Protecting Roofing Systems Against Windstorm Damage
|
|
|
- Anna Rodgers
- 10 years ago
- Views:
Transcription
1 Protecting Roofing Systems Against Windstorm Damage
2 This brochure is made available for informational purposes only in support of the insurance relationship between FM Global and its clients. This information does not change or supplement policy terms or conditions. The liability of FM Global is limited to that contained in its insurance policies. 2
3 I n recent years, there have been a number of hurricanes, typhoons and cyclones that have raised awareness about the significant damage they can cause. It is important to realize that all windstorms wreak havoc especially in areas of the world unaccustomed to them. Most industrial building structures can withstand high winds, but the roofing system which acts like an envelope protecting the interior of a building can be susceptible to damage. Once the roof is compromised, the entire contents of a building become vulnerable to water and wind. FM Global-insured wind losses averaged US$400 million per year from , with 80 percent of the loss dollars related to roofing system failures. In fact, since 1998, approximately 1,128 roof-related wind losses were reported to FM Global, totaling nearly US$1.7 billion.* Protecting commercial roofing systems is the single-most effective way to reduce windstorm loss. In fact, one of the most cost-effective ways to economically upgrade a roofing system is to attach additional fasteners to only the small edge areas of the roof. Wind Losses Since 1985* 41% 59% Severe windstorms (hurricanes, typhoons or cyclones) Other windstorms * Indexed to 2007 dollars. * These percentages represent net wind losses for FM Global clients, from
4 The Wind-Roof Connection To best protect your commercial roofing system from windstorm hazards, it is important to understand the wind-roof connection. Wind forces on a building create an action similar to that of wind passing over an aircraft wing. Know the hazard The most important component of a roofing system is the metal-edge flashing, which secures the roof cover to the edge of the building. If high wind loosens perimeter flashing, further damage to the rest of the roof roof covering and insulation is inevitable, even if properly secured. Inadequately designed and installed flashing will likely lead to additional damage from water leakage. Inspecting existing flashing is easy to do by pulling out on the lower edge. If it feels loose, it can be re-secured fairly inexpensively with appropriate weather-resistant fasteners with washers. A change in the wind s direction as it passes over and around the building results in uplift or suction forces. These forces vary dramatically in magnitude on different parts of the roof with forces much greater along the roof edges than in the main interior or field of the roof. In the corners (shown in red), the wind force can be more than two-and-onehalf times the uplift than in the main interior (field) of the roof. At the perimeter edges of the roof (shown in yellow), the uplift force can be more than one-andone-half times that in the main interior of the roof. Also important to the roofing system is the roof itself, which acts as an envelope protecting the contents of the building. If the roof becomes detached, the interior of the building becomes exposed to rain and wind. In many cases, the main interior (field) of commercial roofing systems is adequately secured, but the corners and perimeter are not. This occurs mostly because roofs tend to be uniformly attached. The higher uplift forces at the corners and perimeter can overload the fasteners that keep the roof attached to the building. The damaged corner or perimeter then allows the wind to act on loose edges of roof cover, and a large area of the roof can peel off. Fortunately, adding fasteners to these small areas of the roof is relatively inexpensive. 4
5 Don t Be Complacent Because Your Facility Survived a Hurricane......And Don t Underestimate the Power of Lesser Wind Speeds So, your building is still standing despite the Category 4 hurricane that swept through your area. You re feeling pretty good. But are you absolutely sure the wind speeds that passed over your facility were actually of Category 4 magnitude? Hurricane wind speeds vary dramatically with the most severe wind occurring in a relatively small area near the eye wall. Your facility may have experienced Category 1 or 2 wind speeds even though the hurricane was a Category 4 at landfall. Minor differences in wind speeds result in much greater uplift forces on the roof because wind uplift pressures increase exponentially with wind velocity. Doubling wind velocity quadruples its pressure. For example, a 140-mph (63-m/s) wind exerts twice the uplift pressure of a 100-mph (45-m/s) wind. Depending on the type of roof, these forces can wreak havoc on areas that are particularly vulnerable to damage, such as the flashing, perimeters and corners. Conversely, loss experience has proven that even wind of less velocity is capable of causing considerable damage when roofing design, installation or maintenance is deficient. For example, insulation boards adhered with hot asphalt directly to steel decks are not recommended for use at any time because, historically, hot asphalt used for securing the insulation boards to the steel deck has been applied improperly. This traditionally poor installation is what makes this type of roofing system susceptible to even minor wind velocity. FM Global engineers have found clay and concrete roof tiles that were fastened improperly. In other cases, facilities used only mortar without any fasteners, and loosely or inadequately attached tiles had been blown off the roof, becoming missiles that broke windows and damaged wall surfaces. Depending on the quality of the roofing design, installation and maintenance, a roofing system may or may not withstand lesser wind speeds. Loss experience has proven that even wind of less velocity is capable of causing considerable damage when roofing design, installation or maintenance is deficient. Hurricane damage to this roof is concentrated at the corners and perimeter, where the uplift pressure is higher. 5
6 Properly designed windows and doors can help protect the roof from damage in a storm. If windows and doors break from wind pressure or windborne debris, the uplift pressure in the building can increase by 10 to 30 percent, blowing off the roof. Additionally, roof-top equipment not properly secured can be blown loose, tumble across the roof, and slice open the roof covering. And, metal panels pulled through their fasteners and gravel blown off the roof can mar building surfaces and break windows or door glazing. Know the Solution Ensuring the integrity of your commercial roofing system can be simple and inexpensive. In many cases, only the small perimeter and corner areas the 10-ft. (3-m) edges of the roof for a 30-ft. (9.1-m) high building up to 100-ft. (30.5-m) wide need to be reinforced. Most of the time, reinforcement can cost less then US$5,000. FM Global is available to help you design the proper roof for your location, using the right combination of FM Approved material. If your existing roof needs more uplift resistance, FM Global can identify vulnerable areas, low-cost solutions and, possibly, alternative ways to improve uplift resistance. Call your FM Global client service representative today. Be Sure To Inspect Your Roof You can conduct a preliminary self-inspection of your roof to determine if there are major deficiencies. Is your flashing secure? Only if it passes the pull test. Is your roof in good condition? If it looks bad, it is bad, and won t hold up in a hurricane. If it feels like it s coming apart, chances are, it will come apart when you need it most. Is the roof covering over your steel deck roof secure? Look for fasteners. If none are visible, your roof is probably deficient. If fasteners are visible, contact FM Global for an analysis of the securement. Are windows and other openings secured? Be sure all building openings (even skylights) are impactresistant or protected by shutters, as needed. 6
7 Additional Resources FM Global offers access to a wide range of educational material designed to increase property protection awareness and understanding. These resources include publications, learning kits, CD-ROMs, videos and FM Global Property Loss Prevention Data Sheets engineering guidelines written to help reduce the chance of property loss due to fire, weather conditions and failure of electrical or mechanical equipment. For more information, visit our online catalog at The following is a partial list of resources available to help you protect your roofing system against windstorm damage: FM Global Property Loss Prevention Data Sheets n 1-28, Wind Design n 1-28R/1-29R, Roof Systems n 1-29, Roof Deck Securement and Above-Deck Roof Components n 1-30, Repair of Wind-Damaged Roof Systems n 1-31, Metal Roof Systems n 1-32, Existing PVC Roof Covers n 1-33, Safeguarding Torch- Applied Roof Installations n 1-34, Hail Damage n 1-35, Green Roof Systems n 1-49, Perimeter Flashing n 1-52, Field Uplift Tests n 1-54, Roof Loads for New Construction Our data sheets are available at no cost at Register today! Publications n Protecting Your Facility Against Major Windstorms (P9811) n Severe Windstorm Checklist (P9308) Online training n Preparing for Hurricanes, available at fmglobal.com Simple Security Sometimes all it takes to prevent a catastrophic property loss is a few well-placed screws. It sounds ridiculously simple, but it s true. Applying additional fasteners at the perimeter and corners of a roof where it s most vulnerable can prevent it from detaching and peeling back, exposing the building s interior contents to wind and water. This is the most cost-effective way to economically upgrade a roofing system. For more information about this and other ways to protect your roofing system, contact your FM Global client service team. 7
8 P0283 (Rev. 6/08) Printed in USA (6/08) 2008 FM Global All rights reserved. In the United Kingdom: FM Insurance Company Limited 1 Windsor Dials, Windsor, Berkshire, SL4 1RS Regulated by the Financial Services Authority. Contact Us: To report an impairment or to find an FM Global office nearest you, visit Report A Loss: Dial (1)877 NEW LOSS ( )* to report a property or cargo loss 24 hours a day, seven days a week. Or, to contact your client service team or designated claims office directly, go to or for location and contact information. * For clients of FM Global and Affiliated FM in Canada and the United States only. Product Ordering Information: For additional copies of this publication or other FM Global resources, order online 24 hours a day, seven days a week at Or, for personal assistance worldwide, contact our U.S.-based customer services team, Monday Friday, 8 a.m. 5 p.m. ET: n Toll-free: (1) (Canada and the United States) n Phone: +1 (1) n Fax: +1 (1) n [email protected]
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET
Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing
Protecting Your Home From Hurricane Wind Damage
T H E W I N D Protecting Your Home From Hurricane Wind Damage During a hurricane, homes may be damaged or destroyed by high winds and high waves. Debris can break windows and doors, allowing high winds
Property Policyholder Risk Improvement Report and Hurricane Survey
Risk Engineering Property Policyholder Risk Improvement Report and Hurricane Survey Zurich Services Corporation Risk Engineering 1400 American Lane Schaumburg, IL 60196-1056 847.605.6000 Fax: 847.605.7854
The Florida Building Code
The Florida Building Code Florida s Response to Hurricane Risk Rick Dixon Florida Building Commission Florida Building Commission Architect Structural Engineer Mechanical Engineer Fire Protection Engineer
SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide
SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide Inspection Questions? Call Bloom At 800-483-9932 www.bloomroofing.com DISCLAIMER
Protecting YOUR NEW HOME FROM Wind Damage
Protecting YOUR NEW HOME FROM Wind Damage Blueprint for Safety... A Blueprint for Life When severe weather threatens, protecting life and property automatically becomes top priority for millions of Florida
Get Rid of Roof Problems for Good. How spray foam roofing can protect your building and make you money
Get Rid of Roof Problems for Good How spray foam roofing can protect your building and make you money What is a Spray Foam Roofing System? 300 MILLION Board feet of roofing spray foam installed annually
Commercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...
Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
Wind Mitigation Discount Plan
Wind Mitigation Discount Plan Louisiana Hurricane Loss Mitigation Survey Form Inspector Instructions The purpose of these instructions is to provide guidance to certified inspectors on how to properly
SECTION 3 ONM & J STRUCTURAL ANALYSIS
Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION
Protecting Your Home from Wind Damage
Protecting Your Home from Wind Damage During severe thunderstorms or hurricanes, homes may be damaged or destroyed by high winds. Debris flying through the air can break windows and doors, allowing high
ROOF INSPECTION & MAINTENANCE
Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long
Insurance Mitigation Factors for Homeowners Purchasing Garage Doors In Florida
Insurance Mitigation Factors for Homeowners Purchasing Garage In Florida The following questions and answers are intended to clarify the effect on insurance premiums for Florida homeowners when a new or
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
The Perfect Fit For Metal Retrofit
D u r o - S h i e l d M e t a l R e t r o f i t R o o f i n g S y s t e m The Perfect Fit For Metal Retrofit Lock out leaks. Lock in your investment. Has time caught up with your metal roof? There are
PERIMETER FLASHING. Table of Contents
FM Global Property Loss Prevention Data Sheets 1-49 February 1985 Revised September 2000 Page1of25 PERIMETER FLASHING Table of Contents Page 1.0 SCOPE... 3 1.1 Changes... 3 2.0 LOSS PREVENTION RECOMMENDATIONS...
Minimizing Water Intrusion Through Roof Vents in High-Wind Regions
Minimizing Water Intrusion Through Roof Vents in High-Wind Regions http://www.fema.gov HURRICANE IKE RECOVERY ADVISORY Purpose: To recommend practices for minimizing water intrusion through roof vent systems
Residential Sheltering: In-Residence and Stand-Alone Shelters
Residential Sheltering: In-Residence and Stand-Alone Shelters Intended Audience and Purpose The purpose of this Tornado Recovery Advisory (RA) is to alert homeowners, renters, and apartment building owners
TRAINING OUTLINE FOR PART TIME BUILDERS
TRAINING OUTLINE FOR PART TIME BUILDERS This is a training outline for persons who get involved in repair work and minor building work, emphasizing disaster resistance and good practice. It is intended
Wind Mitigation Inspection
[email protected] Tampa Bay Area: SW & Central Florida: (813) 368-6407 (239) 896-3986 Wind Mitigation Inspection VonHaase, Dale 4585 Bowen Bayou Road Sanibel, FL 33957 5/6/2013 Note to Policyholder:
CITIZENS PROPERTY INSURANCE CORPORATION. STREET ADDRESS: 14300 Gulf Blvd, Maderia Beach, FL 33708 6 Six story masonry residence
CITIZENS PROPERTY INSURANCE CORPORATION BUILDING TYPE II AND III MITIGATION VERIFICATION AFFIDAVIT This affidavit must be completed to capture mitigation features applicable to a Type II (4 to 6 story)
The Peak of Protection
FUTURE ROOF The Peak of Protection Our Future is Your Satisfaction E l e g a n t Imagine the look of heavy wood shake without all the problems associated with wood. Future Shake by Future Roof Systems
Dollars & Sense of Compliance!
CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors
Windows, skylights, vents, and glazed portions of doors are critical components of a building s
WINDOWS, DOORS, AND OPENING PROTECTION 10 Windows, Doors, and Opening Protection 10.1 Introduction Windows, skylights, vents, and glazed portions of doors are critical components of a building s envelope.
Guide to Safe Building Practices
Guide to Safe Building Practices Guide to Safe Building Practices This is a guide for tradesmen, builders and contractors to help them build, repair and retrofit buildings and particularly roofs, with
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Hurricane Damage. How Wind Forces Affect Homes
Hurricanes are among the most destructive and costliest of all natural disasters. Since 1995, the United States has entered a cycle of more intense hurricane activity. Between 2003 and 2007 Florida was
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
Commercial Roof Inspection Form
Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building
The Florida Building Code
Setting New Standards for Safety The Florida Building Code Florida Building Commission Florida Department of Community Affairs The Florida Building Code System The Florida Building Commission Florida Building
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
Metal Roof Systems in High-Wind Regions
Metal Roof Systems in High-Wind Regions http://www.fema.gov HURRICANE IKE RECOVERY ADVISORY Purpose: To recommend practices for designing and installing metal roof systems that will enhance wind resistance
EAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT
IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT WHAT IS THE RATIONALE BEHIND THE REQUIREMENTS FOR IGNITION RESISTANT CONSTRUCTION? The wildfires of 2003 and 2007 were the largest in California
Roof Inspection and Evaluation
Roof Inspection and Evaluation Sylvester Powell Community Center 6200 Martway Mission, KS 66202 Prepared For: Your name Sample Community Center 6200 Martway Mission, KS 66202 Kansas City, MO 64105 200
Roofing Systems. New Applications / Re-Roofing / Maintenance
Roofing Systems New Applications / Re-Roofing / Maintenance New Roof Installation In terms of the design and installation of an original roofing system (in conjunction with the construction of a new building),
In the Fall 2002 issue of HHE News I examined
Choosing Replacement Windows 1 For Your Home Mark Pierce In the Fall 2002 issue of HHE News I examined reasons for, and against, replacing older windows with new, energy efficient windows. That article
Walls. Add Strength and Water Resistance When Repairing Your. Replace damaged framing members when walls are open
Add Strength and Water Resistance When Repairing Your Walls Any home repair or remodeling work you do presents an opportunity to make your home fare better in the next storm. Whether you are just replacing
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
Maintenance & Inspection Guide
ADDRESSING THE NEEDS OF OUR CUSTOMERS AND THE ENVIRONMENT ONE high Performance roofing SOLUTION AT A TIME. Maintenance & Inspection Guide TABLE OF CONTENTS Topic: Page: I. Introduction 1 II. Maintenance
providing documentation that validates the year of construction. Acceptable documents include
902. WINDSTM MITIGATION FEATURES A. For policies that cover the peril of Windstorm or Hail, a premium credit may be available if one or more of the following loss mitigation features or construction techniques
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
Manufactured Home Inspection Checklist
Where building safety research leads to real-world solutions. Manufactured Home Inspection Checklist Nearly eight percent of the U.S. population lives in a manufactured home, according to the U.S. Census
Approval Standard for Class 1 Exterior Wall Systems
Approval Standard for Class 1 Exterior Wall Systems Class Number 4881 November 2007 2007 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that the
Georgia State University. Urban Life Building Roof Replacement
ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT
Informational Bulletin
Informational Bulletin March 2007 Bulletin #31 *Replaces Informational Bulletin #8 Updated Impact Requirements for Building Components This Bulletin presents a general overview of the current impact requirements
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria
Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
Solutions. New Threats, New Technologies. Learning Objectives HURRICANE-ZONE BUILDING SOLUTIONS ... ... By Barbara Horwitz-Bennett and C.C.
HURRICANE-ZONE BUILDING SOLUTIONS Severe Weather Solutions New Threats, New Technologies Learning Objectives After reading this article, you should be able to: Understand sources and causes of weatherrelated
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its
REPLACE YOUR ROOF TO VISUALLY INSPECT YOUR ROOF REGULARLY SO YOU CAN DISCOVER PROBLEMS WHILE THEY ARE STILL MINOR AND CAN BE REPAIRED.
???????????????????? REPLACE YOUR ROOF ???????????????????? REPLACE YOUR ROOF YOUR ROOF PROTECTS YOUR HOME FROM THE SUN, WIND AND RAIN. AGE, WEATHER AND THE SUBTROPICAL FLORIDA CLIMATE CAN TAKE THEIR TOLL
May 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client,
PROPERTY INSPECTION PROFESSIONALS May 5, 2010 Client Client Address Re: Inspection Address, Chicago, Illinois Dear Mr. Client, On May 4, 2010, Tomacor completed a property inspection of the above referenced
Severe Windstorm Checklist
Severe Windstorm Checklist For locations exposed to hurricanes, cyclones, typhoons or severe localized winds Studies of severe windstorms show conclusively that windstorm-related damage can be prevented
FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS
FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS Table of Contents Chapter 1: FLAT ROOF REPAIR - CUT COST WITHOUT CUTTING CORNERS Chapter 2: PVC RECOVER SYSTEM HOW IT WORKS Chapter 3: 8 STRATEGIES TO
Vision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION
IF SUBSIDIARY, PROVIDE MASTER PERMIT NUMBER HERE: CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION Location of Improvements
CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building
Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Prepared For: Ms Marilyn Bittenbender Colliers International 805 New Hampshire St Lawrence Kansas, 66046 Prepared
What makes DECRA Roofing Systems unique?
Commercial Roofing As the pioneer of stone coated steel technology, Roofing Systems have been proven around the world since 1957. Marketed and installed in over 120 countries, there are over 1 million
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
Before You Start an Energy Efficiency Retrofit The Building Envelope
ABOUT YOUR HOUSE Before You Start an Energy Efficiency Retrofit The Building Envelope The building envelope is the outer layer of the building that separates the indoor living space from the outdoor environment,
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Safeguarding our clients interests. Active Roof Leaks
Safeguarding our clients interests. Active Roof Leaks Vendor Requirements Visually inspect the roof for any damages Exterior inspection of the roof and gutters Interior ceiling inspection Interior attic
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
THIS GUIDE WAS PREPARED BY THE CYCLONE TESTING STATION WITH SUPPORT FROM NORTHERN TERRITORY, QUEENSLAND AND WESTERN AUSTRALIAN GOVERNMENTS
CYCLONES. IS YOUR HOUSE READY? A Homeowner s Guiide THIS GUIDE WAS PREPARED BY THE CYCLONE TESTING STATION WITH SUPPORT FROM NORTHERN TERRITORY, QUEENSLAND AND WESTERN AUSTRALIAN GOVERNMENTS 1.. INTRODUCTION
TABLE OF CONTENTS" SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE 7"
2 TABLE OF CONTENTS SECTION 1: What is a Standing Seam Metal Roof PAGE 3 SECTION 2: Common Types of Standing Seam Metal Roofs..PAGE 5 SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE
+1.877.497.3528 [email protected] www.grscanadainc.com
WORK ORDER AGREEMENT I. Work Site Documentation Quotation / Bid # Core Samples / Infrared Purchase Order # Consultant Report Start Date: II. Work Site Address Building Name Street City Province Postal
Page & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
Maintenance Matters. Window and Door Replacement
Number 13 Maintenance Matters building maintenance bulletin Window and Door Replacement As part of the ongoing maintenance of your home or multi-unit residential building, windows and doors will eventually
Architectural Inspection Site Structures
0141 Freestanding Shelters Open air shelters not attached to the building. Bike rack shelter with bike racks: This 8'x30' structure is located on the north east side of the building on the wooded landscape
2008 Florida Residential Wind Loss Mitigation Study
Florida Office of Insurance Regulation Contract Number IR18 October 28 28 Florida Residential Wind Loss Mitigation Study Prepared for: Florida Office of Insurance Regulation 2 E. Gaines Street, Larson
Roof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
CITIZENS PROPERTY INSURANCE CORPORATION BUILDING TYPE II AND III MITIGATION VERIFICATION AFFIDAVIT
CITIZENS PROPERTY INSURANCE CORPORATION BUILING TYPE II AN III MITIGATION VERIFICATION AFFIAVIT This affidavit must be completed to capture mitigation features applicable to a Type II (4 to 6 story) or
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
Shingle Roofing: What s below the surface is important
What s below the surface is important The roof is leaking, the shingles look old, and the downspouts are dripping. It must be time to replace the roof or is it? Shingle roofs may seem simple, but a roof
bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls
A bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls CE 28 h Exterior finish materials are expected to protect the house from the elements while providing an attractive appearance.
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
contractors, etc. and establish relationships with lease and rental companies.
The following may serve as a checklist when preparing for a Tropical Storm or Hurricane. Although Tornadoes usually provide little advance warning, locations subject to Tornadoes may apply much of the