RE-COMMISSIONING OF VAV BOXES
|
|
- Myron Lang
- 7 years ago
- Views:
Transcription
1 RE-COMMISSIONING OF VAV BOXES Authors: Cristian CUEVAS, Jean LEBRUN (ULg) Patrick LACOTE, Philippe ANDRE (FUL) September
2 Table of contents Nomenclature INTRODUCTION DESCRIPTION OF THE SYSTEM TO BE COMMISSIONED COMMISSIONING OBJECTIVES AND EVALUATION CRITERIA MEASUREMENT PROTOCOL AND PROBES LOCATION Global commissioning Experimental protocol Measured variables Individual commissioning Experimental protocol Measured variables RESULTS AND ANALYSIS OF THE MEASUREMENTS Global analysis Individual analysis Flow rate verification (C02 testing) VAV aeraulic characteristics OPPORTUNITIES FOR AUTOMIZATION CONCLUSIONS AND PRACTICAL RECOMMENDATIONS REFERENCES
3 Nomenclature P : Pressure, Pa T : temperature, C V : Volumetric flow rate, m³/s X : Concentration, ppm Subscripts AHU : Air handling unit a : Air ex : Exhaust hx : Heat exchanger rad : Radiator st : Static su : Supply w : Water 3
4 1. INTRODUCTION This paper concerns the re-commissioning of the CA-MET Building located in Namur, which was designed for a one thousand occupants. The building is divided in 11 modules representing together m 2 of gross floor area and is described in other IEA40 reports [1], [2]. The study is dealing with the verification of the performance of the VAV boxes and their control laws. 2. DESCRIPTION OF THE SYSTEM TO BE COMMISSIONED VAV principle. The air coming from the AHU is brought into the plenum of the air diffuser (A) and passes through the perforated sheet (b) towards the outlet path formed by the bellows (c) and the bellows stop (d), see Figure 1. The cross sectional area of the outlet path is varied by the changing control pressure from the control unit expanding and contracting the bellows. Figure 1 VAV diffuser in cross section 4
5 The air diffuser is essentially self-regulating. The air pressure, which is the controlling force, is itself derived from the primary air supply. This pressure acts on the bellows, which expand, and contract to regulate the rate of the airflow from the unit. The control system is presented in Figure 2; it works as explained hereafter. First, the air bleed passes through the filter that allows supplying clean air to the control system. Then the air passes through the variable orifice 1, which changes as the pressure at the controller inlet changes. The size of orifice 2, set manually by rotating a calibrated sleeve, determines the maximum airflow supplied by the unit. Finally, the thermostat keeps the room temperature constant by controlling the bleed rate across the variable orifice 3. An internal crank linked to a bi-metal strip moves the sliding plate. The bimetal strip is constantly exposed to the room airflow by means of a venturi, which creates a depression within the thermostat. Figure 2 Control schematic The VAV boxes are able to regulate the room temperature between 18 and 28 C thanks to the set point adjusting lever, which is accessible to the occupants. Figure 3 (a) shows the VAV tested during the measurement campaign and the position of the set point 5
6 adjusting lever. Figure 3 (b) shows the room temperature setting; according to the manufacturer the middle position correspond to a room temperature of 23 C. Set point adjusting l 18 C Summer 23 C 28 C Winter (a) (b) Figure 3 Position of the set point adjusting lever The control law, which is supposed to govern the operation of the VAV boxes, is shown by fig. 4. Airflow 2K 2K Max Min 20 C 28 C Summer (blue arrow) Winter (red arrow) Ambient temperature Figure 4: VAV control strategy 6
7 In summer condition (figure3), the lever should be positioned toward the blue arrow, which means a set point around 20 C. If the room temperature exceeds 21 C, the VAV boxes will be wide open, in order to supply a maximum of cool air In winter condition, the lever should be moved toward the red arrow. The offices being heated by radiators, the VAV boxes are then only used to renew the air in the office. In this position, the set point is around 28 C. In that case and with a normal ambient temperature, the VAV boxes are always closed. This means the airflow rate is minimal. VAV installed in CAMET. The CAMET building is equipped with 1248 VAV boxes, which are divided in two types: Nominal flow rate Range Type [m³/h] [m³/h] The type 1 is the most used in the building and it is the VAV studied in this work. Normally, when a type 1 box is closed, there remains a minimal airflow of 68 m³/h. According to manufacturer, a minimum supply pressure of 250 Pa is necessary to guarantee a good performance of the VAV. At this pressure, the VAV covers the whole range of airflow, from the minimum (68 m³/h for type 1) to the maximum, which is fixed by the flow controller. The maximal plenum pressure is limited at 1250 Pa. 3. COMMISSIONING OBJECTIVES AND EVALUATION CRITERIA Commissioning of a VAV system can be carried out at two levels: - Global level: the objective is to check whether the operation as a whole of all the VAV boxes located in the building or in a part of it (for instance connected to a same AHU) is satisfactory - Individual level: the objective is to check individually the operation of some typical VAV boxes. The boxes to be tested are selected according to a global 7
8 analysis, to occupants complaints, or to specific observation made in some of the rooms. The properties of the VAV boxes, which deserve verifications, are: At global level: - The flow rate operating range: does the operation of the VAV boxes drive the corresponding AHU all across its operating range? - The operating pressure of the AHU: is the fan of the AHU able to maintain its nominal pressure for all configurations of the VAV boxes? At individual level: - The temperature control operation of each VAV box - The flow rate range provided by each VAV box 4. MEASUREMENT PROTOCOL AND PROBES LOCATION 4.1. Global commissioning Experimental protocol As the specific objective of this commissioning is to check whether the AHU connected to the verified VAV boxes is able to provide the full range of flow rate (from minimum to maximum), the following protocol is proposed: 1. Launch data archiving. Are concerned the variables, which are useful for the exhaust air, flow rate control (see below). 2. Switch the AHU in automatic mode, Bring the offices temperatures somewhere between the two extreme set points (typically around 24 C) and wait for almost steady state conditions. 3. Go in each office supplied by the AHU and switch each thermostat at the end of scale of summer position (lowest temperature set point). 4. Hold on the stabilization of the fan modulation. 5. Measure the static pressure in, at least, one VAV box plenum, located far away from the AHU. 8
9 If that pressure is outside the tolerances, correct the pressure set point at AHU exhaust. When the advisable pressure is reached, note the airflow rate and the corresponding pressure set point: it will be kept for all further operations. 6. Individual VAV box checking For each office: i. The thermostat being on the summer position (VAV's wide open), note: 1. the VAV noise 2. the air speed close to the outlet (typically with a portable anemometer or simply with the hand) 3. the static pressure in the plenum ii. Put the thermostat at end of scale of winter position (highest temperature set point). The VAV boxes should then reach their minimal opening. This can be checked by: 1. a reduction of VAV noise 2. a lower air speed 3. a higher static pressure in the plenum iii. If nothing is happening, we may conclude that the thermostat is badly connected or deficient. 7. Go in each office supplied by the AHU and switch the thermostat to end of scale of winter position 8. Hold on the stabilization of the fan modulation. 9. Go in each office supplied by the AHU and switch back the thermostat to its normal position, according to the season: a. If we are in winter, let the thermostat in "winter" condition. Or else, switch back the thermostat in "summer" position and ask to the occupants to adjust more accurately, according to their requirements. Note: the here-above described procedure is easier to perform in winter:the 9 th step is then irrelevant. If, the procedure should be applied in summer, then first switch the thermostat on the "winter" position in order to finish with the "summer position". 10. Process the data. By moving all the set-points of the VAV boxes on summer position and then winter position, we force the VAV to be once at maximum flow rate and once at minimal flow rate. If all VAV's local control systems are well connected, we should be able to deduce from AHU monitoring results the maximal and minimal ventilation airflow rates and to compare them with as-built values Measured variables The variables archived are: supply pressure at the exhaust of the AHU 9
10 Heating/cooling coil pressure drop fan modulation pressure at the supply of verified VAV box 4.2. Individual commissioning Experimental protocol In the offices concerned by verification, the following actions have to be carried out: - Loading of selected rooms with auxiliary heating system (radiators or electrical system) to generate response of VAV system - CO2 test to measure ventilation rate (injection of C02 and subsequent concentration measurement) - Test of VAV system at constant fan speed - Test of VAV system at constant exhaust pressure Measured variables In order to study the performance of the VAV boxes, some measurements were performed in two offices located in the third floor of the building. The variables measured were, see figure 5: N T amb T a, su T return T return T a, su T w, su, rad B3708 T a B3508 T a T w, su, rad T w, ex, rad T w, ex, rad Atrium Figure 5 Office schematic measurements T w, su, rad : Radiator supply temperature, C 10
11 T w, ex, rad : Radiator exhaust temperature, C T supply : Supply room temperature, C T thermostat : Air diffuser thermostat temperature, C T return : Return temperature, C T room : Room temperature, C P plenum : VAV plenum pressure, Pa Figure 6 and Figure 7 show the temperature measurements in the offices and the heating system used to load the offices. Thermostat temperature Supply temperature Return temperature Figure 6 Temperature measurements Thermocouple Figure 7 Temperature measurements and auxiliary heating system 5. RESULTS AND ANALYSIS OF THE MEASUREMENTS 11
12 5.1. Global analysis A fan exhaust set point of 400 Pa may be typically required in order to get 250 Pa in the plenum of the most distant VAV boxes, when they are wide open (the most unfavorable condition). In this condition, there is about 150 Pa of pressure drop all along the air network. Pressure measured in the plenum of 2 offices (Pa). Office B3707 Office B3708 (thermostat badly connected) Summer position Winter position Control system disconnected On summer position, when the VAV's should be fully open, we find the nominal plenum pressure (260Pa) for the boxes B3707, whereas the pressure is significantly lower for B3708. Moreover, this pressure doesn t change when the set point is moved to winter position. In this position, the pressure of B3707 increases normally, confirming that the VAV boxes are closed. We conclude that the B3708 thermostat is deficient or disconnected. Pressure in the plenum and noise measurements in 9 offices (AHU exhaust pressure: 675 Pa; thermostats in summer position) Office Pressure plenum (Pa) Noise level (db) B3708 B3508 B3509 C3513 C3713 C3512 K3358 K3361 K B3708 and B3508 are deficient. Indeed, the noise level is higher there than in the other offices and the plenum pressure is lower. The VAV boxes of the other offices are operating at maximal airflow rate, giving around 600 Pa in the plenum. On deficient VAV's, the pressure is lower because there is no more control of the maximum flow and the boxes are fully open. Here also, we can see that the local control system is either disconnected or deficient. 12
13 Pressures measured in several plena: Office C3713 C3512 B3720 K3361 K3363 K3368 Pressure plenum (Pa) As the VAV boxes are closed, these pressures at the plenum are higher than in summer conditions. Figure 8, 9 and 10 show results of an overall commissioning procedure of the VAV boxes installed in the BS module (about 80 offices) of the CAMET building. The pressure difference Htg/Clg, measured between the inlet of the heating coil and the outlet of the cooling coil allows us (after calibration), to calculate the air flow rate. Figure 8: Time schedule of VAV testing phase 13
14 Figure 9: Response of AHU to all VAVs change of set point (from summer to winter position) Figure 10: response of AHU to all VAVs change of set point (winter to summer position 14
15 Figure 8 shows the development of the commissioning procedure: During the first phase (Figure 9), all VAV boxes are moving from open to closed positions and this makes the exhaust pressure to increase. Then, the AHU control makes the fan speed to decrease, in order to compensate the pressure elevation. That s what we can see on the graph: the fan modulation decreases, while the exhaust pressure is maintained to its set point (about 400Pa). The reverse situation is observed in Figure 10. The airflow rate varies from m³/h to m³/h in the first phase and from 9 582m³/h to m³/h in the second phase. This is in accordance with the as-built data. Note: fan modulations at the end of the first phase and at the beginning of the second phase are not the same, while, in both cases, the VAV thermostats are in the same winter position. This can be explained by the very strong difference between both AHU exhaust temperatures (Figure 8): In the winter (red) position during the first phase, the AHU exhaust air temperature is about 27 C, whereas, in same position, but during the second phase, the AHU exhaust temperature is about 14 C. So, during the first case, VAV s are more likely to be entire closed, because of low exhaust temperature combined with a low return temperature. The effect is a little less easy to observe when the thermostats are in summer (blue) position, probably because steady states conditions are not reached yet Individual analysis Temperature control operation. The air supplied by the VAV to the room is controlled by a thermostat, which acts according to the room temperature. So, in a normal functioning, the thermostat temperature should be the same as the room temperature. But, according to the measuring results available, this is not always the case: the thermostat temperature is highly influenced by the supply temperature and by the radiators. The measurements analyzed correspond to Wednesday 20 th (see Figure 11 and 12). Between 03:15 h and 00:05 h hot water at 80 C is supplied to the radiator, maintaining the VAV turned off. The office temperature increases from 21 C to 23 C and the thermostat temperature increases until 28 C, which is normal since hot air is stratified close to the ceiling, where the thermostat is located. At 05:00 h the AHU is turned on, supplying air at 18 C and the supply radiator temperature is decreased to 56 C. From that time, it is possible to see that the temperature measured by the thermostat is very close to the room temperature (23 C). 15
16 At 11:00 h the supply radiator temperature is again increased to 80 C and the supply temperature continues decreasing until 16 C. It disturbs the thermostat temperature, which at the beginning increases to 26 and then decreases to 21 C, which does not correspond to the room temperature (25.5 C). The VAV system sees a temperature lower than the room temperature. This one is then maintained according to a wrong set point. 100 B Temperature [ C] : : : : : : : : :00 Time 35 Tw,ex,rad Tw,su,rad Figure 11 Radiator entering and leaving water temperature B Temperature [ C] /03/ :00 0:00 3:00 6:00 9:00 12:00 15:00 18:00 21:00 Time Troom Tsupply Treturn Tthermostat Figure 12 Evolution of the room, thermostat and supply temperature 16
17 Flow rate verification (C02 testing). Two CO2 tests were performed in order to determinate the airflow rate supplied for the VAV system to the offices. The monitoring system device was used to measure the CO2 concentration, which is shown in Figure 13. As it is shown in Figure 14, one of these probes has a measuring offset. Comparing with the others devices installed in the other offices the probe installed in the office B3508 gives better results; so the values measured in the office B3708 must be corrected. Figure 13 Sensors installed in the monitored offices The first test was performed the Wednesday March 20 th at 13:20 h and the second the Thursday March 21 st at 15:10 h CO2 concentration [ppm] /03/02 00:00:00 19/03/02 12:00:00 20/03/02 00:00:00 20/03/02 12:00:00 21/03/02 00:00:00 21/03/02 12:00:00 Time CO2_B3708 CO2_B
18 Figure 14 Evolution CO2 concentrations in the offices B3508 and B3708 The air renovation can be determined using the following equation: X X X 0 0 X = 1 e τ / τ 0 where X 0 X τ τ 0 : is the initial concentration, ppm : is the final concentration, ppm : is the time, s : time constant (inverse of the air renovation), s The last equation can be expressed as: ln ( X ) = ln( X X ) n τ X 0 where n is the air renovation, 1/s. The nominal airflow rate of each VAV is 200 m 3 /h. In each office there are two VAV, so the nominal airflow rate supplied to each office must be 400 m 3 /h. In the first test the offices were heated with the radiators. The office temperatures increase up to 25 C, for an exhaust AHU temperature of 14 C, as is shown in Table 1. According to Figure 15 the VAV are not fully opened. In fact, the static pressure used to control the fan speed was not measured correctly during this test. The sensor scale was incorrect, the measured monitoring pressure was 600 Pa and in fact the real pressure was 120 Pa. So the pressure at the inlet of the VAV box was not sufficient to ensure its good performance. In the second test the offices were again heated with the radiators, but also by an additional heat load of 1500 W in B3508 and 1575 W in B3708. According to the results got in this case, the VAV boxes were fully opened, supplying the offices B3508 and B3708 with 445 m 3 /h and 485 m 3 /h respectively (see Figure 16). 18
19 The air temperatures were maintained at 22 C in both offices. 8 7 ln(x-xinf) y = x V = 209 m³/h y = x V = 149 m³/h Time [min] CO2_B3708 CO2_B3508 Figure 15 Airflow rate supplied to the offices ( :20) y = x V = 485 m³/h ln(x-xinf) y = x V = 445 m³/h Time [min] CO2_B3708 CO2_B3508 Figure 16 Airflow rate supplied to the offices ( :20) Table 1 Summary of the CO2 tests Test P st, P hx T exhaust, T return, a AHU V, a,b 3508 V V a,b3708 T B3508 T B
20 AHU AHU AHU VAV aeraulic characteristics. In order to observe the opening of the VAV boxes, two tests were performed: test at constant fan frequency and test at constant exhaust static pressure. The airflow rate supplied for the AHU is determined using the heat exchangers pressure drop and the model identified previously. With this information and with the temperatures measured in the offices is possible to analyze the performance of the VAV boxes installed in the modules B and C of the building. In the first test the Modules B and C were heated with the radiators and with the air supplied by the AHU. The fan frequency was kept fix at 40 Hz. According to Figure 7 the supplied temperature increases from 14 C to 40 C and the room temperature from 21 C to 27 C. The opening of the VAV increases slightly and the supplied air flow rate increases only of 8 % in 2 hour. Airflow [m3/h] :48 19:12 21:36 Test period B /03/2002 0:00 21/03/2002 2:24 21/03/2002 4: /03/2002 7:12 Temperature [ C] Time Airflow T_supplyB3708 T_roomB3708 T_returnB3708 Tthermostat Figure 17 VAV behavior 20
21 Figure 8 shows the evolution of the AHU airflow rate against the AHU return temperature for the period where the VAV was tested. It can be seen that the AHU return temperature continues increasing, while the AHU airflow rate increases. This indicates that the VAV boxes are not still fully open. As it can be seen in Figure 9 the pressure at the exhaust of the AHU decreases while the airflow rate increases. The same behavior is observed for the plenum pressure measured in the VAV boxes Airflow rate [m³/h] Treturn,AHU [ C] Figure 18 AHU airflow rate against AHU return temperature 1200 Test period Presion [Pa] :48 19:12 21:36 21/03/2002 0:00 21/03/2002 2:24 21/03/2002 4: /03/2002 7:12 Time PplenumB3708 PplenumB3508 Pexhaust,AHU Treturn,AHU Figure 19 Evolution of the pressure and return AHU temperature during the test 21
22 6. OPPORTUNITIES FOR AUTOMIZATION Automatization of such a procedure for commissioning of a VAV system entirely relies on the possibility to measure and to control the individual operation of each box. In the case presented in this report, the VAV boxes are essentially self-regulating devices: remote measurement of the thermostat temperature, remote adjustment of the set point and remote control of the VAV opening are not possible. As a consequence, automization of the procedure using that kind of device is difficult. If it were the case, the global checking would be the easiest to carry out. 7. CONCLUSIONS AND PRACTICAL RECOMMENDATIONS The methods presented in this report allow carrying out the checking if VAV boxes, both at a global level and at an individual level. In the case study presented here, they allowed to check that, as whole, the behavior of the VAV system was satisfactorily, while they identified the devices that are likely non-operating. The main recommendations would be to start from a global approach (in conjunction with a parallel verification of the Air Handling Units) to detect problems. If this global approach points out deficiencies, the analysis should carry over to a more detailed analysis of selected individual devices. The global verification can take place during normal operation of the building (passive testing), while the individual verification requires the generation of artificial (and forced) conditions (active testing). 8. REFERENCES [1] CUEVAS, C; LACÔTE, P.; LEBRUN, J. Recommissioning of an Air Handling Unit, IEA Annex 40 working document, University of Liège, May
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More informationExample of Functional Performance Test : FPT for VAV Ventilation Systems
Example of Functional Performance Test : FPT for VAV Ventilation Systems Document Identification Type of documents: Glossary Cx Process Project Tool Model Type of building : 1 2 3 4 5 Type of Cx. : Initial
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationHVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
More informationSECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
More informationASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationCOMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN Umesh Atre Innovative Design Inc 850 W Morgan St Raleigh, NC 27603 umesh@innovativedesign.net
More informationPowers Controls TH 192 HC Heating/Cooling Room Thermostat
Powers Controls TH 192 HC Heating/Cooling Room Thermostat Technical Instructions Document No. 155-066P25 TH 192-2 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 192 HC thermostats are proportional
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationRiverside City College. Math & Science Building HVAC Investigation. May 23, 2013
May 23, 2013 Prepared by: P2S Engineering, Inc. 5000 East Spring St, Eighth Floor Long Beach, CA 90815 T 562.497.2999 F 562.497.2990 www.p2seng.com Table of Contents Executive Summary... 2 Background...
More informationEnergy Saving Tips. Adjust set point temperature up a few degrees... Window contact. Occupancy sensor. A Programmable Thermostat
Energy Saving Tips Nowadays when Energy costs are skyrocketing and the awareness to environmental issues is increasing, we all want to reduce energy consumption and have a greener lifestyle. Heating &
More informationRKE. Heat recovery unit. heat recovery unit RKE. from 200 to 6800 m 3 /h. General features
RKE Heat recovery unit from 200 to 6800 m 3 /h General features RKE heat recovery units are suitable for residential and commercial applications and offer a real energy saving in forced ventilation plants,
More informationEFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE
EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE Vivek Khaire, Dr. Avijit Goswami Applied Thermal Technologies India 3rd Floor,C-Wing,Kapil Towers, Dr. Ambedkar Road, Pune- 411 1 Maharashtra,
More informationBuilding Re-Tuning Training Guide: AHU Heating and Cooling Control
Building Re-Tuning Training Guide: AHU Heating and Cooling Control Summary The purpose of the air-handling unit (AHU) heating and cooling control guide is to show, through examples of good and bad operations,
More informationBenefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
More informationPERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
More informationDual Maximum VAV Box Controls
ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How
More informationTesting methods applicable to refrigeration components and systems
Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University
More informationVariTrane Duct Designer An in depth look...
VariTrane Duct Designer An in depth look... Introduction The VariTrane Duct Designer duct design program was written to help optimize design while obtaining a minimum pressure system. The program is based
More informationAutomated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview
Automated Commissioning for Energy (ACE) Platform for Large Retail Property $62,900 dollars of energy savings identified during the first 6 weeks Overview The ability to pull large amounts of complex data
More informationCGC s Hybrid System Loop Control
verview The CGC Group Hybrid Heat Pump System does NT operate with the same fluid loop temperatures as a conventional reversing Water Source Heat Pump system. The CGC system differs from a WSHP system
More informationBring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationRev. No. 0 January 5, 2009
ENERGY & ENVIRONMENTAL ENERGY ISSUES COMMITTEE 415 Main Building Telephone (574) 631-6666 Notre Dame, Indiana Facsimile (574) 631-5883 46556 USA Energy Conservation Plan For HVAC Systems Rev. No. 0 January
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationVariable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
More informationAir Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
More informationEFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
More informationOnce you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.
COOLING FAN REQUIREMENTS CALCULATIONS Determining System Impedance Determining the actual airflow produced by a fan mounted in an enclosure is much more difficult than calculating the airflow required.
More informationThe main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
More informationR22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
More informationEnclosed Football Stadium Design History and Lessons Learned
Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP btowell@cxegroup.com CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention
More informationWhy and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
More informationA. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.
DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly
More informationPowers Controls TH 192 S Single Temperature Room Thermostat
Technical Instructions Document No. 155-065P25 TH 192-1 Powers Controls TH 192 S Single Temperature Room Thermostat 50 60 70 80 TH0355R1 70 80 POWERS Description The TH 192 S thermostats are proportional
More informationS & P COIL PRODUCTS LTD SPC HOUSE, EVINGTON VALLEY ROAD, LEICESTER. LE5 5LU. Electrical layouts for EC Motors in Fan Convector units
S & P COI PRODUCTS TD SPC HOUSE, EVIGTO VAEY ROAD, EICESTER. E5 5U Guidance Document Electrical layouts for EC Motors in Fan Convector units Hasnain Merchant Richard Meskimmon 4/9/0 This document is intended
More informationLesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
More information2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power
More informationAttached is a link to student educational curriculum on plug load that provides additional information and an example of how to estimate plug load:
Energy Conservation Tip #1 Always turn off all lights when you leave a room or when they are not needed. It is estimated that 26% of a building s electricity is used for lighting. For D-11 this equals
More informationVariable Capacity Compressors, a new dimension for refrigeration engineers to explore
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents
More informationwww.inspection-for-industry.com
Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.
More informationHeat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools
Heat Recovery Dehumidification (HRD) system Designed for municipal swimming pools A dehumidification and ventilation system with dynamic heat pump heat recovery to swimming pool water and air ENVIRONMENTAL
More informationIntelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange
Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange ING. TOMMASO FERRARESE Thermodynamics Laboratory Engineer
More informationHow To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
More informationHow to Measure HVAC System Airflow
How to Measure HVAC System Airflow About National Comfort Institute National Comfort Institute is an international training Since our and beginning development in 1994 company we have trained with and
More informationELECTRIC CENTRAL HEATING FLOW BOILER
ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment
More informationCHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)
More informationPresentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
More informationHow To Get A Passive House
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product
More informationCondensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
More informationHow To Control Humidity With A Humidifier
Control of ventilation and air conditioning plants Building Technologies s Contents.Temperature control in air treatment systems 2. Humidity controls 3. Recirculated air mixing. Internal heat sources 6.2
More informationFAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7
FAQs Conserve package Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7 FAQs Gateway Can I have someone install my system for me? If you are concerned
More informationAccurate Air Flow Measurement in Electronics Cooling
Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: info@degreec.com Air is the most commonly used medium to remove heat from electronics
More informationHVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
More informationAPC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
More informationInstallation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
More informationENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS.
1 ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS. - EXPERIENCE FROM A PLANT RECONSTRUCTION BASED ON A NEW SUPPLY AIR TERMINAL
More informationTechnical Concept. Filter Fan Unit COMPACT. Type COMPACT AC Type COMPACT EC
Technical Concept Filter Fan Unit COMPACT Type COMPACT AC Type COMPACT EC Ultra Filter Fan Unit COMPACT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide
More informationFAN COIL UNIT SOFTWARE User Manual
User Manual Thanks for using Tiba fan coil units' selection software. To start the selection process to software selection there are some steps we need to follow: Front page: 1. Only selection 2. Performance
More informationMP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
More informationControls for fan coil units and cassettes
Controls for fan coil units and cassettes Selection of controls for use with fan coil & cassette units. Stand alone, selection guide Control unit Motor Standard QZAZ-04-10 QZAZ-04-20 QZAZ-04-75 QZAZ-05-11
More informationCase Study. Vermont Hospital: Advanced Analytics as a Preventative Maintenance Tool
Case Study Vermont Hospital: Advanced Analytics as a Preventative Maintenance Tool August 1, 2015 Contents Overview... 3 Location... 4 Issue Description... 4 The Results... 5 Issue 1: Improper damper actuator
More informationT-100-R Installation Guide
T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard
More informationFebruary 1, 2006. Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure
February 1, 2006 Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure Overview - Several measurements of air source heat pump system performance are required
More informationApplying Schedules and Profiles in HAP
This HAP e-help discusses the importance of properly applying schedules and profiles in HAP. We will also discuss potential misapplications of these user inputs. First, we need to understand the differences
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More informationMistrale. Fusion Terminal
Mistrale Fusion Terminal PUBLICATION NATURAL VENT. 1 SEPT 2015 Features - Slimline energy efficient ventilation solution - Standard and high capacity terminals provide 128 or 256 L/s capacity - Compliant
More informationT-4000 Series Pneumatic Room Thermostats
T-4000 Series Pneumatic Room Thermostats Pneumatic Control Manual 717.1 Room Devices Section Product Bulletin T-4000 Issue Date 1285 Features Adjustable Sensitivities and Set Points Individual Set Points
More informationT 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ
TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size
More informationPowers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat
Document No. 155-068P25 TH 193-4 Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 193 HC thermostats are proportional dual
More informationSolar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...
Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system
More informationCAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?
Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,
More informationComparing Energy Savings of Different VAV Systems
Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March
More information3. AIR CONDITIONER CONTROLLER (UNIT)
9 3. AIR CONDITIONER CONTROLLER (UNIT) Functions of Full Automatic Air Conditioner ler 1 1. Temp SW 2. Auto SW 3. OFF SW 4. Amb SW 5. Mode SW 6. Blower SW 2 3 10 5 8 7 9 Temperature control: Air mix actuator
More informationTHERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
More informationUsing Time-of-Day Scheduling To Save Energy
The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.
More informationApplying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009
Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort
More informationHEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium
HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING Cleide Aparecida Silva 1, cj.hannay@ulg.ac.be Stéphane Bertagnolio 1, stephane.bertagnolio@student.ulg.ac.be
More informationKONRAD. Hybrid Fancoil Series
KONRAD Hybrid Fancoil Series Konrad is an innovative radiator which cools you down and warms you up. Indeed, it cools in summer and heats in winter; but it makes it with an incomparable quietness. Thanks
More informationImpacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
More informationImpact of Control System Technologies on Industrial Energy Savings
Impact of Control System Technologies on Industrial Energy Savings Priyam Parikh Industrial Assessment Center Texas A&M University Bryan P. Rasmussen Industrial Assessment Center Texas A&M University http://farolconsulting.com/?page_id=110
More informationDUCT TYPE AIR CONDITIONER
OPERATING MANUAL OPERATING MANUAL BEDIENUNGSANLEITUNG MODE D EMPLOI MANUAL DE FUNCIONAMIENTO MANUALE DI ISTRUZIONI ΕΓΧΕΙΡΙ ΙΟ ΛΕΙΤΟΥΡΓΙΑΣ MANUAL DE INSTRUÇÕES AIR CONDITIONER DUCT TYPE English Deutsch
More informationDehumidification Design
Dehumidification Design Using Data-Center Heat Utilizing free heat from a server room was the concept behind an air-handling system in a college-campus building Considerable energy savings are possible
More informationData Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
More informationExample of audit of an air conditioning system
Example of audit of an air conditioning system Authors and affiliations: André Philippe Hannay Cleide, Hannay Jules, Lebrun Jean University of Liège, Belgium Main author: Jean Lebrun Email : j.lebrun@ulg.ac.be
More informationHVAC Characteristics. Test Space HVAC Characteristics
HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,
More informationPrediction Is Better Than Cure CFD Simulation For Data Center Operation.
Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
More informationDesigned for multi-injector endurance testing, the
Designed for multi-injector endurance testing, the ETB Test Bench can optionally provide shot-to-shot mass measurement. The injectors are precisely subject to variable controls and hydraulic pressures
More informationVENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING
VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEFINITION OF VENTILATIVE COOLING VENTILATIVE COOLING IS APPLICATION (DISTRIBUTION IN TIME AND SPACE) OF VENTILATION AIR FLOW TO REDUCE COOLING LOADS IN
More informationMechanical Systems Proposal revised
Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option
More informationSPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
More informationPANDA SPRAY BOOTH FILTER INFORMATION
PANDA SPRAY BOOTH FILTER INFORMATION Our Spray Booth has been designed to reduce the risk of potential hazardous situations occurring. You must adhere to the specifications chart listed below when replacing
More informationRadiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
More informationDesign Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)
Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) 1. In addition to the information scheduled below, the pre-tender designer is responsible for: (i)
More informationChilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
More informationNew Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
More informationTechnical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A
COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850
More information