Typical Air Cooled Data Centre Compared to Iceotope s Liquid Cooled Solution

Size: px
Start display at page:

Download "Typical Air Cooled Data Centre Compared to Iceotope s Liquid Cooled Solution"

Transcription

1 Typical Air Cooled Data Centre Compared to Iceotope s Liquid Cooled Solution White Paper July 2013 Yong Quiang Chi University of Leeds

2 Contents Background of the Work... 3 The Design of the Iceotope Liquid Cooled System M HFE Liquid Properties... 5 Natural Convection Principle... 5 Main Advantage (Thermal)... 6 Other Benefits... 6 Disadvantages... 7 Project Overview... 7 Case Study... 9 System Configuration... 9 Energy Cost and Temperature... 11

3 Background of the work When a higher performance and more dense data centre is deployed, the temperature on computer components becomes critical and traditional air cooled methods are forced to push their limitations of releasing the heat from the data centre. Under such circumstances a more advanced liquid cooled encapsulation technology has been deployed at the University of Leeds, which enables increased performance and density but also resolves the cooling issue by way of liquid cooling. Liquid cooling is thousands of times more effective at removing heat than air and allows all components to run room neutral. This unique and patented technology is called the Iceotope Solution and is proudly designed, engineered and manufactured in the UK by Iceotope. Traditional air cooled data centres use chiller and air conditioning systems to gain lower temperature gages in order to maintain the chip temperature on the motherboard. With such a design an air cooled based data centre can achieve a higher computer density and performance yet fans and chillers amount for extra energy consumption thus resulting in lower power usage efficiency (PUE). To resolve the conflict between efficiency and performance in the data centre, liquid cooled solutions, similar to those deployed in the 1970 s, are being reintroduced and are starting to be seen more often in modern retrofit and new build data centres. Nowadays designs like backdoor water-cooled and waterblock solutions are seen more often in high efficiency data centres, which can improve the PUE down to 1.2 or lower. However, such types of liquid cooled solutions are still based on air-cooled design, and the reality is that there is still potential for liquid cooled designs to achieve even higher efficiencies. As a result, fully immersed liquid cooled solutions such as the liquid encapsulation solution offered by Iceotope have been introduced into the market to achieve the ultimate efficiency in data centre design. With the motherboard fully encapsulated inside the Iceotope Module, which contains a dielectric coolant, it does not require air to transport heat. The solution is also modular and scalable, making it one of the most successful liquid cooled designs available in the data centre market today. Iceotope Liquid Cooled System Design The design of the Iceotope Solution is based on the principle of liquid encapsulation using 3M Novec Engineered Fluid as the dielectric coolant medium. The coolant motion in the primary stage relies on density driven natural convection. In this stage the Novec is in direct contact with all electronic components and heat sinks and as such, extracts the heat from everything to the cold plate where the other side of the cold plate makes contact with a water jacket, which is cast into the design of the Iceotope Module. Figure 1 Iceotope Module (computer node) in detail

4 The rest of Iceotope Solution features a gravity fed water circulation system that is thermally coupled to the outside environment. This water system can be flexible to connect with other applications such as local and/or building water supply and also allows the option for heat reuse by way of hot water, which can be reused to heat the building or nearby facilities. The Iceotope installation at the University of Leeds reused the heat by way of two domestic radiators that heat a laboratory. Figure 2 Iceotope Platform (cabinet) Diagram Figure 3 Iceotope Solution Expanded View

5 3M HFE Liquid Properties The first problem facing fully immersed liquid cooled systems is the choice of the liquid agent, which directly contacts the electronic parts in computers. Although water is almost the best liquid for heat transfer it is also an electrical conductor and would not just damage but completely destroy the motherboard immediately when coming into contact with a live circuit board. Historically speaking some liquid cooled solutions have made use of di-electrical oils (i.e., mineral oils) to work as thermal agents. However, mineral oils are not only poor thermal agents but are also poor fluidity agents and as such the use of mineral oil based systems has remained in the concept stage for many years with little progress. In recent years 3M has developed a family of hydrofluoroether engineered liquids (Novec) that are suitable for electronic cleaning and thermal management. In 2009, Novec was tested by 3M and found to possess the required properties for computer liquid cool applications. The Iceotope Solution is currently the only liquid encapsulated system on the planet that has a market ready product utilising Novec in its design. Molecular Weight Boiling Point (1) Freeze Point (1) Density (2) SHC Thermal Conductivity Unit ( o C) ( o C) Kg/m 3 J/(kg K) W/(m K) Dynamic Viscosity (2) Kinematic Viscosity (2) Thermal Expensive (2) Unit Pa s cst 1/K Table 1 3M Novec Engineered Fluid Properties (1) : At 760 mmhg (2) : At 25 o C Natural Convection Principle Natural convection is a flow mechanism, which usually occurs in a closed environment with a heating and cooling source. When the flow in the closed volume heats up by the surrounding source, the density of the heated fluid changes (usually less dense) would rise up to the top while the cooled fluid drops (usually heavier) to the button. This fluid motion usually forms a loop such that the cooled fluid feeds to the heat source and sustains the motion. Figure 4 Diagram of Density Driven Natural Convection

6 Also by the definition, a fluid with a higher thermal expansion ratio would have a stronger natural convection effect. Novec has quite a high thermal expansion factor of /k, which is relatively high among general liquids. Main Advantage (Thermal) The primary goal of using a liquid cooled solution versus a traditional air cooled solution is the heat transfer efficiency of liquid. Due to the high conductivity properties that liquids usually possess, especially in a system without an air-to-liquid heat exchanger, a pure liquid-to-liquid heat exchanger should have much lower delta temperature. The typical properties of liquids versus air can be seen in the table below: Unit Water Air Novec Density Kg/m SHC J/(kg K) Thermal Conductivity W/(m K) KinematicViscosity (2) cst Thermal Expensive (2) 1/K Specific heat per unit volume J/( m 3 K) Table 2 Thermal Properties (1) : At 760 mmhg (2) : At 25 o C In fact gases also have a very low density (about 1/1000 of which air compares to water), however driving gas (air) flow over an object to take away a certain amount of heat would require pushing a larger volume in a higher speed rather than smaller volume and still be slower than liquid. Another advantage of using liquid as a thermal medium, particularly with those possessing a large thermal expansion ratio, is to use the density driven from natural convection to transport thermal energy rather force convection. As in previously stated the natural convection flow is driven by the density changes of the fluid via temperature difference, it is basically a true free cooling method, which can deliver heat energy over a distance without costing any extra energy. Generally speaking all fluids (gas or liquid) with thermal expansion abilities could offer natural convection, however the driving force of natural convection is usually a small force so the convection flow would be very slow. In such cases air is not ideal to deliver large amounts of heat in low speeds due to its small density, and for this reason Iceotope chose to use Novec in the design of their products. Other Benefits Along with the significant thermal advantage, there are other benefits to using liquid cooled systems. In the Iceotope design the primary coolant is contained in a static condition (state) with static sealing (encapsulation). So there are no motions or extra moving parts required in the primary stage of the system. The Iceotope Solution deployed at the University of Leeds (500kW) requires 64 pumps (N+N) in the server room with only 32 of them in active, compared to a similar air cooled solution which usually has more than 1,000 fans spinning, and the noise level o is almost zero.

7 Another benefit that liquid cooling can offer is that all the motherboards are contained within sealed containers to create fully controlled environments impervious to dust, humidity, pollution and vibration resulting in increased accessibility for the server room as well as the modules (computer nodes) themselves. A final benefit, unique to Iceotope s design, is the option for heat recapture and reuse. Disadvantages Although liquid cooled systems have obvious thermal benefits compares to traditional air cooled systems, the major disadvantages of most liquid cooled solutions on the market today are the sealing and leakage of liquid. In most fully immersed liquid cooled designs the primary cooling stage is forced convection, or in other words pumping liquid from the first stage. In the Iceotope Solution design motion is avoided in the primary loop and natural convection is utilised instead of pumping coolant /forced convection. As such the increased reliability of the Iceotope system improves the reliability in deployment and still manages to pump water through each module and the cabinet itself. Another disadvantage of most liquid cooled systems is the internal pressure inside the system. Consider a typical 42U rack that is approximately 2 meters tall, the water from the top to the bottom would have about 0.2 atm gage pressure. In fact with all the pumping force to accomplish the head loss of the system, the actual pressure inside a liquid cooled system can be up to +/- 0.5 atm gage. Although 0.5 atm is not a very high value in general industrial water circuit system, it is significantly higher than the air pressure of atm which a powerful 120mm turbine cooling fan can general (Delta PFB1212UHE, 252CFM, 45W at 5500RPM) Project Overview This project is based on the review of the Iceotope liquid cooled encapsulated computer server system as a data centre solution. It is the first of its kind and ready for the commercial market, which aims to provide high efficiency data centre solutions with lower PUE s and full time free cooling to data centre operators in any geographic location in the world. In 2012 the University of Leeds was the first user to fully deploy an Iceotope Solution beta system comprised of one cabinet with 11 computing modules + 2X2 PSU modules inside a university lab at the Mechanical Engineering Building. The project focus in this case was to compare between a liquid cooled solution and an identical air cooled solution, which is based on experimental data acquired from the Iceotope Solution versus the university's existing HPC data centre. It is important to note that the Iceotope Solution is a single standalone supercomputer, which is not fully populated, and the university's HPC data centre is a combination of air cooled, back door water-cooled, old servers and new servers, and as such it is not ideal to compare them directly. Real system HPC Centre in Leeds University Iceotope Solution in Leeds University Capacity (W) 480KW (240kW X2) 3KW Computer system Mixture of Sun, Dell and Intel SuperMicro CPU / GPU Intel / AMD / nvidia / Others Intel / AMD Rack cooling method 84kW (28kW X3) Airedale backdoor water cooled 170KW conventional air cooled Fully liquid cooled (Iceotope) External heat exhaust Airedale free cooling Passive air cooled Table 3 Basic Configuration of the HPC Server and Iceotope Solution at the University of Leeds

8 Figure 5 Photo of HPC Servers in the University of Leeds' Server Room Figure 6 Photo of Iceotope Solution in the University of Leeds' Lab

9 Case Study Assumptions have been made in during this project in order to scale up the Iceotope system and make fair comparisons. In this project the fabricated liquid cooled and air cooled systems are based on an identical systems, as noted in the table below. Fabricated System Air Cooled system Liquid Cooled System Capacity (W) 480KW (240kW X2) 480W (240kW X2) Computer system SuperMicro X9D series SuperMicro X9D series CPU / GPU Intel (E5-2620) Intel (E5-2620) Rack cooling method back-door water cooled (Airedale OnRak 28Kw) Fully liquid cooled (Iceotope) External heat exhaust Airedale free cooling Airedale free cooling Table 4 Fabricated System Configurations In the table above the Iceotope Solution has been scaled up to match the same size of the Leeds HPC system, assuming the use of the same motherboard and CPU solutions (SuperMicro X9D with Intel 2620) and the Airedale Ultima Compact Free Cool heat exhaust solution. With such assumptions the only physical difference in the 2 sides would only be the computer and cabinet cooling method, which eventually provides an idea of how much energy efficiency can be saved just by switching the air cooled portion of the data centre for a fully liquid cooled design. System Configuration The air cooled system in this project is based on a typical SuperMicro 2U rack design (CSE217HQ- R1K62MB) with 4 1U motherboards inside a 2U package. In such a configuration it has a typical N+N redundant PSU layout in each computer node, and 4 computer boards towards 1+1 PSU. Figure 7 SuperMicro 2027TR-HTRF+ 2U Rack System (CSE-217HQ-R1K62MB) Computer / PSU Node Layout

10 Figure 8 500kW Air Cooled Data Centre Layout with Chillers, Air Conditioning and Rack Level Backdoor Water-cooling The liquid cooled system is a typical liquid cooled system based on the Iceotope solution with 8 computer nodes and 2+2 PSU nodes in each rack level. Figure 9 Iceotope Liquid Cooled System Computer / PSU Node Layout

11 Figure kW Fully Immersed Liquid Cooled Data Centre Layout Although the air cooled and liquid cooled system has less in common in its layout, they have the same computer node to PSU ratio (4:1), which makes them have identical topology to each other in energy efficiency calculation. Figure 11 SuperMicro Air Cooled Rack Layout (left) Compared to Iceotope Liquid Cooled Rack Layout Energy Cost and Temperature The energy calculation of a typical 10kw rack in both an air cooled system and liquid cooled configuration is demonstrated in the table below, assuming both designs are identical to each other in computing level.

12 Server level IT load Rack level Total Facility Power Type Unit Load (kw) Number Air-cooled energy cost SuperMicro System Cooling Fans X9DTT / Intel Xeon E W 201Gflops 48 X 32 = 1536 Nidec V80E12BS2 23.4W 48 X 32 = 1536 Storage Intel SSD W 48 X 32 = 1536 PSU Super Micro PWS1K62 PSU Fan Rack fan Nidec R40W12BGCA Airedale LogiCool OnRak LOR6042UC % loss X880W=61.6W 24X32= active 15.8W 24X32= active Pump GrundFos Alpha 2L 45W 2X32=64 32 active Telco Equipment D-Link DGS PDU Avocent PM % loss X10.56kW =369.6W UPS CRACs Ventilation APC Symmetra PX 250kW Airedale Ultima Compact Chiller UCFC250D-8/2 Airedale AlpaCoolDF25A / CUS kW 308Tflops kW 1.306kW kW 6.067kW Liquid-cool energy cost kW 308Tflops N/a 1.306kW kW 6.067kW Total load 396.3kW 360.4kW Gflops/W W kW N/a N/a 1.44kW 33.4W 2X32= kW 2.138kW 4% loss X250kW =10kW 79.9kW (Chiller on) 7.824kW (Chiller off) kW kW component kW kW Total load 415.4kW 375.8kW 2 20kW 20kW kW N/a 2 N/a kW 880W kW N/a component 197.4kW kW Total load 612.8kW 412.7kW Total PUE Gflops/W Table 5 Energy Stack-up Data of an Air Cooled Data Centre Compared to a Liquid Cooled Data Centre Notice: The energy data from above is based on both systems running under full load condition. The table above demonstrates that the liquid cooled solution can achieve a PUE of compared to an identical air cooled system, which can achieve a PUE of about In actual fact at the IT level and

13 cabinet level of the liquid solution does not gain a great deal of improvement in energy efficiency, however at the building level when chillers and compressors can be switched off, the liquid cooled system can save a significant amount of energy. As a matter of fact most air conditioning and/or chillers have an EER (Energy Efficiency Rate) of 3 in the full load condition and this can equate to the ideal PUE of the chiller that is no more than 1+ERR / ERR = Dr Jon Summer, Senior Lecturer at the University of Leeds, claims that the HPC data centre in the university requires approximately 100W cooling power to cool down a 250W system with a PUE of 1.4. The reason that liquid cooled system can avoid using chillers is that in a liquid encapsulated system, the liquid to liquid heat exchanger can have extremely low delta temperatures from onstage to another stage. Therefore it does not require chillers and/or compressors to bring down the temperature and create a larger delta temperature. Air-cooled system Liquid-cooled system medium Temperature medium Temperature in out In out Ambient Air 25 o C Air 25 o C Chiller R407c/ water 19 o C 13 o C Water 32 o C 28 o C Building water Water 13 o C 19 o C Water 28 o C 32 o C Ventilation Air / water 22 o C N/a Rack Air 25 o C 45 o C Water 32 o C 38 o C Computer node Air 60 o C Water/ 32 o C 38 o C HFE o C CPU Air 75 o C HFE o C Max delta temperature 63 o C 50 o C Table 6 Temperature Stack-up Data of an Air Cooled Data Centre Compared to a Liquid Cooled Data Centre The table above demonstrates that the temperature related to each part of a data centre both in the air cooled solution and the liquid cooled solution. With the air cooled solution the maximum delta temperature is 13 o C greater than that of the liquid cooled solution, as a result it has to use chillers to generate that extra temperature gap.

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

A-CLASS The rack-level supercomputer platform with hot-water cooling

A-CLASS The rack-level supercomputer platform with hot-water cooling A-CLASS The rack-level supercomputer platform with hot-water cooling INTRODUCTORY PRESENTATION JUNE 2014 Rev 1 ENG COMPUTE PRODUCT SEGMENTATION 3 rd party board T-MINI P (PRODUCTION): Minicluster/WS systems

More information

Holistic, Energy Efficient Datacentre Design @ Cardiff Going Green Can Save Money

Holistic, Energy Efficient Datacentre Design @ Cardiff Going Green Can Save Money Holistic, Energy Efficient Datacentre Design @ Cardiff Going Green Can Save Money Dr Hugh Beedie CTO ARCCA & INSRV The Context Introduction Drivers to Go Green Where does all the power go? Before the equipment

More information

Oil Submersion Cooling for Todayʼs Data Centers. An analysis of the technology and its business implications

Oil Submersion Cooling for Todayʼs Data Centers. An analysis of the technology and its business implications Oil Submersion Cooling for Todayʼs Data Centers An analysis of the technology and its business implications Contents Introduction... 2 Data Center Cooling Technologies... 2 Oil Submersion Cooling... 2

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale

More information

News in Data Center Cooling

News in Data Center Cooling News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase

More information

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres School of something School of Mechanical Engineering FACULTY OF OTHER ENGINEERING Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres A. Almoli 1, A. Thompson 1, N. Kapur 1,

More information

Data Center Environments

Data Center Environments Data Center Environments ASHRAE s Evolving Thermal Guidelines By Robin A. Steinbrecher, Member ASHRAE; and Roger Schmidt, Ph.D., Member ASHRAE Over the last decade, data centers housing large numbers of

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 4, Lancaster University, 2 nd July 2014 Background Data centres estimated to use 2-3% of total electricity consumption in the UK and generate

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Technical Systems. Helen Bedford

Technical Systems. Helen Bedford Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Rittal Liquid Cooling Series

Rittal Liquid Cooling Series Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2013

European Code of Conduct for Data Centre. Presentation of the Awards 2013 European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started

More information

HPC TCO: Cooling and Computer Room Efficiency

HPC TCO: Cooling and Computer Room Efficiency HPC TCO: Cooling and Computer Room Efficiency 1 Route Plan Motivation (Why do we care?) HPC Building Blocks: Compuer Hardware (What s inside my dataroom? What needs to be cooled?) HPC Building Blocks:

More information

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

A Paradigm Shift in Data Center Sustainability Going Beyond Aisle Containment and Economization

A Paradigm Shift in Data Center Sustainability Going Beyond Aisle Containment and Economization A Paradigm Shift in Data Center Sustainability Going Beyond Aisle Containment and Economization A CONTENTS Introduction... 1 Introduction to Oil Submersion Cooling... 2 The CarnotJet System... 3 Conclusion...

More information

TSUBAME-KFC : a Modern Liquid Submersion Cooling Prototype Towards Exascale

TSUBAME-KFC : a Modern Liquid Submersion Cooling Prototype Towards Exascale TSUBAME-KFC : a Modern Liquid Submersion Cooling Prototype Towards Exascale Toshio Endo,Akira Nukada, Satoshi Matsuoka GSIC, Tokyo Institute of Technology ( 東 京 工 業 大 学 ) Performance/Watt is the Issue

More information

Optimization of energy consumption in HPC centers: Energy Efficiency Project of Castile and Leon Supercomputing Center - FCSCL

Optimization of energy consumption in HPC centers: Energy Efficiency Project of Castile and Leon Supercomputing Center - FCSCL European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 12) Santiago de Compostela

More information

Natural Convection. Buoyancy force

Natural Convection. Buoyancy force Natural Convection In natural convection, the fluid motion occurs by natural means such as buoyancy. Since the fluid velocity associated with natural convection is relatively low, the heat transfer coefficient

More information

Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources

Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

The CEETHERM Data Center Laboratory

The CEETHERM Data Center Laboratory The CEETHERM Data Center Laboratory A Platform for Transformative Research on Green Data Centers Yogendra Joshi and Pramod Kumar G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Driving Data Center Efficiency Through the Adoption of Best Practices

Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary

More information

Guide to Minimizing Compressor-based Cooling in Data Centers

Guide to Minimizing Compressor-based Cooling in Data Centers Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi

More information

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Two-Phase Evaporative Precision Cooling Systems

Two-Phase Evaporative Precision Cooling Systems Two-Phase Evaporative Precision Cooling Systems For heat loads from 3 to 300kW Using non-conductive refrigerant fluid, our patented Next-generation, two-phase evaporative precision cooling systems enable

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Improve competiveness of IDC and enterprise data centers with DCIM

Improve competiveness of IDC and enterprise data centers with DCIM Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Energy Efficiency Best Practice Guide Data Centre and IT Facilities 2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

Data Center Energy Consumption

Data Center Energy Consumption Data Center Energy Consumption The digital revolution is here, and data is taking over. Human existence is being condensed, chronicled, and calculated, one bit at a time, in our servers and tapes. From

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center

More information

Blade Server & Data Room Cooling Specialists

Blade Server & Data Room Cooling Specialists SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling

More information

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate: Questions to be responded to by the firm submitting the application Why do you think this project should receive an award? How does it demonstrate: innovation, quality, and professional excellence transparency

More information

Data Centre. Flexible, high efficiency cooling solutions. www.airedale.com CONDITIONING CONDENSING UNITS CONTROLS SERVICE TRAINING

Data Centre. Flexible, high efficiency cooling solutions. www.airedale.com CONDITIONING CONDENSING UNITS CONTROLS SERVICE TRAINING Sector Data Centre Data Centre Flexible, high efficiency cooling solutions IT COOLING PRISION AIR CONDITIONING CHILLERS CONDENSERS & CONDENSING UNITS www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE. Industry leading data center solutions for HPC, Cloud and Enterprise markets.

Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE. Industry leading data center solutions for HPC, Cloud and Enterprise markets. Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE Industry leading data center solutions for HPC, Cloud and Enterprise markets. Leadership, Collaboration & Expertise CooIIT Systems Innovates and Delivers

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

Midas XCI Immersion Cooling. The High Efficiency, High Density, High Performance Data Center Cooling Solution

Midas XCI Immersion Cooling. The High Efficiency, High Density, High Performance Data Center Cooling Solution Midas XCI Immersion Cooling The High Efficiency, High Density, High Performance Data Center Cooling Solution Midas XCI Immersion cooling technology allows you to maximize server density and power efficiency

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

High Performance Computing (HPC) Solutions in High Density Data Centers

High Performance Computing (HPC) Solutions in High Density Data Centers EXECUTIVE REPORT High Performance Computing (HPC) Solutions in High Density Data Centers How s Houston West data center campus delivers the highest density solutions to customers Overview With the ever-increasing

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch

More information

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com. Vicot Solar Air Conditioning V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.cn Cooling, heating, and domestic hot water. Return on investment

More information

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION 1/16 Contents: 1. Introduction: the increasing importance of energy efficiency 1.1 Power consumers in the data

More information

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite

More information

NEC Micro Modular Server Introduction. NEC November 18,2014

NEC Micro Modular Server Introduction. NEC November 18,2014 NEC Micro Modular Server Introduction NEC November 18,2014 Market Trend Cloud Computing Public cloud service market is growing. It is expected over 20% of annual growth. Cloud services used in companies

More information

Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions

Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions Data Centre Solutions... energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2014

European Code of Conduct for Data Centre. Presentation of the Awards 2014 European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Gas Absorption Heat Pumps. Future proofing your heating and hot water

Gas Absorption Heat Pumps. Future proofing your heating and hot water Gas Absorption Heat Pumps Future proofing your heating and hot water Gas Absorption Heat Pumps 1 Contents Gas Absorption Heat Pumps (GAHPs) The heating solution What is a Gas Absorption Heat Pump? How

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Fan Basics and Selection Criteria (How to Use)

Fan Basics and Selection Criteria (How to Use) Feature: Understanding SANYO DENKI Products from Scratch Fan Basics and Selection Criteria (How to Use) Honami Osawa 1. Introduction In recent years, the importance of cooling technology has become even

More information

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER Your Complete Turnkey Server Room Air Condition UPS THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER AVAILABLE IN WATER AND GAS SYSTEM MODEL AIR-CONDITIONED CABINET EXCELLENT TEMPERATURE CONTROL FOR

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is

More information

Submersion Cooling Evaluation

Submersion Cooling Evaluation Submersion Cooling Evaluation ET Project Number: Project Manager: Jeff Beresini Pacific Gas and Electric Company Prepared By: Luke Werner, P.E. Energy Resources Integration (ERI) 251 Donahue St. Sausalito,

More information

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...

More information

White Paper Rack climate control in data centres

White Paper Rack climate control in data centres White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC

More information

System solution for data centres

System solution for data centres 1 System solution for data centres Energy-efficient air conditioning with ServeLine Cooling IT infrastructure, high availability, low energy costs and communication with DCIM systems all in one from your

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Data Centre. Flexible, high efficiency cooling solutions. www.airedale.com CONDITIONING CONDENSING UNITS CONTROLS SERVICE TRAINING

Data Centre. Flexible, high efficiency cooling solutions. www.airedale.com CONDITIONING CONDENSING UNITS CONTROLS SERVICE TRAINING Sector Data Centre Data Centre Flexible, high efficiency cooling solutions IT COOLING PRISION AIR CONDITIONING CHILLERS CONDENSERS & CONDENSING UNITS www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Thermal analysis of liquid immersed electronics for data centres. Abdulmajeed Hamad Almaneea

Thermal analysis of liquid immersed electronics for data centres. Abdulmajeed Hamad Almaneea Thermal analysis of liquid immersed electronics for data centres By Abdulmajeed Hamad Almaneea Submitted in accordance with the requirements for the degree of Doctor of Philosophy The University of Leeds

More information

Critical Infrastructure for the World s Leading Data Centers

Critical Infrastructure for the World s Leading Data Centers Critical Infrastructure for the World s Leading Data Centers 2 YOU MAY KNOW US BY OUR BRAND NAMES THE EXPERTISE OF MANY. THE POWER OF ONE. Nortek Air Solutions provides critical infrastructure for the

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information