ink Home Inspections, LLC
|
|
- Eustacia Mitchell
- 8 years ago
- Views:
Transcription
1 Cover Page ink Home Inspections, LLC Property Inspection Report Inspection prepared for: Carey Smith Real Estate Agent: agent ACME Homes Date of Inspection: 9/14/2013 Time: 9:00am - 12:00pm Age of Home: 42 years (Built in 1972) Size: 1340 Square Feet Weather: 65 Degrees Farenheit Inspector: Paul Ryan License #1127 PO BOX 55343, SEATTLE, WA Phone: Info@iNKinspections.com
2 Short Summary of Critical Items The following summary is not a comprehensive listing of all of the findings in the report, just potentially major items to note. These findings can be a safety hazard, a deficiency, or items that are important to note. Please review the report in its entirety as the summary alone does not explain all of the issues nor does it specify the systems of subsystems of the property. It is our recommendation that repairs be done by a licensed professional. I recommend obtaining a copy of all receipts, warranties and permits for any work completed. This report reflects the opinion of the inspector. Exterior Areas Page 5 Item: 6 Chimney Chimney wash needs repair. The wash is the concrete topping on the chimney allowing water to run off the top. Roof Page 6 Item: 1 Roof Condition Exposed nails on roofing material. Recommend sealing all fastener heads. Page 7 Item: 3 Chimney Chimney mortar shows sign of deterioration. Recommend having repaired as necessary. Basement/Crawlspace Page 8 Item: 2 Insulation Insulation was observed to be missing or out of place in one or more locations. Recommend replacing damaged insulation and securing any reusable pieces. Page 9 Item: 5 Slab Floor Loose cables and wiring need to be properly secured to structure and not dangling under structure. Miscellaneous debris scattered over crawl space floor, strongly recommend it be removed. Attic Page 11 Item: 5 Duct Work Oven hood vent duct is a flexible type, and not properly supported, recommend changing to a rigid duct to reduce any buildup. Page 11 Item: 6 Electrical All wiring should be properly secured to the framing. Garage Page 12 Item: 6 Electrical It is highly recommended to (have a qualified electrician) install an Arc Fault Circuit Interrupter breaker in place of the the one currently protecting the bedroom circuits,in the near future it will be a requirement and is a very safe and sound update. Page 12 Item: 9 Exterior Door Garage-to-house door may not be properly fire rated. No rated labels were found at time of inspection. Page 12 Item: 10 Fire Door The door between the garage & house may not be fire rated. This may not have been required when originally built. Fire doors are fundamental to the integrity of fire barriers which provide resistance to the spread of fire, smoke, and toxic gasses. This means that should a fire occur in the garage, this door does not afford timely protection for exit. This door should have a fire rating label to verify its rating. Page 13 Item: 13 Garage Opener Status Garage vehicle door sensors appear to be mounted higher than the standard auto-reverse height. Page 13 Item: 14 Garage Door's Reverse Status No photoelectric beam sensor present at proper mounting height. It is recommended not to be installed no higher then 6" for ground. Kitchen Page 16 Item: 3 Dishwasher Lack of a proper air gap noted at dishwasher drain line. In the event of a sewer backup this device prevents sewer matter from entering into dishwasher. Recommend having a qualified plumber install a air gap to prevent possible contamination. Page 17 Item: 5 Garbage Disposal No air gap between dishwasher and disposal. required strongly recommend having one installed. Page 17 Item: 9 Sinks Drain line from disposal to sink has improper flow. Page 18 Item: 10 Vent Condition Seal air gap around duct into attic. All air gaps between floors need to be sealed for fire safety reasons. Page 1 of 22
3 Inspection Details We appreciate the opportunity to conduct this inspection for you. Please review your entire inspection report carefully. Remember, when the inspection is completed and the report is delivered, we are still available to you for any questions you may have, throughout the entire closing process. A home inspection is a non-invasive visual examination of a residential dwelling, performed for a fee, which is designed to identify observed material defects within specific components of said dwelling. Components may include any combination of mechanical, structural, electrical, plumbing, or other essential systems or portions of the home. The inspection is intended to assist in evaluation of the overall condition of the dwelling and is based on observation of the visible and apparent condition of the structure and its components on the date of the inspection. This inspection is not intended as a prediction of future conditions. Properties being inspected do not "Pass" or "Fail. The following report is based on an inspection of the visible portion of the structure. It is important to note that the inspection may be limited by vegetation and possessions. Depending upon the age of the property, some common items may not be installed, i.e. GFI outlets. Therefore, this inspection and report focuses on safety, function and condition as oppose to current code. This report identifies specific non-code, non-cosmetic concerns that the inspector feels may need further investigation or repair, though cosmetic observations will be made. A material defect is a condition with a residential real property or any portion of it that would have a significant adverse impact on its value or that involves an unreasonable risk to people. The fact that a structural element, system or subsystem is near, at or beyond the end of the normal useful life is not by itself a material defect. An Inspection report shall describe and identify in written format the inspected systems, structures, and components of the dwelling and shall identify material defects observed. Inspection reports may contain recommendations regarding conditions reported or recommendations for correction, monitoring or further evaluation by professionals, but this is not required. If the living area has been remodeled or part of an addition, we recommend that you verify the permit and certificate of occupancy. This is important because our inspection does not tacitly approve, endorse, or guarantee the integrity of any work that was done without a permit, and latent defects could exist. For your safety and liability purposes, we recommend that licensed professionals evaluate and repair any critical concerns and defects. Note that this report is a snapshot in time. We recommend that you or your representative carry out a final walk-through inspection immediately before closing to check the condition of the property, using this report as a guide. Please feel free to contact our office with any questions or concerns and thank you for your business. 1. Attendance 2. Home Type 3. Occupancy Client present Buyer Agent present Fully Participated Attached Single Family Home Ranch Style Vacant - Furnished (Staged for sale) The utilities were on at the time of inspection. Page 2 of 22
4 1. Driveway and Walkway Condition Grounds Asphalt driveway noted. In good shape for its age Concrete walkway noted. Some cracks, no safety concerns. Driveway in good shape. Recommend sealing to extend life. Normal settlement / separation crack at concrete walk. Normal settlement / separation crack at concrete walk 2. Grading Highly recommend removing bricks from close proximity to the south side of the house. Present location invites insects and moisture against the house. Soil is in contact or in close proximity to the siding. This may provide entrance of moisture or insects to siding. Recommend pulling bark away so there is at least 6" of space (where practical) between the siding and the soil below, does not appear to have effected siding at time of inspection. This only exists in the front of the house. Back and sides are have proper clearance. Beauty bark needs to be pulled away from house a minimum of 6" clearance. Highly recommend removing bricks from close proximity to the south side of the house. Present location invites insects and moisture against the house. Beauty bark need to be pulled away from house min of 6" clearance. Page 3 of 22
5 3. Vegetation Observations Tree limbs within 10 feet of roof on south east corner. The limbs should be trimmed away to provide air and sunlight to roof, to minimize debris and dampness. 4. Gate Condition Wood Gate operated as designed. 5. Patio and Porch Deck Newly constructed at time of inspection. Deck substructure inspection excluded, due to no reasonable access (low clearance). 6. Stairs & Handrail 7. Grounds Electrical Appeared functional at time of inspection. Service Entrance : Electrical service underground. Meter located at front side of home left of entrance. Property equipped with a 200 AMP electrical panel. 8. GFCI 9. Main Gas Valve Condition North side. Meter located on exterior. Each gas appliance has its own shut-off valve in line. No gas odors detected. 10. Plumbing 11. Water Pressure 12. Pressure Regulator Copper piping noted. Recommend 80 psi. We recommend the installation of a pressure regulator. Page 4 of 22
6 13. Exterior Faucet Condition Location: Front of structure. East side of house. Appears functional. One or more water hose bibs are not frost proof and will need to be winterized before next cold weather season as pipe damage can occur. Exterior Areas 1. Doors 2. Window Condition 3. Siding Condition 4. Eaves & Facia 5. Exterior Paint 6. Chimney Appeared in functional and in satisfactory condition, at time of inspection. Components appeared in satisfactory condition at time of inspection. Cedar siding noted and in good shape. No major system safety or function concerns noted at time of inspection. Suggest sealing/caulking as part of routine maintenance. Recent paint noted on house. Chimney wash needs repair. The wash is the concrete topping on the chimney allowing water to run off the top. Re- grout mortar joints where needed at brick joints. Chimney wash needs repair. The wash is the concrete topping on the chimney allowing water to run off the top. Page 5 of 22
7 Chimney wash needs repair. The wash is the concrete topping on the chimney allowing water to run off the top. Chimney wash needs repair. The wash is the concrete topping on the chimney allowing water to run off the top. Re- Grout mortar Joints where needed at brick joints. 1. Roof Condition Egressed roof Roof Asphalt shingles noted. Clean roof areas signs of organic debris evident. Exposed nails on roofing material. Recommend sealing all fastener heads. Page 6 of 22
8 Clean roof areas: Signs of organic debris evident. Clean roof areas: Signs of organic debris evident. Exposed nails on roofing material. Recommend sealing all fastener heads. 2. Flashing Exposed nails on roofing material. Recommend sealing all fastener heads. 3. Chimney The chimneys flue is missing its rain cap. This is a potential point of water entry and can lead to deteriorating brickwork. Have rain caps installed by a qualified individual. Chimney mortar shows sign of deterioration. Recommend having repaired as necessary. Page 7 of 22
9 The chimneys flues are missing rain cap. This is a potential point of water entry and can lead to deteriorating brickwork. Have rain caps installed by a qualified individual. 4. Spark Arrestor 5. Gutter No chimney rain cap observed, suggest installing a chimney rain cap to prevent the entrance of the elements and local wildlife and to preserve the life of the chimney as well as minimize maintenance. No major system safety or function concerns noted at time of inspection. 1. Walls 2. Insulation 3. Plumbing Materials Basement/Crawlspace Crawlspace noted. No deficiencies were observed at the visible portions of the structural components of the home. Insulation was observed to be missing or out of place in one or more locations. Recommend replacing damaged insulation and securing any reusable pieces. Supply line for fridge water supply and or ice maker not properly attached to structure and needs to be properly secured. Copper Page 8 of 22
10 4. Access fridge supply line attachment improperly attached supply line. 5. Slab Floor Dirt Floor with plastic vapor barrier noted. Prior evidence of rodent droppings and debris. No current activity at time of inspection Loose cables and wiring need to be properly secured to structure and not dangling under structure. Miscellaneous debris scattered over crawl space floor, strongly recommend it be removed. loose cables and wiring need to be properly secured to structure and not dangling under structure. Miscellaneous Debri scattered over Crawl space floor, Strongly Recommend it be removed. Page 9 of 22
11 6. Finished Floor Prior evidence of rodent droppings and debri. NO CURRENT Activity at time of inspection 7. Framing Appears functional. 8. Subfloor 9. Columns 10. Piers No deficiencies were observed at the visible portions of the structural components of the home. No deficiencies were observed at the visible portions of the structural components of the home. 1. Access 2. Structure Attic Attic access is located in the ceiling garage in front of water heater. Overall structure of the attic/roof in sound condition. Page 10 of 22
12 3. Ventilation 4. Vent Screens 5. Duct Work Under eave soffit inlet vents noted. Fixed, roof-field exhaust vent noted. Vent screens noted as functional. Oven hood vent duct is a flexible type, and not properly supported, recommend changing to a rigid duct to reduce any buildup. Oven hood vent duct is a flexible type, and not properly supported, recommend changing to a rigid duct to reduce any buildup. 6. Electrical All wiring should be properly secured to the framing. 7. Insulation Condition Loose fill insulation noted. Depth: Insulation averages about 4-6 inches in depth; more recommended. Insulation level in the attic is typical for homes this age. 1. Roof Condition 2. Walls Garage Roofing is the same as main structure. Asphalt shingles noted. Clean roof areas, organic debris evident. No major system safety or function concerns noted at time of inspection. Page 11 of 22
13 3. Anchor Bolts 4. Floor Condition 5. Rafters & Ceiling 6. Electrical 7. GFCI Volt 9. Exterior Door 10. Fire Door The builder used masonry or "cut" nails to attach the bottom plates to the foundation wall. We recommend adding retrofit style anchor bolts as necessary. Bare concrete floors noted. Garage floor in good shape for age of the house. Visible areas appear satisfactory, at time of inspection. It is highly recommended to (have a qualified electrician) install an Arc Fault Circuit Interrupter breaker in place of the the one currently protecting the bedroom circuits,in the near future it will be a requirement and is a very safe and sound update. GFCI in place and operational, GFCI was not requirement in garage at time of construction. All garage outlet should be upgraded if not already in place. There are no 240 volt outlets visible in this room. Garage-to-house door may not be properly fire rated. No rated labels were found at time of inspection. Self-closing hinges operational when tested. The door between the garage & house may not be fire rated. This may not have been required when originally built. Fire doors are fundamental to the integrity of fire barriers which provide resistance to the spread of fire, smoke, and toxic gasses. This means that should a fire occur in the garage, this door does not afford timely protection for exit. This door should have a fire rating label to verify its rating. 11. Garage Door Condition Roll-up door noted. Missing handle. 12. Garage Door Parts The garage door appeared functional during the inspection. 13. Garage Opener Status Garage vehicle door sensors appear to be mounted higher than the standard auto-reverse height. Page 12 of 22
14 14. Garage Door's Reverse Status Photo sensors missing at proper location. The door auto-reverse mechanism is in working order at time of inspection. No photoelectric beam sensor present at proper mounting height. It is recommended not to be installed no higher then 6" for ground. 15. Ventilation 16. Vent Screens Fixed, roof-field exhaust vent noted. Vent screens noted as functional. Water Heater 1. Base The water heater base is functional. 2. Water Heater Condition Heater Type: Electric Location: The heater is located in the garage. A Temperature Pressure Relief (TPR) valve present. This safety valve releases water (and thus relieves pressure) if either the temp or pressure in the tank gets too high. The TPR valve discharge tube must be made of copper, iron, or CPVC (NOT regular PVC). It must terminate within 6" above the floor--the end cannot be threaded or have a fitting. Water Source: Public Water heater manufactured 2012 Page 13 of 22
15 3. TPRV 4. Number Of Gallons 5. Plumbing A Temperature Pressure Relief Valve (TPR Valve) present. This safety valve releases water (and thus relieves pressure) if either the temp or pressure in the tank gets too high. The TPR valve discharge tube must be made of copper, iron, or CPVC (NOT regular PVC). It must terminate within 6" above the floor--the end cannot be threaded or have a fitting. 50 gallons Copper No deficiencies observed at the visible portions of the supply piping. Main water Shut off valve, Located in garage. Recommend adding pressure regulator. 6. Overflow Condition 7. Strapping Copper Appears to be in satisfactory condition -- no concerns. Water heater straps present Example of installed pressure regulator. Electrical Page 14 of 22
16 1. Electrical Panel 2. Main Amp Breaker Location: Main Location: interior of garage. Location: Located in the garage. No major system safety or function concerns noted at time of inspection at main panel box. Aluminum wiring present Between 1965 and 1973, aluminum wiring was sometimes substituted for copper wiring in residential electrical systems. Connections in outlets, switches, and light fixtures with aluminum wiring become increasingly dangerous as time passes. Poor connections cause wiring to spark and overheat, creating a potential fire hazard. The wiring should be evaluated by a qualified electrician experienced in evaluating and correcting aluminum wiring problems. Not all electrical contractors qualify. Aluminum wiring connections are subject to greater deterioration than is copper due to thermal expansion and contraction, vibration (caused when electric currents pass through wiring), oxidation (caused by exposure to oxygen in the air), and galvanic corrosion (caused when two different metals are connected together), all of which can cause poor connections. When wires are poorly connected they overheat, which creates a potential fire hazard. 200 amp 3. Breakers in off position 1 (dish washer) 4. Cable Feeds 5. Breakers There is an underground service lateral noted. Aluminum non-metallic sheathed cable noted. All of the circuit breakers appeared serviceable. 6. Fuses 1. Heater Condition Heat/AC The furnace is located in the garage Gas fired forced hot air. Fuel Furnace: Last service date is over one year ago, or is unable to be determined. Although this unit appears to be operating properly from controls, there are areas which cannot be seen without specialized equipment and training. One such area is the combustion chamber / heat exchanger where cold air blows across the "fire box", becoming the hot air that circulates throughout your home. During the life span of any furnace, this metal wall may develop a crack or a broken weld, allowing carbon monoxide to circulate throughout the home. This is why furnace specialists recommend a complete inspection annually; consider having unit inspected by certified HVAC technician. Page 15 of 22
17 2. Heater Base 3. Venting 4. Gas Valves 5. Registers 6. Filters 7. Thermostats The heater base appears to be functional. Metal double wall chimney vent pipe noted. Gas shut off valves were present within a safe proximity of furnace. The return air supply system appears to be functional. Location: Located inside heater cabinet. MAINTENANCE: The air filter(s) should be inspected at least monthly and cleaned or replaced as required. There are two types of filters commonly used: (1) Washable filters, (constructed of aluminum mesh, foam, or reinforced fibers) these may be cleaned by soaking in mild detergent and rising with water. Or (2) Fiberglass disposable filters that must be REPLACED before they become clogged. Remember that dirty filters are the most common cause of inadequate heating or cooling performance. Functional at the time of inspection. 1. Cabinets 2. Counters 3. Dishwasher 4. Doors Kitchen Appeared functional and in satisfactory condition, at time of inspection. Plastic laminate tops noted. There is normal wear noted for the age of the counter tops. Dish washer water did not run Lack of a proper air gap noted at dishwasher drain line. In the event of a sewer backup this device prevents sewer matter from entering into dishwasher. Recommend having a qualified plumber install a air gap to prevent possible contamination. Page 16 of 22
18 5. Garbage Disposal Operated - appeared functional at time of inspection. No air gap between dishwasher and disposal. required strongly recommend having one installed. 6. Microwave 7. Cook top condition 8. Oven & Range No air gap between dishwasher and disposal. required strongly recommend having one installed. Built-in microwave ovens are tested using normal operating controls. Unit was tested and appeared to be serviceable at time of inspection. Electric cook top noted. All heating elements operated when tested. All heating elements operated when tested. 9. Sinks Drain line from disposal to sink has improper flow. Page 17 of 22
19 10. Vent Condition Drain line from disposal to sink has improper flow. Exterior Vented Seal air gap around duct into attic. All air gaps between floors need to be sealed for fire safety reasons. seal air gap around duct into attic. all air gaps between floor need to be sealed for fire safety reasons. 11. Window Condition Vinyl framed sliding window noted. Outlet cover missing, Replace missing cover. 12. Floor Condition 13. Plumbing Hardwood flooring is noted. Galvanized. Plumbing noted under sink. Page 18 of 22
20 14. Ceiling Condition 15. Patio Doors There are drywall ceilings noted. Sliding Patio Doors. 16. Screen Doors 17. Electrical 18. GFCI No major system safety or function concerns noted at time of inspection. GFCI in place and operational. 1. Locations 2. Cabinets 3. Ceiling Condition 4. Counters 5. Doors 6. Electrical Bathroom Locations: Full bath in hallway, half bath by garage. No deficiencies observed - new cabinets There are drywall ceilings noted. Granite or natural stone tops noted. No major system safety or function concerns noted at time of inspection. No major system safety or function concerns noted at time of inspection. Page 19 of 22
21 7. GFCI 8. Exhaust Fan 9. Floor Condition 10. Heating 11. Mirrors 12. Plumbing 13. Showers 14. Shower Walls GFCI in place and operational The bath fan was operated and no issues were found. Natural stone floors noted. Heat lamp mounted in the ceiling noted in this room. At the time of the inspection, it appeared to be functioning and in serviceable condition. Up to standard at time of inspection. Functional Ceramic tile noted. Caulking or latex based color matched grout needed in the corners of showers where cracks in grout are present. Caulking needed in the corners of showers where cracks in grout are present. Page 20 of 22
22 15. Bath Tubs 16. Enclosure 17. Sinks 18. Toilets 19. Window Condition Tub with left-hand drain. The shower enclosure was functional at the time of the inspection. Operated normally, at time of inspection. Operated when tested. No deficiencies noted. Observed as functional and in good visual condition. Vinyl framed sliding window noted. 1. Locations 2. Closets 3. Doors 4. Electrical Locations: Master Hall#1 Hall#2 Bedrooms The closet is in serviceable condition. All doors were in proper operating order at time of inspection. No Arc-Fault Circuit Interrupter (AFCI) protection was installed to protect electrical circuits in bedrooms. Building codes with which new homes must comply require the installation of AFCI protection of all bedroom outlets. This type of protection is designed to detect electrical arcing, which is a potential fire hazard. Although AFCI protection was not required at the time the home was originally constructed, as general knowledge of safe building practices has improved with the passage of time, building standards have changed to reflect current understanding. Consider updating the existing electrical to provide AFCI protection. Arc-fault protection can be provided using either of two methods: 1. Arc Fault Circuit Interrupters (AFCI's) electrical outlets which have this capability built in. 2. AFCI circuit breakers installed at the main electrical panel which provide this protection to all non- AFCI outlets on the circuit controlled by that AFCI breaker. Page 21 of 22
23 5. Floor Condition 6. Smoke Detectors 7. Window Condition Flooring Types: Carpet is noted. The smoke detectors were present in proper location. Vinyl framed sliding window noted. Newer vinyl windows is good operating condition at time of inspection. 1. Locations 2. Counters 3. Dryer Vent Locations: Bathroom Area Laundry 4. Exhaust Fan 5. Wash Basin 6. Floor Condition The exhaust fan was operated and no issues were found. Good working condition. Natural stone floors noted. 7. Plumbing Page 22 of 22
Vari Inspection Services
Cover Page Vari Inspection Services Property Inspection Report Inspection prepared for: Sample Real Estate Agent: None - Date of Inspection: 5/13/2015 Inspector: Tony Vari License # HI8047 23110 STRD 54
More informationGeorgia Home Inspection Services
Cover Page Property Inspection Report My street, Anytown GA, 30000 Inspection prepared for: John Doe Inspection Date: 7/18/2011 Time: 5pm Age: 25+ Size: >1500 Weather: Clear This ranch style home is in
More informationPROPERTY INSPECTION REPORT
(850) 297-1998 1716 Monticello Dr Tallahassee, Florida 32303 PROPERTY INSPECTION REPORT THIS INSPECTION IS A DETAILED LISTING OF AREAS VISUALLY INSPECTED AT:, Tallahassee FL Client Tallahassee, FL 32304
More informationInspecton Report. Property Address:
Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 bob@nationalhomeinspections.com www.nationalhomeservices.com Property Address: 873
More informationA and S Property Inspector
Cover Page A and S Property Inspector Property Inspection Report Inspection prepared for: xxxxx xxxxx Real Estate Agent:.. - Date of Inspection: 8/25/2014 Time: 10am Age of Home: 1999 Size: 1841 Weather:
More informationHome Inspection Report
Report# 21009 Page 1 of 24 Home Inspection Report Property Address: 123 Maple Lane, St. Augustine, FL 32092 Prepared For: Mr. Smith Prepared By: EDGE Inspections www.edgeinspections.com PO Box 601055 Jacksonville,
More informationCOMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
More informationHome Inspection Report
4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:
More informationSelf-Home Inspection Checklist
To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional
More informationSNS Home Inspections LLC
Cover Page SNS Home Inspections LLC Property Inspection Report 12345 Inspection prepared for: Donald Duck Real Estate Agent: - Date of Inspection: 2/21/2015 Time: 1:00 PM Age of Home: 1988 Size: 1866 sq
More informationHOME INSPECTION CHECKLIST
CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways
More informationSNS Home Inspections LLC
Cover Page SNS Home Inspections LLC Property Inspection Report 32750 Inspection prepared for: Donald Duck Real Estate Agent: - Date of Inspection: 2/6/2015 Time: 2:00 PM Age of Home: 1980 Size: 2453 sq
More informationA.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111
A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111 Inspector Name: Tim Knight, ASHI Member 202490 Inspection No: 12121212 Inspection Date: 1/1/2012 Client: Address: John
More informationPropery Inspection Report
Propery Inspection Report Cover Page,, Ok Inspection prepared for: Date of Inspection: 9/28/2014 Time: 8:30 AM Age of Home: 2011 MOL Weather: Clear 62 degrees Inspector: License #130 5400 Hwy 177, Marland,
More informationReport for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
More informationCLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
More informationPrinted Monday, August 27, 2007 Inspected By: Michelle Teague. Client Information: Inspection, Condo City Lane Chicago, IL. Inspected 8/22/07 8:00 AM
Pa g e 1 o f 1 5 All About Homes, LLC Michelle M. Teague Owner 312-371-7414 Phone 773-508-6209 Fax www.michelleinspects.com michelle@michelleinspects.com 1725 W. Granville Ave. Chicago, IL 60660 Printed
More informationTotal Home Inspection Checklist
Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are
More informationCHRIS CURLES and ASSOCIATES INSPECTION SERVICES
CHRIS CURLES and ASSOCIATES INSPECTION SERVICES Inc. Chris Curles, President www.homeinspectionsatlanta.com chriscurl@comcast.net Office: 770-493-0227 Professional Member Of: GAHI # 93006 ASHI # 211725
More informationBuilding Condition Assessment Report
Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.
More informationINSPECTION PROPERTY ADDRESS: Fort Bend County, Texas
5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction
More informationQuality Home Inspections, LLC 4433 Tennyson Street Denver, Colorado 80212 303-885-1288
Page 1 of 22 Quality Home Inspections, LLC 4433 Tennyson Street Denver, Colorado 80212 303-885-1288 Printed Friday, January 16, 2015 Inspected By: Dale Gibbs Referral Information Joe Agent Client Information:
More informationVision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
More informationMagpie Property Inspections LLC
Cover Page Magpie Property Inspections LLC Property Inspection Report, Denver, CO 80224 Inspection prepared for: Date of Inspection: 5/3/2013 Time: 2:00 Age of Home: 1898 Size: 2600 approx Weather: Clear
More informationAccurate Home Inspection of Illinois. Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave., Westmont, Illinois
Accurate Home Inspection of Illinois 815-260-1727 1213 Norley st. Joliet, illinois 60435 aaccurate1@yahoo.com We Inspect to Protect!!! Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave.,
More informationSWF Home Inspections
Cover Page SWF Home Inspections Property Inspection Report Inspection prepared for: Mr & Mrs Home Buyer Real Estate Agent: My Favorite Agent - Date of Inspection: 7/4/2013 Age of Home: 2004 Size: 1568
More informationwww.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
More informationInspection Tech. (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg
Inspection Tech (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg Inspection Tech Home Inspection Report Prepared For: Mr. & Mrs. Homebuyer Property
More informationBUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
More informationHome Inspection Report
Home Inspection Report Cincinnati, Ohio 45000 Prepared for: Dean Murphy Prepared by: BEDROCK ENTERPRISES, INC. 4060 Simca Lane Cincinnati, OH 45211 20:13 July 07, 2008 Page 1 of 18 Definitions NOTE: All
More informationReport Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10
Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 PROPERTY DESCRIPTION PROPERTY INSPECTED: INSPECTION ADDRESS: 4722 Baltimore Avenue
More informationInspection Report Atlanta Strip Mall Commercial Building Property Address:
Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of
More informationI NI NP R Inspected Items
6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and
More informationCrawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
More informationOrlando Home Inspection Services
PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com
More informationInspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
More informationCode Enforcement Inspection Manual. City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division
Code Enforcement Inspection Manual City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division LIVING ROOM 304.15 EXTERIOR DOOR(S) Check door(s) and trim for condition,
More informationPre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
More informationInspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668
Inspection Report Property Address: 123 Dream Home Way Frisco, CO 80443 Prepared for: Inspector: Tim Nixon Tim Nixon Inspection date: 3/28/2014 1 of 9 General Information Property Information Address:
More informationA TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared
More informationInspection Report. Prepared For: Sampath Sample. Property Address: 12712 Waterside Drive. Alpharetta, GA 30004. Atlanta Home Inspections
Page 1 of 37 Inspection Report Prepared For: Sampath Sample Property Address: Alpharetta, GA 30004 Atlanta Home Inspections Matthew A Thoroman 6625 Hwy. 53 E. Ste. 410-151 Dawsonville Ga 30534 (678)-410-8062
More informationInspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com
More information#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check
#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check Zoning laws Deed restrictions on home size, foundation style, roof pitch, etc. Suitability (slope, wetland issues, etc.) Accessibility
More informationRRIO Checklist. Use of checklist: Definitions: Limitations
CITY OF SEATTLE RENTAL REGISTRATION AND INSPECTION ORDINANCE (RRIO) RRIO Checklist Use of checklist: Property owners will use the RRIO Checklist to confirm that their rental housing properties and units
More informationA comfortable house is a great source of happiness. - Sydney Smith. Home Maintenance Guide
A comfortable house is a great source of happiness. - Sydney Smith Home Maintenance Guide HOME GUIDE By conducting regular maintenance checks, you can prevent small inexpensive repairs from becoming more
More informationReal Estate Inspection Report
1010 22nd Ave N Naples, Florida 34103 Real Estate Inspection Report 470 Golden Gate Blvd W Naples, Florida 34120 Page 1 of 19 Table of Contents Definitions 2 General Information 2 Lots and Grounds 3 Exterior
More informationEAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST
DATE TIME EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST INSPECTOR: LICENSE # ADDRESS: PROPERTY OWNER: SINGLE: DOUBLE: MULTI-UNIT # OF UNITS POINT OF INSPECTION Sanitation IPMC 302.1
More informationEstimating Database Checklist
Estimating Database Checklist If you are creating a new estimating database for projects, the following list offers a thorough listing of Main and Sub Categories. You can also use it as a checklist to
More informationNew Home Walk-Through Package
New Home Walk-Through Package Carrying out a Successful Walk-through Before Closing John MacDonald Architect inc. The Courtyard @ Bonnie Stuart, 141 Whitney Place Suite 101, Kitchener, ON. N2G 2X8 New
More informationBuilding Condition Assessment Report
C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses
More informationSummit Series Single Section and Double Section Homes
Single Section and Double Section Homes SM-01 All New 20 Wides Now Available! SM-08 Units shown with optional features SM-01-4814 42 Bedrooms 41 Bathrooms 648 Sq. Ft. SM-01-5214 42 Bedrooms 41 Bathrooms
More informationCity of St. Charles Basement Finish or Remodel
City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct
More informationInspection Report. Mr. Sample Sample. Property Address: 1234 USA Drive Indianapolis IN 12345. 1234 USA Drive. Morris Home Inspection Group, LLC
Inspection Report Mr. Sample Sample Property Address: 1234 USA Drive Indianapolis IN 12345 1234 USA Drive Morris Home Inspection Group, LLC Cedric Morris HI01200039 Fishers, IN 46037 317-550-6281 Table
More informationAztec Property Inspections 2719 Mission Blvd San Diego, CA 92109 (858) 245-9329. 6352 Some Road San Diego, CA 92114
2719 Mission Blvd San Diego, CA 92109 (858) 245-9329 Client: Could Be You 6352 Some Road San Diego, CA 92114 Page 1 of 14 Defective Summary This summary is not the entire report. The complete report may
More informationCOST OF WORK FORM. Abbreviations: ea = each, LF = linear feet, SF = square feet, HSF = square feet of living area (including garage conversion space)
COST OF WORK FORM All costs shown are estimates using base grade materials, taxes, and labor. For houses where a higher quality is indicated, the costs should be increased for work requiring upgraded materials.
More informationBOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE
More informationHome Inspection Report
Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector
More informationPROPERTY INSPECTION REPORT Property Address:
Scott Certified Member P. O. Box 9007 Indianapolis, IN 690-007 (7)-750-60 Fax: 7-876-8 PROPERTY INSPECTION REPORT Property Address: Prepared for: Inspection Inspector: Lou Buehler Inspection #: BUYERS
More informationVirginia Maintenance Code Requirements
Virginia Maintenance Code Requirements THE VIRGINIA MAINTENANCE CODE The City of Roanoke has adopted and enforces the Virginia Maintenance Code (VMC) on all existing structures located in the city. This
More informationBUILDING ANALYSIS REPORT. John Doe 1234 Smith Road Atlanta, Georgia 30396
BUILDING ANALYSIS REPORT July 25, 2014 John Doe 1234 Smith Road Atlanta, Georgia 30396 Agent: Ausker and Barbara Morris AT Morris Realty Group, Inc. 3162 Johnson Ferry Road, Suite 260-25 Marietta, Georgia
More informationHome Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
More informationHome Inspection Report
Home Inspection Report 555 Wind Way, Fake City, OR 54645 Inspection Date: Monday May 12, 2014 Prepared For: John Doe Prepared By: House to Home 3468 N. Bartlett Ave Milwaukee, WI 53211 262-754-5973 christopher@ahit.com
More informationSouth Carolina Home Inspector Standards of Practice
South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,
More informationSAMPLE INSPECTION REPORT PREPARED FOR: John Q Public
925 W. Baseline Road Suite 105-Y1 Tempe AZ 85283 Tel: 480-456-8809 Fax: 480-456-6139 Mobile: 602-790-0976 www.accuproinspect.com AccuPro@AccuProINSPECT.com SAMPLE INSPECTION REPORT PREPARED FOR: John Q
More informationInspection Report. provided by: Delaware Property Inspection. Inspector: Richard Hiddemen (302)355-1748
Inspection Report provided by: Delaware Property Inspection Inspector: Richard Hiddemen (302)355-1748 ASHI # 243377 DPR #H4-0000018 DDA #06-444 Delaware 1992105842 Wilmington #03857 New Castle #2010-845
More informationInspection Report. Prepared for: William Smith 2700 New Street Plano, TX 75025
Inspection Report Prepared for: William Smith 2700 New Street Plano, TX 75025 This report sample only includes minimal information to display the report's format. Your individual inspection reports may
More informationVilla Home Inspections
PROPERTY INSPECTION REPORT SITE INFORMATION Property Address: City, State, Zip: Date of Inspection: Time of Inspection: Parties Present during Inspection: Inspector: Address Omitted. Inglewood, CA 90305.
More informationBuilding Permits: When are they required?
Building Permits: When are they required? Generally, you need to obtain a building permit from the City whenever you construct, enlarge, alter, repair, move, remove, improve, convert, or demolish a building
More informationPROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792
More informationInspection Report. Jacksonville Krystals Inspection. Property Address: Downtown. Jacksonville FL 32204. South East Building Consultants
Page 1 of 53 Inspection Report Jacksonville Property Address: Jacksonville FL 32204 South East Building Consultants Ray Thoroman Inspecting Jacksonville FL and entire South East Page 2 of 53 Table of Contents
More informationSUMMARY REPORT THE BOTTOM LINE. Electrical. Report Number: 1860. Inspection Date: Saturday, February XX, XXXX
SUMMARY REPORT Report Number: 1860 Inspection Date: Saturday, February XX, XXXX Property Address: XX XXXXX XXX Toronto, ON XXX XZX Client Name: Xxxx Xxxxxxxxxxxxx Prepared by: Andrew Marioselva BSc,CHI
More informationKITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
More informationInspection Report. Prepared For: Atlanta Commercial Customer. Property Address: xxx Sandy Plains Road. Building 5 Marietta, GA 30066
Page 1 of 58 Inspection Report Prepared For: Atlanta Commercial Customer Property Address: Building 5 Marietta, GA 30066 Superior Home Inspections Ray Thoroman 8070 Ivy Shaw Dr. Gainesville,GA 30506 678-410-3005
More informationU.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live!
U.S. Department of Housing and Urban Development Office of Public and Indian Housing A Good Place to Live! Introduction Having a good place to live is important. Through your Public Housing Agency (or
More informationHOME INSPECTION REPORT
Edgewood Home Inspections, Inc. 407 W. Smith Valley Rd. #1032 Greenwood, IN 46142 (317) 833-6048 HOME INSPECTION REPORT Indianapolis IN 46000 Inspector's Name: License Number: Scott Kissel HI00800073 TABLE
More informationNovember 18, 2010. Customer Name Customer Address. Inspection Address Seattle, WA Inspection #: Dear Customer:
5921 Indian Trail SE Tacoma, WA 98422 253-235-5678 Fax: -- www.homteaminspection.com/southsound E-mail: ht646@hometeaminspection.com November 18, 2010 Customer Name Customer Address RE: Inspection Address
More informationGROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More information2. What building projects are exempted? (permit not required)
BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and
More informationSimplify. Homeownership
Simplify Homeownership Home Pulse An Innovative Program To Maintain Your Home. The Home Pulse Preventive Maintenance Plan will keep your home looking great, dramatically slow the deterioration process
More informationInspection Report. Mr. Happy 2 flat owner. Property Address: Focal Point Home Inspection Ltd.
Page 1 of 35 Inspection Report Mr. Happy Property Address: Joseph Poelsterl 450.010220 6334 W. Grace st Chicago Illinois 60634 1-773-454-6700 Page 2 of 35 Table of Contents Cover Page Table of Contents
More informationINSPECTION REPORT. LOCATION OF PROPERTY 1234 Sample Street Tucson, AZ 85701. CLIENT Mr. & Mrs. John Q. Sample c/o Agent DATE OF INSPECTION 1/30/2008
INSPECTION REPORT LOCATION OF PROPERTY 1234 Sample Street CLIENT Mr. & Mrs. John Q. Sample c/o Agent DATE OF INSPECTION 1/30/2008 INSPECTOR Dave Woityra FILE CODE: 0100114.SAM AGENT Sample Q. Jones A.B.C.
More informationHow To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
More informationHow To Insure Against Problems With Your Home Warranty
Subcontractor Warranty Policy ALL WARRANTY REQUESTS MUST BE IN WRITING. Please submit all warranty requests online by visiting: www.rigginscustomhomes.com/customerservice.html Please fill out the form
More informationHome Warranty Inspection Report
Scope of the Inspection 1111 Sample Dr. home warranty inspection 2/30/2006 Home Warranty Inspection Report 1111 Sample Dr., Detroit, MI 48223 Inspection Date: February 30, 2006 Client: Alfred E. Neumann
More informationLicense Requirements for Persons Engaging in the Business of Inspection Practice:
SC Standards of Practice SOUTH CAROLINA RESIDENTIAL BUILDERS COMMISSION HOME INSPECTOR STANDARDS OF PRACTICE Adopted by the Residential Builders Commission May 13, 1998 PURPOSE: The purpose of a residential
More informationInspection Report TPCC. Property Address: 22 Touisset Road Warren RI 02885. Lane's Perfection Inspections
Inspection Report TPCC Property Address: 22 Touisset Road Warren RI 02885 Lane's Perfection Inspections Lane Ukura Ma.# 578 7 St.Louis Avenue Bristol, R.I. 02809 401-255-0726 Table of Contents Cover Page...1
More informationThis handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
More informationBurns Home Services SUMMARY REPORT. 7/18/2006 Start: 9:00 am End: 12:30 pm
Burns Home Services Service Makes the Difference 2620 W Grovers Ave, Phoenix, AZ 85053 Tel: 602-889-6970 Fax: 602-870-4563 Mobile: 602-291-7138 Garryh@burnshomeservices.com SUMMARY REPORT Client: John
More informationHome. Safe. Home. home inspection report
home inspection report Home. Safe. Home. Each office is independently owned and operated. 2013 The HomeTeam Inspection Service, Inc. All rights reserved. What is a home inspection? The purpose of a home
More informationHomeSpec REPORT SUMMARY
HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above
More informationTerry Jenkins, Owner Member, American Society of Home Inspectors Virginia Certified Home Inspector Certificate # 3380 000373, expires 1/2010
Terry Jenkins, Owner Member, American Society of Home Inspectors Virginia Certified Home Inspector Certificate # 3380 000373, expires 1/2010 Tel: (804) 378-0861 terry@prospectpropertiesva.com Inspection
More informationThe BrickKicker is pleased to present this professional home inspection report for the property located at: 123 Main St. Happy Town, IL 65432
The BrickKicker is pleased to present this professional home inspection report for the property located at: 123 Main St. Happy Town, IL 65432 inspected on 05/26/2014 For more information please contact
More informationGeorgiaHomePros.com. 6858 Yellow Creek Road Ball Ground, GA 30107 770-893-2271 www.georgiahomepros.com inspections@tds.net Inspected By: Scott Webb
GeorgiaHomePros.com 6858 Yellow Creek Road Ball Ground, GA 30107 770-893-2271 www.georgiahomepros.com inspections@tds.net Inspected By: Scott Webb Home Inspection Report Prepared For: Jack & Diane Samples
More informationHOMEOWNER S PERMIT GUIDE
HOMEOWNER S PERMIT GUIDE WHEN IS A PERMIT REQUIRED? Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor P.O. Box 15225 Chesapeake, VA 23328 Phone: (757) 382-6018 Fax: (757) 382-8448
More informationGENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
More information19 Ellis Park Road, Toronto
19 Ellis Park Road, Toronto Inspection Report September 9, 2015 19 Ellis Park Road, Toronto Inspection Report Overall Condition: This is a solidly built older double-brick home that is in fairly original
More informationStructure Survey Findings:
Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,
More informationJoe Buyer 12345 Somewhere Special St.
This Home Inspection Report Has Been Prepared Exclusively For: Joe Buyer 12345 Somewhere Special St. Oklahoma City, OK 73123 Dan Bixler - OK Lic#258 PROFESSIONAL & COMMERCIAL INSPECTION SERVICE Copyright
More informationTable of Contents. Definitions General Information Lots and Grounds Exterior Surface and Components Garage/Carport Electrical
Page 1 of 24 Table of Contents Definitions 2 General Information 2 Lots and Grounds 3 Exterior Surface and Components 4 Garage/Carport 5 Electrical 5 Roof 7 Air Conditioning 8 Fireplace/Wood Stove 8 Heating
More information159 Morningside Avenue, Toronto
159 Morningside Avenue, Toronto Inspection Report February 6, 2013 159 Morningside Avenue, Toronto Inspection Report Overall Condition: This 60±-year-old home was extensively renovated and extended in
More information