James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc.



Similar documents
2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

Interfacing Elevators with Fire Alarm and Sprinklers

city of edmonds development information

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Amendments to the 2012 INTERNATIONAL FIRE CODE

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

Overview of Hotel Fire Safety Requirements

Challenges to the Designer:

FIRE-FIGHTING DESIGN BRIEF REPORT

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

Building Code Clarifications - 7. Fire Resistance

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

HOUSTON FIRE DEPARTMENT HIGH-RISE SURVEY CHECKLIST

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

Current as of 11/10/08 1 of 1

Life Safety Code Enabling References

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

- 5 - Table1. Maximum Compartment Volumes

CHAPTER 9 FIRE PROTECTION SYSTEMS

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)

Hotel Fire Safety for staff

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST

Firefighter Review. Instructor Guide

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS

City of Bettendorf Fire Alarm System Requirements

Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.

Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata Developer Premier Mica Mining And Manufacturing Company

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.

St. John s University

Certification: Building Plans Examiner. Exam ID: B3

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

2007 ICC FINAL ACTION AGENDA

BS5839 Part 1:2002 Overview

Indiana Building Rehabilitation Standard

FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE

Chapter 9 Fire Protection Systems

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist

rpsa FIRE PROTECTION ENGINEERS

CBD-233. Fire Alarm and Detection Systems

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson

Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?

Sprinkler and Fire Alarm Systems for the Building Official

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, , ]

New York City Department of Buildings

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

Pearl River Tower, Guangzhou: Fire Protection Strategies for an Energy Efficient High-Rise Building

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2

Harris County Fire Code Electronic Lock Procedures

Wyoming State Capitol Building Restoration and Modernization

Code Requirements for Existing Buildings

FIRE RISK ASSESSMENT

CITY OF HOUSTON HIGH-RISE OFFICE BUILDING FIRE SAFETY PLAN

2014 Limited Plan Submittal Checklist

I. Basic Smoke Control Strategy and Tactics

North York General Hospital Policy Manual

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

CITY OF FAIRFAX CODE ADMINISTRATION / FAX

FIRE PROTECTION SYSTEMS

University Design Standard. Fire Alarm Systems

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

VILLAGE OF HUDSON FALLS 220 MAIN STREET HUDSON FALLS, NY (518) /

FIRE-RESISTANCE-RATED CONSTRUCTION

Arizona Health Care Association DISASTER PLANNING AND EMERGENCY MANAGEMENT GUIDE POST INCIDENT DAMAGE ASSESSMENT CHECKLIST

Environment of Care Fire Safety Management Plan 2014

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

Healthcare Engineering. Code Summary Report

Fire Safety Risk Assessment Checklist for Residential Care Premises

All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.

Schedule B to By-law Part A Fees Payable for Permits

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Important Ontario Fire Code Information for Building Owners in the City of Windsor

NFPA Edition Fire dampers shall be permitted to be installed in exhaust systems in the following situations:

Appendix B Florida Building Code Building Section Public Shelter Design Criteria

Mobile Fire Rescue Department Bureau of Fire Prevention

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9

Fire Safety Report Fire Statistics

Name Of Occupancy Date. Yes No Describe

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

CHILD CARE CENTER INFORMATION SHEET

Guidance on loft conversions in two-storey houses

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

The Mission Critical Fire Protection Experts

Safe Operating Procedure

Building Control Guidance Note

FIRE-RESISTANCE-RATED CONSTRUCTION

Transcription:

AT THE STRATOSPHERE TOWER, LAS VEGAS NEVADA By: James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc. INTRODUCTION This paper discusses the performance based approach to fire protection that was used at the Stratosphere Tower in Las Vegas, Nevada. It includes a description of the building, some of the problems faced, the analyses conducted and the solutions proposed and implemented. The building is now open and occupied, and is a major new landmark on the Las Vegas skyline. The Stratosphere Tower is the tallest free standing observation tower in the United States. It is 1,149 feet high. It contains several occupied floors including wedding chapels, function rooms, restaurant and lounge, and observation levels. At the top are two ride levels, which include an outside roller coaster and the Space Shot. Figures 1 and 2 show typical floors of the tower. This paper identifies many of the problems that needed to be resolved in the design of the tower. However, it concentrates on the solutions used for evacuation of the building. ISSUES TO BE ADDRESSED In developing the fire protection program for a building such as the tower, there are many issues that had to be addressed. The most obvious issue is how to evacuate the building. The lowest occupied floor is 795 feet above grade. The area of the shaft is not large enough to provide remotely located stairs, and the height of the building makes the use of stairs as an evacuation route a less than perfect solution. A second problem was how to determine the occupant load in the tower, and how to limit that load. Third, the height of the tower had to be considered in evaluating fire fighter access and methods. Fourth, each utility, be it fire protection or other utilities, had to be specifically evaluated to assure reliability and safety. This includes all of the typical fire protection features such as water supply, fire alarm, smoke control, and emergency power. It also includes protection of gas lines that serve cooking equipment in the tower and use and shut-down of the rides at the top of the tower. 118

Page 2 Lastly, the program needed to evaluate exposures to the tower from the structure below. The tower rises above a casino building and the impact of a fire in the casino had to be evaluated. THE EXIT, PROGRAM As stated previously, the tower presented specific problems with relation to evacuation of the building. Because some floors of the building may include occupancy by more than 500 people, strict code application would require three exit stairs leading from the top of the tower to the base of the building. However, as with other observation towers, the shaft of the structure is not large enough to contain three exit stairs. Even with multiple stairs in the shaft, separation of those stairs would be impossible. Therefore, an alternate method of evacuating people was developed. The primq evacuation method for this building is the use of typical exit stairs for the occupied floors discharging to areas of refuge on the lowest two floors of the pod. In other words, from Floors 3 through 10 of the pod, three exit stairs are provided, enclosed in 2-hour construction, just as would be found in any other building. However, these stairs discharge to an area of refuge at the lowest two levels of the pod, which is still 750 feet above grade. These two areas of refuge are used for no other purpose, and are completely non-combustiile. Rather than rely on mechanical systems to maintain them free of smoke in the event of fire, the two areas of refuge are open to outer air so that natural ventilation of these levels occur. Since the two areas are below the occupied levels, it is unlikely that fire in an occupied level would spread to the areas of refuge. With all the other fire protection systems provided, the possibility of fire spread is virtually eliminated. See Figure 3 for a layout of one of the areas of refuge levels. From the area of refuge, a single stair leads down through the shaft of the tower to grade. The primary evacuation route Erom the area of refuge involves the elevators. These elevators are two-level elevators which travel at 1,800 feet per minute and can discharge either within the main casino or at two specially designed discharge levels at the roof of the base building. These discharge levels are enclosed in two-hour construction from the roof to grade, and are separated from all other areas by two-hour construction. SPECIAL ELEVATOR PROTECTION In order to assure safety of the elevators, special protection was provided in the building. This building design was occurring during many of the NIST studies regarding use of elevators for evacuation in buildings. Many of the NIST recommendations, that were 119

Page 3 developed in symposiums and through research on the use of elevators, were incorporated into this design. Some of these include the following: 1. 2. 3. 4. 5. 6. 7. 8. Elevators open into two-hour elevator lobbies on all floors, both at the top and at the bottom of the building. There are four elevators which travel through the shaft from the base to the top. These elevators are served by two independent elevator machine rooms. The elevator machine rooms are separated by two-hour construction and have a 4-inch curb installed between them so that waterflow in one machine room will not impact the other machine room. Elevator lobbies are on a separate smoke control system to maintain pressurization with relation to adjacent spaces. Therefore, fire in an adjoining area will not spread smoke into the elevator lobby. Openings into the elevators are slightly raised from the remainder of the floor. Therefore, water flow on a floor level will not spill into the elevator hoistway because of the raised entry. Because the areas of refuge are at the two lowest levels of the pod, the elevators will not need to travel past a fie floor. Elevators will travel only between the areas of refuge and the base building. NOTE: Areas of refuge for disabled persons are provided within the enclosed pressurized stairwells at each level. Elevator shafts are vented to the outside at the top and the vents are separate from the machine rooms. In addition, the machine rooms are on separate smoke control systems and air conditioning for the machine rooms is on emergency power. All four elevators are on emergency power. The emergency power riser is in a separate dedicated 2-hour shaft. Only three of the elevators are assumed to be available for evacuation purposes. The fourth elevator is dedicated for use by the fire department. In addition to the elevator evacuation, a single stair leads down through the tower and discharges to grade. This stair enclosure is pressurized, and remains independent of the base building. The stair enclosure has periodic enlarged landings, which will allow 120

Page 4 occupants to stop and rest as the descend through the building. In addition, the three stairs in the pod of the building are enclosed in 2-hour construction and pressurized. Each of these stairs has areas of evacuation assistance, with communication capability to the central control room. OCCUPANT LOAD DETERMINATION With a building of this type, it is important to understand and control the occupant load. Three methods were used to determine occupant load. Once the three calculations were performed, the lowest occupant load calculated is used as the limiting factor for the building. These three methods are as follows: 1. Building codes typically allow holding areas or areas of refuge for horizontal exits. Where those holding areas are used, the code requires a minimum of 3 square feet per person for holding area.. Therefore, one of the limiting factors for this building was the size of the areas of refuge. The areas of refuge were calculated at one person per 3 square feet to determine their maximum holding capacity. This provides a factor of safety for several reasons: a. The area of stairs leading to the areas of refuge was not included in the holding area. These stairs would significantly increase the number of people that can be safely accommodated within an area separated from the fire by 2-hour construction. b. The calculations assume that no occupants are leaving the building via elevator or stair. Instead, they assume that all occupants are contained within the areas of refuge. c. The evacuation scenario is to evacuate the floor of origin, the floor above, and the floor below. Therefore, only a portion of the building will be simultaneously evacuated. However, the occupant load of the entire building is limited by the size of the area of refuge. 2. The second means of limiting the occupant load of the building was based on code calculations. The expected occupant load, based on Table 33-A of the Uniform Building Code, was calculated for each floor of the building. The load was then totaled for the entire building and this occupant load is used as a limiting factor for the number of people in the building. 121

Page 5 3. The third limiting factor is the capacity of the elevators to evacuate the people. The speed of evacuation was based upon NIST studies which contain calculation methods for elevator evacuation. In this project, it was concluded that a 1-hour time frame was a reasonable time to fully evacuate the areas of refuge. This 1- hour time frame was based on three of the four elevators being used for evacuation, with the fourth dedicated solely to fire department use. The 1-hour calculation also ignores the availability of the stair leading down through the shaft. Therefore, by this calculation, all occupants are expected to leave via the three elevators. NOTE: Operational considerations require the occupant load to be further limited if one of the elevators is down for repair. Once these three methods of calculations were completed, an occupant load of approximately 2,600 people was developed as the expected load of the building. This was the load factor around which the remainder of the building was designed. In order to be confjdent that this load factor is not exceeded, the building owner has instituted an occupant counting system which keeps track of the number of people entering and leaving the tower. Therefore, the load of the building will not exceed the calculated occupant loads. OTHER FEATURES The evacuation system for this building cannot stand alone. The fire protection features for this building were specifically designed to rapidly detect and suppress a fire, and control smoke generated by the fire. Some of the other features provided within the building are as follows: Automatic Sprinklers - The building is completely protected with automatic sprinklers. Sprinkler densities exceed those required by the codes. The sprinkler system was calculated to provide a very high density for the first four sprinklers operating, plus ordinary hazard density for the most remote 1,500 square feet. Water supply is from two pumps at street level which pump up to the pod. There is onsite water storage within the pod and two additional pumps sized for sprinkler plus standpipe demand in the pod. With these pumps and on-site water storage, redundant water supply is available. Detection and Alarm - The building is fully protected with automatic smoke detectors, except that kitchens contain heat detection. The smoke detectors are on an addressable system, with alarm verification to reduce the number of unwanted alarms. Manual pull 122

Page 6 stations are also provided in the facility. In order to reduce unwanted pull station alarms, the manual pulls have been placed within the stahways. The alarms report to the main central control room for the Stratosphere Casino, as well as two auxiliaxy control rooms. One of the auxiliaq control rooms is located at the base of the tower, and the second is located within the area of refuge at elevation 750 feet. The control room within the area of refuge is accessed directly from the fire fighters elevator. Communication and infomation flow from the three control rooms is identical. The fire alarrn system is a Class A system, with separate risers running up through the shaft. The risers are separated by 2-hour construction. Ernereencv Power - Emergency power is sized to accommodate all portions of the fie protection system. This includes the fire pumps, fire alarm system, all elevators, smoke control and necessary lighting. The emergency power riser is routed through a separate 2-hour shaft up through the tower in order to prevent a single event from impacting the primary and emergency power. Smoke Control - The building is provided with an automatic smoke control system. Upon actuation of an alarm, the floor or origin and any floors open to it go to full exhaust while adjoining floors are pressurized. In addition, the elevator lobbies for all floors are pressurized, as is the stair leading down through the shaft of the tower. Exhaust from the smoke control system is ducted to discharge above the ride level at the top of the tower in order to eliminate reintroduction of smoke into the building. CONCLUSION The Stratosphere Tower provided an opportunity and a need to develop a fire protection approach which departs from the typical building code approach to a building. Use of stairs as the sole evacuation method was not feasible or reasonable. Requiring all of the occupants to utilize stairs would result in an unsafe condition for many of the expected occupants of this building. A more reasonable method was to provide an area where people could be staged until evacuated, and a reliable means to perform that evacuation. The approach, as briefly descnied in this paper, provides protection in accordance with the overall intent of the buiiding codes, while departing significantly from the detailed requirements of code. Therefore, this is a true application of performance based approaches to fire protection in a building. JRQ:dp 123

FIGURE 1 STEUTOSPH

FIGURE 2 e- YOU ARE HERE STRATOSPHERE TOWER n

FIGURE 3 STRATOW- CORPORATION