PowerChute TM Network Shutdown in Redundant UPS Configurations



Similar documents
PowerChute TM Network Shutdown Operating Modes and supported UPS Configurations

Setting up PowerChute Network Shutdown Version 4.0 for advanced configuration.

How To Shut Down A Powerchute On A Hyperv V3.2.2 (Powerchute) On A Powerpack V3 (Powerchip) On An Uniden V3 On A Pc Or Mac (Powercheute)

PowerChute Network Shutdown v4.1 Release Notes

PowerChute TM Network Shutdown Security Features & Deployment

Ambient Temperature In Range Probe X

PowerChute Network Shutdown v4.0. Installation Guide. Windows Linux/Unix Mac OS X Hyper-V/SCVMM VMware

User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer

Tripp Lite PowerAlert

1. Installing and configuring APC UPS Management

Netwatch Installation For Windows

Installation Guide. PowerChute Network Shutdown v4.1 Windows Linux/Unix Mac OS X Hyper-V/SCVMM VMware K /2015

Title Page Web/SNMP Management SmartSlot Card

APC UPS Management Solutions

USER S GUIDE. network management card. Contents. Introduction--1. Control Console--13

User s Guide. UPS Network Management Card 2 AP9630, AP9631

How To Log On Main Screen Control Console Menus... 19

Release Notes: PowerChute plus for Windows 95 and Windows 98

Microsoft Windows Built-In Serial and USB UPS Support

PowerPanel Business Edition Installation Guide

Dell Smart-UPS 1,500 3,000 VA

Before You Start 1 Overview 2 Supported Devices 4 Public (User LAN) and Private (APC LAN) Networks 5. Initial Configuration Requirements 6

Introducing Tripp Lite s PowerAlert Network Management Software

SGI NAS. Quick Start Guide a

Smart-UPS On-Line 230 V

Eaton NetWatch v5.0 NetWatch on Microsoft Hyper-V server 2008 Installation and configuration guide

NEW APC Smart-UPS. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS.

USER S GUIDE. network management card. Contents. Introduction--1. Control Console--13

Configurable Events for APC Network Management Card

If you are unable to set up your Linksys Router by using one of the above options, use the steps below to manually configure your router.

SentryPlus. Shutdown Management Software for Windows. User s Manual

User s Guide. SNMPWEBCARD Firmware Version through Revision A

InsightPower Client. Shutdown Management Software for Windows 2000/XP/2003. User s Manual

OnCommand Performance Manager 1.1

PN5212/PN5320/PN7212/PN7320

Citrix XenServer 5.6 OpenSource Xen 2.6 on RHEL 5 OpenSource Xen 3.2 on Debian 5.0(Lenny)

Using ESXi with PowerChute Business Edition

Network Management Card. User Manual

Portal Authentication Technology White Paper

User s Manual. Remote Management Card

Network Management Card Security Implementation

Network Management Card

Features Overview Guide About new features in WhatsUp Gold v14

NEW APC Smart-UPS. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS.

Environment Sensor

Issue 2EN. Nokia and Nokia Connecting People are registered trademarks of Nokia Corporation

User s Manual. Remote Management Card RMCARD202. Intelligent Remote Management Card allows a UPS system to be managed, monitored, and configured

Configuring Security for FTP Traffic

Network Management Card. Installation and Quick Start Manual

Intelligent Power Protector User manual extension for Microsoft Virtual architectures: Hyper-V 6.0 Manager Hyper-V Server (R1&R2)

Emerald. Network Collector Version 4.0. Emerald Management Suite IEA Software, Inc.

Liebert MultiLink. User Manual - Fundamental & Advanced

Configuring the Cisco SPA9000 Voice System with the Cyberdata VoIP Intercom for Door Bell Applications

How to install PowerChute Network Shutdown on VMware ESXi 3.5, 4.0 and 4.1

Configuring VPN Using Windows XP

USER S GUIDE Switched Rack PDU

Dell UPS Local Node Manager USER'S GUIDE EXTENSION FOR MICROSOFT VIRTUAL ARCHITECTURES Dellups.com

Gigabyte Management Console User s Guide (For ASPEED AST 2400 Chipset)

Virtual Managment Appliance Setup Guide

Prerequisites Guide for ios

User s Manual Network Management Card

Session Title: Exploring Packet Tracer v5.3 IP Telephony & CME. Scenario

Advanced Settings. Help Documentation

Owner of the content within this article is Written by Marc Grote

Addendum: PowerNet SNMP Management Information Base (MIB)

Virtual Web Appliance Setup Guide

WildFire Reporting. WildFire Administrator s Guide 55. Copyright Palo Alto Networks

Central Administration QuickStart Guide

Configuration Manual English version

Ad Hoc Transfer Plug-in for Outlook Installation Guide

OnCommand Unified Manager 6.3

How to Log On Main Screen Control Console Menus How to Log On Summary Page Navigation Menu... 29

Setting up a Scheduled task to upload pupil records to ParentPay

Windows Server 2008 Hyper-V, Windows Server 2008 Server Core Installation Notes

Operation Manual. Smart-UPS X Uninterruptible Power Supply

How to Obtain an OPC License--5. Creating a System Code 5 Entering an Authorization Code 6. Getting Started with SNMP Editor--7

- 1 - SmartStor Cloud Web Admin Manual

WhatsUp Gold v16.3 Installation and Configuration Guide

SNMP-NET Client Shutdown Management Software for Windows 2000/XP/2003 User s Manual

User's Reference Guide for PowerAlert UPS Management Software Version 10.2 for Windows

Basic & Advanced Administration for Citrix NetScaler 9.2

Kaseya 2. Quick Start Guide. for Network Monitor 4.1

Table of Contents. 1 Overview 1-1 Introduction 1-1 Product Design 1-1 Appearance 1-2

C-more Remote Access, Data Log, FTP File Transfer, and Tutorial

Cisco Performance Visibility Manager 1.0.1

Configuring Global Protect SSL VPN with a user-defined port

Minislot Transverse Environment Sensor 66846

Network Management Proxy 5 User manual

How to Configure Dynamic DNS on a Virtual Access Router

There are numerous ways to access monitors:

Remote Monitoring Service - Setup Guide for InfraStruXure Central and StruxureWare 1 5

GWAVA 5. Migration Guide for Netware GWAVA 4 to Linux GWAVA 5

Using triggers and actions

Introduction to TightVNC. Installation. TightVNC for Windows: Installation and Getting Started. TightVNC Version 2.6 Copyright 2012 GlavSoft LLC.

HP UPS Management Module Overview

NAS 221 Remote Access Using Cloud Connect TM

Title Page. Installation Guide. PowerChute plus Version for Windows 95

WhatsUp Gold v11 Features Overview

Transcription:

PowerChute TM Network Shutdown in Redundant UPS Configurations By Sarah Jane Hannon ABSTRACT PowerChute TM Network Shutdown software works in conjunction with the UPS Network Management Card to provide graceful, unattended shutdown of multiple computer systems over a network. UPS s can support the load in several different physical configurations. This Application Note explains the differences between Single and Redundant configurations and how PowerChute Network Shutdown works under various shutdown scenarios in a Redundant-UPS configuration. Applications IT Server Rooms, Data Centers, Remote Branch Offices, Distributed Networks. Introduction Each APC UPS in a single or redundant configuration has a UPS Network Management Card (NMC); an AP9630, AP9631 or AP9635 inserted. Each server protected by a UPS needs to have PowerChute Network Shutdown installed and registered to the NMC(s). Communication between the UPS and the server is handled over the network using the UPS NMC(s). Customer Benefits Graceful network-based shutdown Sequenced server shutdown Integration with VMware & Hyper-V Intuitive PowerChute setup wizard Browser accessible Command file integration Event logging HTTPS communications IPv6 support PowerChute Network Shutdown receives PCNS packets of data (every 25 seconds) from the UPS NMC describing the state of the UPS. PowerChute Network Shutdown then parses the PCNS data packet for various events to which it may respond, by notifying administrators or users, or by gracefully shutting down the system 1. The user configures which events require action, depending on their requirements, using the PowerChute Network Shutdown Configure Events screen. 1 See Application Note #20 (AN-20) The Communications Process of PowerChute Network Shutdown

Definitions Single UPS Configuration Each server or group of servers is protected by a single UPS. Each server has one PowerChute Network Shutdown Agent communicating with a single NMC inserted in the UPS. This single UPS provides the full power capacity of the load for all connected servers. When an event that requires shutdown occurs, PowerChute Network Shutdown receives the notification and triggers a graceful shutdown command for all connected servers. This application of PowerChute Network Shutdown includes all servers receiving power through the same UPS. PowerChute Network Shutdown responds to all the UPS events. Single UPS Configuration: All servers are protected by a single UPS. The UPS Network Management Card (NMC) communicates with each server that has PowerChute installed. Redundant UPS Configuration PowerChute Network Shutdown recognizes a group of up to four UPS s as a single UPS. In this configuration, one PowerChute Network Shutdown Agent on a server communicates with up to four NMCs (depending on the number of UPS s in the configuration). Typically, the servers have multiple power cords. Each UPS has its own NMC, which has a unique IP address. In addition, all the NMCs use the same HTTP port and the same administrator user name and authentication phrase. Each UPS has the capacity to supply power to the load on its own. The first UPS provides all the power for the load, the additional UPS(s) act as reserve. When the first UPS in unable to supply power, the server switches over to take power from the next UPS. As a result, if one of the UPS s goes down, for whatever reason, the other UPS(s) can continue to supply power to the load and therefore provide redundancy between UPS s. PowerChute Network Shutdown recognizes that the UPS s are set-up in a Redundant-UPS configuration and listens to all the UPS NMCs for a shutdown command. 2 February 2015

Redundant UPS Configuration: Two or more UPS s protect each server. Each UPS can support the server load on its own. All NMC s communicate with each server that has PowerChute installed. Table 1 Supported UPS s in a Redundant-UPS Configuration Smart-UPS Redundant (Minimum) Redundant (Maximum) Smart-UPS VT Galaxy 3500 (3:1 & 3:3) Symmetra 1-Phase Symmetra 3-Phase All UPS s in a Redundant-UPS configuration must be from the same UPS Family as opposed to the same UPS model. For example; SMX, SMT or SUA Smart-UPS can be mixed together but an SMX Smart-UPS cannot be mixed with an SURT or SRT model which belongs to the Smart-UPS On-Line Family. Each UPS must have enough battery power to support the entire load in the event of a power outage. While up to four UPSs can be supported, the Redundancy level is set so that if two UPS s in the configuration have a critical UPS event, then a graceful shutdown will be triggered. 3 February 2015

Event Handling PowerChute Network Shutdown aggregates the events from all the UPS s in the Redundant configuration to form one virtual UPS System. These events are always considered critical: Low Battery UPS Off UPS Turn off Initiated Additionally, in a Redundant-UPS configuration, PowerChute Network Shutdown will always recognize and report the following events even if they occur on only one UPS: Runtime exceeded. Any event generated by an Environmental Monitoring Card. It is possible to configure other events to be considered critical by enabling the Shutdown action on the Configure Events screen. The critical event type and combination will impact the shutdown delays (if any) that are counted. 2 identical critical events such as Low Battery OR UPS Turn Off Initiated occurring in succession on 2 UPS devices will cause a shutdown; the shutdown will be immediate and no configured delay is counted down. 2 identical configured critical events such as UPS: On Battery occurring in succession on 2 UPS devices will cause a shutdown; any configured delay time will be counted down first. As the above events are not aggregated, if for example an environment threshold exceeded event is configured for shutdown, it will initiate a shutdown even if only 1 UPS has that threshold exceeded. All other events are aggregated (read in combination from all the UPS s) and need to occur on at least two UPS s before they are recognized and reported. 2 different critical events (may or may not have been configured by the user) such as Low Battery and PowerChute cannot communicate with the Management Card occurring in succession on 2 UPS devices will cause the event called Multiple Critical Events occurred which always leads to a shutdown. A 10 second delay prior to the PowerChute shutdown process starting will be counted. No additional configured delay time for the events themselves is counted down. Shutdown Scenarios (Note: Same rules apply if there are 2, 3 or 4 UPS s in a Redundant UPS Configuration) Scenario 1: Two UPS s supporting a load the same critical events occur on each UPS: UPS 1 reaches a critical event such as Low Battery; the UPS Network Management Card in that UPS will log the shutdown notification - no event is logged, no shutdown occurs. The same critical event occurs on UPS 2 and its UPS Network Management Card sends the shutdown notification the event is logged and an immediate shutdown occurs. No shutdown delay is counted. Figure 1 Two identical critical events, one in each UPS will trigger a graceful shutdown of the server with no shutdown delay counted. 4 February 2015

Shutdown Scenarios Scenario 2: Two UPS s supporting a load the same configured critical events occur on each UPS: UPS 1 reaches a configured critical event such as UPS: On Battery; the UPS Network Management Card in that UPS will log the shutdown notification However, no event is logged and no shutdown occurs. The same configured critical event occurs on UPS 2 and its UPS Network Management Card sends the shutdown notification the event is logged and shutdown occurs. Any configured delay time will be counted down first. Figure 2 Two identical configured critical events, one in each UPS will trigger a graceful shutdown of the server with any configured delay time counted down first. Scenario 3: Two UPS s supporting a load Different critical events occur on each UPS: UPS 1 reaches an event such as UPS: On Battery or Low Battery (may or may not be a configured critical event). The UPS Network Management Card in that UPS will log the shutdown notification - no event is logged, no shutdown occurs. A different critical event (such as UPS Turn Off Initiated) occurs on UPS 2, its UPS Network Management Card sends the shutdown notification the event is logged and shutdown occurs. As the critical events are different for both UPS s, a 10 second shutdown delay is counted. No other shutdown delays are counted down. Figure 3 Two different critical events (whether configured or not), one in each UPS will trigger a graceful shutdown of the server. A 10 second shutdown delay is counted down first. Scenario 4: Two UPS s supporting a load A critical event only occurs on one of the UPS s: If UPS 1 reaches Low Battery and eventually turns off but no events occur on UPS 2 and the UPS stays online, PowerChute Network Shutdown will not begin a shutdown as the second UPS is capable of supporting the entire load itself. Figure 4 Critical events in one UPS will not trigger a graceful shutdown of the server if no critical events occur on the second UPS. 5 February 2015

Conclusion In a Redundant-UPS configuration, each UPS must be able to support the entire load itself. A critical event must occur on two of the UPS s to trigger PowerChute Network Shutdown to initiate a graceful server shutdown. When PowerChute Network Shutdown combines or aggregates critical events from the UPS s, it only reports an event if the systems ability to support the load is at risk. In a Redundant-UPS system, this means that two UPS s must report the issue before PowerChute Network Shutdown will report the event and initiate the required safe server shutdown actions. While PowerChute Network Shutdown supports up to four UPS s of the same UPS Family in a Redundant-UPS configuration, PowerChute will trigger a graceful shutdown if a critical event occurs on two or more UPS s. 6 February 2015