REPLACE ROOFING DENVER CENTRAL LIBRARY PHASE I CITY & COUNTY OF DENVER DENVER, COLORADO
|
|
- Melvyn Tucker
- 8 years ago
- Views:
Transcription
1 PUBLIC LIBRARY PHASE I 4828 W. 6TH Avenue, Unit B-8 Golden, Colorado 8040 Phone: (303) VICINITY MAP SHEET INDEX GT /26/2009 SHEET DESCRIPTION G.0 COVER SHEET R.0 COMPOSITE ROOF PLAN R. NEW ROOF PLAN NEW ROOF DETAILS NEW ROOF DETAILS ABO DCL G-0.DWG COVER SHEET NO SCALE RG.0 5
2 ACCESS & SETUP NOTES:. FENCED SCAFFOLD ACCESS POINTS WILL BE NEEDED THROUGHTOUT THE PROJECT. 2. PERIODIC COORDINATED ACCESS WILL BE NEEDED AT THE PLAZA & SIDEWALK AREAS. 3. NO ENTRIES OR SIDEWALKS MAY BE BLOCKED WITHOUT COORDINATION WITH OWNER.. 4. LANDSCAPING AND SIDEWALK CONDITIONS PRIOR TO WORK SHALL BE DOCUMENTED. 4TH AVENUE ROOF DECK A PUBLIC LIBRARY ROOF DECK B ROOF DECK P2 ROOF DECK P ROOF DECK B ROOF DECK C ROOF DECK 4828 W. 6TH Avenue, Unit B-8 Golden, Colorado 8040 Phone: (303) METAL ROOF - ROOF DECK P3 TILE ROOF PROJECT AREA IS SHADED GRAY ROOF DECK E ADD ALTERNATE #2 PATIO DECK - ROOF DECK Q BROADWAY STREET ROOF DECK D BASE BID ROOF DECK D BASE BID GT /26/2009 SCAFFOLD ACCESS AREA ROOF DECK F ROOF DECK G SCAFFOLD ACCESS AREA PATIO DECK - ROOF DECK O ADD ALTERNATE #3 ROOF DECK N ADD ALTERNATE # ROOF DECK I ROOF DECK R ROOF DECK H ROOF DECK R3 ROOF DECK J ABO DCL R-0.DWG R.0 COMPOSITE ROOF PLAN SCALE: /6" = '-0" (:92) ROOF DECK K ROOF DECK M ROOF DECK R2 ROOF DECK M ROOF DECK L 0 4' 8' 6' 32' COMPOSITE ROOF PLAN /6" = '-0" (:92) R.0 /6" = '-0" 2 5
3 264'-6" PUBLIC LIBRARY C DECK D DECK D 84' SIM. C DECK E C 4828 W. 6TH Avenue, Unit B-8 Golden, Colorado 8040 Phone: (303) '-3" B C DECK O DECK N B B 20'-6" GT /26/2009 R.0 NEW ROOF PLAN SCALE: 3/32" = '-0" (:28) SYMBOL LEGEND PARAPET WALL SAFTEY TIEBACK RAIL TAPERED INSUL. RIDGE TAPERED INSUL. VALLEY EXISTING ROOF SYSTEM - DECK D (BASE BID) " WOOD FIBER INSUL. BD. TAPERED EPS BEADBOARD (0.25/2) NEW ROOF SYSTEM - DECK D (BASE BID) EXISTING ROOF SYSTEM - DECK N (ADD ALT. #) " WOOD FIBER INSUL. BD. TAPERED EPS BEADBOARD (0.25/2) EXISTING ROOF SYSTEM - DECK E (ADD ALT. #2) " WOOD FIBER INSUL. BD. TAPERED EPS BEADBOARD (0.25/2) EXISTING ROOF SYSTEM - DECK O (ADD ALT. #3) " WOOD FIBER INSUL. BD. TAPERED EPS BEADBOARD (0.25/2) NEW ROOF SYSTEM - DECK N (ADD ALT. #) NEW ROOF SYSTEM - DECK E (ADD ALT. #2) NEW ROOF SYSTEM - DECK O (ADD ALT. #3) TAPER SLOPE (0.25/2) PRIMARY ROOF DRAIN OVERFLOW ROOF DRAIN TAPERED INSUL. DRAIN SUMP PIPE/CONDUIT WINDOW WASH DAVIT BASE EXHAUST FAN CURB ABO DCL R-.DWG NEW ROOF PLAN / TAPERED ISOCYANURATE FOAM INSUL. (0.25/2).5" ISOCYANURATE FOAM INSUL. BD. / TAPERED ISOCYANURATE FOAM INSUL. (0.25/2) / TAPERED ISOCYANURATE FOAM INSUL. (0.25/2) / TAPERED ISOCYANURATE FOAM INSUL. (0.25/2) DUCT CURB 0 6' 2' 24' 48' 3/32" = '-0" (:28) R. 3/32" = '-0" 3 5
4 LIFT & RESET STRAINER & CLAMP RING ASSEMBLY TO FLASH CARRY EPDM INTO CLAMP RING & SET IN WATERBLOCK TAPERED INSULATION SUMP 4'x4' DO NOT SHAVE INSULATION DETAIL NOTES. THICKNESS OF BASE LAYER OF INSULATION VARIES. 2. DENOTES EXISTING ITEM TO REMAIN, ALL OTHER ARE NEW. 3. DETAILS ARE EXPLODED FOR CLARITY. MAKE ALL CONNECTIONS WATERTIGHT..5" ISO. FOAM INSUL. BD. PUBLIC LIBRARY LAP SEALANT UNCURED EPDM PIPE WRAP STRIP-IN FLASHING ROOF DRAIN ASSEMBLY NOTE: FLASH OVERFLOW DRAIN THE SAME.LIFT & RESET OVERFLOW COLLAR. 60 MIL ADHERED TPO MEMBRANE C ROOF DRAIN FLASHING SCALE: 3" = '-0" (:4) STEEL PANEL CLEAT 5 LF OR SEALANT AT FAILED COPING SAW CUT 4" OFF BOTTOM OF.5" ISO. FOAM INSUL. BD. 4" 6" NOTE: AT TIE-BACK ANCHORS PROVIDE PITCH PAN IF PIPE CAN'T BE WRAPPED. PANEL COPING STONE 24 GA. GALVANIZED SHEET PIN TO WALL 8" O.C. TIE-BACK ANCHOR FLASHING SCALE: 3" = '-0" (:4) CONDUIT OR PIPE 4828 W. 6TH Avenue, Unit B-8 Golden, Colorado 8040 Phone: (303) LAP SEALANT UNCURED EPDM PIPE WRAP STRIP-IN FLASHING.5" ISO. FOAM INSUL. BD. 60 MIL ADHERED TPO MEMBRANE WALL FLASHING SCALE: 3" = '-0" (:4) B SCALE: 3" = '-0" (:4) 5 LF OR SEALANT AT FAILED COPING.5" ISO. FOAM INSUL. BD. 00 LF OR SEALANT AT FAILED COPING PIPE/CONDUIT FLASHING SCALE: 3" = '-0" (:4) METAL DOOR GT /26/2009 COPING STONE PANEL COPING STONE THRESHOLD PLATE LIFT & RESET METAL EXPOSURE VARIES FROM DOOR TO DOOR CARRY EPDM FLASHING UNDER NEW GALV. FLASHING PIN TO CURB 2' O.C. 24 GA. GALV. FLASHING SET UNDER THRESHOLD PLATE - LIFT & RESET PANEL.5" ISO. FOAM INSUL. BD..5" ISO. FOAM INSUL. BD. ABO DCL R2-0.DWG NEW ROOF DETAILS 3" = '-0" (:4) SCALE: 3" = '-0" (:4) SCALE: 3" = '-0" (:4) DOOR THRESHOLD FLASHING SCALE: 3" = '-0" (:4) 4 5
5 DETAIL NOTES. THICKNESS OF BASE LAYER OF INSULATION VARIES. 2. DENOTES EXISTING ITEM TO REMAIN, ALL OTHER ARE NEW. 3. DETAILS ARE EXPLODED FOR CLARITY. MAKE ALL CONNECTIONS WATERTIGHT. PUBLIC LIBRARY SEALANT 24 GA. PRE-FINISHED SHEET PIN TO WALL 8" O.C. 22 GA. PRE-FINISHED SHEET METAL GRAVEL GUARD ~2'-6 NEW 3 4" PLYWOOD PLATE SECURED TO TOP OF EXISTING SHEET METAL MULTI-PIECE COPING CAP CARRY TPO MEMBRANE OVER TOP OF NEW PLYWOOD PLATE & DOWN WALL FACE 22 GA. GALV. SHEET METAL CLEAT, NAIL 8" O.C. CONCRETE KNEE WALL METAL ON WALL FRAMING 4828 W. 6TH Avenue, Unit B-8 Golden, Colorado 8040 Phone: (303) " CONCRETE KNEE WALL ~36" B SCALE: 3" = '-0" (:4) SCALE: 3" = '-0" (:4) LOUVER WALL METAL SILL FLASHING NEW 3 4" PLYWOOD PLATE SECURED TO TOP OF EXISTING SHEET METAL MULTI-PIECE COPING CAP SCHEDULE 00 LF OF COLORED SEALANT AT EXISTING METAL FLASHINGS AND LOUVER WALL STEEL PANEL CLEAT 22 GA. PRE-FINISHED SHEET METAL COPING CAP CARRY TPO MEMBRANE OVER TOP OF NEW PLYWOOD PLATE & DOWN WALL FACE GT /26/2009 4" 6" SAW CUT 4" OFF BOTTOM OF 24 GA. GALVANIZED SHEET PIN TO WALL 8" O.C. 22 GA. GALV. SHEET METAL CLEAT, NAIL 8" O.C. METAL ON WALL FRAMING CONCRETE CURB WOOD INFILL KNEE WALL REMOVE WALL TO FLASH CONCRETE KNEE WALL ~36".5" ISO. FOAM INSUL. BD. ABO DCL R2-.DWG NEW ROOF DETAILS 3" = '-0" (:4) SCALE: 3" = '-0" (:4) SCALE: 3" = '-0" (:4) WALL BASE FLASHING SCALE: 3" = '-0" (:4) 5 5
Sheet A-1 KEY SHEET A-1. Football Roof Plan SHEET A-2 SHEET A-3 SHEET A-4. LaCross Roof Plan. Soccor 2 Roof Plan 88' 45' 87' 46' 45' 45' 10' 3' 25'
Sheet A-1 SHEET A-1 Football Roof Plan 5 LaCross Roof Plan 5 88' 87' SHEET A- 1 DRIP EDGE WITH STANDING SEAM PANEL 2 RAKEWALL SHEET A- RIDGE HIP HEAD WALL 11700 Pierson Rd. Wellington, FL. 1 Soccor 2 Roof
More informationSmooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36.
Demolition/Removal of Work 4-ply built up roofing to the insulation (smooth cap sheet) Smooth cap sheet - 0-10 SQ $ 63.00 Smooth cap sheet - 11-50 SQ $ 63.00 Smooth cap sheet - 51-100 SQ $ 35.00 Smooth
More informationCHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS
TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes
More informationFig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION
SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.
More informationRoof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.
Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...
More informationSTANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
More informationLINE OF EXISTING ADJACENT STRUCTURE 6" MIN. PROTECTION COURSE (NOT REQUIRED WHERE THERE IS NO ADJACENT BLDG. MOISTURE RESISTIVE MEMBRANE AT EXIST. AND NEW BLDG. AS OCCURS WATER STOP SLAB-ON-GRADE TERMINATION
More informationNRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
More informationThe better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs
The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................
More informationClear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015
Clear Fork Valley Local School District Roofing Repairs Spring/Summer 2015 Instructions to Bidders: Public Notice To Bidders (ORC 3313.46) Notice is hereby given that sealed bids will be received at the
More informationROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
More informationWESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC
More informationHow To Repair A Boat Landing Deck With A Boat Bed
RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing
More informationIndefinite Quantity Unit Price Schedule
Indefinite Quantity Unit Price Schedule DCS # 08002 THIS SET OF BID FORMS IS FOR AREA 4 WORK DESCRIPTION Unit Unit Price Specification Number 2.1 WATERPROOFING & DAMPPROOFING 2.1 10 100 Pressure cleaning.
More informationVer. 2. Guide to. Inspecting Residential Brick Veneer
Ver. 2 Guide to Inspecting Residential Brick Veneer 1. A guide created by industry professionals. The knowledgeable staff at MASONPRO together with technical support from the Masonry Institute of Michigan
More informationRoof Inspection and Evaluation
Roof Inspection and Evaluation Sylvester Powell Community Center 6200 Martway Mission, KS 66202 Prepared For: Your name Sample Community Center 6200 Martway Mission, KS 66202 Kansas City, MO 64105 200
More informationTARRANT COUNTY DETAIL STANDARDS
TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout
More informationCERVANTES COMMUNITY CENTER RE-ROOFING NEW MEXICO STATE UNIVERSITY
420 CENTER DR,, NM DESIGN DEVELOPMENT DRAWING INDEX TITLE SHEET T1.1 PROJECT DATA, VICINITY MAP, INDEX ARCHITECTURAL DEMOLITION FLOOR, CEILING & ROOF PLANS FLOOR & CEILING PLAN & ROOF PLAN MECHANICAL M1.0
More informationRoof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building
Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Prepared For: Ms Marilyn Bittenbender Colliers International 805 New Hampshire St Lawrence Kansas, 66046 Prepared
More informationSAMPLE SCHEDULE OF VALUES APPLICATION & CERTIFICATE FOR PAYMENT
SAMPLE SCHEDULE OF S 1.00 General Conditions 1.01 Project Management 1.02 General Superintendent 1.03 Superintendents 1.04 Safety Engineer 1.05 Scheduling 1.06 Field Engineering 1.07 Bonds 1.08 Trailer
More informationREQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION
RESIDENTIAL: REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION 2 COMPLETE SETS OF PRINTS WITH ENGINEERS STAMP ON FOUNDATION PLAN INCLUDING ELECTRICAL, PLUMBING, ETC. SITE PLAN SHOWING HOUSE LOCATION
More informationCITYPLEX TOWERS BOILER INSTALLATION ORU RFP-1138
ALTERNATE No. 2 BFS LOCATION: Locate BFS North of B-3 on new house-keeping pad. HOUSE KEEPING PAD and DRAIN CONNECTIONS: Furnish house-keeping pad for new boilers B-2 and B-3 including trench drains to
More informationSECTION 07320 ROOFING TILE
SECTION 07320 ROOFING TILE PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: 1. Vitrified clay roofing tiles. 2. Tile accessories. 3. Felt underlayment. 4. Self-adhering sheet underlayment. 5. Snow guards.
More informationDelaney-Vogel School
Wrentham Public Schools Delaney-Vogel School Schematic Design 1. INTRODUCTION Wrentham Public Schools contracted with Turowski2 Architecture, Inc. on November 11, 2015 to assess necessary roof repairs
More information!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!
Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing
More informationAir-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
More informationRESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
More informationClassic Products, Inc. ClickLock Standing Seam Installation Manual
Classic Products, Inc. ClickLock Standing Seam Installation Manual Classic Products, Inc. 8510 Industry Park Drive Piqua, OH 45356 800.543.8938 Table of Contents page Introduction 1. 1 Starter. 2. 1 Panels.
More informationA0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET
POYNTZ AVENUE, STE 9 MANHATTAN, KS 0..0..9 FAX WEST th STREET JUNCTION CITY, KS.... FAX 0, Bruce McMillan AIA, Architects, P.A. HERITAGE TRUST FUND GRANT PROJECT NO. 0-0 ROOF REPAIR OF THE 00 LOCUST STREET
More informationAPPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET
Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing
More informationNEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
More informationMINNEAPOLIS MARKET STREAM PRIVATE DATA CENTER CHASKA, MINNESOTA. 2001 Ross Avenue, Suite 2800 Dallas, Texas 75201
STREAM PRIVATE DATA CENTER MINNEAPOLIS MARKET CHASKA, MINNESOTA 2001 Ross Avenue, Suite 2800 Dallas, Texas 75201 www.streamdatacenters.com 866.301.0901 2 SECURE INDEPENDENT EFFICIENT SECURE Secured perimeter
More informationCHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
More informationSINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
More informationSuperform Products Ltd.
TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000
More informationSTANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
More informationENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill
ENERGY STAR Qualified New Homes Thermal Enclosure Checklist & Water Management Checklist Eli Caudill ENERGY STAR Version 3 Tighter Standards Whole Home Approach Better, More Sustainable Construction Surpasses
More informationINSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
More informationWISCONSIN HOUSING AND ECONOMIC DEVELOPMENT AUTHORITY
WISCONSIN HOUSING AND ECONOMIC DEVELOPMENT AUTHORITY EPDM - SINGLE PLY MEMBRANE ROOFING REPLACEMENT SPECIFICATION Section 07500 - June 97 - Revised TO: Owners/Project Managers/Contractors RE: All WHEDA
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design
Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)
More informationUL Online Certifications Directory
UL Online Certifications Directory Home Quick Guide Contact Us UL.com TGFU.R11183 Roofing Systems Page Bottom Roofing Systems See General Information for Roofing Systems PACTIV CORP SUITE 175 2100 RIVEREDGE
More informationMark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
More informationAMERICAN GOTHIC PLAYHOUSE
AMERICAN GOTHIC PLAYHOUSE Project Plan #856 Sheet 1 of 5 Pick a spot and get started with the beautiful that your kids will love. The design of the playhouse includes 35 square feet of interior space plus
More informationSEAMS SEAMING USING SEAM TAPE
SEAMING USING SEAM TAPE SEAMS The membrane should be positioned so that the width of the seam is 3. Remove excess chalk from a chalk line by snapping the line into the air and then chalk a line one-quarter
More informationAsphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
More informationCONTINENTAL MATERIALS, INC. ALL-WEATHER APP INSTALLATION GUIDELINES
CONTINENTAL MATERIALS, INC. ALL-WEATHER APP INSTALLATION GUIDELINES Page 1 APP INSTALLATION GUIDELINES This guide provides instructions for the installation of CMI All Weather APP roofing materials. Any
More informationREQUEST FOR PROPOSALS
Page 1 of 6 REQUEST FOR PROPOSALS Issue Date: 2/19/2013 RFP# WHS-2013-001 Title: Services for roofing improvements and annual roof assessments, Windsor School Complex, State Street, Windsor, Vermont Issuer
More informationSECTION 07 54 23 PVC SINGLE PLY ROOFING
SECTION 07 54 23 PVC SINGLE PLY ROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Attached GENERAL CONDITIONS, GENERAL NOTES, INSTRUCTIONS TO BIDDERS, AND BID FORM are components of this section. B. Section
More informationEPDM System Repair and Cleaning
EPDM single-ply roof systems have represented a third of the volume of the low-sloped commercial market for close to twenty years. The majority of these roofs were installed to receive the manufacturer
More informationLarry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010
Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Custom bid generated for: Job site address: Lake Villas Condominium Attention:
More informationAll substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.
2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other
More informationRoof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:
More informationMaintenance & Inspection Guide
ADDRESSING THE NEEDS OF OUR CUSTOMERS AND THE ENVIRONMENT ONE high Performance roofing SOLUTION AT A TIME. Maintenance & Inspection Guide TABLE OF CONTENTS Topic: Page: I. Introduction 1 II. Maintenance
More informationWhitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.
Building Type Building Code Whitley Classroom Buildings BOCA, UBC, SBCCI, NEC, ADA Structural Support Outrigger construction standard, Whitley model classrooms. Main support beams to be 12 11.8# per lineal
More informationBITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC.
93-106 Revised March 2007 BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC. BITEC APM-4.5T is a torch applied, mineral surfaced,
More information!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035
Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí
More informationWaterproof Rooftop Balconies & Decks. Or How To Keep Your Ceiling Dry When People Walk On Your Roof
Waterproof Rooftop Balconies & Decks Or How To Keep Your Ceiling Dry When People Walk On Your Roof Overarching Concerns That Apply to All Walkable Decks Over Roofs Structure must be strong enough to support
More informationSTREAM PRIVATE DATA CENTER SAN ANTONIO MARKET WESTOVER HILLS. 2001 Ross Avenue, Suite 2800 Dallas, Texas 75201. www.streamdatacenters.com 866.301.
STREAM PRIVATE DATA CENTER SAN ANTONIO MARKET WESTOVER HILLS 2001 Ross Avenue, Suite 2800 Dallas, Texas 75201 www.streamdatacenters.com 866.301.0901 2 SECURE INDEPENDENT EFFICIENT SECURE Concrete roof,
More informationFLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS
FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS Table of Contents Chapter 1: FLAT ROOF REPAIR - CUT COST WITHOUT CUTTING CORNERS Chapter 2: PVC RECOVER SYSTEM HOW IT WORKS Chapter 3: 8 STRATEGIES TO
More information609 West Rock Road, Radford,VA 24141 540-633-5000 / (fax) 540-731-3712 RECOMMENDED ATTACHMENTS & CONNECTION DETAILS
609 West Rock Road, Radford,VA 24141 540-633-5000 / (fax) 540-731-3712 RECOMMENDED ATTACHMENTS & CONNECTION DETAILS INDEX OF DRAWINGS SECTION A: A-1 = METAL TRACK TO PANEL ATTACHMENT A-2 = WOOD PLATE TO
More informationPERIMETER FLASHING. Table of Contents
FM Global Property Loss Prevention Data Sheets 1-49 February 1985 Revised September 2000 Page1of25 PERIMETER FLASHING Table of Contents Page 1.0 SCOPE... 3 1.1 Changes... 3 2.0 LOSS PREVENTION RECOMMENDATIONS...
More informationROOF FLASHING SPRINGLOK FLASHING SYSTEM FEATURES & BENEFITS PRODUCT DESCRIPTION
SPRINGLOK SYSTEM PRODUCT DESCRIPTION FEATURES & BENEFITS Fry Reglet offers five flashing systems, each tailored for a particular type of substrate so you can get exactly what you need. SM Surface mounted
More informationTable of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities
Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)
More informationUniversity of California - Santa Barbara West Campus Point Faculty Housing
University of California - Santa Barbara West Campus Point Faculty Housing Reconstruction Guidelines and Considerations to Correct Exterior Building Envelope Weatherproofing Defects and Recommended Upgrades
More informationROOFS - Guidance for Repair, Maintenance and Replacement
ROOFS - Guidance for Repair, Maintenance and Replacement Guilford Association Architectural Committee ROOFING Slate and tile roofs are a critical design feature of Guilford homes. The homes were designed
More informationFinal inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
More information0845 0098 980 www.nicholsonsts.com
0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution
More informationHISTORIC PRESERVATION COMMISSION ADMINISTRATIVE APPROVAL ISSUED JULY - SEPTEMBER 2014 DATE PROJECT ADDRESS PROJECT DESCRIPTION
HISTORIC PRESERVATION COMMISSION ADMINISTRATIVE APPROVAL ISSUED JULY - SEPTEMBER 2014 DATE PROJECT ADDRESS PROJECT DESCRIPTION 07/02/14 212A King George Street Remove existing picket fence from side yard
More informationSTREAM PRIVATE DATA CENTER
STREAM PRIVATE DATA CENTER SAN ANTONIO 75,840 SF stand-alone hardened Private Data Center 30,000 SF of raised floor data center space Three (3) Private Data Center Suites 1,200 KW critical load per Private
More informationIssue of the Guidelines on Prevention of Water Seepage in New Buildings
graphic: Buildings Department Your REF 來 函 檔 號 :. OUR REF 本 處 檔 號 :.BD GR/1-55/173 FAX 圖 文 傳 真 :..28400451 TEL 電 話 :..2626 1717 www.info.gov.hk/bd To : All Authorized Persons 7 March 2005 Registered Structural
More informationMUNICODE SERVICES LTD.
The Preserved Wood Foundation Guide MUNICODE SERVICES LTD. Prepared by MuniCode Services Ltd. Outline and Restrictions of this Guide The following information required for the construction of Preserved
More informationEnvelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit
R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed
More informationResidential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
More informationTITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
More informationAPPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE
APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT NCE Table Application Type Description Page 1A-1 Wood New, Reroof (Tear-Off), Recover C-1 Mechanically Attached Insulation, Bonded Roof Cover 4 1A-2
More informationPETERSONS WATERFRONT CONDOMINIUMS
CONSULT DESIGN CONSTRUCT PETERSONS WATERFRONT CONDOMINIUMS 103 Park Street Chelan, Washington Findings Summary Report Prepared for: Petersons Waterfront Condominium Association March 21, 2014 J2 Project
More informationISO Types 1-6: Construction Code Descriptions
ISO 1 Frame (combustible walls and/or roof) Class 1B Buildings where the exterior walls are wood or other combustible materials, including construction where the combustible materials are combined with
More informationROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof
ROOF CONSTRUCTION The overall appearance of a building is greatly affected by the roof lines and the roofing materials. The designer has many standard designs to choose from and should be able to find
More informationDISTRICT OF BARRIERE REQUEST FOR PROPOSAL
DISTRICT OF BARRIERE REQUEST FOR PROPOSAL SUPPLY AND INSTALLATION OF FLAT ROOF SYSTEM AND RELATED REPAIRS RFP No. 2014-02 1. SUMMARY OF REQUIREMENT The District is planning on reroofing the existing flat
More informationLITITZ MUTUAL INSURANCE COMPANY 2 North Broad Street Lititz, Pennsylvania - MAIN OFFICE -
The original section of this building was constructed in 1941. The exterior walls are built of good quality stone. In the early 1980 s a similar addition was added to the north elevation. The exterior
More informationROOF ASSEMBLIES CHAPTER 9
CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION
More informationEpdm Flat Roofing Systems
Epdm Flat Roofing Systems EDPM can be fully bonded, loose laid and ballasted or mechanically attached depending on the existing roof and its proposed usage. This applies to roofs to be refurbished and
More informationFebruary 4, 2016. Estimate
Wrentham, MA February 4, 2016 Architect: Turowski2 Architecture, Inc. P.O. Box 1290 313 Wareham Road Marion, MA 02738 (508) 758-9777 Cost Estimator: Miyakoda Consulting 300 Black Mallard Road Bridgewater,
More informationRoofing and Sealants. Contents. Section 6. 6.6.3 Single-ply membrane splicing cement. 6.0.0 Most frequently used types of roofing
Section 6 Roofing and Sealants Contents 6.0.0 Most frequently used types of roofing 6.0.0.1 Built-up membrane roofing 6.0.0.2 Fluid-applied membrane roofing 6.0.0.3 Single-ply membrane roofs 6.0.0.4 Metal
More informationFree 12 x 8 Shed Plan With Illustrations, Blueprints & Step By Step Details
Free 12 x 8 Shed Plan With Illustrations, Blueprints & Step By Step Details Brought To You By: MyShedPlans Click Here To Download 12,000 Shed Plans >> 12 x 8 Basic Shed This 8 12-ft. shed features a simple
More informationSECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
More informationSECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,
More informationTHERMOPLASTIC MEMBRANE (PVC) ROOFING Added 11/2012 07 54 19-1 Thermal and Moisture Protection
SECTION 07 54 19 - SINGLE PLY PVC REROOFING PART 1 - GENERAL 1.1 SUMMARY A. All roofing areas, flashings, penetrations and equipment shall be included in the work under this section. B. Furnish materials
More informationFirestone RubberGard The EPDM reference
Firestone RubberGard The EPDM reference EPDM Roofing Systems 1.000.000.000 m 2 of proven performance The Firestone heritage of success and quality is extended to the construction industry through the Firestone
More informationDIVISION 7 - THERMAL AND MOISTURE PROTECTION
DIVISION 7 - THERMAL AND MOISTURE PROTECTION Note: This is a guide for Designers only. Contents shall not be used in lieu of specifications as part of the Designer s Contract Documents. SECTION 07 1000
More informationPoint Auditorium Design Narrative PROJECT NAME: Point Auditorium DATE: 06/25/15 TO: Lance Francis FROM: Leslie Ellsworth
INTRODUCTION: Kronberg Wall Architects is pleased to present the Design Narrative for the Point University Auditorium conversion from the existing warehouse space. General Project Description: This project
More informationRoof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
More informationIf you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
More information3 Installation. 9 Roof Edges... p. 3. 19 10 Wall Terminations... p. 3. 20 11 Membrane Repair... p. 3. 21 12 Miscellaneous... p. 3. 22. 3.
3 Installation The information provided within this chapter may assist the contractor to install the Firestone UltraPly TPO Systems in accordance with Firestone s requirements. It may also help him and
More informationAdditions and Alterations
Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal
More informationREPLACE ROOF AT CCAC NORTH CAMPUS. RADELET McCARTHY POLLETTA INCORPORATED ARCHITECTS AND INTERIOR DESIGNERS DRAWING SYMBOLS
REPLACE AT CCAC NORTH CAMPUS Roof Replacement 0 TEAM RADELET McCARTHY POLLETTA INCORPORATED ARCHITECTS AND INTERIOR DESIGNERS INDE OF DRAWINGS G00 COVER SHEET AD0 DEMOLITION PLAN DEMOLITION DETAILS PLAN
More informationNominal Life Expectancy for Building Components
Nominal Life Expectancy for Building Components Building System Page A. HVAC 2 B. Elevator/Escalator 6 C. Plumbing 7 D. Roofing 8 E. Electrical 10 F. Fire/Life/Safety/Security System 11 G. Interior Finishes
More informationTHERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING
DIVISION 7 THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING 07110. MEMBRANE WATERPROOFING: The following are minimum requirements to assure adequately designed waterproofed floors for machine and equipment
More informationROOF DRAINS TABLE OF CONTENTS
Pictorial Index Product Recommendations Roof Drain Selection Factors Sizing Placement Material & Characteristics Pipe Connection Commonly Specified Options Typical Installations TABLE OF CONTENTS ROOF
More informationRenovating Your Basement
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:
More information