Direct liquid cooling by bull. Laurent Cargemel Server Design & Development June 27th, 2012

Size: px
Start display at page:

Download "Direct liquid cooling by bull. Laurent Cargemel Server Design & Development June 27th, 2012"

Transcription

1 Direct liquid cooling by bull Laurent Cargemel Server Design & Development June 27th, 2012

2 Green datacenter characteristics PUE small as possible 1 Energy reuse : warmer liquid may open new usage 65 C outlet temperatures open «central heating» market Reduce liquid cooling footprint within the datacenter Mobull, new racks Today Bull focuses on smaller PUE by using liquid cooling 2 Current DLC offer 2nd generation improvements Research activities

3 Water cooling & PUE Water cooled blade don t need icecold water Cooling with hot water improves significantly the PUE Cool doors AirCooled 10(20) kw/rack Room 20 C A/C water PUE C Direct Liquid Cooling 40 kw/rack 60 kw/rack Room 20 C 27 C Room up to 27 C Water 712 C 1419 C Water 3040 C PUE PUE A/C 3

4 Bullx direct liquid cooling technology Cooperative Power Chassis (CPC) Chassis Partitioning of water cooling and AC voltage for safety reasons 54V DC to the chassis 18 bisockets blades Switch IB & Ethernet embedded 7U 100% water cooled fan less Noiseless Hydraulic Chassis (HYC) Provide water cooling for the 5 chassis Redundant 2N at rack level (Cheaper than at blade level ) 100% liquid cooled 42U Bull rack (19 ) HYC 2 Bisockets nodes per blade 4

5 Bullx dlc Main features Bullx dlc technology allows to implement more powerful blades Double EP node blades, Single EP node blade plus accelerators 2kW blade with 1 EP node plus custom accelerators It supports largest MIC adaptors Maintainability remains as it was in an air flow design Maximum rack water inlet temperature: Direct access to CPU sockets Direct access to Dimms Direct access to disks Type of blade 2 Bisockets nodes blade 1 EP node with GPU CPU power Node power EP 130W 820W 35 C EP 115W 790W 40 C MIC 300W 1400W 40 C > 2000W 20 C 1 EP node with accelerators 5 Water T (customer loop)

6 Bullx dlc Very accurate Blade cooling control (1) Blade Water inlet temperature is regulated by setting appropriate inlet valve openness Water Redundancy is provided by putting 2 Hydraulic Controller per rack. One HYC is active at a time Regulation worst case is when one active HYC fails: Tcase CPU variation is much smaller than water inlet temperature variation : 23 C Figure shows real test results Influe nce d'une é lév ation de T e au sur la T de s CPU 10 Tcase CPU 8 T d'entrée d'eau dans les lames Degré ( C) T e m p s (s )

7 Bullx dlc Blade cooling control accuracy (2) Other source of variation: 34 Start at warm or cold water condition, blade power variations (+/ 1 C around reference temperature) Rac k c onsumption Water flow is regulated depending on the rack configuration 34 T inlet blade Temperatures ( C) Power (kw) W ater tem perature control Scrutation 10s Kp=20 Ki=0,5 Regul 30 C Resulting measured water flow variation : (1,4 à 1,7 l/min) Related Tcase CPU variation (1,4 C) Time (s) Blade water flow control (differential pressure) T c a s e C P U e n fo n c tio n d e s v a ria tio n m a x im u m d e d é b it d a n s le s la m e s A rm o i re 4 0 k W 4 5 P l a q u e s fro id e s W i n x e n T e a u c l ie n t 3 5 C From 5 to 1 chassis, and from 1 to 5 chassis ,6 E c art Tc as e C P U 1, , Number of chassis Differential pressure 2 1 Ecart / nominal ( C) 150 Number of chassis Différential pressure (kpa) ,8 0,6 0,4 0, ,4 7 1,4 5 1,5 1,5 5 D é b it (l/m in ) Time (min) 1,6 1,6 5 1,

8 Bullx dlc technology 2nd generation (1) Today, a good solution is based on free cooling (warm water system) Tomorrow, a warmer outlet temperature may help for energy reuse Here is the split of the temperature difference between CPU case and water Losses by exchange type Margin 10% Series water path 13% Conduction 45% TIM 13% Exchange w. Fluid 19% 8 2 main candidates for an optimization are the heat spreader geometry and the heat exchange at cold plate level

9 Bullx dlc technology 2nd generation (2) Example of heat exchange optimization at coldplate level More turbulence involves the heat exchange between cold plate en fluid Several simulations done with different shapes of fins Intensity of turbulence (%) Cold plate bullx Exchange area Fluid path 9 Fluid speed spectrum (m/s)

10 Bullx dlc research activities (1) Experiment new fluid : Nanofluid 12 kw Blade immersion while saving easy access to the different removable parts 12 kw blade without liquid connectors Copper nanoparticles fluid has been tested : 1 C improvement might be expected Illustration 2: Nanofluides vus au microscope électronique: (a) éthylène glycol + cuivre à 0,5 %; (b) eau + alumine ; (c) eau + or à 2 nm; (d) eau + nanotubes Critère 2: Performances thermiques "Pouvoir caloprteur" à 45 C 14,0 12,0 ΔTio (eau)_45 C ΔTio (T10)_45 C ΔTio (T10/ZnO)_45 C ΔTio (Eau/CuO)_45 C ΔT (inout) [ C] 10,0 8,0 6,0 4,0 2,0 0,0 0,6 0,8 1,0 1,2 1,4 1,6 Débit [l/min] 10 1,8 2,0 2,2 2,4 2,6

11 Bullx dlc research activities (2) Water cooling with no liquid in the board Advantage : No hydraulic disconnection during maintenance operations (security & cost improvement) Technical stakes : Electronic components are far from the cooling liquid Thermal : The usage of heat pipes is mandatory to drive heat toward the thermal exchange surface of the blade Mechanical : Need perfect alignment between blade and cold plate in order to use very thin high performance TIM Mechanical Test vehicle has been done : first results are promising Poignée amovible Coque de la lame Coque du châssis Zone de contact CPU TIM CPU Plaque froide CPU CPU Effort Dissipateur à caloduc Refroidissement Zone d'appui caloduc Design principle that ensures a uniform compression of the TIM 11 Design of a 400mm high performance heat pipe

12 Make datacenter easier Current Mobull Racks layout uses warm and cold corridors scheme AC main connection + Fire allarm and protection + Access control Thermal insulation Hydraulic pipes Floor Shock absorber is needed to insure full container transportation: container floor 12

13

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

The CEETHERM Data Center Laboratory

The CEETHERM Data Center Laboratory The CEETHERM Data Center Laboratory A Platform for Transformative Research on Green Data Centers Yogendra Joshi and Pramod Kumar G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

The Mission Critical Data Center Understand Complexity Improve Performance

The Mission Critical Data Center Understand Complexity Improve Performance The Mission Critical Data Center Understand Complexity Improve Performance Communications Technology Forum Fall 2013 Department / Presenter / Date 1 Rittal IT Solutions The State of the Data Center Market

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

HPC TCO: Cooling and Computer Room Efficiency

HPC TCO: Cooling and Computer Room Efficiency HPC TCO: Cooling and Computer Room Efficiency 1 Route Plan Motivation (Why do we care?) HPC Building Blocks: Compuer Hardware (What s inside my dataroom? What needs to be cooled?) HPC Building Blocks:

More information

Power Supply, Cooling and Mechanical Technologies for Green IT

Power Supply, Cooling and Mechanical Technologies for Green IT Power Supply, Cooling and Mechanical Technologies for Green IT Yoshinori Uzuka Kazuhiko Itakura Nobuyoshi Yamaoka Tomoyoshi Kitamura There is an emerging trend for green IT on servers. This trend includes

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

BB-18 Black Body High Vacuum System Technical Description

BB-18 Black Body High Vacuum System Technical Description BB-18 Black Body High Vacuum System Technical Description The BB-18 Black Body is versatile and is programmed for use as a fixed cold target at 80 K or variable target, at 80 K- 350 K no extra cost. The

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Standardised Data centres. Sales presentation

Standardised Data centres. Sales presentation Standardised Data centres 1 Standardised Data Centres l Motivation ll Change of paradigm lll Rittal s Data centre concept lv Benefits V Summary Standardised Data Centre Motivation Does every data centre

More information

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering Energy Efficient Data Center Design Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering 1 Bio Can Ozcan received his Master of Science in Mechanical Engineering from Bogazici University of Turkey in

More information

EHDC. Cooling system for Data Center and server cabinets.

EHDC. Cooling system for Data Center and server cabinets. EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment

More information

Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources

Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services

More information

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

Technical specifications. Containerized data centre NTR CDC 40f+

Technical specifications. Containerized data centre NTR CDC 40f+ Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION

More information

Technical Concept. Filter Fan Unit COMPACT. Type COMPACT AC Type COMPACT EC

Technical Concept. Filter Fan Unit COMPACT. Type COMPACT AC Type COMPACT EC Technical Concept Filter Fan Unit COMPACT Type COMPACT AC Type COMPACT EC Ultra Filter Fan Unit COMPACT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide

More information

Vapor Chambers. Figure 1: Example of vapor chamber. Benefits of Using Vapor Chambers

Vapor Chambers. Figure 1: Example of vapor chamber. Benefits of Using Vapor Chambers Vapor Chambers A vapor chamber is a high-end thermal management device that can evenly dissipate heat from a small source to a large platform of area (see Figure 1). It has a similar construction and mechanism

More information

Automation's Modular Containerized Datacenter Solutions

Automation's Modular Containerized Datacenter Solutions SAFE Automation's Modular Containerized Datacenter Solutions Automation's SAFE (Secure, Autonomous, Flexible, Efficient) Modular Containerized Datacenter offers a fast, flexible and efficient solution

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation.

DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation. DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation. Dr. Rainer Weidmann, DC Architecture & DC Innovation Dr. Rainer Weidmann, DC Architecture

More information

Data Centers: Definitions, Concepts and Concerns

Data Centers: Definitions, Concepts and Concerns Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data

More information

Energy Performance Optimization of Server Room HVAC System

Energy Performance Optimization of Server Room HVAC System International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department

More information

A-CLASS The rack-level supercomputer platform with hot-water cooling

A-CLASS The rack-level supercomputer platform with hot-water cooling A-CLASS The rack-level supercomputer platform with hot-water cooling INTRODUCTORY PRESENTATION JUNE 2014 Rev 1 ENG COMPUTE PRODUCT SEGMENTATION 3 rd party board T-MINI P (PRODUCTION): Minicluster/WS systems

More information

Computer Centre Evolution: Infrastructure Issues. Board of Sponsors Meeting April 26 th 2007

Computer Centre Evolution: Infrastructure Issues. Board of Sponsors Meeting April 26 th 2007 Computer Centre Evolution: Infrastructure Issues CERN openlab Board of Sponsors Meeting April 26 th 2007 Tony Cass Many interesting discussions with Intel personnel gratefully acknowledged Agenda Power

More information

Self-organization of applications and systems to optimize resources usage in virtualized data centers

Self-organization of applications and systems to optimize resources usage in virtualized data centers Ecole des Mines de Nantes Self-organization of applications and systems to optimize resources usage in virtualized data centers Teratec 06/28 2012 Jean- Marc Menaud Ascola team EMNantes-INRIA, LINA Motivations

More information

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres School of something School of Mechanical Engineering FACULTY OF OTHER ENGINEERING Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres A. Almoli 1, A. Thompson 1, N. Kapur 1,

More information

Boosting the Energy efficiency of a Server Room: experimental + virtual approach.

Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Nowadays, the increase in computing power allows the successful applications of the CFD simulation methods in civil environments.

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

Enabling an agile Data Centre in a (Fr)agile market

Enabling an agile Data Centre in a (Fr)agile market Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without

More information

Data Center Temperature Rise During a Cooling System Outage

Data Center Temperature Rise During a Cooling System Outage Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 0 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly

More information

Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE. Industry leading data center solutions for HPC, Cloud and Enterprise markets.

Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE. Industry leading data center solutions for HPC, Cloud and Enterprise markets. Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE Industry leading data center solutions for HPC, Cloud and Enterprise markets. Leadership, Collaboration & Expertise CooIIT Systems Innovates and Delivers

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

Thinking Outside the Box Server Design for Data Center Optimization

Thinking Outside the Box Server Design for Data Center Optimization Thinking Outside the Box Server Design for Data Center Optimization Marie Ross, Senior Applications Engineer Tom Gregory, Consultant Engineer October 2013 The benefits of analyzing thermal performance

More information

Recovering Stranded Capacity in the Data Center. Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09

Recovering Stranded Capacity in the Data Center. Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09 Recovering Stranded Capacity in the Data Center Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09 2 Recovering Stranded Data Center Capacity most data centers are overcooled & inefficient

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

Technical data. Danfoss DHP-A

Technical data. Danfoss DHP-A Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Oil / Air Cooling Units for mechanical engineering and mobile hydraulics

Oil / Air Cooling Units for mechanical engineering and mobile hydraulics Oil / Air Cooling Units for mechanical engineering and mobile hydraulics ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki, Finland tel. +358 40 178 0920 fax +358 9 4789 2800 viflow@viflow.fi www.viflow.fi

More information

Filter Fan Unit SILENT. Type SILENT AC Type SILENT EC

Filter Fan Unit SILENT. Type SILENT AC Type SILENT EC Technical Concept Filter Fan Unit SILENT Type SILENT AC Type SILENT EC Filter Fan Unit SILENT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide clean

More information

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing

More information

MEGWARE HPC Cluster am LRZ eine mehr als 12-jährige Zusammenarbeit. Prof. Dieter Kranzlmüller (LRZ)

MEGWARE HPC Cluster am LRZ eine mehr als 12-jährige Zusammenarbeit. Prof. Dieter Kranzlmüller (LRZ) MEGWARE HPC Cluster am LRZ eine mehr als 12-jährige Zusammenarbeit Prof. Dieter Kranzlmüller (LRZ) LRZ HPC-Systems at the End of the UNIX-Era (Years 2000-2002) German national supercomputer Hitachi SR800

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

January 16-17, 2013 Santa Clara

January 16-17, 2013 Santa Clara January 16-17, 2013 Santa Clara Open Rack Workshop Day 1 Matt Corddry, Facebook Pierluigi Sarti, Facebook Steve Mills, Facebook Richard Chan, Delta Products Patrick MacDonald, Sanmina Corp Eric Wilcox,

More information

Module 1 : Conduction. Lecture 5 : 1D conduction example problems. 2D conduction

Module 1 : Conduction. Lecture 5 : 1D conduction example problems. 2D conduction Module 1 : Conduction Lecture 5 : 1D conduction example problems. 2D conduction Objectives In this class: An example of optimization for insulation thickness is solved. The 1D conduction is considered

More information

High-density modular data center making cloud easier. Frank Zheng Huawei

High-density modular data center making cloud easier. Frank Zheng Huawei High-density modular data center making cloud easier Frank Zheng Huawei 2012-10-10 Content 1 2 3 4 Cloud s impact to data center Concerns of DC construction 4S DC making cloud easier Success stories Cloud?

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

How To Build A T7 Rack For Information Technology

How To Build A T7 Rack For Information Technology THE NEXT GENERATION RACK FOR INFORMATION TECHNOLOGY THE RACK CABINET FOR INFORMATION TECHNOLOGY T7, THE HI-TECH HEART OF THE BLADESHELTER SYSTEM The real answer to the requirements of: Safety Versatility

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products

More information

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department

More information

RiMatrix S Make easy.

RiMatrix S Make easy. RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power

More information

How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring

How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring Brian Rehnke e-pdu Business Development Manager November, 2011 The Problems Energy Usage in most data centers

More information

ICT and the Green Data Centre

ICT and the Green Data Centre ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

Data Center Temperature Rise During a Cooling System Outage

Data Center Temperature Rise During a Cooling System Outage Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 1 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly

More information

2011 DC Electropumps Bull. Rotation Ø 15 6,45 3,5 5,7

2011 DC Electropumps Bull. Rotation Ø 15 6,45 3,5 5,7 Ø 5 ±. DC Electropumps Bull,5 Rotation,5 5,7 Email: sales@hydronit.com Fax B... Electro pumps Bull series MODEL CODE EPB,5 DC /S5 K, V** Electro Pump Bull series Gear pump displacement (cc/rev (see tables

More information

Thermal Simulation of a Power Electronics Cold Plate with a Parametric Design Study

Thermal Simulation of a Power Electronics Cold Plate with a Parametric Design Study EVS28 KINTEX, Korea, May 3-6, 2015 Thermal Simulation of a Power Electronics Cold Plate with a Parametric Design Study Boris Marovic Mentor Graphics (Deutschland) GmbH, Germany, boris_marovic@mentor.com

More information

Analysis of the UNH Data Center Using CFD Modeling

Analysis of the UNH Data Center Using CFD Modeling Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,

More information

CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB

CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB Compact automatic flow rate regulator with polymer cartridge 127 series REGISTERED BS EN ISO 9001:2000 Cert. n FM 21654 UNI EN ISO 9001:2000 Cert. n 0003 CALEFFI 01166/09 GB Function The AUTOFLOW devices

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

NAISSUS THERMAL MANAGEMENT SOLUTIONS

NAISSUS THERMAL MANAGEMENT SOLUTIONS NAISSUS THERMAL MANAGEMENT SOLUTIONS HIGH PERFORMANCE CLOSED LOOP WATER COOLING SYSTEM NTMS30 30kW SYSTEM Cool the servers, not the room! NAISSUS THERMAL MANAGEMENT SOLUTIONS HIGH PERFORMANCE CLOSED LOOP

More information

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features

More information

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

Dynamic Power Variations in Data Centers and Network Rooms

Dynamic Power Variations in Data Centers and Network Rooms Dynamic Power Variations in Data Centers and Network Rooms By Jim Spitaels White Paper #43 Revision 2 Executive Summary The power requirement required by data centers and network rooms varies on a minute

More information

UNDERSTANDING CENTRAL HEATING SYSTEMS

UNDERSTANDING CENTRAL HEATING SYSTEMS UNDERSTANDING CENTRAL HEATING SYSTEMS This advice guide is part of a series of free guides produced by the Association of Plumbing & Heating Contractors Ltd. which provide consumers with essential basic

More information

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

An Experimenatl Study on Heat Transfer Behaviors of A Welded - Aluminum Minichannel Heat Exchanger

An Experimenatl Study on Heat Transfer Behaviors of A Welded - Aluminum Minichannel Heat Exchanger ISSN (e): 2250 3005 Vol, 05 Issue,02 February 2015 International Journal of Computational Engineering Research (IJCER) An Experimenatl Study on Heat Transfer Behaviors of A Welded - Aluminum Minichannel

More information

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014)

Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014) EPJ Web of Conferences 67, 02070 (2014) DOI: 10.1051/ epjconf/20146702070 C Owned by the authors, published by EDP Sciences, 2014 Flow in data racks Lukáš Manoch 1,a, Jan Matěcha 1,b, Jan Novotný 1,c,JiříNožička

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Data Center Facility Basics

Data Center Facility Basics Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern

More information

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Typical Air Cooled Data Centre Compared to Iceotope s Liquid Cooled Solution

Typical Air Cooled Data Centre Compared to Iceotope s Liquid Cooled Solution Typical Air Cooled Data Centre Compared to Iceotope s Liquid Cooled Solution White Paper July 2013 Yong Quiang Chi University of Leeds Contents Background of the Work... 3 The Design of the Iceotope Liquid

More information

Thermoelectric Generator (TEG) for Heavy Diesel Trucks John C. Bass, Aleksandr S. Kushch, Norbert B. Elsner Hi-Z Technology, Inc.

Thermoelectric Generator (TEG) for Heavy Diesel Trucks John C. Bass, Aleksandr S. Kushch, Norbert B. Elsner Hi-Z Technology, Inc. Thermoelectric Generator (TEG) for Heavy Diesel Trucks John C. Bass, Aleksandr S. Kushch, Norbert B. Elsner Hi-Z Technology, Inc. Abstract An improved TEG for the Heavy Duty Class Eight Diesel Trucks is

More information