Increasing the evaporation temperature with the help of an internal heat exchanger



Similar documents
UNIT 2 REFRIGERATION CYCLE

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Refrigeration Basics 101. By: Eric Nelson

New Trends in the Field of Automobile Air Conditioning

How To Calculate The Performance Of A Refrigerator And Heat Pump

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

How To Know If A Refrigeration System Is Efficient

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

How does solar air conditioning work?

Open Cycle Refrigeration System

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Energy savings in commercial refrigeration. Low pressure control

Mohan Chandrasekharan #1

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES

How To Design A Refrigeration System

REFRIGERATION (& HEAT PUMPS)

Chapter 3.4: HVAC & Refrigeration System

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

Research on the Air Conditioning Water Heater System

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

Characteristics of Evaporators

Energy Efficiency Best Practice Guide Industrial Refrigeration

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL

Optimal operation of an Ammonia refrigeration cycle

ARP Food Industry, Portugal

Why and How we Use Capacity Control

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

How To Clean Water From An Ammonia Refrigeration System

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

High Pressure Ammonia Systems New Opportunities

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

How to choose a heat pump and use it wisely

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

How Ground/Water Source Heat Pumps Work

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Energy Procedia Energy 00 Procedia (2011) (2012) 56 65

Heat Recovery In Retail Refrigeration

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Rusty Walker, Corporate Trainer Hill PHOENIX

Refrigeration & HVAC

Testing methods applicable to refrigeration components and systems

AIR REVERSING R744 AIR CONDITIONING SYSTEM

Condensers & Evaporator Chapter 5

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight Temperature glide o C Boiling point (1 atm)

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

GPC. How do I call up the bid text for a selected unit? Why does the GPC calculate the surface reserve and not the capacity reserve?

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

Efficiency of Hydrogen Liquefaction Plants

UNDERSTANDING REFRIGERANT TABLES

SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS

Fundamentals of Mechanical Refrigeration Systems

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

National Grid Small Business Energy Efficiency Program Overview. Central New York Energy Expo March 30, 2010

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

AdSORPTION CHILLER NAK

DRAFT. Appendix C.2 - Air Conditioning Thermodynamics 1

AMMONIA AND CARBON DIOXIDE HEAT PUMPS FOR HEAT RECOVERY IN INDUSTRY

Experimental and Modeling Investigation of Two Evaporator Automotive Air Conditioning Systems

Guide to Good Commercial Refrigeration Practice. Part 2. System Design and Component Selection

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

How To Understand Evaporator

DEFROSTING. Service Engineers Section Technical Bulletin No 3

System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

Analysis of Ammonia Water (NH3-H2O) Vapor Absorption Refrigeration System based on First Law of Thermodynamics

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Waste Heat Recovery through Air Conditioning System

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )

Analytical Study of Vapour Compression Refrigeration System Using Diffuser and Subcooling

Engineering Recommendation on: Accumulators Revised Issued January 10, 1979 Page 1 of 7

Test Report issued under the responsibility of:

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance

Warm medium, T H T T H T L. s Cold medium, T L

Split units TH with hermetic compressors

The Development of a Frost-Less Heat Pump

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests

The Second Law of Thermodynamics

OPTIMIZING REFRIGERANT DISTRIBUTION IN EVAPORATORS

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

Transcritical CO2 booster system How to control the system

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors

Energy Efficient Ammonia Heat Pump. Energy and Climate Refrigeration and Heat Pump Technology

Transcription:

Increasing the evaporation temperature with the help of an internal heat exchanger A. TAMBOVTSEV (a), H. QUACK (b) (a,b) Technische Universität Dresden, D-01062, Dresden, Germany (a) Fax: (+49351) 463-37247, e-mail: alex@memkn.mw.tu-dresden.de (b) Fax: (+49351) 463-37247, e-mail: quack@memkn.mw.tu-dresden.de 1. ABSTRACT Increasing the evaporation temperature by one degree lowers the power consumption of a refrigerator by about 3 percent. A method will be presented, how in many applications the evaporation temperature can be increased by about 3 to 5 K with the help of an internal heat exchanger. This arrangement is advantageous for all refrigerants, even for ammonia, where normally internal heat exchangers are detrimental. 2. MOTIVATION It is well known, that the power consumption of refrigerators is reduced by about 2-3 %, when the evaporation temperature is increased by 1 K. Therefore it is worth while to look for simple means to increase the evaporation temperature, if possible without changing the design of the evaporator or the type of the expansion valve. In normal dry evaporators, as shown in figure 1, the heat transfer area on the refrigerant side is often only partially used effectively, because the last about 15 % are needed for the superheating of the refrigerant. The superheating is needed for two reasons: One needs a clear measurement for the control action of the thermostatic expansion valve and one wants to protect the compressor from liquid in the suction stream, which may lead to mechanical damage. Figure 1 Simple refrigerating plant The Motivation of this investigation was a non complete using of the evaporator area for the evaporation of a refrigerating medium. The figure 1 shows the foundation of the engineering [1]. The refrigerating plant consists of a compressor with condenser 1, an expansion valve 2 and an evaporator 3. The expansion valve regulates with help of his heat sensor the mass flow of a refrigerating medium to the evaporator in dependence from the refrigerating medium superheat after the evaporator. It is well known, that the normal thermostatic expansion valve due to a need of at least 6 K superheat reduces the liquid content in the evaporator below the optimum level. Manufacturers of electronic expansion valves point out, that with their products a superheat of only about 2 K can be realized [2]. But if one looks closer into the dependence of the heat transfer coefficient on the liquid content and on superheating, one realizes, that it would be best, if there would be still 2 to 5% liquid at the outlet of the evaporator. 2 1 4 3

The superheat in this cycle is realized in the evaporator. The heat-transfer coefficient in this superheated area of evaporator is very low. For achievement of necessary superheat there is a need to work by low evaporating temperature. The low evaporating temperature leads to produce quick frost and to frequent thaw requirement. The purpose of this investigation was to remove the superheating out of the evaporator. 3. REALIZATION If the superheating does not take place in the evaporator, then it must occur in an other heat exchanger. One possibility is to install an internal heat 2 5 1 Figure 2 Realization 4 3 temperature can be controlled in a tighter regime. But unfortunately it has turned out in reality, that the cycle shown in figure 2 can not be used, because the control system is not stable. The fundamental problem of the flow diagram in figure 2 is that the deviation of the coming liquid from the evaporator to the IHX reaches the acting valve faster than the sensor of the controller. To avoid this, one has to look for an alternate flow diagram. Figure 3 shows a flow diagram, where the IHX is arranged as a co-current heat exchanger. In this arrangement the disturbance by the change of liquid content on the evaporator reaches the sensor of the expansion valve sooner than the expansion valve itself. So the expansion exchanger (IHX). Figure 2 shows an IHX as a countercurrent exchanger 5. The intention is that in this IHX the residual liquid refrigerant is evaporated and then the vapour flow is superheated. The sensor 4 of the expansion valve 2 must be placed between the IHX 5 and the compressor 1. This arrangement allows to use all of the evaporator area for the evaporation of the liquid refrigerant with a very good heat-transfer coefficient. Therefore it is possible to work with a higher evaporating temperature. The energy consumption is reduced and the volumetric refrigeration capacity is increased. In addition in air coolers a more homogeneous air temperature at the evaporator exit is obtained and the air valve has enough time to close the expansion valve to reduce the mass flow of the condensate before the better subcooled condensate reaches the valve. This refrigerating scheme was investigated theoretically and experimentally. The design of the IHX has an important influence. The used IHX consists of a shell and 5 internal pipes with longitudinal fins. The condensate flows inside the pipes and the low pressure flow runs on the shell side. It was theoretically and practically established that there is a maximum liquid content in the inlet of the low pressure flow, under which the control system can not work stable. The maximum for this design of IHX is about 8% liquid in the refrigerant flow rate. 2 5 Figure 3 Alternative refrigerating plant 1 3 4 4. THEORETICAL RESEARCHES The theoretical researches have been done with refrigerating mediums R507 and ammonia. The refrigerating capacity was constant 10 kw and the cooling of the air through the evaporator was set from 8 to 4 C for all investigations. In the case of the refrigerating cycle without IHX the superheat was chosen to 6K. The calculations were carried for

different condensing temperatures in the range between 25 and 45 C. The superheating in the IHX was varied from 6 to 16K. In the case of ammonia the superheat was chosen to 6 and 8K. To achieve the best results the IHX area was optimized for each superheating case. The higher the condensing temperature is, the more heat must be transferred in the IHX. For a constant control of the superheat under such conditions the IHX area was defined, so that the liquid content at the inlet to the IHX was never more then 8% for the highest condensing temperature. Vh/Qo in Improvement of COP in % Superheat in evaporator a. 9K Condensing temperature in C Figure 4 Required compressor volume (Refrigerating medium R507). Condensing temperature in C Figure 5 Improvement of COP (Refrigerating medium R507) Figures 4 and 5 show for R507 the change of the required compressor suction volume and the change of the COP for different condensing temperatures depending on the IHX area. One realizes that the increase of the IHX area leads to a decrease of the required compressor suction volume. In addition, it reduces the energy consumption and improves the COP. But it also shows that one should not try too much. If one chooses a too large internal heat exchanger and aims for a too high superheat, this leads to a deterioration of the system at lower condensing temperatures. The reason is, that under these conditions, the evaporation end moves back into the main evaporator and one comes back to the operation without internal heat exchanger. Figure 6 Required compressor volume (Refrigerating medium R507) Figure 7 Improvement of COP (Refrigerating medium R507) Figures 6 and 7 show a further decrease of the compressor suction volume and an improvement of the COP by use of one oversized evaporator. The calculations were done with a condensing temperature of 30 C and a superheating of 6K downstream of the internal heat exchanger. The results of the calculation show that with this flow diagram it pays to use an oversized evaporator. It can bring a remarkable increase of the COP. Of course there will a limit of improvement taking into account pressure drop and cost.

Similar investigations were done for a refrigerating plant with ammonia (NH 3 ) as refrigerant. Because of the special properties of HN 3 (small molecule weight) a use of an IHX is normally not recommended for HN 3 -refrigerators, because the COP would decrease. But our calculations show that in our arrangement the effect of a co-current internal heat exchanger is positive both for the volumetric capacity as for the COP. Figures 8 and 9 show the change of the required compressor suction volume and the COP for different condensing temperatures dependent on the IHX area. The calculations were done for the two superheats 6 and 8K. As can be seen the improvement of the COP with 8K superheating is smaller than with 6K. This is the case because of the negative influence of the superheating on the compression work with NH 3. Similar to the same effect with R507, the COP can be further increased using an oversized evaporator. Condensing temperature in C Condensing temperature in C Figure 8 Required compressor volume (NH 3 ) Figure 9 Improvement of COP (NH 3 ) 5. EXPERIMENTS For a confirmation of the theory the experiments were conducted with the refrigerant R507. The task was to cool an air stream from 7 to 4 C. First the plant was operated with the conventional cycle (Figure 1) without IHX with 6 K superheat. Then with the cycle with IHX, the superheating was varied between 10 and 16K. The condensing temperature was varied between 30 and 39 C. Then the results of the two experiments were compared. Figure 10 shows an increase of the evaporating temperature of more than 2 K due to the IHX with unchanged air temperatures. As all experiments were conducted with the same compressor, the increase in evaporation temperature allowed an increase in refrigeration capacity. The large increase in refrigeration capacity with only a small increase in compressor power lead to a corresponding increase of the COP (Figure 11) Figure 10 Increase of To Figure11Improvement of COP

Superheat 10K 6. CONTROL SYSTEM For a test of the control system the evaporator load was decreased rapidly from 100 to 70%. Figure 12 shows the temperatures at the inlet and the outlet of the evaporator and the change of the controlled superheat in function of the time. Figure 16 shows that after Superheat12K Superheat in K Superheat in K Temperature Evaporating temperature Temperature Evaporating temperature Exit temperature Exit temperature Time hh:mm Time in hh:mm Figure 12 Dynamics of the control system (condensation temperature: 35 C) Time hh:mm Time in hh:mm the decrease of the evaporator load the superheat goes down in both cases till about 7K and then the control system finds the stable working point again. In the case of the 10K superheat, the liquid content oat the IHX inlet was about 5% and in the case of 12K superheat about. 3%. Figure 13 shows what happened when the liquid content was about. 7-8% (higher condensation temperature). In this case, the superheating decreased from 12 to 2 K for a short time and then the control system found the working point again. For these experiments a pulsating electric expansion valve was used. Experiments with a simple thermostatic expansion valve are planned. Superheat in K Temperature Evaporating temperature Exit temperature Time hh:mm Figure 13 Dynamics of the control system (Superheat: 12K, condensation temperature: 39 C) 7. SUMMARY By using the co-current IHX the evaporation temperature can be increased by more than 2K. It leads to a reduced of the energy consumption and an increase of the volumetric

refrigeration capacity. The refrigeration cycle works stable even under large and rapid changes of the evaporator load. The increase of the evaporation temperature leads to additional benefits: There is less frost formation on the air side and therefore less need for defrosting. Owing to the use of all evaporator area only for the evaporation of the refrigerant and no superheating, the minimal difference between air and the refrigerant temperature in the evaporator can be reached. It enables to control the air temperature e. g. in a cold store rather accurately. The choice of an oversized evaporator in the refrigerating cycle would bring a further increase of the COP. 8. REFERENCES [1] Mickan, P.; Fischer, H.; Handbuch Grundlagen der Kältetechnik [2] H. L. von Cube; Lerhbuch der Kältetechnik; Bd. 1; Karlsruhe 1981 [3] H. L. von Cube; Lerhbuch der Kältetechnik; Bd. 2; Karlsruhe 1981