1 Technical Systems in Data Centres Helen Bedford

2 Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre infrastructure Management (DCIM) Overall Data Centre Modular Data Centre Solution Power: Provision i and Back-Up Fire Detection and Suppression Excellence in Market Intelligence 2

3 Recent Changes to Cooling Requirements Resulted in New Technology Adoption Power Usage Effectiveness is a measure used to understand the energy efficiency of Data Centres IT + DC Power PUE = IT Power At the moment the average PUEinmany Data Centres ranges from , however, the most recent deployments, such as Capgemini Data Centre in Swindon (Merlin) states PUE=1.08 As cooling can account as much as 30% of operating costs, considerations of the type of cooling systems installed can directly impact PUE and operating costs after project deployment. However, traditionally, the main priority in the critical managed facilities was security and stability of operations running with low downtime risk. As IT equipment was more likely to suffer from faults and failures at higher temperatures, the cooling systems in Data Centres in the UK provided temperatures at ~18-20 C, inlet temperature falling sometimes as low as 12 C The new temperature and humidity ranges were relaxed in the latest ASHRAE9.9 guidelines to reflect the technological changes in server equipment able to operate effectively at higher levels At the same time, the back-up options should be implemented to ensure that the data centres stay operational under all conditions, incl. cases of prolonged power cuts and main cooling systems failures (DX is the most common back-up option in the UK). Another consideration is that, if the air temperature is raised to 25 C, then servers will start to aggressively increase air flow to the servers, thus counteracting the energy savings achieved in cooling (through increased fan power consumption by servers). Hot and cold aisle containment is a popular solution, providing a cost effective way to increase energy efficiency by blocking the air streams through installation of air blankets. Hot aisle is more popular in New Data Centre Market applications while cold aisle containment is the most popular option in retrofit. Rising inlet and return temperatures is promoted as an effective way to increase PUE and allow for the direct free cooling method being successfully deployed in certain regions in the UK (mainly in the North). Excellence in Market Intelligence 3 ASHRAE 9.9 Guidelines expanded allowable humidity and temperature corridors for Data Centre Applications Source: HP 2012, ASHRAE 2011, Green Grid ASHRAE 2004 and 2008 Guidelines: Comparison Year Guidelines Recommended Allowable Recommended Allowable Temperature 20 C 25 C 15 C 32 C 18 C 27 C 10 C 35 C Humidity 40 % - 55 % 20 % - 80 % 5.5 C 60 C 20 % - 80 % In 2011, recommended range stayed at 2008 level, with allowable temperatures for A1 class being 15 C 32 C and extended to lower classes to 5 C 45 C; allowable humidity range 8% - 90%

4 Most Popular Cooling Solutions in Data Centres in the UK As a rule of thumb, if the data centre has 50+ racks it is most likely to go down the chilled water route, whereas those with <10 racks tend mostly to use DX condensers to cool the cooling solutions. Thus, DX condensers are more popular for smaller Data Centres, while chillers are mostly suitable for large Data Centres due to their applicability and the levels of costs. DX condensers in smaller Data Centres are installed in double capacity to cater for redundancy. Water Cooling Towers are not commonly used in the Data Centres in the UK, mainly owing to the risk associated with legionella disease. It is estimated that 70% of IT equipment in the UK is now cooled using hot or cold aisle containment, with Hot Aisle Containment being used mainly in the New Build Data Centres market segment. Cold Aisle Containments is a very cost-effective option for brown-field Data Centres. Hot Aisle containment is a less preferable option for shared Data Centre Space. Air and pressure blankets allow for implementation of Aisle containment and are relatively cheap. Excellence in Market Intelligence Most Common Cooling Systems Overview System Type Heat Rejection Mechanical Cooling Equipment Chilled Water Direct Expansion (DX) Source: ASHRAE, 2011 Cooling Tower Chiller (air-cooled) Chiller (watercooled) Condenser CRAC C (DX) Dry Cooler Hot Aisle Containment Courtesy Condensing Unit CRAC (water/ glycol) Self-contained AC unit/ rooftop unit Terminal Equipment CRAH (chilled water) Air handler (DX) Cold Aisle Containment

5 Special Features: Cooling - Overview (1) CRAC (Computer Room Air Conditioning) Still the most common type of cooling system that provides cooling via raised floor or an overhead duct distribution system CRAC units contain a cooling coil, a supply air fan, return air filer; some might also have refrigerant compressors, a humidifier, a reheat coil and a free-cooling coil. Can be combined either with DX condensers or watercooled chillers The cost of CRAC units with fans, centralised ventilation/dehumidification system and separate Direct Expansion (DX) Condensing Units DX systems are ideal for small Data Centres or as a system providing for additional redundancy They perform better in harsh environmental conditions, so are more reliable Normally in the UK they accompany evaporative cooling as a back-up option in case of failure, both in traditional and modular design humidifiers make them one of the most cost effective solutions for a new Data Centre facility Adding Variable Controls and EC Fans will provide the necessary option for energy efficiency; and, alongside other possible measures, such as raising supply and return air, bring additional increase of PUE in a New Data Centre in a cost effective way European players: Emerson, Schneider, GEA Denco, Stulz Not applicable for large Data Centres due to impracticality Require increased level of maintenance due to the multiple pieces of equipment (fans, controls, compressors) Can have high levels of energy consumption Players: Gea Denco, Climaveneta, APC, EdenAir Source: Uniflair Source: Airdale Chillers High efficiency multi scroll with free cooling nibbling at Chillers account for a large portion of the overall cooling system cost in the new Data Centres, especially larger ones the lower end. Above kW screw and turbocor dominate. Adiabatic cooling more relevant to southern Europe, although rolled out in some projects in the UK, It is estimated that total value of chillers sold in the UK mainly in the educational sector data centre market is 9% of the total value of the UK chiller market. This amounts to 14m in Cooling towers. Cost of maintenance of cooling towers is reported to be too high and puts a lot of organisations The trend in the market is that free cooling is being made available in smaller machinery. You need to have off installing the equipment, as well as the old chestnut of legionella disease the right water temperature in order to make free cooling a viable option Main leaders: Airdale, Liebert Hiross, Climaveneta and Uniflair. Excellence in Market Intelligence 5

6 Special Features: Cooling Overview (2) Evaporative (or Adiabatic) Cooling Not a very new method but is gaining popularity Utilises evaporation method as a means of cooling down the air or water temperatures Can be direct and indirect be increased if water is sprayed directly into the air stream going into the Data Centre There are some concerns over the applicability and reliability of evaporative cooling in wider range of temperatures in the UK and potential concerns The application of evaporative cooling can have over legionella ll disease geographic limitations in the UK (especially in the Need for maintenance every 24 hours with double coastal areas with increased levels of humidity) units The humidity of the air inside the data centre could Water consumption can be high and expensive Direct Free Cooling provides for wider range of allowable Allows to capitalise the new ASHRAE temperatures and humidity temperatures guidelines If the temperature goes above 18 C, then DX CAPEX costs reduced compared to indirect condenser will work to bring the temperature cooling down. Lower energy consumption Believed to be acceptable in London due to Direct Free Cooling is allowing ambient air to enter climate, the room with heat exchangers folded away and Close Coupled (In-Rack and In-Row) Open-Loop solutions bringing the heat transfer closer to the equipment rack and not completely independent of the room and interacting with the air. Main types: In-Row, in-line air conditioners, Rear Door Heat Exchangers (fairly popular in the UK), Overhead Heat Exchangers (more rarely applied) Liquid Cooling Rather innovative and requires complete change of mind-set to be adopted, especially from the risk adverse IT managers; thus, highly unlikely to gain much traction in the near 3-5 years Mainly refers to submersion into the liquid gas Novec1230 Source: Stulz Closed-Loop solutions is mainly In-Rack solution that are independent of the air stream in the room. AC is applied to server rack and completely sealed. Allows for the direct cooling of servers and not the whole room Provides for scalability and modularity Players: Rittal, APC, Emerson, Hitachi Source: Hitachi (In-Row), USystems Marginal deployment in the UK, undergoing some trials and minor installations in the academic sector More likely to be accepted as a norm on a micro (semiconductor) level, if successfully developed and deployed There are also other types of liquid possible: either Delivers higher cooling capability and lowers PUE directly into water or mineral oil Source: Iceotope Excellence in Market Intelligence 6

7 Other Technical Systems in Data Centres in the UK Helen Bedford

8 Other Technical Systems: Total Market The estimated total value of M&E systems for New Data Centres in the UK (excluding DCIM applications) is around 105 million Estimated Market Size for M&E Systems in New Data Centres in the UK (addressable market) The efficiency of power systems is very BMS Security high and unlikely to be changed in a way Fire that dramatically affects the industry as whole. Introduction of generators feeding into the grid, as well as heat recovery could increase the potential spending on M&E 27 systems in the Data Centre segment, however, overall it is expected to remain at the fairly conservative level of growth of around 3-4%. A marginal dip could be expected in 2013 due to delay of some projects further into Fire Detection is estimated to be worth around 1.7millionwiththefiresuppression to be nearly twice of thatt at 3.33 million Fire Suppression is likely to remain a cost saving option and unlikely to grow dramatically in value. Cooling 65 Power Power Segment represents the majority of value due to the large expense of generators, transformers and other power provision in the Data Centres to cope with the increased IT load requirements Cooling is another big segment estimated to be around 27 million in 2012 for the New Data Centres in the UK BMS sector might receive further expansion to incorporate energy efficiency monitoring and integration with DCIM systems. Excellence in Market Intelligence

9 Major Categories of Gas Fire Suppression in the Data Centres in the UK Heat Absorption Inert Gas Agent Oxygen Hypoxic Atmosphere Du Pont FM-200 is the most common Argonite (Chubb) is electrically non- This type of fire suppression has Fire Suppression System application. The main characteristics behind its popularity are: conductive and is similar to air in density. Main disadvantages: increased in usage in recent years, especially becoming more popular in modular Data Centres. It is relatively cheap to install and Relatively slow flame extinguishing It is based on the notion of providing carries a moderate recharge cost Widely available, however, even in period of supply shortage, sales were not greatly affected end users were not driven away. In contract, Novec1230 has a far longer shelf life, up to 30 years, but could not compete on a larger scale with FM-200, as it is more expensive to buy and recharge, and it is more complicated in handling and transportation. In a longer term, it might be the preferable option. High pressure storage Large volume of gas required, limiting space in the Technical Area Inergen releases the gas under high pressure adjusting the atmosphere, so that fire cannot longer survive. Main disadvantages: Cannot be modular in design High pressure method requires excessive storage, in addition to long and complicated high-pressure pipework oxygen below the level required for fire ignition but at the level safe for the staff operating at the Data Centre. The typical solution falling under the category of Oxygen removal is DeOx by DigiPlex. It is achieved by reducing the level of oxygen to 155 beyond the required 16.2% for fire to sustain itself. The low level e of oxygen still allows staff to carry out essential maintenance work, if needed, and is equivalent to the oxygen conditions in high mountain areas. Water mist and other types of fire suppression are less commonly used in the UK in comparison to the US, where water mist is highly utilised. However, some colos are using this method as well (Digital Realty) Excellence in Market Intelligence 9

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

Webinar: Precision Cooling in Data Centres and other applications 24 June 2014

Webinar: Precision Cooling in Data Centres and other applications 24 June 2014 Webinar: Precision Cooling in Data Centres and other applications 24 June 2014 Jeremy Towler - Senior Manager Energy & Smart Technologies David Garwood Researcher Air-conditioning solutions Helen Bedford

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

White Paper: Free Cooling and the Efficiency of your Data Centre

White Paper: Free Cooling and the Efficiency of your Data Centre AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...

More information

EXAMPLE OF A DATA CENTRE BUILD

EXAMPLE OF A DATA CENTRE BUILD EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 4, Lancaster University, 2 nd July 2014 Background Data centres estimated to use 2-3% of total electricity consumption in the UK and generate

More information

AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES

AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA GLOBAL DATA CENTRE IP TRAFFIC WILL TRIPLE WITHIN 5 YEARS Global data centre IP traffic has set a constant growth path, with

More information

STULZ Water-Side Economizer Solutions

STULZ Water-Side Economizer Solutions STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2013

European Code of Conduct for Data Centre. Presentation of the Awards 2013 European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started

More information

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Introduction to Datacenters & the Cloud

Introduction to Datacenters & the Cloud Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

White Paper #10. Energy Efficiency in Computer Data Centers

White Paper #10. Energy Efficiency in Computer Data Centers s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

Containment Solutions

Containment Solutions Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

Economizer Modes of Data Center Cooling Systems

Economizer Modes of Data Center Cooling Systems Economizer Modes of Data Center Cooling Systems White Paper 132 Revision 0 by John Niemann John Bean Victor Avelar > Executive summary In certain climates, some cooling systems can save over 70% in annual

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Modular Data Centre. Flexible, scalable high performance modular data centre solutions. Data Centre Solutions...energy efficient by design

Modular Data Centre. Flexible, scalable high performance modular data centre solutions. Data Centre Solutions...energy efficient by design Data Centre Solutions...energy efficient by design Modular Data Centre Flexible, scalable high performance modular data centre solutions Creating an effective workspace environment The Modular Data Centre

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2014

European Code of Conduct for Data Centre. Presentation of the Awards 2014 European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European

More information

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

Guide to Minimizing Compressor-based Cooling in Data Centers

Guide to Minimizing Compressor-based Cooling in Data Centers Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi

More information

Free Cooling for Data Centers

Free Cooling for Data Centers Free Cooling for Data Centers Release 1, September 2015 Contents 1. Abstract... 3 2. Introduction... 3 3. Data Center Temperatures and Free Cooling... 4 4. Direct Free Cooling... 4 5. Indirect Free Cooling...

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility

More information

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Energy Efficiency Best Practice Guide Data Centre and IT Facilities 2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for

More information

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale

More information

White Paper Rack climate control in data centres

White Paper Rack climate control in data centres White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2016

European Code of Conduct for Data Centre. Presentation of the Awards 2016 European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European

More information

QUALITATIVE ANALYSIS OF COOLING ARCHITECTURES FOR DATA CENTERS

QUALITATIVE ANALYSIS OF COOLING ARCHITECTURES FOR DATA CENTERS WHITE PAPER #30 QUALITATIVE ANALYSIS OF COOLING ARCHITECTURES FOR DATA CENTERS EDITOR: Bob Blough, Emerson Network Power CONTRIBUTORS: John Bean, APC by Schneider Electric Robb Jones, Chatsworth Products

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Submersion Cooling Evaluation

Submersion Cooling Evaluation Submersion Cooling Evaluation ET Project Number: Project Manager: Jeff Beresini Pacific Gas and Electric Company Prepared By: Luke Werner, P.E. Energy Resources Integration (ERI) 251 Donahue St. Sausalito,

More information

5 Reasons. Environment Sensors are used in all Modern Data Centers

5 Reasons. Environment Sensors are used in all Modern Data Centers 5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however

More information

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units

More information

APC by Schneider Electric

APC by Schneider Electric APC by Schneider Electric Energy Efficiency - The Green Power Solution James Taylor Business Development manager, UK APC by Schneider Electric The Efficient Enterprise Components Close Coupled Cooling

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

Guideline for Water and Energy Considerations During Federal Data Center Consolidations

Guideline for Water and Energy Considerations During Federal Data Center Consolidations Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

Multi-client Technical Systems in Data Centres in the UK. By: Helen Bedford Quality Approved: Lone Hansen September 2013 Project: 57315

Multi-client Technical Systems in Data Centres in the UK. By: Helen Bedford Quality Approved: Lone Hansen September 2013 Project: 57315 Multi-client Technical Systems in Data Centres in the UK By: Helen Bedford Quality Approved: Lone Hansen September 2013 Project: 57315 UK Market is the 2 nd Largest in the World. The Objective To describe

More information

Data Centre Cooling Air Performance Metrics

Data Centre Cooling Air Performance Metrics Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption

More information

Critical Infrastructure for the World s Leading Data Centers

Critical Infrastructure for the World s Leading Data Centers Critical Infrastructure for the World s Leading Data Centers 2 YOU MAY KNOW US BY OUR BRAND NAMES THE EXPERTISE OF MANY. THE POWER OF ONE. Nortek Air Solutions provides critical infrastructure for the

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Capgemini UK Infrastructure Outsourcing

Capgemini UK Infrastructure Outsourcing Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

FEAR Model - Review Cell Module Block

FEAR Model - Review Cell Module Block F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data

More information

Engineers Ireland Cost of Data Centre Operation/Ownership. 14 th March, 2013 Robert Bath Digital Realty

Engineers Ireland Cost of Data Centre Operation/Ownership. 14 th March, 2013 Robert Bath Digital Realty Engineers Ireland Cost of Data Centre Operation/Ownership 14 th March, 2013 Robert Bath Digital Realty Total Cost of Operation (TCO) Rental TCO - 10 Year Lease Term Power Cooling Connectivity Costs 26%

More information

PAYGO for Data Center -- Modular Infrastructure

PAYGO for Data Center -- Modular Infrastructure PAYGO for Data Center -- Modular Infrastructure Introduction The infrastructure costs for Data Centers are increasing at a significant pace. Construction costs and their environmental impact are also soaring.

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

Raised Floor Data Centers Prepared for the Future

Raised Floor Data Centers Prepared for the Future Raised Floor Data Centers Prepared for the Future Raised Floors Protect My Investment by Providing a Foundation for Current and Future Technologies. Creating the Future Proof Data Center Environment The

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational

More information

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel. Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning

More information

DATA CENTER & COOLING SOLUTIONS

DATA CENTER & COOLING SOLUTIONS DATA CENTER & COOLING SOLUTIONS 2012 Typical Energy Consumption of a Data Center Infrastructure 19 Racks Cooling units Cooling %50 Fire protection IT components %35 Raised floor Power Power Distribution

More information

This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.

This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA

More information

Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis

Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

HVAC Infrastructure Retrofit Solutions

HVAC Infrastructure Retrofit Solutions Kyoto Cooling Lunch & Learn David Belleville, APA LLC March 9, 2015 Owners choose APA solutions to: Rely on our 30+ years of delivering engineered solutions; HVAC Infrastructure Retrofit Solutions Insure

More information

Business white paper. A new approach to industrialized IT. HP Flexible Data Center

Business white paper. A new approach to industrialized IT. HP Flexible Data Center Business white paper A new approach to industrialized IT HP Flexible Data Center Table of contents 4 Introduction 4 Levels of modularity 5 What is HP Flexible DC? 5 HP Flexible DC features 6 The core-and-quadrant

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information