DATA CENTER & COOLING SOLUTIONS

Size: px
Start display at page:

Download "DATA CENTER & COOLING SOLUTIONS"

Transcription

1 DATA CENTER & COOLING SOLUTIONS 2012

2 Typical Energy Consumption of a Data Center Infrastructure 19 Racks Cooling units Cooling %50 Fire protection IT components %35 Raised floor Power Power Distribution 15%

3 DRIVING FACTORS FOR THE NEED OF EFFICIENT COOLING Increasing energy prices Increasing capacity and cooling requirement of blade servers and pizza boxes Rising number of servers Increasing datacenter performance Regulatory requirements Power density is increasing 15% per year By 2011 average kw per rack is above 15kW (up from 1kW in year 2000)

4 Cooling Requirement for some Servers!

5 CHALLENGE IN % 18% 18% 2% 13% 13% 6% 2< kw 2-4kW 4-8kW 8-12kW 12-16kW 20-24kW 24> kw From 1kw (2000) to avg. 15kw (2011) per rack!!

6 Cooling Alternatives

7 Cooling Alternatives *Traditional Perimeter Cooling Thermal load per rack up 5 Kw -Raised floor -Chiller, Closed Control Unit *Innovative Aisle Containment Application Thermal load per rack up 10 kw - Raised floor - Isolation - Chiller, Closed Control Unit

8 Cooling Alternatives *Combination of in row liquid cooling system Front Cooler + Cold corridor -Eliminates Raised floor *Side Cooler: Liquid cooling systems for thermal load up to 30 kw -Side mountable to racks, enables high density cooling

9 Air flow in traditional Systems If the distance from CRAC increases, pressure of air decreases Hot and cold air mixes with each other Non-uniform (uneven) distribution of Cold Air, top of the rack is not sufficiently cooled RESULT!! % 75 of all server failures happens at the 1/3 top section of the racks

10 EFFECT OF DENSE CABELING BELOW RAISED FLOOR

11 PROBLEMS OF TRADITIONAL APPROACH Low return temperature C Short circuit of hot air Small Delta T, high air flow Hot spots C Hot spots CRAC Warm air > 30 C CW temperature C Loss of cold air C Low supply temperature C High Presssure&velocity Balancing required

12 FACTORS TO BE CONSIDERED IN EFFICIENT COOLING Do not move more air than required! Focus on hot spots Do not cool the whole datacenter, just cool the servers only! Maintain strict cold and hot air seperation Obtain a uniform and more controllable closed cooling area Keep the cold air temperature between C instead of C Do not waste energy to cool the hot aisle Use energy efficient alternatives like free cooling

13 SOLUTION: COLD AISLE! High return temperature C Cold Aisle C High Delta T, small air flow CRAC Uniform temp. Uniform temp. Warm air < 28 C CW temperature C C Higher supply temperature C Low velocity&pressure No need for balancing!

14 Loss Of Cold Air COLD AISLE SOLUTION Hot Air Short-Circuits Raised Floor Raised Floor *Newest technology in data center design Cost effective and high capacity cooling up to 10 kw per rack Eliminates the need for raised floor balancing Eliminates hot spots and waste of cold air Easy to operate Min investment, high ROI Energy savings up to 50% Fully scalable, from small to large deployments

15 COLD AISLE SOLUTION Optimized for energy efficiency Cooling capacity up to 10 kw for each cabinet Modular construction Separation of cold and warm air Reduction of the gradient of temperature

16 COLD AISLE SOLUTION Sliding doors Acrylic glass top cover-modular

17 COLD AISLE SOLUTION

18 IDEAL RACK FOR DATACENTER APPLICATIONS PLATINIUM SERIES RACKS (ALU frame) Unique Technology patented by European Patent office 18

19 Advantages of Aluminum Frame Patented design from European Patent Office and WIP Load capacity up to kg- Industry record! %30weight reduction compared to conventional welded steel cabinets Appropriate for critical applications like seismic cabinets- Zone4 certificated 19

20 Advantages of Aluminum Frame Ease of assembly/disassembly with only 3 screws Diecast type corner joints with self-locking mechanism High corrosion resistance compared to steel based structures Natural cooling characteristics of Aluminum 20

21 19Server Cabinets Aluminum frame chassis Compatible to all major server providers like HP, Dell, Sun, Compaq and IBM Perforated front&rear doors 1. Perforation up to 80% (Free Air Ratio) 2. Unique honeycomb ventilation pattern to increase airflow capacity 3. Emka multipoint point swing handle locks Side panels with cylinderical locks and extra handles to ease assembly 2pairs of heavy duty type 19 mounting rails from galvanized steel protected against corrosion Top cover with 3 holes for cable entry and a fan unit fixing hole Support rails on the sides of the frame to increase stability and for efficient cable management 2 pairs of adjustable feets 21

22 Features Aluminum Frame Honeycomb ventilation pattern Up to %80 Free Air Ratio EMKA Multipoint Swinghandle lock Bottom cover with 3 holes for cable entry Single Perforated Rear Door

23 19Network Cabinets Aluminum frame chassis Glass front door Tempered glass for security purposes Unique serigraphie cover (tinted) on the left and right sides of glass to hide the cables from the view Emka single point swinghandle locks Side and rear panels with cylinderical locks 2pairs of 19 mounting rails from galvanized steel protected against corrosion Top cover with 3 holes for cable entry and a fan unit fixing hole Support rails on the sides of the frame to increase stability and for efficient cable management 2pairs of adjustable feet

24 COLD AISLE CONTAINMENT IMPLEMENTATION Water Chiller *Liquid based chiller (closed control unit) cooling on raised floor Free-Cooling opportunity during winter times, huge energy saving (Green IT!)- below 10C outside temperature, 100% free cooling, up to 50% energy saving is possible *Compact datacenter design

25 FRONT COOLER In row technology No raised floor needed Width of 300 mm or 600 mm Height 2000 mm / depth 1000 mm 30kW or 60 kw cooling capacity Pressure controlled EC-technology No condensing water due to high inlet water temperature of 14 C Water and DX-Version Extra developed for Corridorcooling High efficient power management

26 Hot swap

27 FRONT COOLER

28 COLD AISLE CONTAINMENT + Liquid Based Front Cooler ( In row Cooler ) 2 Options: a) 300mm width: range kw b) 600mm width: range Kw c) Runs with 5 EC-fans

29 Control SW - TEMPTRONIC RJ 45 interfaceoptional serial interface RS 485 possible. Interface can communicate with following protocols - OPC Server - Modbus - LON - ECHELON - BACnet - Third Party Protocols - SNMP - METASYS - DLL

30 COLD AISLE CONTAINMENT + Liquid Based Front Cooler (Inrow Cooler) Water Chiller Front Coolers No need for Raised Floor!! Ambient air is extracted from the warm aisle through the perforated rear door, cooled and blown into the cold corridor

31 COLD AISLE CONTAINMENT + Liquid Based Front Cooler (In row Cooler) COLD CORRIDOR + FRONT (IN ROW COOLING)) C C Warm air <25 C Uniform temp. Uniform temp. Warm air <25 C C C No need for raised floor!

32 Hot Aisle with FrontCooler

33 Cold Aisle with FrontCooler

34 Hot Aisle with FrontCooler

35 DIRECT LIQUID BASED RACK COOLING SIDECOOLER *High density hot spot cooling up to 30kW *Patented modular and ergonomic design

36 Functionality of the SideCooler

37 Direct rackcooling / key features SideCooler Reliable against failures Redundant No condensing water Saving space because of case shape Simple construction with only a few mechanical components Energy efficient fans High energy efficient level cause of using high water inlet temperatures More than 1000 installations worldwide

38 Advantages of SideCooler Automatic regulation of the cooling capacity 0-30 kw Cooling capacity up to 30 kw Space reduction because of the trademarked Slide In design. Failsafe with emergency running at fail of the controlling Hot-plug fans Working with BacNet, Modbus, RS 485, RJ 45 uva. Variants : H= 1800, 2000, 2200 mm T= 800, 900, 1000, 1200 mm Available for all fabricates of cabinets / racks Integrated monitoring system Also working with water/glycol

39 All-in-one Compact Datacenter

40 All-in-one Compact Datacenter Cabinet Side Cooling System Modular UPS IP PDU 1U Fire Extinguisher System with Novee 1230

41 Competitor Analysis Front Cooler 60KW Front Cooler 30 KW DX ACRC502 ACRC103 ACRD 502 APC Inr0w APC Inr0w APC RC RC Inr0w CC Stulz Schäfer Emerson Knürr CoolLoop Rittal LCP Inline Cooling Capacity for Watertemp. 14/20 60kW 30kW 37kW 11kW 29kW 25kW 24kW 30kW Power Comsumption 980W 790W 3300W 1100W kw Energy saving due to high inlet water temperature compared APC Condenswater by nominal cooling capacity 915W 1230W 1800/250 0W 21% 21% no no no no no 21% no no yes yes yes yes yes no InRack Cooling no yes no no yes yes yes yes

42 Energy effiency of the SideCooler Condensing water free cooling up to 24 kw with water temperature 14 C No wasting of energy for latent Cooling With warm water 18 C still 19 kw cooling capacity Maximum consumption of energy per SideCooler is <= 500 W FreeCooling up to 90% p.a.

43 Examples of placings of Side Cooler left / right placing redundant placing part redundant placing space saving placing space saving placing with part redundancy 43

44 Flexible Installation Easy installation No raised floor required No device outside the building required

45 Green-IT-Cooling /PUE Leistungsaufnahme Standard RZ Leistungsaufnahme sauber geplanter RZ Electrical Transformer UPS 11% Lightning etc. 2% PUE = 2,5 Standard Datacenter installed Electrical Transformer UPS 10% Lightning etc. 3% Air Movement 14% IT Equipment 40% Air Movement 12% Cooling 33% PUE=150/60=2,5 PUE = 2,0 new standard datacenter with Cold Aisle Containment Cooling 25% IT Equipment 50% PUE=120/60= 2 PUE = Power Usage Effectivness = total energy consumption / IT- Equipment Electrical Transformer UPS 7% Air Movement 2% Cooling 16% Lightning etc. 2% PUE = 1,39 Cold Aisle Containment with Front Cooler or SideCooler by using FreeCooling PUE 1,39 = 83/60= Electrical Transformer UPS 5% Air Movement 4% Cooling 2% Lightning etc. 3% PUE=70/60= 1,17 IT Equipment 73% PUE = 1,17 SideCooler with Geothermic cooling IT Equipment 86%

46 Comparison PUE of different Free Cooling solutions Datacenter with 500 kw IT-load FreeCooling No No Indirect Indirect Indirect Indirect Geothermic FreeCooling 100% 2 = < C 2 = < C 13 = < C 15 = < C technic CRAC standard CRAC new technologie CRAC Cold Aisle CRAC Cold Aisle FC SideCooler SideCooler % kw % kw % kw % kw % kw % kw % kw IT Equipment 59,9% ,3% ,2% ,3% ,1% ,5% ,3% 500 Cooling 24,0% ,7% ,5% ,8% ,2% ,7% 80 4,5% 26 Air Movement 9,6% 80 5,9% 45 6,0% 45 4,3% 30 3,8% 25 2,7% 17 3,5% 20 USV 6,0% 50 6,5% 50 6,6% 50 4,3% 30 4,6% 30 4,8% 30 4,4% 25 Lightning etc. 0,6% 5 0,7% 5 0,7% 5 0,3% 2 0,3% 2 0,3% 2 0,3% 2 energie costs Klima :) ( ( cent / kwh) 100% % % % % % % 573 PUE: 1,67 1,53 1,51 1,38 1,31 1,26 1,15 Energie costs % 289% 218% 206% 165% 129% 100% 47%

47 FREE COOLING Free-Cooling opportunity during winter times, huge energy saving (Green IT!!) - Below 10C outside temperature 100% free cooling - Up to 50% energy saving is possible - Applications from 80kW up to 2000 kw

48 Free Cooling Potential Solution Averageambient temperatures of Nürnberg region- Germany APC ambient temp. 20 = > C 19 C 18 C 17 C 16 C 15 C 14 C 13 C 12 C 11 C 10 C 9 C 8 C 7 C 6 C 5 C 4 C 3 C 2 C 1 C 0 C " 5-"= < hours per year cumulatet hours in % 100% 95% 92% 89% 85% 81% 77% 72% 68% 63% 60% 55% 51% 47% 43% 39% 34% 30% 25% 21% 17% 13% 10% 8% 6% 5% 25%Konventionell indirect freecooling 70%Indirect Free Cooling Best Practise 95%Optimized Direct Free Cooling 90days/year more freecooling than the competition!

49 SPACE COMPARISON BASED ON 60kW Traditional Perimeter Cooling 5kW 5kW 5kW 5kW 5kW 5kW 5kW 5kW 5kW 5kW 5kW 5kW Cold Corridor 10kW 10kW 10kW 10 kw 10kW 30kW 30kW 10kW Side Cooler-Liquid Cooling %300space reduction %50space reduction Benefits: Less space required Less rent expense Less HW requirement (cable, rack, raised floor etc)

50 FreeCooler as retrofit solution Saving of energy To place outside the building Silent version Retrofit version In addition useable as redundancy The whole system has to check for energy savings

51 Coolmanager / Pumping stations Integration of SideCooler or FrontCoolers in an existing infrastructure of waterchillers Save separation of primary and secondary water circuit Redundant pumping station Regulation of water inlet temperatures Regulation of condensing freeness

52 Using the geothermal cooling for the direct rack cooling Space -Checking the location of the drilling based on a geothermal map + permit of the public government 240 -m drilling in flushing drilling method ( 3 x drilling each a 80 mtr. depth / diameter per drilling 140 mm ) -Piping work 3 x 80 mtr. HDPE pipes 32( x 2,9 mm) = 3 double sondes - Covering with clay farina cement suspension -System stability with design with a double circulation pump N+1 (redundant) +UPS - buffered

53 Mode of operation : The SideCooler require an inlet temperature of 14 C, to avoid condensate during operation. In the soil (app. 90 meter. deep) a constant temperature of 11 C exists. The glycol-water returns with app. 11 C from the underground pipe. The supply temperature to the Sidecooler of 14 C is controlled by the three-way- valve. In the SideCooler the water-glycol will gain a temperature of app. 19 C. The closed cycle transfers the heat of the IT equipment to the ground.

54 Geothermal cooling

55 Geothermal cooling Execution the drillings

56 Comparison of energy costs Supply of a cooling capacity 68 kw A) Power consumption with usual mechanical cooling system (water chiller) B) Power consumption with geothermal system A) Energy consumption ca. equates p.a. ca. B) Energy consumption ca. equates p.a. 23,0kW kW/h 1,5kW ca kW/h EUR ,00 EUR 1.971,00 energy savings p.a. kw/h x 0,15 pro kw/h saving costs +carbon emission basis on energy mix = 514 gr./kwh p.a. ca ca. EUR -, ca kg.

57 Comparison costs of invest A) Invest costs water chillers (2 pieces cause redundancy) EUR -, B) Invest costs geothermal systems EUR -, Yearly saving energy costs with geothermal system EUR -, ROI (Return of Investment) 18 months!

58 Direct Free Cooling No transfer medium like water or any agent Uses air temperature up to 22 C Environment friendly Freecooling potential up to 90%

59 Direct Free Cooling

60 solar cooling systems Solar cooling systems

61 solar cooling systems Solar cooling systems The sun collectors are equipped with vacuum tubes. The heat is getting collected to a hot water buffertank. The hot water is getting pumped to the absorber cooling machine where through a chemical reaction the warmness would be changed to cooling (near without mechanical power, only a pump.) The cold water can be used for air cooling systems (closed control unit or direct rack cooling systems.)

62 solar cooling systems Solar cooling systems

63 Solar cooling systems

64 INSIDE WATER CHILLERS Advantages for placing a water chiller inside: No need for anti freezing medium (glycol) Movable and flexible instead of a fixed placed water chiller outside.

65 OUTSIDE WATER CHILLERS Advantages for placing a water chiller outside: if there is no place to put water chiller inside-space limitations if there is long distance between side & front cooler and the chiller unit

66 CLOSED CONTROL UNITS (CCU) Pressurized liquid based cooling, for cold corridor applications

67 Example of Datacenter Installation

68 Micro Datacenter with Top-mountable AC Benefits: Cooling up to 4kw with top mountable AC unit Eleminates external cooling unit and raised floor Compact datacenter with Monitoring, UPS, IP PDU, Cooling Ideal solution for branch offices (Banks, Police, Schools, Ministries etc)

69 Micro Datacenter with Door-mountable AC

70 Complete Solution for Data Centers 19 Racks: Aluminum frame based high quality server racks with carrying capacity of 2000kg and perforation of 80% Air flow ratio Cooling solutions: a.cold corridor application based on modular aluminum frame structure- newest and latest trend in data centers b. Liquid cooling system up to 30KW, AC units - c. Security Systems: Electronic locks Monitoring Systems: Rack monitoring systems Power Systems: Rack mount and modular UPS Systems Power distribution Units: - IP controlled smart PDU s - All types of modular customized PDU s 70

71 IP PDU s with POPS Feature Per Outlet Power Sensing and Control Integrated temperature and humidity sensors Wireless sensor connectivity -up to 9 sensors Industry leading accuracy level: 97% accuracy in measuring Camera connection capability 71

72 RACK MONITORING AND CONTROL SYSTEM Designed to monitor the working environment and control access to eletronic equipment in racks and data center applications. Technical Specifications TCP/IP, RS232 and RS485 connection 10/100 Base Ethernet 8 different sensor connection- wireless!!.temperature.humidity.motion.smoke.non-contact access.proxy card reader Electromagnetic Lock Optional Fan Controller

73 Waterless Fire Suppression Systems FM-200 Fire Suppression Systems Reach extinguishing levels in 10 seconds or less Less damage Lower repair costs Less downtime and disruption of business. FM-200 is in use in over one hundred thousand applications, in more than 70 nations.

74 1U Inrack fire Extinguisher with Novec 1230 The 1U active extinguishing system is acompact, independent unit for detecting and extinguishing fires in closed cabinet systems. Fire extinguisher agent Novec 1230 Used inside racks Only 1U sytem in the world Less downtime and disruption of business.

75 Security Lock System. Ideal solution for Colocation centers of ISP s Remote management up to 300 locks Numerical&smart card access

76 Efficient, Modular UPS UPS SOLUTION

77 UPS Flexibility Compact - more power in less space 25 kw modules occupy of standard rack space, Combine modules in building block fashion to deliver 250 kw of redundant backup power in one rack enclosure Scalable - easily deploy and expand Flexible numerous configurations The solution can grow with expanding IT needs offers a fully redundant architecture, as opposed to simply adding power modules to increase capacity

78 UPS Efficiency Efficiency - Reduce cooling costs Unparalleled efficiency results in cooler operating conditions and less heat dissipation Overall air conditioning requirements reduce by more than one third UPS can be located close to equipment racks without creating hot spots Efficiency - Reduce energy costs delivers an industry-leading 97% efficiency UPS will quickly pay for itself through energy and cooling savings alone On average, a user will save more than 24,000 over a five-year period, coupled with increased reliability and performance on a 60 kw N+1 configuration

79 Highest efficiency in modular three-phase UPS design industry leading >96 %efficiency even at loads below 40% of capacity.

80

81 THANK YOU FOR YOUR ATTENTION QUESTIONS? 81

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

How To Build A T7 Rack For Information Technology

How To Build A T7 Rack For Information Technology THE NEXT GENERATION RACK FOR INFORMATION TECHNOLOGY THE RACK CABINET FOR INFORMATION TECHNOLOGY T7, THE HI-TECH HEART OF THE BLADESHELTER SYSTEM The real answer to the requirements of: Safety Versatility

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

White Paper Rack climate control in data centres

White Paper Rack climate control in data centres White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC

More information

Blade Server & Data Room Cooling Specialists

Blade Server & Data Room Cooling Specialists SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

CoolTeg Plus Chilled Water (CW) version: AC-TCW

CoolTeg Plus Chilled Water (CW) version: AC-TCW version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

RiMatrix S Make easy.

RiMatrix S Make easy. RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power

More information

EHDC. Cooling system for Data Center and server cabinets.

EHDC. Cooling system for Data Center and server cabinets. EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Knürr Miracel. Knürr Miracel. 19 Network and Server Rack Platform 1.12 to 1.22 1.11

Knürr Miracel. Knürr Miracel. 19 Network and Server Rack Platform 1.12 to 1.22 1.11 Knürr Miracel 19 Network and Server Rack Platform 1.12 to 1.22 1.11 19" Server Rack: Knürr Miracel Strong points 1.13 Knürr Miracel ASP ASP/Server Rack 1.16 Knürr Miracel Server Rack 1.18 Knürr Miracel

More information

Rittal Liquid Cooling Series

Rittal Liquid Cooling Series Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

Technical Systems. Helen Bedford

Technical Systems. Helen Bedford Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

DIGITUS Network & Server Cabinets. UNIQUE Series

DIGITUS Network & Server Cabinets. UNIQUE Series DIGITUS Network & Server Cabinets UNIQUE Series Benefits - Server Rack 4-Point locking system front door 3-point locking system rear door Swing handle lock with profile zylinder in front and rear door

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE ENVIRONMENTAL MONITORING

MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE ENVIRONMENTAL MONITORING MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE Chris C. Gaskins Vice President of Product Development RF Code, Inc. AUGUST 2010 Shawn Griggs Director of Product Management

More information

Knürr DCL Modular Rack Cooling from 6 kw to 60 kw

Knürr DCL Modular Rack Cooling from 6 kw to 60 kw Knürr DCL Modular Rack Cooling from 6 kw to 60 kw Emerson Network Power Business-Critical Continuity so your success continues! Core competencies AC Power Connectivity DC Power Embedded Computing Embedded

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

Data Sheet FUJITSU PRIMECENTER M2 19-inch Racks

Data Sheet FUJITSU PRIMECENTER M2 19-inch Racks Data Sheet FUJITSU PRIMECENTER M2 19-inch Racks Data Sheet FUJITSU PRIMECENTER M2 19-inch Racks 19-inch Industry Standard Rack Systems The trend to consolidation as a result of virtualization and optimization

More information

SERVER ROOM CABINET INSTALLATION CONCEPTS

SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS ZPAS 169 EXAMPLES OF SERVER ROOMS PROJECTS WITH ZPAS CABINETS Data Box in the

More information

IPSIP M series-m Modular Data Center

IPSIP M series-m Modular Data Center IPSIP M series-m Modular Data Center IPSIP MODULAR TECHNOLOGIES. 1 With the rapid development of cloud computing and mobile Internet businesses, the growth of IT density and energy consumption are bringing

More information

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Containment Solutions

Containment Solutions Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION 1/16 Contents: 1. Introduction: the increasing importance of energy efficiency 1.1 Power consumers in the data

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com sales@42u.com Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

(Examples of various colocation sites)

(Examples of various colocation sites) Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

STULZ Water-Side Economizer Solutions

STULZ Water-Side Economizer Solutions STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

INFRASTRUCTURE FOR DATACENTERS

INFRASTRUCTURE FOR DATACENTERS INFRASTRUCTURE FOR DATACENTERS 02 ENERGY EFFICIENCY IN DATACENTERS The energy efficiency is one of the biggest challenges that datacenter infrastructures are facing today. The datacenters need to have

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

Cabcon. Data Centre Solutions. www.cabcon.co.uk. an acal group company UK +44 (0)1189 122980 IRE (00353) 1 629 2640

Cabcon. Data Centre Solutions. www.cabcon.co.uk. an acal group company UK +44 (0)1189 122980 IRE (00353) 1 629 2640 Data Centre Solutions www.cabcon.co.uk UK +44 (0)1189 122980 IRE (00353) 1 629 2640 About Us are a specialist distributor of copper, fibre, power, security, active and cable management products for the

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power

More information

Secure your IT equipment with confidence... secure with NetClosure

Secure your IT equipment with confidence... secure with NetClosure Secure your IT equipment with confidence... secure with NetClosure SERVER CABINETS NetClosure s REM Series Server Cabinet is the ultimate solution designed and engineered for demanding data center environments.

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

News in Data Center Cooling

News in Data Center Cooling News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase

More information

JAWAHARLAL NEHRU UNIVERSITY

JAWAHARLAL NEHRU UNIVERSITY School of Biotechnology JAWAHARLAL NEHRU UNIVERSITY New Delhi 110 067 Tender No. JNU/SBT/DBT-BUILDER/Data Centre/2015-16 Sealed Quotation for the establishment of a Data Centre for High-End Computational

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

Modular Access Floor for Data Center. From Rack to Row to Room to Building

Modular Access Floor for Data Center. From Rack to Row to Room to Building Modular Access Floor for Data Center From Rack to Row to Room to Building Why using Scneider Electric modular access floor in Data Centers The evolution of modern Data Centers emphasizes specific exigencies

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

Customized Server Cabinets

Customized Server Cabinets GOING GREEN WITH CUSTOMIZABLE CABINETS AND RACKS Designed to provide industry leading airflow, CyrusOne s cabinets and rack solutions promote optimal cooling and contribute to reduced power consumption.

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

NAISSUS THERMAL MANAGEMENT SOLUTIONS

NAISSUS THERMAL MANAGEMENT SOLUTIONS NAISSUS THERMAL MANAGEMENT SOLUTIONS HIGH PERFORMANCE CLOSED LOOP WATER COOLING SYSTEM NTMS30 30kW SYSTEM Cool the servers, not the room! NAISSUS THERMAL MANAGEMENT SOLUTIONS HIGH PERFORMANCE CLOSED LOOP

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational

More information

Access Server Rack Cabinet Compatibility Guide

Access Server Rack Cabinet Compatibility Guide Access Server Rack Cabinet Compatibility Guide A Guide to the Selection and Evaluation of Access Server Rack Cabinets for Compatibility and Use with Third Party Server Chassis Kalkenstraat 91-93 B-8800

More information

Improve competiveness of IDC and enterprise data centers with DCIM

Improve competiveness of IDC and enterprise data centers with DCIM Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM

More information

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale

More information

HVAC Infrastructure Retrofit Solutions

HVAC Infrastructure Retrofit Solutions Kyoto Cooling Lunch & Learn David Belleville, APA LLC March 9, 2015 Owners choose APA solutions to: Rely on our 30+ years of delivering engineered solutions; HVAC Infrastructure Retrofit Solutions Insure

More information

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing

More information

Technical specifications. Containerized data centre NTR CDC 40f+

Technical specifications. Containerized data centre NTR CDC 40f+ Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION

More information

Visions become real. Temperature control and cooling systems. The innovative and reliable solution

Visions become real. Temperature control and cooling systems. The innovative and reliable solution Temperature control and cooling systems The innovative and reliable solution With our PulseTemp equipment you have the option of up to 72 cooling circuits in the impulse cooling, temperature control, temperature

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment The Intelligent Data Center Cooling Solution: Liebert CRV Trust the industry leader in Precision Cooling to deliver

More information

Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package

Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package Munther Salim, Ph.D. Yury Lui, PE, CEM, LEED AP eyp mission critical facilities, 200 west adams street, suite 2750, Chicago, il 60606

More information

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Energy Efficiency Best Practice Guide Data Centre and IT Facilities 2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Energy Performance Optimization of Server Room HVAC System

Energy Performance Optimization of Server Room HVAC System International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Standardised Data centres. Sales presentation

Standardised Data centres. Sales presentation Standardised Data centres 1 Standardised Data Centres l Motivation ll Change of paradigm lll Rittal s Data centre concept lv Benefits V Summary Standardised Data Centre Motivation Does every data centre

More information

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels

More information

imagine SOLAR AIR CONDITIONING MADE EASY

imagine SOLAR AIR CONDITIONING MADE EASY imagine SOLAR AIR CONDITIONING MADE EASY WHY SOLAR COOLING? Imagine...being able to fit a solar air conditioning system to your building that would result in dramatic reductions in electricity consumption

More information

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures

More information

Eaton 93PM UPS Where aesthetics meet intelligence.

Eaton 93PM UPS Where aesthetics meet intelligence. Brochure 100 kw Eaton 93PM UPS Where aesthetics meet intelligence. 93PM features and benefits The Eaton 93PM UPS combines unprecedented and reliability with eye-catching design. A space-saving, flexible

More information

Modular Datacenter based in a 20' container

Modular Datacenter based in a 20' container Modular Datacenter based in a 20' container RETEX, S.A. Avda Tecnología, 35. 08840 VILADECANS (Barcelona), SPAIN. T. +34 932 649 850 F. +34 936 592 368 info@retex.es www.retex.es INDEX 1. THE DATABOX SOLUTION...

More information

DATA CENTER RACK SYSTEMS: KEY CONSIDERATIONS IN TODAY S HIGH-DENSITY ENVIRONMENTS WHITEPAPER

DATA CENTER RACK SYSTEMS: KEY CONSIDERATIONS IN TODAY S HIGH-DENSITY ENVIRONMENTS WHITEPAPER DATA CENTER RACK SYSTEMS: KEY CONSIDERATIONS IN TODAY S HIGH-DENSITY ENVIRONMENTS WHITEPAPER EXECUTIVE SUMMARY Data center racks were once viewed as simple platforms in which to neatly stack equipment.

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2013

European Code of Conduct for Data Centre. Presentation of the Awards 2013 European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started

More information