Pre-Drywall Inspection Report

Size: px
Start display at page:

Download "Pre-Drywall Inspection Report"

Transcription

1 SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia Prepared for Betsy and Paul Dougherty January12, 2015 Medallion Services Group LLC

2 SM MEDALLION INSPECTIONS helping people make informed decisions January12, 2015 Betsy and Paul Dougherty 101 Maple Street Atlanta, Georgia Subject: Pre-Drywall Inspection Summary 5657 Garden Valley Place Milton, Georgia Dear Betsy and Paul: At your request, we performed a visual inspection of the construction of your new home on January12, We have summarized the highlights of our findings into the categories listed below. However, please refer to the full report for normal maintenance items, and more detail and photographs of the items of concern. Building Code Issues Conditions listed in this section do not meet the Georgia Building Code in effect when the house permit was issued. Floor and Wall Framing: 1. There are several locations throughout the garage and basement where the outside wall sole plate is not properly secured to the foundation using foundation straps or bolts as required by 2007 Georgia Building Code 2006 IRC section R Each section of sole plate on the perimeter walls must be secured using bolts embedded in the foundation, or straps that are embedded in concrete. They must be secured with 12 inches of the end of each section of wood used. There are numerous locations where the plates are not secured within 12 inches of the ends as required. The locations include the left side of the garage, the right basement side wall, and both sides of the back wall at the intersection of the wall where it turns from running parallel with the back of the house and makes a 90 degree turn towards the back. Also, on both sides of the basement double door, and on the left side of the basement near the beam in the middle of the house. Recommend an experienced framing carpenter inspect and install the missing foundation anchorage as required. 2. The load path does not transmit to the slab in the basement under one set of supports in the stairwell to the basement. Load paths must be maintained all the way to the foundation or slab. In this location it appears that the framers missed the path. Recommend adding the required necessary jack studs. Reference 2007 Georgia Building Code 2006 IRC section R Medallion Services Group LLC

3 Smoke Detectors: 3. The smoke detector in the master bedroom is located in the direct path of an HVAC supply vent located at the back wall corner, and the return vent located near the front wall of the bedroom. This will result in the smoke detector being either less effective or ineffective when needed Georgia Building Code NFPA 72 Article (6) specifically states that smoke detectors cannot be located in this direct path. Recommend moving the smoke detector so that it is in an approved location, and not within the direct path of an HVAC supply and return. They also must be within 12 inches of the highest point in the room, and cannot be closer than 36 inches horizontally from the opening to a bathroom with a tub or shower, and no closer than 36 inches horizontally from the travel of the tips of any ceiling fans. Roof Covering: 4. The sidewall flashing is missing between the left rear corner of the garage roof and house siding. Recommend the roofer install the flashing Georgia Building Code 2006 IRC R Exterior Wall Surface: 5. The wall sheathing is exposed where the house vapor barrier is exposed on the right rear corner of the master bedroom sitting room wall. Recommend the contractor properly repair the vapor barrier before siding is installed Georgia Building Code 2006 IRC R The gable return roof framing is exposed between the brick and trim on the left front garage roof gable return. Recommend having the framing properly protected Georgia Building Code 2006 IRC R The weep holes are missing on the front entrance brick above the flashing for the arch. Recommend the mason install the needed weep holes Georgia Building Code 2006 IRC R Immediate Repairs Recommended Conditions listed in this section are items are not installed correctly but are not code items. Roof Framing: 1. There are large gaps between the fascia and roof decking across the base of the front roof between the master closet gable and the upstairs front center bedroom roof. Animals will be able to enter the attic in this area. Recommend installing flashing or trim to seal the opening. 2. The roof decking is exposed at the base of the valley between the sitting room roof and rear roof. Recommend having flashing or trim installed to protect decking. Ductwork and Vents: 3. The vent serving the master bath shower fan is disconnected. Recommend reattach and secure the vent line to the fan. 4. The laundry vent and vent connector are offset in the laundry room wall. Recommend moving the laundry vent connector. Coolant Lines: 5. The insulation is torn on several sections of the coolant suction return lines in the attic. This is generally when pulling the line set up through the wall during installation. If the insulation is not repaired, condensation will form on the exposed copper coolant line during A/C operation, Medallion Services Group LLC

4 and will drip onto the ceiling below. Recommend HVAC technician inspect and repair the insulation on the coolant return line in the attic. Roof Covering: 6. The front left main hip roof has an exposed nail at the ridge. The front gable return roofs have not been sealed between the shingles and fascia and soffits. Recommend the roofer seal the exposed nail and gable return connections with roofing cement. Foundation: 7. The left living room foundation wall has an opening at the base that is exposing soil from missing vapor barrier and slab. Recommend having the vapor barrier and concrete installed at slab and wall.. 8. The left foundation drain discharge piping is damaged. Recommend repair or replacement of piping. Thank you for choosing us for your pre-drywall inspection. If you have any questions after reviewing the report, please call us. Very truly yours, MEDALLION INSPECTIONS Joe Bettez ICC Residential Building Inspector Certified ASHI Inspector Jim Radcliffe ICC Residential Combination Inspector Certified ASHI Inspector MI:jgr Dougherty file Medallion Services Group LLC

5 Page 5 Property Address: 5657 Garden Valley Place, Milton, Georgia Report Index INFORMATION FRAMING ELECTRICAL SYSTEMS PLUMBING SYSTEM HEATING, VENTILATION & AIR CONDITIONING FIREPLACES ROOF COVERING & ATTIC VENTILATION EXTERIOR WALL, WINDOWS AND DOORS FOUNDATION AND SLAB Orientation The orientation of LEFT or RIGHT in this report is from the street facing the house. Report Text Color Legend Black text is used to identify normal conditions. Burgundy text is used to report conditions that do not meet Georgia Building Codes. Red text is used to report conditions that we recommend be corrected immediately. Blue text is used to report conditions that we consider to be normal maintenance. Green text is used to report items we recommend be upgraded or monitored for changes the future.

6 Page 6 INFORMATION Client Client First Name: Betsy and Paul. Client Last Name: Dougherty. Current Street Address: 101 Maple Street. Current City/State/Zip: Atlanta, Georgia Property to be Inspected Property Street Address: 5657 Garden Valley Place. Lot Number: 101. Property City/State/Zip: Milton, Georgia Property Subdivision Name: Peachtree Pearl Ridge. Purchase Price: $300,000. Builder: Bob Weiland Homes. Phase One Inspection Details Inspection Date: January12, Time: 9:00 AM. Type of Inspection Pre-Drywall. People Present During Inspection: No one. Climatic Conditions Weather: Overcast. Temperature: 60's. Last Measurable Rain: Overnight. Soil Conditions: Damp. Building Characteristics Building Type: Single family home.

7 Page 7 Stories: 2 Number of Bedrooms Five. Number of Full Baths Four. Space Below Grade: Basement. FRAMING Floor and Wall Framing: Floor/Ceiling Structure Condition: OK. Well done. Anchoring Walls to the Foundation: There are several locations throughout the garage and basement where the outside wall sole plate is not properly secured to the foundation using foundation straps or bolts as required by 2007 Georgia Building Code 2006 IRC section R Each section of sole plate on the perimeter walls must be secured using bolts embedded in the foundation, or straps that are embedded in concrete. They must be secured with 12 inches of the end of each section of wood used. There are numerous locations where the plates are not secured within 12 inches of the ends as required. The locations include the left side of the garage, the right basement side wall, and both sides of the back wall at the intersection of the wall where it turns from running parallel with the back of the house and makes a 90 degree turn towards the back. Also, on both sides of the basement double door, and on the left side of the basement near the beam in the middle of the house. Recommend an experienced framing carpenter inspect and install the missing foundation anchorage as required.

8 Page 8

9 Page 9 Jack Framing Support The load path does not transmit to the slab in the basement under one set of supports in the stairwell to the basement. Load paths must be maintained all the way to the foundation or slab. In this location it appears that the framers missed the path. Recommend adding the required necessary jack studs. Reference 2007 Georgia Building Code 2006 IRC section R Wall Framing OK. Loose Framing: None. Sheathing Condition OK. Firestops OK. Roof Framing: Roof Bracing Ok. Roof Framing: Ok.

10 Page 10 Roof Decking: There are large gaps between the fascia and roof decking across the base of the front roof between the master closet gable and the upstairs front center bedroom roof. Animals will be able to enter the attic in this area. Recommend installing flashing or trim to seal the opening. Roof Decking Sheathing: The roof decking is exposed at the base of the valley between the sitting room roof and rear roof. Recommend having flashing or trim installed to protect decking. Deck, Porch, or Balcony: Framing of Deck/Porch: Ok. Flashing Deck to Exterior Wall: Ok. ELECTRICAL SYSTEMS

11 Page 11 Primary Power Source: Service Voltage: The incoming electrical service to this structure is 120/240 volts. Service/Entrance/Meter: Underground service to the structure is desirable for safety and appearance. Contact the power company to mark the location of the underground cable before digging. Main Service Panel: Main Power Distribution Panel Location: Basement. Main Power Panel Size: expect 200 amps. Service Cable to Panel Type: Aluminum. Grounding Protection: Main Service Ground Verified: Rebar encased in concrete on the left side of the foundation. The grounding conductor is present but has not been attached to the main ground yet. Smoke Detectors: Placement: The smoke detector in the master bedroom is located in the direct path of an HVAC supply vent located at the back wall corner, and the return vent located near the front wall of the bedroom. This will result in the smoke detector being either less effective or ineffective when needed Georgia Building Code NFPA 72 Article (6) specifically states that smoke detectors cannot be located in this direct path. Recommend moving the smoke detector so that it is in an approved location, and not within the direct path of an HVAC supply and return. They also must be within 12 inches of the highest point in the room, and cannot be closer than 36 inches horizontally from the opening to a bathroom with a tub or shower, and no closer than 36 inches horizontally from the travel of the tips of any ceiling fans.

12 Page 12 PLUMBING SYSTEM Plumbing: Main Water Line Cutoff Location: Basement level wall. Interior Supply Piping Material: CPVC. Waste Line Materials: The predominant waste line material is plastic. Waste Piping Condition: The visible plumbing waste piping appears functional. Water Heater: Water Heater Location: Basement. Fuel Source for Water Heater: The water heater will be gas fired. HEATING, VENTILATION & AIR CONDITIONING Ductwork and Vents: Type of Ducts flexible ducts. Condition of Ducts OK.

13 Page 13 Bathroom Vents The vent serving the master bath shower fan is disconnected. Recommend reattach and secure the vent line to the fan. HVAC Vent Stack not present - house has heat pumps installed. Strap Protection OK.

14 Page 14 Laundry Vent The laundry vent and vent connector are offset in the laundry room wall. Recommend moving the laundry vent connector. Coolant Lines: Line Condition: The insulation is torn on several sections of the coolant suction return lines in the attic. This is generally when pulling the line set up through the wall during installation. If the insulation is not repaired, condensation will form on the exposed copper coolant line during A/C operation, and will drip onto the ceiling below. Recommend HVAC technician inspect and repair the insulation on the coolant return line in the attic. FIREPLACES FIREPLACE #1 Location: Family room. Type: Prefabricated metal gas only direct vent. Flue: Metal. Condition: The fireplace appears to be installed correctly. FIREPLACE #2 Location: Outside deck. Type: Prefabricated metal ventless gas only. Condition: The fireplace appears to be installed correctly.

15 Page 15 ROOF COVERING & ATTIC VENTILATION Roof Covering: Roof Condition: The front left main hip roof has an exposed nail at the ridge. The front gable return roofs have not been sealed between the shingles and fascia and soffits. Recommend the roofer seal the exposed nail and gable return connections with roofing cement. Flashing: The sidewall flashing is missing between the left rear corner of the garage roof and house siding. Recommend the roofer install the flashing Georgia Building Code 2006 IRC R Roof Gutter System: Not installed yet. Attic Ventilation: Ventilation: Ok. EXTERIOR WALL, WINDOWS AND DOORS Exterior Wall Surface:

16 Page 16 Siding Condition: The wall sheathing is exposed where the house vapor barrier is exposed on the right rear corner of the master bedroom sitting room wall. Recommend the contractor properly repair the vapor barrier before siding is installed Georgia Building Code 2006 IRC R Corner Boards: Ok.

17 Page 17 Trim: The gable return roof framing is exposed between the brick and trim on the left front garage roof gable return. Recommend having the framing properly protected Georgia Building Code 2006 IRC R Brick Veneer Conditions: The weep holes are missing on the front entrance brick above the flashing for the arch. Recommend the mason install the needed weep holes Georgia Building Code 2006 IRC R

18 Page 18 Windows: Windows Installation: OK. Exterior Doors: OK. Door Installation: FOUNDATION AND SLAB Foundation: Type of Foundation: Poured in place concrete, 8" or more thick. Visible Foundation Wall Cracks The left living room foundation wall has an opening at the base that is exposing soil from missing vapor barrier and slab. Recommend having the vapor barrier and concrete installed at slab and wall.. Perimeter Foundation Drainage Surface: The drainage around the perimeter of the foundation appears to have adequate ground slope to remove run-off water from the immediate area.

19 Page 19 Footer Drain Tile The left foundation drain discharge piping is damaged. Recommend repair or replacement of piping. Soil Conditions Wet. Slab Condition Ok. Parge Coat Ok. Slab:

Home Inspection Report

Home Inspection Report 4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:

More information

HomeSpec REPORT SUMMARY

HomeSpec REPORT SUMMARY HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above

More information

Inspecton Report. Property Address:

Inspecton Report. Property Address: Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 bob@nationalhomeinspections.com www.nationalhomeservices.com Property Address: 873

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

PDmB, Inc. Definitions

PDmB, Inc. Definitions Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or

More information

CHRIS CURLES and ASSOCIATES INSPECTION SERVICES

CHRIS CURLES and ASSOCIATES INSPECTION SERVICES CHRIS CURLES and ASSOCIATES INSPECTION SERVICES Inc. Chris Curles, President www.homeinspectionsatlanta.com chriscurl@comcast.net Office: 770-493-0227 Professional Member Of: GAHI # 93006 ASHI # 211725

More information

Home Inspection Report

Home Inspection Report Report# 21009 Page 1 of 24 Home Inspection Report Property Address: 123 Maple Lane, St. Augustine, FL 32092 Prepared For: Mr. Smith Prepared By: EDGE Inspections www.edgeinspections.com PO Box 601055 Jacksonville,

More information

Total Home Inspection Checklist

Total Home Inspection Checklist Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are

More information

Inspection Tech. (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg

Inspection Tech. (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg Inspection Tech (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg Inspection Tech Home Inspection Report Prepared For: Mr. & Mrs. Homebuyer Property

More information

Structure Survey Findings:

Structure Survey Findings: Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

Building Condition Assessment Report

Building Condition Assessment Report Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.

More information

PROPERTY INSPECTION REPORT

PROPERTY INSPECTION REPORT (850) 297-1998 1716 Monticello Dr Tallahassee, Florida 32303 PROPERTY INSPECTION REPORT THIS INSPECTION IS A DETAILED LISTING OF AREAS VISUALLY INSPECTED AT:, Tallahassee FL Client Tallahassee, FL 32304

More information

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,

More information

Inspection Report Atlanta Strip Mall Commercial Building Property Address:

Inspection Report Atlanta Strip Mall Commercial Building Property Address: Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector

More information

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

Georgia Association of Home Inspectors

Georgia Association of Home Inspectors Georgia Association of Home Inspectors Standards of Practice for Framing Inspections OVERVIEW The purpose of the GAHI (Georgia Association of Home Inspectors) Standards of Practice for Framing Inspections

More information

Common Problems with Walls

Common Problems with Walls Common Problems with Walls Common Problems with Walls There are problems and concerns that are shared by all walls and siding installations. In this article, we will learn about the following commonly

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared

More information

I NI NP R Inspected Items

I NI NP R Inspected Items 6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111

A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111 A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111 Inspector Name: Tim Knight, ASHI Member 202490 Inspection No: 12121212 Inspection Date: 1/1/2012 Client: Address: John

More information

Self-Home Inspection Checklist

Self-Home Inspection Checklist To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional

More information

BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207

BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas 5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction

More information

Home Inspection Report

Home Inspection Report Home Inspection Report 1234 School House Road Yourtown, US 12345 Prepared for: Bob Smith Prepared by: Your Company Name Here 9600 Colerain Ave Suite 110 Cincinnati, OH 45215 17:26 August 02, 2006 Page

More information

Inspection Report. Prepared For: Sampath Sample. Property Address: 12712 Waterside Drive. Alpharetta, GA 30004. Atlanta Home Inspections

Inspection Report. Prepared For: Sampath Sample. Property Address: 12712 Waterside Drive. Alpharetta, GA 30004. Atlanta Home Inspections Page 1 of 37 Inspection Report Prepared For: Sampath Sample Property Address: Alpharetta, GA 30004 Atlanta Home Inspections Matthew A Thoroman 6625 Hwy. 53 E. Ste. 410-151 Dawsonville Ga 30534 (678)-410-8062

More information

Uniform Construction Code (UCC) Building Permit Application Package

Uniform Construction Code (UCC) Building Permit Application Package Uniform Construction Code (UCC) Residential Building Permit Application Package Per the Uniform Construction Code (UCC) all structures must be built per the standards of the most currently adopted International

More information

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000 Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,

More information

Home Inspection Report

Home Inspection Report Home Inspection Report 1234 School House Road Yourtown, US 12345 Prepared for: Bob Smith Prepared by: Your Company Name Here 9600 Colerain Ave Suite 110 Cincinnati, OH 45215 17:22 August 02, 2006 Page

More information

October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr.

October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr. 117 S. Market St. Benton, AR 72015 * 501-315-2626 * Fax 501-315-0024 October 30, 2014 Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR Re: Report of Findings,, Benton, Arkansas, Dear Mr. Vick: This

More information

Inspection Report. provided by: Delaware Property Inspection. Inspector: Richard Hiddemen (302)355-1748

Inspection Report. provided by: Delaware Property Inspection. Inspector: Richard Hiddemen (302)355-1748 Inspection Report provided by: Delaware Property Inspection Inspector: Richard Hiddemen (302)355-1748 ASHI # 243377 DPR #H4-0000018 DDA #06-444 Delaware 1992105842 Wilmington #03857 New Castle #2010-845

More information

Inspection Report. Prepared For: Atlanta Commercial Customer. Property Address: xxx Sandy Plains Road. Building 5 Marietta, GA 30066

Inspection Report. Prepared For: Atlanta Commercial Customer. Property Address: xxx Sandy Plains Road. Building 5 Marietta, GA 30066 Page 1 of 58 Inspection Report Prepared For: Atlanta Commercial Customer Property Address: Building 5 Marietta, GA 30066 Superior Home Inspections Ray Thoroman 8070 Ivy Shaw Dr. Gainesville,GA 30506 678-410-3005

More information

South Carolina Home Inspector Standards of Practice

South Carolina Home Inspector Standards of Practice South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,

More information

PROFESSIONAL ENGINEERING INSPECTIONS, INC.

PROFESSIONAL ENGINEERING INSPECTIONS, INC. PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

Quality Home Inspections, LLC 4433 Tennyson Street Denver, Colorado 80212 303-885-1288

Quality Home Inspections, LLC 4433 Tennyson Street Denver, Colorado 80212 303-885-1288 Page 1 of 22 Quality Home Inspections, LLC 4433 Tennyson Street Denver, Colorado 80212 303-885-1288 Printed Friday, January 16, 2015 Inspected By: Dale Gibbs Referral Information Joe Agent Client Information:

More information

COMPREHENSIVE PROPERTY INSPECTIONS

COMPREHENSIVE PROPERTY INSPECTIONS COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited

More information

Rehab Inspection Report Page 1

Rehab Inspection Report Page 1 Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation

More information

WOODLAND HOMES BUILDING PROCESS A STEP BY STEP CONSTRUCTION GUIDE TO YOUR NEW HOME

WOODLAND HOMES BUILDING PROCESS A STEP BY STEP CONSTRUCTION GUIDE TO YOUR NEW HOME WOODLAND HOMES BUILDING PROCESS A STEP BY STEP CONSTRUCTION GUIDE TO YOUR NEW HOME 1 THE BUILDING PROCESS The focus of Woodland Homes building department is Quality, Service and Predictability. Through

More information

BUILDING SAFETY UNIT

BUILDING SAFETY UNIT POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential

More information

Accurate Home Inspection of Illinois. Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave., Westmont, Illinois

Accurate Home Inspection of Illinois. Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave., Westmont, Illinois Accurate Home Inspection of Illinois 815-260-1727 1213 Norley st. Joliet, illinois 60435 aaccurate1@yahoo.com We Inspect to Protect!!! Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave.,

More information

Inspection Item COMMENTS

Inspection Item COMMENTS APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:

More information

Georgia Home Inspection Services

Georgia Home Inspection Services Cover Page Property Inspection Report My street, Anytown GA, 30000 Inspection prepared for: John Doe Inspection Date: 7/18/2011 Time: 5pm Age: 25+ Size: >1500 Weather: Clear This ranch style home is in

More information

Propery Inspection Report

Propery Inspection Report Propery Inspection Report Cover Page,, Ok Inspection prepared for: Date of Inspection: 9/28/2014 Time: 8:30 AM Age of Home: 2011 MOL Weather: Clear 62 degrees Inspector: License #130 5400 Hwy 177, Marland,

More information

Estimating Database Checklist

Estimating Database Checklist Estimating Database Checklist If you are creating a new estimating database for projects, the following list offers a thorough listing of Main and Sub Categories. You can also use it as a checklist to

More information

Holz Choices & Specifications

Holz Choices & Specifications March 21, 2011 0. SALES AND DESIGN 1. UTILITIES AND PERMITS Holz Choices & Specifications 2. EXCAVATION AND LOT PREPARATION Job Beginning date of Monday May 2 nd, 2011 ALTERNATE: Garage walls as drawn

More information

PROPERTY INSPECTION REPORT

PROPERTY INSPECTION REPORT Page 1 of 18 PROPERTY INSPECTION REPORT Dynamic Property Inspection 1701 Cimarron Tr. Grapevine, Tx 76051 817-442-9100 Inspected By: Stephen Ferguson 7807 Inspection Date: 6/23/2005 Client Joe Homeowner

More information

License Requirements for Persons Engaging in the Business of Inspection Practice:

License Requirements for Persons Engaging in the Business of Inspection Practice: SC Standards of Practice SOUTH CAROLINA RESIDENTIAL BUILDERS COMMISSION HOME INSPECTOR STANDARDS OF PRACTICE Adopted by the Residential Builders Commission May 13, 1998 PURPOSE: The purpose of a residential

More information

The Uniform Building Inspection Report Condensed

The Uniform Building Inspection Report Condensed The Uniform Building Inspection Report Condensed Single Family Residence:, Scottsdale, AZ Condensed Report Version Prepared for: John Doe Inspection Date: 9/19/2005, 1:00:00 AM Report Number: 091805s Inspection

More information

STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE:

STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE: STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE: 61-30.801 Standards of Practice, General. (1) Home inspections performed to these Standards of Practice are intended to provide the client with information

More information

PROPERTY INSPECTION REPORT Property Address:

PROPERTY INSPECTION REPORT Property Address: Scott Certified Member P. O. Box 9007 Indianapolis, IN 690-007 (7)-750-60 Fax: 7-876-8 PROPERTY INSPECTION REPORT Property Address: Prepared for: Inspection Inspector: Lou Buehler Inspection #: BUYERS

More information

HOME INSPECTION CHECKLIST

HOME INSPECTION CHECKLIST CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Water Management & Damage Prevention:

Water Management & Damage Prevention: Water Management & Damage Prevention: A Guide for Homeowners This article provides homeowners with basic information to make these decisions and take the appropriate actions to keep their homes dry and

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Cincinnati, Ohio 45000 Prepared for: Dean Murphy Prepared by: BEDROCK ENTERPRISES, INC. 4060 Simca Lane Cincinnati, OH 45211 20:13 July 07, 2008 Page 1 of 18 Definitions NOTE: All

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

ST. MONICA FOOD PANTRY HOUSTON, TEXAS

ST. MONICA FOOD PANTRY HOUSTON, TEXAS PROJECT MANUAL FOR ST. MONICA FOOD PANTRY HOUSTON, TEXAS OWNER: ST. MONICA CATHOLIC CHURCH 8421 W. MONTGOMERY ROAD HOUSTON, TEXAS 77088 ARCHITECT: C SIX ARCHITECTURE, LLC 4606 F.M. 1960 WEST, STE 400 HOUSTON,

More information

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by

More information

October 28, 2010. Re: Raleigh, NC 27617. Dear Mr. and Mrs.:

October 28, 2010. Re: Raleigh, NC 27617. Dear Mr. and Mrs.: October 28, 2010 Re: Raleigh, NC 27617 Dear Mr. and Mrs.: At your request, and in your presence, a visual inspection of the above referenced property was conducted on October 27, 2010. This inspection

More information

HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com

HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com 2007 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,

More information

The minimum reinforcement for the stem wall is the placement of:

The minimum reinforcement for the stem wall is the placement of: PolySteel creates an ideal insulated stem wall for concrete slabs that can make this part of your project easier and faster, in addition to making your finished project more energy-efficient. Figures 3.20

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

Home Management Checklist: Spring

Home Management Checklist: Spring Home Management Checklist: Spring HVAC System Attic Plumbing and Electrical Service air conditioning unit (Ventilation inspected as part of service call). Ensure gutters are discharging water away from

More information

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination

More information

Estimated Cost of Repair

Estimated Cost of Repair 1 Applicant: Property: Home: Business: Assessor: Applicant Number: Type of Loss: Hurricane Date Contacted: 1/18/2014 Date of Loss: 10/29/2012 Date Received: 1/14/2014 Date Inspected: 2/4/2014 Date Entered:

More information

Printed Monday, August 27, 2007 Inspected By: Michelle Teague. Client Information: Inspection, Condo City Lane Chicago, IL. Inspected 8/22/07 8:00 AM

Printed Monday, August 27, 2007 Inspected By: Michelle Teague. Client Information: Inspection, Condo City Lane Chicago, IL. Inspected 8/22/07 8:00 AM Pa g e 1 o f 1 5 All About Homes, LLC Michelle M. Teague Owner 312-371-7414 Phone 773-508-6209 Fax www.michelleinspects.com michelle@michelleinspects.com 1725 W. Granville Ave. Chicago, IL 60660 Printed

More information

City of St. Charles Basement Finish or Remodel

City of St. Charles Basement Finish or Remodel City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct

More information

Prestige Home Inspection LLC

Prestige Home Inspection LLC Cover Page Prestige Home Inspection LLC IAC2/ESA - Mold Assessment and Water Damage Report 555 W. Brook ave., Client's town MI, 48059 Inspection prepared for: Client's name Inspection Date: 10/15/2012

More information

Attachment #23 Health Safety Table. Client Education Inform issue and document. How to clean & maintain gutters. How to adjust sprinklers

Attachment #23 Health Safety Table. Client Education Inform issue and document. How to clean & maintain gutters. How to adjust sprinklers Exterior Visual Health & Safety Issue Allowable Action Site Drainage Exterior grade does not slope 2% within the first 10' Site drainage causing bulk moisture in crawl space or basement Repairs to existing

More information

Vari Inspection Services

Vari Inspection Services Cover Page Vari Inspection Services Property Inspection Report Inspection prepared for: Sample Real Estate Agent: None - Date of Inspection: 5/13/2015 Inspector: Tony Vari License # HI8047 23110 STRD 54

More information

SWF Home Inspections

SWF Home Inspections Cover Page SWF Home Inspections Property Inspection Report Inspection prepared for: Mr & Mrs Home Buyer Real Estate Agent: My Favorite Agent - Date of Inspection: 7/4/2013 Age of Home: 2004 Size: 1568

More information

HOME INSPECTION REPORT

HOME INSPECTION REPORT Edgewood Home Inspections, Inc. 407 W. Smith Valley Rd. #1032 Greenwood, IN 46142 (317) 833-6048 HOME INSPECTION REPORT Indianapolis IN 46000 Inspector's Name: License Number: Scott Kissel HI00800073 TABLE

More information

Home Warranty Inspection Report

Home Warranty Inspection Report Scope of the Inspection 1111 Sample Dr. home warranty inspection 2/30/2006 Home Warranty Inspection Report 1111 Sample Dr., Detroit, MI 48223 Inspection Date: February 30, 2006 Client: Alfred E. Neumann

More information

If there are any further questions with regards to the report or inspection, please call.

If there are any further questions with regards to the report or inspection, please call. National Home Inspection Ltd. 1055 Woodbine Avenue Toronto, Ontario M4C 4C2 TEL: (416) 467-7809 FAX: (416) 429-5443 April 15, 2014 SUMMARY INSPECTION REPORT PROPERTY: 75 Fairlawn Avenue, Toronto, Ontario

More information

Additions and Alterations

Additions and Alterations Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal

More information

South Carolina Home Inspector Standards of Practice

South Carolina Home Inspector Standards of Practice South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,

More information

Chapter 2: Foundations

Chapter 2: Foundations Chapter 2: Foundations Crawlspace [V502.1.2] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup under the floor.

More information

159 Morningside Avenue, Toronto

159 Morningside Avenue, Toronto 159 Morningside Avenue, Toronto Inspection Report February 6, 2013 159 Morningside Avenue, Toronto Inspection Report Overall Condition: This 60±-year-old home was extensively renovated and extended in

More information

How To Make A House Safe

How To Make A House Safe 1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design

More information

ELIGIBLE REPAIR PROJECT PARAMETERS

ELIGIBLE REPAIR PROJECT PARAMETERS THE DISTRICT MUNICIPALITY OF MUSKOKA ONTARIO RENOVATES PROGRAM FOR HOMEOWNERS ELIGIBLE REPAIR PROJECT PARAMETERS 1. To have your project considered and payment processed, all projects requiring a Building

More information

Foundation. Foundation

Foundation. Foundation Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their

More information

Inspection Report. Sample Client. Property Address: XXXX N. Atolia Drive Tucson AZ 85743. House and Home

Inspection Report. Sample Client. Property Address: XXXX N. Atolia Drive Tucson AZ 85743. House and Home Inspection Report Sample Property Address: XXXX N. Atolia Drive Tucson AZ 85743 House and Home Brian Pemble #45238 6909 E. Kingston Drive Tucson, AZ. 85710. 520-245-7897 Table of Contents Cover Page...1

More information

Mold Inspection Report (Initial Assessment)

Mold Inspection Report (Initial Assessment) Morlin Home Services, LLC 4435 Nanticoke Court Sw Lilburn, GA. 30047 Phone: (770) 564-1505 Fax: (770) 564-1575 Cell: (770) 344-7416 InspectorRick@Bellsouth.net www.morlinpropertyinspections.com Mold Inspection

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

Development Services City of Lawrence, KS

Development Services City of Lawrence, KS Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.

More information

Residential Inspection Guidelines

Residential Inspection Guidelines Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against

More information

Foundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for:

Foundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for: A Full Service Real Estate Inspection & Engineering Firm for Houston, Texas 77089 August 30, 2012 Prepared for: CLIENT S NAME MAILING ADDRESS Houston, Texas 77089 Prepared by: Charles J. Jenkins, P.E.

More information

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill ENERGY STAR Qualified New Homes Thermal Enclosure Checklist & Water Management Checklist Eli Caudill ENERGY STAR Version 3 Tighter Standards Whole Home Approach Better, More Sustainable Construction Surpasses

More information

INSPECTION REPORT. Client Name Address From the inspection on: August XX, 2011 805-256-5519 CHRIS LOWE

INSPECTION REPORT. Client Name Address From the inspection on: August XX, 2011 805-256-5519 CHRIS LOWE 08XX11aa 805-256-5519 CHRIS LOWE President, Inspector INSPECTION REPORT Client Name Address From the inspection on: August XX, 2011 This report is solely for the use of client personnel. No part of it

More information

Name of course: Residential Construction Site Management (RCSM) Level 1

Name of course: Residential Construction Site Management (RCSM) Level 1 Name of course: Residential Construction Site Management (RCSM) Level 1 Core (required courses) or Optional (elective course): Required Delivery Method: This is an online course only with no classroom

More information

Applications for building permits will not be reviewed until all of the required information has been submitted.

Applications for building permits will not be reviewed until all of the required information has been submitted. NOTICE: Applications for building permits will not be reviewed until all of the required information has been submitted. Once all items are submitted a minimum of ten (10) working days are required to

More information

A and S Property Inspector

A and S Property Inspector Cover Page A and S Property Inspector Property Inspection Report Inspection prepared for: xxxxx xxxxx Real Estate Agent:.. - Date of Inspection: 8/25/2014 Time: 10am Age of Home: 1999 Size: 1841 Weather:

More information

GENERAL ELECTRICAL REQUIREMENTS

GENERAL ELECTRICAL REQUIREMENTS GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of

More information

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the

More information