Dual Maximum VAV Box Controls
|
|
- Primrose Barnett
- 7 years ago
- Views:
Transcription
1 ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC engineering.com
2 Agenda VAV Box basics Sizing VAV Boxes How low can you go? VAV Box control logic Conventional VAV box control logic Dual Maximum control logic Non-complying dual maximum control logic Determining setpoints How well does Dual Maximum logic work? ASHRAE RP-1515 Results
3 VAV Box Sizing Oversized box Less pressure drop Less noise Higher box min more reheat, higher fan energy Cost more Undersized box Higher pressure drop More noise Lower box min less reheat, lower fan energy
4 VAV Box Sizing: LCC Analysis Compared TP from 0.3 to 0.8 Low rise office building Sensitivity Analysis Climate Loads operating schedules Utility rates Load calc (aggressive, conservative) 8 bit versus 10 bit A/D converter SAT (50 F-60 F), SAT reset, SP reset TP RESULT: Size VAV Boxes for ~0.5 TP SP VP
5 VAV Box Sizing: Sample Calc. Nominal size Inlet dia. (in.) Outlet width (in.) Outlet height (in.) SP (in. w.g.)* VP (in. w.g.) TP (in. w.g.) Max CFM Radiated NC* *From selection software using ARI and assuming inlet SP = 1.5 and outlet SP = 0.25
6 What is the lowest minimum? Function of FPM DDC Controller: What s the lowest controllable velocity pressure (VP) signal? DDC velocity pressure transducer accuracy A/D converter resolution (bits) VAV Box: Amplification factor, F Inlet size, D min 4005 VP F min CFM min FPM min D 4 2
7 Why Not Just Look in the VAV Box Catalog? Equates to ~0.03 minimum VP and about 30% of design CFM for typical box selections
8 Why Not Just Look in the VAV Box Still too high Catalog? Good Advice! NEVER use Box manufacturer s minimums!
9 Controllable VP Minimum Some manufacturers list the range in catalog Some you have to ask Most available from ASHRAE RP 1353 and PG&E research projects (see references) Almost all controllers ± 10% at Specify allowable setpoint 0.004
10 Typical DDC Performance Flow Error [cfm] A Nailor VAV Box B Titus VAV Box Reference Flow [cfm] Highly accurate down to about 50 CFM (0.003 )
11 Flow Probe Amplification C F M I n l e t S i z e 22 inch 16 inch 14 inch 12 inch 10 inch 9 inch 8 inch 7 inch 6 inch 5 inch 4 inch Flow Probe Velocity Pressure Signal (Inches W.G.) K C F O n e I n c h S i g n a l F 4005A K F = amplification factor K = actual flow in CFM at flow probe output of 1.0 w.c. A = is the nominal inlet area in ft 2 2
12 Typical Flow Probe Performance Velocity [fpm ] Flow Grid Pressure [iwc] F slope ~ 2.6 Specify 2.0
13 Sample Controllable Minimum FPM CFM min 4005 min FPM min VP F D 4 min Box Inlet Diameter Maximum CFM at 0.5 in.w.g. pressure drop Minimum CFM at in.w.g. sensor reading Minimum Ratio at Highest Maximum, % Minimum Ratio at lowest Maximum, % % % 13.6% 10 1, % 12.7% 12 1, % 11.8% 14 2, % 11.3% 16 2, % 10.9%
14 VAV Reheat Control
15 Q: Why do some buildings use 3-5 times as much energy as others? 2,500 Boiler Input (Btu/sf) 2,000 1,500 1, Site #1 Site #2 0 Mar-02 Apr-02 May-02 Jun-02 Jul-02 A: Reheat
16 Conventional VAV Control
17 Conventional VAV Box Minimum Setpoint No less than larger of: Minimum ventilation rate Per Title 24 Controller minimum Not an issue for conventional logic see discussion above Limit dumping Not an issue see RP-1515 results below Limit stratification No more than 20 F above space temperature (~ 95 F) per Standard 90.1 No more than larger of: 30% of cooling maximum Per Title 24/Standard Now only allowed for non-ddc controls Minimum ventilation rate
18 Title 24 VAV Control Requirement for zones with DDC
19 Dual Maximum Control per Title 24 and Standard 90.1 for DDC
20 Dual Maximum Logic in Action Start heating, increase DAT setpoint At 50% Heat, start increasing airflow
21 Sort of Dual Maximum Control (Found in some configurable controllers) T-24
22 Sort of Dual Maximum Control (Found in some configurable controllers) Title 24
23 VAV Box Dual Maximum Control Setpoints per Title 24 and Standard 90.1 Minimum: 1. No less than larger of: Minimum ventilation rate for the zone Controller minimum 2. No more than 20% of cooling maximum Heating Maximum: 1. No less than larger of: Minimum Limit stratification - 20 F SAT above space temperature ( ~90 F to 95 F) 2. No more than 50% of cooling maximum MARK INLET DESIGN CFM SIZE COOL MIN HEAT VR VR VR Always use Option 1 above Do not use code maximum just because it s legal! Avoid using %-of-cooling-maximum setpoints boxes are usually oversized!
24 What about Standard 62.1 Multiple Spaces compliance? Oakland Office - VAV System with Outdoor Air Economizer
25 How Well Does Dual Max Logic Actually Work? RP-1515 results
26 RP 1515, "Thermal and Air Quality Acceptability in Buildings that Reduce Energy by Reducing Minimum Airflow from Overhead Diffusers" Objectives Measure energy savings & validate simulations Identify comfort issues that may occur at low flow Funding California Energy Commission - PIER ASHRAE UC Berkeley - Center for the Built Environment Research Team UC Berkeley Taylor Engineering Price Industries Method Field Study in 7 buildings Background survey Right now survey matched to zone trends Energy monitoring Laboratory Study Air distribution for various diffuser types
27 Yahoo! Sunnyvale Campus 1073 Zones 3700 Occupants Plaque face diffusers
28 800 Ferry Building 22 Zones Perforated Diffuser with blades in face
29 Measured flow fractions: Yahoo campus Warm Season All Occupied Hours Cool Season All Occupied Hours Density Low Minimum 30% Minimum Density Low Minimum 30% Minimum Flow Fraction [%] Flow Fraction [%]
30 Total Electricity Usage
31 Energy Savings
32 Occupant Comfort Survey Questions When the logic changed from conventional (High minimum) to Dual Maximum (Low minimum): Did occupants become less comfortable? Was their sense of air movement stronger due to dumping? Approach 3 surveys: Yahoo warm and cool seasons 800 Ferry building warm season 3 4 weeks of surveying each season Switched between high and low minimum operation in the middle of each survey period Surveys administered 3 times/day About 10,000 responses received
33 "How satisfied are you with the temperature in your workspace? HIGH min flow rate LOW min flow rate 30.0% 249 % dissatisfied of people 25.0% 20.0% 15.0% 10.0% 5.0% % 800 Ferry Building Yahoo! Cool season Yahoo! Warm season % Dissatisfied people HIGH Conventional LOW Dual Maximum 800 Ferry Building 27.3% 12.5% Yahoo! cool season 8.7% 9.4% Yahoo! warm season 20.1% 10.3%
34 Thermal sensation distribution (Yahoo! warm season)
35 Loads are very low! CFM/FT 2 at 20 F T 140 Zones, 2 buildings, 1 warm month (Sept)
36 What happens when load is less than airflow minimum? Conventional Logic Actual Required CFM Dual Max Logic
37 Air temperature (800 Ferry building) High flow: average Tair = 71.2ºF Low flow: average Tair = 73.3ºF 85 HIGH minimum flow rate LOW minimum flow rate /22 09/23 09/26 09/27 09/28 09/29 09/30 10/03 10/04 10/05 10/06 10/07 10/10 10/11 10/12 10/13 10/14 10/17 10/18 zone temperature [F] 10/19 10/20 N Mean sd Dates
38 How about Drafts? (800 Ferry building)
39 Perceived air quality
40 CBE background survey results
41 Price Lab Tests Perforated diffusers with blades in the neck, Cooling Mode. Results: Negligible impact on ADPI all near 1 Negligible impact on ACE all near 1
42 Dual Maximum VAV Box Logic Summary Title 24 requires Dual Maximum logic for VAV zones with DDC Setpoints Set minimum and heating-maximum setpoints as low as possible Minimum allowed by controls is seldom a factor if box properly sized Do not use maximum allowed by T-24 just because it is legal Cost impact Requires discharge temperature sensor This is nice for diagnostics anyway Usually requires programmable zone controller Configurable controller programming should soon catch up Performance Thermal comfort improves with low flow operation Dumping & draft are not an issue at low flow Energy savings are significant and similar to simulation predictions
43 Bibliography Taylor S., Stein J.; Sizing VAV Boxes, ASHRAE Journal, March 2004 Dickerhoff D., Stein J.; Stability and Accuracy of VAV Terminal Units at Low Flow, PG&E 0514, Lui R., Wen J.; Stability and Accuracy of VAV Box Control at Low Flows, ASHRAE 1353-RP Taylor S. Dual Maximum VAV Box Logic, ASHRAE Journal, December 2012
44 Questions? Steve Taylor
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
More informationMethods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update
More informationNEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More informationDemand Based Static Pressure Reset Control for Laboratories
LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a
More informationAIR DISTRIBUTION FOR COMFORT AND IAQ
AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant
More informationSECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution.
SECTION EG Air Distribution Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. Space Air Diffusion AIR DISTRIBUTION ENGINEERING GUIDE Proper selection of air diffusion
More informationRev. No. 0 January 5, 2009
ENERGY & ENVIRONMENTAL ENERGY ISSUES COMMITTEE 415 Main Building Telephone (574) 631-6666 Notre Dame, Indiana Facsimile (574) 631-5883 46556 USA Energy Conservation Plan For HVAC Systems Rev. No. 0 January
More informationComparing Energy Savings of Different VAV Systems
Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March
More informationCentral Plant Air Systems: Keeping the Heart and. Title Style. Better Buildings Summit May 2016
Central Plant Air Systems: Keeping the Heart and Click Lungs To Healthy Edit Master Title Style Better Buildings Summit May 2016 Introductions Michael Deru National Renewable Energy Laboratory New Resources
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationVAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
More informationSPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
More informationT 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ
TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size
More informationCommissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
More informationProblem Statement In order to satisfy production and storage requirements, small and medium-scale industrial
Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.
More informationAMD-33 Air Measuring Station with VCD-33 Control Damper
Application and esign Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness 16 ga. (1.5mm) 12 ga. (2.7mm) Frame Type 5 in. x 1 in. hat channel - Blade Material Galvanized
More informationplenum slot diffusers
light powered Redefine your comfort zone. www.titus-hvac.com dual-function smart logic light powered energy solutions Table of Contents PLENUM SLOT IFFUSERS products Plenum Slot iffusers Products... 4
More informationUsing Time-of-Day Scheduling To Save Energy
The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.
More informationApplying Schedules and Profiles in HAP
This HAP e-help discusses the importance of properly applying schedules and profiles in HAP. We will also discuss potential misapplications of these user inputs. First, we need to understand the differences
More informationContinuous Energy Management at UC San Diego. Anna Levitt, P.E. Assistant Energy Manager June 13, 2013
Continuous Energy Management at UC San Diego Anna Levitt, P.E. Assistant Energy Manager June 13, 2013 UC San Diego: A 42 megawatt Microgrid With a daily population of over 45,000, UC San Diego is the size
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationAIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
More informationUNDERFLOOR AIR DISTRIBUTION
FINAL REPORT NCEMBT-080801 UNDERFLOOR AIR DISTRIBUTION AN EXPERIMENTAL COMPARISON OF AIR DIFFUSION PERFORMANCE BETWEEN UNDERFLOOR AIR DISTRIBUTION AND CONVENTIONAL OVERHEAD AIR DISTRIBUTION SYSTEMS AUGUST
More informationJ O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
More informationAMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application and Design. Ratings. Features and Control Options.
Application and esign Thermal ispersion Air Measuring Station with VC-23 Control amper The combines the functionality of a highly accurate thermal dispersion airflow measuring station and a low leakage
More informationL EED & G r e e n B u i ldi ngs
L EED & G r e e n B u i ldi ngs A P P L I C AT I O N G U I D E contents 3 - General 3 - Introduction 3 - Leadership in Energy & Environment 3 - Purpose 3 - LEED Rating System 4 - Energy & Atmosphere 4
More informationAir Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012
Air Side Economizers and Energy Recovery - Improvements and New Regulations Richard Lord 09-20-2012 Introduction For commercial buildings the use of outside air for cooling and ventilation is an important
More informationDuct Design. Presented by Dave Janquart
Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length
More informationMetrics for Energy Efficiency
The following article was published in ASHRAE Journal, April 28. Copyright 28 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes only.
More informationENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS.
1 ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS. - EXPERIENCE FROM A PLANT RECONSTRUCTION BASED ON A NEW SUPPLY AIR TERMINAL
More informationULTRA-EFFICIENT HVAC DESIGN AND CONTROL
CASE STUDY ULTRA-EFFICIENT HVAC DESIGN AND CONTROL MAJOR HEATING, VENTILATING AND AIR- CONDITIONING REPLACEMENT AT THE COUNTY OF SAN DIEGO CRIME LAB December 30, 2005 8520 Tech Way, Suite 110 San Diego,
More informationChilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
More informationAIR DISTRIBUTION ENGINEERING
AIR DISTRIBUTION ENGINEERING a1 a1-1 a1 Table of Contents Terms & Definitions...a1-...a1-3 Primary Jet...a1-3 Entrainment, Jet Interface, Primary Air, & Total Air...a1-4 Natural Convection Currents...a1-5
More informationFan Applications & System Guide
Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation
More informationMULTIZONE APPLICATION OF SOLUTION UNITS
MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages
More informationNew Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
More informationCHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
More informationExample Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
More informationRadiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
More informationCase Studies: Infrared Heating in Industrial Applications
Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000
More informationProper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History
Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems Ryan R. Hoger, LEED AP 708.670.6383 ryan.hoger@tecmungo.com History VAV systems came into favor for mid and large size
More information5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment
5.6 Technical Specification: Premium Efficiency Electric Conditioning Equipment Small Premium Project Type: For Premium Conditioning Retrofit Projects: Projects that voluntarily replace existing unitary
More informationFan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs Fan Performance (Paper I.D. 021) Mark Stevens Air Movement and Control Association International Abstract
More informationCondensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
More informationCenter for the Built Environment UC Berkeley
Center for the Built Environment UC Berkeley Peer Reviewed Title: Analysis of a hybrid UFAD and radiant hydronic slab HVAC system Author: Raftery, Paul, National University of Ireland Galway Lee, Kwang
More informationHow To Design A Power Plant
Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-6427 (510) 749-9135 Fax (510) 749-9136 LLC JEFF STEIN, P.E. Jeff Stein is a registered mechanical engineer with over 16 years
More informationHVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
More information2006 Delta T Corporation dba Big Ass Fan Company
Saving Energy Savings with HVLS Fans Josh Eddy LEED-AP National Sales Manager Big Ass Fans Outline Who is Big Ass Fans HVLS fan types How HVLS fans save energy HVLS fan applications How utilities are helping
More informationModeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
More informationDedicated Outdoor Air Systems (D.O.A.S.)
Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate
More informationVariable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
More informationHVAC. Kitchen Exhaust. rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier!
HVAC & Kitchen Exhaust The Heart of Restaurant HVAC rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier! 1 CKV Design: Just not that easy! There is no piece of equipment in the commercial
More informationConsiderations for Building Controls
Considerations for Building Controls Does Nighttime Setback really save energy? Natalia Camblor, CEM Project Engineer Sustainable Engineering Group LLC AIA Quality Assurance Learning Objectives 1. Recognize
More informationCirculator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE
This article was published in ASHRAE Journal, September 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without
More informationVenice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
More informationApplying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009
Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort
More informationComparisons of HVAC Simulations between EnergyPlus and DOE-2.2 for Data Centers
ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Comparisons of HVAC Simulations between EnergyPlus and DOE-2.2 for Data Centers Tianzhen Hong, Dale Sartor, Paul Mathew, Mehry Yazdanian Environmental
More informationBuilding Commissioning 17900-1
SECTION 17900 BUILDING COMMISSIONING PART 1 - GENERAL 1.01 WORK DESCRIPTION: A. General: 1. The Commissioning process is a joint team effort to ensure that all mechanical equipment, controls, and systems
More informationAppendix B: VAV Controller Flow Calculation Constants
Appendix Issue Date September 18, 2003 Appendix B: VAV Controller Flow Calculation VAV Controller Flow Calculation...2 Introduction... 2 ey Concepts... 3 About Flow Calculation... 3 Carnes Company... 4
More informationTABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C
Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the
More informationFAQ' s. Frequently Asked Questions. A1 Control Units. Pge 1 of 7 PUMPKIN HOOK ROAD PO BOX OGD VAN HORNESVILLE NY 13475 USA 315-858-1002
Frequently Asked Questions FAQ' s A1 Control Units Pge 1 of 7 Table of Contents Q-1 Who are OGD and V-HVAC? 3 Q-2 Why do I need the A1 Control Unit and what are the benefits? 3 Q-3 How is the A1 Control
More informationvav retrofit terminals
retrofit Redefine your comfort zone. www.titus-hvac.com energy solutions Table of Contents products Application Icons Key... 2 VAV Retrofit Terminals roducts... 3 external round duct series EXX, ECX and
More informationHOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
More informationFundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational
More informationSIMULATION OF RADIANT COOLING PERFORMANCE WITH
SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE
More informationENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
More informationPresented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE <walterjohnston@bellsouth.net
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE
More informationDehumidification Design
Dehumidification Design Using Data-Center Heat Utilizing free heat from a server room was the concept behind an air-handling system in a college-campus building Considerable energy savings are possible
More informationFan-Powered Parallel
Table of Contents Model Number Description FPP 2 3 Service Model Number Description FPP 4 Selection Procedure FPP 5 7 General Data Valve/Controller Airflow Guidelines FPP 8 Performance Data Pressure Requirements
More informationVariTrane Duct Designer An in depth look...
VariTrane Duct Designer An in depth look... Introduction The VariTrane Duct Designer duct design program was written to help optimize design while obtaining a minimum pressure system. The program is based
More informationAchieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled
More informationANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals
ANSI/AHRI Standard 880 (I-P) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:
More informationFlexibility, Efficiency In San Antonio Arena
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not
More informationCFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER
International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)
More informationHow To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
More informationProduct Data. Features/Benefits 37HC. Moduline VAV Air Terminals With Product Integrated Controls (PIC) Nominal 100 to 400 Cfm
Product Data 37HC Moduline VAV Air Terminals With Product Integrated Controls (PIC) Nominal 100 to 400 Cfm Features/Benefits Thirty years ago, Carrier s introduction of the first modular integral diffuser
More informationHVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
More informationApplication Guide. www.titus-hvac.com www.titus-energysolutions.com
Application Guide leed AND GREEN BUILDINGS www.titus-hvac.com www.titus-energysolutions.com table of contents General 3 Introduction 3 Leadership in Energy & Environment 3 Purpose 3 LEED Rating System
More informationfor Plans Examiners and Building Inspectors
Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared
More informationBring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
More informationThe Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control
The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control Chenggang Liu Research Associate Homer L. Bruner, Jr., CEM Mechanical Systems
More informationMistrale. Fusion Terminal
Mistrale Fusion Terminal PUBLICATION NATURAL VENT. 1 SEPT 2015 Features - Slimline energy efficient ventilation solution - Standard and high capacity terminals provide 128 or 256 L/s capacity - Compliant
More informationPreliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
More informationThe main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
More informationHVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
More informationMetrics That Matter: Pam Greenley MIT EHS Associate Director greenley@mit.edu. Steve Lanou MIT Deputy Director, Sustainability slanou@mit.
Metrics That Matter: Energy Efficiency in Laboratories Pam Greenley MIT EHS Associate Director greenley@mit.edu Steve Lanou MIT Deputy Director, Sustainability slanou@mit.edu Today Measuring progress of
More informationRole of the PI System in Research @ Georgia Tech Data Center Laboratory
Role of the PI System in Research @ Georgia Tech Data Center Laboratory Presented by Vaibhav K. Arghode Prepared by Vikneshan Sundaralingam Outline Data center laboratory general information Current use
More informationLife Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany
Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment
More informationOutline. CC objectives Site and building description Typical data floor overview CC measures Results Lessons learned
Outline CC objectives Site and building description ypical data floor overview CC measures Results Lessons learned 2 CC Objectives Identify and solve existing operating problems Improve building thermal
More informationWORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 Wallet card photocopy Inspection Authority: Signature: Date: / / Submitted For: ( Owner ) Name Address City Prov Postal code Phone ( ) Fax ( ) Designer/Signature:
More informationInstallation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
More informationFundamentals of HVAC Control Systems
ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong
More informationHIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons
Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined
More informationsecurity products metric sizes Redefine your comfort zone. www.titus-hvac.com
metric sizes secure lethal objects monitoring areas suicide deterrent Redefine your comfort zone. www.titus-hvac.com humid areas prevents corrosion minimum security medium security maximum security Table
More informationHow To Design A Room Air Conditioning System
Comparison of HVAC Technology in Buildings Conventional HVAC Technology Bauer Optimising Technology The Differences Room environment (Occupant Comfort) Energy Consumption Architecture Air flows in a room
More informationUnique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models
Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits
More informationCentrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
More informationHVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
More informationSelecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment
AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.
More informationThe New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
More information