitor for that module is executed. Slots through 7 are valid for each base module. 2 -
127 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Key Function Scrolls display up or down one level to display the system configuration of the level number just before or after the one that is currently displayed. Operation of these keys is enabled when the system configuration extends to three levels or more. : Scrolls down one level. : Scrolls up one level Monitor screen configuration and key functions This section describes the structure of the monitor screen that is displayed by specifying the module with the system configuration screen, and the key functions that are displayed at the top of the screen. ( Display (with A68RD) 3) All types of data are displayed when the readout from the special function module is complete. (OS executes it automatically.) 2) Displays format of module being monitored. Displays buffer memory data of object module in its current form, or in a graph. 2) Display status of I/O signal with the PLC CPU. When testing, tests after moving the cursor to the display position of the target data. The keys used for the operation with the monitor screen shown in (2) are displayed. 3) (Touch input) (2) Key functions The chart below shows the functions of the keys that are used with the System monitor screen operation. Key END MONIT MENU Data Chg. SET/ RESET Function Monitoring ends; and display returns to the screen where the special module monitor function was begun. Ends current monitoring and moves to screen that shows monitor menu. Operation can be used only if the special function module has a Monitor menu. Starts change of current values for buffer memory of special function module displayed on screen. Starts test set/reset for I/O signal between PLC CPU and special function module. 2-2
128 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2..3 Setting method for remote station monitoring The setting method to perform remote station monitoring during special module monitoring is described below. <Special Module Monitor> When connected to MELSECNET 2) Touch SP.UNIT to display the system configuration screen. Depending on the connection method, the screen first displayed will be different as indicated below. Bus connection and CPU direct connection MELSECNET (II), /B connection MELSECNET/ connection The base of the connection station is displayed. No system configuration display No system configuration display for MELSECNET connections, the following operations will always be required: Touch NETPCNo. to display the window shown in 2) 2) Touch Alphanumeric to specify the network No. and PLC station No.. Alphanumeric.. Enter the network No. and PLC station No..... Select the input area.... Set the area value. In the case of data link systems NETWK NO. : STATION : FF (Host) : (Master station) : to 64 (Local station) In the case of network systems NETWK NO. : (Host loop) : to 255 (Specified loop) STATION : FF (Host) : (Station number of management station) : to 64 (Normal station) When the setting is finished, the system configuration of the specified station is displayed. See Sec for operations which come after these operations. 2-3
129 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2..4 Specifying monitor module and selecting monitor menu The operation when starting the special module monitor for an optional module is explained, using the positioning module (AD7 as an example. [Operation procedure] Display System Configuration screen.!!! See Sec [Specify module to be monitored] (Touch display position of module.) Display screen that shows monitor menu. [Specify menu to be monitored] (Touch display position of menu.) ( From the modules assigned to slots through 7 of each base unit, specify the special function module where the format is displayed. * For modules where the format is not displayed, monitor with the system monitor function (See Sec. 9.5.). Specify input/output modules according to Sec. 3.. (2) Specify the menu corresponding to the type of data to be monitored. (3) With modules for which the monitor menu cannot all be displayed in one screen, touch the keys at the right of the screen to scroll the display menu. Display monitor screen of specified menu. (4) Check the contents of the display. Carry out the subsequent operation according to Sec. 2.2 to (5) Carry out tests for the displayed data according to Sec Change current value of buffer memory Turn output signal from PLC CPU on and off Proceed to Sec and Secs. 2.2 to
130 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2..5 Test for special function module CAUTION Read the manual carefully and fully understand the operation before the test operation (modifying the current value of a buffer memory) of special function module monitor. In addition, never modify data in a test operation to a device which performs a crucial operation to the system. It may cause an accident by a false output or malfunction. Testing can be performed for all buffer memory data displayed on the current monitor screen. This section describes the operation for changing the current value of the buffer memory and turning the output signal from the PLC CPU to the special module on and off. POINTS ( When testing, test for the buffer memory to be written in from the PLC CPU and the output signal that is output from the PLC CPU. (2) Be sure to carry out the test operation with the PLC CPU in STOP status. If the PLC CPU is tested during RUN status, it returns to the output values and output status from the sequence program. [Operation procedure] Display monitor screen. 2) 3) Data Chg., SET/ RESET (Touch) 2-5
131 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Display key window on monitor screen. (Touch: input confirmation) 3) (Test continues) (Test ends) (Touch) 2) Data When is touched (changes current value of buffer Chg. memory) All of the following operations can be carried out by touching the keys in the displayed key window. When you touch at the upper left of the key window, the key window closes and the display returns to the monitor screen. ( Move the cursor to the position where the data to be tested is displayed. (* ( : Up/down : Left/right) (2) Use the numeric keys to specify the value to be changed. (*2) The DEL key can be used to clear individual characters among those input. SET/ When is touched (tests the I/O signal) RESET All of the following operations can be carried out by touching the keys in the displayed key window. When you touch at the upper left of the key window, the key window closes and the display returns to the monitor screen. ( Use the alphabetic character keys to specify the name of the device to be tested, and then touch. (* (2) Use the numeric keys to specify the device number, and then touch. (3) Use the numeric keys to specify "Set" or "Reset". : OFF : ON * Do not perform the following tests. When testing, the module may not operate correctly or the buffer memory/input signal may return to the output value/output status from the special function module. Test the buffer memory for reading-only from the PLC CPU. 2) Test the input signal to the PLC CPU from the special function module. *2 When testing buffer memory data, specify the change value in the following way. For data where 6/32 bits is displayed with one number, specify the change value in decimal. 2) For data where one number of 6/32 bits is displayed as a percent, such as with an A/D conversion module, specify the change value corresponding to the percentage in decimal. Example: When the set value of the offset or gain is to 2, when specifying a change value of 5%, input. 3) For data where 6 bits is displayed one bit at a time as "" and "", specify the change value of 6 bits in decimal. 2-6
132 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2..6 Changing the screen This section describes how to change the screen when executing each monitor function of the special module monitor function from the status where the user-created monitor screen is displayed. Start ( User-created monitor screen Touch ( Touch the key where the touch switch (expanded) function was set with the drawing software, and start the special module monitor operation. When the Utility screen is displayed, touch SP.UNIT and start the special module monitor function. Utility screen!!!!!!!!! The system monitor function and special module monitor function can also be started from the Utility menu screen. Touch END Touch SP.UNIT System Configuration screen (See Sec. 2...) Key window display screen for test (See Sec ) Touch sys.conf. Monitor menu display screen for specified module (See Sec ) Touch END Touch on display module. When I/O module is selected When special function module is selected Touch on monitor menu. Touch MONIT MENU Touch DataChg. and SET/RESET Touch Monitor screen for specified monitor menu (See Sec ) Go to user-created monitor screen or utility screen. 2-7
133 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.2 A6LS module monitor 2.2. Operation monitor 2) 3) 4) 5) 6) 7) 8) 9) ) ) No. Contents of display Buffer memory address to reference (decimal) The number of the program being used is displayed. The output status of each channel is displayed. 4 2) The specified status for the Output Enable command of each channel is displayed. 3) The measured distance value for the distance detection function is displayed. 5, 6 4) The rotation speed of the resolver connected to A6LS is displayed. 3 5) The set value of the target address for the positioning function is displayed. 2 6) 7) The compensation value for the zero point compensation function is displayed. The current value of the resolver after compensation by the zero point compensation function is displayed. 8) The error code is displayed when an error occurs. 8 9) ) When an A6LS resolver underflow is detected, "" is displayed. 2 When an A6LS resolver overflows is detected, "" is displayed. When a low battery charge is detected, "" is displayed. 9 The set values A and B for executing the positioning function are displayed for each channel. 3 to
134 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-9
135 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.3 AD6 module monitor 2.3. Operation monitor 2) 3) 4) No. Contents of display Buffer memory address to reference (decimal) The current values of channels and 2 are displayed. 4, 5, 36, 37 2) The set values of channels and 2 are displayed. 6, 7, 38, 39 3) The specified status of the mode register of channels and 2 is displayed. 3, 35 4) The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2 -
136 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.4 ASD6 module monitor 2.4. Operation monitor The Channel and 2 Monitor Screen is used as an example. 7) 5) 8) 9) ) 2) 6) 3) 4) No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. A "!" is displayed when a watchdog timer error occurs. 2) A "!" is displayed when a writing data error occurs; the channel where it occurred and the error code are displayed. Buffer memory address to reference (decimal) 3) The number of multi-dogs that are set is displayed. 2 to 47 4) The set value for the on position and off position of the multi-dog no. is displayed for each channel. 2 to 47 5) The specified status of the counter function selection is displayed. 5 6) 7) 8) The limit switch output status of each channel is displayed. : OFF : ON The current value of the counter is displayed for the following situations: in pulse input mode, when preset, when the ring counter function is being executed, and when the counter is disabled. The count value for execution of the latch counter, sampling counter, and periodic pulse counter set with the counter function selection (5) is displayed. 9) The preset value is displayed. 6, 7 ) The ring counter value that was set is displayed. 8, 9 The set status of the pulse input mode is displayed. 4, 2, 3 2 -
137 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-2
138 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.5 A62DA-S module monitor 2.5. Operation monitor 2) 2) 3) No. 2) 3) Contents of display The current input value, a value between to 4 for the digital input value of channels and 2, is displayed as a percentage ranging from to %. "" is displayed for Output Over when an input value of 4 or greater was set for channel or 2; "" is displayed for Output Under when a negative number was set. The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. Buffer memory address to reference (decimal), 2 to 5 2-3
139 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor 2) 3) 4) No. 2) 3) Contents of display The current input value, a value between to 4 for the digital input value of channels and 2, is displayed as a percentage ranging from to %. A "!" is displayed in the Over Error column when an input value of 4 or greater was set for channel or 2. A "!" is displayed in the Under Error column when an input value consisting of a negative number was set for channel or 2. Buffer memory address to reference (decimal) 4) A "!" is displayed when a watchdog timer error occurs., 2, 4 3, 5 2-4
140 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.6 AS62DA module monitor 2.6. Operation monitor 2) 3) 4) 5) 6) 7) 5) 6) 7) 8) 9) ) 8) 9) ) 2) 3) No. Contents of display The specified enable/disable status for the analog output of each channel is displayed. : Enable : Disable 2-5 Buffer memory address to reference (decimal) 2) The channel digital input value is displayed. 3) The channel 2 digital input value is displayed. 2 4) 5) 6) 7) 8) 9) ) 2) 3) The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. The current input value, a value between -4 to 4 for the digital input value of channels and 2, is displayed in a graph as a percentage ranging from to %. The current input value, a value between -8 to 8 for the digital input value of channels and 2, is displayed in a graph as a percentage ranging from to %. The current input value, a value between -2 to 2 for the digital input value of channels and 2, is displayed in a graph as a percentage ranging from to %. The current input value, a value between to 4 for the digital input value of channels and 2, is displayed in a graph as a percentage ranging from to %. The current input value, a value between to 8 for the digital input value of channels and 2, is displayed in a graph as a percentage ranging from to %. The current input value, a value between to 2 for the digital input value of channels and 2, is displayed in a graph as a percentage ranging from to %. When the channel digital input value was set outside the allowable setting range, a check code is displayed. When the channel 2 digital input value was set outside the allowable setting range, a check code is displayed. The set resolution selection is displayed. : /4 2: /8 3: /2, 2 9
141 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.7 A62LS module monitor 2.7. Operation monitor As a screen example, we will store the monitor screens from CH. to CH. 3 in the memory. 2) ) 3) 4) 5) 6) 7) 8) 9) No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. Buffer memory address to reference (decimal) 2) The error code is displayed when an error occurs. 7 The output status of each channel is displayed. 4 : OFF : ON 3) The set limit switch output enable/disable status for each channel is displayed. 8 : Enable : Disable 4) The sensor binary current value is displayed. 2, 3 5) After module conversion of the sensor binary current value to mm or inches, the value added to the minimum current value is displayed as the scaling binary current value., 6) The set value of the positioning object stop position is displayed., 7) The program number used with the limit switch output function is displayed. 9 8) The answer back program number corresponding to the program number used with the limit switch output function is displayed. 5 The A62LS operation mode status is displayed. b4b3b2bb 9) "" is displayed in the bit corresponding to the selected operation mode. Run Trial run Set Parameter Initial settings 6 ) The number of multi-dogs that are set is displayed. 2 to 226 The set value for the on position and off position of the multi-dog No. is displayed for each channel. 2 to
142 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-7
143 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.8 AS62RD module monitor 2.8. Operation monitor 2) 3) 4) 5) 6) 7) 8) 9) ) No. 2) 3) 4) Contents of display The temperature detection value of each channel is displayed up to digit after the decimal point. The temperature detection value of each channel is displayed up to 3 digits after the decimal point. The values set for the time and count of times for averaging processing of each of the channels is displayed. The specified conversion enabled/disabled status of each channel is displayed. Buffer memory address to reference (decimal), 8 to 2 5) The Conversion Completed flag status for each channel is displayed. 35 6) The specified status for the averaging processing/sampling processing of each channel is displayed. The specified status for the averaging processing of each channel is 7) displayed. A "!" is displayed when a watchdog timer error occurs. 8) A "!" is displayed when a writing data error occurs; the channel where it occurred and error code are displayed. 9) ) The specified status of the platinum temperature sensor that is used is displayed. For AS62RD3 A "!" is displayed in a channel where broken wire was detected. For AS62RD4 A "!" is displayed in CH when a broken wire is detected in any channel. 2,
144 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-9
145 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor 7) 2) 3) 4) 5) 6) 7) 8) No. Contents of display Buffer memory address to reference (decimal) The temperature detection value of each channel is displayed as a graph., 2) The specified conversion enabled/disabled status for each channel is displayed. 3) The status of the Conversion Complete flag for each channel is displayed. 35 4) The specified status for the averaging processing/sampling processing of each channel is displayed. The specified status for the averaging processing of each channel is 5) displayed. A "!" is displayed when a watchdog timer error occurs. 6) A "!" is displayed when a writing data error occurs; the channel where it occurred and the error code are displayed. 7) 8) The specified status of the platinum temperature sensor that is used is displayed. For AS62RD3 A "!" is displayed in a channel where a broken wire was detected. For AS62RD4 A "!" is displayed in CH when a broken wire is detected in any channel
146 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.9 AS63DA module monitor 2.9. Operation monitor 2) 3) 4) 5) 6) 7) 8) 9) ) 2) No. Contents of display Buffer memory address to reference (decimal) The specified conversion enabled/disabled status for each channel is displayed. 2) The Conversion Completed flag status for channels and 2 is displayed. 5 3) 4) 5) 6) 7) 8) 9) The specified status for the averaging processing/sampling processing of channels and 2 is displayed. The specified status for the averaging processing of channels and 2 is displayed. The values set for the time and number of times for averaging processing of channels and 2 is displayed. The current output value, a value between to 4 for the digital output value of channels and 2, is displayed as a percentage ranging from to %. (Resolution selection: 2: to 8, 3: to 2) The upper limit of the digital value following D/A conversion with channel 3 is displayed. The lower limit of the digital value following D/A conversion with channel 3 is displayed. The set value of the digital value following D/A conversion with channel 3 is displayed. ) The digital value of channel 3 calculated by simple loop control is displayed. 3 The error code is displayed when a writing data error occurs. 6 2) The set resolution selection is displayed. 4 2, 3,
147 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Simple loop monitor 4) 5) 2) 3) 6) 7) 8) No. Contents of display Buffer memory address to reference (decimal) The specified simple loop control execution enabled/disabled status is displayed. 2) The control mode set status is displayed. 6 3) The set value of the simple loop control constant is displayed. 7, 8, 9 4) 5) 6) The set values of channel coordinates that were set in each point are displayed. The set values of channel 3 coordinates that were set in each point are displayed. The number of coordinate points of the simple loop control that was set is displayed. 8 to 37 7) The error code is displayed when a writing data error occurs. 6 8) The set resolution selection is displayed
148 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-23
149 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2. AS64DA module monitor 2.. Operation monitor 2) 3) 4) 5) 6) 7) No. 2) 3) 4) Contents of display The specified conversion enabled/disabled status of each channel is displayed. The specified status for the averaging processing/sampling processing of each channel is displayed. The specified status for the averaging processing of each channel is displayed. The values set for the time and number of times for averaging processing of each channel is displayed. Buffer memory address to reference (decimal) 2 to 5 5) The current output value, a value between to 4 for the digital output value of each channel, is displayed as a percentage ranging from to %. to 3 (Resolution selection: 2: to 8, 3: to 2) 6) The error code is displayed when a writing data error occurs. 8 7) The set resolution selection is displayed
150 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2..2 I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-25
151 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2..3 Graph monitor 2) 2) 3) 4) No. 2) Contents of display The current output value, a value between to 4 for the digital output value of each channel, is displayed in a graph as a percentage ranging from to %. (Resolution selection: 2: to 8, 3: to 2) The set resolution selection is displayed. : /4 2: /8 3: /2 Buffer memory address to reference (decimal) to 3 3) A "!" is displayed when a writing data error occurs. 4) A "!" is displayed when a watchdog timer error occurs
152 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2. A68AD module monitor 2.. Operation monitor 2) 5) 3) 4) 6) No. 2) 3) 4) 5) Contents of display The specified status for the averaging processing/sampling processing of each channel is displayed. The specified status for the averaging processing of each channel is displayed. The values set for the time and number of times for averaging processing of each channel is displayed. The current output value, a value between to 2 for the digital output value of each channel, is displayed as a percentage ranging from to %. The number of channels that are used is displayed. (With A68AD-S2 monitoring, the display value is invalid.) Buffer memory address to reference (decimal) 2 to 9 to 7 6) The error code is displayed when a writing data error occurs
153 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2..2 I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-28
154 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2..3 Graph monitor 2) No. Contents of display The current output value, a value between to 2 for the digital output value of each channel, is displayed in a graph as a percentage ranging from to %. Buffer memory address to reference (decimal) to 7 2) A "!" is displayed when a watchdog timer error occurs. 2-29
155 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.2 AS68AD module monitor 2.2. Operation monitor 2) 3) 4) 5) 6) 7) No. Contents of display Buffer memory address to reference (decimal) The A/D conversion enabled/disabled status of each channel is displayed. 2) 3) The specified status for the averaging processing/sampling processing of each channel is displayed. The specified status for the averaging processing of each channel (Time/count) is displayed. 4) The A/D Conversion Complete flag status for each channel is displayed. 28 5) 6) The values set for the time and count of times for averaging processing of each channel is displayed. The current output value, a value between to 2 for the digital output value of each channel, is displayed as a percentage ranging from to %. 2 2 to 7 2 to 27 7) The error code is displayed when a writing data error occurs. 2-3
156 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-3
157 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor 2) No. Contents of display The current output value, a value between to 2 for the digital output value of each channel, is displayed in a graph as a percentage ranging from to %. Buffer memory address to reference (decimal) 2 to 27 2) A "!" is displayed when a watchdog timer error occurs. 2-32
158 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.3 A68ADN module monitor 2.3. Operation monitor 2) 3) 4) 5) 6) 7) No. 2) 3) 4) 5) Contents of display The specified conversion enabled/disabled status of each channel is displayed. The specified status for the averaging processing/sampling processing of each channel is displayed. The specified status for the averaging processing of each channel is displayed. The values set for the time and count of times for averaging processing of each channel is displayed. The current output value, a value between to 4 for the digital output value of each channel, is displayed as a percentage ranging from to %. (Resolution selection: 2: to 8, 3: to 2) Buffer memory address to reference (decimal) 2 to 9 to 7 6) The error code is displayed when a writing data error occurs. 8 7) The resolution selection that was set is displayed
159 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-34
160 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor 2) 3) 4) No. 2) Contents of display The current output value, a value between to 4 for the digital output value of each channel, is displayed as a percentage ranging from to %. (Resolution selection: 2: to 8, 3: to 2) The set resolution selection is displayed. : /4 2: /8 3: /2 Buffer memory address to reference (decimal) to 7 3) A "!" is displayed when a writing data error occurs. 4) A "!" is displayed when a watchdog timer error occurs
161 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.4 A68RD module monitor 2.4. Operation monitor 2) 3) 4) 5) 6) 7) 8) 9) ) No. 2) 3) 4) Contents of display The temperature detection value of each channel is displayed up to digit after the decimal point. The temperature detection value of each channel is displayed up to 3 digits after the decimal point. The values set for the time and count of times for averaging processing of each channel is displayed. The specified conversion enabled/disabled status of each channel is displayed. Buffer memory address to reference (decimal) to 7 8 to 33 5) The conversion complete flag status for each channel is displayed. 35 6) 7) The specified status for the averaging processing/sampling processing of each channel is displayed. The specified status for the averaging processing of each channel is displayed. A "!" is displayed when a watchdog timer error occurs. 8) A "!" is displayed when a writing data error occurs; the channel where it occurred and the error code are displayed. 9) ) The specified status of the platinum temperature sensor that is used is displayed. For A68RD3 A "!" is displayed in a channel where a broken wire was detected. For A68RD4 A "!" is displayed in CH when a broken wire is detected in any channel. 2 to
162 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-37
163 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor 2) 3) 4) 5) 6) 7) 8) No. Contents of display Buffer memory address to reference (decimal) The temperature detection value of each channel is displayed in a graph. to 7 2) The specified conversion enabled/disabled status of each channel is displayed. 3) The conversion complete flag status for each channel is displayed ) 5) The specified status for the averaging processing/sampling processing of each channel is displayed. The specified status for the averaging processing of each channel is displayed. A "!" is displayed when a watchdog timer error occurs. 6) A "!" is displayed when a writing data error occurs; the channel where it occurred and the error code are displayed. 7) 8) The specified status of the platinum temperature sensor that is used is displayed. For A68RD3 A "!" is displayed in a channel where a broken wire was detected. For A68RD4 A "!" is displayed in CH when a broken wire is detected in any channel
164 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.5 AS68DAI, AS68DAV module monitor The contents displayed on each monitor of the AS68DAI module and AS68DAV module are nearly identical, except for the sections displaying the module format. The AS68DAV module monitor screen is used as an example in each of the following sections Operation monitor 2) 3) 4) No. Contents of display Buffer memory address to reference (decimal) The analog output enabled/disabled status for each channel is displayed. 2) 3) 4) For AS68DAI: The present input value, a value between to 4 for the digital input value of each channel, is displayed as a percentage ranging from to %. For AS68DAV: The present input value, a value between -2 to 2 for the digital input value of each channel, is displayed as a percentage ranging from to %. When the digital input value set for each channel is greater than the allowable value, "" is displayed. When the digital input value set for each channel is less than the allowable value, "" is displayed. to 8 to 7 to
165 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-4
166 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor 2) 3) No. Contents of display For AS68DAI: The present input value, a value between to 4 for the digital input value of each channel, is displayed in a graph as a percentage ranging from to %. For AS68DAV: The present input value, a value between -2 to 2 for the digital input value of each channel, is displayed in a graph as a percentage ranging from to %. Buffer memory address to reference (decimal) 2) The analog output enabled/disabled status for each channel is displayed. A "!" is displayed when a watchdog timer error occurs. 3) When the digital input value set for each channel is greater than/ less than the allowable value, a "!" is displayed. to 8 to 7 2-4
167 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.6 A66AD module monitor 2.6. Operation monitor 4) 2) 5) 3) 6) 7) No. 2) 3) Contents of display The specified conversion enabled/disabled status of each channel is displayed. The set status of the data format for each channel is displayed. : Data format : Data format The current output value, a value between to 4 for the digital output value of each channel, is displayed as a percentage ranging from to %. Buffer memory address to reference (hexadecimal) 4) The error code is displayed when an error occurs. 5 5) The set value of the sampling period is displayed. 3 6) The channels where direct access occurs are displayed. 7) The current output value, a value between to 4 for the digital output value for each channel where direct access occurs, is displayed as a percentage ranging from to %. F 4 3 to 3F
168 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Operation monitor (connect No. to connect No. 7 when multiplex module is used) 2) 3) 5) 6) 7) 4) 8) 9) No. Contents of display Buffer memory address to reference (hexadecimal) The connect number of the monitor being used is displayed. 2) 3) 4) The specified conversion enabled/disabled status of each channel is displayed. The set status of the data format for each channel is displayed. : Data format : Data format The current output value, a value between to 4 for the digital output value of each channel, is displayed as a percentage ranging from to %. to 7 4 to 7F 5) The error code is displayed when an error occurs. 5 6) "" is displayed when an error with error code to 3 occurs for any channel. 7) The set value of the sampling period is displayed. 3 8) The channels where direct access occurs are displayed. 9) The current output value, a value between to 4 for the digital output value for each channel where direct access occurs, is displayed as a percentage ranging from to %
169 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-44
170 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor 2) 3) No. 2) Contents of display The current output value, a value between to 4 for the digital output value of each channel, is displayed as a percentage ranging from to %. A "!" is displayed when watchdog timer error occurs. A "!" is displayed when an error occurs. Buffer memory address to reference (hexadecimal) 3 to 3F The set status of the data format for each channel is displayed. 4 3) The specified conversion enabled/disabled status of each channel is displayed. F 2-45
171 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor (connect No. to connect No. 7 when multiplex module is used) 2) 3) 4) No. Contents of display Buffer memory address to reference (hexadecimal) The connect number of the monitor being used is displayed. 2) 3) The current output value, a value between to 4 for the digital output value of each channel, is displayed in a graph as a percentage ranging from to %. A "!" is displayed when watchdog timer error occurs. A "!" is displayed when an error occurs. to 7F The set status of the data format for each channel is displayed. 4 4) The specified conversion enabled/disabled status of each channel is displayed. to
172 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.7 A66DAI, A66DAV module monitor The contents displayed on each monitor of the A66DAI module and A66DAV module are nearly identical, except for the sections displaying the module format. The A66DAI module monitor screen is used as an example in each of the following sections Operation monitor 3) 4) 2) No. 2) 3) 4) Contents of display Buffer memory address to referende (hexadecimal) The set D/A conversion enabled/disabled status for each channel is displayed. The set analog output enabled/disabled status for each channel is displayed. The current input value, a value between to 4 for the digital input value of each channel, is displayed as a percentage ranging from to %. When the digital input value for any channel is set to 496 or higher, "" is displayed in the over error column. For A66DAI: When the digital input value for any channel is set as a negative number, "" is displayed in the under error column. For A66DAV: When the digital input value for any channel is set to 497 or less, "" is displayed in the under error column. to F 3 to 3F 3 to 3F 2-47
173 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-48
174 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor 2) 3) No. 2) 3) Contents of display The current input value, a value between to 4 for the digital input value of each channel, is displayed in a graph as a percentage ranging from to %. Buffer memory address to reference (hexadecimal) to F The set D/A conversion enabled/disabled status for each channel is displayed. The set analog output enabled/disabled status for each channel is displayed. A "!" is displayed when a watchdog timer error occurs. For A66DAI: A "!" is displayed when the digital input value of any channel is set to 496 or higher, or to a negative number. For A66DAV: A "!" is displayed when the digital input value of any channel is set to 496 or higher, or to -497 or lower. 2-49
175 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.8 A66TD module monitor 2.8. Operation monitor (INPUT -F) 3) 4) 2) 5) 6) 6) 7) 8) 9) No. Contents of display The specified D/A conversion enabled/disabled status for each channel is displayed. Buffer memory address to reference (hexadecimal) 2) The set status of the data format for each channel is displayed. 3) An error code is displayed when an error occurs. 4) "" is displayed for CNT No. when an error with error code to 4 has occurred due to a malfunction of the A6MXT unit or a setting error. 5) "" is displayed for the sampling period current value. 4 6) 7) 8) 9) For a channel not connected to the A6MX, the current output value, a value between to 4 for the digital output of that channel, is displayed as a percentage ranging from to %. When a channel is connected to the A6MX, the above is displayed for the digital output value for CH of A6MX. When the A6MXT is used, "!" is displayed when a temperature was input that exceeds the temperature range set according to the digital output value set for each channel. When the A6MXT is used, "!" is displayed when a temperature was input that exceeds the measurement temperature range set for the measurement range of each channel. When the A6MXT is used, "!" is displayed when broken wire is detected in the thermocouple or the compensating lead wire. F 2 7 to 7F 2-5
176 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Operation monitor (connect No. to connect No. 7 when multiplex module is used) 2) 3) 5) 6) 7) 8) 4) 9) ) No. Contents of display Buffer memory address to reference (hexadecimal) The connect number of the monitor being used is displayed. 2) The specified conversion enabled/disabled status for each channel is displayed. to 7 3) The set status of the data format for each channel is displayed. : Data format : Data format ) The current output value, a value between to 4 for the digital output value of each channel, is displayed as a percentage ranging from to %. 8 to FF 5) When the A6MXT is used, "" is displayed when a temperature was input that exceeds the temperature range set according to the digital output value 5 to 57 set for each channel. 6) When the A6MXT is used, "" is displayed when a temperature was input that exceeds the measurement temperature range set for the measurement 6 to 67 range of each channel. 7) When the A6MXT is used, "" is displayed when broken wire is detected in the thermocouple or the compensating lead wire. 4 to 47 8) When the A6MXT is used, the set status of the broken wire detection for the thermocouple that is connected to each channel is displayed. 2 to 27 : Broken wire detection disabled : Broken wire detection enabled 9) ) When the A6MXT is used, the temperature detection value of each channel is displayed. The set temperature value (when the digital value is or 4) of the channel to which the A6MXT being monitored is connected is displayed. 2 to 27F 3 to 3F A "!" is displayed when an error occurs. 2-5
177 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-52
178 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Setting monitor (when A6MXT is used) 2) 3) 4) No. Contents of display The set value corresponding to the thermocouple used in each channel is displayed only in the column of the the CNT No. to which the A6MXT is connected. The types of thermocouples that correspond to the set values are indicated below. Buffer memory address to reference (hexadecimal) Type of thermocouple Set value Rating to 7F 2) JIS K J E R T B S ANSI K J E R T B S BS DIN NiCr -NiAl NiCr -Ni Fe -CuNi NiCr -CuNi PtRh3 -Pt Cu -CuNi PtRh3 -PtRh6 PtRh -Pt PtRh -Pt Fe -CuNi Cu -CuNi The error correction value of each channel is displayed only in the column of the CNT No. to which the A6MXT is connected. 8 to FF 3) The error code is displayed when an error occurs. 4) The connect number and channel are displayed when an error occurs in the thermocouple type setting
179 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Temperature monitor (connect No. to connect No. 7 when A6MXT is used) 2) 4) 3) No. Contents of display Buffer memory address to reference (hexadecimal) The connect number of the monitor being used is displayed. 2) The temperature detection value for each channel is graphically displayed. 2 to 27F The set status of the data format for each channel is displayed. 3) The specified conversion enabled/disabled status for each channel is displayed. to 7 A "!" is displayed when a watchdog timer error occurs. A "!" is displayed when an error occurs. 4) A "!" is displayed when a temperature was input that exceeds the measurement temperature range set for the measurement range of each channel. 2-54
180 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor (INPUT -F) 2) 3) No. 2) Contents of display For a channel not connected to the A6MX, the current output value, a value between to 4 for the digital output of that channel, is displayed as a percentage ranging from to %. When a channel is connected to the A6MX, the above is displayed for the digital output value for CH of A6MX. A "!" is displayed when a watchdog timer error occurs. A "!" is displayed when an error occurs. When the A6MXT is used, "!" is displayed when a temperature was input that exceeds the temperature range set according to the digital output value set for each channel. When the A6MXT is used, "!" is displayed when a temperature was input that exceeds the measurement temperature range set for the measurement range of each channel. Buffer memory address to reference (hexadecimal) 7 to 7F The set status of the data format for each channel is displayed. 3) The specified conversion enabled/disabled status for each channel is displayed. F 2-55
181 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Graph monitor (connect No. to connect No. 7 when multiplex module is used) 3) 2) 4) 5) No. Contents of display Buffer memory address to reference (hexadecimal) The connect number of the monitor being used is displayed. 2) 3) The current output value, a value between to 4 for the digital output value of each channel, is displayed in a graph as a percentage ranging from to %. When the A6MXT is used, the temperature detection value of each channel is displayed. A "!" is displayed when a watchdog timer error occurs. A "!" is displayed when an error occurs. 8 to FF 2 to 27F When the A6MXT is used, "" is displayed when a temperature was input that exceeds the temperature range set according to the digital output value 4) set for each channel. When the A6MXT is used, "" is displayed when a temperature was input that exceeds the measurement temperature range set for the measurement range of each channel. The set status of the data format for each channel is displayed. 5) The specified conversion enabled/disabled status for each channel is to 7 displayed. 2-56
182 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.9 AD7, ASD7 module monitor The contents displayed on each monitor of the AD7 module and ASD7 module are nearly identical, except for the sections displaying the module format. The AD7 module monitor screen is used as an example in each of the following sections Positioning and parameter data monitor 2) 3) 4) 5) 6) 7) 8) 9) ) 3) 4) 5) 6) 7) 8) 9) 2) 2 22) 23) 24) 2) No. 2) 3) 4) Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. The calculated command pulse number (PLS) based on the command value is displayed. The actual amount of servo movement (feedback pulse number) (PLS) calculated from the feedback pulse is displayed. The difference between the command pulse number x CMS/CDV and the feedback pulse number (PLS) is displayed. Buffer memory address to reference (decimal), 2, 3 6, 7 5) The set value of positioning address P (PLS) is displayed. 6, 62 6) The set value of positioning address P2 (PLS) is displayed. 65, 66 7) The set value of positioning velocity V is displayed. 63, 64 8) The set value of positioning velocity V2 is displayed. 67, 68 9) ) The set status of the positioning pattern is displayed. : Positioning : 2-speed trapezoid positioning The status of the control mode when changing modes from velocity to position control is displayed. : Positioning control in progress : Velocity control in progress
183 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN No. 2) Contents of display The error code is displayed when an error occurs that can be handled by a sequence program such as a startup data error or BUSY in progress. The error code is displayed when an error occurs that causes monitoring to stop due to an external signal when starting or when a startup is in progress. Buffer memory address to reference (decimal) 3) The change value (PLS) of the current value is displayed. 8, 8 4) The change value (PLS) of the speed/position/travel distance is displayed. 88, 89 5) The change value of the velocity change is displayed. 82, 83 6) The set value of the JOG velocity is displayed. 84, 85 7) The set value (PLS) of the upper stroke limit is displayed., 8) The set value (PLS) of the lower stroke limit is displayed. 2, 3 9) The command pulse ratio numerator (CMX) and denominator (CDV) are displayed. 2) The set value of the velocity limit is displayed. 2, 2 2 The set value of the acceleration time is displayed ) The set value of the deceleration time is displayed ) The set value (PLS) of the in-position range is displayed ) The set status of the positioning mode is displayed. : Positioning : Velocity positioning 4 5 4,
184 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Zero return monitor 2) 3) 4) 5) 6) 7) 8) 9) 3) 4) 5) 6) 7) 8) ) 9) 2) 2 2) No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. Buffer memory address to reference (decimal) 2) The calculated command pulse number (PLS) based on the command value is displayed., 3) 4) The actual amount of servo movement (feedback pulse number) (PLS) calculated from the feedback pulse is displayed. The difference between the command pulse number x CMS/CDV and the feedback pulse number (PLS) is displayed , 3 6, 7 5) The set value of positioning address P (PLS) is displayed. 6, 62 6) The set value of positioning address P2 (PLS) is displayed. 65, 66 7) The set value of positioning velocity V is displayed. 63, 64 8) The set value of positioning velocity V2 is displayed. 67, 68 9) The set status of the positioning pattern is displayed. : Positioning : 2-speed trapezoid positioning 6 ) The status of the control mode when changing modes from velocity to position control is displayed. : Positioning control in progress : Velocity control in progress The error code is displayed when an error occurs that can be handled by a sequence program such as a data error or BUSY in progress. 4 2) The error code is displayed when an error occurs that causes monitoring to stop due to an external signal when starting or when a startup is in progress. 3) The change value (PLS) of the current value is displayed. 8, 8 4) The change value (PLS) of the speed/position/travel distance is displayed. 88, 89 5) The change value of the speed change is displayed. 82, 83 6) The set value of JOG speed is displayed. 84, 85 7) After zero return starts, the travel distance (PLS) from when the near zero point signal goes on until zero return is complete is displayed. 8, 9 8) The set value (PLS) of the travel distance after the near zero point signal goes on is displayed. 46, 47 9) The set value (PLS) of the zero address is displayed. 4, 4 2) The set value of the zero return velocity is displayed. 42, 43 2 The set value of the creep velocity is displayed. 44, 45 5
185 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O Monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-6
186 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.2 A7D module monitor 2.2. Positioning monitor 2) 3) 4) 5) 6) 7) 8) 9) 5) 6) 7) 8) 9) 2) 2 22) 23) 24) 25) ) 2) 3) 4) No. 2) 3) 4) Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. The calculated command pulse number (PLS) based on the command value is displayed. The actual amount of servo movement (feedback pulse number) (PLS) calculated from the feedback pulse is displayed. The difference between the command pulse number x CMS/CDV and the feedback pulse number (PLS) is displayed. Buffer memory address to reference (decimal), 2, 3 4, 5 5) The set value of positioning address P (PLS) is displayed. 6, 62 6) The set value of positioning address P2 (PLS) is displayed. 65, 66 7) The set value of positioning velocity V is displayed. 63, 64 8) The set value of positioning velocity V2 is displayed. 67, 68 9) ) The set status of the positioning pattern is displayed. : Positioning : 2-speed trapezoid positioning The status of the control mode when changing modes from velocity to position control is displayed. : Positioning control in progress : Velocity control in progress This displays whether the torque command (electrical current command) for the motor is controlled by the rated torque written in the motor catalog x the "torque limit value". : When motor is rotating within set torque limit : Limited
187 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN No. 2) 3) 4) Contents of display The error code is displayed when an error occurs that can be handled by a sequence program such as a data error or BUSY in progress. The error code is displayed when an error occurs that causes monitoring to stop due to an external signal when starting or when a startup is in progress. The error code output from the servo amp that was converted into an error code for AD7D is displayed. Buffer memory address to reference (decimal) 5) The change value (PLS) of the current value is displayed. 8, 8 6) The change value (PLS) of the speed/position/travel distance is displayed. 86, 87 7) The change value of the velocity change is displayed. 82, 83 8) The set value of the JOG velocity is displayed. 84, 85 9) The change value of the torque limit is displayed. 89 2) The actual number of revolutions of the motor is displayed. 2 The motor current is displayed as % of the rated current. 22) The data for monitoring the load of the regeneration resistance is displayed. 2 23) The maximum torque is displayed when it is % of the rated torque. 3 Valid when using peripheral equipment (SW GP-AD7DP). Bit Servo Not in Test mode Ready test normal 24) OFF mode 25 Contents of display Servo Ready ON The set status of the AD7D slide switch is displayed. Test mode request error Test mode in progress Bit SW8 SW7 SW6 SW5 SW4 SW3 SW2 SW "OFF" "OFF" "OFF" "OFF" "OFF" "OFF" "OFF" "OFF" 25) 26 Contents of display SW8 "ON" SW7 "ON" SW6 "ON" SW5 "ON" SW4 "ON" SW3 "ON" SW2 "ON" SW "ON"
188 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Zero return monitor 2) 3) 4) 5) 6) 7) 8) 9) ) 6) 7) 8) 9) 2) 2 22) 23) 24) 25) 26) 2) 3) 4) 5) No. 2) 3) 4) Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. The calculated command pulse number (PLS) based on the command value is displayed. The actual amount of servo movement (feedback pulse number) (PLS) calculated from the feedback pulse is displayed. The difference between the command pulse number x CMS/CDV and the feedback pulse number (PLS) is displayed. Buffer memory address to reference (decimal), 2, 3 4, 5 5) The set value (PLS) of the zero address is displayed. 3, 3 6) The set value of the zero return velocity is displayed. 32, 33 7) The set value of the creep velocity is displayed. 34, 35 8) 9) ) After zero return starts, the near zero point signal goes off, decelerates and stops. The travel distance (PLS) from that point until zero return is complete is displayed. After zero return starts, the travel distance (PLS) from when the near zero point signal goes on until zero return is complete is displayed. The set value (PLS) of the travel distance after the near zero point signal goes ON is displayed. The status of the control mode when changing modes from velocity to position control is displayed. : Positioning control in progress : Velocity control in progress 8, 9 6, 7 36,
189 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN No. 2) 3) 4) 5) Contents of display This displays whether the torque command (electrical current command) for the motor is controlled by the rated torque written in the motor catalog x the "torque limit value". : When motor is rotating within set torque limit : Limited The error code is displayed when an error occurs that can be handled by a sequence program such as a data error or BUSY in progress. The error code is displayed when an error occurs that causes monitoring to stop due to an external signal when starting or when a startup is in progress. The error code output from the servo amp that was converted into an error code for AD7D is displayed. Buffer memory address to reference (decimal) 6) The change value (PLS) of the current value is displayed. 8, 8 7) The change value (PLS) of the speed/position/travel distance is displayed. 86, 87 8) The change value of the velocity change is displayed. 82, 83 9) The set value of the JOG velocity is displayed. 84, 85 2) The change value of the torque limit is displayed The actual number of revolutions of the motor is displayed. 22) The motor current is displayed as % of the rated current. 23) The data for monitoring the load of the regeneration resistance is displayed. 2 24) The maximum torque is displayed when it is % of the rated torque. 3 Valid when using peripheral equipment (SW GP-AD7DP). Bit Servo Not in Test mode test ready OFF normal 25) mode 25 Contents of display Servo ready ON The set status of the AD7D slide switch is displayed. Test mode request error Test mode in progress Bit ) Contents of display SW8 "OFF" SW8 "ON" SW7 "OFF" SW7 "ON" SW6 "OFF" SW6 "ON" SW5 "OFF" SW5 "ON" SW4 "OFF" SW4 "ON" SW3 "OFF" SW3 "ON" SW2 "OFF" SW2 "ON" SW "OFF" SW "ON"
190 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Parameter data monitor 2) 3) 3) 4) 4) 5) 5) 6) 6) 7) 8) 9) ) 2) 7) 8) 9) 2) 2 22) 23) No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is on when displayed in a reverse display. Buffer memory address to reference (decimal) 2) The set value (PLS) of the upper stroke limit is displayed., 3) The set value (PLS) of the lower stroke limit is displayed. 2, 3 4) The command pulse ratio numerator (CMX) and denominator (CDV) are displayed. 4, 5 5) 6) 7) The set status of the system is displayed. : MR-SB (standard) : MR-SB (absolute values) The set status of the regeneration resistance is displayed. : None : RB3 2: RB5,5 3: RB, The set status of the motor type is displayed. : Standard : Low inertia L 2: Flat U 8) The motor output capacity is displayed. 3 9) The set status of the motor rpm is displayed. 4 ) The set value of the position loop gain is displayed. 5 The set value of the velocity loop gain is displayed. 6 2) The set value of the velocity integration is displayed. 7 3) The set value of the in-position range is displayed. 8 4) The feedback pulse number (PLS) of one revolution of the motor is displayed. 9 5) The set status of the direction of rotation is displayed. : Counter-clockwise with address increase : Clockwise with address increase 6) The set value of the torque limit is displayed. 2 7) The set value of the velocity limit is displayed. 4,
191 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN No. Contents of display Buffer memory address to reference (decimal) 8) The set value of the acceleration time is displayed. 42 9) The set value of the deceleration time is displayed. 43 2) The set status of the positioning mode is displayed. : Positioning mode : Velocity position control change mode 2 The servo amp model code and version are displayed. 4 to 7 Valid when using peripheral instrument (SW GP-AD7DP) Bit Servo Not in Test mode test ready OFF normal 22) mode 25 Contents of display Servo ready ON The set status of the AD7D slide switch is displayed. Test mode request error Test mode in progress Bit ) Contents of display SW8 "OFF" SW8 "ON" SW7 "OFF" SW7 "ON" SW6 "OFF" SW6 "ON" SW5 "OFF" SW5 "ON" SW4 "OFF" SW4 "ON" SW3 "OFF" SW3 "ON" SW2 "OFF" SW2 "ON" SW "OFF" SW "ON"
192 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-67
193 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.2 AD7 Module monitor 2.2. Positioning monitor 3) 4) 5) 6) 7) 8) 9) ) 2) 2) 3) 4) 5) No. Contents of display Buffer memory address to reference (decimal) X axis Y axis The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2) The set manual pulser run enabled/disabled status is displayed ) The data number during execution of current positioning is displayed ) The remaining pointer value is displayed ) The current value during execution of current positioning is displayed. 6) The change value of the current value is displayed. 7) The zero address set value is displayed ) The set value of the output speed is displayed ) The set value of the speed limit is displayed ) The change value of the speed change is displayed The set value of the jog speed is displayed ) The set value of the jog speed limit is displayed ) The set value of the M code is displayed. : M code not used ) The error code is displayed when an error occurs ) The starting data number of each point is displayed. to 37 3 to
194 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Zero return monitor 3) 4) 5) 6) 7) 8) 9) ) 2) 5) 5) 6) 7) 2) 3) 4) No. Contents of display Buffer memory address to reference (decimal) X axis Y axis The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2) The set manual pulser run enabled/disabled status is displayed ) The data number during execution of current positioning is displayed ) The remaining pointer value is displayed ) The current value during execution of current positioning is displayed ) The change value of the current value is displayed ) The zero address set value is displayed ) The set value of the output speed is displayed ) The set value of the speed limit is displayed ) The change value of the speed change is displayed The set value of the zero return speed is displayed ) The set value of the zero return creep speed is displayed ) The set value of the M code is displayed. : M code not used ) The error code is displayed when an error occurs The zero return data is displayed. 5) b5 b4 b Method where return is complete when stopper stops. Zero return direction Zero return method ) The set value of the torque limit is displayed ) The set value of the dwell time is displayed
195 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Parameter data monitor 9) ) 3) 4) 5) 6) 7) 8) 2) 3) 6) 6) 2) 4) 5) No. Contents of display Buffer memory address to reference (decimal) X axis Y axis The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed.the I/O signal is ON when displayed in a reverse display. 2) The set manual pulser run enabled/disabled status is displayed ) The set value of the travel distance per pulse is displayed ) The set value of the travel distance per pulse using the manual pulser is displayed ) The set value of the speed limit is displayed ) The set value of the jog speed limit is displayed ) The set value of the acceleration/deceleration time is displayed ) The set value of the backlash compensation amount is displayed ) The set value of the upper stroke limit is displayed. ) The set value of the lower stroke limit is displayed. The set value of the error compensation amount is displayed ) The set value of the starting bias speed is displayed ) The set value of the positioning complete signal output time is displayed ) The set value of the M code is displayed ) The error code is displayed when an error occurs ) The set status of the parameter data is displayed
196 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN M code comment monitor 3) 5) 6) 7) 4) 8) 2) No. Contents of display Buffer memory address to reference (decimal) X axis Y axis The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2) The set manual pulser run enabled/disabled status is displayed ) The set value of the M code is displayed ) The set value of the comment for the M code is displayed. 49 to to 5 5) The data number during execution of current positioning is displayed ) The remaining pointer value is displayed ) The error code is displayed when an error occurs The 8 bits where the status is saved are displayed in hexadecimal format. When "FF" is displayed b5 b 8) "" display conditions "" display conditions Battery alarm Zero return request During dwell time During positioning busy status (except for zero return, jog run, Not condition at left manual pulser run) Zero return complete Near signal on Drive module ready signal on Stop signal from drive module on
197 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-72
198 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Positioning data monitor The positioning Data Monitor Screen No. is used as an example. 2) 3) 4) 5) No. Contents of display Buffer memory address to reference (decimal) X axis Y axis The set value of the positioning address for each data number is displayed. 572 to to 7 2) The set value of the positioning speed for each data number is displayed to to 629 3) The set value of the dwell time for each data number is displayed to to 669 4) The set value of the M code for each data number is displayed to to 589 The 4 bits where the set status of the positioning pattern, the positioning method, and the positioning direction for each data number is stored are displayed in hexadecimal format. When "F" is displayed b5 b 5) 3)2) M code housed Positioning pattern : Positioning complete : Positioning continues : Speed changes and positioning continues 2)Positioning method : Absolute : Incremental 3)Positioning direction (only valid in incremental mode) : Forward direction (address increase direction) : Reverse direction (address decrease direction) 3872 to to
199 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.22 AD72, ASD7 module monitor The contents displayed on each monitor of the AD72 module and the ASD7 module are nearly identical, except for the sections displaying the module format. The AD72 module monitor screen is used as an example in each of the following sections Positioning monitor 3) 4) 5) 6) 7) 8) 9) ) 2) 2) 3) 4) 5) No. Contents of display Buffer memory address to reference (decimal) X axis Y axis The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2) The set manual pulser run enabled/disabled status is displayed ) The data number during execution of current positioning is displayed ) The remaining pointer value is displayed ) The current value during execution of current positioning is displayed ) The change value of the current value is displayed ) The zero address set value is displayed ) The set value of the output speed is displayed ) The set value of the speed limit is displayed ) The change value of the speed change is displayed The set value of the jog speed is displayed ) The set value of the jog speed limit is displayed ) The set value of the M code is displayed. : M code not used ) The error code is displayed when an error occurs ) The starting data number of each point is displayed. to 37 3 to
200 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Zero return monitor 3) 4) 5) 6) 7) 8) 9) ) 2) 5) 5) 6) 7) 2) 3) 4) No. Contents of display 2-75 Buffer memory address to reference (decimal) X axis Y axis The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2) The set manual pulser run enabled/disabled status is displayed ) The data number during execution of current positioning is displayed ) The remaining pointer value is displayed ) The current value during execution of current positioning is displayed ) The change value of the current value is displayed ) The zero address set value is displayed ) The set value of the output speed is displayed ) The set value of the speed limit is displayed ) The change value of the speed change is displayed The set value of the zero return speed is displayed ) The set value of the zero return creep speed is displayed ) The set value of the M code is displayed. : M code not used ) The error code is displayed when an error occurs The zero return data is displayed. Method where return is complete when stopper stops 5) b5 b4 b Method where return is complete when stopper stops. Zero return direction Zero return method ) The set value of the torque limit is displayed ) The set value of the dwell time is displayed
201 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Parameter data monitor 3) 4) 5) 6) 7) 8) 6) 6) 9) ) 2) 3) 2) 4) 5) No. Contents of display Buffer memory address to reference (decimal) X axis Y axis The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2) The set manual pulser run enabled/disabled status is displayed ) The set value of the travel distance per pulse is displayed ) The set value of the travel distance per pulse using the manual pulser is displayed ) The set value of the speed limit is displayed ) The set value of the jog speed limit is displayed ) The set value of the acceleration/deceleration time is displayed ) The set value of the backlash compensation amount is displayed ) The set value of the upper stroke limit is displayed. ) The set value of the lower stroke limit is displayed. The set value of the error compensation amount is displayed ) The set value of the starting bias speed is displayed ) The set value of the positioning complete signal output time is displayed ) The set value of the M code is displayed. : M code not used ) The error code is displayed when an error occurs ) The set status of the parameter data is displayed
202 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN M code comment monitor 3) 5) 6) 7) 4) 8) 2) No. Contents of display Buffer memory address to reference (decimal) X axis Y axis The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2) The set manual pulser run enabled/disabled status is displayed ) The set value of the M code is displayed ) The set value of the comment for the M code is displayed. 49 to to 5 5) The data number during execution of current positioning is displayed ) The remaining pointer value is displayed ) The error code is displayed when an error occurs The 8 bits where the status is saved are displayed in hexadecimal format. When "FF" is displayed b5 b 8) "" display conditions "" display conditions Battery alarm Zero return request During dwell time During positioning busy status (except for zero return, jog run, Not condition at left manual pulser run) Zero return complete Near signal on Drive module ready signal on Stop signal from drive module on
203 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-78
204 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Positioning data monitor The Positioning Data Monitor Screen No. is used as an example. 2) 3) 4) 5) No. Contents of display Buffer memory address to reference (decimal) X axis Y axis The set value of the positioning address for each data number is displayed. 572 to to 7 2) The set value of positioning speed for each data number is displayed to to 629 3) The set value of the dwell time for each data number is displayed to to 669 4) The set value of the M code for each data number is displayed to to 589 The 4 bits where the set status of the positioning pattern, the positioning method, and the positioning direction for each data number is stored are displayed in hexadecimal format. When "F" is displayed b5 b 3)2) M code housed 5) Positioning pattern : Positioning complete : Positioning continues : Speed changes and positioning continues 2) Positioning method : Absolute : Incremental 3) Positioning direction (only valid in incremental mode) : Forward direction (address increase direction) : Reverse direction (address decrease direction) 3872 to to
205 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.23 AD75, ASD75 module monitor I/O monitor The contents displayed on each monitor of the AD75P (P2, P3) module and the ASD75P (P2, P3) module are nearly identical, except for the sections displaying the module format. The AD75P3 module monitor screen is used as an example in this section. No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The I/O signal is ON when displayed in a reverse display. 2-8
206 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Operation monitor 2) 3) 4) 5) 6) 7) 8) 9) ) No. Contents of display The feed current value is displayed. 2) The axis speed is displayed. Buffer memory address to reference (decimal) Axis Axis 2 Axis ) The axis operation status is displayed ) The axis error No. is displayed when an axis error occurs ) The axis warning No. is displayed when an axis warning occurs ) 7) The M code (valid M code) that is set in the data during positioning is displayed. Positioning data No. during positioning is displayed. (The actual data No. is also displayed when specified indirectly.) The positioning identifier of the positioning data during positioning is displayed ) 9) ) Bit 5 to 9) ) 3 to 8) Operation pattern Acceleration time no. Deceleration time no. Data control method
207 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Basic parameter monitor ( Basic parameter 2) 3) 4) 5) 6) No. Contents of display Buffer memory address to reference (decimal) Axis Axis 2 Axis 3 The command module for positioning control is displayed ) The pulse number per revolution of the motor determined by the machine system is displayed ) The travel distance per revolution of the motor determined by the machine system is displayed ) The multiplier of the travel distance per pulse is displayed ) The pulse output mode is displayed ) The direction of rotation when the current value is increased is displayed
208 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN (2) Basic parameter 2 2) 3) No. 2) 3) Contents of display The maximum speed for the positioning operation (also including zero return) and the manual pulser operation is displayed. With the positioning operation, the acceleration time from speed until the speed limit has been attained is displayed. With the positioning operation, the deceleration time from the speed limit to speed is displayed. Buffer memory address to reference (decimal) Axis Axis 2 Axis
209 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Extended parameter monitor ( Extended parameter 2) 3) 4) 5) 6) No. 2) 3) 4) 5) Contents of display The machine backlash compensation amount when the positioning direction changes is displayed. The upper limit of the range that the machine can travel is displayed. (Software stroke upper limit) The lower limit of the range that the machine can travel is displayed. (Software stroke lower limit) This shows whether the software stroke limit is applied to the feed current value or the feed machine value. Check the feed current value with the operation monitor (Sec Check the feed machine value with the target value and the machine value monitor (Sec ). This shows whether the software stroke limit for the jog operation and the manual pulser operation is enabled/disabled. Buffer memory address to reference (decimal) Axis Axis 2 Axis ) The torque limit is displayed
210 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN (2) Extended parameter 2 2) No. 2) Contents of display With the positioning operation, acceleration time through acceleration time 3 from speed until the speed limit is attained is displayed. With the positioning operation, deceleration time through deceleration time 3 from the speed limit to speed is displayed. Buffer memory address to reference (decimal) Axis Axis 2 Axis 3 36 to 4 86 to to to to to
211 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Zero return parameter monitor ( Basic parameters for zero return 2) 3) 4) 5) 6) No. Contents of display Buffer memory address to reference (decimal) Axis Axis 2 Axis 3 The zero return method is displayed ) The zero return direction is displayed. Forward: address increase direction Reverse: address decrease direction ) The zero address that is set when the zero return is complete is displayed. 4) The maximum speed for the zero return is displayed. 5) 6) The creep speed after the near signal turns on is displayed. (speed before zero return is complete) This indicates whether or not to retry the zero return with the zero return retry function
212 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN (2) Detailed parameters for origin return 2) 3) 4) 5) 6) No. 2) 3) 4) 5) 6) Contents of display The time from when the proximity dog goes ON to when the origin point return is completed is displayed. (for stopper stop The restriction value used to limit the torque of the servomotor after reaching the creeping speed is displayed. The amount of movement after the proximity dog goes ON is displayed. (for count equation) The display shows which acceleration time, to 3 (basically, this is set using the detailed parameters) is to be used as the acceleration time when making an origin point return. The display shows which deceleration time, to 3 (basically, this is set using the detailed parameters) is to be used as the deceleration time when making an origin point return. The shift amount (amount of movement) for an origin point shift is displayed. Buffer memory address to reference (decimal) Axis Axis 2 Axis
213 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring the error history and warning history 2) No. 2) Contents of display The error history is displayed. Axis : No. of axis on which error occurred Code : Code for error which occurred (decimal) Time : Time at which error occurred The warning history is displayed. Axis : No. of axis on which warning occurred Code : Code for warning which occurred (decimal) Time : Time at which warning occurred Buffer memory address to reference (decimal) Axis Axis 2 Axis to 687 (624, 628 ) (625, 629 ) (626, 63 ) 689 to 752 (689, 693 ) (69, 694 ) (69, 695 ) 2-88
214 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring the error termporary startup history and startup history 2) No. 2) Contents of display The error startup history is displayed. Axis : Startup axis no. Startup source : Source which initiates startup (* : PLC CPU (Y) : External signal : Peripheral equipment (AD75P) Type of operation : Type of operation at startup (*2) If restarting from a stopped status, "Re" is displayed just before this. Time : Startup time (hour: minutes: seconds: milliseconds) Judgment : Error code when startup error occurred (decimal) The numeric values of the least significant 4 bits of the buffer memory are displayed. The startup history is displayed. (The contents of the display are the same as in.) Axis : Startup axis no. Startup source : Source which initiates startup (* Type of operation : Type of operation at startup (*2) Time : Startup time (hour: minutes: seconds: milliseconds) Judgment : Error code when startup error occurred (decimal) 2-89 Buffer memory address to reference (decimal) Axis Axis 2 Axis to 622 (543, 548 ) (544, 549 ) (544, 549 ) (545! 546, 55! 55 ) (547, 552 ) 462 to 54 (462, 467 ) (463, 468 ) (463, 468 ) (464! 465, 469! 47 ) (466, 47 )
215 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN * The display is based on the data in Bits 3 and 4 of the object buffer memory. *2 The correspondence between the numeric value displayed in the "Operation Type" column and the type of startup is shown below. The display is based on the data in Bits to 2 of the object buffer memory. Data no. Type of startup Remarks to 6 Startup with positioning operation 7 Startup with block positioning operation 85 Startup with origin point return 852 Startup with high-speed origin point return 853 Startup with change in current value 86 Startup with jogging operation 86 Startup with manual pulser operation Indicates the data number at the time of startup Items with the "Re" prefix are displayed based on the data of Bit 5 of the object buffer memory. 2-9
216 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring Speed/Position Control 2) 3) 4) 5) No. 2) 3) 4) 5) Contents of display The address (amount of movement) for position control in speed/position changing control is displayed. The changed value is displayed when the position control address (amount of movement) in the speed control function is changed in speed/position changing control. The ON/OFF status of the speed/position changing latch flag (the flag indicating the control status) is displayed. (The status of Bit of the pertinent buffer memory is displayed.) " : Position control in progress #: Speed control in progress/positioning is in progress in another control method or operation method (such as jogging) This displays whether control switching in response to an external signal is effective or not in speed/position changing control. : Switching is permitted : Switching is not permitted The ON/OFF status flag during speed control (the flag indicating the control status) is displayed. (The status of Bit of the pertinent buffer memory is displayed.) " : Speed control in progress #: Position control in progress/positioning is in progress in another control method or operation method (such as jogging) Buffer memory address to reference (decimal) Axis Axis 2 Axis
217 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring special startup, jogging, and manual pulser operation 2) 3) 4) No. Contents of display The information for the special startup currently in progress is displayed. Operation : Startup data pointer Information : Command code of the special startup data specified by the startup data pointer Parameter : Parameters for the special startup data specified by the startup data pointer Data No. : Positioning data number specified by the startup data pointer 2) The jogging speed used during jogging operation is displayed. 3) 4) The input magnification per one pulse from the manual pulser is displayed. The display shows whether or not manual pulser operation is permitted. Buffer memory address to reference (decimal) Axis Axis 2 Axis
218 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring an origin point return 2) 3) 4) 5) 6) 7) No. 2) Contents of display The address of the origin point set when an origin point return is completed is displayed. The amount of movement after the proximity dog goes ON is displayed. Buffer memory address to reference (decimal) Axis Axis 2 Axis ) The torque limit value is displayed ) 5) 6) 7) The ON/OFF status of the external I/O signal corresponding to the signal name displayed on the screen is displayed.! :OFF " :ON Bit 5 to Zero point signal Proximity signal Upper limit Lower limit
219 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring axis control data 2) 3) 4) 5) 6) 7) No. Contents of display The value for the current value change is displayed. 2) The speed change value is displayed. 3) 4) 5) 6) 7) The override value in relation to the positioning speed is displayed. The ON/OFF status for the flag indicating whether step action is effective is displayed; this flag confirms the actions of the various positioning data in the step function. : Step effective (step action is carried out) : Step invalid (step action is not carried out) This displays the module to be used for step action in operation based on the step function. : Step action in data number modules : Step action in reduced-speed modules The ON/OFF status of the skip command is displayed. : Request for skip in progress : Request for skip has been completed/no request The display shows whether control based on an external startup signal is effective or invalid. : External startup effective : External startup invalid Buffer memory address to reference (decimal) Axis Axis 2 Axis
220 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring the output speed 2) 3) No. 2) Contents of display When positioning, the actual speed, taking the override and the speed limit value into consideration, is displayed. When using interpolation operation, the target speeds for the composite speed/reference axis speed are displayed on the reference axis side, and "" is displayed on the other axis side. When using jogging operation, the actual speed taking the jogging speed limit value into consideration is displayed. The speed set for the positioning data is displayed. When using interpolation operation, the target speeds for the composite speed/reference axis speed are displayed on the reference axis side, and "" is displayed on the other axis side. 3) The actual positioning speed is displayed. Buffer memory address to reference (decimal) Axis Axis 2 Axis
221 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring the target values and machine values 2) No. 2) Contents of display The object values when using positioning based on position control are displayed. (With ABS:adress/With INC:amount of movement) When using speed/position changing control, the amount of movement following a change to position control is displayed. The individual position determined by the machine is used as the machine origin point, and the current machine feed value (position)is displayed. Buffer memory address to reference (decimal) Axis Axis 2 Axis
222 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring external I/O signals and status signals (flags) 2) No. Contents of display The ON/OFF status for the external I/O signal corresponding to the signal name shown on the screen is displayed.! : OFF " : ON Buffer memory address to reference (decimal) Axis Axis 2 Axis 3 Bit 5 to Deviation counter Speed/position Drive module ready Change External startup Lower limit Upper limit Zero point Imposition Proximity point Stop The ON/OFF status for the various flags corresponding to the flag shown on the screen is displayed.! : OFF " : ON Bit 5 to 2 9 to ) Absolute origin point position Underflow Overflow Speed change Axis warning detection Speed control in progress Speed/position change Command imposition Request for origin point return Origin point return completed
223 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring positioning information 2) 3) No. 2) 3) Contents of display The positioning data corresponding to the data number and data name shown on the screen for Axis is displayed. Pattern : This is displayed based on Bits to of the applicable buffer memory address. Control method : Acceleration : Deceleration : Address : Arc address : Specified speed : Dwell time : M code : The positioning data corresponding to the data number and data name shown on the screen for Axis 2 is displayed. Pattern : (The contents of the display are the same as for.) Address : Arc address : Dwell time : M code : The positioning data corresponding to the data number and data name shown on the screen for Axis 3 is displayed. Pattern : (The contents of the display are the same as for.) Address : Arc address : Dwell time : M code : Buffer memory address to reference (decimal) 3 to 2299 (3, 3 ) (3, 3 ) (3, 3 ) (3, 3 ) (36. 37, ) (38. 39, ) (34, 34 ) (32, 32 ) (3, 3 ) 23 to 3299 (23, 23 ) ( , ) ( , ) (232, 232 ) (23, 23 ) 33 to 4299 (33, 33 ) ( , ) ( , ) (332, 332 ) (33, 33 ) 2-98
224 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.24 AJ7PT32-S3 and ASJ7PT32-S3 module monitor The contents displayed on the monitor screens of the AJ7PT32-S3 and ASJ7PT32-S3 modules are the same, except for the section where the module model name is displayed. In this section, we will look at the monitor screens for the AJ7PT32-S I/O monitor (I/O mode) No. Contents of display The ON/OFF status of the I/O signal corresponding to the PLC CPU of the master module is displayed. The I/O signal is ON when displayed in a reversed display. 2-99
225 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring the link status 4) 2) 5) 6) 7) 3) 8) No. Contents of display Buffer memory address to reference (decimal) The total number of remote stations connected is displayed. 2) This shows whether the station number of the connected remote module is for input or output. 7 to 77 3) A "" is displayed for the remote terminal module number where the error has occurred. 95 When an error occurs in link communications, the communications error code is displayed. 4) : No error : Initial data error 7 2: Ladder error 3: Erroneous station issued 4: Separate refresh type remote I/O module error 5) A communications error has occurred, and a "" is displayed for the station number of the remote module. The detection status is maintained until the error is reset. 9 to 93 6) A communications error has occurred, and a "" is displayed for the station number of the remote module. If the automatic recovery function is on, a "" is displayed when to 3 normal communications have been resumed. 7) A "" is displayed for the station number of a separate refresh type remote I/O module where the input information could not be read out within a given time period. The 598 detection status is maintained until the error is reset. 8) A "" is displayed for the station number of a separate refresh type remote I/O module where the input information could not be read out within a given time period. If the automatic recovery function is on, a "" is displayed when the station is able to read the input normally
226 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring batch refreshing 2) No. 2) Contents of display The output status for the batch refresh type remote I/O module is displayed. : OFF : ON The input status for the batch refresh type remote I/O module is displayed. : OFF : ON Buffer memory address to reference (decimal) to 4 to 4 2 -
227 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring separate refreshing As a screen example, we will store the monitor screens from the split refresh monitors (numbers to 8) in the memory. 2) No. 2) Contents of display The output status for the separate refresh type remote I/O module is displayed. : OFF : ON Output statuses are displayed in the following order for each of the station numbers. (2nd digit) (st digit) (4th digit) (3rd digit) The input status for the separate refresh type remote I/O module is displayed. : OFF : ON Input statuses are displayed in the following order for each of the station numbers. (2nd digit) (st digit) (4th digit) (3rd digit) Buffer memory address to reference (decimal) 3 to to
228 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring input and output (expansion mode) No. Contents of display The ON/OFF status for the I/O signal corresponding to the PLC CPU of the master module is displayed. An I/O signal is ON when it is displayed in a reverse display. 2-3
229 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.25 AJ7ID (ID2)-R4 and ASJ7ID (ID2)-R4 module monitor Action monitor (CH and CH 2) No. Contents of display The contents of the data storage area are displayed in address modules. (The illustration above shows the results when the CH side is monitored.) (Addresses are displayed in decimal format and data in hexadecimal format.) Buffer memory address to reference (decimal) CH CH2 4 to 63 to
230 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status for the I/O signal corresponding to the PLC CPU is displayed. An I/O signal is ON when it is displayed in a reverse display. 2-5
231 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring set information 2) 3) 4) 5) 6) 7) 8) Buffer memory address No. Contents of display to reference (decimal) CH CH2 The output command for the data carrier is displayed. 4 The first address for the data carrier which is reading and writing the data is displayed, 4 2) along with the number of processing points for the data being read and written ) The number of retries when a data communications error occurs is displayed The number of communications (accumulated number of times) for the data carrier is ) displayed (exclusing the CM, CL, OF, and ON commands) ) The results of executing the compare command (CM) are displayed The direction in which data is copied when the copy data command (CO) is executed 6) 4 is displayed. The lighting status of the error LED is displayed. (A "!" is displayed when an error 7) 2 42 occurs.) 44 8) The error codes for the five most recent times that an error has occurred is displayed. 4 to 8 to
232 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN 2.26 A84AD module monitor Action monitor 2) 3) 4) 5) 6) 9) 7) 8) No. Contents of display Buffer memory address to reference (decimal) The current I/O data, a value between to or to 2 for the digital I/O value of the various channels, is displayed as a percentage ranging from to %, in the to 3 corresponding module code column. 2) The temperature detection values for the various channels are displayed. 8 to 2 3) The codes for installed modules for the various channels are displayed. 28 to 3 If the digital values for the various channels have been set to values larger than the 4) maximum value for the various modules, a "" is displayed in the "Output Over" 22 to 25 column. If the digital values for the various channels have been set to values smaller than the 5) maximum value for the various modules, a "" is displayed in the "Output Under" 22 to 25 column. 6) If an error occurs in the data being written, the channel on which the error occurred, and the error code, are displayed. 26 The specified effective/invalid status for the analog output enable signal for each of 7) the channels is displayed. 27 : Effective : Invalid The specified status for the output enable command of each of the channels is 8) displayed. : The offset value is output as an analog value. : The analog value following D/A conversion is output. 9) A "!" is displayed when a watchdog timer error occurs. A "!" is displayed when an error occurs in a module on the various channels. 2-7
233 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Setting monitor 2) 3) 4) 5) No. 2) 3) 4) 5) Contents of display The specified status for the averaging processing/sampling processing of each of the channels is displayed. The specified status for the averaging processing of each of the channels is displayed. The values set for the time and number of times for averaging processing of each of the channels is displayed. When a temperature sensor input module is installed, the offset values for each of the channels is displayed. When a temperature sensor input module is installed, the gain values for each of the channels is displayed. Buffer memory address to reference (decimal) 2 to 5 32,34,36,38 33,35,37,39 2-8
234 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN I/O monitor No. Contents of display The ON/OFF status for the I/O signal corresponding to the PLC CPU is displayed. An I/O signal is ON when it is displayed in a reverse display. 2-9
235 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Monitoring graphs 3) 2) 4) 5) No. Contents of display Buffer memory address to reference (decimal) The current I/O value, a value between to or to 2 for the digital I/O value of the various channels, is displayed as a percentage ranging from to %. to 3 2) The temperature detection values for the various channels are displayed. 8 to 2 3) The module codes for installed modules for the various channels are displayed. 28 to 3 The specified effective/invalid status for the analog output enable signal for each of the channels is displayed. 27 : Effective : Invalid 4) The specified status for the output enable command of each of the channels is displayed. : The offset value is output as an analog value. : The analog value following D/A conversion is output. 9) A "!" is displayed when a watchdog timer error occurs. A "!" is displayed when an error occurs in a module on the various channels. 2 -
236 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN AS64TCTT(BW)-S and AS64TCRT(BW)-S module monitor Operation monitor 2) 3) 4) 5) 6) 7) 8) No. Contents of display Buffer memory address to reference (hexadecimal) CH CH2 CH3 CH4 The type of the thermocouple connected to each channel is displayed ) The temperature measurement unit set for each channel is displayed The decimal position information of the temperature measurement value, goal value, and warning setting value for the input range and temperature measurement unit setting are displayed. Display When reading from PLC CPU When writing from PLC CPU 3) Use the data from buffer Write the value to be specified When memory as is. directly as is. When Use the /th of the data read as actual value. Write the value to be specified as times the value. 4) 5) 6) 7) 8) The measured temperature (PV value) detected for each channel is displayed. In the decimal point position = column, the value of the detected measured temperature is displayed as is. In the decimal point position = column, the value /th of the detected measured temperature is displayed. The goal value (SV value) set for each channel is displayed. In the decimal point position = column, the value of the set goal value is displayed as is. In the decimal point position = column, the /th of the set goal value is displayed. The PID-calculated values (-5.% to 5.%) of the temperature values read from the thermocouple of each is displayed in the graph. A "!" is displayed when a warning is indicated in each channel. The details of the warning can be verified in the warning occurrence details monitor screen. A "!" is displayed when out-of-range data is stored in the temperature adjustment module buffer memory. 9 A B C D E F 2 -
237 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Alert detail monitor No. Contents of display A "!" is displayed in the column corresponding to the warning details detected for each channel. Buffer memory address to reference (hexadecimal) CH CH2 CH3 CH
238 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN Operation monitor (CH to CH4) 4) 8) 5) 2) 7) ) 3) 6) 9) 2) 3) 4) 5) 8) 9) 6) 7) No. Contents of display Buffer memory address to reference (hexadecimal) CH CH2 CH3 CH4 The type of the thermocouple connected to each channel is displayed ) The temperature measurement unit set for each channel is displayed The decimal position information of the temperature measurement value, goal value, and warning setting value for the input range and temperature measurement unit setting are displayed. Display When reading from PLC CPU When writing from PLC CPU 3) Use the data from buffer Write the value to be specified When memory as is. directly as is. When Use the /th of the data read as actual value. Write the value to be specified as times the value. 4) 5) 6) The measured temperature (PV value) detected for each channel is displayed. In the decimal point position = column, the value of the detected measured temperature is displayed as is. In the decimal point position = column, the value /th of the detected measured temperature is displayed. The goal value (SV value) set for each channel is displayed. In the decimal point position = column, the value of the set goal value is displayed as is. In the decimal point position = column, the /th of the set goal value is displayed. The PID-calculated values (-5.% to 5.%) of the temperature values read from the thermocouple of each is displayed in the graph. 9 A B C D E F 2-3
239 2. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN No. Contents of display Buffer memory address to reference (hexadecimal) CH CH2 CH3 CH4 7) The ratio range (P) which is set in the PID constant setting of each channel is displayed. When, the 2-position control is set ) 9) ) 2) 3) 4) 5) The integral time (I), set in the PID constant setting of each channel is displayed The derivative time (D), set in the PID constant setting of each channel is displayed When, the PI control is set. A "!" is displayed when out-of-range data is stored in the temperature adjustment module buffer memory. The buffer memory address for which an error was detected during the performance of a write to the temperature adjustment module buffer memory is displayed. The details of the error detected during the performance of a write to the temperature adjustment module buffer memory is displayed. The temperatures for which the warning alarms to 4 set for each 26 to to to to 89 channel turns on are displayed. The warning mode of warning alarm to 4 set for each channel are displayed. A to A3 The current sensors connected to each channel are displayed. : When using CTL-2-S36-8 : When using CTL-6-P (When using AS64TCRTBW-S or AS64TCTTBW-S 6) The heater currents detected for each channel are displayed. 9 A B C 7) The standard heater current values set for each channel are displayed. AB AC AD AE 8) The upper/lower limits for when the movement value (MV) which are 2A 4A 6A 8A calculated with the PID calculation set for each channel is outputted to 2B 4B 6B 8B the external device are displayed. 9) A "!" is displayed when a warning occurs for each channel. 2-4
240 3. OPERATING I/O MODULE MONITOR SCREENS Chapter3 Operating I/O module monitor screens This section explains how the various screens are operated in the special module monitor function, when monitoring input or output modules. 3. Specifying the module to be monitored This describes how to start monitoring an optional special input or output module. [Operation procedure] Display the System Configuration screen.!!!!!!! See Sec Specify the module to be monitored (Touch the position at which the module is displayed.) ( Of the modules installed in Slot to Slot 7 of the base unit, specify a module for which "Input" or "Output" is displayed. For information on specifying special function modules, please see Sec Display the monitor screen for the specified module. " # 2 " 3 " 4 " 5 # 6 # 7 # 8 # 9 " A " B " C # D # E # F # X MODULE " " 2 " 3 " 4 # 5 # 6 # 7 # 8 " 9 " A " B " C # D # E # F # 2 " 2 " 22 " 23 " 24 # 25 # 26 # 27 # 28 # 29 # 2A # 2B # 2C # 2D # 2E # 2F # sys. conf. X " X END 3 " 3 # 32 " 33 " 34 " 35 # 36 # 37 # 38 # 39 " 3A " 3B " 3C # 3D # 3E # 3F # (2) For information on confirming the displayed contents and subsequent operation, please see Sec * Tests cannot be conducted on input or output modules. 3 To Sec
241 3. OPERATING I/O MODULE MONITOR SCREENS 3.2 Monitor screen configuration and key functions This section describes the configuration of monitor screens displayed by specifying the input module on the system configuration screen, and explains the functions of the keys displayed on the screen. ( Display (for an input module) 2) 3) A B C D E F " # " " " ## # # " " " ## # # X MODULE A B C D E F A 2B 2C 2D 2E 2F sys. conf A 3B 3C 3D 3E 3F END X " X Displays the statuses of input and output " " " " ## # # " " " " ## # # " " " " ## # # # # # # # # # # " # " " " ## # # " " " ## # # 4) signals after being read out from the corresponding module. (OS executes it automatically.) Statuses for up to 64 can be displayed. Signal statuses: # : ON ": OFF Displays the type of the object module (input or output module). 2) Displays the name of the signal being monitored (X or Y). 3) Displays the number and status of the input or output signal. 4) Displays keys that are used with the operation of the monitor screen shown in (2) (Touch input). (2) Key functions The chart below shows the functions of the keys that are used with the Monitor Screen operation. Key END sys. conf. Function Monitoring ends; and display returns to the screen where the special module monitor function was begun. The current monitoring ends; and returns to the system configuration screen. 3-2
242 4. ERROR DISPLAY AND HANDLING WITH SPECIAL MODULE MONITORING Chapter4 Error display and handling with special module monitoring The following chart shows the error messages that may be displayed when operating the special module monitor and the method of handling them. Error message Description Method of Handling Can not Communication Communication could not be established with the PLC CPU. ( To try the operation again, touch "Retry". When the operation is retried, the error message disappears and monitoring resumes automatically, so no action is required. If monitoring is not resumed for a long period of time, however, check the following: Connections between the PLC CPU and the GOT (disconnected or cut cables). 2) Has an error occurred in the PLC CPU? Etc
243 4. ERROR DISPLAY AND HANDLING WITH SPECIAL MODULE MONITORING MEMO 4-2
244 5. OPERATING THE NETWORK MONITOR FUNCTION Chapter5 Operating the network monitor function This chapter describes how to operate the network monitor function. 5. Steps in getting started with the network monitor function The following flowchart outlines how to transmit and install an operating system (OS) for the network monitor function in the GOT internal memory using the Personal computer. For further information on screen displays and key operations, see the online help of the drawing software. Start Connect the GOT and the Personal computer.!!!!! The GOT does not require further setup procedures or operations after the startup. Start up the GOT. Start up the Personal computer and start the drawing software. With the drawing software, transmit the OS for the network monitor function from the Personal computer to the GOT and install it in the built-in memory.!!!!! Transmit the data in the installation dialog box. 5 After the installation is finished, the network monitor is ready to start through the GOT.!!!!! After the installation is complete, a message indicating "End" appears in the installation dialog box. Finish operating the drawing software. Exit.!!!!! Proceed to Section 5.2 to operate the network monitor. 5 -
245 5. OPERATING THE NETWORK MONITOR FUNCTION 5.2 Steps in starting the network monitor function from the user-created monitor screen The following flowchart outlines how to start the network monitor function after the operating system (OS) for the network monitor has been installed in the GOT built-in internal memory. Start Install a memory board on the GOT. Start up the GOT. Go to the user-created monitor screen. Start the network monitor function.!!!!! (* Go to the own station monitor screen.!!!!! See Section 7.. Select the detailed own station monitor or other station monitor option. Go to the detailed own station monitor or other station monitor menu.!!!!! See Sections 7.2 and 7.3. * Touch the key assigned to the network monitor function (set in the touch switch expanded function of the drawing software). In the Utility Menu screen, touch NET.MON. to start the network monitor function. 5-2
246 6. SWITCHING THE NETWORK MONITOR SCREENS Chapter6 Switching the network monitor screens The following flowchart outlines the steps involved in switching the network monitor screens. Utility menu screen or user-created monitor screen (Touch a touch key for the network monitor function) Host-station monitor screen Touch a module Other station monitor menu screen (Select a module) END RET Touch a box. 6 RET (Select a box) RET (Select a menu item) Detailed own station monitor screen Other station monitor screen END END 6 -
247 6. SWITCHING THE NETWORK MONITOR SCREENS MEMO 6-2
248 7. USING THE NETWORK MONITOR SCREENS Chapter7 Using the network monitor screens This chapter describes how to use various monitor screens when you execute the network monitor function. 7. Own station monitor This section describes the structure of the monitor screen and the common operations used when executing the own station monitor. 7.. Display contents and keys functions: own station monitor This section describes the own station monitor screen and the function of on-screen keys, all of which are displayed and used when executing the network monitor function. ( Display contents When the A985/97*/96GOT is used 2) 3) When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. Touch button to change the display. (Display example) No. Contents of Display ( This shows the action mode of the own station: On-line, Off-line, loop test. (2) This shows the status of the F-loop (primary loop): OK, NG. (3) This shows the status of the R-loop (secondary loop): OK, NG. (4) This shows whether the loopback was executed or not: Executed, Not executed. (5) This shows link scan time required for the control station and the ordinary station, for the remote master station and the remote I/O station, and for the mater station and all the sub-stations. (a) Maximum (the maximum value of link scan time) (b) Minimum (the minimum value of link scan time) (c) Current (the current value of link scan time) 2) This shows the network category, network number, and station number. This shows the loop status of a network system as follows: (Primary loop: F, Secondary loop: R) (a) Primary loop : OK Secondary loop : OK (b) Primary loop : OK Secondary loop : NG (c) Primary loop : NG Secondary loop : OK 7 R F R F R F 3) (d) Executing loopback F R (e) Primary loop : NG Secondary loop : NG R F (f) MELSECNET/ coaxial bus (OK) (g) MELSECNET/ coaxial bus (NG) 7 -
249 7. USING THE NETWORK MONITOR SCREENS No. Contents of Display The following loop status in the data link system is displayed. (Primary loop: F, Subloop: R) (a) Data is linked in the Primary loop. (b) Data is linked in the subloop. (c) Loop-back is performed in the Primary/sub loop direction. F F F R R 3) R (d) Loop-back is performed in the Primary loop direction only. (e) Loop-back is performed in the sub-loop direction only. (f) Data link is not available. F F R F R R (2) Key functions This section describes the function of keys to be used on the own station monitor screen. Key Function Exits the own station monitor screen and returns to the previous monitor screen where the network monitor function was executed. Switches to the detailed monitor screen that corresponds to the module displayed on the current monitor screen. This key is effective for each screen. Switches to the other station monitor menu that corresponds to the network displayed on the current monitor screen. This key is effective for each screen. Changes the details on the window. (only for A95*GOT) 7-2
250 7. USING THE NETWORK MONITOR SCREENS 7.2 Detailed own station monitor This section describes the structure of the monitor screen and the common operations used when executing the detailed own station monitor Display contents and keys functions: acting as a MELSECNET/B or MELSECNET (II) master station This section describes the detailed own station monitor screen and the function of onscreen keys, all of which are displayed and used when the own station acts as the master station on the MELSECNET/B or MELSECNET (II). ( Display contents 2) When the A985/97*/96GOT is used 3) When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. Touch button to change the display. (Display example) No. Section Contents of Display TsSt s Info This Station s # Indicates the station number of the own station. This Station s: Indicates the category of the own station. 2) D-Link Info Total of L-Sta: Indicates the maximum number of the stations to be linked. The maximum number is defined by common parameters. 3) LoopBK Info FLoop: Shows the status of the primary loop lines of the own station. (Normal/NG) RLoop: Shows the status of the secondary loop lines of the own station. (Normal/NG) Floop Back Station: Indicates the station number of a station that executes the loopback along the primary loop. Rloop Back Station: Indicates the station number of a station that executes the loopback along the secondary loop. # of Loop Switching: Indicates the cumulative number of times for which loops have been switched. (2) Key functions The table below shows the function of keys that are used on the detailed own station monitor screen. Key Function RET Returns to the own station monitor screen. Exits the detailed own station monitor screen and returns to the END previous monitor screen where the network monitor function was executed. Changes the details on the window. (only for A95*GOT) 7-3
251 7. USING THE NETWORK MONITOR SCREENS Display contents and keys functions: acting as a MELSECNET/B or MELSECNET (II) local station This section describes the detailed own station monitor screen and the function of onscreen keys, all of which are displayed and used when the own station acts as the local station on the MELSECNET/B or MELSECNET (II). ( Display contents 2) 3) 4) When the A985/97*/96GOT is used 6) When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. Touch button to change the display. (Display example) 5) No. Section Contents of Display TsSt Info This Station s # Indicates the station number of the own station. This Station s: Indicates the category of the own station. 2) D-Link Info Total of L-Sta: Indicates the maximum number of the stations to be linked. The maximum number is defined by common parameters. 3) Com Status Com Status: Displays the communications status of the own station. (Parameter wait, Cyclic comm, NG) This shows the status of receiving Device BWY from the 4) master station. BWY From OK: Data is being received by cyclic receiving. Master NG: The own station cannot receive data because of column reading. 5) BW From Hostmaster 6) LoopBK Info This shows the status of receiving Device BW from the master station of a dual-layer system. OK: Data is being received by cyclic receiving. NG: The own station cannot receive data due to column reading. FLoop: Shows the status of the primary loop lines of the own station. (Normal/NG) RLoop: Shows the status of the secondary loop lines of the own station. (Normal/NG) (2) Key functions The table below shows the functions of keys that are used on the detailed own station monitor screen. Key RET END Function Returns to the own station monitor screen. Exits the detailed own station monitor screen and returns to the previous monitor screen where the network monitor function was executed. Changes the details on the window. (only for A95*GOT) 7-4
252 7. USING THE NETWORK MONITOR SCREENS Display contents and keys functions: acting as a MELSECNET/ Control station/ordinary Station This section describes the contents of the detailed own station monitor screen and the function of on-screen keys. All these are displayed and used when the own station acts as the control station/ordinary station on the MELSECNET/. ( Display contents 2) When the A985/97*/96GOT is used 4) 5) When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. Touch button to change the display. (Display example) 6) 3) No. Section Contents of Display TsSt Info 2) Ctrl St Info This Station s #: Indicates the station number of the own station. Network #: Indicates the network number. Group #: Indicates the group number. Spc Ctrl Sta: Indicates the station number of a station that is specified as a control station. Curr Ctrl Sta: Indicates the station number of a station that is currently acting as the control station. Com Info: Indicates whether the own station is communicating with the control station or the sub control station. SubCtrl Sta Com: Indicates the availability of a sub control station. (Available/None) Rmt I/O Mst Sta: Indicates the station number of a remote I/O master station in Block or Block 2. If the master station is not available, this indicates "None" instead. 7-5
253 7. USING THE NETWORK MONITOR SCREENS No. Section Contents of Display 3) D-Link Info 4) Constant LS 5) LoopBK Info Total of L-Sta: Indicates the maximum number of the stations to be linked. The maximum number is defined by common parameters. Largest Nrm Sta: Indicates the station number of the largest station that is connected in a normal condition. Largest DL-Sta: Indicates the station number of the largest station that is datalinked. Com Status: Show the current communications status of the own station. (D Link in prog, D Link Stop (A), D Link Stop (H), B Pass excut, Disconnection, Testing, Reset. in prgr.) Causes of Ssp: Indicates the causes why the communications were interrupted. This indicates "OK" if communications is in a normal condition. (Normal, Offline, Offline Test, Others (error codes)) Causes of Stop: Indicates the causes why the data link was stopped. This indicate "OK" if the data link is in a normal condition. (No common para, Host Para error, Instructed by Other Station (n station), Essential Parameter Not Matched, Instructed by Host Station, Improper I/O Allocation, Instructed by All Stations (n stations), Others (error codes)) Constant LS: Indicates the predetermined time of constant link scans. FLoop: Shows the status of the primary loop lines of the own station. (Normal/LoopBK Trans/D-Link Impo) RLoop: Shows the status of the secondary loop lines of the own station. (Normal/LoopBK Trans/D-Link Impo) FLoop Back Station: Indicates the station number of a station that executes the loopback along the primary loop. RLoop Back Station: Indicates the station number of a station that executes the loopback along the secondary loop. # of Loop Switching: Indicates the cumulative number of times for which loops have been switched. * "---" is displayed when coaxial bus connections are established. 7-6
254 7. USING THE NETWORK MONITOR SCREENS No. Section Contents of Display 6) TsSt Sta Parameter Setting: Common Param, Common + Spec if, Default Param, Default + Specif Reserved Sta: Indicates the availability of a reserved station. (Have/None) Communication Mode: Indicates either of "Normal mode" or "Constant LS." Transmission Mode: Indicates either of "Normal Trans" or "Multipl Trans." * Transmission Stat: Indicates either of "Normal Trans" or Multipl Trans." * * "---" is displayed when coaxial bus connections are established. (2) Key functions The table below shows the function of keys that are used on the detailed own station monitor screen. Key RET END Function Returns to the own station monitor screen. Exits the detailed own station monitor screen and returns to the previous monitor screen where the network monitor function was executed. Changes the details on the window. (only for A95*GOT) 7-7
255 7. USING THE NETWORK MONITOR SCREENS Display contents and keys functions: acting as a MELSECNET/ remote master station This section describes the detailed own station monitor screen and the function of onscreen keys, all of which are displayed and used when the own station acts as the remote master station on the MELSECNET/. ( Display contents 2) When the A985/97*/96GOT is used 4) 5) When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. Touch button to change the display. (Display example) 6) 3) No. Section Contents of Display TsSt Info 2) Ctrl St Info This Stations #: Indicates the station number of the own station. Network #: Indicates the network number. Group #: Not displayed. Spc Ctrl Sta: Not displayed Curr Ctrl Sta: Not displayed Com Info: Not displayed SubCtrl-Sta Com: Not displayed 7-8
256 7. USING THE NETWORK MONITOR SCREENS No. Section Contents of Display 3) D-Link Info 4) Constant LS 5) LoopBK Info Total of L-Sta: Indicates the maximum number of the stations to be linked. The maximum number is defined by common parameters. Largest Nrm Sta: Indicates the station number of the largest station that is connected in a normal condition. Largest DL-Sta: Indicates the station number of the largest station that is data-linked. Com Status: Show the current communications status of the own station. (D Link in prog, D Link Stop (A), D Link Stop (H), B Pass excut, Disconnection, Testing, Reset. in prgr.) Causes of Ssp: Indicates the reason why the communications were interrupted. This indicates "OK" if communications is in a normal condition. (Normal, Offline, Offline Test, Others (error codes)) Causes of Stop: Indicates the causes why the data link was stopped. This indicates "OK" if the data link is in a normal condition. (No common para, Host Para error, Instructed by Other Station (n station), Essential Parameter Not Matched, Instructed by Host Station, Improper I/O Allocation, Instructed by All Stations (n stations), Others (error codes)) Constant LS: Indicates the predetermined time of constant link scans. FLoop: Shows the status of the primary loop lines of the own station. (Normal/LoopBK Trans/D-Link Impo) RLoop: Shows the status of the secondary loop lines of the own station. (Normal/LoopBK Trans/D-Link Impo) FLoop Back Station: Indicates the station number of a station that executes the loopback along the primary loop. RLoop Back Station: Indicates the station number of a station that executes the loopback along the secondary loop. # of Loop Switching: Indicates the cumulative number of times for which loops have been switched. * "---" is displayed when coaxial bus connections are established. 7-9
257 7. USING THE NETWORK MONITOR SCREENS No. Section Contents of Display 6) TsSt Sta Parameter Setting: Not displayed. Reserved Sta: Indicates the availability of a reserved station. (Have/None) Communication Mode: Indicates either of "Normal mode" or "Constant LS." Transmission Mode: Indicates either of " Normal Trans " or " Multipl trans." * Transmission Stat: Indicates either of " Normal Trans " or Multipl trans." * * "---" is displayed when coaxial bus connections are established. (2) Key functions The table below shows the function of keys that are used on the detailed own station monitor screen. Key RET END Function Returns to the own station monitor screen. Exits the detailed own station monitor screen and returns to the previous monitor screen where the network monitor function was executed. Changes the details on the window. (only for A95*GOT) 7 -
258 7. USING THE NETWORK MONITOR SCREENS 7.3 Other station monitor This section describes the structure of the monitor screen and the common operations used when executing the other station monitor Display contents and keys functions: other station monitor menu This section describes the other station monitor menu screen and the function of onscreen keys. The menu screen for the other station monitor is displayed by touching a module number displayed on the own station monitor screen. The menu screen provides many options for the other station monitor. ( Display contents 2) When the A985/97*/96GOT is used 3) 4) When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. (Display example) 5) 6) No. Touch Key Contents of Display Communications Status Switches to a monitor screen that shows the communications status of other stations. * 2) Data Link Switches to a monitor screen that shows the data link status of other stations. * 3) Parameters Switches to a monitor screen that shows the parameter status of other stations. * 4) CPU Action Switches to a monitor screen that shows the CPU action status of other stations. 5) CPU RUN Switches to a monitor screen that shows the CPU RUN status of other stations. 6) Loop Switches to a monitor screen that shows the loop status of other stations. * This is not selectable when connected to a MELSECNET/B or MELSECNET (II) local station. (2) Key Functions The table below shows the function of keys that are used on the other station monitor screen. Key RET END Function Switches to the other station monitor screen. Returns to the own station monitor screen. Exits the other station monitor screen and returns to the previous monitor screen where the network monitor function was executed. 7 -
259 7. USING THE NETWORK MONITOR SCREENS Display contents and keys functions: other station communication status monitor This section describes the other station communications status monitor screen and the function of on-screen keys. ( Display contents 2) When the A985/97*/96GOT is used When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. (Display example) 3) No. Contents of Display Station numbers are shown up to the maximum number of linked stations. 2) Any station in an abnormal condition is highlighted on-screen. 3) Any station specified as a reserved station is treated as a station that stays in a normal condition. (2) Key Functions The table below shows the function of keys that are used on the other station communications status monitor screen. Key RET END Function Returns to the own station monitor screen. Exits the other station communications status monitor screen and returns to the previous monitor screen where the network monitor function was executed. 7-2
260 7. USING THE NETWORK MONITOR SCREENS Display contents and keys functions: other station data link status monitor This section describes the other station data link status monitor screen and the function of on-screen keys. ( Display contents 2) When the A985/97*/96GOT is used When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. (Display example) 3) No. Contents of Display Station numbers are shown up to the maximum number of linked stations. 2) Any station that is not data-linked is highlighted on-screen. 3) Any station specified as a reserved station is treated as a station that stays in a normal condition. (2) Key Functions The table below shows the function of keys that are used on the other station data link status monitor screen. Key RET END Function Returns to the own station monitor screen. Exits the other station data link status monitor screen and returns to the previous monitor screen where the network monitor function was executed. 7-3
261 7. USING THE NETWORK MONITOR SCREENS Display contents and keys functions: other station parameter status monitor This section describes the other station parameter status monitor screen and the function of on-screen keys. ( Display contents When the A985/97*/96GOT is used 2) 3) When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. (Display example) 4) No. Contents of Display Station numbers are shown up to the maximum number of linked stations. 2) Any station whose parameters are monitored is highlighted on-screen. * 3) Any station that stays in an abnormal condition is highlighted on-screen. A station specified as a reserved station is treated as a station that stays in a 4) normal condition. * Not highlighted when connected to a MELSECNET/B or MELSECNET (II) master station. (2) Key Functions The table below shows the function of keys that are used on the other station parameter status monitor screen. Key RET END Function Returns to the own station monitor screen. Exits the other station parameter status monitor screen and returns to the previous monitor screen where the network monitor function was executed. 7-4
262 7. USING THE NETWORK MONITOR SCREENS Display contents and keys functions: other station CPU action status monitor This section describes the other station CPU action status monitor screen and the function of on-screen keys. This option is not selectable when connecting to a remote I/O network system. ( Display contents 2) When the A985/97*/96GOT is used When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. (Display example) 3) No. Contents of Display Station numbers are shown up to the maximum number of linked stations. 2) Any station that stays in an abnormal condition or out of action is highlighted on-screen. 3) A station specified as a reserved station is treated as a station that stays in a normal condition. (2) Key Functions The table below shows the function of keys that are used on the other station CPU action status monitor screen. Key RET END Function Returns to the own station monitor screen. Exits the other station CPU action status monitor screen and returns to the previous monitor screen where the network monitor function was executed. 7-5
263 7. USING THE NETWORK MONITOR SCREENS Display contents and keys functions: other station CPU RUN status monitor This section describes the other station CPU RUN status monitor screen and the function of on-screen keys. This option is not selectable when connecting to a remote I/O network system. ( Display contents When the A985/97*/96GOT is used When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. (Display example) 2) No. Contents of Display Up to 64 station numbers are shown. 2) "---" is displayed below station numbers of reserved stations or any stations that come after the maximum number of linked stations. (2) Key Functions The table below shows the function of keys that are used on the other station CPU RUN status monitor screen. Key RET END Function Returns to the own station monitor screen. Exits the other station CPU RUN status monitor screen and returns to the previous monitor screen where the network monitor function was executed. 7-6
264 7. USING THE NETWORK MONITOR SCREENS Display contents and keys functions: other station loop status monitor This section describes the other station loop status monitor screen and the function of on-screen keys. * This option is not selectable when connecting to a MELSECNET/B or MELSECNET (II) local station or establishing MELSECNET/ coaxial bus connections. ( Display contents When the A985/97*/96GOT is used 3) 4) When the A95*GOT is used The display details are the same as the ones on the A985/97* /96GOT. (Display example) 2) No. Contents of Display The F-loop (primary loop) status and the R-loop (secondary loop status are displayed. 2) Station numbers are shown up to the maximum number of linked stations. 3) Any station that stays in an abnormal condition is highlighted on-screen. 4) A station specified as a reserved station is treated as a station that stays in a normal condition. (2) Key Functions The table below shows the function of keys that are used on the other station loop status monitor screen. Key RET END Function Returns to the own station monitor screen. Exits the other station loop status monitor screen and returns to the previous monitor screen where the network monitor function was executed. 7-7
265 7. USING THE NETWORK MONITOR SCREENS MEMO 7-8
266 8. ERROR DISPLAYS AND COUNTERMEASURES WHEN MONITORING NETWORKS Chapter8 Error Displays and Countermeasures when Monitoring Networks The following chart shows the error messages that are displayed during the network monitor operation and how to handle them. Error message Contents of error Action to take Can not Communication Key Word error Communication could not established with the PLC CPU. The PLC CPU to be connected is keywordprotected by the QnA. Check the connections between the PLC CPU and the GOT for disconnected connectors and cables. Check if an error has occurred in the PLC CPU. Release the keyword
267 8. ERROR DISPLAYS AND COUNTERMEASURES WHEN MONITORING NETWORKS MEMO 8-2
268 9. OPERATION PROCEDURES FOR THE LIST EDITOR FUNCTION Chapter9. Operation Procedures for the List editor function This section describes the operation procedures for use of list editor function. 9. Operation procedures before starting the list edit Procedures for transferring the operating system (OS) for the list editor function from the personal computer to the GOT and for installing the system into the memory. For details, refer to the Help of the drawing software. Detailed information including displays and key operations is provided. Start Connect the GOT to the personal computer. Start the GOT.... The GOT does not require setting and operation after start-up. Start the personal computer and the drawing software. Transfer the OS for the list editor function from the personal computer to the GOT. Install it into the memory.... Transfer the system in the installation dialog box. After installation, the GOT allows editing the list.... After installation, the installation dialog box shows "Completed". End the drawing software. End... For list edit, go to
269 9. OPERATION PROCEDURES FOR THE LIST EDITOR FUNCTION 9.2 Operation procedures from user-created monitor screen display to starting list editing This section explains how you should operate the GOT to access the list editor function after having installed the list editor function operating system (OS) to the GOT internal memory. Start Start up the GOT. Display the user-created monitor screen. Start the list editor function. If no keyword is stored. Is a keyword stored in the ACPU?... (The screen switches automatically after about one second.) Activate the list editor function by touching a touch key to which you have assigned this expanded function using the drawing software. If the utility menu or ladder monitor screen is displayed, touch the LIST EDITER key to activate the list editor function. If a keyword is stored: Enter the keyword stored in the connected ACPU.... See Section Keyword GO Select the list editor function mode. *** MODE SELECTION *** (READ) (INS) (PARAM) PRESS MODE KEY SHIFT *** MODE SELECTION *** (WRITE) (DEL) (OTHERS) PRESS MODE KEY READ WRITE INSERT DELETE PARAM OTHER... See Section READ MODE WRITE MODE INSERT MODE DELETE MODE PARAMATER MODE OTHER MODE... See Chapter 2. (Selection of a different mode) 9-2
270 9. OPERATION PROCEDURES FOR THE LIST EDITOR FUNCTION 9.2. Operation of keyword input If a keyword is registered in the ACPU when the connected ACPU or the ACPU PLC No. corresponding to the operation is changed, the GOT requests for input of the registered keyword. Input the keyword registered in the ACPU and press the GO key. If a keyword is not registered in the ACPU, this operation is not required. (The operation automatically changes to Selection of Function and Mode in ) * NOW READING PLC PLESE WAIT A MOMENT MOTION CONTOROLLER NOT SUPPORTED Start the list editor function. (* shows communication status with the PLC CPU.) KEYWORD= [ ] Input of the keyword is requested. 4 4 GO KEYWORD= [******] When the keyword (44 is input Input the keyword registered in the connected ACPU and press the GO key. The GOT checks the input keyword and displays the result. Input the keyword to 6 letters maximum with the device No./constant setting key. ("" to "9", "A" to "F") If an incorrect keyword is input KEYWORD= [ OK ] When the input keyword is correct To Mode Selection in The check result display time is about 2 seconds. KEYWORD= [ NG ] When the input keyword is not correct * * When the input keyword does not match with the registered keyword, only the following operations in Chapter 2 can be allowed. Other modes Error step reading Buffer memory overall monitor Time monitor PLC No. setting Main/sub switching POINTS For operations not shown in other modes, clear (delete) the registered keyword with the "PLC memory all clear" in the following page if you do not remember the keyword registered in the ACPU. When "PLC memory all clear" is performed, the user data including sequence program is also cleared. The keyword registered in the ACPU can be changed or a new keyword can be registered as shown in Chapter
271 9. OPERATION PROCEDURES FOR THE LIST EDITOR FUNCTION When input of a keyword is requested, all parameters and sequence programs can be cleared together with the keyword registered in the ACPU using the operation below. (Step Display the keyword input request. KEYWORD= [ ] (Step 2) Stop operation of ACPU A L L C L R GO (Step 3) Operation of PC memory all clear Input "ALLCLR" and press the GO key. (Step 4) Display of PC memory all clear process When the GOT starts clearing the process, the display in the left appears. "*" column and the total number of bytes change sequentially. * ALL CLEAR 2KB ********** "*" (maximum per process) is displayed according to the memory capacity to be cleared. As the clearing process proceeds, each "*" is deleted. One "*" shows % of memory capacity. The memory capacity (total number of bytes) to be cleared is displayed in kbytes. As the clearing process proceeds, kbyte is decreased. ** MODE SELECTION ** (READ) (INS) (PARAM) PRESS MODE KEY (Step 5) Completion of PC memory all clear process When the GOT completes the clearing process, the screen in the left appears. (status before the mode selection) (Step 6) Select the mode as in and start the following operation. 9-4
272 9. OPERATION PROCEDURES FOR THE LIST EDITOR FUNCTION Selection and operation of mode After the keyword input, select the mode in the list editor function for operations in Chapter 2. ( Selection and change of mode with mode key Select the mode with the mode key (Refer to ) so that operation corresponding to the mode in Chapter 2 may be performed. The mode can be freely changed when operations in Chapter 2 are performed. Various operations can be continued while changing modes. * READ Read mode WRITE Write mode INSERT Insert mode DELETE Delete mode PARAM Parameter mode OTHER Other mode * Mode key input is always valid. Input of the mode key clears the input data except for the step numbers. The display returns to the initial status of the mode selection. (2) Operation in each mode The mode selected in ( allows for operation corresponding to the mode in Chapter 2. Operation procedures of each mode are described in Chapter 2. Operate the GOT according to the description. If an error message appears during operation, take action according to Chapter
273 9. OPERATION PROCEDURES FOR THE LIST EDITOR FUNCTION MEMO 9-6
274 2. OPERATION OF EDITING SCREEN FOR EACH LIST Chapter 2. Operation of Editing Screen for Each List This section describes the operation procedures of the list edit screen. 2. Basic operation of key input After starting the list editor function, basic operations of key input are described. 2.. Switching of valid key (function indicated at the upper/lower part of the key) When the list edit has started, whether the upper or the lower key available for two purposes is valid is displayed on the second line at the left end of the display. The GOT controls and displays the valid key. A user may switch the valid key with the following keys. SHIFT * SET :Upper character key is valid. :Lower character key is valid. * The following keys can be input if the valid key is at the lower character. (Input of SHIFT key is not required.) Comparison symbol key at the command input of comparison operation instruction. <, >, = Minus key at the source data of command. - The valid key after setting each mode switches as follows: Read mode, Write mode, Insert mode Parameter mode and other modes Help of each mode : Upper character key (When the cursor position is at the setting value and the device step is in the Write mode, the "lower character" key is valid.) : Always lower character key : Always lower character key (When "Command Read" is selected from the Help in the Read mode, the upper character key is valid.) 2 When SHIFT key is input and the valid key is switched, the switched side is valid until the mode key and the control key are input. For details of each key, refer to
275 2. OPERATION OF EDITING SCREEN FOR EACH LIST 2..2 Command input procedures Command input procedures can be classified as follows: Input the command key to use the command on the key. 2) Input the alphanumeric keys corresponding to each character of command sequentially. 3) Select and input the command to be used from the Help function. Command input procedures for and 2) above are as follows. For command input procedure 3) from the Help function, refer to POINT When the command is input, the input details are displayed at the 4th line (the bottom line) on the display. In the following description, the input of SP key may be omitted when a blank space between the input command and the cursor position is automatically inserted. Refer to the example in each description. ( For command code only When the command available on the keyboard is input Command GO (Ex) When END is input W N N U K T P P 2 3 T END GO W E N N K N D P P 2 3 2) When the command not available on the keyboard is input (Ex) When FOR K5 is input W N N N U T P P P Y 2 2 SET F R SP K 5 GO W F N N K R 5 P P 2-2
276 2. OPERATION OF EDITING SCREEN FOR EACH LIST (2) For command code and device ( Command SP DEVICE DEVICE No. GO (Ex) When LD X is input W N N U K T P P 2 3 T LD X GO W L N N K D 2 3 P P X (3) For commands other than above Input the SP key between the command and the device, the source data, and the destination data. (Ex When FMOV K-2 DO K5 is input W L N N M D 5 P P M 3 F MOV K - 2 SP D SP K 5 GO W N N D K 5 P P (Ex 2) When OUT T K is input W L N N K D 2 3 P P X OUT T SP K GO W N N U K T P P T 2-3
277 2. OPERATION OF EDITING SCREEN FOR EACH LIST (Ex 3) When MC N3 M5 is input W N N U K T P P T MC N 3 SP M 5 GO W M N N C M 5 P P N 3 (Ex 4) When LD = K D is input W N N U K T P P T LD = K SP D GO W N N K D P P (Ex 5) When ANDD<=H7FFFF D2 is input W N N K D P P AND D < = H 7 F F F F SP D 2 GO W N N H D 2 P P 7 F F F F (4) Handling of devices M, L and S Devices M, L and S in the Test, Monitor, Write and Insert modes change the display depending on the set parameters. If LD L is input for the parameter setting of M to 999 and L to L247, the result is LD M. 2-4
278 2. OPERATION OF EDITING SCREEN FOR EACH LIST (5) For extension timer/extension counter of AnA and AnUCPU When the extension timer (T256 to T247) and the extension counter (C256 to C23) are input as the first device of the command, input the first device and the device number. (Ex) When OUT T256 D5 is input W L N N U D T P P M OUT T GO W N N U D T 5 P P T The device (D5) for the T256 setting value on the parameter is automatically displayed. POINT When the extension timer and the extension counter are used, be sure to set the 257 points or more and the setting value device (D, W, R) on the parameter for both the timer and the counter. 2-5
279 2. OPERATION OF EDITING SCREEN FOR EACH LIST 2..3 Action if an incorrect key is input ( Input the CLEAR key before the GO key. Then input the correct key. Input of the CLEAR key clears the command and the device number that have been input immediately. The display returns to the status (status before change in the Write mode) when the mode is selected. (2) When the GO key is input, repeat the intended operation. Command input procedures can be classified as follows: REMARK When the CLEAR key is input in the parameter mode, the GOT stops the process. To continue the operation, carry on the key input. 2-6
280 2. OPERATION OF EDITING SCREEN FOR EACH LIST Basic operation of list edit This section describes basic operations of list edit with simple operation examples Reading sequence program The sequence program is read to check its content. [Operation example] READ R E N N D N O O 2 D P P Select the "Read" mode. 2) SET GO R 2 3 L O A O D R N U I T X Y X Y Read the th step. 3) GO R O O L U U K D T T Y T T Scroll the screen with the GO key.
281 2. OPERATION OF EDITING SCREEN FOR EACH LIST Changing (overwriting) command The following example shows the changing procedure of the sequence program. Before change 3 OUT Y 4 OUT T K After change X Y X Y T K Change the timer setting value from K to K. 3 OUT Y 4 OUT T K Change the timer setting value from K to K. [Operation example] SHIFT WRITE W 7 K8 7 7 K5 D2 4 END 2) SET 4 GO W 3 OU T 4 OU T 4 K 5 LD 3) GO W 3 OU T 4 OU T 4 K K 4) K GO W 4 OU T 4 K 5 LD 6 ANI Select the "Write" mode. Y Read the 4th step that changes T the setting value. T Y Move the cursor to setting T value "K" of T. T T M The setting value of timer T was changed from "K" to "K". 2-8
282 2. OPERATION OF EDITING SCREEN FOR EACH LIST Adding (inserting) command The following example shows the procedure of adding the command to the sequence program.. Before addition 7 +P K8 K5 D2 4 END After addition 5 T M +P K8 K5 D2 MOV D2 K2Y8 Add the MOV command. 7 +P K8 K5 D2 4 MOV D2 K2Y8 9 END Add the MOV command. [Operation example] INSERT I ) SET 4 GO I 7 3) MOV D 2 SP K 2 Y 8 GO OU T T K LD T ANI M Select the "Insert" mode. D2 Read the 4th step to insert END NO P NO P the command. I D2 K2Y8 END NO P The command of "MOV D2 K2Y8" was added to Step
283 2. OPERATION OF EDITING SCREEN FOR EACH LIST Deleting command The following example shows the procedure of deleting the command from the sequence program. Before deletion 5 LD T 6 ANI M 7 +P K8 K5 D2 5 T Delete the ANI MO command. M +P K8 K5 D2 MOV D2 K2Y8 After deletion 5 LD T 7 +P K8 K5 D2 Delete the ANI MO command. [Operation example] SHIFT DELETE D D2 K2Y8 END NO P 2) SET 6 GO D 5 LD T 6 ANI M 7 + P 7 K8 3) GO D LD + P K8 K5 T Select the "Delete" mode. Read the 6th step The GO key deletes the command at the cursor position. The step number is brought forward. The "ANI MO" command was deleted. 2 -
284 2. OPERATION OF EDITING SCREEN FOR EACH LIST Using Help function HELP is input to use the Help function. Input of HELP displays the Help function menus in each mode. Select the corresponding item for execution. ( Reading the command in the sequence program Example of reading the area using the "MOV" command in the sequence program. [Operation example] READ HELP 2) 3) 2 4) MOV * * *HELP MENU*** : READ 2: COMMENT DISPLAY CLEAR:END Input the HELP key in the Read mode. * * * READ * * * / 2 Select "Read". : STEP 2: INSTRUCTION CLEAR:END HELP:MENU *** READ *** KEY IN STEP NO. [ ] CLEAR:END HELP:MENU *** READ *** KEY IN STEP NO. [ MOV ] CLEAR:END HELP:MENU 2: Select "Command". Set the "MOV" command. 5) GO R 6) GO 6 D2 3 MO V 3 D2 3 K2Y8 Reading "MOV D2 K2Y8" of the 3th step. R 6 D2 3 MO V 3 D2 Message when the "MOV" NOT FOUND command is not present after the 3th step. Now, reading the command with the Help function command specification is completed. 2 -
285 2. OPERATION OF EDITING SCREEN FOR EACH LIST (2) Displaying Kana comment The following example shows the procedure of displaying the Kana comment in the Read mode. [Operation example] HELP 2) 2 * * *HELP MENU*** : READ 2: COMMENT DISPLAY CLEAR:END * * *COMMENT DISP.*** : YES 2: NO CLEAR:END HELP:MENU Input the HELP key in the Read mode. 2: Select the Kana comment display. 3) R 2 LD OU T LD X Y 2 X Motor start limit Select ": Kana comment display". Display the Kana comment of the device at the cursor position. 4) R 2 LD OU T LD X Y2 X Motor start check 2-2
286 2. OPERATION OF EDITING SCREEN FOR EACH LIST 2.3 Operation procedure list of list edit 2.3. Common operation Basic operation Details Purpose Procedures (key input sequence) Input of keyword Input when the keyword is Keyword GO at start-up registered in the ACPU. Mode key ( READ, INSERT, PARAM ) Mode selection Select the mode. SHIFT Mode key ( WRITE, DELETE, OTHERS ) Switching of valid key Action for incorrect input Operation of command help function Switch the valid key (function indicated at the upper/lower part of the key) by a user. Perform the operation for incorrect key input. Perform operation with the Help function command specification. SHIFT or SET CLEAR, Mode key or SHIFT Perform program display HELP operation in the Write/Insert mode. GO Mode key Input the capital letter of the command. Input the capital letter of the command. Input the corresponding command number. GO Display of Comment Display the comment stored in the ACPU. Perform program display operation in the Write/Read/Insert/Delete mode. HELP 2 2 Command input operation Command code only Command code and device Other than above command key input) Other than above (device key input) Input the command code only. Input the command code and device. Input the command other than above with the command key. Input the command other than above without the command key. Command GO Command SP Device Device No. GO Input the SP between the device, the source data and the destination. Input the SP between the command, the device, the source data and the destination Operation in Write mode (W) Details Purpose Procedures (key input sequence) Program display HELP 2 in the Write mode Set the specified range in Continuous write in NOP the program to NOP. Start step specification GO Final step specification 2 Start step specification GO GO Write/modify (change) of program Write the new program/modify (change) SHIFT WRITE SET Step number GO Com mand GO 2-3
287 2. OPERATION OF EDITING SCREEN FOR EACH LIST Operation in Read mode (R) Details Purpose Procedures (key input sequence) Command reading with the specified step number Read the command of the specified step number in the program. READ SET Step number GO GO Read the command with the specified command. Read the specified command in the program. READ Command Device Device number GO GO Read the command with the specified device. Read the command with the specified device used in the program. READ SET Device Device number GO GO Read operation above SET Automatic scroll Display the program with automatic scroll. SET SET Step number SP Operation in Insert mode (I) Details Purpose Procedures (key input sequence) Insert a command in the program. Insert a command in the program. INSERT SET Step number GO Com mand GO Move the program. Move the whole program. Display the program in the Insert mode. GO HELP Specify the movement end step. GO 2 Specify the movement start step. Specify the movement destination step. GO Copy the program. Copy the program. Display the program in the Insert mode. HELP 3 Specify the copy start step. GO Specify the GO Specify the copy GO copy end step. destination step Operation in Delete (D) mode Details Purpose Procedures (key input sequence) Delete a command from the program. Delete a command from the program. SHIFT DELETE SET Step number GO GO Delete the specified range of the program. Specify the range of the program for deletion. Display the program in the Delete mode. GO HELP Specify the deletion end step. GO Specify the deletion start step. Delete the whole NOP. Delete the whole NOP in the program. Display the program in the Delete mode. HELP 2 2-4
288 2. OPERATION OF EDITING SCREEN FOR EACH LIST Operation in Parameter mode (P) Details Purpose Procedures (key input sequence) Clearing all parameters Parameter setting (for AJ2HCPU) Setting of latch range Setting of step relay Completion of setting (write) Parameter setting (other than AJ2HCPU) Setting of memory capacity Return the parameters to the initial setting status. Set the parameters for the AJ2HCPU. Select the latch range from "No latch", "/2 latch" and "All latch". Set the availability (S536 to 247) of the step relay. When the parameter setting is complete, write the PLC CPU. Set the parameters other than AJ2HCPU. Set the main sequence program capacity and the file register capacity. Set the top device number M, L, S setting used in the latch relay/step (other than AnA, AnUCPU) relay. M, L, S setting (AnA, AnUCPU only) Timer setting (other than AnACPU) Timer setting (AnACPU) Counter setting (AnACPU only) Setting of latch range WDT setting Setting of I/O control system (only for A3HCPU and A3MCPU) Completion of setting (write) Set the top device number used in the latch relay/step relay/internal relay. Set the top device used in the low speed/high speed/retentive timers. Set the number of timers used, the top device number that stores the setting value after T256, and the top device used in the low speed/high speed/retentive timers. Set the number of counters used, and the top device number that stores the setting value after C255. Set the range of the device for latch setting. Set the value of the watchdog timer in the unit of ms. Set the I/O control system. When parameter setting is complete, write the PLC CPU. PARAM GO END GO PARAM 2 GO 2) 2 GO 2) 2) Setting for multiple items is also available. PARAM CLEAR END GO (End of writing is displayed.) Capacity GO END 2) (For main, input unit: K step) Capacity GO END 2) (For sub, input unit: K step) points GO END 2) (For file register, input unit: K point) 2 Top number of L GO Top number of S GO 2) 2 Top number of L GO Top number of S GO 3 Top number of timer GO 2) Top number of M 3 No. of timers GO Top device for storage of setting values GO GO Top number of timer GO 2) 4 No. of counters GO Top device for storage of setting values 5 Top number of latch GO GO End number of latch GO 6 WDT value GO 2) (input unit: ms) 7 GO 2) 2) Setting for multiple items is also available. CLEAR END END GO (End of writing is displayed.) 2) GO 2) 2)
289 2. OPERATION OF EDITING SCREEN FOR EACH LIST Operation in Other modes (O) Error check Program check Buffer memory batch monitoring Clock monitor Details Purpose Procedures (key input sequence) Clearing of all PC memories Clearing of all programs Clearing of all device memories Operation that checks the error step number/error code for the current error in the ACPU. (other than AnA and AnUCPU) Check the program (double coil, command code, END command). Monitor the buffer memory details of the special function unit. Monitor the clock data of the ACPU. Clear all memories in the ACPU. Clear all sequence program, microcomputer program and T/C setting value areas. Clear all details of the bit device and the word device in the ACPU. SHIFT OTHER 2 2 (Except AnA, AnUCPU) (AnA, AnUCPU) SHIFT OTHER 2 2 GO Step number SHIFT OTHER 3 2 Y Top I/O number of unit H K Buffer memory address GO SHIFT OTHER 3 3 SHIFT OTHER 3 2 GO GO SHIFT OTHER GO SHIFT OTHER GO SP PLC No. setting Main/sub-program switching Remote run/stop Set the PLC No. of other stations for access on the MELSECNET II (/B) or MELSECNET/. Select the main/subprogram displayed on the list edit screen. Operate the run/stop status of the ACPU from the GOT. SHIFT OTHER PC No. GO Network No. GO Station No. GO SHIFT OTHER GO SHIFT OTHER 3 4 GO END Read/write of machine language Specify the memory address (absolute address) of the ACPU. Read the memory details and write the machine language to the memory. SHIFT OTHER SET Address (hexadecimal) SET Address GO (hexadecimal) GO GO Machine language code GO GO 2-6
290 2. ERROR DISPLAY AND CORRECTIVE ACTIONS FOR LIST EDIT Chapter 2. Error Display and Corrective Actions for List Edit 2. Error detected with the list editor function If an error is detected with the list editor function during operation of each mode, an error message appears at the 4th line of the display. Error messages, display conditions and corrective actions are displayed below. If an error message appears, take the following actions to resume operation. Check the error message. 2) Remove the cause of the error. 3) Input the corresponding key. (The error message disappears. The screen returns to the status before error.) (Example) R 2 3 L A D R N I U T X Y M Y 2 2 RST M GO... Reading the step with the RST command. R 2 N O T F O U N D L D R A N I X Y M 2 Display the error message. SET... Delete the error message. R 2 L D R A N I X Y M 2 The error message disappears. The next operation is resumed
291 2. ERROR DISPLAY AND CORRECTIVE ACTIONS FOR LIST EDIT Error message Display condition Action Address error In machine language writing, the address which was tried to be written was at the Set the correct address. write-protect area. No corresponding program The specified command was not found. Check the program. In communication with the CPU for clearing Memory cassette check the keyword or writing the parameter, the Mount the memory cassette properly. memory cassette is insufficient or not Replace the memory cassette with a new one. mounted. Step over error The set step number is larger than the maximum step number. Set the correct step number. Setting error Setting value is not correct. Set the correct value. Not selectable The function which cannot be executed was selected. Select other function. Operation error The set device symbol is incorrect. Perform the correct key operation. Device error The specified command was not found. Set the correct device symbol. The device number exceeds the range. Set the number within the range of CPU device. Identical coil Proceed to the next operation if it does not affect The identical coil is found in the sequence the control. program. Correct the program if it affects the control. When the CPU has detected the error, stop Command error running of the operation. After resetting the When the program is read, it cannot be CPU, check the command around the error. converted to the proper command. Write the correct command. (For check of the error step, refer to ) Command setting error The command set at the time of read, write or insert is not correct. Set the correct command. Memory protect When writing in the Write or the Turn OFF the memory protect switch in the Insert/Delete mode, the memory protect memory cassette. switch in the memory cassette is ON. Capacity over Memory assignment set in the parameter Set the parameter within the capacity of the exceeded the capacity of the memory memory cassette. cassette. No END command There is no END command. Write the END command at the last step of the program. PLC communication error When the list editor function is started, proper communication with the PLC is not made. Restart the list editor function. If communication is not made properly, check the following: GOT main unit Connection of the cable CPU main unit (if any error has occurred) Check the setting of RAM/ROM. PC write error Correct writing was not made in the Write or Check the RAM mounting. Insert mode. Check the setting of the memory protect switch in the CPU. PLC is running Writing, insertion or deletion was attempted during running of the CPU. Stop the CPU. PC No. error The PLC number is set to other station. Change the PLC number and set the station for access to the host. 2-2
292 2. ERROR DISPLAY AND CORRECTIVE ACTIONS FOR LIST EDIT Error message Display condition Action **KS over The value exceeding the range of the Reduce the program capacity by **K steps for program capacity by **K steps was setting. attempted to be set. **KP over The value exceeding the range of the file register capacity by **K points was attempted to be set. The value exceeding the range of the file register capacity by **K points was attempted to be set. Not available for QnACPU. Set the PLC No. The CPU at the list edit destination is QnACPU. Set the PLC number and change the station for access. Set the PLC number and change the station for The keyword is not input. The GO key was pressed without input of list edit. Or select the same station and input Set the PLC No. the keyword on the keyword input screen. the keyword. The PLC parameter was changed. The PLC parameter exceeding the file (R) Restart the GOT system. register capacity was set. Restart the GOT system if required. The PLC parameter was changed. Read the ladder monitor on the PLC again if The capacity of the file (R) register was set. Read the ladder monitor again. required. The PLC program was edited. Read Set the PLC number and change the station for Edit the PLC program. the ladder monitor again. access. 2-3
293 2. ERROR DISPLAY AND CORRECTIVE ACTIONS FOR LIST EDIT 2.2 Error of PLC CPU When the error step read in other mode is performed, the error message and the error step of the current error in the ACPU are displayed. Error messages, error details and corrective actions are displayed below. If an error message appears, take the following actions to resume operation. Check the error message. 2) If the error code is not displayed, check the error code of special register D98 with the system monitor function (Refer to Chapter 8.). 3) Remove the cause of the error. (Display) Example of display for an error in the CPU other than AnA and AnU E S E R P R R. R. U. N S I C T E P T D O D E = O WN = Mode is displayed (other mode). Error step number is displayed (step number of D9). Error message is displayed. Error code is displayed (error code of D98). Example of display for an error in the AnA or AnUCPU E S E E R P R R R. R R. U.. N S I C I T E T O D N F P D E O = O WN = = Mode is displayed (other mode). Error step number is displayed (step number of D9). Error message is displayed. Error code is displayed (error code of D98). Error detail code is displayed (error code of D99. Error history if available is displayed. Example of next display for the display of "[«" above (error history is available) E A E 9 R R C R R 9 /. D. O 7 S T E P W N C / O D 2 E = = 9 : 5 5 : Mode is displayed (other mode). Error history number is displayed (history control No. of ACPU). Error step number is displayed. Error message is displayed. Error code is displayed. Error detail code is displayed. Second, minute, hour, date, month and year of the error are displayed. Displayed if other error history is available. POINT When an error message of the PLC CPU appears, refer to the ACPU programming manual (Common Command) and the user's manual for each CPU for corrective actions. 2-4
294 2. ERROR DISPLAY AND CORRECTIVE ACTIONS FOR LIST EDIT 2.3 Error using list editor function on the link system When the list editor function is used on the link system, the "PLC communication error ( **)" may appear. In this case, check the error details and the corrective actions. Error No. Error message Action Time-out error: No response to the request Process cancel: New process request was given to the list editor function while the CPU is processing. Sum check error: A sum check error from the link communication has occurred. Check the cable wiring. Perform correct key operations on the GOT. There may be noise interference. Check the system again. PLC No. error: Check the PLC number setting. Set 6 There is no station corresponding to the PLC number. the correct number. 9 This error may occur when the ACPU is reset during monitoring. Perform the monitor setting again Remote error: Although remote stop/pause is performed from the computer link unit, remote run/stop is additionally performed. Link error: While the slave station is monitoring the master station, the master station is reset. EEPROM failure: The EEPROM, cannot be written due to EEPROM failure. Perform the remote run/stop/pause from either unit. Perform the monitor setting again. Replace the EEPROM with a new one. If error number "25" appears, the following causes are possible. Check the details and the corrective actions. ( When connected to the master station Device number Description Details M92 Link card error (for master station) OFF: Normal ON : Error The control depends on whether there is an error at the hardware of the link card. The link card in the CPU link unit is judged at the CPU. Replace the link unit. M9224 Link status OFF: Online ON : Offline, station-to-station test, or self-loopback test The control depends on whether the master station itself is online or offline, or in the station-to-station mode or the selfloopback mode. Check the mode switch. M9227 Loop test status OFF: Not executed ON : Normal loop test and subloop test are being executed. The control depends on whether the master station itself is executing the normal loop test or the sub-loop test. (2) When connected to the local station Device number Description Details M92 Link card error (for local station) OFF: Normal ON : Error The control depends on whether there is an error at the hardware of the link card. The link card in the CPU link unit is judged at the CPU. Replace the link unit. M924 Link status OFF: Online ON : Offline, station-to-station test, or self-loopback test The control depends on whether the local station itself is online or offline, or in the station-to-station mode or the self-loopback mode. Check the mode switch. M9257 Loop test status OFF: Not executed ON : Normal loop test and subloop test are being executed. The control depends on whether the local station itself is executing the normal loop test or the sub-loop test. 2-5
295 2. ERROR DISPLAY AND CORRECTIVE ACTIONS FOR LIST EDIT (3) When connected to the CPU in MELSECNET/ An error in the MELSECNET/ is reported using a four digit (hexadecimal) error number. For details of the errors and corrective actions, see the MELSECNET/ Network System Reference Manual. POINT If an error code not listed in the previous page is displayed, contact the nearest of our system service centers, agents, and branch offices. 2-6
296 INDEX [A] Adaptor address [B] Batch monitor BM monitor Brightness/contrast adjustment of monitor screen Brightness/contrast adjustment screen Buzzer sound [C] Capacity of special module monitor data Connection transmission speed Clock setting [D] Deleting a registered device Detailed own station monitor [E] Entry monitor Error display and handling Ladder monitor function Network monitor function Special module monitor function System monitor function... - List editor function [F] Features Ladder monitor function Network monitor function Special module monitor function System monitor function... - Utility function List editor function Function list Functions requiring a memory board... - [G] Grip switch [H] Host (FF) address How to display the utility menu Human sensor detection sensitivity Human sensor function Human sensor OFF delay [L] Ladder monitor function Ladder read operation List editor function [M] Memory capacity of OS Memory information Message display Microcomputer connection protocol Microcomputer connection transmission speed [N] Network monitor function [O] Operation for defect search Operation procedures Ladder monitor function Network monitor function Special module monitor function... - System monitor function List editor function...9- Other station monitor Outside speaker sound Own station monitor [P] Password [Q] QC24 connection transmission speed Quick test function QBUS extension number QBUS slot number IND. Index -
297 [R] Reading data from the PLC Required equipment Reverse display [S] Screen display and key functions Batch monitor BM monitor Detailed own station monitor Entry monitor Ladder monitor function Other station monitor Special module monitor function System monitor function TC monitor Screen cleanup Screen & OS copy Screen save light Screen saver function Screen saver Human sensor Screen save time Security password Self test Setup Special module monitor function Specifications Ladder monitor function Network monitor function Special module monitor function System monitor function List editor function Specifying the monitor station and device Switching the display form System monitor function... - [T] TC monitor Test for special function module Test function [U] Utility function Utility function list Index - 2
298 MEMO Index - 3
299 WARRANTY Please confirm the following product warranty details before starting use.. Gratis Warranty Term and Gratis Warranty Range If any faults or defects (hereinafter "failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the dealer or Mitsubishi Service Company. Note that if repairs are required at a site overseas, on a detached island or remote place, expenses to dispatch an engineer shall be charged for. [Gratis Warranty Term] The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place. Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (8) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs. [Gratis Warranty Range] ( The range shall be limited to normal use within the usage state, usage methods and usage environment, etc., which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product. (2) Even within the gratis warranty term, repairs shall be charged for in the following cases.. failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design. 2. Failure caused by unapproved modifications, etc., to the product by the user. 3. When the Mitsubishi product is assembled into a user's device, failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided. 4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced. 5. Failure caused by external irresistible forces such as fires or abnormal voltages, and failure caused by force majeure such as earthquakes, lightning, wind and water damage. 6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi. 7. Any other failure found to not be the responsibility of Mitsubishi or the user. 2. Onerous repair term after discontinuation of production ( Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued. Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc. (2) Product supply (including repair parts) is not possible after production is discontinued. 3. Overseas service Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center may differ. 4. Exclusion of chance loss and secondary loss from warranty liability Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to damages caused by any cause found not to be the responsibility of Mitsubishi, chance losses, lost profits incurred to the user by failures in Mitsubishi products, damages and secondary damages caused from special reasons regardless of Mitsubishi's expectations, compensation for accidents, and compensation for damages to products other than Mitsubishi products and other duties. 5. Changes in product specifications The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice. 6. Product application ( In using the Mitsubishi MELSEC programmable logic controller, the usage conditions shall be that the application will not lead to a major accident even if any problem or fault should occur in the programmable logic controller device, and that backup and fail-safe functions are systematically provided outside of the device for any problem or fault. (2) The Mitsubishi general-purpose programmable logic controller has been designed and manufactured for applications in general industries, etc. Thus, applications in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies, and applications in which a special quality assurance system is required, such as for each Japan Railways company or the Department of Defense shall be excluded from the programmable logic controller applications. Note that even with these applications, if the user approves that the application is to be limited and a special quality is not required, application shall be possible. When considering use in aircraft, medical applications, railways, incineration and fuel devices, manned transport devices, equipment for recreation and amusement, and safety devices, in which human life or assets could be greatly affected and for which a particularly high reliability is required fin terms of safety and control system, please consult with Mitsubishi and discuss the required specifications.
300 GOT-A9 Series Operating Manual (SW4D5C-GOTR-PACKE compatible Extended Option Functions Manual) MODEL MODEL CODE SW4-GOTR-O(SYS)-E 3J979 SH(NA)-869-B(5)MEE HEAD OFFICE : MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO -83 TELEX : J24532 CABLE MELCO TOKYO NAGOYA WORKS : -4, YADA-MINAMI 5, HIGASHI-KU, NAGOYA, JAPAN When exported from Japan, this manual does not require application to the Ministry of International Trade and Industry for service transaction permission. Specifications subject to change without notice.
How to read this guide
How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information
MELSEC-QS CC-Link IE Field Network Master/ Local Module User's Manual -QS0J71GF11-T2
MELSEC-QS CC-Link IE Field Network Master/ Local Module User's Manual -QS0J71GF11-T2 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this
SAFETY PRECAUTIONS (Read these precautions before using this product.)
SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the
CW Configurator Operating Manual -SW1DND-RCCPU-E
CW Configurator Operating Manual -SW1DND-RCCPU-E SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully
SIMATIC S7-300. Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01
SIMATIC S7-300 Getting Started for First Time Users Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01 Safety Guidelines This manual contains notices you have to observe in order to ensure your personal
The Next Generation in Industrial Programming Mitsubishi FA Integrated Concept
Mitsubishi iq Platform Compatible Programmable Controller Engineering Software MELSOFT GX Works2 The Next Generation in Industrial Programming Mitsubishi FA Integrated Concept Increase productivity and
ZEN-SOFT01-V3. Cat.No.W386-E1-03
ZEN-SOFT01-V3 Cat.No.W386-E1-03 ZEN-SOFT01-V3 ZEN Support Software Operation Manual Revised April 2003 iv Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator
UTILITY INSTRUCTION MANUAL BNP-B2196 (ENG)
UTILITY INSTRUCTION MANUAL BNP-B2196 (ENG) MELDASMAGIC is a registered trademark of Mitsubishi Electric Corporation. Microsoft and Windows are registered trademark of Microsoft Corporation in the USA.
Open Field Network CC-Link Troubleshooting Guide
2006 Mar Open Field etwork CC-Link Troubleshooting Guide Mitsubishi Electric Corporation agoya Works is a factory certified for ISO14001 (standards for environmental management systems) and ISO9001 (standards
Setup and Programming of the. Master Module R72-11Z-SLSASG-028
Setup and Programming of the FX3U-16CCL-M eth1000_large.jpg FX3U CC-LINK Master Module R72-11Z-SLSASG-028 Contents Contents... i FURTHER READING REFERENCE LIST... ii Chapter 1 Introduction... 1-1 Chapter
Setting/Monitoring Tools for the C Controller Module Version 4 Operating Manual -SW4PVC-CCPU-E
Setting/Monitoring Tools for the C Controller Module Version 4 Operating Manual -SW4PVC-CCPU-E SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please
SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program
Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves
S7 for Windows S7-300/400
S7 for Windows S7-300/400 A Programming System for the Siemens S7 300 / 400 PLC s IBHsoftec has an efficient and straight-forward programming system for the Simatic S7-300 and ern controller concept can
SAFETY PRECAUTION. (Always read these instructions before using the products.)
SAFETY PRECAUTION (Always read these instructions before using the products.) When designing the system, always read the relevant manuals and give sufficient consideration to safety. During the exercise,
Mitsubishi Electric Q Series PLC Ladder Monitor. Operation Manual
Mitsubishi Electric Q Series PLC Ladder Monitor Operation Manual Preface Thank you for purchasing Pro-face's PLC Ladder Monitor Add-on Kit for the Mitsubishi Electric Q Series PLC. This manual ("Mitsubishi
Introduction. - Please be sure to read and understand Precautions and Introductions in CX-Simulator Operation Manual and
Introduction - Please be sure to read and understand Precautions and Introductions in CX-Simulator Operation Manual and CX-Programmer Operation Manual before using the product. - This guide describes the
Cat. No. V062-E1-04. NT31 and NT31C. Programmable Terminals. Setup Manual
Cat. No. V062-E1-04 NT31 and NT31C Programmable Terminals Setup Manual NT31 and NT31C Programmable Terminals Setup Manual Revised September 2007 POWER RUN iv Notice: OMRON products are manufactured for
Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4
Present sample project 1 HMI configuration 2 SIMATIC Getting Started Insert HMI device from libraries 3 Configuring HMI connection 4 Configuring system diagnostics 5 Simulating an HMI device 6 05/2014
6AV3617-1JC30-0AX1. Type of voltage. UPS connectable (serial) Backup battery. minimum backup duration Memory. Flash / RAM.
6AV3617-1JC30-0AX1 Page 1 Product data sheet 6AV3617-1JC30-0AX1 OPERATOR PANEL OP17/DP12 LC DISPLAY, BACKLIT LED 4X20/8X40 LINESXCHARACTERS SIMATIC S5, 505, S7, M7, NATIVE DRIVERS, PROFIBUS-DP 12 MBAUD,
Type SW3D5F-OLEX-E Excel Communication Support Tool Operating Manual
Type SW3D5F-OLEX-E Excel Communication Support Tool Operating Manual Mitsubishi Programmable Logic Controller SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) Before using
IMPORTANT PRODUCT INFORMATION
January 2010 IMPORTANT PRODUCT INFORMATION READ THIS INFORMATION FIRST Product: Max-ON Hot-Backup Redundancy Software, Release 2.05 Introduction Max-ON is a trademark of GE Intelligent Platforms, Inc.
The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example. Select [Project] [New].
How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Caution This symbol explains information you need
NT620S/620C Programmable Terminals OPERATION MANUAL
Cat. No. V033-E1-5 NT620S/620C Programmable Terminals OPERATION MANUAL Authorized Distributor: Cat. No. V033-E1-5 Note: Specifications subject to change without notice. Printed in Japan 0401-0.7M (0597)
SOFTWARE SETUP MANUAL. GX Developer-FX
SOFTWARE SETUP MANUAL GX Developer-FX FX Series Programmable Controllers Foreword This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation
Barcode Reader Connection Guide (COGNEX SLMP Connection)
Barcode Reader Connection Guide (COGNEX SLMP Connection) CONTENTS SAFETY PRECAUTIONS... A- REVISIONS... A- INTRODUCTION About This Connection Guide... Required Modules and Devices... Input/output cables...
L5354 ControlNet Communications Interface
L5354 ControlNet Communications Interface Technical Manual HA470733 Issue 2 Copyright SSD Drives Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or
Logix5000 Controllers Import/Export Project Components
Programming Manual Logix5000 Controllers Import/Export Project Components Catalog Numbers 1768-L43, 1768-L45 Important user information Read this document and the documents listed in the additional resources
USER S MANUAL. CompoBus/D (DeviceNet) Communications Unit MODEL 3G3MV-PDRT1-SINV. (For SYSDRIVE 3G3MV Multi-function Compact Inverters)
Cat. No. I529-E1-1 USER S MANUAL CompoBus/D (DeviceNet) Communications Unit MODEL 3G3MV-PDRT1-SINV (For SYSDRIVE 3G3MV Multi-function Compact Inverters) Thank you for choosing a 3G3MV Multi-function Compact
SA-9600 Surface Area Software Manual
SA-9600 Surface Area Software Manual Version 4.0 Introduction The operation and data Presentation of the SA-9600 Surface Area analyzer is performed using a Microsoft Windows based software package. The
Positioning Module Software Package
Positioning Module Software Package Operating Manual Mitsubishi Programmable Logic Controller SW0D5C-QD75P-E SAFETY INSTRUCTIONS (Always read these instructions before using this equipment.) Before using
Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3. Simatic. Readme. Readme
Validity 1 Improvements in STEP 7 2 Simatic Improvements in WinCC 3 2012 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety,
Abbreviations and Terms in This Manual Section 2.1, 3.1.1, 4.1.1
REVISIONS Print Date Manual Number Revision Feb., 2000 Jun., 2000 IB(NA)-0800093-A First edition IB(NA)-0800093-B Corrections The manual number is given on the bottom left of the back cover. Abbreviations
WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide
WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide Version 2.1, 4/2010 Disclaimer While every effort has been made to ensure that the information in this guide is accurate
OPERATION MANUAL. FX Configurator-FP
OPERATION MANUAL FX Configurator-FP Safety Precautions (Read these precautions before using.) Before installing, operating, maintenance or inspecting this product, thoroughly read and understand this
SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.
SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation
Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library. Deleting program block Main [OB1] Copying program blocks
Loading the block library 1 Deleting program block Main [OB1] 2 TIA Portal SIMATIC Getting Started Copying program blocks 3 Cyclic interrupt OB 4 Copying tag tables 5 Compiling a project 6 Load project
CONTENTS CONTENTS... A - 1 FURTHER READING REFERENCE LIST...A - 3. CHAPTER 1 INTRODUCTION 1-1 to 1-4. 1.1 Database Overview... 1-1
CONTENTS CONTENTS... A - 1 FURTHER READING REFERENCE LIST...A - 3 CHAPTER 1 INTRODUCTION 1-1 to 1-4 1.1 Database Overview... 1-1 1.2 MES Interface Module Overview... 1-3 CHAPTER 2 EXAMPLE SYSTEM OUTLINE
PLC Master / Slave Example
PLC Master / Slave Example A 2 PLC The Example This chapter provides an example of a PLC master / slave network and is designed for the experienced user. This chapter does not provide detailed descriptions
isppac-powr1220at8 I 2 C Hardware Verification Utility User s Guide
November 2005 Introduction Application Note AN6067 The isppac -POWR1220AT8 device from Lattice is a full-featured second-generation Power Manager chip. As part of its feature set, this device supports
SHORT TRAINING COURSES
Post Office Box SR 95, Spintex Road, Ghana Tel: +233 302 812680, Fax: +233 302 814709 E mail: [email protected] Website: www.automationghana.com SHORT TRAINING COURSES Equipping industries with
Programmable Controllers
Cat. No. W146-E1-5 SYSMAC C20K/C28K/C40K/C60K Programmable Controllers K-type Programmable Controllers OPERATION MANUAL Revised July 1999 Notice: OMRON products are manufactured for use according to proper
AC-115 Compact Networked Single Door Controller. Installation and User Manual
AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.
CPU 317-2 PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device
CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device SIMATIC PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device Introduction 1 Preparation 2 Learning units 3 Further Information
Series Six Plus Programmable Controller
Series Six Plus Programmable Controller Gl?K-0147B June 1989 Central Processor Unit 8-Slot Rack 1l-Slot Rack General Description The Central Processor Unit (CPU) for the Series Six Plus Programmable Logic
OPERATOR PANEL OP7/DP LC DISPLAY, BACKLIT LED 4 LINES, 20 CHARACTERS/LINE, SIMATIC S7, M7, PROFIBUS-DP 1.5 MBAUD UL/CSA-LISTED
6AV3607-1JC20-0AX1 Page 1 Product data sheet 6AV3607-1JC20-0AX1 OPERATOR PANEL OP7/DP LC DISPLAY, BACKLIT LED 4 LINES, 20 CHARACTERS/LINE, SIMATIC S7, M7, PROFIBUS-DP 1.5 MBAUD UL/CSA-LISTED Supply voltage
WinCC. Communication Manual. Manual 2. This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 C79000-G8276-C156-01
WinCC Communication Manual Manual 2 This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 Release: September 1999 WinCC, SIMATIC, SINEC, STEP are trademarks of Siemens.
T-BOXN12R. First steps with T-BOXN12R. You can make it wireless. Date: 2004-07-16 Version 1.0
T-BOXN12R You can make it wireless First steps with T-BOXN12R Date: 2004-07-16 Version 1.0 Content 1. Purpose of this document... 3 2. T-BoxN12R overview... 4 3. First step... 5 3.1. Preparing your workshop
Programming A PLC. Standard Instructions
Programming A PLC STEP 7-Micro/WIN32 is the program software used with the S7-2 PLC to create the PLC operating program. STEP 7 consists of a number of instructions that must be arranged in a logical order
TEXT DISPLAY TD17 LC DISPLAY, BACK-LIT LED, 4X20/8X40 LINES X CHARACTERS F0R SIMATIC S5,505,S7,M7 NATIVE DRIVERS, PROFIBUS-DP12
6AV3017-1NE30-0AX0 Page 1 Product data sheet 6AV3017-1NE30-0AX0 TEXT DISPLAY TD17 LC DISPLAY, BACK-LIT LED, 4X20/8X40 LINES X CHARACTERS F0R SIMATIC S5,505,S7,M7 NATIVE DRIVERS, PROFIBUS-DP12 Supply voltage
How To Operate Loader On A Microsoft Powerbook 2.5 (Powerbook) With A Powerbee 2.2 (Powerbee) And Powerbee 3.5 Powerbee (Powerbore) (Powerboard) (Operating
Inverter Support Software FRENIC Loader 3.2 (FRENIC-Mini/Eco/Multi/MEGA/HF) Instruction Manual INR-SI47-1549b-E Copyright 2008-2012 Fuji Electric Co., Ltd. No part of this publication may be reproduced
Alliance System Ordering Guide
Alliance System Ordering Guide Multiple Technologies Versatile Hardware Powerful Software One family of parts and accessories Version 12-Nov-03 Alliance System Ordering Guide Table of Contents Controllers
INGENIEURBÜRO FÜR TECHNOLOGIE TRANSFER DIPL.-ING. B. P. SCHULZ-HEISE. Getting Started with. S7 for Windows. Version 6.x
INGENIEURBÜRO FÜR TECHNOLOGIE TRANSFER DIPL.-ING. B. P. SCHULZ-HEISE Getting Started with S7 for Windows Version 6.x TTI Ingenieurbüro für Technologie Transfer Dipl. Ing. B. Peter Schulz-Heise Stadtring
The modular concept of the MPA-3 system is designed to enable easy accommodation to a huge variety of experimental requirements.
HARDWARE DESCRIPTION The modular concept of the MPA-3 system is designed to enable easy accommodation to a huge variety of experimental requirements. BASE MODULE GO LINE Digital I/O 8 Analog Out AUX 1
DUKANE Intelligent Assembly Solutions
PC Configuration Requirements: Configuration Requirements for ipc Operation The hardware and operating system of the PC must comply with a list of minimum requirements for proper operation with the ipc
MITSUBISHI. New! Excel Communication Support Tool MX Sheet Version 1. 2002 No.191E NEW PRODUCT RELEASE. Mitsubishi Integrated FA Software
MITSUBISHI Mitsubishi Integrated FA Software 2002 No.191E NEW PRODUCT RELEASE Excel Communication Support Tool Version 1 New! is a communication support software package. It monitors the PLC CPU, performs
MI4 - Operator Panel : Engineering
MI4 - Operator Panel : Engineering MI4 - Operator Panel : Engineering Overview MI4 Text Operator Panel MI4 Graphic Operator Panel MI4 Touch Operator Panel Communication modules Accessories MI4-CFG-1 Engineering
(Cat. No. 6008-SI) Product Data
(Cat. No. 6008-SI) Product Data 1 Because of the variety of uses for this product and because of the differences between solid state products and electromechanical products, those responsible for applying
CC-Link Network Monitor Function
CC-Link Network Monitor Function Sample Screen Manual Mitsubishi Electric Corporation Using the Samples The sample screen data and files such as the instruction manual can be used upon agreement to the
DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual
DVPPF02-H2 PROFIBUS DP Slave Communication Module Application Manual Warning Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages
How To Program A Microsoft Cx-One (Microsoft) Microsoft Microsoft Pc (Microsatellite) Microsatellite (Microsimulated) (Microphones) (Powergen) (Programmer) (Cx-
Introduction - Please be sure to read and understand Precautions and Introductions in CX-One Setup Manual, CX-Programmer Operation Manual and CX-Integrator Operation Manual before using the product. -
USER MANUAL GUIMGR Graphical User Interface Manager for FRM301/FRM401 Media Racks
USER MANUAL GUIMGR Graphical User Interface Manager for FRM301/FRM401 Media Racks CTC Union Technologies Co., Ltd. Far Eastern Vienna Technology Center (Neihu Technology Park) 8F, No. 60 Zhouzi St. Neihu,
SIMATIC. C7-621, C7-621 AS-i Control Systems. Volume 2 Working with C7 A B C D E. Contents. User Information. Introduction. Startup.
Contents User Information Introduction 1 Startup 2 SIMATIC C7-621, C7-621 AS-i Control Systems Volume 2 Working with C7 Manual Controlling Controlling with the C7 CPU 3 Addessing, Parameter Assignment,
Custom Solutions Center. Users Guide. Low Cost OEM PackML Templates L02 Release. Version LC-1.0
Users Guide Low Cost OEM PackML Templates L02 Release Version LC-1.0 Users Guide Low Cost OEM PackML Templates L02 Release: Part 1 - Overview Version LC-1.0 Content 1 Introduction...1 2 Low Cost PackML
Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!
Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8
MELSEC iq-r High-Speed Counter Module User's Manual (Application) -RD62P2 -RD62P2E -RD62D2
MELSEC iq-r High-Speed Counter Module User's Manual (Application) -RD62P2 -RD62P2E -RD62D2 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read
Technical Training Module ( 30 Days)
Annexure - I Technical Training Module ( 30 Days) Section 1 : Programmable Logic Controller (PLC) 1. Introduction to Programmable Logic Controller - A Brief History, Need and advantages of PLC, PLC configuration,
EasyMP Monitor Operation Guide Ver.4.40
EasyMP Monitor Operation Guide Ver.4.40 2 Notations Used in This Guide The following table shows the symbols used in this manual, along with descriptions of what they mean. Caution q s Indicates procedures
Training Document for Integrated Automation Solutions Totally Integrated Automation (TIA) MODULE M1
Training Document for Integrated Automation Solutions Totally Integrated Automation (TIA) MODULE M1 Startup Programming of the SIMATIC S7-1200 with TIA Portal V10 T I A Ausbildungsunterlage Seite 1 von
M68EVB908QL4 Development Board for Motorola MC68HC908QL4
M68EVB908QL4 Development Board for Motorola MC68HC908QL4! Axiom Manufacturing 2813 Industrial Lane Garland, TX 75041 Email: [email protected] Web: http://www.axman.com! CONTENTS CAUTIONARY NOTES...3 TERMINOLOGY...3
SCADAPack E ISaGRAF 3 User Manual
SCADAPack E ISaGRAF 3 User Manual 2 SCADAPack E ISaGRAF 3 User Manual Table of Contents Part I ISaGRAF 3 User Manual 3 1 Technical... Support 3 2 Safety... Information 4 3 Preface... 6 4 Overview... 8
Sharp Remote Device Manager (SRDM) Server Software Setup Guide
Sharp Remote Device Manager (SRDM) Server Software Setup Guide This Guide explains how to install the software which is required in order to use Sharp Remote Device Manager (SRDM). SRDM is a web-based
CPU systron S 200 - S 250 - S 250c. systron S 200 - S 250 - S 250c. CPUs to the process modules. Stand-alone PLC
E031019 000823 systron S 200 - S 250 - S 250c CPU systron S 200 - S 250 - S 250c 45 mm width Flexible and expandable Easy to use software for bus connection (S 250/ S 250c) CPUs to the process modules
WinProladder User Guide Content
WinProladder User Guide Content 1 General Information... 1-1 1.1 Operation Environment Requirements... 1-1 1.1.1 Operating System... 1-1 1.1.2 Hardware Requirements... 1-1 1.2 Introduction to Functions
SIMATIC. S7-1200 Getting started with S7-1200. Preface. Quick review 1. Installation 2. Create a simple latch circuit 3. Complete the user program 4
Preface S7-1200 SIMATIC S7-1200 Getting Started Quick review 1 Installation 2 Create a simple latch circuit 3 Complete the user program 4 Use a watch table for monitoring 5 11/2009 A5E02486791-01 Legal
EXTERNAL DIMENSIONS AND PARTS
FX2N-4DA SPECIAL FUNCTION BLOCK USER S GUIDE JY992D65901A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX2N-4DA special
Machine Automation Controller NJ-series. Startup Guide. for Motion Control W514-E1-01
Machine Automation Controller NJ-series Startup Guide for Motion Control W514-E1-01 OMRON, 2011 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
Lifecycle Service Tool. Operator's manual
REF 542plus 1MRS756725 Issued: 23.12.2008 Version: A/23.12.2008 REF 542plus Contents Copyrights... 5 1. Introduction...7 1.1. This manual... 7 1.2. Use of symbols... 7 1.3. Intended audience... 7 1.4.
Software redundancy for SIMATIC S7 SIMATIC. S7-300/S7-400 Software redundancy for SIMATIC S7. Contents 1
Contents 1 How should I use this description? - A tip for 2 readers SIMATIC S7-300/S7-400 Software redundancy for SIMATIC S7 Function Manual Introduction 3 How software redundancy works 4 Blocks for software
ERC-to-MRC JOB TRANSLATOR MANUAL
Yasnac MRC Controller ERC-to-MRC JOB TRANSLATOR MANUAL Part Number 133110-1 Yasnac MRC Controller ERC-to-MRC Job Translator Manual Part Number 133110-1 June 13, 1995 MOTOMAN 805 Liberty Lane West Carrollton,
E-mail:[email protected] Web site: www.tst-software.com
E-mail:[email protected] Web site: www.tst-software.com Solutions That Make Sense for Windows 7/XP/2008 and 2003 Server/2000 Multi-DNC v8.0 for Windows 7/XP/2008 and 2003 Server/2000 communications
CB15/CB155. PROFIBUS Module
CB15/CB155 PROFIBUS Module Contents Warning and Caution Notes 1. OVERVIEW 1.1 Description and Features 1.2 Application on a PROFIBUS Link 2. INSTALLATION 2.1 Installing the Module 2.1.1 CB15 Installation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Safety Precautions Read and understand this specifications, instruction manual, installation manual and catalog to make proper use of the product. WARNING If critical situations that could lead to user
USBSPYDER08 Discovery Kit for Freescale MC9RS08KA, MC9S08QD and MC9S08QG Microcontrollers User s Manual
USBSPYDER08 Discovery Kit for Freescale MC9RS08KA, MC9S08QD and MC9S08QG Microcontrollers User s Manual Copyright 2007 SofTec Microsystems DC01197 We want your feedback! SofTec Microsystems is always on
SAFETY PRECAUTIONS (Please read these instructions before using this equipment.)
SAFETY PRECAUTIONS (Please read these instructions before using this equipment.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay
Omron Health Management Software Ver1.3 User s Help Manual
Omron Health Management Software Ver1.3 User s Help Manual Copyright 2006-2008 Omron Healthcare Co., Ltd. World Rights Reserved Visit http://software.omronhealthcare.com to register your customer information
1 How configure S7 PLC in the configuration tool
Quick Start Rev Date File Name Industrial Ethernet communication with Siemens S7-300 and S7-400 PLCs 1.1 29/01/07 QuickStart_IndusEthernet comm with Siemens S7-300 and S7-400 PLC Description Product concerned:
IEEE 802.11b WLAN PC Card
IEEE 802.11b WLAN PC Card User s Guide Version: 1.3 August 2001 Please install the Utility/Driver first before inserting the PCMCIA Card. FCC Class B Radio Frequency Interference Statement The manufacturer
1. Introduction... 3 Introduction...2. 4. Deal command... 13
Dealer4 PC Software User Manual Service Software Manual ver:ver: 1.11.2 1. Introduction... 3 Introduction...2 2.1 Main Menu... 4 2.1. Main Menu window...4 Summary of additional functions...3 2.2. Board
PNSPO! Modbus Solution CP1H / CP1L / CJ1 / CJ2 / CS1. Version 2.05 6/18/2009
PNSPO!! Modbus Solution CP1H / CP1L / CJ1 / CJ2 / CS1 Version 2.05 6/18/2009 Section 1. Overview The Omron CP1H and CP1L PLCs offer a built in function called Easy Modbus, that performs a Modbus RTU Master
SIMATIC. WinCC V7.0. Getting started. Getting started. Welcome 2. Icons 3. Creating a project 4. Configure communication 5
SIMATIC WinCC V7.0 SIMATIC WinCC V7.0 Printout of the Online Help 1 Welcome 2 Icons 3 Creating a project 4 Configure communication 5 Configuring the Process Screens 6 Archiving and displaying values 7
13 Managing Devices. Your computer is an assembly of many components from different manufacturers. LESSON OBJECTIVES
LESSON 13 Managing Devices OBJECTIVES After completing this lesson, you will be able to: 1. Open System Properties. 2. Use Device Manager. 3. Understand hardware profiles. 4. Set performance options. Estimated
ScanRouter Lite 2.0.6.0
ScanRouter Lite 2.0.6.0 ScanRouter V2 Lite Distribution software bundled to the MFPs, FAXs, and Scanners ScanRouter V2 Lite helps users create a "paperless office" environment by providing easy distribution
Operating Instructions
Operating Instructions (For Setting Up) Digital Imaging Systems Installation Overview Model No. DP-8060 / 8045 / 8035 Table of Contents Setting Your Machine Installation Overview General Installation Overview...
Copley Camming User Guide
Copley Camming User Guide P/N 95-00501-000 Revision 2 June 2008 Copley Camming User Guide. TABLE OF CONTENTS About This Manual... 5 1: Operational Overview... 7 1.1: Host System Requirements... 8 1.2:
MicroLogix 1100 Embedded Web Server
User Manual MicroLogix 1100 Embedded Web Server Bulletin 1763 Controllers Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment.
StruxureWare Power Monitoring 7.0.1
StruxureWare Power Monitoring 7.0.1 Installation Guide 7EN02-0308-01 07/2012 Contents Safety information 5 Introduction 7 Summary of topics in this guide 7 Supported operating systems and SQL Server editions
EA7-T8C EA7-T10C EA7-T12C EA7-T15C
The new Generation of Touch Panels with ambitious image presentation and integrated operating function With the C-more series, featuring STN and TFT touch screens, AutomationDirect now provides the best