Roof Inspection and Evaluation

Size: px
Start display at page:

Download "Roof Inspection and Evaluation"

Transcription

1 Roof Inspection and Evaluation Sylvester Powell Community Center 6200 Martway Mission, KS Prepared For: Your name Sample Community Center 6200 Martway Mission, KS Kansas City, MO NW Platte Valley Dr. Riverside, MO Office: Fax:

2 Data and Budget Review List of Roof Sections Section Sq. Ft. System Deck Core Condition Index Grade Remaining Life Years Annual Repair Cost Estimate Recommendation Roof A 9,722 BUR Roof B 4,920 Roof C 11,402 Roof D 450 Granular Surface Mod. Bit. Granular Surface Mod. Bit. Granular Surface Mod. Bit. Metal Deck Metal Metal Metal Roof E 793 BUR Metal Roof F 1,2 1 4 BUR Metal Roof G 1,0 3 5 BUR Metal Roof H 7,8 0 8 BUR Metal Roof I 1,0 3 8 BUR Metal Roof J 357 BUR Metal Embeded Pea Gravel, Multiply Ashalt, 2 layers 2" ISO Poor D 2 years $1,800 Repair Granular Cap Sheet, Multiply Asphalt, 2 Layers 2 " ISO Fair C 5 years $900 Repair Granular Cap Sheet, Multiply Asphalt, 2 Layers 2 " ISO Fair C 5 years $1,050 Repair Granular Cap Sheet, Multiply Asphalt, 2 Layers 2 " ISO Fair D 5 years $750 Repair Embeded Pea Gravel, Multiply Ashalt, 2 layers 2" ISO Poor D 2 years $500 Repair Embeded Pea Gravel, Multiply Ashalt, 2 layers 2" ISO Poor D 2 years $600 Repair Embeded Pea Gravel, Multiply Ashalt, 2 layers 2" ISO Poor D 2 years $600 Repair Embeded Pea Gravel, Multiply Ashalt, 2 layers 2" ISO Poor D 2 to 3 $ 1,6 0 0 Repair Embeded Pea Gravel, Multiply Ashalt, 2 layers 2" ISO Poor D 2 to 3 $600 Repair Embeded Pea Gravel, Multiply Ashalt, 2 layers 2" ISO Poor D 2 to 3 $500 Re[pair Tile 2 5 9,9 0 3 Tile NA No Core Taken Good B 15+ $ 2,0 0 0 Re[pair Grading Scale A - New roof or needing no work at this time B - A newer roof that is less than 5 years old and has no leaks C - A middle age roof that has had some maintenance prior to either warranty issues or 3rd party D - A roof on the latter stages of its longevity and should be budgeted for replacement F - Roof has failed, is leaking and needs to be replaced as soon as possible 2

3 3

4 Roof Defects Roof A Open Laps-There is several open laps on the skylights and on the wall Flashings Low pitch pan filler All the pitch pans need to be topped off Budget Recommendations We recommend that the roof be repaired with three course repairs. Estimated Immediate Repair Cost: $1550 4

5 Sample Roof A Overall 5

6 Sample Roof A Defects Low Pitch Pan Filler Open Lap 6

7 Roof Defects Roof B Loss Of Granulation-Widespread-monitor Open Laps There is less than seven open laps Cut in Membrane There is one cut in the granulated cap sheet. Budget Recommendations We recommend that this roof be repaired with three course repairs. Estimated Immediate Repair Cost: $825 7

8 Sample Roof B Overall 8

9 Sample Roof B Defects Open Lap Cut in Membrane 9

10 Roof Defects Roof C Open Laps-There is several open laps in the wall flashings and in the skylights. Budget Recommendations We recommend that the roof be repaired with three course repairs Estimated Immediate Repair Cost: $750 10

11 Sample Roof C Overall 11

12 Sample Roof C Defects Open Lap Open Lap 12

13 Roof Defects Roof D Open Laps-four locations Budget Recommendations We recommend that the roof be repaired with three course repairs. Estimated Immediate Repair Cost: $300 13

14 Sample Roof D Overall 14

15 Roof Defects Roof E Open Laps-three is several open laps Budget Recommendations We recommend that the roof be repaired with three course repairs. Estimated Immediate Repair Cost: $400 15

16 Overall Roof E 16

17 Defects Roof E Open Lap 17

18 Roof Defects Roof F Open Laps there is six open laps Debris-there is one area of plywood and debris on the roof Budget Recommendations We recommend that the roof be repaired with three course repairs. Estimated Immediate Repair Cost: $600 18

19 Sample Roof F Overall 19

20 Sample Roof F Defects Debris Open Lap 20

21 Roof Defects Roof G No Defects Budget Recommendations We recommend that this roof maintained. Estimated Immediate Repair Cost: $0 21

22 Sample Roof G Overall 22

23 Roof Defects Roof H Open Laps-there is several open laps in the wall flashings and skylights Leak There is one leak location. Budget Recommendations We recommend that the roof be repaired with three course repairs. Estimated Immediate Repair Cost: $

24 Roof Defects Roof I Open Laps-eight locations Budget Recommendations We recommend that the roof be repaired with three course repairs. Estimated Immediate Repair Cost: $400 24

25 Defects Roof I Open Laps 25

26 Roof Defects Roof J No Defects Budget Recommendations We recommend that the roof be maintained. Estimated Immediate Repair Cost: $0 26

27 Roof Defects Roof K No defects Budget Recommendations We recommend that the roof be maintained. Estimated Immediate Repair Cost: $ 27

28 Roof Defects Tile Roof Broken or loose tile There is eight broken tile and one that has slide down approximately six inches. Budget Recommendations We recommend that the roof be maintained. Estimated Immediate Repair Cost: $

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC

More information

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof! Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing

More information

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide Inspection Questions? Call Bloom At 800-483-9932 www.bloomroofing.com DISCLAIMER

More information

Maintenance & Inspection Guide

Maintenance & Inspection Guide ADDRESSING THE NEEDS OF OUR CUSTOMERS AND THE ENVIRONMENT ONE high Performance roofing SOLUTION AT A TIME. Maintenance & Inspection Guide TABLE OF CONTENTS Topic: Page: I. Introduction 1 II. Maintenance

More information

Roof Condition Analysis

Roof Condition Analysis Roof Condition Analysis Prepared for: J.W. Nelson John Evans Middle School - Gym Dome 2900 15th Avenue Greeley, Colorado Prepared by: Gregory Ham Coastal Specified Products 5252 Sherman Street Denver,

More information

Clear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015

Clear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015 Clear Fork Valley Local School District Roofing Repairs Spring/Summer 2015 Instructions to Bidders: Public Notice To Bidders (ORC 3313.46) Notice is hereby given that sealed bids will be received at the

More information

87% visibility in all search engines

87% visibility in all search engines shopinkelowna.com/madgecontractingroof RepairsKelowna/04.htm % visibility in all search engines Flashing Repairs Kelowna 2 Roof Humidity Kelowna 2 Flat Roofs Repairs Kelowna Roof Leak Repair Kelowna Skylight

More information

Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2

Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building

More information

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It

More information

Thank You! Owner Aaron Perry! Email info@exteriorproinc.com! 2936 Clifty Drive! Madison IN 47250! (855) 274-0444! (812) 274-0444!

Thank You! Owner Aaron Perry! Email info@exteriorproinc.com! 2936 Clifty Drive! Madison IN 47250! (855) 274-0444! (812) 274-0444! A properly installed and maintained flat roof can be one of a building s biggest assets while a leaking or failing roof can quickly become a building s biggest expense. We ve put this simple guide together

More information

REPLACE ROOFING DENVER CENTRAL LIBRARY PHASE I CITY & COUNTY OF DENVER DENVER, COLORADO

REPLACE ROOFING DENVER CENTRAL LIBRARY PHASE I CITY & COUNTY OF DENVER DENVER, COLORADO PUBLIC LIBRARY PHASE I 4828 W. 6TH Avenue, Unit B-8 Golden, Colorado 8040 Phone: (303) 233-092 VICINITY MAP SHEET INDEX GT /26/2009 SHEET DESCRIPTION G.0 COVER SHEET R.0 COMPOSITE ROOF PLAN R. NEW ROOF

More information

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING Roofing Manufacturers Association Why is a built-up roof considered a multi-ply roof? ARMA defines a built-up roofing system as a roof where multiple

More information

SchoolRoof Repair - Cost For Replacement of a Student Roof, Part 2

SchoolRoof Repair - Cost For Replacement of a Student Roof, Part 2 ROOF REPAIR UPDATE For the November school newsletter, I wrote an article in which I explained the condition of the school roof, the estimated cost of replacing the three flat sections from the 1996 building

More information

Firestone Warranty Program

Firestone Warranty Program EPDM Warranty Pricing ***For Red Shield Contractors Only*** Red Shield 20 Years $0.10 $500.00 No Dollar Limit 15 Years $0.07 $400.00 No Dollar Limit 10 Years $0.04 $350.00 No Dollar Limit When Firestone

More information

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER DESCRIPTION TORCH OVER (15,17,19 YR) TH/BS-TH/CS 2 1 0 No 0. SUBSTRATE 1. THERMOTEK USA 2.0 FV TORCH SMOOTH 2. THERMOTEK USA PRO FP TORCH GRANULE COMPONENTS

More information

Prices Effective April 1, 2016

Prices Effective April 1, 2016 Domestic U.S. Warranty Pricing Guide Longer term warranties have additional installation requirements and not all warranty terms are available for all roofing specifications. Please refer to the Firestone

More information

THERMOTEK SELF ADHESIVE MEMBRANE +G2 OVER WOOD SYSTEM DESCRIPTION SELF ADHESIVE OVER WOOD (8YR) BS-SA/CS

THERMOTEK SELF ADHESIVE MEMBRANE +G2 OVER WOOD SYSTEM DESCRIPTION SELF ADHESIVE OVER WOOD (8YR) BS-SA/CS THERMOTEK SELF ADHESIVE MEMBRANE +G OVER DESCRIPTION SELF ADHESIVE OVER (8YR) BS-SA/CS 1 0 No 0. SUBSTRATE 1. BASE SHEET G FIBER GLASS BASE. THERMOTEK SELF ADHESIVE 3.0 FP GRANULE COMPONENTS AND WEIGHTS

More information

FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS

FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS Table of Contents Chapter 1: FLAT ROOF REPAIR - CUT COST WITHOUT CUTTING CORNERS Chapter 2: PVC RECOVER SYSTEM HOW IT WORKS Chapter 3: 8 STRATEGIES TO

More information

Commercial Roof Inspection Form

Commercial Roof Inspection Form Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building

More information

Commercial Roof Management

Commercial Roof Management Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading

More information

Safeguarding our clients interests. Active Roof Leaks

Safeguarding our clients interests. Active Roof Leaks Safeguarding our clients interests. Active Roof Leaks Vendor Requirements Visually inspect the roof for any damages Exterior inspection of the roof and gutters Interior ceiling inspection Interior attic

More information

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36.

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36. Demolition/Removal of Work 4-ply built up roofing to the insulation (smooth cap sheet) Smooth cap sheet - 0-10 SQ $ 63.00 Smooth cap sheet - 11-50 SQ $ 63.00 Smooth cap sheet - 51-100 SQ $ 35.00 Smooth

More information

16 2 10.3 Materials and Colors

16 2 10.3 Materials and Colors 16 2 10.3 Materials and Colors To create a harmonious and coherent image for each development, building designs shall pay close attention to choice of materials and colors. Building construction shall

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

A0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET

A0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET POYNTZ AVENUE, STE 9 MANHATTAN, KS 0..0..9 FAX WEST th STREET JUNCTION CITY, KS.... FAX 0, Bruce McMillan AIA, Architects, P.A. HERITAGE TRUST FUND GRANT PROJECT NO. 0-0 ROOF REPAIR OF THE 00 LOCUST STREET

More information

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Department of Advanced Education and Skills Apprenticeship and Trades Certification Division Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Note to Apprenticeship Applicants

More information

Detached accessory structures that contain no conditioned floor area are exempt.

Detached accessory structures that contain no conditioned floor area are exempt. RESIDENTIAL ROOFING PERMITS: A roofing permit is required for roofing of residential dwellings and garages in accordance with Section R105 of the International Residential Code. Updated 11/2013 City of

More information

CHAPTER 6 ASPHALT ROLL ROOFING

CHAPTER 6 ASPHALT ROLL ROOFING CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed

More information

Getting The Most Out of Your Roof Asset. Program #099 PM

Getting The Most Out of Your Roof Asset. Program #099 PM Getting The Most Out of Your Roof Asset Program #099 PM Garland 12 Steps: Specifications, Inspections, Details, Field Support Budget vs. Desired Life Expectancy Reduction of Liability Resource Staying

More information

HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION

HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION ADVANCED TECHNOLOGY FROM OWENS CORNING TRUMBULL ASPHALT TruLo Lo Odor and TruLo Max asphalt raising the roof on asphalt performance.

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

The existing roof angle change terminations and flashings when sound and intact can be reused.

The existing roof angle change terminations and flashings when sound and intact can be reused. January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing

More information

Work Experience Form Roofer

Work Experience Form Roofer 2006 - National Occupational Analysis (NOA) Work Experience Form Roofer 1-877-978-7233 www.manitoba.ca/tradecareers Personal Information (please print) Legal First Name Middle Initial Legal Last Name Birth

More information

DISTRICT OF BARRIERE REQUEST FOR PROPOSAL

DISTRICT OF BARRIERE REQUEST FOR PROPOSAL DISTRICT OF BARRIERE REQUEST FOR PROPOSAL SUPPLY AND INSTALLATION OF FLAT ROOF SYSTEM AND RELATED REPAIRS RFP No. 2014-02 1. SUMMARY OF REQUIREMENT The District is planning on reroofing the existing flat

More information

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck. SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied

More information

FIRESTONE BUILT-UP ROOFING SYSTEMS APPLICATION GUIDE 3/14/2011

FIRESTONE BUILT-UP ROOFING SYSTEMS APPLICATION GUIDE 3/14/2011 FIRESTONE BUILT-UP ROOFING SYSTEMS APPLICATION GUIDE TABLE OF CONTENTS 2.01.1 GENERAL......2 2.02.1 JOB SITE CONSIDERATIONS (CAUTION AND WARNINGS)...2 2.03.1 ROOF SUBSTRATE PREPARATION...2 2.04.1 WOOD

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

ROOF INSPECTION REPORT

ROOF INSPECTION REPORT ROOF INSPECTION REPORT Date: October 9, 2012 Requesting Firm: FIRST CHOICE INSPECTIONS Santiago Salazar Address: 447 Chilberg Court, San Jose, CA 95133 Phone #: 408-771-7563 Roof Inspected At: 1465 Gerlach

More information

Crescent Valley High School Roof Investigation

Crescent Valley High School Roof Investigation Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

ROOFS - Guidance for Repair, Maintenance and Replacement

ROOFS - Guidance for Repair, Maintenance and Replacement ROOFS - Guidance for Repair, Maintenance and Replacement Guilford Association Architectural Committee ROOFING Slate and tile roofs are a critical design feature of Guilford homes. The homes were designed

More information

Obvious statement of the day: the storm was strong enough to damage the storm and hailstones can often be gathered

Obvious statement of the day: the storm was strong enough to damage the storm and hailstones can often be gathered Obvious statement of the day: the storm was strong enough to damage the storm and hailstones can often be gathered Hail can damage low-slope roof, in today s age of information, chances from these eyewitness

More information

Georgia State University. Urban Life Building Roof Replacement

Georgia State University. Urban Life Building Roof Replacement ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT

More information

BUSI 441 Project 1: Reserve Fund Study

BUSI 441 Project 1: Reserve Fund Study BUSI 441 Project 1: Reserve Fund Study Estimating Roofing Replacement Cost In Project 1, Part One, section (b) you are instructed to identify the roofing type and area for your subject building. The section

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing

More information

HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION

HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System

More information

TARRANT COUNTY DETAIL STANDARDS

TARRANT COUNTY DETAIL STANDARDS TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout

More information

BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES

BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES ABOUT POLYGLASS U.S.A., INC. MODIFIED CEMENTS & ADHESIVES MASTICS ALUMINUM COATINGS EMULSIONS & PRIMERS PROTECTIVE COATINGS Polyglass manufactures

More information

ADDENDUM #2 November 4, 2015 IFB-15-881

ADDENDUM #2 November 4, 2015 IFB-15-881 ADDENDUM #2 November 4, 2015 IFB-15-881 Roof Replacement Housing Authority of Kansas City 920 Main Street, Suite 701 Kansas City, MO 64105 NOTICE TO ALL POTENTIAL RESPONDENTS The following addendum to

More information

CHAPTER 5 ASPHALT-SHINGLE ROOFING

CHAPTER 5 ASPHALT-SHINGLE ROOFING CHAPTER 5 ASPHALT-SHINGLE ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 5.1.1 References double-coverage shingles provide two layers over Specifications for shingles and allied materials are most

More information

Nondestructive Evaluation of. Lockheed Martin Building at. 7152 Windsor BVLD, Windsor Mill, MD. Provided by: HurleyIR

Nondestructive Evaluation of. Lockheed Martin Building at. 7152 Windsor BVLD, Windsor Mill, MD. Provided by: HurleyIR Nondestructive Evaluation of Lockheed Martin Building at 7152 Windsor BVLD, Windsor Mill, MD Provided by: HurleyIR On Monday April 23, 2014, HurleyIR provided a nondestructive evaluation for Ruff Roofers

More information

INDIAN HEAD ELEMENTARY SCHOOL

INDIAN HEAD ELEMENTARY SCHOOL ROOF ASSESSMENT REPORT INDIAN HEAD ELEMENTARY SCHOOL NOVEMBER 08, 2010 PREPARED FOR: FACILITIES DEPARTMENT WHITMAN HANSON REGIONAL SCHOOL DISTRICT 1. Purpose This Roofing Assessment Report provides a summary

More information

BLACK JACK ALL WEATHER ROOF COATING

BLACK JACK ALL WEATHER ROOF COATING PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.

More information

CITY OF BELL PROFESSIONAL CONSULTING SERVICES FOR ROOF REPAIRS TO CITY OWNED FACILITIES

CITY OF BELL PROFESSIONAL CONSULTING SERVICES FOR ROOF REPAIRS TO CITY OWNED FACILITIES CITY OF BELL 6330 PINE AVENUE BELL, CA 90201 PH: (323) 588-6211 FAX: (323) 771-9473 CITY OF BELL PROFESSIONAL CONSULTING SERVICES FOR ROOF REPAIRS TO CITY OWNED FACILITIES I. INTRODUCTION City of Bell

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

What makes DECRA Roofing Systems unique?

What makes DECRA Roofing Systems unique? Commercial Roofing As the pioneer of stone coated steel technology, Roofing Systems have been proven around the world since 1957. Marketed and installed in over 120 countries, there are over 1 million

More information

CREEK Technical Services, LLC

CREEK Technical Services, LLC EVALUATION REPORT 2010 FLORIDA BUILDING CODE Manufacturer: Henry Company Report Issued February 20, 2013 999 North Sepulveda Blvd., Suite 800 El Segundo, CA 90245 (800) 486-1278 Manufacturing Plants: Quality

More information

Durapax Coal Tar BUR Application Guide

Durapax Coal Tar BUR Application Guide 400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof

More information

Roofing 101 - Signs that Your Roof Needs Repair/Replacement

Roofing 101 - Signs that Your Roof Needs Repair/Replacement By: Cherie Martel Roofing 101 - Signs that Your Roof Needs Repair/Replacement 1. Tell us a little bit about your company and its foundation. In 1963, Samuel T. Martel began a small family run roofing company,

More information

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)

More information

Genesis Home Inspections LLC

Genesis Home Inspections LLC Genesis Home Inspections LLC _ This Inspection was performed and Completed by a Licensed Home Inspector under Section 468.8314, Florida Statutes who has completed the statutory number of hours of Hurricane

More information

METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES

METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES REFLECTICLEAN ACRYLIC/URETHANE Elastomeric Roofing Systems, Inc 6900 Bleck Dr. Rockford, MN 55373 800.403.7747 -or- 763.565.6900 fax: 763.565.6901 email:

More information

ROOF INSPECTION & MAINTENANCE

ROOF INSPECTION & MAINTENANCE Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long

More information

Shingle Roofing: What s below the surface is important

Shingle Roofing: What s below the surface is important What s below the surface is important The roof is leaking, the shingles look old, and the downspouts are dripping. It must be time to replace the roof or is it? Shingle roofs may seem simple, but a roof

More information

0845 0098 980 www.nicholsonsts.com

0845 0098 980 www.nicholsonsts.com 0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution

More information

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809

More information

Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010

Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Custom bid generated for: Job site address: Lake Villas Condominium Attention:

More information

How To Replace A Roofing System In Florida

How To Replace A Roofing System In Florida Florida Consumer Considerations in Replacing their Roofing System The Florida Roofing, Sheet Metal and Air Conditioning Contractors Association provides the following general information to help Florida

More information

Nuiqsut - City Building Roof Repair

Nuiqsut - City Building Roof Repair Total Project Snapshot Report 2014 Legislature TPS Report 62228v1 Agency: Commerce, Community and Economic Development Grants to Municipalities (AS 37.05.315) Grant Recipient: Nuiqsut Project Title: Nuiqsut

More information

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING

More information

NRCA s steep-slope manual is thoroughly revised for 2013

NRCA s steep-slope manual is thoroughly revised for 2013 Photo courtesy of Boone Brothers Roofing, Omaha, Neb. NRCA s steep-slope manual is thoroughly revised for 2013 by Maciek Rupar 38 www.professionalroofing.net MARCH 2013 P ublished in January, The NRCA

More information

Common Property Maintenance Code Violations. An illustrated guide

Common Property Maintenance Code Violations. An illustrated guide Common Property Maintenance Code Violations An illustrated guide 1) Lawn and Vegetation Overgrown weeds, grass, or vegetation. Vegetation obstructing sidewalks, driveways, and other right of ways. Improper

More information

TABLE OF CONTENTS" SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE 7"

TABLE OF CONTENTS SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE 7 2 TABLE OF CONTENTS SECTION 1: What is a Standing Seam Metal Roof PAGE 3 SECTION 2: Common Types of Standing Seam Metal Roofs..PAGE 5 SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE

More information

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded

More information

DIY INSPECTION & MAINTENANCE

DIY INSPECTION & MAINTENANCE DIY INSPECTION & MAINTENANCE A Service of the Jewett Roofing Company 800-664-2845 JEWETT ROOFING COMPANY ST. LOUIS, MO - GREENVILLE, IL A Letter from our President Our customers have been the true blessing

More information

Roofing and Sealants. Contents. Section 6. 6.6.3 Single-ply membrane splicing cement. 6.0.0 Most frequently used types of roofing

Roofing and Sealants. Contents. Section 6. 6.6.3 Single-ply membrane splicing cement. 6.0.0 Most frequently used types of roofing Section 6 Roofing and Sealants Contents 6.0.0 Most frequently used types of roofing 6.0.0.1 Built-up membrane roofing 6.0.0.2 Fluid-applied membrane roofing 6.0.0.3 Single-ply membrane roofs 6.0.0.4 Metal

More information

WATERPROOFING FOR CONCRETE STRUCTURES

WATERPROOFING FOR CONCRETE STRUCTURES MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck

More information

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS OPTIONAL TITLE 24 CRITICAL POINTS POLYISO THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE DESCRIPTION TORCH OVER POLYISO (5,7,9 YR) TH/BS-TH/CS 2 No 0. SUBSTRATE. THERMOTEK USA PRO 2.0 FV

More information

C. Remove all existing asphalt shingles, underlayment and any loose debris into contractor provided dumpsters.

C. Remove all existing asphalt shingles, underlayment and any loose debris into contractor provided dumpsters. SCOPE OF WORK Project Title: Replace Deteriorated Roof Singles at Cape Lookout National Seashore Maintenance Shop PMIS # 159350 Prepared By: Mike Baker Cape Lookout National Seashore 131Charles St Harkers

More information

ROOFING CONTRACTORS QUESTIONNAIRE

ROOFING CONTRACTORS QUESTIONNAIRE ROOFING CONTRACTORS QUESTIONNAIRE ALL QUESTIONS MUST BE ANSWERED 1. Applicant Name: Website Address: Address: Years in business under the applicant name: Are you an NRCA (National Roofing Contractors Association)

More information

After the business decisions

After the business decisions After the business decisions have been made and the wet insulation and deteriorated deck have been identified, the real challenge of a comprehensive roof restoration the job of finding and repairing the

More information

THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING

THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING DIVISION 7 THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING 07110. MEMBRANE WATERPROOFING: The following are minimum requirements to assure adequately designed waterproofed floors for machine and equipment

More information

Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado

Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado Roof Condition Report Academy International School 8550 Charity Drive Colorado Springs, Colorado FOR Mr. Robert Thompson Academy School District 20 10221 Lexington Drive Colorado Springs, Colorado July

More information

Protecting Roofing Systems Against Windstorm Damage

Protecting Roofing Systems Against Windstorm Damage Protecting Roofing Systems Against Windstorm Damage This brochure is made available for informational purposes only in support of the insurance relationship between FM Global and its clients. This information

More information

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

A. This Section includes rubberized asphalt sheet membrane waterproofing systems. SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

UNIFIED FACILITIES CRITERIA (UFC) ROOFING MAINTENANCE AND REPAIR

UNIFIED FACILITIES CRITERIA (UFC) ROOFING MAINTENANCE AND REPAIR UNIFIED FACILITIES CRITERIA (UFC) ROOFING MAINTENANCE AND REPAIR APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED UNIFIED FACILITIES CRITERIA (UFC) ROOFING MAINTENANCE AND REPAIR Any copyrighted material

More information

RESIDENTIAL ROOF PERMITTING - 101. A REFRESHER WORKSHOP September 11, 2014

RESIDENTIAL ROOF PERMITTING - 101. A REFRESHER WORKSHOP September 11, 2014 RESIDENTIAL ROOF PERMITTING - 101 A REFRESHER WORKSHOP September 11, 2014 Agenda Basics of Permit Application Use of Charlotte County GIS system Florida Product Approvals Top Application Mistakes Standard

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

Roofer On-the-Job Training Guide

Roofer On-the-Job Training Guide Roofer On-the-Job Training Guide Roofers install and maintain built-up roofs, flat deck roofs, steep roofs and other roofs with a variety of covering materials. Training Requirements: 4500 hours (3 years)

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within

More information

UL Online Certifications Directory

UL Online Certifications Directory UL Online Certifications Directory Home Quick Guide Contact Us UL.com TGFU.R11183 Roofing Systems Page Bottom Roofing Systems See General Information for Roofing Systems PACTIV CORP SUITE 175 2100 RIVEREDGE

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer

Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Leak Buster Repair & Maintenance Products Quality You Can Trust Since 1886...From North America s Largest Roofing Manufacturer

More information

SECTION 07320 ROOFING TILE

SECTION 07320 ROOFING TILE SECTION 07320 ROOFING TILE PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: 1. Vitrified clay roofing tiles. 2. Tile accessories. 3. Felt underlayment. 4. Self-adhering sheet underlayment. 5. Snow guards.

More information

Fluid-Applied Roofing for Repair and Renovation FACILITIES & MAINTENANCE PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015

Fluid-Applied Roofing for Repair and Renovation FACILITIES & MAINTENANCE PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015 PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015 FACILITIES & MAINTENANCE By Rick Thomas Fluid-Applied Roofing for Repair and Renovation Leaking roofs are one thing which every private university facility

More information