Section 4 Page 2. Flow in Pipes

Size: px
Start display at page:

Download "138.255 Section 4 Page 2. Flow in Pipes"

Transcription

1 Flow in Pipes

2 Section 4 Page 2 Flow in Pipes 1.0 INTRODUCTION In this module we are focusing on the fundamental principles of headloss and we learn how to use headloss charts to estimate the headloss in a simple pipe system. HEADLOSS CALCULATION / PIPE SELECTION 2.1 Using the Headloss Charts Once a fluid starts to flow in a pipe there will be a loss of head in the pipe. This shows up as a drop in pressure or a difference in head. Manometer Tubes Headloss Pressure Gauge WATER FLOW Pipe manufacturers make available tables or charts of headloss for different pipes. The information contained in the chart is: the pipe size and usually the pressure rating. the flow rate in litres per second. the rate of headloss in metres of headloss per 1000 m of pipe.

3 Section 4 Page 3 If we know any two of these three items we can determine the third. Thus to determine the pipe size we need to know what flow we want and our allowable rate of headloss. Alternatively if we know the pipe and the flow we can work out what headloss will occur. Exercise 1 A flow of 1 litre per second in a DN40 PN9 Rural Redline pipe will result in what rate of headloss? [The answer is 39 m/1000 m.] Exercise 2 We have 2500 m of DN32 PN9 Polyethylene with a flow of 40 litres per minute, what is the loss of head which occurs? [The answer is 150 m.] Exercise 3 Water is flowing at 70 l/min from a pump. The pump pressure is 455 kpa and the pipe is DN50 PN9 Rural Redline. What will be the head at the end of 350 m of pipe? [The answer is 39.2 m.]

4 Section 4 Page 4 Exercise 4 An existing system has DN25 PN12 Rural Redline pipe. If the headloss is 10 m/1000 m what flow will occur? [The answer is 0.11 litres per second.] 2.2 Head loss in fittings The head loss in fittings is often referred to as minor losses although in some cases this is misleading since the head loss in fittings can be greater than the head loss in the pipe itself. The easiest way to deal with the headloss in fittings is to compute the equivalent length of a fitting ; this is defined as that length of straight pipe which gives the same head loss as the fitting itself. The table below gives equivalent lengths in pipe diameter for each fitting. To use this data we must know what pipe diameter we are working with. For example, if we have a 25 standard elbow the equivalent length = 30 x = 0.75 m. The following table is from an American source and uses some different terminology; therefore set out after it are diagrams of the different fittings mentioned in the table.

5 Section 4 Page 5 Globe valves Angle valves Gate valves Check valves REPRESENTATIVE EQUIVALENT LENGTHS IN PIPE DIAMETER (l/d) OF Conventional Y-pattern Conventional VARIOUS VALVES AND FITTINGS Description of Product Conventional wedge disc, double disc, or plug disc Conventional swing In-line ball Foot valves with strainer Butterfly valves (6inch, and larger) 90 standard elbow 45 standard elbow 90 long radius elbow Fittings 90 street elbow 45 street elbow Square corner elbow Standard tee Standard tee With no obstructions in flat, bevel, or plug-type seat With wing or pin-guided disc. No obstruction in flat, bevel, or plug-type seal. With stem 60 from run of pipe line With stem 45 from run of pipe line With no obstruction in flat, bevel, or plug-type seat With wing or pin-guided disc. With poppet lift type disc With flow through run With flow through branch Fully open Fully open Fully open Fully open Fully open Fully open Equivalent Length in Pipe Diameters (l/d) Fully open 13 Fully open 135 Fully open 150 Fully open 420 Fully open

6 Section 4 Page 6 Figure 1: Types of Valves

7 Section 4 Page 7 Example: A piggery water system consists of 150 m of DN25 PN15 upvc pipe and includes 25 elbows, 6 gate valves (fully open) and 5 tees (with flow through run). If the system was to carry 40 litres per minute what would be the total headloss? First calculate the equivalent length of straight pipe. Equivalent length = Straight pipe : 150 m 25 elbows : 25 x 30 x : 18.8 m 6 gate valves : 6 x 13 x : 2.0 m 5 tees : 5 x 20 x : 2.5 so, equivalent length = 173 m

8 Section 4 Page 8 For DN25 PN15 40 litres per minute the rate of headloss is : 53 m/1000 m so total headloss = 53 x 173/1000 = 9.18 m. Exercise 5 A pipeline consists of 15 elbows, 2 gate valves (fully open) and 700 m of DN40 PN12 upvc pipe. If the flowrate is to be 60 litres/minute what will be the total headloss? (57m) 2.3 Residual Head When water flows from a pipe its pressure is the same as that of the atmosphere; therefore all the pressure (or head) is used up as it flows through the pipe. That is to say, when we turn on a hose the flow increases until it reaches a level whereby all the available head is used up by the time the water reaches the end of the pipe. Now if there is a ballcock, or any sort of valve, on the end of the pipe then some head will be lost when water flows through it. To accommodate this requirement the concept of residual head is used, it is the head which must be left over at the end of the pipeline so that it can be used up as the water flows through the fitting. The following residual heads are recommended:

9 Section 4 Page 9 Water Outlet Fitting Flow l/min Residual Head m. Trough valve 45 3 Trough valve 82 7 Trough valve Yard washdown (Nozzle size must match pump) 180/ Domestic shower 9 5/7 Garden hose 12 15/ SELECTION OF PIPE SIZE In designing a water system, the prime tasks are to decide what size and type of pipe to use and what pump to use. The method used does depend on what sort of system we are designing for. 3.1 Natural Gravity Systems To determine the pipe type and size we need to know the flow, the allowable rate of headloss, and the maximum head which will occur. The maximum head will be the difference in height between the highest and lowest points of the pipeline; with the maximum head occurring in the pipeline when there is no flow. We can then determine the pressure rating of the pipe required. To determine the maximum allowable rate of headloss we first work out how much head there is available for headloss and then divide it by the number

10 Section 4 Page 10 of 1000 m of pipe. Then using this number and the desired flow we go to the headloss chart and determine the pipe size. Example: A tank on a hill supplies water to 3 troughs. The lowest trough is 35 m below the base of the tank. It is also the farthest away at a distance of 900 m. The flow must be 60 litres/minute. What size and type of pipe should be used? Solution: The maximum working head is 35 m, this is low so we will try MDPE. (Greenline) The head available for headloss = 35 m The maximum allowable rate of headloss = 35/(900/1000) = 35/0.90 = 38.9 m per 1000 m go to headloss chart for MDPE (Greenline) Enter at 1.0 litre per second go up until you meet the line for 38.9 m/1000 m. Take the next biggest pipe below this point. The head loss for a 40mm pipe is approx 39m., so we must go to next size of pipe, but notice from the chart how the pressure rating of the pipe changes with size. What should be done? Exercise 1 A tank is situated on a hill 73 m above a cowshed. If the flowrate to washdown the yard is to be 5 l/s and the pipeline is 850 m long, what size of Black n Blue pipe should be used?

11 Section 4 Page 11 [The answer is 63 mm] Exercise 2 A tank is to deliver water to a house sited 25 m below the level of the tank. If the house is 450 m away and it requires a peak flow of 30 litres/minute and a residual head of 7 m what pipe would you install? Check all three common types, then justify your decision. [The answer is DN32 PN6.3 Greenline, DN32 PN9 Rural Redline,] 3.2 PUMPED GRAVITY SYSTEMS Falling Main In the case of the falling main system we have two pipelines to design. Firstly, the pipe the water is pumped to the tank in, and secondly, the pipe the water goes from the tank to the outlets in. The pipe from the tank to the outlets is in fact a gravity system and so the procedure in 3.1 above is used. For the pipe from the pump to the tank we use the following procedure: determine the static head, this is the head which exists when no water is flowing. It is usually the difference in height between the two ends of the pipe. It represents the height through which the pump must push the water; determine the design flow; determine the head which the pump delivers at the design flow; determine the residual head required, if any; determine the head available for headloss: head available for head loss = pump head static head residual head. determine the maximum allowable rate of headloss in m/1000 m. go to the head loss chart to select a pipe.

12 Section 4 Page 12 Example: A pump delivers 60 litres/minute at a head of 55 m. The water is to be delivered to a tank 35 m above the pump and 700 m away; a residual head of 5 m is required, select a suitable pipe. The static head = 35 m Design flow = 60 litres/minute = 1.0 l/s Pump head = 55 m Residual head = 5 m Head available for head loss = = 15 m Maximum allowable rate of head loss = = 21.4 m/1000 m The pipe has to withstand a head of 55 m. for Rural Redline use DN50 PN9. Exercise 3 A pump is to deliver 50 litres/minute to a tank 50 m above the pump and 1200 m away from the pump. The pump head is assumed to be 75 m and a residual head of 5 m is needed at the tank, determine the pipe to be used. [The answer is DN50 PN9 Rural Redline]

13 Section 4 Page 13 Exercise 4 You are to select a pump to deliver water to a tank, there are no off-takes along the pipeline. The pump is to be at an elevation of 42 m and the tank is at an elevation of 88 m. The pump will be controlled by probes in the tank. The tank is 2 m high. The pipeline is DN40 PN9 Rural Redline, and is 2.4 km long. The elevation of the water source is 42 m. The desired flow is 30 l/minute. What head must the pump produce at the desired flow? [74.4m] Rising Main In this case we do two design checks. One when the rising main has the pump working and one when it is not working (and is therefore a gravity pipeline). Example: A rising main is to deliver a flow of 40 litres/minute when the pump is running and is to deliver a peak flow of 60 litres/minute as a gravity pipeline. The static head is 50 m and the pump head is 65 m; no residual head is required and the pipeline is 750 m long. Select a suitable pipe. Maximum working head = 65 m (when pump is running) for gravity pipeline: Head available for headloss = 50 m Maximum allowable rate of headloss = = 66.7 m/1000 m. at 60 litres/minute and 66.7 m/1000 m

14 Section 4 Page 14 pipe selected is: DN40 PN9 Rural Redline, or, DN32 PN12 upvc Now check these pipes for the pump running situation. Design flow = 40 litres/minute. Head available for head loss = = 15 m Maximum allowable rate of headloss = = 20 m/1000 m at 40 litres/minute and 20 m/1000 m pipe selected is: DN40 PN9 Rural Redline (very close to being on the line). NOTE: the reason for the difference in flows is that the pump can fill the tank over a longer period of time than the peak flow occurs for. Exercise 5 A rising main pumped gravity system is to deliver 40 litres/minute when acting as a gravity system and 30 litres/minute when the pump is running. If the tank is 600 m away and 30 m above the pump, (pump head = 45m) what pipe would you install?

15 Section 4 Page 15 Exercise 6 You are to replace an existing piston pump and pipe in a rising main system. The piston pump was a MacEwans H3 delivering 800 gph with a cut-in pressure of 105 psi and a cut-out pressure of 125 psi. The static head is 40 m. The pipeline is 750 m long. A 20 mm trough valve is installed at the inlet to the tank; the water source is another tank immediately beside the pump site. Select a new pipe and specify the pump head that will be required. 3.3 Hydropneumatic Systems For these systems the method is essentially the same as for the pipeline from the pump to the tank in a falling main system. Thus the steps are: determine the static head between the pump and the highest outlet. determine the design flow. determine the pump head, this is usually the cut-in pressure. determine the residual head required. determine the head available for headloss head available for headloss = pump head static head residual head. determine the maximum allowable rate of headloss in m/1000 m. determine the maximum working head; this is the cut-out pressure if the pump is at the lowest point in the system. If the pipe runs down hill from the pump, the maximum working head is the cut-out pressure (expressed as a head) plus the static head between the pump and the lowest outlet. go to the headloss chart to select a pipe.

16 Section 4 Page 16 Exercise 7 A very independent dairy farmer recently needed to upgrade his water supply because he had purchased a neighbouring farm. He purchased a bigger pump believing that this would solve his problems, which it did not. You have been asked to solve his problem but he has indicated that he doesn t want to buy yet another new pump. The design flow in the mainline to the cowshed is 146 l/min. The pump is 2 m lower in elevation than the cowshed and a residual head of 35 m is required at the cowshed. Assume that the new pump will deliver the design flow at a pressure of 650 kpa and that the cut-out pressure is 700 kpa. Select a mainline pipe to run from the pump to the cowshed; the pipeline is 650 m long. [The answer is DN63 PN9 Rural Redline] Exercise 8 A hydropneumatic system is to be used to deliver 65 litres/minute peak flow on a farm which rises from a river (the water source) to an elevation 20 m above the river flats. The pump is on the river flats. It has been determined that the main pipeline will be 2400 m long and that the cut-out pressure will be 80 psi and the cut-in pressure will be 60 psi; it is assumed that the pump will deliver 65 litres/minute at the cut-in pressure. A residual head of 5 m is required. Select a suitable pipe for the mainline and then select a pump for this application. [The answer is DN63 PN9 Rural Redline.]

SIZING OF WATER PIPING SYSTEM

SIZING OF WATER PIPING SYSTEM SIZING OF WATER PIPING SYSTEM SECTION E101 GENERAL E101.1 Scope. E101.1.1 This appendix outlines two procedures for sizing a water piping system (see Sections E103.3 and E201.1). The design procedures

More information

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes

More information

SIZING AND CAPACITIES OF GAS PIPING

SIZING AND CAPACITIES OF GAS PIPING APPENDIX A (IFGS) SIZING AND CAPACITIES OF GAS PIPING (This appendix is informative and is not part of the code.) A.1 General. To determine the size of piping used in a gas piping system, the following

More information

Fluid Dynamics Basics

Fluid Dynamics Basics Fluid Dynamics Basics Bernoulli s Equation A very important equation in fluid dynamics is the Bernoulli equation. This equation has four variables: velocity ( ), elevation ( ), pressure ( ), and density

More information

Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29

Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29 _02 A centrifugal with a 12 in. diameter impeller requires a power input of 60 hp when the flowrate is 3200 gpm against a 60 ft head. The impeller is changed to one with a 10 in. diameter. Determine the

More information

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS 1 WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS Please read and follow all these instructions carefully before proceeding with the installation,

More information

Minor losses include head losses through/past hydrants, couplers, valves,

Minor losses include head losses through/past hydrants, couplers, valves, Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within

More information

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As

More information

123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com

123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com 123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com INTRODUCTION The purpose of this manual is to assist you in the assembly, operation and maintenance of your sprayer

More information

SIZING AND CAPACITIES OF GAS PIPING (Not Adopted by the State of Oregon)

SIZING AND CAPACITIES OF GAS PIPING (Not Adopted by the State of Oregon) (IFGS) SIZING AND CAPACITIES OF GAS PIPING (Not Adopted by the State of Oregon) (This appendix is informative and is not part of the code. This appendix is an excerpt from the 2006 International Fuel Gas

More information

SIZING AND CAPACITIES OF GAS PIPING

SIZING AND CAPACITIES OF GAS PIPING CALIFORNIA RESIDENTIAL CODE MATRIX ADOPTION TABLE APPENDIX A SIZING AND CAPACITIES OF GAS PIPING (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state

More information

CHAPTER II. This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192.

CHAPTER II. This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192. CHAPTER II REGULATOR AND RELIEF DEVICES This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192. BASIC CONCEPT In understanding

More information

How To Launch A Rocket From A Formica

How To Launch A Rocket From A Formica Building the Basic Bottle Rocket Launch Pad Materials: -Formica double-sink countertop cutout. This can be easily and cheaply obtained from a local company that manufactures and/or installs countertops.

More information

367 000 Suction assembly for 1.000 l IBC and 205 l drums 1.060 mm suction tube. 367 003 Suction assembly for tanks 1.600 mm suction tube.

367 000 Suction assembly for 1.000 l IBC and 205 l drums 1.060 mm suction tube. 367 003 Suction assembly for tanks 1.600 mm suction tube. PUMPMASTER 2 accessories, other MOBILE oil dispensers PumpMaster 2 Accessories 01 OIL PUMPS 360 1 360 120 367 000 367 011 369 910 360 1 Wall bracket 360 120 Floor bracket 360 001 Bung adaptors 2" (M) connection

More information

WC flushing cistern single or dual flush 0.13 0.05 2 to fill in 2 minutes WC trough cistern 0.15 per WC 0.10 2 Wash basin tap size 1 2

WC flushing cistern single or dual flush 0.13 0.05 2 to fill in 2 minutes WC trough cistern 0.15 per WC 0.10 2 Wash basin tap size 1 2 HAC_C0.qxd 7/4/08 9: Page 74 Chapter Pipe sizing Pipes and fittings should be sized so that the flow rates for individual draw-offs are equal to the design flow rates shown in table.. During simultaneous

More information

Complete Systems & Parts Automatic Oiler & Grease Bank

Complete Systems & Parts Automatic Oiler & Grease Bank MADE IN THE USA Complete Systems & Parts Automatic Oiler & Grease Bank www.gosuburban.com 2 Lubrication Systems Lubrication Systems, a division of Suburban Manufacturing, manufactures a complete line of

More information

Pipe Flow Expert. Verification of Calculation Results

Pipe Flow Expert. Verification of Calculation Results http://www.pipeflow.com Pipe Flow Expert Fluid Flow and Pressure Loss Calculations Software Verification of Calculation Results Table of Contents Results Data: Systems Solved by Pipe Flow Expert Introduction...

More information

Goulds Water Technology

Goulds Water Technology APPLICATIONS Specifically designed for: Homes Farms Cottages Booster service SPECIFICATIONS Pump: Pipe connections: 1¼" NPT suction, 1" NPT discharge, 1" NPT drive (pressure) Pressure switch: AS4 preset

More information

Pacific Pump and Power

Pacific Pump and Power Pacific Pump and Power 91-503 Nukuawa Street Kapolei, Hawaii 96707 Phone: (808) 672-8198 or (800) 975-5112 Fax: (866) 424-0953 Email: sales@pacificpumpandpower.com Web: www.pacificpumpandpower.com Pumps

More information

Vacuum Control. Vacuum Applications. Vacuum Regulators. Vacuum Breakers (Relief Valves) Vacuum Control Devices. Vacuum Terminology

Vacuum Control. Vacuum Applications. Vacuum Regulators. Vacuum Breakers (Relief Valves) Vacuum Control Devices. Vacuum Terminology Vacuum Applications Vacuum regulators and breakers are widely used in process plants. Conventional regulators and relief valves might be suitable for service if applied correctly. This section provides

More information

VAD. Variable Area Desuperheaters

VAD. Variable Area Desuperheaters Desuperheater overview Steam used in process plants can be superheated, that is, heated to a temperature above saturation. The excess of temperature above its saturation is called 'superheat'. Desuperheated

More information

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style

More information

lifting stations motralec

lifting stations motralec 3.0 lifting stations motralec 4 rue Lavoisier. ZA Lavoisier. 95223 HERBLAY CEDEX Tel. : 01.39.97.65.10 / Fax. : 01.39.97.68.48 Demande de prix / e-mail : service-commercial@motralec.com www.motralec.com

More information

VAD Variable Area Desuperheaters

VAD Variable Area Desuperheaters Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

FLUID FLOW Introduction General Description

FLUID FLOW Introduction General Description FLUID FLOW Introduction Fluid flow is an important part of many processes, including transporting materials from one point to another, mixing of materials, and chemical reactions. In this experiment, you

More information

AURORA. 1030 AND 1040 Series SUCTION DIFFUSERS, COMBINATION AND TRIPLE DUTY VALVES WWW.AURORAPUMP.COM

AURORA. 1030 AND 1040 Series SUCTION DIFFUSERS, COMBINATION AND TRIPLE DUTY VALVES WWW.AURORAPUMP.COM UROR 1030 ND 1040 Series SUCTION DIFFUSERS, COMINTION ND TRIPLE DUTY VLVES WWW.URORPUMP.COM UROR 1030 ND 1040 Series Suction Diffusers, Combination and Triple Duty Valves Designed for Direct Mounting on

More information

MFP14, MFP14S and MFP14SS Automatic Pumps

MFP14, MFP14S and MFP14SS Automatic Pumps Page 1 of 6 TI-P136-02 ST Issue 12 Cert. No. LRQ 0963008 ISO 9001, S and SS utomatic Pumps Description The Spirax Sarco automatic pump is a displacement receiver operated by steam or compressed air. It

More information

HS-901(A) BASIC STEAM HEATING SYSTEMS

HS-901(A) BASIC STEAM HEATING SYSTEMS HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,

More information

Pipe Sizes For Water Distribution System Design

Pipe Sizes For Water Distribution System Design Appendix D Pipe Sizes For Water Distribution System Design D-. This appendix contains information to help determine pipe sizes when designing a water distribution system. Use Table D- and Tables D- through

More information

Practice Tests Answer Keys

Practice Tests Answer Keys Practice Tests Answer Keys COURSE OUTLINE: Module # Name Practice Test included Module 1: Basic Math Refresher Module 2: Fractions, Decimals and Percents Module 3: Measurement Conversions Module 4: Linear,

More information

REGISTRATION EXAMINATION, JUNE 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

REGISTRATION EXAMINATION, JUNE 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours Affix label with Candidate Code Number here. If no label, enter candidate Number if known No. 99 REGISTRATION EXAMINATION, JUNE 009 PLUMBING INSTRUCTIONS QUESTION AND ANSWER BOOKLET Time allowed THREE

More information

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. MULTIPOINT Please read and understand these instructions before starting work. Please leave this leaflet

More information

123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com

123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com 123 Industrial Loop Road Paynesville, MN 56362 Phone: 1-800-864-1649 www.master-mfg.com INTRODUCTION The purpose of this manual is to assist you in the assembly, operation and maintenance of your sprayer

More information

Installation, Maintenance, & Repair Series 4000B/LF4000B

Installation, Maintenance, & Repair Series 4000B/LF4000B Installation, Maintenance, & Repair Series 4000B/LF4000B Reduced Pressure Zone Assemblies Sizes: 1 2" 2" (15 50mm) RP/IS-A-4000B 4000B/LF4000B Size: 3 /4"! WARNING Testing Read this Manual BEFORE using

More information

Visage. Digital. Digital diverter. Installation guide. Visage Digital diverter installation instructions Page 1

Visage. Digital. Digital diverter. Installation guide. Visage Digital diverter installation instructions Page 1 Visage Digital Digital diverter TM Installation guide Visage Digital diverter installation instructions Page 1 Visage Digital diverter Visage Digital concealed with adjustable and fixed head Visage Digital

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 4 DIRECTIONAL CONTROL VALVES The material needed for outcome 2 is very extensive

More information

Pressure drop in pipes...

Pressure drop in pipes... Pressure drop in pipes... PRESSURE DROP CALCULATIONS Pressure drop or head loss, occurs in all piping systems because of elevation changes, turbulence caused by abrupt changes in direction, and friction

More information

Pipe Sizing for Commercial and Industrial Natural Gas at Operating Pressures 75 mbar

Pipe Sizing for Commercial and Industrial Natural Gas at Operating Pressures 75 mbar Pipe Sizing for ommercial and Industrial Natural Gas at Operating Pressures 75 mbar These notes form part of the gas safety training programme from RD Training (Midland) Ltd. They are for information only

More information

PRESSURE REDUCING CONTROL VALVE

PRESSURE REDUCING CONTROL VALVE Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line

More information

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS GAP.14.1.2.2 A Publication of Global Asset Protection Services LLC WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS INTRODUCTION A hydrant or other large-volume flow test is necessary for proper water

More information

1. Description. 2. List of Accessories included A B C F G H

1. Description. 2. List of Accessories included A B C F G H 1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin. The unit will start automatically. Please pay particular attention to the following: Possible danger to

More information

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids Dr. J. M. Meyers Dr. D. G. Fletcher Dr. Y. Dubief 1. Introduction Last lab you investigated flow loss in a pipe due to the roughness

More information

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS 2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS Water system improvements proposed for inclusion into Western s service area shall be designed in accordance with all appropriate AWWA standards, include

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

Waste Oil Handling, Spill Containment & Lighting

Waste Oil Handling, Spill Containment & Lighting 58 Waste Oil Handling, Spill Containment & Lighting 372000 SAMOA Mobile Waste Oil Drainer & Extractor Drains and/or extracts waste oil from cars and light commercial vehicles Drain bowl capacity of 20

More information

This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink.

This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. 1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. The unit will start automatically. Please pay particular

More information

Vickers. Check Valves. Check Valves. Inline, right angle, manifold mounted, and pilot operated designs. Released 9/93

Vickers. Check Valves. Check Valves. Inline, right angle, manifold mounted, and pilot operated designs. Released 9/93 Vickers Check Valves Check Valves Inline, right angle, manifold mounted, and pilot operated designs Released 9/93 645 Introduction Vickers inline, right-angle, and manifold mounted check valves are direct

More information

British Standard Underground Hydrant Range

British Standard Underground Hydrant Range British Standard Underground Hydrant Range 2 THE NEW AVK BRITISH STANDARD HYDRANT RANGE AVK are the renowned market leading innovators, manufacturers and suppliers of BS 750 fire hydrants into the UK,

More information

INTERNATIONAL FIRE TRAINING CENTRE FIREFIGHTER INITIAL PUMPS AND PRIMERS. Throughout this note he means he/she and his means his/hers.

INTERNATIONAL FIRE TRAINING CENTRE FIREFIGHTER INITIAL PUMPS AND PRIMERS. Throughout this note he means he/she and his means his/hers. INTERNATIONAL FIRE TRAINING CENTRE FIREFIGHTER INITIAL PUMPS AND PRIMERS Throughout this note he means he/she and his means his/hers. Areas of bold type are considered to be of prime importance. INTRODUCTION

More information

HYDRAULICS AND HWH SYSTEMS

HYDRAULICS AND HWH SYSTEMS HYDRAULICS AND HWH SYSTEMS 1. PREFACE This is a discussion of basic hydraulics which can help with the diagnostics and repair of HWH hydraulic leveling and room extension systems. The first section of

More information

BERMAD Waterworks. Pressure Reducing Valve. 700 Series. Model 720. Features and Benefits. Major Additional Features

BERMAD Waterworks. Pressure Reducing Valve. 700 Series. Model 720. Features and Benefits. Major Additional Features Pressure Reducing Valve Flow and leakage reduction Cavitation damage protection Throttling noise reduction Burst protection System maintenance savings The Pressure Reducing Valve is a hydraulically operated,

More information

ENGINEERING REPORT FOR PAIES WATER SUPPLY SYSTEM KlTTl MUNICIPALITY, SECTION I, POHNPEI FEDERATED STATES OF MICRONESIA

ENGINEERING REPORT FOR PAIES WATER SUPPLY SYSTEM KlTTl MUNICIPALITY, SECTION I, POHNPEI FEDERATED STATES OF MICRONESIA ENGINEERING REPORT FOR PAIES WATER SUPPLY SYSTEM KlTTl MUNICIPALITY, SECTION I, POHNPEI FEDERATED STATES OF MICRONESIA Ulla Mogensen SOPAC Secretariat May 1996 SOPAC Technical Report 230 Prepared for the

More information

Design Information. Designing Your Dust Collection System. Typical dust or fume collection system

Design Information. Designing Your Dust Collection System. Typical dust or fume collection system Design Information Designing Your Dust Collection System There are five simple steps to designing an effective and efficient dust collection system. 1. Draw a floor plan of your shop Important Terms to

More information

Blowdown vessels Meeting the requirements of HSE PM60

Blowdown vessels Meeting the requirements of HSE PM60 Blowdown vessels Meeting the requirements of HSE PM60 BDV60 blowdown vessels complete range of equipment for the safe disposal of boiler blowdown Boiler blowdown Steam boilers must be blown down to remove

More information

TD10. Selecting Circulators. Technical Documents. Taco Radiant Made Easy Application Guide STEP 1: ESTABLISH THE TARGET FLOW RATE FOR THE SYSTEM

TD10. Selecting Circulators. Technical Documents. Taco Radiant Made Easy Application Guide STEP 1: ESTABLISH THE TARGET FLOW RATE FOR THE SYSTEM EFFECTIVE:August, Taco Radiant Made Easy Application Guide Selecting Circulators Technical Documents TD SUPERSEDES: New This article shows you how to select a Taco circulator that lets the hydronic system

More information

BERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features

BERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features Pressure Relief/Sustaining Valve Prioritizing pressure zones Ensuring controlled pipeline fill-up Preventing pipeline emptying Pump overload & cavitation protection Safeguarding pump minimum flow Excessive

More information

BERMAD Waterworks. High Pressure, Surge Anticipating Control Valve. 800 Series. Model 835-M. Features and Benefits. Major Additional Features

BERMAD Waterworks. High Pressure, Surge Anticipating Control Valve. 800 Series. Model 835-M. Features and Benefits. Major Additional Features High Pressure, Surge Anticipating Control Valve Eliminates surge in all pumping systems: Booster & deep well, single & variable speed Eliminates surge in all distribution networks: Municipal, high-rise

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15062 STEAM AND CONDENSATE PIPING PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Comply with the provisions of the following: 1.2 DESIGN CRITERIA 1. ASME B 31.9 Building Services Piping : for

More information

08.09. Triple Service Valve Assembly

08.09. Triple Service Valve Assembly SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS Victaulic Tri-Service valve is an assembly (shipped as individual components) of a standard Victaulic butterfly or Vic-Plug valve and a check valve. This combination

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 3 HYDRAULIC AND PNEUMATIC MOTORS The material needed for outcome 2 is very extensive

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2. May 3, 2013 Foam 138a 1. DESCRIPTION Chemguard Water Powered Oscillating Monitors are designed to automatically discharge over a specific design area upon system activation. These are suitable for use

More information

PREPIPED LIQUID FUEL MANIFOLDS PLPM

PREPIPED LIQUID FUEL MANIFOLDS PLPM PREPIPED LIQUID FUEL MANIFOLDS PLPM INSTRUCTIONS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components,

More information

Morrison Bros. Co. General Product Specifications

Morrison Bros. Co. General Product Specifications Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage

More information

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE

More information

MASTER CYLINDER. Section 2. Master Cylinder. Tandem Master Cylinder. Master Cylinder

MASTER CYLINDER. Section 2. Master Cylinder. Tandem Master Cylinder. Master Cylinder MASTER CYLINDER Master Cylinder The master cylinder converts the motion of the brake pedal into hydraulic pressure. It consists of the reservoir tank, which contains the brake fluid; and the piston and

More information

I. Introduction. 10 minutes

I. Introduction. 10 minutes I. Introduction 10 minutes Introduction (1 of 2) An uninterrupted water supply is: The primary weapon for extinguishment Essential for fire fighter safety Ensuring a dependable water supply is a critical

More information

Conversions between the common units of length used in the Imperial system are listed below 12 in = 1 ft 3 ft = 1 yard 1760 yards = 1 mile

Conversions between the common units of length used in the Imperial system are listed below 12 in = 1 ft 3 ft = 1 yard 1760 yards = 1 mile THE METRIC SYSTEM The metric system or SI (International System) is the most common system of measurements in the world, and the easiest to use. The base units for the metric system are the units of: length,

More information

a cannonball = (P cannon P atmosphere )A cannon m cannonball a cannonball = (P cannon P atmosphere ) πd 2 a cannonball = 5.00 kg

a cannonball = (P cannon P atmosphere )A cannon m cannonball a cannonball = (P cannon P atmosphere ) πd 2 a cannonball = 5.00 kg 2.46 A piston/cylinder with a cross-sectional area of 0.01 m 3 has a mass of 100 resting on the stops as shown in the figure. With an outside atmospheric pressure of 100 kpa what should the water pressure

More information

Session 2: Hot Water Supply

Session 2: Hot Water Supply MEBS6000 Utility Services http://www.hku.hk/mech/msc-courses/mebs6000/index.html Session 2: Hot Water Supply Dr. Benjamin P.L. Ho Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

Class A Foam Mixing and Application Equipment

Class A Foam Mixing and Application Equipment Class A Foam Mixing and Application Equipment Adding Phos-Chek Class A foam concentrate to water: There are many methods of adding Phos-Chek Class A foam concentrate to water. The different methods have

More information

CRANE. Σελίδα 1 από 2. Dimensions and Weights. Weight (kg) Size

CRANE. Σελίδα 1 από 2. Dimensions and Weights. Weight (kg) Size CRANE Σελίδα από 2 DM93 Variable Orifice Double Regulating Valve PN6 Cast Iron Balancing Valve (VODRV), Flanged to BSEN 92-2 The DM93 variable orifice double regulating valves will give satisfactory performance

More information

REGISTRATION EXAMINATION, NOVEMBER 2013 CERTIFYING PLUMBER ANSWER SCHEDULE

REGISTRATION EXAMINATION, NOVEMBER 2013 CERTIFYING PLUMBER ANSWER SCHEDULE No. 9195 REGISTRATION EXAMINATION, NOVEMBER 2013 CERTIFYING PLUMBER ANSWER SCHEDULE Plumbers, Gasfitters and Drainlayers Board, 2013. All rights reserved. No part of this publication may be reproduced

More information

Product catalogue, pipe and sewer cleaning systems

Product catalogue, pipe and sewer cleaning systems Product catalogue, pipe and sewer cleaning systems Nozzles Rotorjet trolley Hose reels Cleaning devices www.hammelmann.com Contents (Navigation via Bookmarks) Rotorjet trolley Rotary joints, spray pipes

More information

STABITHERM INSTALLATION & SERVICE BOOKLET

STABITHERM INSTALLATION & SERVICE BOOKLET STABITHERM INSTALLATION & SERVICE BOOKLET TABLE OF CONTENTS Introduction...3 Warranty...3 Product Range and Physical Description...4 Method of Operation...5 Recommended Pressures and Temperatures...6 Flow

More information

Fluid Flow in Pipes The Darcy-Weisbach Equation and the Fluid-Flow Calc v1.0 Tool for Engineers

Fluid Flow in Pipes The Darcy-Weisbach Equation and the Fluid-Flow Calc v1.0 Tool for Engineers Fluid Flow in Pipes The Darcy-Weisbach Equation and the Fluid-Flow Calc v1.0 Tool for Engineers by Lawrence H. Smith, Sr., P.E. Copyright 2011 Lawrence H. Smith, Sr., P.E. www.suncam.com Copyright 2011

More information

Builder Specifications for Solar Ready Homes

Builder Specifications for Solar Ready Homes Builder Specifications for Solar Ready Homes This document specifies the essential elements required to make a new home ready for the future installation of roof-mounted solar domestic hot water and photovoltaic

More information

AIR LINE VALVES AND GAUGES

AIR LINE VALVES AND GAUGES AIR LINE VALVES AND GAUGES INGERSOLL-RAND AIR LINE VALVES AND GAUGES Maintaining consistent air pressure throughout the entire system is crucial for maximum performance and productivity. Ingersoll-Rand

More information

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

3, 4, 6 & 8 Model H Series Alarm Check Valve Installation and Maintenance Guide ", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,

More information

Technical Solution Sheet 5.03 5: Cold Water Plumbing

Technical Solution Sheet 5.03 5: Cold Water Plumbing 5: Cold Water Plumbing Drawings of Typical Water and Fire Services, Pipe Materials and Private Service AIM The aim of this technical solution is to inform practitioners on the typical requirements for

More information

Uni-Quick Duct System. Moveable. Uni-Quick. Duct System. DUST COLLECTION and MATERIAL HANDLING APPLICATIONS a McGill AirFlow product

Uni-Quick Duct System. Moveable. Uni-Quick. Duct System. DUST COLLECTION and MATERIAL HANDLING APPLICATIONS a McGill AirFlow product United McGill products Uni-Quick TM An enterprise of United McGill Corporation Family owned and operated since 1951 Moveable Duct System DUST COLLECTION and MATERIAL HANDLING APPLICATIONS a McGill AirFlow

More information

Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves

Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves CRANE Energy Flow Solutions TM Donald H. Johnson Crane Energy Flow Solutions 1 Crane Co. Resolution Made By Richard Teller

More information

CO 2 41.2 MPa (abs) 20 C

CO 2 41.2 MPa (abs) 20 C comp_02 A CO 2 cartridge is used to propel a small rocket cart. Compressed CO 2, stored at a pressure of 41.2 MPa (abs) and a temperature of 20 C, is expanded through a smoothly contoured converging nozzle

More information

SunMaxx Solar Filling Station Operating Instructions

SunMaxx Solar Filling Station Operating Instructions SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...

More information

Style 07 Zero Flex Rigid Coupling. Style 75 Flexible Coupling. Style 77 Flexible Coupling 11. Description

Style 07 Zero Flex Rigid Coupling. Style 75 Flexible Coupling. Style 77 Flexible Coupling 11. Description Style 07 Zero Flex Rigid Coupling The unique angled pad design adjusts to standard pipe tolerances to positively clamp the pipe to resist flexural and torsional loads. Working pressures are based on standard

More information

TYPE E Main Valve Sizes 3 /8 through 12

TYPE E Main Valve Sizes 3 /8 through 12 SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,

More information

OUTCOME 1 STATIC FLUID SYSTEMS TUTORIAL 1 - HYDROSTATICS

OUTCOME 1 STATIC FLUID SYSTEMS TUTORIAL 1 - HYDROSTATICS Unit 41: Fluid Mechanics Unit code: T/601/1445 QCF Level: 4 Credit value: 15 OUTCOME 1 STATIC FLUID SYSTEMS TUTORIAL 1 - HYDROSTATICS 1. Be able to determine the behavioural characteristics and parameters

More information

MAINTENANCE MANUAL INDEX DOUBLE CHECK ASSEMBLIES MODELS 850 & 850U 1/2" - 2"

MAINTENANCE MANUAL INDEX DOUBLE CHECK ASSEMBLIES MODELS 850 & 850U 1/2 - 2 MAINTENANCE MANUAL INDEX DOUBLE CHECK ASSEMBLIES MODELS 850 & 850U 1/2" - 2" FEATURES AND OPERATING PROCEDURES VANDALISM GENERAL SERVICE PROCEDURES CUT-A-WAY DRAWING TROUBLE SHOOTING PROCEDURES CHECK MODULE

More information

Pump Ratio and Performance Charts

Pump Ratio and Performance Charts Pump Ratio and Performance Charts Concept and Theory Training Table of Contents Introduction... 1 Overview... 1 How to use this Module... 2 Learning Objectives...2 Text...2 Charts, Illustrations...2 Progress

More information

A basic introduction to steam

A basic introduction to steam A basic introduction to steam FOR HOT, COLD, MOIST AND DRY, FOUR CHAMPIONS FIERCE. STRIVE HERE FOR MASTERY Milton 1666 Steam Wonderful Steam Very high heat content Recyclable Clean, non toxic Biodegradable

More information

Low Energy Pumping Systems for Rainwater Tanks

Low Energy Pumping Systems for Rainwater Tanks School of Photovoltaic and Renewable Energy Engineering University of New South Wales Kensington, NSW, 2052 AUSTRALIA ABSTRACT The supply of low flow rate residential water appliances such as toilet cisterns

More information

Electric Instantaneous. Water Heaters. Service manual

Electric Instantaneous. Water Heaters. Service manual Electric Instantaneous Water Heaters Service manual Before installation quoting stage Work out with the customer what is the right model to install for the application Site assessment 1. The electrician

More information

In-Line Air Separators

In-Line Air Separators Air Elimination & Control In-Line Air Separators The AC models of air separators deliver all the quality and performance you expect from Taco products. They are built to last with shell, heads and ANSI

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

Installation and Operation Instructions Domestic hot water modules: FriwaMidi DN 20 FriwaMaxi DN 25

Installation and Operation Instructions Domestic hot water modules: FriwaMidi DN 20 FriwaMaxi DN 25 PAW GmbH & Co. KG Böcklerstr. 11, D-31789 Hameln, Germany Phone: +49-5151-9856-0, Fax: +49-5151-9856-98 E-mail: info@paw.eu, Web: www.paw.eu Installation and Operation Instructions Domestic hot water modules:

More information

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained

More information

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Powers Controls TH 192 HC Heating/Cooling Room Thermostat Powers Controls TH 192 HC Heating/Cooling Room Thermostat Technical Instructions Document No. 155-066P25 TH 192-2 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 192 HC thermostats are proportional

More information

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES BQ FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES Versatility, power, compactness and low running costs are the main characteristics of B&C vane pumps. All the components subject to wear are contained

More information